eta Control Plex Installation Instruction

Rack
Installation Instruction
2
Date of issue:
Date of publication: May 2017
This document replaces the following documents: „ControlPlex
®
Rack I_19BGTCP_d_200916
Editor:
E-T-A Elektrotechnische Apparate GmbH Industriestraße 2-8 . 90518 ALTDORF GERMANY Tel. +49 9187 10-0 . Fax +49 9187 10-397 E-Mail: info@e-t-a.de . www.e-t-a.de
Copyright © 2017 E-T-A GmbH
The contents of this document are the property of E-T-A GmbH. No part of this publication must in any way be reproduced or distributed without prior written consent of E-T-A GmbH. Any person acting illegally with regard to this publication can be prosecuted.
Limitation of liability
Although all provisions were taken when creating this document, the editor does not accept any reponsibility for errors or omissions or for damages caused by using the information contained in this document. The in­formation contained in this document may be revised at any time without pre-advice.
Brands
All references to software and hardware in this document are generally protected by brands or patents.
© E-T-A GmbH 2017. All rights reserved
3
About this manual
This manual describes the electrical start-up of the ControlPlex® Rack system in connection with compatible ControlPlex® Rack components. The ControlPlex® Rack allows artless and reliable protection and monitoring
of minus-supplied systems. Typical applications include telecommunications as well as IT centres, e.g. the protection and electrical monitoring of server or router cabinets.
Besides this document, more information about the E-T-A ControlPlex
®
Rack can be found in the following
documents.
ControlPlex
®
Rack
Data sheet Here you will find more technical data and figures as well as approval infor-
mation on the various components of the ControlPlex
®
Rack system
ControlPlex
®
Rack
Operation instruction manual RCI10 Here you will find an instruction for configuration and for integration of the
module Remote Control Interface RCI10 into your network. In addition this document holds a user description of the web browser and the SSH surface as well as the SNMP MIB for integration into a management system.
ControlPlex
®
Rack
Release Notes RCI10_SW_V2.0 Here you will find the information of the extended performance features of
the current software for the RCI10 sub-assembly.
ControlPlex
®
Rack
Application examples EAI300 Here you will find further configuration and connection examples for the
EAI300 module
The latest documents can be found on our website under www.e-t-a.de/controlplex_rack
All documents contain important instructions for connection and safe operation of the ControlPlex
®
Rack
system. Safety instructions have to be observed. All users have to be informed about all safety instructions. The documents have to be accessible for the user.
4
Contents
About this manual ...........................................................................................................................................3
Contents ........................................................................................................................................................... 4
General note ....................................................................................................................................................6
1 Introduction ............................................................................................................................................. 8
2 Minimal requirements of installation.....................................................................................................9
3 General: ControlPlex
®
Rack Power-D-Box® .......................................................................................10
3.1 Use of the Power-D-Box
®
............................................................................................................. 10
3.2 Technical data of the Power-D-Box
®
............................................................................................11
3.3 Scope of delivery of the Power-D-Box
®
........................................................................................12
3.4 Pictures of Power-D-Box
®
versions (front view) ............................................................................12
3.5 Drawings and dimensions of Power-D-Box
®
versions ..................................................................13
3.6 Schematic diagrams of Power-D-Box
®
versions .......................................................................... 15
3.7 Pin assignment of Power-D-Box
®
versions ..................................................................................16
3.8 Installation and start-up of the Power-D-Box
®
.............................................................................18
3.8.1 Recommended installation site for Power-D-Box
®
..........................................................18
3.8.2 Basic notes on cabling for Power-D-Box
®
......................................................................18
3.8.3 Mounting and start-up of Power-D-Box
®
........................................................................19
4 General: ControlPlex
®
Rack, electronic circuit protector ESX300-S ...............................................21
4.1 Application ESX300-S .................................................................................................................... 21
4.2 Technical data of the Power-D-Box
®
............................................................................................21
4.2.1 Current rating, voltage drop and load capacity of ESX300-S ..........................................22
4.2.2 LED status indication ........................................................................................................ 22
4.3 Delivery scope ESX300-S .............................................................................................................. 22
4.4 Picture ESX300-S ...........................................................................................................................23
4.5 Installation and start-up ESX300-S ................................................................................................ 23
4.6 Removal of the electronic circuit protector ESX300-S ..................................................................25
4.7 Trouble-shooting concerning electronic circuit protector ESX300-S .............................................26
5 General: ControlPlex
®
Rack, signalling sub-assembly RSI10 ........................................................... 27
5.1 Application RSI10 ..........................................................................................................................27
5.2 Technical data of RSI10 .................................................................................................................27
5.2.1 Operating conditions and LED indication ......................................................................... 28
5.3 Delivery scope RSI10 ..................................................................................................................... 28
5.4 Picture of RSI10 .............................................................................................................................29
5.5 Installation and start-up RSI10 ......................................................................................................29
5
6 General: ControlPlex® Rack, control interface RCI10 .......................................................................30
6.1 Application RCI10 ..........................................................................................................................30
6.2 Technical data of RCI10 ................................................................................................................. 30
6.2.1 Momentary switch function and LED status indication .................................................... 32
6.2.2 Function IP-reset by pressing the reset button with LED display .....................................33
6.3 Delivery scope RCI10 .....................................................................................................................33
6.4 Picture of RCI10 ............................................................................................................................. 33
6.5 Installation and start-up RCI10 ...................................................................................................... 34
6.5.1 Picture of slot for RCI10 or RSI10 ....................................................................................35
6.5.2 Picture of an example for network connection ................................................................. 35
6.6 Configuration and start-up RCI10 .................................................................................................. 35
7 General: ControlPlex
®
Rack, E/A external alarm interface EAI300 .................................................36
7.1 Operating mode and application EAI300 ....................................................................................... 36
7.2 Technical data of EAI300 ................................................................................................................36
7.2.1 Operating conditions LED signalling.................................................................................37
7.3 Delivery scope EAI300 ................................................................................................................... 37
7.4. Picture EAI300 ................................................................................................................................37
7.5 Installation and connection EAI300 ................................................................................................38
7.5.1 Example: EAI300 slot configuration .................................................................................. 39
7.5.2 EAI300 pin assignment and connection example ............................................................39
7.6 Configuration and start-up EAI300 ................................................................................................39
6
General note
Qualified personnel
The system must only be installed, connected and configured in connection with this document. Installation and operation of the device/system must only be carried our by qualified personnel. With regard to the safety instructions of this documentation, qualified persons are persons authorised to operate devices, systems and circuits according to the standards and rules of safety engineering.
Safety instructions
Please follow the installation and configuration instructions given in this document carefully. Failure
to complay may lead to serious damages of the product or the system. E-T-A does not accept any liability for problems caused by improper installation or handling by the customer or a third person.
Symbols
You will find the following symbols in the entire manual. Their meaning is as follows:
Danger!
You are in a situation which might cause injury. Before working with one of the devices you have to be aware of the risks of electrical circuitries and you ought to be familiar with standard procedures of accident prevention.
Warning
There is a risk in this situation to do something which might cause damage of the devices or data loss.
Note
Here you receive information which might be particularly useful for the application.
Caution:
Electrostatically sensitive devices (ESD). Devices must exclusively be opened by the manufacturer.
7
8
1 Introduction
You chose ControlPlex® Rack, a comprehensive, future-oriented protection system which combines safety, user convenience and service friendliness. It is a power distribution and management system which provides electronic and, in the event of a short circuit, current-limiting protection of various loads. By means of an internal bus system and an additional, hot-pluggable control interface module (optional), each load can remotely be controlled and monitored. In addition it allows recording of measuring data of every single load. Besides providing overcurrent and short circuit protection, it increases system availability by a multiple, because it disconnects faulty loads quickly, selectively and without voltage dips.
In connection with the control interface module type RCI10 the ControlPlex
®
Rack system can be connected
to a centralised management system (control computer). For this purpose an Ethernet interface is made avail­able with SNMP v1, v2c or v3 protocol. The required private MIB for embedding is part of the delivery scope. An additional possibility for a centralised or also local monitoring/control is provided by the integral web server, which can be used without additional software on the control computer by means of the web browser.
Thanks to its system properties the ControlPlex
®
Rack is the perfect solution for smart protection, control
and energy measurement for DC-supplied minus switching system cabinets. Typical applications include:
System cabinets of any kind in telecommunications with DC -48 V or DC -60 V rated supply
Server cabinets in IT centres with equipment for DC -48 V or DC -60 V rated supply
System cabinets for mobile radio and television for DC -40 V to DC -72 V
Protection and control of illuminated advertising with a power supply of DC -48 V
Further descriptions of the ControlPlex
®
Rack system with information on the configuration and network
connection by means of the module control interface RCI10 are available in the Operation instruction RCI10 manual ControlPlex® Rack.
This document contains the mounting and connection procedures for the hardware of the ControlPlex
®
Rack
system as well as an instruction for the first operation. You will learn more about
how to mount and connect the different ControlPlex
®
Rack Power-D-Box® versions
how to start up or exchange the electronic circuit protectors type ESX300-S
how to identify and remedy failures of the electronic circuit protectors ESX300-S
how to install and connect the optional control interface RCI10
how to identify and remedy failures of the control interface RCI10 by means of LED indication
how to install and connect the E/A external alarm interface EAI300.
how to identify failures of the EAI300 by means of LED indication.
9
2 Minimal requirements of installation
Please check the delivered components upon receipt with regard to completeness. You require the following hardware components for installation and start-up of the ControlPlex® Rack system:
One or more Power-D-Box
®
modules type: PDB-N-CP
Electronic circuit protectors type ESX300-S-x00-xx A (version e.g.: with aux. contact only for PDB-N-
CP-xxx-xx-S, old version) or with bus interface; various current ratings: 2 A…24 A
Optional: control interface with Ethernet interface type RCI10-000-x. The circuit protector type ESX300-
S-300-xxA is mandatory for use with control interface and signalling sub-assemblies RSI10.
Optional: Alarm interface EAI300 for including additional “external” alarm contacts. Operation of EAI300
sub-assemblies requires control interface RCI10.
In addition you require different cables for connection of the Power-D-Box
®
, of the supply line, the loads
and the ground. Many manufacturers offer standard cables for this purpose.
2.1 Important information and safety instructions
The following table lists various information and safety instructions for start-up and use of the device.
Danger: Installation and operation of the device
This device has to be installed and operated in compliance with the given instructions. Failure to comply can lead to injury, damage of loads or of the ControlPlex
®
Rack system.
Danger: Turn off the supply voltage
Before beginning with installation, the system has to be disconnected from the mains. A cable connection must only be established if the supply voltage is OFF.
Danger: Possible ignition hazard
The device must NOT be used in inflammable surroundings.
Danger: high voltage
The cover must NEVER be opened. Access to the inner components is not allowed unless indicated otherwise in this manual.
Caution: Work with ESD protection
Electronic modules must only be touched and installed with ESD protection so as to ensure protection against electrostatic voltage. Failure to comply can cause damages on the ControlPlex® Rack system or the corresponding components.
Warning: Grounding
The device must be grounded before switching on.
Table 1: Important information
2.12 EMC installation directives
The ControlPlex
®
Rack hardware and accessories comply with the EMC directives. Thus electromagnetic interferences between the devices are avoided which would otherwise affect the system performance. A professional installation is mandatory. In order to ensure the best EMC conditions, the widest possible dis­tance between the different electrical devices should be applied.
2.3 Technical Accuracy
All technical data in this manual were correct in all conscience at the time of printing. E-T-A cannot be held liable for any (inadvertent) errors. Due to continuous product improvements at E-T-A there could be discrepancies between the actual product and the manual. Product changes or amendments of the technical
specifications will be carried out without prior notification. The latest versions of the ControlPlex
®
Rack
documents are available on our website (www.e-t-a.de).
10
3 General: ControlPlex
®
Rack Power-D-Box
®
By using the Power-D-Box® type PDB-N-CPxxx-xx-A you can benefit from the advantages of the ControlPlex®
Rack system to full extent, no matter whether the control interface RCI10 is used from the start or only later.
3.1 Use of the Power-D-Box
®
The ControlPlex® Rack Power-D-Box® has been designed for the quick and easy installation into 19" or ETSI racks which is ensured by a rotating mounting flange. Depending on the required termination technology (front or rear) the corresponding Power-D-Box® will be available as a product. The service friendliness has to be mentioned as a special advantage. The system can be extended with power on and additional circuit protectors can be plugged into the load terminals. The control interface can also be fitted later with power on without having to disconnect the loads.
11
3.2 Technical data of the Power-D-Box
®
The entire 19" rack features the protection degree IP20. Table 2 summarizes the vital information.
Electrical data PDB-N-
CP09A-RR-A
PDB-N­CP09A-RF-A
PDB-N­CP09A-FF-A
PDB-N­CP19A-RR-A
PDB-N­CP18R-RR-A
Operating voltage DC -48 V or
DC -60 V
DC -48 V or DC -60 V
DC -48 V or DC -60 V
DC -48 V or DC -60 V
DC -48 V or DC -60 V
Max. supply current:
150 A 150 A 100 A 200 A 2 x 150 A
number of circuit pro­tectors
9 9 9 19 18
Redundant system no no no no yes Protected pole Negative pole protected electronically, without physical isolation Suitable for
circuit protector
ESX300-S-3xx (2 A, 5 A, 8 A, 12 A, 16 A, 20 A, 24 A, with BUS)
Ambient temperature -20...+60 °C
Mechanical data PDB-N-
CP09A-RR-A
PDB-N­CP09A-RF-A
PDB-N­CP09A-FF-A
PDB-N­CP19A-RR-A
PDB-N­CP18R-RR-A
Dimensions see drawings and dimensions Mounting method 4 mounting screws M6 x 16 mm (not supplied with product)
tightening torque 5.3...5.7 Nm
Supply PDB-N-
CP09A-RR-A
PDB-N­CP09A-RF-A
PDB-N­CP09A-FF-A
PDB-N­CP19A-RR-A
PDB-N­CP18R-RR-A
Terminals on the rear on the rear on the front on the rear on the rear Screw terminals 16 – 50 mm²
AWG 5 – AWG 1
16 – 50 mm² AWG 5 – AWG 1
4 – 25 mm² AWG 11 – AWG 3
16 – 50 mm² AWG 5 – AWG 1
16 – 50 mm² AWG 5 – AWG 1
Tightening torque 6…8 Nm 6…8 Nm 4 ...4.5 Nm 6…8 Nm 6…8 Nm
Loads PDB-N-
CP09A-RR-A
PDB-N­CP09A-RF-A
PDB-N­CP09A-FF-A
PDB-N­CP19A-RR-A
PDB-N­CP18R-RR-A
Max. load current per load terminal
30 A with 9 ways
30 A with 9 ways
30 A with 9 ways
30 A with 19 ways
30 A with
2 x 9 ways Terminals on the rear on the front on the front on the rear on the rear Screw terminals 0.5 – 6 mm²
AWG 20 – AWG 10
0.5 – 6 mm²
AWG 20 – AWG 10
0.5 – 6 mm²
AWG 20 –
AWG 10 SUB-D connector 2.5 – 10 mm²
AWG 13 – AWG 7
2.5 – 10 mm² AWG 13 – AWG 7
Tightening torque 0.5…0.8 Nm 0.5…0.8 Nm 0.5…0.8 Nm
Signalling PDB-N-
CP09A-RR-A
PDB-N­CP09A-RF-A
PDB-N­CP09A-FF-A
PDB-N­CP19A-RR-A
PDB-N-
CP18R-RR-A
Terminals on the rear on the front on the front on the rear on the rear Screw terminals 0.25 – -1.5
mm² AWG 23 – AWG 16
0.25 – 1.5
mm² AWG 23 – AWG 16
0.25 – 1.5
mm²
AWG 23 –
AWG 16 SUB-D connector 2.5 – 10 mm²
AWG 13 – AWG 7
2.5 – 10 mm² AWG 13 – AWG 7
Tightening torque 0.22…0.25 Nm– 0.22…0.25 Nm0.22…0.25
Nm
Grounding PDB-N-
CP09A-RR-A
PDB-N­CP09A-RF-A
PDB-N­CP09A-FF-A
PDB-N­CP19A-RR-A
PDB-N-
CP18R-RR-A
Ground connector M6 ground stud, always on the rear, tightening torque 6 Nm
Table 2: A selection of technical data / *) further information can be found in the data sheet.
12
3.3 Scope of delivery of the Power-D-Box
®
The following parts are part of the delivery scope of the Power-D-Box®:
19" rack with 19“ / ETSI interchangeable flange (mounted 19“)
blanking pieces for slots of circuit protectors and control interface (mounted)
mating plugs in the event of rear screw terminals (plugged on). Versions: PDB-N-CPxxx-xR-Ax
mating plugs of signalling terminals (screwed on). Versions: PDB-N-CPxxx-xR-Ax
The following accessories can be ordered separately:
rear cable grip rail (part no. X223 260 01)
connector set, high current SUB-D for load terminal on the front (part no. X223 189 01)
marking frame with labels, 0.5U, for customised marking of circuit protectors (part no. X22357501)
marking frame with labels, 1U with cable gland on the front, for customised marking of circuit protectors
(part no. X22357601)
circuit protectors, type ESX300-S-3xx-xxA
signalling sub-assembly RSI10-xxx-x
control interface type RCI10-xxx-x
control alarm interface type EAI300-xxx-x
For more information on accessories please see the data sheet of ControlPlex
®
Rack.
3.4 Pictures of Power-D-Box
®
versions (front view)
fig. 1: front view PDB-N-CP18R-RR-A, PDB-N-CP19A-RR-Ax
fig. 2: front view PDB-N-CP09A-RR-Ax
fig. 3: front view PDB-N-CP09A-FF-Ax terminals on the front with high current SUB-D connectors
13
3.5 Drawings and dimensions of Power-D-Box® versions
515 (ETS)
465 (19“)
76.2 (19“)
75 (ETS)
88.9 (2HE)
fig. 4: front view PDB-N-CP09A-FF-Ax 1 x 9 slots, terminals on the front with high current SUB-D connectors
fig. 5: rear view PDB-N-CP09A-FF-Ax 1 x 9 slots (with rear cable grip rail)
482.6
88.9
fig. 6: front view PDB-N-CP19A-RR-Ax 1 x 19 slots
fig. 7: rear view DB-N-CP19A-RR-Ax without cable grip
14
515 (ETS)
465 (19“)
531.4 (ETS)
482.6 (19“)
76.2 (19“)
75 (ETS)
88.9 (2HE)
fig. 8: front view PDB-N-CP18R-RR-Ax 2 x 9 slots
fig. 9: front view PDB-N-CP18R-RR-Ax 2 x 9 slots
450
171.5
16014
201.5
271.5
cable grip set (optional)
cable guide supply
fig. 10: top view PDB-N-CP18R-RR-Ax 2 x 9 slots (with rear cable grip rail)
15
3.6 Schematic diagrams of Power-D-Box® versions
ESX300-S
E-T-A
RCI/RSI
A7 A4
1 11 1 11 1 11 1 11 1 11 1 11 1 11 1 11 1 11 1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 142 12 142 12 142 12 142 12 142 12 142 12 142 12 142 12 142 12 14A9
Status OK FAULT
LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-
LINE-LINE-LINE-LINE-LINE-LINE-LINE-LINE-LINE-
LINE-
EL-BUS
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LINE- LINE-LINE-LINE-LINE-LINE-LINE-LINE-LINE- LINE-
LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-
OK FAULTOK FAULTOK
FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULT OK FAULTOK FA ULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULT
-X0
-A1
-A2
-A3
-A4
-A5
-A6
-A7
-A8
-A9
-A10
-A11
-A12
-A13
-A14
-A15
-A16
-A17
-A18
-A19
pcb X22360401
busbar
busbar
busbar
busbar
A+
A-
A+
A-
ground enclosure
ground enclosure
-1.1
+1.3
-X2.1 - + -X2.2 - + -X2.3 - + -X2.4 - +-X2.5 - + -X2.6 - + -X2.7 - +-X2.8 - + -X2.9 - + -X2.10 - +-X2.11 - +
1.9 / Plus
1.9 / LIN
1.9 / ADR
1.9 / GND
1.9 / Line
2.1 / Plus
2.1 / LIN
2.1 / ADR
2.1 / GND
2.1 / Line
-X2.12 - + -X2.13 - +-X2.14 - + -X2.15 - + -X2.16 - + -X2.17 - +-X2.18 - +-X2.19 - +
-1.2
+1.4
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
fig. 11: Schematic diagram PDB-N-CP19A-RR-Ax, 1 x 19 slots with signalling
ESX300-S
E-T-A
RCI/RSI
A7 A4
1 11 1 11 1 11 1 11 1 11 1 11 1 11 1 11 1 11
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
1 11
2 12 14
2 12 142 12 142 12 142 12 142 12 142 12 142 12 142 12 142 12 14A9
Status
LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-
LINE-LINE-LINE-LINE-LINE-LINE-LINE-LINE-
LINE-
EL-BUS
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
LOAD-
LIN
Adresse
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LINE-
GND+
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LIN-BUS
LINE-
LINE-LINE-LINE-LINE-LINE-LINE-LINE-LINE- LINE-
LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-LOAD- LOAD-
OK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK
FAULT
OK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULTOK FAULT
-X0
-A1
-A2
-A3
-A4
-A5
-A6
-A7
-A8
-A9
-B1
-B2
-B3
-B4
-B5
-B6
-B7
-B8
-B9
pcb X22360411
pcb X22360421
busbar busbar
busbar
A
+
ground enclosure
ground enclosure
ribbon cable connection to pcb B1
ribbon cable connection to pcb A1
+A1.2
A- -A1.1
A1
-X2.1 - +-X2.2 - +-X2.3 - + -X2.4 - + -X2.5 - +-X2.6 - + -X2.7 - +-X2.8 - + -X2.9 - +
-X2.11 - +
B+ +B1.2
/ 7.9 / 6.9
B-
B1
-B1.1
-X2.12 - +-X2.13 - +-X2.14 - + -X2.15 - + -X2.16 - + -X2.17 - + -X2.18 - +-X2.19 - +
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
ESX300-S
E-T-A
fig. 12: Schematic diagram PDB-N-CP18R-RR-Ax, 2 x 9 slots with signalling
16
3.7 Pin assignment of Power-D-Box® versions
pin assignment PDB-N-CP09A-RR-Ax, PDB-N-CP18R-RR-Ax
Rear-side supply terminals DC 48 V–DC 60 V / max. 2 x 150 A
Cable cross section max. 50 mm²
loads B-/B+ loads A-/A+
plus 48 V DC B+ minus 48 V DC A-minus 48 V DC B- plus 48 V DC A+
fig.13 version PDB-N-CP18R-RR-A, pin assignment (cable grip removed)
Pin assignment PDB-N-CP09A-FF-Ax
Front-side supply terminals DC 48 V–DC 60 V / max. 100 A
Cable cross section max. 25 mm²
Front-side supply terminals A1 ... A9 DC 48 V–DC 60 V / max. 30 A
Cable cross section max. 10 mm²
17
minus 48 V DC A-
plus 48 V DC A+
plus 48 V DCminus 48 V DC
protected pole
empty
fig.14 version PDB-N-CP09A-FF-Ax, pin assignment
pin assignment PDB-N-CP09A-RF-Ax
line entry see PDB-N-CP09A-RR-Ax
load terminals see PDB-N-CP09A-FF-Ax
pin assignment PDB-N-CP19A-RR-Ax
Rear-side supply terminals DC 48 V–DC 60 V / max. 200 A with supply via two supply terminals
(internally bridged). Max. 150 A per supply terminal at 50 mm² cable cross section.
cable cross section max. 50 mm² per supply line
cable cross section max. 4 mm² with wire end ferrule per load terminal
plus 48 V DC A+ max. 150 A per terminal
plus 48 V DC A+ max. 150 A per terminal
minus 48 V DC A­max. 150 A per terminal
minus 48 V DC A­max. 150 A per terminal
load A19-/19+...A1-/A1+
cable grip (optional)
fig. 15 version PDB-N-CP19A-RR-A, pin assignment (cable grip installed)
18
3.8 Installation and start-up of the Power-D-Box®
The ControlPlex
®
Rack system has been designed for stationary installation in an indoor system cabinet.
For installation in an outdoor cabinet we recommend a fully conditioned cabinet with heating and cooling. In the event of high humidity the surrounding has to be additionally dried.
3.8.1 Recommended installation site for Power-D-Box
®
Usually the Power-D-Box
®
is installed in the top or bottom area of the sytem rack. We recommend installation
in close proximity to the connected loads so as to reduce wiring and cable management.
Important:
Leave sufficient space for heat dissipation, min. 0.5U above or below the
Power-D-Box
®
should be free for ventilation.
Please take care to install the Power-D-Box
®
in enclosed and dry rooms.
Please observe the required degree of protection.
GENERAL REQUIREMENTS OF INSTALLATION SITE
Various aspects have to be considered when choosing the installation site.
Ventilation
Please ensure sufficient ventilation by leaving enough space at all sides of the device and ensure that the vent holes are not blocked. Leave enough space between the devices.
Cable management
Ensure installation at a site where the cables can be laid and connected properly. Ensure ease of access for service and system extensions of all termination versions even after installation.
Electrical noise pulses
The installation site should provide sufficient distance to any devices that might emit noise pulses.
Table 3: Power-D-Box® Requirements of installation site
3.8.2 Basic notes on cabling for Power-D-Box®
The selection of the correct cable types regarding temperature resistance and ampacity is important for the reliable power distribution, control and monitoring by means of a ControlPlex
®
Rack system. Please ensure
to use cables of superior quality with the suitable cross sections so as to avoid voltage drops.
Laying of cables must be carried out carefully. The table 4 gives general hints regarding wiring of a
Power-D-Box
®
, including the connected loads.
Item Note
1 Cables must be protected against damages and heat. Avoid the proximity to moveable or
hot parts and to machines.
2 Ensure a suitable strain relief. 3 Check cables with regard to intact insulation, above all after cable laying.
Table 4: Power-D-Box® wiring hints
19
3.8.3 Installation and start-up of the Power-D-Box®
Important notes
Danger: Turn off the supply voltage
Before beginning with installation, the system has to be disconnected from the mains. A cable connection must only be established if the supply voltage is OFF.
Caution: Work with ESD protection
To protect electronic components against electrostatic voltage, any work must only be carried out with corresponding ESD protection means. Failure to comply can cause damages on the ControlPlex® Rack system or the corresponding components.
Warning: Mounting position
The Power-D-Box® must only be installed horizontally in the cabinet, vertical installation may cause overheating.
Warning: Supply voltage
The voltage of the power supply must be between DC 38 V and DC 72 V to ensure a smooth operation. In the event of a voltage in excess of DC 75 V the Power-D-Box® may be damaged.
Table 5: Power-D-Box® Important hints for start-up
Start-up of the Power-D-Box® comprises the following steps:
step action
1 Prepare all necessary devices and tools such as:
different screw drivers and M6 box wrench (not delivered with product)
connecting cables for power supply and ground (not delivered with product)
connecting cables for load terminals (not part of the delivery scope)
4 mounting screws M6 x 16mm with plastic sleeve
2 x M6 cable lug, not part of the delivery scope (ground connection Power-D-Box
®
)
load terminal mating plug (can be ordered as accessory for version with front connection, otherwise it is part of the Power-D-Box
®
delivery scope)
2
If installation shall be in an ETSI rack: Re-work of the Power-D-Box
®
mounting brackets to ETSI dimensions:
remove, turn bracket by 180°, re-fit with the 2 mounting screws.
3
Important: Please ensure that the system is dead-voltage.
4
Lay all necessary cables for grounding, supply and load terminals of the
Power-D-Box
®
5 Connect the load terminal cables with the corresponding load connectors and mark them
with the corresponding way no. of the Power-D-Box®
Important: Do not yet connect the load connectors to the Power-D-Box®.
Depending on the version, see chapter 3.7 pin assignment Depending on the version, tightening torque of supply terminals,
see table 2, "Technical data/supply"
6
Mounting of Power-D-Box® in the system cabinet:
Install the Power-D-Box® horizontally in the system cabinet and
fix it with the 4 supplied mounting screws. The tightening torque of the mounting screws is 5.3–5.7 Nm.
20
7 Connection of the Power-D-Box® grounding cable(s):
The ground connection is on the rear side of the Power-D-Box® (see fig. 15) and is
marked with a grounding symbol. In the event of two separate power supplies (redundant system) both ground connections have to be connected with one grounding cable each. The grounding cable can be fixed with an M6 cable lug and the fitted grounding nut with a tightening torque of 6 Nm.
8 Connection of the Power-D-Box® supply lines:
Depending on the version, see chapter 4.7 pin assignment Depending on the version, tightening torque of supply terminals,
see table 2, "Technical data/supply"
Important: Do not yet connect any load lines.
9 Switch on the power supply.
Check correct polarity with a voltmeter (plus, minus) and the correct voltage value of
the power supply. terminals. In the event of a failure please remedy before proceeding with step 10.
10
For installation of circuit protectors, go to chapter 4 "ControlPlex® Rack,
electronic circuit protector ESX300-S"
11
For installation as group alarm indicator (population without circuit protectors, only
with alarm interface EAI300) please go to chapter 7 "ControlPlex® Rack, E/A
external alarm interface EAI300"
End
Table 6: Power-D-Box® steps for start-up
21
4 General: ControlPlex® Rack,
electronic circuit protector ESX300-S
The electronic circuit protector ESX300-S has particularly designed for the use in the Power-D-Box® of type PDB-N-CP. It can be installed and de-installed with the system live without having to disconnect the application from the mains. Thus you can reduce the installation and service periods to a minimum.
4.1 Application ESX300-S
The electronic circuit protector ESX300-S is suitable for minus supplied systems with voltage ratings from DC -48 V and DC -60 V. It is capable of disconnecting all faulty loads selectively in the event of overcurrent and short circuit, i.e. without voltage dip or failure of neighbouring loads. In the event of overcurrent or short circuit the active current limitation of the ESX300-S prevents a overload-dependent voltage regulation of the (switched mode) power supply. In the event of a failure the latter prevents a voltage dip of the switch-mode power supply and thus repercussions on the neighbouring loads. The ESX300-S is available both with BUS interface and with potential-free signalling: only for PDB-N-CPxxx-xx-S (old version) The version with BUS interface in connection with the signalling sub-assembly RSI10 (see chapter 5) or with the control interface RCI10 (see chapter 6) allows failure indication as well as an automatic remote control of the ESX300-S via a controlling computer.
4.2 Technical data of ESX300-S
Electronic circuit protectors with active current limitation for use in minus-switching equipment.
Technical data of ESX300-S
Current ratings 2 A, 5 A, 8 A, 12 A, 16 A, 20 A, 24 A Capacitive load max. 7,000 uF (depending on the current rating)
Trip electronically (1-pole), no physical isolation Threshold for active
current limitation
Typical 1.2 x rated current ESX300-S
Reliability in the event of faulty electronics
integral fail-safe element (blade fuse)
Protected pole minus pole protected Operating voltage DC -37 V to DC -72 V Signalling (optional) potential-free auxiliary contacts BUS system (optional) EL-BUS
®
for communication with sub-assembly RCI10 Status indication LEDs red and green Low voltage indication < DC -37 V Overvoltage indication = / > DC minus 72 V Trip times typically < 10 ms at short circuit (current limitation active)
typically < 30 sec at overcurrent (I > IN < current limitation threshold)
Approval logos CE to EN 61000-6-3 and EN 61000-6-2, UL 2367
Mechanical data ESX300-S
Ambient temperature -20 °C ... +60 °C * Cooling convection cooling Mounting position vertical mounting position Version rack module with front plate, no separate enclosure, for installation in
Power-D-Boxes
®
Table 7: ESX300-S, technical data *) major technical data, for further information please see data sheet of ControlPlex® Rack
22
4.2 Current ratings, voltage drop and load capacity ESX300-S
Current
rating
range I
N
Typical voltage
drop UON at I
N
active current
limitation typically
trip time
typically at
1.2 x I
N
Fail-safe
element
max. load current at
100 % ON
duty
Max.
capacitive
load (µF)
T
AMB
= 40
°C
2 A 130 mV 1.20 x I
N
0.2 – 3 s 4 A 2 A 1500
5 A 130 mV 1.20 x I
N
0.2 – 3 s 10 A 5 A 2000
8 A 200 mV 1.20 x I
N
0.2 – 3 s 10 A 8 A 3000
12 A 150 mV 1.20 x I
N
0.2 – 3 s 20 A 12 A 4000
16 A 200 mV 1.20 x I
N
0.2 – 3 s 20 A 16 A 5000
20 A 160 mV 1.20 x I
N
0.2 – 3 s 30 A 20 A 6000
24 A 200 mV 1.20 x I
N
0.2 – 3 s 30 A 24 A 7000
Note: The total current of neighbouring devices must not exceed 44 A.
The derating factor at an ambient temperature of > 40 °C is 0.8 times rated current.
Table 8: ESX300-S, electrical data
4.2.2 LED Status Indication
Operating condition Load output LED green LED red
auxiliary contact
N/C (optional)
no error -> OFF locked flashing slowly OFF open normal operation connected ON OFF open
error undervoltage with device in OFF condition (15 V < U < 37 V)
locked OFF ON closed
error undervoltage with device in OFF condition (U > 72 V)
locked OFF ON closed
overcurrent error detected (I > IN < 1.2 x IN) overcurrent failure has to be detected for approx. 30 sec before disconnection is effected
connected ON flashing fast open
error – overcurrent or short circuit disconnection
locked OFF ON closed
error undervoltage (U > 15 V < 37 V)
connected ON ON closed
error overvoltage (72 V, < U < 75 V)
connected ON ON closed
error, no voltage or internal error
locked
1
OFF OFF closed
error high temperature locked
1
OFF flashing slowly closed
remote disconnection (ordering option control interface)
locked flashing fast OFF ------
Table 9: ESX300-S operating conditions - LED display
4.3 Delivery scope ESX300-S
The following parts are part of the delivery scope of the ESX300-S:
Electronic circuit protector, type: ESX300-S-xxx-xxA with front plate
removeable label in the front plate
23
4.4 Picture ESX300-S
fig. 16 ESX300-S electronic circuit protector
4.5 Installation and start-up ESX300-S Important notes
Note: Power-D-Box
®
installed
Before starting the installation, the Power-D-Box® has to be properly installed first and supply voltage should be applied. All steps in chapter 3 were carried out properly.
Caution: Work with ESD protection
To protect electronic components against electrostatic voltage, any work must only be carried out with corresponding ESD protection means. Failure to comply can cause damages on the ControlPlex® Rack system or the corresponding components.
Warning: Mounting position
The ESX300-S sub-assembly has to be pushed in vertically into the Power-D-Box®.
Warning: load terminal
Load terminal must be open (not connected) when installing the ESX300-S.
Warning: Supply voltage
The voltage of the power supply must be between DC 38 V and DC 72 V to ensure a smooth operation. In the event of a voltage in excess of DC 75 V the electronic circuit protector may be damaged.
Table 10: ESX300-S, Important hints for start-up
status LEDs
engagement nose
ON/OFF
rated current circuit protector
groove for label
24
Start-up of the ESX300-S comprises the following steps:
step action
1 Prepare all necessary devices and tools such as:
Electronic circuit protectors ESX300-S (check the ESX300-S with regard to the required current ratings, see chapter 4.5 fig. 16 "rated current value"
For use with PDB-N-CPxxx-xx-Ax (new version of Power-D-Box®), use of bus-capable circuit protectors is mandatory, type ESX300-S-3xx
2
Danger: Please ensure that all steps in chapter 3 for starting up the
Power-D-Box® are carried out correctly.
3
Warning: The total current of neighbouring devices must not exceed 44 A. The derating factor is 0.8 times rated current of the ESX300-S with ambient tempera­tures > 40°C.
4
Installation of the circuit protectors ESX300-S into the Power-D-Box
®
:
Push the ESX300-S with the correct current rating carefully into the related and
documented slot (e.g.: slot A1) until it latches on into the front plate in the
Power-D-Box®.
5
Check the LED indication of the installed ESX300-S:
The status LED "OK" must blink green (load output not yet connected). If the green
LED is lighted continuously, push the "On/Off" momentary switch once until it blinks.
Important: The red status LED "Fault" must be off. If this is not the case, please
go chapter 4.7 ESX300-S trouble-shooting and remedy the failure. Do not continue with step 6 before the LED status indication (both LEDs) is as described in step 5.
6
Connection load output to the corresponding load channel of the Power-D-Box
®
:
Important: Check correct polarity (plus/minus) before connecting.
Plug in the load terminal connector pertinent to the installed ESX300-S slot. Example: ESX300-S slot A1 is assigned to load connector A1+ / A1-
7
Switch on the load output of the ESX300-S:
Push the momentary switch "On/Off" of the installed circuit protectors ESX300-S.
LED status indication: Green LED "OK" is lighted continuously, red LED "fault" is off. If the LED indication is different from the description, please go to chapter 4.7 ESX300-S trouble-shooting.
8 Optional: Individual marking of ESX300-S with a corresponding name.
This can be done either on the small label of the ESX300-S or by means of the
marking bar available as accessory.
9
Repeat step 1–8 for each ESX300-S to be installed.
10
Optional: If additional population with E/A external alarm interfaces EAI300,
please go to chapter 7 "ControlPlex® Rack, E/A external alarm interface EAI300"
END
Table 11: Start-up ESX300-S
25
4.6 Removal of the electronic circuit protector ESX300-S
The electronic circuit protectors can be removed as follows:
step action
Caution: Work with ESD protection
To protect electronic components against electrostatic voltage, any work must only be carried out with corresponding ESD protection means. Failure to comply can cause damages on the ControlPlex® Rack system or the corresponding components.
1
Important: The ESX300-S has to be in the OFF condition before being removed.
Push the momentary switch "On/Off" until the green LED blinks slowly or
disconnect the Power-D-Box® (dead-voltage, both LEDs off)
2
When removing the electronic circuit protector, the interlock at the bottom of the front plate of the circuit protector must be pushed down (see fig. 17).
3 Hold down the interlock and remove the circuit protector by pulling simultaneously
at the handles on the top and the bottom of the front plate (see fig. 18).
END
Table 12: Removal of type ESS30-S...
fig. 17: ESX300-S interlock fig. 18: ESX300-S removal
interlock of front plate ESX300-S
push down interlock and pull the two handles of the circuit protector simultaneously
26
4.7 Trouble-shooting concerning electronic circuit protector ESX300-S
The electronic circuit protector ESX300-S has two status LEDs allowing a comprehensive failure analysis in the event of a failure. Please proceed as follows for trouble-shooting:
Important notes
Caution: Work with ESD protection
To protect electronic components against electrostatic voltage, any work must only be carried out with corresponding ESD protection means. Failure to comply can cause damages on the ControlPlex® Rack system or the corresponding components.
Special precautions must be taken in the system or machine which reliably prevent an automatic re-start of moveable parts of the system (cf. Machinery Directive 98/37/EG and EN 60204-1, Safety of Machinery).
Note: ESX300-S time after short circuit or overcurrent trip
After tripping due to a short circuit, the circuit protector ESX300-S can only be reset after a delay time of approx. 20 seconds.
Table 13: Hints for trouble-shooting for ESX300-S
What to do in the event of a failure
step action
1 Check status indication of ESX300-S:
Check the status of the LEDs of the ESX300-S by table 9, chapter 4.2.2
and put down the cause of the failure
2
Depending on the cause of the failure you can establish physical isolation of the faulty circuit by pulling out the ESX300-S
See chapter 4.6 Removal of the electronic circuit protectors.
3
Remedy the cause of the failure
As described in step 1, e.g. short circuit on load
4
Re-install the ESX300-S after remedy of the failure
See chapter 4.5 Start-up of ESX300-S
END
Table 14: Trouble-shooting ESS300-S
27
5 General: ControlPlex® Rack, signalling sub-assembly RSI10
The Remote Signalling Interface RSI10 has particularly been designed for use with the Power-D-Box® type PDB-N-CPxxx-xx-x in connection with the circuit protector ESX300-S. It can be installed and de-installed with the system live without having to disconnect the application from the mains. Thus you are able to add the RSI10 interface sub-assembly later if required, saving costs and avoiding downtimes.
5.1 Application RSI10
The Remote Signalling Interface RSI10 is designed for an operating voltage of DC 20 V to DC 75 V. It com­municates with all other ESX300-S circuit protectors installed in the Power-D-Box
®
via an internal bus. Thus it is possible to realise a potential-free group signalling of alarm messages of the ESX300-S electronic circuit protectors used in the system (version with bus interface. Per supply group of the Power-D-Box® the RSI10 provides one each potential-free change-over contact. An integral three-coloured LED additionally indicates failure conditions directly on site. The system can easily be extended at a later date to add the functions remote control, data logging and extended alarm monitoring by means of replacing the RCI10 sub-assembly by RSI10 without a failure of the connected loads.
5.2 Technical data of RSI10
Interface card for group alarm signalling of all circuit protectors installed in the ControlPlex
®
Rack.
Technical data of RSI10
Operating voltage DC 20 V…DC 75V Dielectric strength DC 100 V for 1 ms
Power consumption typical 1.2 W Internal interfaces ELBus
®
/power, 20-pole pcb connector
External connection two plug-in type 3-pole screw terminals with mating plugs
Cable cross section: 0.25 mm² … 2.5 mm² Alarm contact potential-free change-over contact Alarm contact
max. switching voltage
DC 72 V
Alarm contact Max. switching current
1 A
Alarm contact Max. rupture capacity
60 W / 62.5 VA
Status indication multicoloured LED (red, green, blue) Ambient operating tem-
perature
-20° C ... +60° C (without condensation, cf. EN 60204-1)
Storage temperature -30° C ... +70 °C Cooling convection cooling Mounting position vertical mounting position Version rack module with front plate, no separate enclosure, for installation in
Power-D-Box
®
type PDB-N-CP Degree of protection IP00 DIN 40050 Approval logos CE to EN 61000-6-3 / EN 61000-6-2 Conformity EN 60950-1 / UL 60950-1 compliant (when installed in PDB)
Table 15: RSI10, technical data
*) major technical data, for further information please see data sheet of ControlPlex
®
Rack
28
5.2.1 Operating conditions and LED indication
Operating condition circuit protector ESX300-S-3xx
Load output circuit protector ESX300-S-3xx
LED status RSI10 sub-assembly
Auxiliary contact RSI10 sub­assembly group signal “break contact”
status RSI10 sub-assembly
no error -> OFF locked green open normal operation normal operation connected green open normal operation error undervoltage with
device in OFF condition (15 V < U < 37 V)
locked green closed normal operation
error undervoltage with device in OFF condi­tion (U > 72 V)
locked green closed normal operation
Overcurrent error detected (I > IN < 1.2 x IN); overcurrent failure has to be detected for approx. 30 sec be­fore disconnection is effected
connected green open normal operation
error – overcurrent or short circuit discon­nection
locked green closed normal operation
error undervoltage (U > 15 V < 37 V)
connected green closed normal operation
error overvoltage (72 V < U < 75 V)
connected green closed normal operation
error: no voltage locked OFF (green)1 closed normal duty 1
locked green closed normal operation
green closed no ESX300-S
circuit protector availabe
check if ESX300-S bus version is plugged in
---------- ---------- red closed internal RSI10 error or internal bus error
---------- ---------- 5 sec blue open one new circuit protector ESX300-S was identified
1
In a redundant system with two supply voltages the green LED lights if only one voltage supply fails, otherwise the RSI10 sub­assembly is dead-voltage table 16: RSI10, operating conditions – LED
5.3 Delivery scope RSI10
The following parts are part of the delivery scope of the RSI10:
Remote control interface, type: RSI10-xxx-A with front plate and label including alarm connection mating plug
29
5.4 Picture of RSI10
fig. 19: RSI10 sub-assembly
5.5 Installation and start-up RSI10 Important notes
Information: Power-D-Box® and ESX300-S installed
Before starting the installation, the Power-D-Box® has to be properly installed first and supply voltage should be applied. All steps in chapter 3.8.3 and chapter 4.5 were carried out properly.
Caution: work with ESD protectionTo protect electronic components against electrostatic voltage, any work must only be carried out with corresponding ESD protection means. Failure to comply can cause damages on the ControlPlex® Rack system or the corresponding components.
!
Important: Mounting position
The RSI10 sub-assembly has to be pushed in vertically into the Power-D-Box® in slot:. X0.
Table 17: RSI10, Important hints for start-up
status LED
alarm contact terminal supply group A of the Power-D-Box
alarm contact terminal supply group B of the Power-D-Box
engagement nose
groove for label
30
Start-up of the RSI10 sub-assembly comprises the following steps:
step action
1 Prepare all necessary devices and tools such as:
Remote Signalling Interface RSI10
connecting cables for external alarm signalling
2
Important: Please ensure that all steps in chapter 3 for starting up the Power-D-Box® and in chapter 4 "Start-up ESX300-S" were carried out correctly.
4
Installation of the RSI10 sub-assembly into the Power-D-Box
®
:
Push the RSI10 sub-assembly carefully into slot X0 and push until latch-on in the
front plate in the Power-D-Box®, see fig. 22.
5
Check the LED indication of the RSI10:
The green status LED must be lighted continuously latest after 10 seconds. If this is not the case,please go chapter 5.2.1 LED operating conditions and remedy the
failure. Do not continue with step 6 before the green LED is lighted continuously.
6
Connection of an external alarm indication
Connect a prepared external alarm indication via the 3-pole alarm contact terminal
to the plug of the corresponding screw terminal ( C = root; NC = break contact; NO = make contact). An error signal can be indicated via C/NC, an OK signal via C/NO.
Split-up group signal of the Power-D-Box
®
for supply group A = upper 3-pole
terminal on RSI10
Split-up group signal of the Power-D-Box
®
for supply group B = lower 3-pole
terminal on RSI10
Note: If there is only one supply group on the Power-D-Box
®
, the group alarm
signal “A” is emitted at both terminal blocks.
7 In the event of an extension with additional circuit protectors
The RSI10 LED must be lighted in blue for approx. 5 sec. This means that the
newly plugged in circuit protector was identified, see also chapter 5.2.1.
END
Table 18: RSI10, installation and connection
31
6 General: ControlPlex® Rack, control interface RCI10
The Remote Control Interface RCI10 has particularly been designed for use with the Power-D-Box® type PDB-N-CPxxx-xx-A in connection with the circuit protector ESX300-S. It can be installed and de-installed with the system live without having to disconnect the application from the mains. Thus you are able to add the interface sub-assembly later if required, saving costs and avoiding downtimes.
6.1 Application RCI10
The Remote Control Interface RCI10 is designed for an operating voltage of DC 20 V to DC 75 V. It com­municates with all circuit protectors type ESX300-S-3xx-xxA (version with BUS interface) installed in the
Power-D-Box
®
via an internal BUS. The RCI10 can easily be interconnected with a local LAN network via an external Ethernet interface. Various integral protocols allow a complete automation and remote control of the individual circuit protectors, e.g. ON/OFF operation depending on the voltage or current value. In addition alarm signals and a continuous data recording per query can be forwarded to a connected control computer.
6.2 Technical data of RCI10
Interface card for measuring data recording, automation and remote control of all circuit protectors installed in the ControlPlex
®
Rack.
5.2 Technical data of RCI10
Operating voltage DC 20 V…DC 75 V Dielectric strength DC 100 V for 1 ms
Power consumption Typical 2 – 3 W Internal connection 20-pole pcb connector (EL-BUS, power etc.) External connection Ethernet 10 / 100 Base-T, RJ45-connection sleeve for standard network cable
of category Cat-5, type "Shielded Twisted Pair" Status indication RGB LED (red, green, blue) Momentary switch reset and special functions Supported protocols SNMP v1, v2c, v3; HTTP, HTTPS, SSH2, DHCP, NTP, IPv4, IPv6 Ambient operating tem-
perature
- 20° C ... +60° C (without condensation, cf. EN 60204-1)
Storage temperature -30° C ... +70 °C Cooling convection cooling Mounting position vertical mounting position Version rack module with front plate, no separate enclosure, for installation in
Power-D-Box
®
Degree of protection IP00 DIN 40050 Approval logos CE to EN 61000-6-3 / EN 61000-6-2 Conformity EN 60950-1 / UL 60950-1 compliant (when installed in PDB)
Table 19: RCI10, technical data
*) major technical data, for further information please see data sheet of ControlPlex
®
Rack
32
6.2.1 LED operating conditions, momentary switch "reset" and failure remedy
"reset" mo­mentary switch
LED colour
LED condition:
importance description / action
- green ON normal operation The green LED is lighted continuously when booting
is completed and the RCI10 is operating faultlessly. Network connection can be established after another 10 sec.
pushed down for 35 sec
green blinking reset IP address
to factory settings
By pushing the reset button for 35 seconds, the IP settings can be reset For visual control that the reset button has been pushed down long enough, the green LED will blink for 5 seconds. Release the momentary switch while the LED blinks, see fig. 19
- red ON internal failure
RCI10
The red LED indicates a serious internal failure in the RCI10 sub-assembly. The sub-assembly is no longer operational. By means of a cold boot (remove the sub-assembly
- wait for 20 seconds - plug in again) the failure may be remedied. The RCI10 sub-assembly should be replaced nevertheless.
- red ON Serious internal
failure BUS (EL-BUS)
The red LED indicates an EL-BUS failure. The communication with the circuit protector ESX300-S and the RCI10 is disrupted. This problem can be caused by a defective circuit protector or a defective RCI10 sub-assembly.
- blue ON Ethernet link
available
If a network connection is established in operation (layer 1), the LED will be lighted blue for some 10 seconds.
- blue ON reset IP address
to factory settings
The blue LED will be lighted for 10 seconds when the IP address has successfully been reset to factory settings, see fig. 19 Automatic booting will follow, this can last up to 60 seconds.
- - OFF Booting The RCI10 sub-assembly is booting. Booting can
take up to 60 seconds.
- - OFF no supply
voltage
No supply voltage or wrong polarity. 1) The voltage supply of the Power-D-Box
®
must at least be DC
20 V. 2) Check polarity of the voltage supply at the
Power-D-Box® (plus/minus).
pushed down for 3 sec
- OFF Warm boot The system can be reset by pushing the reset button for 3 seconds (warm boot)
- OFF RCI10 sub-as-
sembly defective
If the LED remains unlighted after booting (max. 60 sec), the RCI10 sub-assembly is defective. The sub-assembly must be replaced.
Table 20: RCI10, operating conditions - LED
33
6.2.2 Function IP-reset by pressing the reset button with LED display
fig. 20: RCI10 IP-Reset
6.3 Delivery scope RCI10
The following parts are part of the delivery scope of the RCI10:
Remote control interface, type: RCI10-xxx-A with front plate
6.4 Picture of RCI10
fig. 21: RCI10 sub-assembly
RGB Status LED
RJ45 / Ethernet
engagement nose
momentary switch / reset
label
34
6.5 Installation and start-up RCI10 Important notes
Note: Power-D-Box® and ESX300-S and/or EAI300 installed
Before starting the installation, the Power-D-Box® has to be properly installed first and supply voltage should be applied. All steps in chapter 3.8.3, chapter 4.5 and (optional) chapter 7.5 were carried out properly.
Caution: Work with ESD protection
To protect electronic components against electrostatic voltage, any work must only be carried out with corresponding ESD protection means. Failure to comply can cause
damages on the ControlPlex® Rack system or the corresponding components.
Warning: Mounting position
The RCI10 sub-assembly has to be pushed in vertically into the Power-D-Box® in slot: X0.
Table 21: RCI10, Important hints for start-up
Installation and connection of the RCI10 sub-assembly comprise the following work steps:
step action
1
Prepare all necessary devices and tools such as:
Remote Control Interface RCI10
Ethernet cable 10 / 100 Base-T with the correct terminal length
2
Important: Please ensure that all steps in chapter 3 for starting up the
Power-D-Box® and in chapter 4 "Start-up ESX300-S" were carried out
correctly.
3
Important: Please make sure that any connected signalling cables (group signalling) on the Power-D-Box® are de-installed. Should voltage be applicable here, parts of the ControlPlex® Rack could be destroyed.
4
Installation of the RCI10 sub-assembly into the Power-D-Box®:
Push the RCI10 sub-assembly carefully into slot X0 and push until latch-on in the
front plate in the Power-D-Box®, see fig. 22.
5
Check the LED indication of the RCI10:
The green status LED must be lighted continuously latest after 60 seconds.
If this is not the case,please go chapter 6.2.1 LED operating conditions and remedy the failure. Do not continue with step 6 before the green LED is lighted continuously.
6
Connection of Ethernet cable
Plug the Ethernet cable into the RJ45 connector of the RCI10 sub-assembly, see
fig. 20, and connect it to your internal network or directly with a configuration PC, see fig. 23.
7
Go to chapter 6.6 and configure the RCI10 sub-assembly according to your requirements.
END
Table 22: RCI10, installation and connection
35
6.5.1 Picture of slot for RCI10 or RSI10
Information: The slot X0 is at the same position with all PDB-N-CPxxx-xx-x versions, first slot on the left side.
fig. 22: PDB slot X0
6.5.2 Picture of an example for network connection
router
PDB-N-CP
Ethernet cable
load-1
load-2
load-3
SNMP v1, v2c, v3 (HTTP(S)/SSH)
configuration PC system cabinet
Power
HTTP(S)/SSH
management system / main computer
intranet
ControlPlex® Rack
RCI10
ESX300-S
EAI300
Fig. 23: connection example network
6.6 Configuration and start-up RCI10
For configuring the RCI10 sub-assembly you need the ControlPlex
®
Rack Operation Instruction RCI10.
In order to establish a logic connection in your LAN network with a configuration PC, the RCI10 sub-assembly has to be connected with the PC via an Ethernet cable, see fig. 23.
The document ControlPlex
®
Rack Operation instruction RCI10 is available on our website:
www.e-t-a.de/controlplex_rack
Slot RCI10 or RSI10
36
7 General: ControlPlex
®
Rack, E/A external alarm interface EAI300
The EAI300 has particularly been designed for use with the Power-D-Box® type PDB-N-CP in connection with the remote control interface RCI10. It can be installed and de-installed in the Power-D-Box® later with the system live without having to disconnect the application from the mains. The EAI300 only requires a free ESX300 slot (slot for circuit protectors) in the Power-D-Box®.
7.1 Operating mode and application EAI300
The EAI300 has been conceived for connection and free text indication of alarm messages from “external” alarm contacts and sensors in the plant room by means of a control computer. This could include door contacts, temperature sensors or alarm contacts of the air conditioning system. The EAI300 interface communicates with the RCI10 Remote Control Interface installed in the Power-D-Box
®
via an internal bus. The RCI10 sub-assembly communicates with a management system or a control computer by means of an Ethernet interface. With the help of an integral LED an “external” alarm can also be indicated locally on the EAI300. An integral 24V voltage output can be used directly for reading the alarm contacts. Equally, there are two potential-free outputs available for activating e.g. a door lock or for realising an additional group signalling of the ESX300 circuit protectors. Within a Power-D-Box® you can install up to 20 EAI300 sub-assemblies.
7.2 Technical data of EAI300
Interface card for forwarding additional alarms in the engineering room, so-called “external alarms”.
Technical data of EAI300
Operating voltage
DC 20 V … DC 75 V
Dielectric strength
DC 100 V for 1 ms
Power consumption
Typically 1.9 W
Internal interfaces
EL-Bus
®
and supply via blade terminals
External connection
Two plug-in type 8-pole connection sleeves with spring-loaded connectors on the front side Cross-section
0.14 mm² … 1.5 mm²
Number of digital inputs:
Eight physically isolated inputs Current consumption 1 mA at 24 V Input resistance: 22.1 kOhm Voltage potential “HIGH” level DC 12 V … DC 72 V Voltage potential “LOW” level DC 0 V … DC 4 V
Number of analog inputs:
One physically isolated input Measuring input 4 mA … 20 mA
Number of digital outputs (relay outputs)
Two physically isolated relay outputs (break contacts) Max. load current of contact 2 A Voltage range – contact DC 12 V … DC 72 V
Internal supply voltage for I/O connection
Typically DC 24 V
(at Power-D-Box supply voltage ≥ DC 30 V) Max. load current: 100 mA
37
External supply voltage for I/O connection
DC 12 V … DC 72 V
Max. number of EAI300 sub-assemblies per
Power-D-Box® and RCI10 sub-assembly
20 (depending on Power-D-Box
®
type)
Table 23: EAI300, technical data
*) major technical data, for further information please see data sheet of ControlPlex
®
Rack
7.2.1 Operating conditions LED signalling
Operating condition EAI300 LED indication EAI300
EAI300 normal duty green EAI300 normal duty: digital input has status
“High“
green / cyan blue blinking
EAI300 normal duty: identified new circuit protector ESX300 (relay output configured as group signal)
5 seconds blue
EAI300 fault condition: no control interface RCI10 available
red blinking
EAI300 fault condition: EAI300 internal fault red EAI300 fault condition: no RCI10 available
and digital input on status “High“
red / cyan blue blinking
Table 24: EAI300, operating conditions – LED
7.3 Delivery scope EAI300
The following parts are standard part of the delivery scope of the EAI300:
External Alarm Interface, type: EAI300-xxx-A with front plate including spring force mating plugs
Accessories: 16 labels and coding pin for spring force mating plugs
7.4 Picture EAI300
38
7.5 Installation and connection EAI300 Important notes
Note: Power-D-Box® and additional sub-assemblies installed
Before starting the installation, the Power-D-Box® has to be properly installed first and supply voltage should be applied. All steps in chapter 3 were carried out properly.
Caution: Work with ESD protection
To protect electronic components against electrostatic voltage, any work must only be carried out with corresponding ESD protection means. Failure to comply can cause damages on the ControlPlex® Rack system or the corresponding components.
Warning: Mounting position
The EAI300 sub-assembly has to be pushed in vertically into the Power-D-Box®.
Table 25: EAI300, Important hints for start-up
Installation and connection of the EAI300 sub-assembly comprise the following work steps:
step action
1
Prepare all necessary devices and tools such as:
External Alarm Interface EAI300 and accessories
connecting cables for external Alarm Interface
Probably a distribution terminal is required
2
Important: Please ensure that all steps in chapter 3 for starting up the
Power-D-Box® and in chapter 4 "Start-up ESX300-S" were carried out correctly.
3
Important: INSTALLATION POSITION
When using the EAI300 together with ESX300 circuit protectors within one
Power-D-Box®, the EAI300 should always be plugged into the highest slot of the Power-D-Box®, e.g. with Power-D-Box type: PDB-N-CP19A… into slot 19, the
following EAI300 into slot 18 etc.
4
Installation of the EAI300 sub-assembly into the Power-D-Box®:
Push the EAI300 sub-assembly carefully into the corresponding slot and push until
latch-on in the front plate in the Power-D-Box®, see fig. 7.5.1 "Example EAI300 slot configuration"
5
Check the LED indication of the EAI300:
1. RCI10 sub-assembly already pre-installed: The green status LED must be lighted continuously.
2. RCI10 sub-assembly not installed: The red status LED must be blinking.
If this is not the case, please go chapter 7.2.1 LED operating conditions and
remedy the failure. Do not continue with the next step before the LED status indication shows the correct condition.
6
Plug coding and plug numbering
Please code the plug X5 and number the contacts of the plugs X5 and X6 with the
supplied accessory set, see chapter 7.5.2 "EAI300 pin assignment and connection example"
7
Connection of "external" alarm contacts
Connect the "external" alarm contacts / alarm outputs with the appropriate
terminals via the connectors of the EAI300, please see chapter 7.5 2 "EAI300 connection example"
8
Please record each connected alarm contact
You will require this information later for the logical assignment of the alarms
(software configuration) Example: "Door contact cabinet 1 = PDBxx- slot A19 / digital input 1"
9
Repeat step 1–8 for each EAI300 to be installed.
39
10
No RCI10 sub-assembly pre-installed
Please go to chapter 6 and install the RCI10 sub-assembly.
11
RCI10 sub-assembly pre-installed Go to chapter 7.6 and configure the EAI300
sub-assembly according to your requirements.
END
Table 26: EAI300, installation and connection
7.5.1 Example: EAI300 slot configuration (mixed population with ESX300 and EAI300)
slot X0: control interface RCI10
example: 4 slots external alarm interface EAI300
example: 16 slots circuit protectors ESX300-S
cable gland upwards to rear wall of cabinet
7.5.2 EAI300 pin assignment and connection example
connector X5
alarm output
sensor 4–20 mA
-
+
connector X6
Label
LED
retaining clip
alternative supply: external power supply for the inputs and outputs
Extern DC 12 V ... DC 72 V
max. 100 m
A
Ext. GND
alarm contact 3alarm contact 1
digital input 1 digital input 3 digital input 5 digital input 7
output 1 (NC) output 2 (NC) Iso. + DC 24 V analog input (+)
digital input 2 digital input 4 digital input 6 digital input 8
output 1 (C) output 2 (C)
analog input (-)
Iso. GND
1 3 5 7
1 3 5 7
2 4 6 8
2 4 6 8
7.6 Configuration and start-up EAI300
For configuring the EAI300 sub-assembly you need the ControlPlex
®
Rack Operation Instruction RCI10.
The document “Operation instruction Remote Control Interface RCI10” is available on our website: www.e-t-a.de/controlplex_rack.
E-T-A Elektrotechnische Apparate GmbH Industriestraße 2-8 . 90518 ALTDORF GERMANY Tel. +49 9187 10-0 . Fax +49 9187 10-397 E-Mail: info@e-t-a.de . www.e-t-a.de
Installation manual I_19BGTCP_d_200617 Issue 03 All rights reserved
Loading...