INSTRUCTION SHEET
ECLA
Installation Tooling for Dual Rated Aluminum Connectors
Select proper lugs or splice connector for the size of cable being installed, make sure
1.
that the size matches the description in the table below.
Strip the insulation from the conductor to a length so that the stripped area of the
2.
conductor can be completely inserted into and fill the barrel of the lug or splice.
Carefully strip the insulation from the conductor without nicking the strands.
Wire brush the stripped portion of the conductor to remove oxide films.
3.
The stripped portion of the conductor must be clean and inserted completely into
4.
the connector barrel.
Using the tool and die combination specified for that in the table below, install 5.
crimps, leaving a space of 1/8" maximum between successive crimps unless
overlapped to fill the connector barrel at the referenced location illustrated.
Global Part No.
---
ECLA6S14
ECLA4S14, ECLA4S516
ECLA2S14, ECLA2S38
ECLA1S38, ECLA1S516
ECLA1/0S38
ECLA2/0S12
ECLA3/0S12
ECLA4/0S12, ECLA4/0S14,
ECLA4/0S38, ECLA4/0S58,
ECLA4/0S516
ECLA250S516,
ECLA250S12, ECLA250S38,
ECLA250S58
ECLA300S12
ECLA350S12
ECLA400S12
ECLA500S12
ECLA600S58
ECLA750S58
Cable Size
8 AWG
6 AWG
4 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 MCM
300 MCM
350 MCM
400 MCM
500 MCM
600 MCM
750 MCM
Die Color
Blue
Gray
Green
Pink
Gold
Tan
Olive
Ruby
White
Red
Blue
Brown
Green
Pink
Black
Yellow Red
Burndy® Y35
Die Sets
U8CABT
U6CABT
U4CABT
U2CABT
U1CART
U25ART
U26ART
U27ART
U28ART
U29ART U28ART
U30ART
U31ART
U32ART
U34ART
U36ART
U39ART
Burndy® Y35
Die Sets for
Smooth Weave
---
---
---
---
---
---
---
---
U28RT
---
---
---
---
---
---
Die Index
374
346
375
348
471
296
297
467
298
324
470
299
472
300
473
936
Lug
Splice
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be
3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and death.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
Burndy is a registered trademark of Hubbell Incorporated.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT
www.erico.com
and from your ERICO customer service representative.
completely
followed to ensure proper and safe installation and performance.
IP8242_B
1 OF 1
© 2012, 2013 ERICO International
Corporation.