ERICO PEC Series Potential Equalization Clamp User Manual

INSTRUCTION SHEET
Potential Equalization Clamp (PEC Series)
WARNING:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
www.erico.com
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
CADDY, CADWELD, CRITEC, ERICO, ERITECH, ERIFLEX, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT
www.erico.com
and from your ERICO customer service representative.
completely
IP8108_A
1 OF 2
©2013 ERICO International Corporation
INSTRUCTION SHEET
Potential Equalization Clamp (PEC Series)
Purpose:
In communications and computer installations it is not uncommon to install separate ground systems for lightning, mains power, computer (quiet ground), and communications (for security, and tempest requirements). Although this approach may be desirable for certain operating reasons, when lightning or other transient voltages occur, differences in ground potentials between the ground electrodes are inevitable and equipment damage can result.
The Potential Equalization Clamp (PEC) is an isolation spark gap that is designed to help prevent ground potential differences by operating under transient conditions to effectively clamp the grounds together. Normally the PEC presents an effective open circuit. Once the ground potential difference exceeds the breakdown voltage of the PEC, the circuit immediately closes and the ground potentials are equalized. The PEC is fully resettable and has a life of over ten thousand operations.
Many buried pipelines are protected from corrosion by cathodic protection systems. To maintain the insulation integrity of the pipe at metering and telemetry stations, insulating joints are inserted into the pipe and those sections between insulating joints are grounded at the station. With long lengths of pipelines, induced voltages in the pipe caused by local lightning or power line faults activity can be in the order of tens of kilovolts. The result is that insulated joints failure is almost inevitable, with flange type insulated joints particularly susceptible.
To help protect against insulated joint break-down, the PEC can be connected directly across the joint. In its inactive state the PEC presents an effective open circuit across the joint. Should the insulated joint voltage start to rise due to transients, the PEC will conduct and safely pass the transient current to ground, limiting the voltage stress across the joint. After conduction the PEC will automatically reset to its inactive state.
Installation:
· Installation and/or replacement of a PEC should only be carried out by qualified personnel
· The product must be installed in compliance with all national regulations and conditions
· The PEC may be damaged if exposed to lightning discharges in excess of rated values
· Unauthorized tampering or opening of the PEC is not permitted and invalidates the warranty
Markings: