ERICO MBNC240A User Manual

INSTRUCTION SHEET
Bonding Network Connector
MBNC82, MBNC240 and MBNC240A
Part #
MBNC82
MBNC240
MBNC240A
1. Stranded conductors #8 - #2 AWG: 7 or 19 strands
2. Solid Conductors: #2 AWG; Stranded Conductors #2 AWG 7 or 19 strands, #1 - 4/0 AWG: 7, 19 or 37 strands
Conductor Type
Solid, Stranded
Solid, Stranded
Solid, Stranded
Size
1
2
2
8 - 2 AWG
2 - 4/0 AWG
2 - 4/0 AWG
MBNC82
MBNC240
(Configurations for reference only)
CORRECT
INCORRECT
(MBNC82 Only) (MBNC82 Only)
MBNC240A
MBNC82, MBNC240 and MBNC240A Installation:
Using a 5/8" deep well socket, torque nuts to 150 in-lbs [17 N-m].
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2. All instructions must be
3. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4. damage, serious bodily injury and death.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
and from your ERICO customer service representative.
completely
followed to ensure proper and safe installation and performance.
MBNC240A attached to a metal plate
(Reference only)
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT
www.erico.com
IP8175_C
1 OF 1
© 2010, 2012 ERICO International Corporation.
Loading...