Brief operating instructionsMicropilot M FMR244 HART 4 to 20 mA
Brief operating instructions
KA235F/00/a2/08.06
52025245
000
measured
value
E
+
-
Group
selection
00
basic
+
setup
01
safety
settings
04
linearisation
05
extended
calibr.
06
output (HART, FF)
profibus param. (PA)
09
display
0E
envelope
curve
-
0A
diagnostics
0C
system parameter
092
language
0E1
plot settings
- envel. curve
- incl. FAC
- incl. cust. map
0A0
present error
Micropilot M FMR240/244/245/250 - Brief operating instructions
Contrast:+or +
E
E
051
check
distance
-ok
- too small
- too big
- unknown
- manual
D
F
L
001
media
type
- liquid
- solid
002
002
tank
tank
shape
shape
- dome
ceiling
- horizontal
cyl.
- bypass
00A
vessel /
silo
- unknown
- metal silo
- concrete
silo
- bin / bunker
…
… …
0E2
recording
curve
- single curve
- cyclic
0A1
previous error
+
-
- unknown
- DC: <1.9
- DC: 1.9 … 4
-DC:4…10
- DC: >10
…
00B
medium
cond.
- unknown
- DC: 1.6...1.9
- DC: 1.9 …2.5
- DC: 2.5 …4
...
003
medium
cond.
00C
proscess
cond.
- standard
- fast change
- slow change
- test: no filter
0A4
unlock parameter
…
= 100: unlocked
100: locked≠
= 2457: unlocked
2457: locked≠
004
process
cond.
- standard
- calm
surface
- add.
agitator
…
005
empty
calibr.
input E
(see sketch)
005
empty
calibr.
input E
(see sketch)
…
HART
}
PA, FF
}
006
full
calibr.
input F
(see sketch)
006
full
calibr.
input F
(see sketch)
flange:
reference point of
measurement
threaded
connection
1½”(R1
or 1½ NPT
reference point of
measurement
007
pipe
diameter
only for
bypass +
stilling well
BSPT½”)
:
008
dist./
meas value
D and L are
displayed
(see sketch)
E
008
E
dist./
meas value
052
range of
mapping
confirm
suggestion
or specify
range
Solid Liquid
52025245
L00-FMR250xx-19-00-00-en-020
053
start
mapping
20 mA
100%
4mA
0%
!
Note!
This operating manual explains the installation and initial start-up for the level transmitter. All
functions that are required for a typical measuring task are taken into account here. In addition, the
Micropilot M provides many other functions that are not included in this operating manual, such as
optimising the measuring point and converting the measured values.
An overview of all device functions can be found on → ä 86.
The operating manual BA00291F/00/EN "Description of Instrument Functions" provides an
extensive description of all device functions, which can be found on the enclosed CD-ROM.
2Endress+Hauser
Page 3
Micropilot M FMR244 HART 4 to 20 mATable of contents
Safety instructionsMicropilot M FMR244 HART 4 to 20 mA
1Safety instructions
1.1Designated use
The Micropilot M is a compact radar level transmitter for the continuous, contactless measurement
of liquids, pastes, sludge and solids. The device can also be freely mounted outside closed metal
vessels because of its operating frequency of about 26 GHz and a maximum radiated pulsed energy
of 1 mW (average power output 1 μW). Operation is completely harmless to humans and animals.
1.2Installation, commissioning and operation
The Micropilot M has been designed to operate safely in accordance with current technical, safety
and EU standards. If installed incorrectly or used for applications for which it is not intended,
however, it is possible that application-related dangers may arise, e. g. product overflow due to
incorrect installation or calibration. For this reason, the instrument must be installed, connected,
operated and maintained according to the instructions in this manual: personnel must be authorised
and suitably qualified. The manual must have been read and understood, and the instructions
followed. Modifications and repairs to the device are permissible only when they are expressly
approved in the manual.
1.3Operational safety and process safety
Alternative monitoring measures must be taken to ensure operational safety and process safety
during configuration, testing and maintenance work on the device.
Hazardous areas
Measuring systems for use in hazardous environments are accompanied by separate "Ex
documentation", which is an integral part of this Operating Manual. Strict compliance with the
installation instructions and ratings as stated in this Additional documentation is mandatory.
• Ensure that all personnel are suitably qualified.
• Observe the specifications in the certificate as well as national and local regulations.
1.3.1FCC approval
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions:
1.This device may not cause harmful interference.
2.This device must accept any interference received, including interference that may cause
undesired operation.
Caution!
"
Changes or modifications not expressly approved by the part responsible for compliance could void
the user’s authority to operate the equipment.
4Endress+Hauser
Page 5
Micropilot M FMR244 HART 4 to 20 mASafety instructions
1.4Notes on safety conventions and symbols
In order to highlight safety-relevant or alternative operating procedures in the manual, the following
conventions have been used, each indicated by a corresponding symbol in the margin.
Safety conventions
Warning!
#
"
!
Explosion protection
0
A warning highlights actions or procedures which, if not performed correctly, will lead to personal
injury, a safety hazard or destruction of the instrument.
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal
injury or incorrect functioning of the instrument.
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect
operation or may lead to an instrument response which is not planned.
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous
area.
-
.
Electrical symbols
%
&
)
*
+
Explosion hazardous area
Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring
entering areas with the designation “explosion hazardous areas” must conform with the stated type
of protection.
Safe area (non-explosion hazardous area)
Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in
safe areas still require a certificate if their outputs run into explosion hazardous areas.
Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied.
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or
supplied.
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of an
earth grounding system.
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection to the
equipment.
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e. g. neutral star or
equipotential line according to national or company practice.
t >85°C
Endress+Hauser5
Temperature resistance of the connection cables
States, that the connection cables must be resistant to a temperature of at least 85 °C (185 °F).
Page 6
IdentificationMicropilot M FMR244 HART 4 to 20 mA
2Identification
2.1Device designation
2.1.1Nameplate
The following technical data are given on the instrument nameplate:
ENDRESS+HAUSER
1
Order Code:
Ser.-No.:
4
5
7
8
9
12
Information on the nameplate of the Micropilot M
1Instrument designation
2Order code
3Serial number
4Process pressure
5Process temperature
6Length (optional)
7Power supply
8Current supply
9Ambient temperature
10Cable specification
11Factory sealed
12Radio equipment number
13TÜV identification mark
14Certificate symbol (optional) e.g. Ex, NEPSI
15Certificate symbol (optional) e.g. 3A
16Certificate symbol (optional) e.g. SIL, FF
17Place of production
18Degree of protection e.g. IP65, IP67
19Certificates and approvals
20Document number of safety instructions e.g. XA, ZD, ZE
21Dat./Insp. xx / yy (xx = week of production, yy = year of production)
13
10
14
2
3
19
6
if modification
X=
see sep. label
20
15
11
16
Dat./Insp.:
17
18
21
Typenschild-FMxxxx-xx
6Endress+Hauser
Page 7
Micropilot M FMR244 HART 4 to 20 mAIdentification
2.1.2Ordering structure
This overview does not mark options which are mutually exclusive.
10Approval
A Non-hazardous area
F Non-hazardous area, WHG
2 ATEX II 1/2G EEx ia IIC T6, XA note safety instruction (XA) (electrostatic charging)!
7 ATEX II 1/2G EEx ia IIC T6, WHG, XA note safety instruction (XA) (electrostatic charging)!
5 ATEX II 1/2G EEx d [ia] IIC T6, XA note safety instruction (XA) (electrostatic charging)!
H ATEX II 1/2G EEx ia IIC T6, ATEX 3D, XA note safety instruction (XA) (electrostatic charging)!
B ATEX II 1/2D, Alu blind cover, XA
C ATEX II 1/3D, XA
G ATEX II 3G EEx nA II T6
S FM IS - Cl.I Div.1 Gr. A-D, zone 0, 1, 2
T FM XP - Cl.I Div.1 Group A-D, zone 1, 2
N CSA General Purpose
U CSA IS - Cl.I Div.1 Group A-D, zone 0, 1, 2
V CSA XP - Cl.I Div.1 Group A-D, zone 1, 2
K TIIS EEx ia IIC T4
L TIIS EEx d [ia] IIC T4
D IECEx Zone 0/1, Ex ia IIC T6, XA note safety instruction (XA) (electrostatic charging)!
E IECEx Zone 0/1, Ex d (ia) IIC T6, XA note safety instruction (XA) (electrostatic charging)!
I NEPSI Ex ia IIC T6
J NEPSI Ex d (ia) ia IIC T6
R NEPSI Ex nAL IIC T6
Y Special version, TSP-no. to be spec.
20Antenna
2 40mm/1-1/2", PTFE encapsulated
4 80mm/3", PP cladded
9 Special version, TSP-no. to be spec.
30Antenna Seal; Temperature
S Silicone; -40...80°C/-40…176°F
V FKM Viton GLT; -40…130°C/-40…266°F
Y Special version, TSP-no. to be spec.
40Process Connection
GGSThread ISO228 G1-1/2, PVDF
GNSThread ANSI NPT1-1/2, PVDF
XMEMounting bracket, 304
XRXW/o slip on flange/mounting bracket, customer side connection
XVGUNI slip on flange 3"/DN80/80, PP max 4bar abs/58psia, suitable for 3" 150lbs/DN80 PN16/10K
80
XXGUNI slip on flange 4"/DN100/100, PP
max 4bar abs/58psia, suitable for 4" 150lbs / DN100 PN16 / 10K 100
X1GUNI slip on flange 6"/DN150/150, PP
max 4bar abs/58psia, suitable for 6" 150lbs / DN150 PN16 / 10K 150
YY9Special version, TSP-no. to be spec.
50Output; Operation
A 4-20mA SIL HART; 4-line display VU331, envelope curve display on site
B 4-20mA SIL HART; w/o display, via communication
K 4-20mA SIL HART; Prepared for FHX40, remote display (Accessory)
C PROFIBUS PA; 4-line display VU331, envelope curve display on site
D PROFIBUS PA; w/o display, via communication
L PROFIBUS PA; Prepared for FHX40, remote display (Accessory)
E FOUNDATION Fieldbus; 4-line display, envelope curve display on site
F FOUNDATION Fieldbus; w/o display, via communication
M FOUNDATION Fieldbus; Prepared for FHX40, remote display (Accessory)
Y Special version, TSP-no. to be spec.
60Housing
A F12 Alu, coated IP65 NEMA4X
C T12 Alu, coated IP65 NEMA4X, separate conn. compartment
D T12 Alu, coated IP65 NEMA4X, separate conn. compartment, OVP=overvoltage protection
Y Special version, TSP-no. to be spec.
5Plug M12
6 Plug 7/8"
9 Special version, TSP-no. to be spec.
80Additional option
A Basic version
F Advanced dynamics, max. MB=70m liquids, max. MB=15m solids,
MB=measuring range
H 5-point linearity protocol, see additional spec.
L 5-point, advanced dynamics, 5-point linearity protocol, see additional spec.,
Advanced dynamics, max MB=70m liquids, max MB=15m solids, MB=measuring
range
S GL/ABS/NK marine certificate
Y Special version, TSP-no. to be spec.
995Marking
1Tagging (TAG)
2 Bus address
FMR244-Complete product designation
8Endress+Hauser
Page 9
Micropilot M FMR244 HART 4 to 20 mAIdentification
2.2Scope of delivery
Caution!
"
It is essential to follow the instructions concerning the unpacking, transport and storage of
measuring instruments given in the chapter "Incoming acceptance, transport, storage", → ä 11!
The scope of delivery consists of:
• Assembled instrument
• Accessories (→ ä 65)
• Endress+Hauser oprating program on the enclosed CD-ROM
• Brief operating instructions KA01009F/00/EN for quick commissioning
• Brief operating instructions KA00235F/00/A2 (basic setup/troubleshooting), housed in the
instrument)
• Approval documentation: if this is not included in the operating manual
• CD-ROM with further documentation, e. g.
- Technical Information
- Operating Instructions
- Description of Intrument Functions
2.3Certificates and approvals
CE mark, declaration of conformity
The device is designed to meet state-of-the-art safety requirements, has been tested and left the
factory in a condition in which it is safe to operate. The device complies with the applicable
standards and regulations as listed in the EC declaration of conformity and thus complies with the
statutory requirements of the EC directives. Endress+Hauser confirms the successful testing of the
device by affixing to it the CE mark.
2.4Registered trademarks
KALREZ®, VITON®, TEFLON
Registered trademark of the company, E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP
Registered trademark of the company, Ladish & Co., Inc., Kenosha, USA
HART
Registered trademark of HART Communication Foundation, Austin, USA
®
ToF
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
PulseMaster
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
PhaseMaster
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
®
®
®
®
®
Endress+Hauser9
Page 10
MountingMicropilot M FMR244 HART 4 to 20 mA
3Mounting
3.1Quick installation guide
Observe orientation when installing!
#
Turn housing
Installation in tank (free space):
Mark on process connector facing the nearest tank wall!
mark at threaded boss
The housing can be turned 350°
in order to simplify access to the
display and the terminal compartment
F12 housing
2
90°90°
90°
Installation in stilling well:
Mark on process connector pointed towards the slots or vent holes!
90°90°
90°
90°
90°
mark at threaded boss
F12 or T12 housing
G 1½”
or
1½ NPT
G 1½”
or
1½ NPT
3
1
T12 housing
2
3
1
Allen key
4 mm (0.16 in)
max. torque0.5Nm(0.37 lbf ft)
Caution!
Tighten instrument only
at thethreaded boss.
AF60
60
max. torque
20 Nm (14.75 lbf ft)
L00-FMR244xx-17-00-00-en-001
10Endress+Hauser
Page 11
Micropilot M FMR244 HART 4 to 20 mAMounting
3.2Incoming acceptance, transport, storage
3.2.1Incoming acceptance
Check the packing and contents for any signs of damage.
Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
3.2.2Transport
Caution!
"
Follow the safety instructions and transport conditions for instruments of more than
18 kg (39.69 lbs). Do not lift the measuring instrument by its housing in order to transport it.
3.2.3Storage
Pack the measuring instrument so that is protected against impacts for storage and transport. The
original packing material provides the optimum protection for this.
The permissible storage temperature is -40 °C to +80 °C (-40 °F to +176 °F) or
-50 °C to +80 °C (-58 °F to +176 °F).
Endress+Hauser11
Page 12
MountingMicropilot M FMR244 HART 4 to 20 mA
3.3Installation conditions
3.3.1Dimensions
Housing dimensions
max. 110 (4.33)
mm (in)
max. 100 (4.33)94 (3.7)
F12 housing
(Aluminium)
65 (2.56)
ENDRESS+HAUSER
65 (2.56)
ENDRESS+HAUSER
78 (3.07)
85 (3.35)
78 (3.07)
ø129 (ø5.08)
150 (5.91)
L00-F12xxxx-06-00-00-en-001
mm (in)
T12 housing
(Aluminium)
85 (3.35)
ø129 (ø5.08)
162 (6.38)
L00-T12xxxx-06-00-00-en-001
12Endress+Hauser
Page 13
Micropilot M FMR244 HART 4 to 20 mAMounting
Process connection
F12 / T12 housing
Group 20 / Code 4Code 2
standard
mounting bracket * optional
E+H UNI**
flange DN80
167.1 (6.58)
135.9 (5.35)
R
PP
R = reference point of measurement
PBT
15
(0.59)
PBT
PP
suitable for DN80 PN16 / ASME3” 150 lbs / 10K 80suitable for
** Installation hints: Thebolt-holes have been enlarged for adaption
of dimensions , therefore, theflange needs to be properly aligned
to thecounterflange before thebolts are tightened.
Flange
øD
228.6 (9.00)
øB
190.5 (7.50)
øC
d
mm (in)
19 (0.75)
15.5 (0.61)
DN 150DN 100
285 (11.22)
241.3 (9.50)
240 (9.45)175 (6.89)
23 (0.91)
20 (0.79)
Ø 75 (2.95)
ø115 (4.53)
øD
øB
øC
d
L00-FMR244xx-06-00-00-en-009
seal
(Viton)
15
(0.59)
Endress+Hauser13
Page 14
MountingMicropilot M FMR244 HART 4 to 20 mA
3.3.2Engineering hints
Orientation
• Recommended distance (1) wall – outer
edge of nozzle: ~1/6 of tank diameter.
Nevertheless the device should not be
installed closer than 15 cm (5.91 in) to the
tankwall.
• Not in the centre (3), interference can cause
signal loss.
• Not above the fill stream (4).
• It is recommended to use a weather
protection cover (2) in order to protect the
transmitter from direct sun or rain. Assembly
and disassembly is simply done by means of a
tension clamp (→ ä 65, "Accessories").
1
234
Tank installations
• Avoid any installations (1), like limit switches,
temperature sensors, etc., inside the signal
beam (→ ä 16, "Beam angle").
• Symmetrical installations (2), i. e. vacuum
rings, heating coils, baffles, etc., can also
interfere with the measurement.
Optimization options
• Antenna size: the bigger the antenna, the
smaller the beam angle, the less interference
echoes.
• Mapping: the measurement can be optimized
by means of electronic suppression of
interference echoes.
• Antenna alignment: "Installation in tank (free
space)", → ä 21
• Stilling well: a stilling well can always be used
to avoid interference.
• Metallic screens (3) mounted at a slope spread
the radar signals and can, therefore, reduce
interference echoes.
L00-FMR2xxxx-17-00-00-xx-008
1
3
2
a
Please contact Endress+Hauser for further information.
L00-FMR2xxxx-17-00-00-xx-009
14Endress+Hauser
Page 15
Micropilot M FMR244 HART 4 to 20 mAMounting
VH
00
End
r
es
s+H
ause
r
-
+
V
H
Made in Germany Maulburg
VH
00
Endres
s
+
H
ause
r
-
+
V
H
Made in Germany Maulburg
VH
00
Endress+Hau
ser
-
+
V
H
Made in Germany Maulburg
Measurement in a plastic tank
If the outer wall of the tank is made of a non-conductive material (e. g. GRP), microwaves can also
be reflected off interfering installations outside the signal beam (e. g. metallic pipes (1), ladders (2),
grates (3), …). Therefore, there should be no such interfering installations in the signal beam.
Please contact Endress+Hauser for further information.
r
e
s
u
a
H
+
s
EN
s
D
e
R
r
ES
d
n
S+
E
H
A
U
MI
S
ER
CR
H
O
V
P
I
LO
T
II
O
r
d
e
r
C
o
d
e
:
S
0
e
r
.
N
0
o
.
:
M
e
s
s
b
e
r
e
i
c
h
M
e
a
s
u
r
i
n
g
r
a
n
m
g
e
a
x
.
2
0
m
I
P
6
5
U
1
6
.
.
.3
6
V
D
C
4
.
.
.
2
0
m
A
T
>
7
A
0
°
C
:
t>
85°C
Made in Germany Maulburg
r
e
s
u
a
H
+
E
ss
NDR
E
dre
S
n
S
+HA
E
US
M
I
ER
C
H
R
OPI
V
L
O
T
I
O
I
r
d
e
r
C
o
d
e
:
S
0
e
r
.
N
0
o
.
:
M
e
s
s
b
e
r
e
i
c
h
M
e
a
s
u
r
i
n
g
r
a
n
m
g
e
a
x
.
2
0
m
I
P 6
5
U
1
6
.
.
.
3
6
V
D
C
4
.
..
2
0
m
A
T>
7
A
0
°
C
:
t>85°
C
Made in Germany Maulburg
r
e
s
u
a
H
+
s
E
s
NDR
re
ES
d
n
S+
E
HA
U
M
S
ICR
ER
H
O
V
PI
LO
T
I
O
I
r
d
e
r
C
o
d
e
:
S
0
e
r
.
N
0
o
.
:
M
e
s
s
b
e
r
e
i
c
h
M
e
a
s
u
r
i
n
g
r
a
n
m
g
e
a
x
.
2
0
m
I
P 6
5
U
1
6
.
.
.3
6
V
D
C
4
.
.
.
2
0
m
A
T
>
7
A
0
°
C
:
t>85
°C
Made in Germany Maulburg
2
1
3
L00-FMR2xxxx-17-00-00-xx-013
Endress+Hauser15
Page 16
MountingMicropilot M FMR244 HART 4 to 20 mA
Beam angle
The beam angle is defined as the angle α where the energy density of the radar waves reaches half
the value of the maximum energy density (3dB-width). Microwaves are also emitted outside the
signal beam and can be reflected off interfering installations. Beam diameter W as function of
antenna type (beam angle α) and measuring distance D:
Antenna size (horn
diameter)
Beam angle α23°10°
Measuring distance
(D)
3 m (9.8 ft)1.22 m (4 ft)0.53 m (1.7 ft)
6 m (20 ft)2.44 m (8 ft)1.05 m (3.4 ft)
9 m (30 ft)3.66 m (12 ft)1.58 m (5.2 ft)
12 m (39 ft)4.88 m (16 ft)2.10 m (6.9 ft)
15 m (49 ft)6.10 m (20 ft)2.63 m (8.63 ft)
20 m (66 ft)8.14 m (27 ft)3.50 m (11 ft)
25 m (82 ft)10.17 m (33 ft)4.37 m (14 ft)
30 m (98 ft)⎯5.25 m (17 ft)
35 m (115 ft)⎯6.12 m (20 ft)
40 m (131 ft)⎯7.00 m (23 ft)
45 m (148 ft)⎯7.87 m (26 ft)
60 m (197 ft)⎯10.50 m (34 ft)
70 m (230 ft)⎯⎯
40 mm (1½")80 mm (3")
Beam diameter (W)
40 mm (1½")80 mm (3")
D
W
a
W
..
=
tan
2
D
L00-FMR2xxxx-14-00-06-de-027
a
_
2
16Endress+Hauser
Page 17
Micropilot M FMR244 HART 4 to 20 mAMounting
Measuring conditions in liquids
Note!
• In case of boiling surfaces, bubbling or tendency for foaming, use FMR230 or FMR231.
Depending on its consistence, foam can either absorb microwaves or reflect them off the foam
surface. Measurement is possible under certain conditions.
• In case of heavy steam development or condensate the max. measuring range of FMR240 may
decrease depending on density, temperature and composition of the steam → use FMR230 or
FMR231.
• For the measurement of absorbing gases such as ammonia NH
or some fluorocarbons 1),
3
please use FMR230 in a stilling well.
0%
A
B
C
ØD
H
L00-FMR2xxxx-17-00-00-de-009
100%
• The measuring range begins, where the beam hits the tank bottom. Particularly with dish bottoms
or conical outlets the level cannot be detected below this point.
• In case of media with a low dielectric constant (groups A and B), the tank bottom can be visible
through the medium at low levels (low height C). Reduced accuracy has to be expected in this
range. If this is not acceptable, we recommend positioning the zero point at a distance C (see Fig.)
above the tank bottom in these applications.
• In principle it is possible to measure up to the tip of the antenna with FMR230/231/240.
However, due to considerations regarding corrosion and build-up, the end of the measuring range
should not be chosen any closer than A (see Fig.) to the tip of the antenna.
For FMR244/245, the end of measuring range should not be chosen closer than A (see Fig.) to
the tip of the antenna, especially if there is development of condensate.
• The smallest possible measuring range B depends on the antenna version (see Fig.).
• The tank diameter should be greater than D (see Fig.), the tank height at least H (see Fig.).
150 (5.91)> 0.2 (> 0.7)50 to 250 (1.97 to 9.84)> 0.2 (> 0.7)> 0.3 (> 1.0)
1) Affected compounds are e. g. R134a, R227, Dymel 152a.
Endress+Hauser17
Page 18
MountingMicropilot M FMR244 HART 4 to 20 mA
Measuring conditions in solids
• The measuring range begins, where the beam hits the bottom. Particularly with conical outlets
the level cannot be detected below this point.
The maximum measuring range can be increased in such applications by using a top target
positioner (see Technical Information TI00345F/00/EN).
• In case of media with a low dielectric constant (groups A and B), the bottom can be visible through
the medium at low levels. In order to guarantee the required accuracy in these cases, it is
recommended to position the zero-point at a distance C above the bottom (see Fig.).
• In principle it is possible to measure up to the tip of the antenna with the Micropilot M. However,
due to considerations regarding abrasion and build-up and depending on the orientation of the
product surface (angel of repose), the end of the measuring range should be at a distance of A, see
Fig. If required, and if some conditions (high DC value, flat angle of repose) are met, shorter
distances can be achieved.
A
100%
Measuring range
0%
A [mm (in)]C [mm (in)]
approx. 400 (15.7)50 to 150 (1.97 to 5.91)
C
L00-FMR250xx-17-00-00-en-001
18Endress+Hauser
Page 19
Micropilot M FMR244 HART 4 to 20 mAMounting
Measuring range in liquids
The usable measuring range depends on the size of the antenna, the reflectivity of the medium, the
mounting location and eventual interference reflections.
The maximum configurable range is:
• 40 m (131 ft) for basic version
• 70 m (230 ft) with additional option F (G), → ä 7, "ordering information"
The following tables describe the groups of media as well as the achievable measuring range as a
function of application and media group. If the dielectric constant of a medium is unknown, it is
recommended to assume media group B to ensure a reliable measurement.
Media groupDC (εr)Examples
A1.4 to 1.9non-conducting liquids, e. g. liquefied gas
B1.9 to 4non-conducting liquids, e. g. benzene, oil, toluene, …
C4 to 10e. g. concentrated acids, organic solvents, esters, aniline, alcohol, acetone, …
D> 10conducting liquids, e. g. aqueous solutions, dilute acids and alkalis
1) Treat Ammonia NH3 as a medium of group A, i. e. use FMR230 in a stilling well.
1)
Measuring range in solids
The FMR244 with 80 mm (3") antenna or FMR240 with 100 mm (4") horn antenna and additional
option F (= advanced dynamics) is also suited for solid applications. The usable measuring range
depends on the reflection properties of the medium, the mounting position and interference
reflections which may be present. The maximum configurable measuring range for the Micropilot
M FMR240 with 100 mm (4") horn antenna and additional option F (= advanced dynamics) is
30 m (98 ft) in solid applications. It is recommended to use the variable flange seal for alignment
(see Technical Information TI00345F/00/EN).
Reduction of the max. possible measuring range through:
• Media with poor reflection properties (= small DC). For examples refer to table below.
• Angle of repose.
• Extremely loose surfaces of bulk solids, e. g. bulk solids with low bulk weight for pneumatic
filling.
• Build-up, above all of moist products.
The following table describes the media groups and the dielectric constant
Media groupDC (
A1.6 to 1.9
B1.9 to 2.5– Portland cement, plaster16 to 13 dB
C2.5 to 4
D4 to 7
E>7
εr)ExamplesSignal attenuation
– Plastic granulate
– White lime, special cement
–Sugar
– Grain, seeds
– Ground stones
–Sand
– Naturally moist (ground) stones, ores
–Salt
– Metallic powder
–Carbon black
–Coal
εr.
19 to 16 dB
13 to 10 dB
10 to 7 dB
< 7 dB
The respective lower group applies for very loose or loosened bulk solids.
Endress+Hauser19
Page 20
MountingMicropilot M FMR244 HART 4 to 20 mA
Measuring range depending on vessel type, conditions and product
Standard:
max. measuring range = 40 m (131 ft)
With additional option F (G):
max. measuring range = 70 m (230 ft)
min. measuring range = 5 m (16 ft)
max. recommended measuring range = 20 m (65 ft) with 80 mm (3") antenna, in solids 15 m (49 ft)
*
1) 2)
1) Larger measuring range in solids available on request.
2) In solids with additional option F (= advanced dynamic), and variable flange seal (see Technical Information
TI00345F/00/EN).
Storage tankBuffer tankProcess tank with agitatorStilling well
1)
Calm product surface (e. g. intermittent filling,
filling from bottom, immersion tubes).
40 mm (1½") 80 mm (3")40 mm (1½") 80 mm (3")40 mm (1½")80 mm (3")40 mm (1½")
AB
3
(9.9)
5
(16)
5
(16)
8
(26)
CD
10
(32)
15
15
(49)
(49)
25
(82)
**
AB
8
(26)
10
(32)
(49)
(65)
15
20
CD
**
30
(98)
40
(131)
Moving surfaces (e. g. continuous filling,
from above, mixing jets).
B
(131)
(197)
CD
2
(6.6)
4
(13)
5
(16)
40
60
(24)
(32)
AB
2.5
(8)
5
(16)
7.5
10
(16)
(32)
5
10
CD
10
(32)
15
15
(49)
(49)
*
25
(82)
Turbulent surface.
Single stage agitator <60 RPM.
(8.2)
B
2.5
(3.2)
B
1
CD
2
(6.6)
3
(9.8)
5
(16)
CD
5
(16)
8
(26)
12
(39)
15
(49)
A,B,C, D
Measuring range [m (ft)]
1) Larger measuring range on request
20
(65)
20Endress+Hauser
Page 21
Micropilot M FMR244 HART 4 to 20 mAMounting
3.4Installation instructions
3.4.1Mounting kit
In addition to the tool needed for flange mounting, you will require the following tool:
• A key AF60 for threaded boss
• 4 mm (0.16 in) Allen wrench for turning the housing.
3.4.2Installation in tank (free space)
Optimum mounting position
mark at threaded boss
G 1½”
or
90°90°
90°
90°
90°
90°
Caution!
Use only the
threaded boss
AF60
60
1½ NPT
max. torque
20 Nm (14.75 lbf ft)
Standard installation - 40 mm (1½")
antenna
When mounting in a tank, please observe
engineering hints (→ ä 14) and the following
points:
• Marker is aligned towards tank wall.
• Install the device using the threaded boss
(AF60) only. Observe the max. torque of
20 Nm (14.75 lbf ft).
• After mounting, the housing can be turned
350° in order to simplify access to the display
and the terminal compartment.
• For optimum measurement, the horn antenna
should extend below the nozzle. Nozzle
heights up to 500 mm (19.7 in) can be
accepted if this should not be possible due to
mechanical reasons.
Note!
Please contact Endress+Hauser for application
with higher nozzle.
• The antenna must be aligned vertically.
L00-FMR244xx-17-00-00-en-003
H
ØD
L00-FMR244xx-17-00-00-de-002
Antenna size40 mm (1½")
D [mm (in)]39 (1.54)
H [mm (in)]< 85 (< 3.35)
Endress+Hauser21
Page 22
MountingMicropilot M FMR244 HART 4 to 20 mA
Standard installation - 80 mm (3" antenna)
When mounting in a tank, please observe engineering hints (→ ä 14) and the following points:
• Marker is aligned towards tank wall.
• The marker is located directly below the housing neck on the stainless steel feedthrough.
• As an option for flange mounting, a variable flange seal (see TI00345F/00/EN) can be used to
align the device (solid applications).
• If using a mounting bracket, the device can be aligned at the bracket (solid applications), → ä 23.
• After mounting (flange), the housing can be turned 350° in order to simplify access to the display
and the terminal compartment.
H
ØD
L00-FMR244xx-17-00-00-xx-011
Antenna size80 mm (3")
D [mm (in)]80 (3.15)100 (3.94)150 (5.91)
H [mm (in)]< 500 (19.7)< 500 (19.7)< 500 (19.7)
22Endress+Hauser
Page 23
Micropilot M FMR244 HART 4 to 20 mAMounting
Mounting bracket
Dimensions:
R18
120 (4.72)
220 (8.66)
183 (7.2)
5.5 (0.22)
43
mm (in)
ø9
2.5
(0.1)
(1.69)
85 (3.35)
9
(0.35)
12
(0.47)
9
(0.35)
4xø5.5 (0.22)
12
0.47)
35
1.38)
L00-FMR244xx-06-00-00-xx-008
!
Note!
With T12 housing it‘s not possible to mount the device direct at the ceiling.
Endress+Hauser23
Page 24
MountingMicropilot M FMR244 HART 4 to 20 mA
3.4.3Installation in stilling well
Optimum mounting position
mark at threaded boss
G 1½”
or
1½ NPT
90°90°
Caution!
Use only the
threaded boss
AF60
60
max. torque
20 Nm (14.75 lbf ft)
L00-FMR244xx-17-00-00-en-004
Standard installation
For installations in a stilling well, follow the engineering hints (→ ä 14) and note the following
points:
• Marker is aligned toward slots.
• Install the device using the threaded boss (AF60) only. Observe the max. torque of
20 Nm (14.75 lbf ft).
• After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment.
• Measurements can be performed through an open full bore ball valve without any problems.
Recommendations for the stilling well
At the construction of a stilling well, please note the following points:
• Metal (no enamel coating, plastic coating on request).
• Constant diameter.
• Stilling well diameter not larger than antenna diameter.
• Weld seam as smooth as possible and on the same axis as the slots.
• Slots offset 180° (not 90°).
• Slot width respectively diameter of holes max. 1/10 of pipe diameter, de-burred. Length and
number do not have any influence on the measurement.
• At any transition (i. e. when using a ball valve or mending pipe segments), no gap may be created
exceeding 1 mm (0.04 in).
• The stilling well must be smooth on the inside (average roughness Rz ≤ 6.3 μm (≤ 248 μin)). Use
extruded or parallel welded stainless steel pipe. An extension of the pipe is possible with welded
flanges or pipe sleeves. Flange and pipe have to be properly aligned at the inside.
• Do not weld through the pipe wall. The inside of the stilling well must remain smooth. In case of
unintentional welding through the pipe, the weld seam and any unevenness on the inside need
to be carefully removed and smoothened. Otherwise, strong interference echoes will be generated
and material build-up will be promoted.
24Endress+Hauser
Page 25
Micropilot M FMR244 HART 4 to 20 mAMounting
Examples for the construction of stilling wells
Micropilot M
FMR 244
marker
threaded connection
G 1½" or 1½ NPT
100 %
< 1/10 ø pipe
stilling well
with slots
< 1/10 ø pipe
150…500
(5.91...19.7)
inside of
holes deburred
0.04<
< 1
gap
full bore
ball valve
Diameter of oof ball valvemust always
be equivalent to pipe diameter.
Avoid edges and constrictions.
pening
0%
L00-FMR244xx-17-00-00-en-005
mm (in)
Endress+Hauser25
Page 26
MountingMicropilot M FMR244 HART 4 to 20 mA
3.4.4Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment. Proceed as follows to turn the housing to the required position:
• Undo the fixing screws (1)
• Turn the housing (2) in the required direction
• Tighten up the fixing screws (1). Maximum torque 0.5 Nm (0.37 lbf ft).
F12 housingT12 housing
2
2
1
allen key
4 mm (0.16 in)
max. torque0.5Nm(0.37 lbf ft)
1
L00-FMR2xxxx-17-00-00-en-011
3.5Post-installation check
After the measuring instrument has been installed, perform the following checks:
• Is the measuring instrument damaged (visual check)?
• Does the measuring instrument correspond to the measuring point specifications such as process
temperature/pressure, ambient temperature, measuring range, etc.?
• Is the flange marking correctly aligned? (→ ä 10)
• Have the flange screws been tightened up with the respective tightening torque?
• Are the measuring point number and labeling correct (visual check)?
• Is the measuring instrument adequately protected against rain and direct sunlight (→ ä 65)?
26Endress+Hauser
Page 27
Micropilot M FMR244 HART 4 to 20 mAWiring
ENDRESS+HAUSER
4Wiring
4.1Quick wiring guide
Wiring in F12 housing
Beforeconnectionpleasenotethefollowing:
l
"
Caution!
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
supplied with acertificate, theexplosionprotection
Housing F12 - Ex ia:
Powersupply mustbeintrinsically safe.
?
The electronics and the current output are galvanically
separated from th
e antenna circuit.
Connect up the Micropilot M as follows:
?
Unscrew housing cover (2).
?
Remove any display (3) if fitted.
?
Remove cover plate from terminal compartment (4).
?
Pull outterminal moduleslightly using pulling loop.
?
Insert cable (5) through gland (6).
A standard installation cable is sufficient if only the analogue signal
is used. Use a screened cable when working with a superimposed
communications signal (HART).
Only ground screening of the line (7) on sensor side.
?
Makeconnection (seepinassignment).
?
Re-insert terminal module.
?
Tightencable gland (6).
?
Tightenscrewsoncoverplate (4).
?
Insertdisplay iffitted.
?
Screw on housing cover (2).
?
Switch on power supply.
5
power
alternatively
Unplug display connector!
#
3
R
E
S
U
A
H
+
S
S
E
R
D
N
E
6
4
Commubox FXA195
FieldCommunicator375, 475
7
4...20 mA
test sockets
(output current)
plant
4
2
3
1
L-
L+
I+
ground
I-
1234
Sealed terminal
compartment
L00-FMR2xxxx-04-00-00-en-011
Endress+Hauser27
Page 28
WiringMicropilot M FMR244 HART 4 to 20 mA
Wiring in T12 housing
Beforeconnectionpleasenotethefollowing:
●
"
Caution!
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Makesure you usethespecificcable gland.
Thepowersupply mustbeidentical tothedataonthe
nameplate (1).
●
Switch off power supply before connecting up the device.
Connect up t
Before unscrew housing cover (2) at seperate connection room
turn off the power supply!
●
Insert cable (3) through gland (4).
A standard installation cable is sufficient if only the analogue sig
used. Use a screened cable when working with a superimposed
communications signal (HART).
he Micropilot M as follows:
Only ground screening of the line (5) on sensor side.
●
Makeconnection (seepinassignment).
●
Tightencable gland (4).
●
Screw on housing cover (
●
Switch on power supply.
2).
power
alternatively
3
Commubox FXA195
Field Communicator 375, 475
5
nal is
4
testsockets
(outputcurrent)
plant
4
2
3
1
L-
L+
I+
ground
I-
1234
L00-FMR2xxxx-04-00-00-en-012
28Endress+Hauser
Page 29
Micropilot M FMR244 HART 4 to 20 mAWiring
4.2Connecting the measuring unit
Terminal compartment
Two housings are available:
• Aluminium housing F12 with additionally sealed terminal compartment for:
–standard,
– Ex ia.
• Aluminium housing T12 with separate terminal compartment for:
–standard,
–Ex e,
– Ex d,
– Ex ia (with overvoltage protection).
The electronics and current output are galvanically isolated from the antenna circuit.
F12 housing
sealed terminal
compartment
T12 housing
L00-FMR2xxxx-04-00-00-en-001
The instrument data are given on the nameplate together with important information regarding the
analog output and voltage supply. Housing orientation regarding the wiring, → ä 26.
Load HART
Minimum load for Hart communication: 250 Ω
Cable entry
Cable gland: M20x1.5 (for Ex d: cable entry)
Cable entry: G ½ or ½ NPT
Endress+Hauser29
Page 30
WiringMicropilot M FMR244 HART 4 to 20 mA
Supply voltage
The following values are the voltages across the terminals directly at the instrument:
Communication
HART
Fixed current, adjustable
e.g. for solar power
operation (measured value
transferred at HART)
Fixed current for HART
Multidrop mode
1) Short-term min. start-up voltage: 11.4 V
2) Start up current 11 mA.
standard
Ex ia
Ex em
Ex d
dust Ex
standard11 mA10 V
Ex ia11 mA10 V
standard4 mA
Ex ia4 mA
Current
consumption
4mA16V36V
20 mA7.5 V36 V
4mA16V30V
20 mA7.5 V30 V
4mA16V30V
20 mA11 V30 V
4 mA16 V30 V
20 mA11 V30 V
2)
2)
Terminal voltage
minimalmaximal
1)
1)
16 V36 V
16 V30 V
36 V
30 V
Power consumption
min. 60 mW, max. 900 mW
Current consumption
• Nennstrom: 3.6...22 mA, for HART-Multidrop: start up current is 11 mA
• Breakdown signal (NAMUR NE43): adjustable
Overvoltage protector
The level transmitter Micropilot M with T12-housing (housing version "D", → ä 7, "Ordering
structure") is equipped with an internal overvoltage protector (600 V surge arrester) according to
DIN EN 60079-14 or IEC 60060-1 (impulse current test 8/20 μs, Î = 10 kA, 10 pulses). Connect
the metallic housing of the Micropilot M to the tank wall or screen directly with an electrically
conductive lead to ensure reliable potential matching.
30Endress+Hauser
Page 31
Micropilot M FMR244 HART 4 to 20 mAWiring
1
234
1
234
4.2.1HART connection with Endress+Hauser RMA422 / RN221N
4...20 mA
ENDRESS + HAUSER
RMA 422
RMA422
RN221N
dsdmdm
df das.
asdas fa
asas la.
FMP40:LIC0001
ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
6
Page
Up
9
DeleteBksp
Page
On
# % &
A B C
D E F
2
1
3
Copy
Paste
Hot Key
G H I
J K L
M N O
4
5
6
Insert
+ Hot Key
P Q R S
T UV
W XY Z
8
7
9
, ( )‘
_ < >
+ * /
.
0
-
375
FIELD COMMUNICATOR
Field Communicator
375,475
FieldCare
Commubox
FXA195
L00-FMR2xxxx-04-00-00-xx-003
4.2.2HART connection with other supplies
DCpowersupply
unit
or
PLC
4...20 mA
dsdmdm
df das.
asdas fa
asas la.
FMP40:LIC0001
ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
6
Page
Up
9
DeleteBksp
Page
On
# % &
A B C
D E F
1
3
2
Copy
Paste
Hot Key
G H I
J K L
M N O
6
4
5
Insert
+ Hot Key
P Q R S
T UV
W XY Z
8
9
7
, ( )‘
_ < >
+ * /
-
.
0
375
FIELD COMMUNICATOR
Field Communicator
375,475
Caution!
"
If the HART communication resistor is not built into the supply unit, it is necessary to insert a
FieldCare
Commubox
FXA195
communication resistor of 250 Ω into the 2-wire line.
L00-FMR2xxxx-04-00-00-en-008
Endress+Hauser31
Page 32
WiringMicropilot M FMR244 HART 4 to 20 mA
4.3Recommended connection
4.3.1Equipotential bonding
Connect the equipotential bonding to the external ground terminal of the transmitter.
4.3.2Wiring screened cable
Caution!
"
In Ex applications, the screen must only be grounded on the sensor side. Further safety instructions
are given in the separate documentation for applications in explosion hazardous areas.
4.4Degree of protection
• with closed housing: IP65, NEMA4X (higher degree of protection e. g. IP68 on request)
• with open housing: IP20, NEMA1 (also ingress protection of the display)
• antenna: IP68 (NEMA6P)
4.5Post-connection check
After wiring the measuring instrument, perform the following checks:
• Is the terminal allocation correct (→ ä 27 und → ä 28)?
• Is the cable gland tight?
• Is the housing cover screwed tight?
• If auxiliary power is available:
Is the instrument ready for operation and does the liquid crystal display show any value?
32Endress+Hauser
Page 33
Micropilot M FMR244 HART 4 to 20 mAOperation
5Operation
5.1Quick operation guide
ENDRESS + HAUSER
–
+
E
X
F
3x
X
X
basic setup
O
safety settings
linearisation
extended calibr.
S
...
...
F
media type
liquids
O
solids
S
F
tank shape
dome ceiling
O
horizontal cyl
bypass
stilling well
flat ceiling
S
sphere
X
F
medium property
unknown
O
DC: < 1.9
DC: 1.9 ... 4
DC: 4 ... 10
DC: > 10
S
X
vessel / silo
F
Example - Selection and configuration in Operation menu:
1.) Change from Measured Value Display toby pressing
2.) Pressorto select the required(e.g.. "basic setup (00)") and confirm by pressing
3.) Activate Edit mode withor.
4) Pressto select the next(e.g. "medium property (003)")
5) Press+(=) oncereturn to previous(e.g. "tank shape (002)")
6) Press+(=) to return to
SO
First f
Ü
F
Note!
The active selection is marked by ain front of the menu text.
Selection menus:
a) Select the requiredin selected(e.g. "tank shape (002)") withor.
b)confirms selectionappears in front of the selected parameter
F
c)confirms the edited valuesystem quits Edit mode
F
d)+(=) interrupts selectionsystem quits Edit mode
OS X
Typing in numerals and text:
a) Pressorto edit the first character of the(e.g. "empty calibr. (005)")
b)positions the cursor at the next character(a) until you have completed your input
F
c) if asymbol appears at the cursor, pressto accept the value entered
• Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the instrument
are split up roughly into different function groups. The function groups that are available include,
e. g.: "basic setup", "safety settings", "output", "display", etc.
• Functions (001, 002, 003, …, 0D8, 0D9): Each function group consists of one or more
functions. The functions perform the actual operation or parameterisation of the instrument.
Numerical values can be entered here and parameters can be selected and saved. The available
functions of the “basic setup” (00) function group include, e. g.: "tank shape" (002),
"medium property" (003), "process cond." (004), "empty calibr." (005), etc.
If, for example, the application of the instrument is to be changed, carry out the following
procedure:
1.Select the “basic setup” (00) function group.
2.Select the "tank shape" (002) function (where the existing tank shape is selected).
5.1.2Identifying the functions
For simple orientation within the function menus (→ ä 86), for each function a position is shown
on the display.
L00-FMRxxxxx-07-00-00-en-005
The first two digits identify the function group:
• basic setup00
• safety settings01
• linearisation04
. . .
The third digit numbers the individual functions within the function group:
• basic setup00→ • tank shape002
• medium property003
• process cond.004
. . .
Hereafter the position is always given in brackets (e.g. "tank shape" (002)) after the described
function.
34Endress+Hauser
Page 35
Micropilot M FMR244 HART 4 to 20 mAOperation
E
N
DRES
S+HA
US
ER
M
I
CRO
PILO
TII
IP6
5
Order
C
ode
:
Ser.-No.:
Messberei
ch
Measur
ing
rang
e
U
16..
.36
V
DC
4
...
20
m
A
max.
20
m
MadeinGermanyMaulburg
T
>7
0°C
:
A
t>85
°C
5.2Display and operating elements
!
E
N
D
R
M
E
O
I
S
r
C
d
e
S
R
r
+
C
O
S
o
H
e
d
P
r
A
e
.-
I
:
N
L
U
o
O
.
S
:
T
E
RII
M
e
s
s
M
b
e
e
r
a
e
s
i
c
u
h
r
in
g
ra
n
g
e
U
m
1
a
6
x
.
.
.
4
.
2
3
.
.
0
6
.
2
m
V
0
D
m
C
A
I
P
6
5
T
A
>
7
0
°
C
:
t>85
°C
MadeinGermanyMaulburg
(liquid crystal display)
Symbols
LCD
ENDRESS + HAUSER
–
+
E
3 keys
snap-fit
L00-FMxxxxxx-07-00-00-en-001
Layout of the display and operating elements
The LCD display can be removed to ease operation by simply pressing the snap-fit (see graphic
above). It is connected to the device by means of a 500 mm (19.7 in) cable.
Note!
To access the display the cover of the electronic compartment may be removed even in hazardous
area (IS and XP).
Endress+Hauser35
Page 36
OperationMicropilot M FMR244 HART 4 to 20 mA
5.2.1Display
Liquid crystal display (LCD):
Four lines with 20 characters each. Display contrast adjustable through key combination.
HeadlinePositionindicator
ENDRESS + HAUSER
Main value
–
Function groups -> Functions
+
E
Symbol
Selection list
Bargraph
Unit
HOME
Display
F
X
O
S
FG00
FG01
FG02
FG03
FG04
FG05
FG06
FG07
...
F000 F001 F002 F003 F004 ...
X
F
FF
O
X
Helptext
S
X
Envelope
curve
5.2.2Display symbols
The following table describes the symbols that appear on the liquid crystal display:
SybmolMeaning
ALARM_SYMBOL
This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a
warning.
LOCK_SYMBOL
This lock symbol appears when the instrument is locked, i.e. if no input is possible.
L00-FMRxxxxx-07-00-00-en-002
COM_SYMBOL
This communication symbol appears when a data transmission via e.g. HART, PROFIBUS PA or
FOUNDATION Fieldbus is in progress.
36Endress+Hauser
Page 37
Micropilot M FMR244 HART 4 to 20 mAOperation
5.2.3Key assignment
The operating elements are located inside the housing and are accessible for operation by opening
the lid of the housing.
Function of the keys
Key(s)Meaning
O
S
X
O
S
and S and
O
or
or
or
F
and
or
and
V
W
Z
F
F
Navigate upwards in the selection list.
Edit numeric value within a function.
Navigate downwards in the selection list.
Edit numeric value within a function.
Navigate to the left within a function group.
Navigate to the right within a function group, confirmation.
Contrast settings of the LCD.
Hardware lock / unlock
After a hardware lock, an operation of the instrument via display or
communication is not possible!
F
The hardware can only be unlocked via the display. An unlock parameter must
be entered to do so.
Endress+Hauser37
Page 38
OperationMicropilot M FMR244 HART 4 to 20 mA
5.3Local operation
5.3.1Locking of the configuration mode
The Micropilot can be protected in two ways against unauthorised changing of instrument data,
numerical values or factory settings:
Function "unlock parameter" (0A4):
A value <> 100 (e. g. 99) must be entered in "unlock parameter" (0A4) in the
"diagnostics" (0A) function group. The lock is shown on the display by the symbol and can be
released again either via the display or by communication.
Hardware lock:
The instrument is locked by pressing the
The lock is shown on the display by the symbol and can only be unlocked again
via the display by pressing the
the hardware by communication. All parameters can de displayed even if the instrument is locked.
and F keys at the same time again. It is not possible to unlock
O, S
and F keys at the same time.
O, S
ENDRESS + HAUSER
–
+
E
⇒
⇓
⇓
and F press simultaneous
O, S
The LOCK_SYMBOL appears on the LCD.
38Endress+Hauser
Page 39
Micropilot M FMR244 HART 4 to 20 mAOperation
5.3.2Unlocking of configuration mode
If an attempt is made to change parameters on display when the instrument is locked, the user is
automatically requested to unlock the instrument:
Function "unlock parameter" (0A4):
By entering the unlock parameter (on the display or via communication)
100 = for HART devices
the Micropilot is released for operation.
Hardware unlock:
ENDRESS + HAUSER
–
+
After pressing the
parameter
100 = for HART devices.
⇒
E
and F keys at the same time, the user is asked to enter the unlock
O, S
and F press simultaneous
O, S
⇓
Please enter unlock code and confirm with F.
⇓
Caution!
"
Changing certain parameters such as all sensor characteristics, for example, influences numerous
functions of the entire measuring system, particularly measuring accuracy. There is no need to
change these parameters under normal circumstances and consequently, they are protected by a
special code known only to the Endress+Hauser service organization.
Please contact Endress+Hauser if you have any questions.
Endress+Hauser39
Page 40
OperationMicropilot M FMR244 HART 4 to 20 mA
5.3.3Factory settings (Reset)
Caution!
"
A reset sets the instrument back to the factory settings. This can lead to an impairment of the
measurement. Generally, you should perform a basic setup again following a reset.
A reset is only necessary if the instrument...
• ... no longer functions.
• ... must be moved from one measuring point to another.
• ... is being de-installed /put into storage/installed.
ENDRESS + HAUSER
–
⇒
+
E
User input ("reset" (0A3)):
• 333 = customer parameters
333 = reset customer parameters
This reset is recommended whenever an instrument with an unknown "history" is to be used in an
application:
• The Micropilot is reset to the default values.
• The customer specific tank map is not deleted.
• A linearisation is switched to "linear" although the table values are retained. The table can be
reactivated in the "linearisation" (04) function group.
List of functions that are affected by a reset:
• tank shape (002) - liquids only
• vessel / silo (00A) - solids only
• empty calibr. (005)
• full calibr. (006)
• pipe diameter (007) - liquids only
• output on alarm (010)
• output on alarm (011)
• outp. echo loss (012)
• ramp %span/min (013)
• delay time (014)
• safety distance (015)
• in safety dist. (016)
• level/ullage (040)
• linearisation (041)
• customer unit (042)
• diameter vessel (047)
• range of mapping (052)
• pres. Map dist (054)
• offset (057)
• low output limit (062)
• fixed current (063)
• fixed cur. value (064)
• simulation (065)
• simulation value (066)
• 4mA value (068)
•20mA value (069)
• format display (094)
• distance unit (0C5)
• download mode (0C8)
The tank map can also be reset in the "mapping" (055) function of the "extended calibr." (05)
function group.
This reset is recommended whenever an instrument with an unknown "history" is to be used in an
application or if a faulty mapping was started:
• The tank map is deleted. The mapping must be recommenced.
40Endress+Hauser
Page 41
Micropilot M FMR244 HART 4 to 20 mAOperation
5.4Display and acknowledging error messages
Types of errors
Errors that occur during commissioning or measuring are displayed immediately on the local
display. If two or more system or process errors occur, the error with the highest priority is the one
shown on the display.
The measuring system distinguishes between two types of errors:
• A (Alarm):
Instrument goes into a defined state (e. g. max 22 mA)
Indicated by a constant symbol.
(For a description of the codes, → ä 68)
• W (Warning):
Instrument continue measuring, error message is displayed.
Indicated by a flashing symbol.
(For a description of the codes, → ä 68)
• E (Alarm / Warning):
Configurable (e. g. loss of echo, level within the safety distance)
Indicated by a constant/flashing symbol.
(For a description of the codes, → ä 68)
ENDRESS + HAUSER
–
+
⇒
E
5.4.1Error messages
Error messages appear as four lines of plain text on the display. In addition, a unique error code is
also output. A description of the error codes, → ä 68.
•The "diagnostics" (0A) function group can display current errors as well as the last errors that
occurred.
• If several current errors occur, use
• The last occurring error can be deleted in the "diagnostics" (0A) function group
with the funktion"clear last error" (0A2).
or S to page through the error messages.
O
Endress+Hauser41
Page 42
OperationMicropilot M FMR244 HART 4 to 20 mA
5.5HART communication
Apart from local operation, you can also parameterise the measuring instrument and view measured
values by means of a HART protocol. There are two options available for operation:
• Operation via the universal handheld operating unit, the HART Field Communicator 375, 475.
• Operation via the Personal Computer (PC) using the operating program FieldCare (→ ä 31).
!
Note!
The Micropilot M can also be operated locally using the keys. If operation is prevented by the keys
being locked locally, parameter entry via communication is not possible either.
5.5.1Handheld unit Field Communicator 375, 475
All device functions can be adjusted via menu operation with the handheld unit Field
Communicator 375, 475.
Menu operation with the DXR375 handheld instrument
Note!
Further information on the HART handheld unit is given in the respective operating manual
included in the transport bag of the instrument.
42Endress+Hauser
Page 43
Micropilot M FMR244 HART 4 to 20 mAOperation
5.5.2Endress+Hauser operating program
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare,
you can configure all Endress+Hauser devices as well as devices from other manufacturers that
support the FDT standard. Hardware and software requirements you can find on the internet:
www.endress.com ➞ select your country ➞ search: FieldCare ➞ FieldCare ➞ Technical Data.
FieldCare supports the following functions:
• Configuration of transmitters in online operation
• Singal analysis via envelope curve
• Tank linearisation
• Loading and saving device data (upload/download)
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA195 and the USB port on a computer
• Commubox FXA291 with ToF Adapter FXA291 (USB) via service interface
Menu-guided commissioning
MicropilotM-en-305
Endress+Hauser43
Page 44
OperationMicropilot M FMR244 HART 4 to 20 mA
Signal analysis via envelope curve
Tank linearisation
MicropilotM-en-306
MicropilotM-en-307
44Endress+Hauser
Page 45
Micropilot M FMR244 HART 4 to 20 mACommissioning
6Commissioning
6.1Function check
Make sure that all final checks have been completed before you start up your measuring point:
• Checklist "Post installation check", → ä 26.
• Checklist "Post connection check", → ä 32.
6.2Switching on the measuring device
When the instrument is switched on for the first time, the following messages appear in a sequence
of 5 s on the display: software version, communication protocol and language selection.
ENDRESS + HAUSER
–
⇒
+
E
Select the language (this message appears the first time
the instrument is switched on)
⇓
⇓
⇓
Select the basic unit (this message appears the first time
the instrument is switched on)
The current measured value is displayed
After F is pressed, you reach the group selection
This selection enables you to perform the basic setup
Endress+Hauser45
Page 46
CommissioningMicropilot M FMR244 HART 4 to 20 mA
6.3Basic Setup
media typemedia type
liquidsolid
tank shapevessel / silo
metal silodome ceiling
measuring cond.measuring cond.
unknown
measuring cond.measuring cond.
Standard
empty calibr.empty calibr.
unknown
Standard
basic setup (standard - solids)
full calibr.full calibr.
level measurement in liquids
flange:
referencepoint of
measurement
SD
D
E
F
L
level measurement in solids
basic setup (standard - liquids)
pipe diameter
(for bypass/stilling well)
mapping
safety settings
linearisation
option
extended calibr.
...
mapping
flange:
referencepoint of
measurement
SD
D
E
F
L
E = empty calibr. (= zero), setting in 005
F = full calibr. (= span), setting in 006
D = distance (distance flange / product), display in 0A5
L = level, display in 0A6
SD = safety distance, setting in 015
(description see BA291F/00/EN)
L00-FMR244xx-19-00-00-en-001
46Endress+Hauser
Page 47
Micropilot M FMR244 HART 4 to 20 mACommissioning
Caution!
"
The basic setup is sufficient for successful commissioning in most applications. Complex measuring
operations necessitate additional functions that the user can use to customise the Micropilot as
necessary to suit his specific requirements. The functions available to do this are described in detail
in the BA00291F/00/EN.
Comply with the following instructions when configuring the functions in the "basic setup" (00):
• Select the functions as described, → ä 33.
• Some functions can only be used depending on the parameterisation of the instrument. For
example, the pipe diameter of a stilling well can only be entered if "stilling well" was selected
beforehand in the "tank shape" (002) function.
• Certain functions (e. g. starting an interference echo mapping (053)) prompt you to confirm your
!
data entries. Press
• If you do not press a key during a configurable time period (→ function group "display" (09)),
an automatic return is made to the home position (measured value display).
Note!
• The instrument continues to measure while data entry is in progress, i. e. the current measured
values are output via the signal outputs in the normal way.
• If the envelope curve mode is active on the display, the measured values are updated in a slower
cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has
been optimised.
• If the power supply fails, all preset and parameterised values remain safely stored in the EEPROM.
• All functions are described in detail, as is the overview of the operating menu itself, in the manual
"BA00291F - Description of the instrument functions", which is found on the enclosed
CD-ROM.
• The default values of the parameters are typed in boldface.
or S to select "YES" and press F to confirm. The function is now started.
O
Endress+Hauser47
Page 48
CommissioningMicropilot M FMR244 HART 4 to 20 mA
6.4Basic Setup with the device display
Function "measured value" (000)
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
E
E
E
⇒
This function displays the current measured value in the selected unit
(see "customer unit" (042) function). The number of digits after decimal point can be selected in
the "no.of decimals" (095) function.
6.4.1Function group "basic setup" (00)
⇒
Function "media type" (001)
⇒
This function is used to select the media type.
Selection:
• liquid
• solid
With the selection "liquid" the
following functions can be adjusted:
With the selection "solids" the
following functions can be adjusted:
• tank shape002• vessel / silo00A
• medium property003• medium property00B
• process cond.004• process cond.00C
• empty calibr.005• empty calibr.005
• full calibr.006• full calibr.006
• pipe diameter007• check distance051
• check distance051• range of mapping052
• range of mapping052• start mapping053
•start mapping053•. . .
•. . .
48Endress+Hauser
Page 49
Micropilot M FMR244 HART 4 to 20 mACommissioning
Function "tank shape" (002), liquids only
ENDRESS + HAUSER
–
⇒
+
E
This function is used to select the tank shape.
Selection:
• dome ceiling
• horizontal cyl
•bypass
• stilling well
• flat ceiling
•sphere
dome ceiling
horizontal cyl
ENDRESS + HAUSER
–
+
bypassstilling well
flat ceilingsphere
L00-FMR2xxxx-14-00-06-en-007
Function "medium property" (003), liquids only
⇒
E
This function is used to select the dielectric constant.
Selection:
• unknown
•DC: < 1.9
• DC: 1.9 ... 4
• DC: 4 ... 10
•DC: > 10
Product classDC (εr)Examples
A1.4 to 1.9non-conducting liquids, e. g. liquefied gas
B1.9 to 4non-conducting liquids, e. g. benzene, oil, toluene, …
C4 to 10e. g. concentrated acids, organic solvents, esters, aniline, alcohol, acetone, …
D>10conducting liquids, e. g. aqueous solutions, dilute acids and alkalis
1)
1) Treat Ammonia NH3 as a medium of group A, i. e. use FMR 230 in a stilling well.
Endress+Hauser49
Page 50
CommissioningMicropilot M FMR244 HART 4 to 20 mA
Function "process cond." (004) , liquids only
ENDRESS + HAUSER
–
⇒
+
E
This function is used to select the process conditions.
Selection:
• standard
• calm surface
• turb. surface
• agitator
• fast change
• test:no filter
standardcalm surfaceturb. surface
For all applications that do not fit into
any of the following groups.
