Epson HWDV080DV User Manual

INSTALLATION
GAS-FIRED
INSTRUCTIONS AND
OWNER'S MANUAL
DIRECT VENT
WALL FURNACE
STANDARD MODELS:
HWDV080DV(N,P)-1 HWDV181DV(N,P)-1
MODELS WITH BLOWER:
HWDV080BDV(N,P)-1 HWDV181BDV(N,P)-1
Installer: Leave this manual with the ap-
pliance.
Consumer: Retain this manual for future
reference.
WARNING: If the information in these in­structions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flam-
mable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed
by a qualified installer, service agency or the gas supplier.
This appliance may be installed in an after­market, permanently located, manufactured home (USA only), or mobile home, where not prohibited by state or local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
Page 1
TABLE OF CONTENTS
SECTION PAGE
Included in the Box .................................................................................................. 3
Hardware Packets ....................................................................................................
Tools Needed .............................................................................................................
Gas Specifications ....................................................................................................
Specifications ............................................................................................................
High Altitude Specifications ....................................................................................
4 4 5 5
5
Unit Dimensions ....................................................................................................... 6
Important Safety Information ................................................................................ 7
Safety Information for Users of LP-Gas ................................................................
Introduction ..............................................................................................................
Requirements for Massachusetts ..........................................................................
8
9
10
Termination Clearances ......................................................................................... 11
Gas Supply ......................................................................................................... 12-13
Clearances ............................................................................................................... 13
Installation Instructions Overview ....................................................................... 14
Installation and Assembly ................................................................................
Interior Preparation and Installation of the Back of the Unit ......................
15-16
17-19
Interior Installation of the Front of the Unit .......................................................
Cutting the Vent Tubes .....................................................................................
Exterior Installation of the Venting .................................................................
Reassembly and Resealing Vent-Air Intake System ......................................
Installation of Optional Blower Kit HW125SCB ...........................................
Before Operating Appliance .............................................................................
20 21-22 23-25 26-28 29-32 33-36
Operating Instructions .......................................................................................... 37
Lighting Instructions ............................................................................................. 38
To Turn Off Gas to Appliance ...............................................................................
38
Pilot Flame Characteristics ................................................................................... 39
Main Burner Flame Characteristics ....................................................................
39
Maintenance Instructions ...................................................................................... 40
Troubleshooting ......................................................................................................
How To Order Repair Parts ..................................................................................
41
41
Parts List ............................................................................................................ 42-43
Parts View ...............................................................................................................
44
Service Notes ...................................................................................................... 45-47
24632-0-0508Page 2
INCLUDED IN THE BOX
DIRECT VENT HEATER
(INSIDE WALL MOUNTING PLATE
AT
TACHED ON BACK)
INLET & OUTLET TUBES
INSTALLATION TEMPLATE
(TEMPLATE FOR HWDV080
ON REVERSE SIDE)
OUTSIDE WALL MOUNTING PLATE
& VENT CAP
VENT KIT
HARDWARE PACKET
VENT SHIELD
HEATER
HARDWARE PACKET
24632-0-0508 Page 3
SNIPS
5/16 NUT DRIVER
ADJUSTABLE WRENCH
CAULKING
PHILLIPS SCREW DRIVER
TAPE MEASURE
DRILL
SA
W
HARDWARE PACKETS
PLASTIC TOGGLE (6)
#10 X 1 ” SLOTTED HEX HEAD SCREW (6)½
NYLON WASHER (2)
#10 X ½” PHILLIPS HEX HEAD SCREW (3)
#10 X 2 ½” HEX HEAD SCREW (4)
HEATER
HARDWARE PACKET
VENT KIT
HARDWARE
PACKET
TOOLS NEEDED
24632-0-0508Page 4
GAS SPECIFICATIONS
MODEL FUEL MAXIMUM INPUT MINIMUM INPUT
HW080
HW181 18,000 Btu/hr
MANIFOLD PRESSURE
Gas Inlet 3/8"
SUPPLY
Natural Gas 5" W.C.P. 10.5" W.C.P.
LP Gas 11" W.C.P. 13" W.C.P.
Note: Appliance input ratings are based on sea level operation and need not be changed for operation up to 2,000 feet.
Propane/LP -- Natural gas
Propane/LP gas: 10.0" water column pressure
MINIMUM PRESSURE MAXIMUM PRESSURE
8,000 Btu/hr 5,000 Btu/hr
9,000 Btu/hr NAT
9,500 Btu/hr LP
Natural gas: 4" water column pressure
SPECIFICATIONS
MODELS HWDV080(B)DV HWDV181(B)DV
COMBUSTION
STANDARD HEATING SPACE
HEIGHT 21 11/16" 25 3/16"
EXTERNAL DIMENSIONS INCHES
NET WEIGHT LBS.
MAX. GAS CONSUMPTION
SAFETY DEVICES
Warning: This direct vent wall furnace is equipped for Natural or Propane gas. Field conversion is not permitted.
WIDTH 18 5/16" 22 5/16"
DEPTH 8 7/8" 9 3/8"
ATMOSPHERIC BURNER
85 - 250 Sq. Ft. 169 - 529 Sq. Ft.
33.5 45.5
8,000 Btu/hr. 18,000 Btu/hr.
Safety valve (thermocouple)
HIGH ALTITUDE SPECIFICATIONS
For altitudes/elevations above 2,000 feet (610 m), input ratings should be reduced at the rate of 4% for each 1,000 feet (305 m) above sea level. Canadian High Altitudes for locations having an elevation above mean sea level between 2,000 feet (609.9 m) and 4,500 feet (1,370 m), use orifices as indicated in the following table:
0 - 2,000 feet (0 - 610 m) 2,000 - 4,500 feet (610 - 1 370 m)
Model
HW080 #55 (4") #66 (10") #1.27 mm (4") #67 (10")
HW181 #49 (4") #56 (10") #50 (4") #57 (10")
24632-0-0508 Page 5
Main Burner Orifice/Gas Pressure Main Burner Orifice/Gas Pressure
Natural Gas LP Gas Natural Gas LP Gas
UNIT DIMENSIONS
MAKE SURE THAT APPLIANCE IS SUITABLE FOR THE GAS SUPPLY AVAILABLE:
NATURAL GAS OR PROPANE/LP.
24632-0-0508Page 6
IMPORTANT SAFETY INFORMATION
Children and adults should be alerted to the haz­ards of high surface temperatures and should stay away to avoid burns or clothing ignition.
Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
Do not use this heater if it has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
Young children should be carefully supervised when they are in the same room as the heater.
Installation and repair should be done by a quali­fied service person. Heater should be inspected be­fore use and at least annually by a qualified service person.
More frequent cleaning may be required due to ex­cessive lint from carpeting, bedding material etc. It is imperative that control compartments, burners, and circulating air passageways of the appliance be kept clean.
Follow State and Local codes for installation.
DO NOT put anything around or on top of the fur­nace that will obstruct the flow of combustion and ventilation air. DO keep the appliance area clear and free from combustible material, gasoline and other flamma­ble vapors and liquids. DO examine venting system periodically and re­place damaged parts. DO make a periodic visual check of pilot and burn­ers. Clean and replace damaged parts. CAUTION: Pilot hole cover must be kept tightly closed during operation.
Vent cap hot while furnace is in operation.
24632-0-0508 Page 7
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until firefighters declare them to be safe.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must find out if you can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some circumstances. For example, if there is an underground leak, the movement of the gas through soil can filter the odorant. Odorants in LP-Gas also are subject to oxidation. This fading can occur if
with the members of your household. Someday when there may not be a minute to lose, everyone's safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.
• Use your neighbor's phone and call a trained LP-Gas service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.
Finally, let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
SOME POINTS TO REMEMBER
Learn to recognize the odor of LP-gas. Your local LP-Gas Dealer can give you a "Scratch and Sniff" pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gas system. If you are qualified, consciously think about the odor of LP-Gas prior to and while lighting pilot lights or perform ing service or making adjustments.
Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed
to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question about the gas odor, call your LP-gas dealer. A periodic sniff test of the LP-gas is a good safety measure under any condition.
If, at any time, you do not smell the LP-Gas odorant and you
-
think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
If you experience a complete "gas out," (the container is un der no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.
-
24632-0-0508Page 8
INTRODUCTION
Always consult your local Building Department regarding regu lations, codes or ordinances which apply to the installation of a direct vent wall furnace.
Instructions to Installer
1. Installer must leave instruction manual with owner after instal­lation.
2. Installer must have owner fill out and mail warranty card sup­plied with furnace.
3. Installer should show owner how to start and operate furnace and thermostat.
Warning: Any change to this furnace or its control can be danger ous. This is a heating appliance and any panel, door or guard removed for servicing an appliance must be re­placed prior to operating the appliance.
General Information
This furnace is design certified in accordance with American Na­tional Standard/CSA Standard Z21.86 and CSA 2.32 by Under­writers Laboratory as a direct vent wall furnace to be installed according to these instructions.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and com pany making the change.
Notice: During initial firing of this unit, its paint will bake out and
smoke will occur. To prevent triggering of smoke alarms, venti­late the room in which the unit is installed.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less than 18" above the floor. Such equipment shall be located, or protected, so it is not subject to physical damage by a moving vehicle.
-
Qualified Installing Agency
­Installation and replacement of gas piping, gas utilization equip­ment or accessories and repair and servicing of equipment shall be performed by a qualified agency. The term “qualified agency” means any individual, firm, corporation or company which either in person or through a representative is engaged in and is respon­sible for (1) the installation or replacement of gas piping or (2) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority hav­ing jurisdiction.
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Mas sachusetts. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/
NFPA 54* Natural Gas and Propane Installation Code, CSA B149.1.
*Available from the American National Standards Institute, Inc., 11 West 42nd St.,
New York, N.Y. 10036.
The vent terminal of a direct vent appliance, with an input of 10,000 Btu per hour (3 kW) or less shall be located at least 6" (150 mm) from any air opening into a building, and such an ap-
-
pliance with an input over 10,000 Btu per hour (3 kW) but not over 50,000 Btu per hour (14.7 kW) shall be installed with a 9" (229 mm) vent terminal clearance and the bottom of the vent ter­minal and the air intake shall be located at least 12" (305 mm) above grade.
WARNING: The nearest point of the vent cap should be a minimum horizontal distance of six (6) feet (1.8 m) from any pressure regulator. In case of regulator malfunction, the six (6) feet (1.8 m) distance will reduce the chance of gas entering the vent cap.
-
24632-0-0508 Page 9
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the fol­lowing requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
(a) In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
(b) In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be per manently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC­TIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equip­ment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIP
MENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation
-
1. Detailed instructions for the installation of the vent-
2. A complete parts list for the venting system design
(e) A copy of all installation instructions for all Product Ap
of the equipment and the venting system shall include:
ing system design or the venting system components; and
or venting system.
proved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instruc­tions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
-
-
-
24632-0-0508Page 10
TERMINATION CLEARANCES
Description US Installations
1
A Clearance above grade, veranda, porch, deck, or balcony 12 inches (305 mm)
B Clearance to window or door that may be open
6 inches (152 mm) for appliance ≤ 10,000 Btuh (3 kW), 9 inches (229 mm) for appliances > 10,000 Btuh (3 kW) and ≤ 50,000 Btuh (15 kW), 12 inches (305 mm) for appliances > 50,000 Btuh (15 kW)
C Clearance to permanently closed window *
D Vertical clearance to ventilated soffit located above the
* terminal within a horizontal distance of 2 feet (610 mm) from the center line of the terminal
E Clearance to unventilated soffit *
F Clearance to outside corner 24"
G Clearance to inside corner 24"
H Clearance to each side of center line extended above me-
* ter/regulator assembly
I Clearance to service regulator vent outlet *
J Clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other appliance.
6 inches (152 mm) for appliance ≤ 10,000 Btuh (3 kW), 9 inches
(229 mm) for appliances > 10,000 Btuh (3 kW) and ≤ 50,000 Btuh
(15 kW), 12 inches (305 mm) for appliances > 50,000 Btuh (15 kW)
K Clearance to a mechanical air supply inlet 3 feet (914 mm) above if within 10 feet (3.04 m) horizontally
L Clearance above paved sidewalk or paved driveway lo-
* cated on public property
M Clearance under veranda, porch, deck, or balcony. *
The minimum distance from the center of the outside vent to the nearest inside and outside corner or obstruction or overhang is 24" (457 mm).
1
In accordance with current ANSI Z223.1/NFPA 54, National Fuel Gas Code
*
For clearances not specified in ANSI Z223.1/NFPA 54
or CSA B149.1, one of the following shall be indicated: a) A minimum clearance value determined by testing in accordance with section 2.19.6, or; b) A reference to the following footnote: “Clearance in accordance with local installation codes and the requirements of the gas supplier.”
24632-0-0508 Page 11
GAS SUPPLY
FLEXIBLE GAS LINE CONNECTION
RIGID GAS LINE CONNECTION
GAS SUPPLY
TEE HANDLE
FLEX TUBE
NPT NIPPLE
REGULATOR
VALVE
FLARE FITTING
FLARE SHUT OFF VALVE
CLOSE NIPPLE
TEE HANDLE
3/8 NIPPLE
REGULATOR
VALVE
NPT GAS SUPPLY
SHUT OFF VALVE
NPT UNION
Locating Gas Supply
The gas line can enter the unit either through the floor or outside wall. The gas line opening should be made at this time. Location of the opening will be determined by the position of floor joists and the valve and union used for servicing.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat. L.P. Nat. L.P.
0-10 feet
0-3 meters
10-40 feet
4-12 meters
40-100 feet
13-30 meters
100-150 feet 31-46 meters
1/2”
12.7 mm
1/2”
12.7 mm
1/2”
12.7 mm
3/4”
19 mm
3/8”
9.5 mm
1/2”
12.7 mm
1/2”
12.7 mm
1/2”
12.7 mm
1/2”
12.7 mm
5/8”
15.9 mm
3/4”
19 mm
7/8”
22.2 mm
3/8”
9.5 mm
1/2”
12.7 mm
1/2”
12.7 mm
3/4”
19 mm
Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended: — ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
Figure 1
CGA-B149 (.1 or .2) installation code.
Method of Installing a Tee Fitting Sediment Trap
Figure 2
24632-0-0508Page 12
GAS SUPPLY (continued)
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.
2. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
Attention! If one of the above procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.
CLEARANCES
Checking Manifold Pressure
Both Propane and Natural have a pressure regulator attached to the gas valve. Natural gas models will have a manifold pressure of approximately 4.0" w.c. (.996 kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 5.0" w.c. (1.245 kPa) for the purpose of input adjustment to a maximum of
10.5" w.c. (2.61 kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49 kPa) at the valve outlet with the inlet pressure to the valve from a minimum of
11.0" w.c. (2.739 kPa) for the purpose of input adjustment to a maximum of 13.0" w.c. (3.237 kPa).
A 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the side of the gas pressure regulator.
1. In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation.
2. Unit is supported by a wall bracket secured to the wall.
3. The minimum clearances from casing to combustible construction is 36" (914.4 mm) on top, 6" (152 mm) on each side and 4" (102 mm) from the floor or from the top surface of carpeting, tile or other floor covering and 0" (0 mm) to rear wall.
4. The minimum distance from the center of the vent cap to the nearest outside corner or obstruction is 24" (610 mm).
5. The minimum wall depth is 4 1/2" (114.3 mm) and the maximum is 12" (304.8 mm). The use of tubes not supplied by the manufacturer results in unsatisfactory performance.
The vent terminal of a direct vent appliance, with an input of 50,000 (14.6 KW) BTU per hour or less shall be located at least 9" (229 mm) from any opening through which flue gases could enter a building. The bottom of the vent terminal and the air intake shall be located at least 12" (305 mm) above grade.
The vent terminal of a direct vent appliance, with an input of 10,000 Btu per hour (3 kW) or less shall be located at least 6" (150 mm) from any air opening into a building, and such an ap­pliance with an input over 10,000 Btu per hour (3 kW) but not over 50,000 Btu per hour (14.7 kW) shall be installed with a 9" (229 mm) vent terminal clearance and the bottom of the vent ter­minal and the air intake shall be located at least 12" (305 mm) above grade.
WARNING: The nearest point of the vent cap should be a minimum horizontal distance of six (6) (1.83m) feet from any pressure regulator. In case of regulator malfunction, the six (6) foot (1.83m) distance will reduce the chance of gas entering the vent cap.
24632-0-0508 Page 13
INSTALLATION INSTRUCTIONS OVERVIEW
Location - All Models
Select a location near the center of the space to be heated. Overflow heat will circulate through doorways into adjacent rooms.
The furnace is to be located on an outside wall. Locate wall studs so that wall opening will be located between wall studs. One wall stud can be used for attachment of inside wall plate. The wall opening required as shown in Figure 3 is a minimum diameter of 6 1/4" (159 mm). The inside wall plate and the outside wall plate are large enough to permit a wall opening diameter of 8" (203 mm). A template is provided in furnace carton for positioning furnace on the wall. Also, refer to Figure 3 for positioning the furnace on wall and for locating gas line connection.
For large homes or spread-out floor plans, two or more furnaces are recommended.
Do not locate furnace where a door could swing over the outer casing, or where circulation could be retarded by furniture or cabinets. See Figure 4.
Do not install in a closet, alcove or small hallway where the furnace could be isolated by closing doors to the heated space. See Figures
5 and 6.
When location is selected, check the walls to make sure there are no obstructions such as pipes, electric wiring, etc., which would interfere with the installation of the furnace or vent pipe.
See Page 18, Box 4 for dimensions.
Figure 3
Figure 4 Figure 5 Figure 6
24632-0-0508Page 14
HEATER TO BACK CASING MOUNTING SCREWS
WALL MOUNTING TA
B
WALL MOUNTING SCREWS
WALL MOUNTING PLA
TE
INSTALLATION AND ASSEMBLY
WARNING: Any change to this heater or its control can be dangerous. Provide adequate clearances and accessibility for purposes of servicing and proper operation.
A manufactured home (USA only) installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 or, when such standard is not applicable, the Standard for Manufactured Home Installations, ANSI Z225.1.
Due to high surface temperature, keep children, clothing, and furniture away. Keep burner and control compartments clean.
INSTALLATION OVERVIEW
WARNING: Improper installation, adjustments, alteration, service, or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
These wall furnace models are designed for direct venting through a wall. Only venting components approved for these furnaces may be used.
This unit is to be installed on a wall from 4 1/2" to 12" (114.3 mm to 304.8 mm) thick.
Note: All references must be considered as if the observer is standing in front of the wall and/or appliance.
1
Mark the venting system hole location (as indicated on page
18) and the six holes through the wall mounting plate. Drill accordingly. Insert the four wall anchors provided and tighten the wall mounting plate firmly. Use special anchor fasteners if the heater is to be installed on a wooden (hollow) wall. Line up the two (2) tabs on the top of the wall mounting plate with the holes in the back of the unit. Slide the back of the unit onto the tabs of the wall mounting plate. Secure the back of the unit into place using two (2) screws. Replace casing door. The heater is now ready to receive the venting system assembly from the opposite side of the wall.
Note: All references must be considered as if the observer is standing in front of the wall and/or appliance.
IMPORTANT: The venting system must be properly installed to insure proper and safe operation. The venting system must also be properly re-installed and re-sealed to insure proper and safe operation.
24632-0-0508 Page 15
Loading...
+ 33 hidden pages