DANGER: means if the safety information is not followed someone will be seriously
injured or killed.
WARNING: means if the safety information is not followed someone could be seriously
injured or killed.
CAUTION: means if the safety information is not followed someone may be injured.
1. To reduce the risk of fire or shock hazard, this humidifier has a polarized plug (one
blade is wider than the other). Plug humidifier directly into a 120V, A.C. electrical
outlet. Do not use extension cords. If the plug does not fully fit
into the outlet, reverse plug. If it still does not fit, contact a qualified electrician to
install the proper outlet. Do not change the plug in any way.
2. Keep the electric cord out of traffic areas. To reduce the risk of fire hazard, never
put the electric cord under rugs, near heat registers, radiators, stoves or heaters.
3. Always unplug the unit before moving, cleaning or removing the fan assembly
section from the humidifier, or whenever it is not in service.
4. Keep the humidifier clean.To reduce the risk of injury, fire or damage to humidifier,
use only cleaners specifically recommended for humidifiers. Never use flammable,
combustible or poisonous materials to clean your humidifier
5. Do not put foreign objects inside the humidifier.
6. Do not allow unit to be used as a toy. Close attention is necessary when used by or
near children.
7. To reduce the risk of electrical hazard or damage to humidifier, do not tilt, jolt or tip
humidifier while unit is running.
8. To reduce the risk of accidental electrical shock, do not touch the cord or controls
with wet hands.
9. To reduce the risk of fire, do not use near an open flame such as a candle or other
flame source.
WARNING: For your own safety, do not use humidifier if any parts are damaged
or missing.
WARNING: To reduce risk of fire, electric shock, or injury always unplug before
servicing or cleaning.
WARNING:To reduce the risk of fire or shock hazard, do not pour or spill water
into control or motor area. If controls get wet, let them dry completely and have
unit checked by authorized service personnel before plugging in.
2
INTRODUCTION
Your new humidifier adds invisible moisture to your home by moving dry inlet air through a
saturated wick. As air moves through the wick, the water evaporates into the air, leaving
behind any white dust, minerals, or dissolved and suspended solids in the wick. Because
the water is evaporated, there is just clean and invisible moist air.
As the evaporative wick traps accumulated minerals from the water, its ability to
absorb and evaporate water decreases. We recommend changing the wick at the
beginning of every season. In hard water areas, more frequent replacement may be
necessary to maintain your humidifier’s efficiency.
Use only AIRCARE® or Essick Air® / MoistAIR® brand replacement wicks and chemicals.
To order parts, wicks and chemicals call 1-800-547-3888. This series of humidifiers uses
wick # HDC12. Only AIRCARE
®
or Essick Air® / MoistAIR® evaporative wicks guarantee
the certified output of your humidifier. Use of other brands of wicks voids the certification of
output and may void your warranty.
KNOW YOUR HUMIDIFIER
Description EA1407/HD1409
*Output per 24 hrs 14 gallons/53 Litres
Capacity of Each Bottle 2.375 gallons/ 9 Litres
*Sq. ft. coverage
Fan Speeds 3
Auto Fan Speed Yes
Replacement Wick HDC12 (Set of 4)
Refill Indicator Yes
Adjustable Humidistat Yes
Auto Shut Off Yes
Controls Digital
Casters Yes (4)
ETL Listed Yes
Volts 120 A.C.
Hertz 60
Amps (High Speed) 2.88
Watts (High Speed) 165
* Based on an area with average insulation and an 8 foot
ceiling height. ANSI/AHAM HU-1-1997. SEC 8.1
Results may vary.
+3,000 (Tight Const.)
2,900 (Avg. Const.)
3
HOW YOUR HUMIDIFIER
WORKS
Dry air is drawn into the
humidifier though the back and
moisturized as it passes
through the evaporative wicks.
It is then fanned out into the
room.
ASSEMBLY
1. Unpack humidifier from carton. Remove manual.
2. Remove all packaging materials. Some packaging material is located under the
fan assembly. Verify the following items are in the humidifier cabinet.
♦ 2 wick assemblies with
4 wicks installed
♦ 2 bottles ♦ 2 bottle caps and 2 valve caps
♦ Float with retainer ring ♦ Manual & registration card
CASTERS
3. Turn the emptied cabinet upside down.
♦ 4 casters and 2 caster pads
4. Insert each caster stem into one ofthe
four caster holes manually Do not use
tools. The casters should fit snugly
and be inserted until the stem shoulder
reaches the cabinet surface.
5. Turn the cabinet right side up.
REINSTALLING COMPONENTS
1. Reinstall float.
2. Reinstall wick assemblies
into cabinet.
3. Reinstall water bottles
Float
Front
Front
FRO
N
T
FRONT
FRONT
Front
Left
Right
FRONT
Front
FRONT
NOTES ON LOCATION:
In order to get the most effective use from your humidifier, it is important to position
the unit where the most humidity is needed or where the moist air will be circulated
throughout the house such as near a cold air return. If the unit is positioned close to
a window, condensation may form on the window pane. If this occurs, the unit
should be repositioned in another location.
Place humidifier on a flat,
level surface. Do NOT
position the unit directly in
front of a hot air duct or
radiator. If placing on
carpet, use caster pads to
ensure level placement.
Due to release of cool,
moist air from the
humidifier, it is best to
direct air away from
thermostat and hot air
registers. Place the unit on
a level surface 2 inches
from the wall.
NOTE: The use of a buble level will ensure
placement for proper bottle draining.
Front of cabinet
Front caster
Caster pad
Carpet or uneven surface
If positioning on carpet or
uneven surface, place caster
pads under front casters only
to level (if necessary).
4
FILLING
WARNING: Disconnect power before filling, cleaning or servicing unit. Keep grille dry
at all times.
WARNING: To reduce the risk of fire or shock hazard, DO NOT pour or spill water into
control or motor area. If controls get wet, let them dry completely and have unit
checked by authorized service personnel before plugging in
NOTE: Fill unit with cool, fresh (preferably unsoftened) water. If you only have softened water
available in your home, you can use it, but mineral buildup will occur more quickly.
NOTE: On initial fill up, it may take approximately 30 minutes for the wicks to become
fully saturated.
CAUTION: Use only EPA Registered Bacteriostat. Under no circumstances should
you use Water Treatment products intended for Rotobelt or Ultrasonic
humidifiers.
We recommend using AIRCARE
when you refill the water reservoir to eliminate bacterial growth. Add bacteriostat
according to the instructions on the bottle. Call 1-800-547-3888 to order.
NOTE: The humidifier contains water bottles. The weight of the bottles in the front of
the cabinet may cause the front casters to sink deeper into the carpet. If this happens,
the water level will be higher towards the front of the humidifier, and lower towards the
back. The water level float (located at the rear of the cabinet) may not sense the water
so the flashing “F” will be displayed and the unit will not energize. If this happens, the
unit will need to be leveled in order for the humidifier to be energized. To level the
humidifier, place the included caster pads under the front two casters of the humidifier
only.
1. Open the pivoting lid of the humidifier.
Remove the water bottles by lifting them
straight up and out of the cabinet.
Notice the water bottles are designed as
right and left hand units. When refilling the
bottles ensure correct placement for proper
function.
The water bottles should rest in the front of
the cabinet. Each “Side-Fill Cap” must be
facing the rear of the unit.
Each water bottle is designed with a
“Side-Fill Cap” and bottom valve cap.
Before filling each bottle check that the
bottle valve cap is on securely.
NOTE: A fill hose, P/N 4400, that attaches to a
faucet can be purchased by calling1-800-547-3888.
®
or Essick Air® Bacteriostat Treatment P/N 1970
5
2. To fill, remove the “Side-Fill Cap” and place the opening under a water faucet (the
bottle should fit under a four-inch clearance faucet). Fill with recommended mixture
of cold water and Bacteriostat (if necessary) only. Solid debris could make the valve
leak. Install the “Side-Fill Cap” by twisting clockwise. Hand tighten only.
NOTE: Both bottle caps have rubber washers in them. Do Not Remove.
3. Check for possible leaks by performing the following:
a. Grasp bottle handle and hold the bottle upright over a sink.
b. Inspect the bottom valve for leaks.
c. Press up on the valve cap plunger for about one second to let out a little water.
d. Release the plunger.
e. Listen for air bubbles. Look for leaks around the“Side-Fill Cap”.
f. If you hear air bubbles or see leaks, retighten the “Side-Fill Cap” and repeat Steps a-e.
4. Wipe off excess water from the bottle.
5. Position the water bottle back into the
unit by grasping the water bottle
handle and lowering it gently into the
cabinet until the bottle sits on pads at
bottom of cabinet. The “Side-Fill Cap”
must be facing the rear of the cabinet.
When positioned properly, the plunger
will open and water will flow into the
cabinet. The water level will
automatically remain at approximately
1/2” until the bottles are empty. Allow
the wick to saturate for 30 minutes
before operation.
ABOUT HUMIDITY
Where you set your desired humidity levels depends on your personal comfort level,
the outside temperature and the inside temperature.
NOTE: Recent CDC tests show that the chances of flu transmission are greatly
reduced at levels of 43% humidity or higher.
You may wish to purchase a hygrometer* to measure the humidity level in your
home. The following is a chart of recommended humidity settings.
*Model 1990 digital hygrometer is available for purchase by calling 1-800-547-3888.
NOTE: External hygrometer readings and humidistat readings may differ. Humidity
levels can vary significantly even in one room.
6
IMPORTANT: Water
damage may result if
condensation starts to form
on windows or walls.
Humidity SET point should
be lowered until
condensation no longer
forms. We recommend
room humidity levels do not
exceed 50%.
HUMIDISTAT
This unit has an humidistat located on the power cord. It
senses the percentage of humidity in the air and causes
the humidifier to cycle on and off to maintain the
selected humidity SET point. The fan will turn on if the
“ROOM” reading falls 3% below the SET
point and will continue to run the humidifier until
a reading of 1% above the SET point is achieved. The
fan will turn off until the ROOM reading falls 3% below
the SET point again.
NOTE: Be sure the humidistat located on the power cord
is at least two inches away from the wall, free from
obstruction and away from any hot air source.
Where you set your desired humidity levels depends on your personal comfort level,
outside temperature and inside temperature. A starting set point of 30%
to 40% ROOM humidity is recommended but there may be conditions that require a
different setting.
NOTE: If excessive condensation occurs, reduce fan to a lower speed setting.
DIGITAL DISPLAY
Press the power button once to
turn the unit on. Initially there is a
slight delay while the electronics
calibrate.Two bars (- -) appear
during this time. Once calibration
is complete a ROOM humidity
reading between 20% - 95% will
be displayed. A flashing 20 display
indicates that the room humidity is
less than 20%.
NOTE: The default settings at initial startup are (LOW) F1 fan speed and 65%
SET humidity. After desired settings are selected by the user, they remain as long as
the unit remains plugged in and there is no power interruption. When the unit is
unplugged, the original default settings are reinstated.
7
®
Digital Display
Fan Speed
Humidity
Control
Power Button
FAN SPEED
This humidifier is equipped with a 3-speed fan control. Initially pressing
the speed button will display the current speed setting. Each push
of the speed button advances the mode through the settings of
(HIGH) F3, (MEDIUM) F2 , (LOW) F1 and A (AUTO).
HUMIDITY CONTROL
This button allows you to adjust the humidity to suit your needs.
This humidifier will automatically cycle on and off as required to
maintain the selected setting.
The readout displays both actual (ROOM) and desired (SET)
humidity percentage (%) settings when humidity control button is pressed. The ROOM
readout has a range of 20% to 95% RH. If the room humidity level is equal to or less
than 20% RH the display will show a flashing 20.
The SET readout has a range of 25% to 65% RH and is adjusted in increments of 5%.
Initially depressing the humidity button will display the current humidity setting. Each
additional press of the button increases the setting by 5%. A SET point of 65% RH
operates the humidifier continuously regardless of the ROOM reading. The humidistat
that senses the readings is located on the power cord. Insure that it is free from
obstruction.
REFILL DISPLAY
For maximum run time both the bottle and the base should be filled.
When both the bottle and the base are empty, the display alternates
the room humidity reading and “F” (FILL), indicating additional
water is required.
CHECK FILTER INDICATOR
The ability of any humidifier to efficiently supply humidity output
relies heavily on the condition of the wick (filter). As the wick loads
with impurities it gradually loses its wicking capability. When this
happens, moisture output is reduced and the humidifier has to work
longer to satisfy the selected setting. This humidifier has a check
filter reminder timed to appear after 720 hours of operation. When the display shows
an alternating “CF” and “room humidity” setting at 5 second intervals it is a reminder to
check the filter (wick) condition.
NOTE: Some areas have high water mineral content causing the need for more
frequent wick changes.
Reset the Check Filter “CF” function each time you replace a wick by unplugging the
unit from the power source for 1-2 minutes, then plug it in again.
Refer to “Replacement of Wick” section below. If a build-up of deposits or severe
discoloration is evident, replace the wick to restore maximum efficiency.
CONTROL LOCK FEATURE
To avoid unwanted tampering with the humidifier settings the
controls can be locked.
CONTROL LOCK ACTIVATION PROCEDURE
After the humidifier functions have been set up, hold the power
button down for 5 seconds. The display will show “CL” for 2 seconds; release the
power button and the control will resume the display of the room humidity. The
humidifier will continue to function with the locked in settings. If buttons are operated
while “CL” is active, the “CL” is displayed and settings are unaffected.
8
CONTROL LOCK DEACTIVATION PROCEDURE
To deactivate the “CL” function simply press and hold the power button for 5 seconds.
“CL” will flash at the rate of 1 second on and 1 second off for a period of 2 seconds
and then resume the display of room humidity.
MANUAL DRY OUT
Center Back of Cabinet
At the end of the
humidification season or if
you do not plan to run the
humidifier for one week or
more, a manual dry out
mechanism is provided to
completely dry out the
humidifier cabinet. To do
this, simply slide the float
retainer clip located at the
back of the humidifier
Fasten float
retainer clip
into top section
of middle slot
for manual dryout
Float with retainer clip
(reference)
For normal
operation,
float retainer clip
should be in
bottom section
of middle slot.
cabinet to the top of the middle slot,
as it is shown in the illustration. This will
hold the float in an upward position and the fan will run until you turn the power off.
NOTE: Be sure to reposition float retainer to the normal operating position (lowest
portion of the slot) before using the humidifier again. See diagram for proper
placement of the float retainer in the float retainer slot in the cabinet back.
REPLACEMENT OF WICKS
WARNING: To reduce the risk of shock or injury from moving parts, always unplug
humidifier before removing or replacing any parts.
NOTE: This unit uses model HDC12 wicks. Replace the wick at the beginning of each
season, and more often in areas with hard water. The wicks may be rinsed periodically
in clear water only. Take care not to damage paper. To replace evaporative wicks in
your humidifier, follow these instructions.
WICK REPLACEMENT
1. Unplug humidifier before removing the wick. We recommend moving the
humidifier to an area where floor coverings are not susceptible to water
damage, i.e. kitchen or bath areas.
2. Open the pivoting lid andremove water
bottle s and set aside. Grasp the fan
assembly front center and rear center.
Left off and set aside on a clean flat
surface. The wick housings are now
accessible.
3. Lift wick housing out of cabinet and
place where you may work on them
comfortably. With a soft, absorbent
cloth remove any remaining water or
loose mineral deposits not trapped in
the wick from the humidifier cabinet.
9
F
R
O
N
T
F
R
O
N
T
4. To open wick housing for easy access to wciks:
Wick Housing Assembly
a. Deflect the two spring tabs on top of wick
housing. Lift top cover off of the wick
housing and set aside.
b. Remove the two wicks and dispose of
FR
O
N
T
properly. Clean internal parts of humidifier
per the “Care and Maintenance” section
(page 11-12) of your operator’s manual.
c. Install new wicks in the wick housing track
Separate Upper and Front
Wick Housings
with the glue beads of the wicking pad to the
inside of the wick housing.
d. Return the top cover of the wick housing by
installing cover over the fixed tabs on the
rear of the lower wick housing and pivoting
the cover down over the top of the wicks.
Snap the cover over the two spring tabs.
e. Replace the wick housing in the cabinet.
Remove Used Wicks and
Replace with New Wicks
NOTE: There is a front and back orientation.
To position the wick housings correctly:
• Be sure that the spring tabs of wick
housings are towards front of cabinet.
• Align the lower portion of the wick
assembly over the six ribs located at the
bottom rear of the humidifier cabinet.
Reassemble Wick Housing
f. Position fan assembly onto the cabinet.
Make sure the fan venturi (lowest cylinder
section below the fan) is placed inside the
wick housing.
g. Replace water bottles.
h. Close the pivoting lid.
i. The unit is ready for use or to be stored
away for next season.
Reinstall Top Onto Cabinet
Flat Portion of Wick Housing
Towards Back of Cabinet
Wick
FRONT
Spring Tabs Toward Front of Cabinet
Water Bottle Placement
Left
FR
O
N
T
FRONT
Right
FRONT
10
CARE AND MAINTENANCE
Cleaning your humidifier regularly helps eliminate odors and bacterial and
fungal growth. Ordinary household bleach is a good disinfectant and can be used to
wipe out the humidifier base and bottle/reservoir after cleaning .We recommend
cleaning your humidifier at least once every two weeks to maintain optimum
environmental conditions for your home. We also recommend using AIRCARE
Essick Air
®
Bacteriostat Treatment each time you refill your humidifier to
®
or
eliminate bacterial growth. Add bacteriostat according to the instructions on the
bottle. Please call 1-800-547-3888 to order Bacteriostat Treatment, part number1970.
CLEANING INSTRUCTIONS
WARNING: To reduce the risk of injury, fire or damage to humidifier, use only
cleaners specifically recommended for humidifiers. Never use flammable,
combustible or poisonous materials to clean your humidifier. To reduce the risk
of scalds and damage to humidifier, never put hot water in humidifier.
CAUTION: Local water purity varies from area to area and under certain
conditions water impurities and airborne bacteria may promote the growth of
microorganisms in the reservoir of the humidifier. To reduce bacteria growth that may
cause odors and be harmful to your health, use only HDC12 replacement wicks. We
also recommend using EPA approved bacteriostat, and humidifier cleaner, available
at your local retailer.
NOTE: If it is necessary to use approved bacteriostat, follow directions correctly.
Each bottle of the whole house humidifier holds 2.375 gallons/9 litres of water.
STEP 1:
To make cleaning easier, the humidifier cabinet should be empty and completely
dried out. To accomplish this, use the following method:
a) On the back side of the humidifier cabinet, find the float retainer. In normal
operating mode, the retainer will be positioned in the bottom of the slot in the
cabinet. Push the retainer up to the top slot position in the cabinet until it locks in
place. (See “Manual Dryout” section on page 9.)
b) Allow the humidifier to run until there is no water left in the cabinet.
c) Unplug humidifier.
WARNING: To reduce the risk of shock, always unplug humidifier before cleaning or
servicing. If humidifier is not unplugged, fan could start after housing is removed.
STEP 2:
TO REMOVE PARTS
a) Open the pivoting lid, remove water bottles and set aside. Grasp the fan assembly
front center and rear center. Lift off and set aside on a clean flat surface. The wick
housings are now accessible.
b) Before removing the internal parts of the humidifier cabinet, we recommend
moving the humidifier to an area where floor covers are not susceptible to water
damage, i.e.; kitchen or bath area. Lift the wick housing assemblies out of the
cabinet and set to the side.
c) Remove the water level float from the humidifier cabinet by pinching the float
retainer to release it from the cabinet. The cabinet should be empty before
cleaning. The cabinet consists of the lower areas of the humidifier where the
wicks are during normal operation time.
d) Empty cabinet of any remaining water.
e) Proceed to “Bi-Weekly Maintenance” or “End of Season Maintenance”.
11
STEP 3:
Install new wicks (use only HDC12 wicks) into the location where the old wicks were
positioned. Install the wick housings with the new wicks into the correct location.
Reinstall the water level float.
NOTE: Float retainer should be positioned in normal operating mode .Ensure that it is
positioned in the bottom of middle slot. (See diagram on page 9.)
Position the fan assembly on top of the cabinet and return the humidifier to the desired
location for use. Refill humidifier bottles with fresh cool water and return them to the
cabinet. Plug the unit into a 120 volt A.C. power outlet and set the controls per the
“CONTROLS AND OPERATION” section (page 7) of this manual.
REMOVING SCALE
1. Fill the reservoir with water and add one 8 oz. (236 ml) cup of white vinegar. Let
solution stay for 20 minutes.
2. Clean all interior surfaces with soft brush. Dampen soft cloth with white vinegar and
wipe out reservoir to remove scale.
3. Rinse thoroughly with clean warm water to remove scale and cleaning solution
before disinfecting the reservoir.
DISINFECTING UNIT
4. Fill humidifier cabinet with 1 teaspoon (5 ml) chlorine bleach in 1 gallon (3.8 litres) of
water. Let solution stay for 20 minutes, carefully swishing every few minutes. Wipe
down all surfaces normally exposed to water.
5. Empty humidifier cabinet after 20 minutes. Rinse with water until bleach smell is
gone. Allow unit to dry out completely.
6. Water bottles should be cleaned in the same manner.
DISINFECTING BASE
7. Pour 1/2 gallon (1.89 litres) of water and 1/2 teaspoon (2.5 millilitres) chlorine bleach
into the base. Let solution stay for 20 minutes, carefully swishing every few minutes.
Wipe down all surfaces normally exposed to water.
8.
Empty base after 20 minutes. Rinse with water until bleach smell is gone. Allow unit
to dry out completely
SUMMER STORAGE
1.
Clean unit as outlined in Care & Maintenance section.
2. Discard used wick and any water in the reservoir. Do not discard wick retainer. Allow
to dry thoroughly before storage. Do not store with water inside reservoir.
3. Do not store unit in an attic or other high-temperature area, as damage is probable.
4. Install new wicks at beginning of season.
12
Troubleshooting
Trouble Probable CauseRemedy
Digital display not
illuminated.
Fan not operating
(digital display is
illuminated).
Fan running
continuously.
Poor evaporation of
water.
Neither bottle
emptying.
Bottles continue to
empty after complete
filling.
• No Power.
• Power button has not
been depressed.
• ROOM humidity level is
not 3% or more below
SET humidity level.
• Reservoir is empty.
• Float is obstructed.
• SET humidity level is
65%.
• ROOM humidity level
has not reached 1% or
more above SET
humidity level.
• CHECK FILTER (CF)
message flashing.
• Mineral buildup on filter
(wick).
• Bottle cap plunger
missing post in bottom of
cabinet
• Dirty wicks.
• Air is entering water
bottle.
• Check 120 volt power source.
• Press power button once to
turn on.
• Raise SET humidity level if desired.
• Increase fan speed.
• Fill humidifier with water.
•Free float from obstruction.
• A SET humidity percentage of 65%
operates fan continuously. Adjust
SET level between 25% - 60%.
• Continue to run until desired
humidity level is achieved. This
may take up to 48 hours initially.
• Change to a fresh new wick
NOTE: Local water varies from area
to area and under certain conditions
minerals will build up more rapidly in
the wick.
•Unplug unit for 1-2 minutes to reset
CF function
• Check orientation of bottles.
Reposition so that bottle cap
plunger (stem) is depressed by
post in bottom of cabinet.
• Change to fresh new wick
(HDC12).
•Check “Side-Fill Caps” and valve
assembly caps to ensure tightness.
• Check for leak in water bottle.
• Ensure gaskets for “Side Fill Caps”
are in place.
Left bottle not
emptying.
Bottle empties
completely
Refill display “F” is on
before bottles are
empty.
“CF” message does
not appear even when
wick is dirty or
humidifier performance
is clearly reduced.
Display blinks or fan
moves slightly when
humidifier is plugged in.
• Right bottle contains
water.
• This is normal for initial
filling
• Unit is not set up on a
level surface. (Float
will not sense water at
the front of the
cabinet.)
• Loss of power or a
power failure has caused
the CF message to
prematurely reset.
Normal • No action required.
•The humidifier is designed so that
right bottle empties first.
• Ensure unit is level - Install caster
pads on front casters, as needed.
• Refill bottle for maximum
run time.
•Position unit level. (Some carpet
padding may allow unit to sit lower in
the front than rear with the additional
weight of water bottles in the front of
the cabinet. Install caster pads under
front casters (see page 5).
• Replace wick.
13
Troubleshooting (con’t)
Trouble Probable CauseRemedy
Alternating “F” and
room humidity
displayed.
Alternating “CF” and
room humidity
displayed.
Controls are
unresponsive or CL is
displayed
CAUTION: Use only EPA Registered Bacteriostat.
Use of other water treatment products may damage the filter elements and void warranty. Under
no circumstances should you use water treatment products designed for Rotobelt or Ultrasonic
humidifiers.