ERICO SBC User Manual

INSTRUCTION SHEET
SBC Series
Beam Clamp, 3/8" and M10
Allows structural
attachment to metal
beams, bar joist,
channel, or angle iron in
top mount position only
unless used on a parallel
flange.
Figure 1
retaining strap
(Sold separately)
1
ARROW ALWAYS POINTING UP
On tapered flange, clamp is to be mounted in top position only.
3
2
On parallel flange, clamp may be top or bottom mounted in this orientation.
Installation Instructions:
Figure 2
Installation:
Install beam clamp
1. Place strap over
2. loaded rod Secure with nut
3. Use hammer to bend
4. strap around beam
Part
Number
SBC037
SBCM10
Position Clamp on top flange of beam per
1. Figure 2.
Tighten screw. Set screw must be tightened to
2. sloped side of I-beam, channel or angle iron flange and torqued to the value specified in the chart below. Tighten set screw jam nut.
Insert threaded rod (not included) into
3. threaded hole and adjust to desired height.
Clamp must not be secured in reverse position.
Figure 3
4. See figure 3 for incorrect mounting positions.
Incorrect mounting
configurations.
Model
SBC
SBC
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2. All instructions must be
3. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4. damage, serious bodily injury and death. Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.
5. All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any
6. other purpose.
NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for: a. Conformance to all governing codes. b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified engineer. c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
Top Mount Beam Clamp to secure
and from your ERICO customer service representative.
Description
threaded rod to structure.
completely
followed to ensure proper and safe installation and performance.
Max. Pipe Dia. Supported by
Clamp & Threaded Rod
Note: Threaded rod is not included.
Min. Set
Screw
Torque
60 in-lbs
60 in-lbs
4 inches
4 inches
Rod Size
3/8 in
M10
Maximum
Recommended Load
500 lbs
500 lbs
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT: