A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective Earth (PE)
A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.
Communication symbols
SymbolMeaning
Wireless Local Area Network (WLAN)
Communication via a wireless, local network.
LED
Light emitting diode is off.
LED
Light emitting diode is on.
LED
Light emitting diode is flashing.
Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
Reference to page.
Reference to graphic.
Visual inspection.
4Endress+Hauser
Proline Promass Q 500
1.
-
.
213
Symbols in graphics
SymbolMeaning
1, 2, 3, ...Item numbers
, 2., 3., …Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
Hazardous area
Safe area (non-hazardous area)
Flow direction
Function and system design
Measuring principle
The measuring principle is based on the controlled generation of Coriolis forces. These forces are
always present in a system when both translational and rotational movements are superimposed.
Fc = 2 · ∆m (ν · ω)
Fc = Coriolis force
∆m = moving mass
ω = rotational velocity
ν = radial velocity in rotating or oscillating system
The amplitude of the Coriolis force depends on the moving mass ∆m, its velocity ν in the system and
thus on the mass flow. Instead of a constant rotational velocity ω, the sensor uses oscillation.
In the sensor, two parallel measuring tubes containing flowing fluid oscillate in antiphase, acting like
a tuning fork. The Coriolis forces produced at the measuring tubes cause a phase shift in the tube
oscillations (see illustration):
• At zero flow (when the fluid is at a standstill) the two tubes oscillate in phase (1).
• Mass flow causes deceleration of the oscillation at the inlet of the tubes (2) and acceleration at the
outlet (3).
A0028850
The phase difference (A-B) increases with increasing mass flow. Electrodynamic sensors register the
tube oscillations at the inlet and outlet. System balance is ensured by the antiphase oscillation of the
two measuring tubes. The measuring principle operates independently of temperature, pressure,
viscosity, conductivity and flow profile.
Endress+Hauser5
Proline Promass Q 500
2
3
1
A
B
1
2
3
Density measurement
The measuring tube is continuously excited at its resonance frequency. A change in the mass and
thus the density of the oscillating system (comprising measuring tube and fluid) results in a
corresponding, automatic adjustment in the oscillation frequency. Resonance frequency is thus a
function of medium density. The microprocessor utilizes this relationship to obtain a density signal.
Volume measurement
Together with the measured mass flow, this is used to calculate the volume flow.
Temperature measurement
The temperature of the measuring tube is determined in order to calculate the compensation factor
due to temperature effects. This signal corresponds to the process temperature and is also available
as an output signal.
Measuring system
The measuring system consists of a transmitter and a sensor. The transmitter and sensor are
mounted in physically separate locations. They are interconnected by connecting cables.
Transmitter
Two versions of the transmitter are available.
Proline 500 – digitalProline 500
For use in applications not required to meet special requirements due to
ambient or operating conditions.
ANon-hazardous area or Zone 2; Class I, Division 2
BNon-hazardous area or Zone 2; Class I, Division 2 or Zone 1; Class I,
Division 1
1Transmitter
2Connecting cable: cable, separate, standard
3Sensor connection housing with integrated ISEM
• Flexible and cost-effective separate installation.
• A standard cable can be used as the connecting cable.
• Electronics in the transmitter housing, ISEM (intelligent sensor
electronics module) in the sensor connection housing
• Signal transmission: digital
Order code for "Integrated ISEM electronics", option A "Sensor"
Connecting cable (can be ordered in various lengths)→ 116
• Length:
• Zone 2; Class I, Division 2: max. 300 m (1000 ft)
• Zone 1; Class I, Division 1: max. 150 m (500 ft)
• Standard cable with common shield (pair-stranded)
Hazardous area
Use in: Zone 2; Class I, Division 2
Mixed installation is possible:
• Sensor: Zone 1; Class I, Division 1
• Transmitter: Zone 2; Class I, Division 2
Device versions and materials
For use in applications required to meet special requirements due to
ambient or operating conditions.
Non-hazardous area or Zone 2; Class I, Division 2 or Zone 1; Class I,
Division 1
1Transmitter with integrated ISEM
2Connecting cable: cable, separate
3Sensor connection housing
Application examples for sensors without electronics:
• Strong vibrations at the sensor.
• Sensor in underground installations.
• Electronics and ISEM (intelligent sensor electronics module) in the
transmitter housing
• Signal transmission: analog
Order code for "Integrated ISEM electronics", option B "Transmitter"
• Length: max. 20 m (65 ft)
• Cable with a common shield and individual shielded cores (3 pairs)
Use in: Zone 1; Class I, Division 1 or Zone 2; Class I, Division 2
6Endress+Hauser
Proline Promass Q 500
Proline 500 – digitalProline 500
• Transmitter housing
• Aluminum, coated: aluminum, AlSi10Mg, coated
• Material: polycarbonate
• Material of window in transmitter housing
• Aluminum, coated: glass
• Polycarbonate: plastic
Configuration
• External operation via 4-line, backlit, graphic local display with touch control and guided menus ("Make-it-run" wizards) for application-specific
commissioning.
• Via service interface or WLAN interface:
• Operating tools (e.g. FieldCare, DeviceCare)
• Web server (access via Web browser, e.g. Microsoft Internet Explorer, Microsoft Edge)
Sensor connection housing
Different versions of the connection housing are available.
• Transmitter housing
• Aluminum, coated: aluminum, AlSi10Mg, coated
• Cast, stainless: cast, stainless steel, 1.4409 (CF3M) similar to 316L
• Window material: glass
Order code for "Sensor connection housing", option A, "Aluminum, coated":
Aluminum, AlSi10Mg, coated
This device version is only available in conjunction with the Proline
500 – digital transmitter.
Order code for "Sensor connection housing", option B, "Stainless":
• Hygienic version, stainless steel 1.4301 (304)
• Optional: order code for "Sensor feature", option CC "Hygienic version,
for maximum corrosion resistance": stainless steel 1.4404 (316L)
Order code for "Sensor connection housing", option C, "Ultra-compact
hygienic, stainless":
Hygienic version, stainless steel 1.4301 (304)
This device version is only available in conjunction with the Proline
500 – digital transmitter.
Order code for "Sensor connection housing", option L, "Cast, stainless":
1.4409 (CF3M) similar to 316L
Sensor
Promass Q• Bent dual-tube system
• Excellent performance across a wide range of applications
• Simultaneous measurement of flow, volume flow, density and
temperature (multivariable)
• Process connections: stainless steel, 1.4404 (316/316L)
A0030075
Endress+Hauser7
Equipment architecture
2
1
6
5
7
4
3
3
Proline Promass Q 500
A0027512
1Possibilities for integrating measuring devices into a system
1Control system (e.g. PLC)
2Connecting cable (0/4 to 20 mA HART etc.)
3Fieldbus
4Coupler
5Non-hazardous area
6Hazardous area: Zone 2; Class I, Division 2
7Hazardous area: Zone 1; Class I, Division 1
SafetyIT security
Our warranty is valid only if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any inadvertent
changes to the settings.
IT security measures, which provide additional protection for the device and associated data transfer,
must be implemented by the operators themselves in line with their security standards.
Device-specific IT security
The device offers a range of specific functions to support protective measures on the operator's side.
These functions can be configured by the user and guarantee greater in-operation safety if used
correctly. An overview of the most important functions is provided in the following section.
Function/interfaceFactory settingRecommendation
Write protection via hardware write
protection switch → 9
Access code
(also applies for Web server login or
FieldCare connection) → 9
WLAN
(order option in display module)
WLAN security modeEnabled (WPA2-
WLAN passphrase
(password) → 9
WLAN modeAccess PointOn an individual basis following risk
Web server→ 9Enabled.On an individual basis following risk
CDI-RJ45 service interface → 10–On an individual basis following risk
Not enabled.On an individual basis following risk
assessment.
Not enabled
(0000).
Enabled.On an individual basis following risk
PSK)
Serial numberAssign an individual WLAN passphrase during
Assign a customized access code during
commissioning.
assessment.
Do not change.
commissioning.
assessment.
assessment.
assessment.
8Endress+Hauser
Proline Promass Q 500
Protecting access via hardware write protection
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be disabled via a write protection switch (DIP switch on the
motherboard). When hardware write protection is enabled, only read access to the parameters is
possible.
Hardware write protection is disabled when the device is delivered.
Protecting access via a password
Different passwords are available to protect write access to the device parameters or access to the
device via the WLAN interface.
• User-specific access code
Protect write access to the device parameters via the local display, Web browser or operating tool
(e.g. FieldCare, DeviceCare). Access authorization is clearly regulated through the use of a userspecific access code.
• WLAN passphrase
The network key protects a connection between an operating unit (e.g. notebook or tablet) and the
device via the WLAN interface which can be ordered as an option.
• Infrastructure mode
When the device is operated in infrastructure mode, the WLAN passphrase corresponds to the
WLAN passphrase configured on the operator side.
User-specific access code
Write access to the device parameters via the local display, Web browser or operating tool (e.g.
FieldCare, DeviceCare) can be protected by the modifiable, user-specific access code.
WLAN passphrase: Operation as WLAN access point
A connection between an operating unit (e.g. notebook or tablet) and the device via the WLAN
interface, which can be ordered as an optional extra, is protected by the network key. The WLAN
authentication of the network key complies with the IEEE 802.11 standard.
When the device is delivered, the network key is pre-defined depending on the device. It can be
changed via the WLAN settings submenu in the WLAN passphrase parameter.
Infrastructure mode
A connection between the device and WLAN access point is protected by means of an SSID and
passphrase on the system side. Please contact the relevant system administrator for access.
General notes on the use of passwords
• The access code and network key supplied with the device should be changed during
commissioning.
• Follow the general rules for generating a secure password when defining and managing the access
code or network key.
• The user is responsible for the management and careful handling of the access code and network
key.
Access via Web server
The device can be operated and configured via a Web browser with the integrated Web server. The
connection is via the service interface (CDI-RJ45) or the WLAN interface. For device versions with
the EtherNet/IP and PROFINET communication protocols, the connection can also be established via
the terminal connection for signal transmission with EtherNet/IP or PROFINET (RJ45 connector).
The Web server is enabled when the device is delivered. The Web server can be disabled if necessary
(e.g. after commissioning) via the Web server functionality parameter.
The device and status information can be hidden on the login page. This prevents unauthorized
access to the information.
For detailed information on device parameters, see:
The "Description of Device Parameters" document → 119
Access via OPC-UA
The "OPC UA Server" application package is available in the device version with the HART
communication protocol → 115.
Endress+Hauser9
Proline Promass Q 500
The device can communicate with OPC UA clients using the "OPC UA Server" application package.
The OPC UA server integrated in the device can be accessed via the WLAN access point using the
WLAN interface - which can be ordered as an optional extra - or the service interface (CDI- RJ45) via
Ethernet network. Access rights and authorization as per separate configuration.
The following Security Modes are supported as per the OPC UA Specification (IEC 62541):
• None
• Basic128Rsa15 – signed
• Basic128Rsa15 – signed and encrypted
Access via service interface (CDI-RJ45)
The device can be connected to a network via the service interface (CDI-RJ45). Device-specific
functions guarantee the secure operation of the device in a network.
The use of relevant industrial standards and guidelines that have been defined by national and
international safety committees, such as IEC/ISA62443 or the IEEE, is recommended. This includes
organizational security measures such as the assignment of access authorization as well as technical
measures such as network segmentation.
Transmitters with an Ex de approval may not be connected via the service interface (CDI-RJ45)!
Order code for "Approval transmitter + sensor", options (Ex de): BA, BB, C1, C2, GA, GB, MA,
MB, NA, NB
The device can be integrated in a ring topology. The device is integrated via the terminal
connection for signal transmission (output 1) and the connection to the service interface (CDIRJ45) .
10Endress+Hauser
Proline Promass Q 500
Input
Measured variableDirect measured variables
• Mass flow
• Density
• Temperature
Calculated measured variables
• Volume flow
• Corrected volume flow
• Reference density
Measuring rangeMeasuring range for liquids
DN
Measuring device
[mm][in][mm][in][kg/h][lb/min]
25125/401/1½0 to 200000 to 736
50250/802/30 to 800000 to 2944
80380/1003/40 to 2000000 to 7360
1004100/1504/60 to 5500000 to 20240
Compatible pipe diameter
DN
Measuring range full scale
values
min(F)
to
Measuring range for gases
The full scale value depends on the density and the sound velocity of the gas used and can be
calculated with the formula below:
= minimum (
max(G)
max(G)
max(F)
<
max(G)
ρ
G
xConstant dependent on nominal diameter
c
G
d
i
max(F)
· ρG : x ; ρG · cG · π/2 · (di)2 · 3600)
max(F)
Maximum full scale value for gas [kg/h]
Maximum full scale value for liquid [kg/h]
can never be greater than
max(G)
Gas density in [kg/m³] at operating conditions
Sound velocity (gas) [m/s]
Measuring tube internal diameter [m]
max(F)
max(F)
DNx
[mm][in][kg/m3]
251100
502100
803120
1004200
To calculate the measuring range, use the Applicator sizing tool → 118
Calculation example for gas
• Sensor: Promass Q, DN 50
• Gas: Air with a density of 60.3 kg/m³ (at 20 °C and 50 bar)
Flow rates above the preset full scale value do not override the electronics unit, with the result that
the totalizer values are registered correctly.
Input signalInput and output versions
→ 14
External measured values
Various pressure transmitters and temperature measuring devices can be ordered from Endress
+Hauser: see "Accessories" section → 118
It is recommended to read in external measured values to calculate the corrected volume flow.
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Current input
The measured values are written from the automation system to the measuring device via the
current input → 12.
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS DP
• PROFIBUS PA
• Modbus RS485
• EtherNet/IP
• PROFINET
Current input 0/4 to 20 mA
Current input0/4 to 20 mA (active/passive)
Current span• 4 to 20 mA (active)
• 0/4 to 20 mA (passive)
Resolution1 µA
Voltage dropTypically: 0.6 to 2 V for 3.6 to 22 mA (passive)
Maximum input voltage≤ 30 V (passive)
Open-circuit voltage≤ 28.8 V (active)
Possible input variables• Pressure
• Temperature
• Density
•
12Endress+Hauser
Proline Promass Q 500
Status input
Maximum input values• DC –3 to 30 V
• If status input is active (ON): Ri >3 kΩ
Response timeConfigurable: 5 to 200 ms
Input signal level• Low signal: DC –3 to +5 V
• High signal: DC 12 to 30 V
Assignable functions• Off
• Reset the individual totalizers separately
• Reset all totalizers
• Flow override
Endress+Hauser13
Output
Proline Promass Q 500
Output and input variants
Depending on the option selected for output/input 1, different options are available for the other
outputs and inputs. Only one option can be selected for each output/input 1 to 4. The following
tables must be read vertically (↓).
Example: If the option BA "4–20 mA HART" was selected for output/input 1, one of the options A, B,
D, E, F, H, I or J is available for output 2, and one of the options A, B, D, E, F, H, I or J is available for
output 3 and 4.
Output/input 1 and options for output/input 2
Options for output/input 3 and 4
Order code for "Output; input 1" (020) →Possible options
Current output 4 to 20 mA HARTBA
Current output 4 to 20 mA HART Ex i passive↓ CA
Current output 4 to 20 mA HART Ex i active↓ CC
FOUNDATION Fieldbus↓ SA
FOUNDATION Fieldbus Ex i↓ TA
PROFIBUS DP↓ LA
PROFIBUS PA↓ GA
PROFIBUS PA Ex i↓ HA
Modbus RS485↓ MA
EtherNet/IP 2-port switch integrated↓ NA
PROFINET 2-port switch integrated↓ RA
Order code for "Output; input 2" (021) →↓↓↓↓↓↓↓↓↓↓↓
Not assignedAAAAAAAAAAA
Current output 4 to 20 mABBBBBBB
Current output 4 to 20 mA Ex i passiveCCCC
User-configurable input/output
Pulse/frequency/switch outputEEEEEEE
Double pulse output
Pulse/frequency/switch output Ex i passiveGGGG
Relay outputHHHHHHH
Current input 0/4 to 20 mAIIIIIII
Status inputJJJJJJJ
2)
1)
DDDDDDD
FF
1)A specific input or output can be assigned to a user-configurable input/output → 21.
2)If double pulse output (F) is selected for output/input 2 (021), only the double pulse output (F) option is available for selection for output/input 3
(022).
14Endress+Hauser
Proline Promass Q 500
Output/input 1 and options for output/input 3 and 4
Options for output/input 2 → 14
Order code for "Output; input 1" (020) →Possible options
Current output 4 to 20 mA HARTBA
Current output 4 to 20 mA HART Ex i passive↓ CA
Current output 4 to 20 mA HART Ex i active↓ CC
FOUNDATION Fieldbus↓ SA
FOUNDATION Fieldbus Ex i↓ TA
PROFIBUS DP↓ LA
PROFIBUS PA↓ GA
PROFIBUS PA Ex i↓ HA
Modbus RS485↓ MA
EtherNet/IP 2-port switch integrated↓ NA
PROFINET 2-port switch integrated↓ RA
Order code for "Output; input 3" (022), "Output; input 4" (023) →↓↓↓↓↓↓↓↓↓↓↓
Not assignedAAAAAAAAAAA
Current output 4 to 20 mABBBBB
Current output 4 to 20 mA Ex i passive
User-configurable input/outputDDDDD
Pulse/frequency/switch outputEEEEE
Double pulse output (slave)
2)
Pulse/frequency/switch output Ex i passive
Relay outputHHHHH
Current input 0/4 to 20 mAIIIII
Status inputJJJJJ
1)
CC
FF
3)
GG
1)For output/input 4 the current output 4 to 20 mA Ex i passive (C) is not available.
2)The double pulse output (F) option is not available for input/output 4.
3)For output/input 4 the pulse/frequency/switch output Ex i passive (G) is not available.
Endress+Hauser15
Output signalCurrent output 4 to 20 mA HART
Order code"Output; Input 1" (20):
Option BA: current output 4 to 20 mA HART
Signal modeCan be set to:
• Active
• Passive
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only with signal mode active)
• Fixed current value
Open-circuit voltageDC 28.8 V (active)
Maximum input voltageDC 30 V (passive)
Load250 to 700 Ω
Resolution0.38 µA
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
Proline Promass Q 500
The range of options increases if the measuring device has one or more
application packages.
Current output 4 to 20 mA HART Ex i
Order code"Output; Input 1" (20) can be set to:
• Option CA: current output 4 to 20 mA HART Ex i passive
• Option CC: current output 4 to 20 mA HART Ex i active
Signal modeDepending on the ordered variant.
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only with signal mode active)
• Fixed current value
Open-circuit voltageDC 21.8 V (active)
Maximum input voltageDC 30 V (passive)
Load• 250 to 400 Ω (active)
• 250 to 700 Ω (passive)
Resolution0.38 µA
16Endress+Hauser
Proline Promass Q 500
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
FOUNDATION Fieldbus
FOUNDATION FieldbusH1, IEC 61158-2, galvanically isolated
Data transfer31.25 kbit/s
Current consumption10 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
PROFIBUS DP
Signal encodingNRZ code
Data transfer9.6 kBaud…12 MBaud
PROFIBUS PA
PROFIBUS PAIn accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically
isolated
Data transmission31.25 kbit/s
Current consumption10 mA
Permitted supply voltage9 to 32 V
Bus connectionWith integrated reverse polarity protection
Modbus RS485
Physical interfaceRS485 in accordance with EIA/TIA-485 standard
Terminating resistorIntegrated, can be activated via DIP switches
EtherNet/IP
StandardsIn accordance with IEEE 802.3
PROFINET
StandardsIn accordance with IEEE 802.3
Endress+Hauser17
Proline Promass Q 500
Current output 4 to 20 mA
Order code"Output; Input 2" (21), "Output; Input 3" (022) or "Output; Input 4" (023):
Option B: current output 4 to 20 mA
Signal modeCan be set to:
• Active
• Passive
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• 0 to 20 mA (only with signal mode active)
• Fixed current value
Maximum output values22.5 mA
Open-circuit voltageDC 28.8 V (active)
Maximum input voltageDC 30 V (passive)
Load0 to 700 Ω
Resolution0.38 µA
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Current output 4 to 20 mA Ex i passive
Order code"Output; Input 2" (21), "Output; Input 3" (022):
Option C: current output 4 to 20 mA Ex i passive
Signal modePassive
Current rangeCan be set to:
• 4 to 20 mA NAMUR
• 4 to 20 mA US
• 4 to 20 mA
• Fixed current value
Maximum output values22.5 mA
Maximum input voltageDC 30 V
Load0 to 700 Ω
Resolution0.38 µA
18Endress+Hauser
Proline Promass Q 500
DampingConfigurable: 0 to 999 s
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Pulse/frequency/switch output
FunctionCan be set to pulse, frequency or switch output
VersionOpen collector
Can be set to:
• Active
• Passive
• Passive NAMUR
Ex-i, passive
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Voltage dropFor 22.5 mA: ≤ DC 2 V
Pulse output
Maximum input valuesDC 30 V, 250 mA (passive)
Maximum output current22.5 mA (active)
Open-circuit voltageDC 28.8 V (active)
Pulse widthConfigurable: 0.05 to 2000 ms
Maximum pulse rate10000 Impulse/s
Pulse valueAdjustable
Assignable measured
variables
Frequency output
Maximum input valuesDC 30 V, 250 mA (passive)
Maximum output current22.5 mA (active)
Open-circuit voltageDC 28.8 V (active)
Output frequencyAdjustable: end value frequency 2 to 10000 Hz (f
DampingConfigurable: 0 to 999 s
Pulse/pause ratio1:1
• Mass flow
• Volume flow
• Corrected volume flow
= 12500 Hz)
max
Endress+Hauser19
Proline Promass Q 500
Assignable measured
variables
Switch output
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Switching behaviorBinary, conductive or non-conductive
Switching delayConfigurable: 0 to 100 s
Number of switching
cycles
Assignable functions• Off
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Unlimited
• On
• Diagnostic behavior
• Limit value
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1-3
• Flow direction monitoring
• Status
• Partially filled pipe detection
• Low flow cut off
The range of options increases if the measuring device has one or more
application packages.
Double pulse output
FunctionDouble pulse
VersionOpen collector
Can be set to:
• Active
• Passive
• Passive NAMUR
Maximum input valuesDC 30 V, 250 mA (passive)
Open-circuit voltageDC 28.8 V (active)
Voltage dropFor 22.5 mA: ≤ DC 2 V
Output frequencyConfigurable: 0 to 1000 Hz
DampingConfigurable: 0 to 999 s
20Endress+Hauser
Proline Promass Q 500
Pulse/pause ratio1:1
Assignable measured
variables
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
The range of options increases if the measuring device has one or more
application packages.
Relay output
FunctionSwitch output
VersionRelay output, galvanically isolated
Switching behaviorCan be set to:
• NO (normally open), factory setting
• NC (normally closed)
Maximum switching
capacity (passive)
Assignable functions• Off
• DC 30 V, 0.1 A
• AC 30 V, 0.5 A
• On
• Diagnostic behavior
• Limit value
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Totalizer 1-3
• Flow direction monitoring
• Status
• Partially filled pipe detection
• Low flow cut off
The range of options increases if the measuring device has one or more
application packages.
User-configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable I/O)
during device commissioning.
The following inputs and outputs are available for assignment:
• Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Pulse/frequency/switch output
• Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Status input
The technical values correspond to those of the inputs and outputs described in this section.
Signal on alarm
Depending on the interface, failure information is displayed as follows:
HART current output
Device diagnosticsDevice condition can be read out via HART Command 48
Endress+Hauser21
PROFIBUS PA
Proline Promass Q 500
Status and alarm
messages
Failure current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with PROFIBUS PA Profile 3.02
0 mA
PROFIBUS DP
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
EtherNet/IP
Device diagnosticsDevice condition can be read out in Input Assembly
PROFINET
Device diagnosticsAccording to "Application Layer protocol for decentralized periphery", Version 2.3
FOUNDATION Fieldbus
Status and alarm
messages
Failure current FDE (Fault
Disconnection Electronic)
Diagnostics in accordance with FF-891
0 mA
Modbus RS485
Failure modeChoose from:
• NaN value instead of current value
• Last valid value
Current output 0/4 to 20 mA
4 to 20 mA
Failure modeChoose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value
0 to 20 mA
Failure modeChoose from:
• Maximum alarm: 22 mA
• Freely definable value between: 0 to 20.5 mA
22Endress+Hauser
Proline Promass Q 500
Pulse/frequency/switch output
Pulse output
Failure modeChoose from:
• Actual value
• No pulses
Frequency output
Failure modeChoose from:
• Actual value
• 0 Hz
• Defined value (f
Switch output
Failure modeChoose from:
• Current status
• Open
• Closed
Relay output
Failure modeChoose from:
• Current status
• Open
• Closed
2 to 12500 Hz)
max
Local display
Plain text displayWith information on cause and remedial measures
BacklightRed backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
• HART protocol
• FOUNDATION Fieldbus
• PROFIBUS PA
• PROFIBUS DP
• Modbus RS485
• EtherNet/IP
• PROFINET
• Via service interface
• CDI-RJ45 service interface
• WLAN interface
Plain text displayWith information on cause and remedial measures
Additional information on remote operation → 97
Web browser
Plain text displayWith information on cause and remedial measures
Endress+Hauser23
Light emitting diodes (LED)
Status informationStatus indicated by various light emitting diodes
Ex connection dataSafety-related values
Proline Promass Q 500
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
• PROFINET network available
• PROFINET connection established
• PROFINET blinking feature
Order code for
Output typeSafety-related values
"Output; input 1"
Option BACurrent output
4 to 20 mA HART
UN = 30 V
UM = 250 V
Option GAPROFIBUS PAUN = 30 V
UM = 250 V
Option LAPROFIBUS DPUN = 30 V
UM = 250 V
Option MAModbus RS485UN = 30 V
UM = 250 V
Option SAFOUNDATION FieldbusUN = 30 V
UM = 250 V
Option NAEtherNet/IPUN = 30 V
UM = 250 V
Option RAPROFINETUN = 30 V
UM = 250 V
Order code for
"Output; input 2";
"Output; input 3"
Output typeSafety-related values
Output; input 2Output; input 3Output; input
"Output; input 4"
24 (+)25 (–)22 (+)23 (–)20 (+)21 (–)
Option BCurrent output
4 to 20 mA
Option DUser-configurable input/
output
Option EPulse/frequency/switch
output
Option FDouble pulse outputUN = 30 V
UN = 30 V
UM = 250 V
UN = 30 V
UM = 250 V
UN = 30 V
UM = 250 V
DC
DC
DC
DC
UM = 250 V
Option HRelay outputUN = 30 V
DC
IN =100 mADC/500 mA
UM = 250 V
Option ICurrent input
4 to 20 mA
Option JStatus inputUN = 30 V
UN = 30 V
UM = 250 V
DC
DC
UM = 250 V
"Output; input 1"
26 (+)27 (–)
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
AC
AC
AC
AC
AC
AC
AC
AC
1)
4
1)The order code "Output; input 4" is only available for the Proline 500 – digital transmitter.
24Endress+Hauser
Proline Promass Q 500
Intrinsically safe values
Order code for
Output typeIntrinsically safe values
"Output; input 1"
Option CACurrent output
4 to 20 mA HART Ex i
passive
Option CCCurrent output
4 to 20 mA HART Ex i
active
Option HAPROFIBUS PA Ex i
(FISCO Field Device)
Option TAFOUNDATION Fieldbus
Ex i
"Output; input 1"
26 (+)27 (–)
Ui = 30 V
li = 100 mA
Pi = 1.25 W
Li = 0 µH
Ci = 6 nF
Ui = 32 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
4)
Ex ic
Ui = 32 V
li = 570 mA
Pi = 8.5 W
Li = 10 µH
Ci = 5 nF
Low flow cut off
Galvanic isolation
1)Only available for the Zone 1; Class I, Division 1 version
2)Only available for the Zone 2; Class I, Division 2 version and only for the Proline 500 – digital transmitter
3)Only available for the Zone 1; Class I, Division 1 version
4)Only available for the Zone 2; Class I, Division 2 version and only for the Proline 500 – digital transmitter
Order code for
"Output; input 2";
"Output; input 3";
"Output; input 4"
Option CCurrent output
Output typeIntrinsically safe values or NIFW values
Output; input 2Output; input 3 Output; input 4
24 (+)25 (–)22 (+)23 (–)20 (+)21 (–)
Ui = 30 V
4 to 20 mA Ex i
li = 100 mA
Pi = 1.25 W
Li = 0
Ci = 0
Option GPulse/frequency/switch
output Ex i
Ui = 30 V
li = 100 mA
Pi = 1.25 W
Li = 0
Ci = 0
1)The order code "Output; input 4" is only available for the Proline 500 – digital transmitter.
The switch points for low flow cut off are user-selectable.
The outputs are galvanically isolated from one another and from earth (PE).
1)
Endress+Hauser25
Protocol-specific dataHART
Manufacturer ID0x11
Device type ID0x3B
HART protocol revision7
Device description files
(DTM, DD)
HART loadMin. 250 Ω
System integrationInformation on system integration: Operating Instructions → 119.
FOUNDATION Fieldbus
Manufacturer ID0x452B48 (hex)
Ident number0x103B (hex)
Device revision1
DD revisionInformation and files under:
CFF revision
Interoperability Test Kit (ITK) Version 6.2.0
ITK Test Campaign NumberInformation:
Link Master capability (LAS)Yes
Choice of "Link Master" and
"Basic Device"
Node addressFactory setting: 247 (0xF7)
Supported functionsThe following methods are supported:
Virtual Communication Relationships (VCRs)
Number of VCRs44
Number of link objects in VFD 50
Permanent entries1
Client VCRs0
Server VCRs10
Source VCRs43
Sink VCRs0
Subscriber VCRs43
Publisher VCRs43
Device Link Capabilities
Slot time4
Min. delay between PDU8
Proline Promass Q 500
Information and files under:
www.endress.com
• Measured variables via HART protocol
• Burst Mode functionality
• www.endress.com
• www.fieldbus.org
• www.endress.com
• www.fieldbus.org
Yes
Factory setting: Basic Device
• Restart
• ENP Restart
• Diagnostic
• Set to OOS
• Set to AUTO
• Read trend data
• Read event logbook
26Endress+Hauser
Proline Promass Q 500
Max. response delay16
System integrationInformation regarding system integration: Operating Instructions → 119.
• Cyclic data transmission
• Description of the modules
• Execution times
• Methods
PROFIBUS DP
Manufacturer ID0x11
Ident number0x156F
Profile version3.02
Device description files (GSD,
DTM, DD)
Supported functions• Identification & Maintenance
Configuration of the device
address
Compatibility with
earlier model
System integrationInformation regarding system integration: Operating Instructions → 119.
Information and files under:
• www.endress.com
On the product page for the device: Documents/Software → Device drivers
• www.profibus.org
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
• DIP switches on the I/O electronics module
• Via operating tools (e.g. FieldCare)
If the device is replaced, the measuring device Promass 500 supports the
compatibility of the cyclic data with previous models. It is not necessary to
adjust the engineering parameters of the PROFIBUS network with the
Promass 500 GSD file.
