ERICO SIM Series 7m Stainless Steel Guyed Mast User Manual

INSTRUCTION SHEET
®
ERICO DYNASPHERE MKIV
Installation Instructions for 7m Stainless Steel Guyed Mast - SIM Series
Mast Detail
ERICO DYNASPHERE
®
(ERICO Part # D/SMKIV-SS) INTCPT ADAPTER
(ERICO Part # INTCPTMIDYN)
Stainless Steel Mast (ERICO Part # SIM28A2)
1
-
(ERICO Part # TMCSS)
Guy Kit (ERICO Part # GUYKIT4M/GRIP) Do not over-tension guy wires (Slightly sagging)
Stainless Steel Mast (ERICO Part # SIM33B3)
Stainless Steel Mast (ERICO Part # SIM40C2)
Stainless Steel Mast Base (ERICO Part # SIMBASE2840) Refer to Detail "B"
Preferred Angle 45° - 60°
1
Not to Scale
-
SIM28A2
SIM33B3
SIM40C2
SIMBASE2840
TMCSS Mast Clamp Installing contractor to field adjust and insure a secure bond on highest SIM series mast
Downconductor
(ERICO Part # TCEC253) Copper Tape
(ERICO Part # PDCUC) Tape Fasteners
2
Typical Conductor Connection
-
Not to Scale
Detail "B"
4 HOLES, Ø11mm
170mm
200mm
Stainless Steel Cable Tie (ERICO Part # CABTIESS) Three every 1m
For complete grounding system refer to Detail "A"
2
-
Detail "A"
Two downconductors
Lightning Event Counter (ERICO Part # LECIV)
Downconductor
are required
®
Lightning Event Counter Refer to installation manual
ERICO CADWELD Connection or mechanical connection
for alternate locations (ERICO Part # LECIV)
Ground Inspection Well
Crow's Foot
(ERICO Part # GF302) 3m tape enclosed in GEM material
Minimum 16mm X 2.4m long ground rod in four locations
Suggested triangular grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench approximately 0.8m deep. The conductor is laid in the trench and is connected to ground rods. The conductor in each trench is encased in GEM material. Ground rods must extend 3m below ground level.
Note: This is one of several alternative installation methods. Refer to ERICO installation manual for more details.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2. All instructions must be
3. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4. damage, serious bodily injury and death.
and from your ERICO customer service representative.
completely
followed to ensure proper and safe installation and performance.
®
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT
www.erico.com
IP79151_A
1 OF 1
© 2014 ERICO International Corporation.
Loading...