Previous model:
Promass 83 PROFIBUS DP
• ID No.: 1529 (hex)
• Extended GSD file: EH3x1529.gsd
• Standard GSD file: EH3_1529.gsd
Description of the function scope of compatibility:
Operating Instructions → 119.
• Cyclic data transmission
• Block model
• Description of the modules
PROFIBUS PA
Manufacturer ID0x11
Ident number0x156D
Profile version3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• www.endress.com
• www.profibus.org
Endress+Hauser27
Proline Promass Q 500
Supported functions• Identification & Maintenance
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
Configuration of the device
address
Compatibility with
earlier model
System integrationInformation regarding system integration: Operating Instructions → 119.
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e.g. FieldCare)
If the device is replaced, the measuring device Promass 500 supports the
compatibility of the cyclic data with previous models. It is not necessary to
adjust the engineering parameters of the PROFIBUS network with the
Promass 500 GSD file.
Earlier models:
• Promass 80 PROFIBUS PA
• ID No.: 1528 (hex)
• Extended GSD file: EH3x1528.gsd
• Standard GSD file: EH3_1528.gsd
• Promass 83 PROFIBUS PA
• ID No.: 152A (hex)
• Extended GSD file: EH3x152A.gsd
• Standard GSD file: EH3_152A.gsd
Description of the function scope of compatibility:
Response times• Direct data access: typically 25 to 50 ms
• Auto-scan buffer (data range): typically 3 to 5 ms
Device typeSlave
Slave address range1 to 247
Broadcast address range0
Function codes• 03: Read holding register
• 04: Read input register
• 06: Write single registers
• 08: Diagnostics
• 16: Write multiple registers
• 23: Read/write multiple registers
Broadcast messagesSupported by the following function codes:
• 06: Write single registers
• 16: Write multiple registers
• 23: Read/write multiple registers
Supported baud rate• 1200 BAUD
• 2400 BAUD
• 4800 BAUD
• 9600 BAUD
• 19200 BAUD
• 38400 BAUD
• 57600 BAUD
• 115200 BAUD
Data transfer mode• ASCII
• RTU
28Endress+Hauser
Proline Promass Q 500
Data accessEach device parameter can be accessed via Modbus RS485.
For Modbus register information
Compatibility with
earlier model
System integrationInformation on system integration: Operating Instructions → 119.
If the device is replaced, the measuring device Promass 500 supports the
compatibility of the Modbus registers for the process variables and the
diagnostic information with the previous model Promass 83. It is not
necessary to change the engineering parameters in the automation system.
Description of the function scope of compatibility:
Operating Instructions → 119.
• Modbus RS485 information
• Function codes
• Register information
• Response time
• Modbus data map
EtherNet/IP
Protocol• The CIP Networks Library Volume 1: Common Industrial Protocol
• The CIP Networks Library Volume 2: EtherNet/IP Adaptation of CIP
Communication type• 10Base-T
• 100Base-TX
Device profileGeneric device (product type: 0x2B)
Manufacturer ID0x11
Device type ID0x103B
Baud ratesAutomatic ¹⁰⁄₁₀₀ Mbit with half-duplex and full-duplex detection
PolarityAuto-polarity for automatic correction of crossed TxD and RxD pairs
Supported CIP connectionsMax. 3 connections
Explicit connectionsMax. 6 connections
I/O connectionsMax. 6 connections (scanner)
Configuration options for
measuring device
Configuration of the EtherNet
interface
Configuration of the device
address
Device Level Ring (DLR)Yes
System integrationInformation regarding system integration: Operating Instructions
• DIP switches on the electronics module for IP addressing
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• Electronic Data Sheet (EDS) integrated in the measuring device
• Speed: 10 MBit, 100 MBit, auto (factory setting)
• Duplex: half-duplex, full-duplex, auto (factory setting)
• DIP switches on the electronics module for IP addressing (last octet)
• DHCP
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• EtherNet/IP tools, e.g. RSLinx (Rockwell Automation)
→ 119.
• Cyclic data transmission
• Block model
• Input and output groups
PROFINET
ProtocolApplication layer protocol for decentral device periphery and distributed
automation, Version 2.3
Communication type100 MBit/s
Endress+Hauser29
Proline Promass Q 500
Conformity classConformance Class B
Netload ClassNetload Class II
Baud ratesAutomatic 100 Mbit/s with full-duplex detection
Cycle timesFrom 8 ms
PolarityAuto-polarity for automatic correction of crossed TxD and RxD pairs
Media Redundancy Protocol
(MRP)
System redundancy supportSystem redundancy S2 (2 AR with 1 NAP)