Storage tanks with immersion tube or
bottom filling.
Storage / buffer tanks with rough
surface due to free filling or mixer
nozzles.
The filter and output damping are set
to average values.
agitatorfast changetest:no filter
Agitated surfaces (with possible
vortex) due to agitators.
Special filters to smooth the input
signals are set to high values.
→ smoothed meas. value
→ medium fast reaction time
→ minimization of effects by agitator
blades
The averaging filters and output
damping are set to high values.
→ steady meas. value
→ precise measurement
→ slower reaction time
Rapid change of level, particularly in
small tanks.
The averaging filters are set to low
values. The output damping is set to 0.
→ rapid reaction time
→ possibly unsteady meas. value
Special filters to smooth the input
signals are emphasised.
→ smoothed meas. value
→ medium fast reaction time
All filters can be switched off for service
/ diagnostic purposes.
All filters off.
50Endress+Hauser
Page 51
Micropilot M FMR244 HART 4 to 20 mACommissioning
Function "vessel / silo" (00A), solids only
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
⇒
E
This function is used to select the vessel / silo.
Selection:
• unknown
• metal silo
• concrete silo
•bin / bunker
•dome
• stockpile
• conveyor belt
Function "medium property" (00B), solids only
⇒
E
This function is used to select the dielectric constant.
Selection:
• unknown
• DC: 1.6 ... 1.9
• DC: 1.9 ... 2.5
• DC: 2.5 ... 4
• DC: 4 ... 7
•DC: > 7
Media groupDC (εr)Examples
– Plastic granulate
A1.6 to 1.9
B1.9 to 2.5– Portland cement, plaster
C2.5 to 4
D4 to 7
E>7
– White lime, special cement
–Sugar
– Grain, seeds
–Ground stones
–Sand
– Naturally moist (ground) stones, ores
–Salt
– Metallic powder
– Carbon black
–Coal
The respective lower group applies for very loose or loosened bulk solids.
Endress+Hauser51
Page 52
CommissioningMicropilot M FMR244 HART 4 to 20 mA
Function "process cond." (00C), solids only
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
E
E
⇒
This function is used to select the process conditions.
Selection:
• standard
• fast change
• slow change
• test:no filter
Function "empty calibr." (005)
⇒
This function is used to enter the distance from the flange (reference point of the measurement) to
the minimum level (=zero).
L00-FMR2xxxx-14-00-06-en-008
Caution!
"
For dish bottoms or conical outlets, the zero point should be no lower than the point at which the
radar beam hits the bottom of the tank.
52Endress+Hauser
Page 53
Micropilot M FMR244 HART 4 to 20 mACommissioning
Function "full calibr." (006)
ENDRESS + HAUSER
–
⇒
+
E
This function is used to enter the distance from the minimum level to the maximum level (=span).
L00-FMR2xxxx-14-00-06-en-009
!
Note!
•If bypass or stilling well was selected in the "tank shape" (002) function, the pipe diameter is
requested in the following step.
• For FMR244, the end of measuring range should not be chosen closer than 150 mm (5.91 in) to
the tip of the antenna, especially if there is development of condensate.
ENDRESS + HAUSER
–
+
Function "pipe diameter" (007)
⇒
E
This function is used to enter the pipe diameter of the stilling well or bypass pipe.
100%
0%
ø
100%
0%
ø
L00-FMR2xxxx-14-00-00-en-011
Microwaves propagate more slowly in pipes than in free space. This effect depends on the inside
diameter of the pipe and is automatically taken into account by the Micropilot. It is only necessary
to enter the pipe diameter for applications in a bypass or stilling well.
Endress+Hauser53
Page 54
CommissioningMicropilot M FMR244 HART 4 to 20 mA
Fuction "dist./meas.value" (008)
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
E
E
⇒
The distance measured from the reference point to the product surface and the level calculated
with the aid of the empty adjustment are displayed. Check whether the values correspond to the
actual level or the actual distance. The following cases can occur:
• Distance correct − level correct → continue with the next function, "check distance" (051)
• Distance incorrect − level incorrect → continue with the next function, "check distance" (051)
Function "check distance" (051)
⇒
This function triggers the mapping of interference echoes. To do so, the measured distance must be
compared with the actual distance to the product surface. The following options are available for
selection:
Selection:
•distance = ok
• dist. too small
• dist. too big
• dist. unknown
• manual
L00_FMR2xxxxx-14-00-06-en-010
distance = ok
• mapping is carried out up to the currently measured echo
• The range to be suppressed is suggested in the "range of mapping" (052) function
Anyway, it is wise to carry out a mapping even in this case.
dist. too small
• At the moment, an interference is being evaluated
• Therefore, a mapping is carried out including the presently measured echoes
• The range to be suppressed is suggested in the "range of mapping" (052) function
54Endress+Hauser
Page 55
Micropilot M FMR244 HART 4 to 20 mACommissioning
dist. too big
• This error cannot be remedied by interference echo mapping
• Check the application parameters (002), (003), (004) and "empty calibr." (005)
dist. unknown
If the actual distance is not known, no mapping can be carried out.
manual
A mapping is also possible by manual entry of the range to be suppressed. This entry is made in the
"range of mapping" (052) function.
Caution!
"
The range of mapping must end 0,5 m (1.6 ft) before the echo of the actual level. For an empty tank,
do not enter E, but E – 0,5 m (1.6 ft). If a mapping already exists, it is overwriten up to the distance
specified in "range of mapping" (052). Beyond this value the existing mapping remains
unchanged.
Function "range of mapping" (052)
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
⇒
E
This function displays the suggested range of mapping. The reference point is always the reference
point of the measurement (→ ä 46). This value can be edited by the operator.
For manual mapping, the default value is 0 m.
Function "start mapping" (053)
⇒
E
This function is used to start the interference echo mapping up to the distance given in "range of
mapping" (052).
Selection:
• off → no mapping is carried out
•on → mapping is started
During the mapping process the message "record mapping" is displayed.
Caution!
"
A mapping will be recorded only, if the device is not in alarm-state.
Endress+Hauser55
Page 56
CommissioningMicropilot M FMR244 HART 4 to 20 mA
Function "dist./meas.value" (008)
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
E
E
⇒
The distance measured from the reference point to the product surface and the level calculated
with the aid of the empty adjustment are displayed. Check whether the values correspond to the
actual level or the actual distance. The following cases can occur:
• Distance correct − level correct → continue with the next function, "check distance" (051)
• Distance incorrect − level incorrect → continue with the next function, "check distance" (051)
⇒
⇓
After 3 s, the following message appears
56Endress+Hauser
Page 57
Micropilot M FMR244 HART 4 to 20 mACommissioning
6.4.2Envelope curve with device display
After the basic setup, an evaluation of the measurement with the aid of the envelope curve
("envelope curve" (0E) function group) is recommended.
Function "plot settings" (0E1)
ENDRESS + HAUSER
–
+
ENDRESS + HAUSER
–
+
⇒
E
⇒
E
!
Select which information will be displayed in the LCD:
• envelope curve
• env.curve+FAC (on FAC see BA00291F/00/EN)
• env.curve+cust.map (i. e. customer tank map is also displayed)
Function "recording curve" (0E2)
This function defines whether the envelope curve is read as a
• single curve
or
• cyclic.
Note!
• If the cyclical envelope curve is active in the display, the measured value is refreshed in a slower
cycle time. It is therefore recommended to exit the envelope curve display after optimising the
measuring point.
•An orientation of the Micropilot can help to optimise measurement in applications with very
weak level echos or strong interference echos by increasing the useful echo/reducing the
interference echo ("Orientation of the Micropilot", → ä 73).
Endress+Hauser57
Page 58
CommissioningMicropilot M FMR244 HART 4 to 20 mA
Function "envelope curve display" (0E3)
The envelope curve is displayed in this function. You can use it to obtain the following information:
envelope curve
only
envelope curve and
interference echo
suppression (map)
full calibr.
minimum distance
of the plot
map
interference echo
quality of
evaluated echo
distance of
evaluated echo
evaluated echo
is marked
empty calibr.
maximum distance
of the plot
level echo
L00-FMU4xxxx-07-00-00-en-003
Navigating in the envelope curve display
Using navigation, the envelope curve can be scaled horizontally and vertically and shifted to the left
or the right. The active navigation mode is indicated by a symbol in the top left hand corner of the
display.
Horizontal Zoom mode:
- h-orizontal zoom in
OE3
…
horizontal zoom out
Move mode:
- m-oved to the left
moved to the right
Vertical Zoom mode:
- vertical zoom (4 steps)
Horizontal Zoom mode
Firstly, go into the envelope curve display. Then press
or S to switch to the envelope curve
O
navigation. You are then in Horizontal Zoom mode. Either or is displayed.
•
increases the horizontal scale.
O
•
reduces the horizontal scale.
S
S
O
L00-FMxxxxxx-07-00-00-en-004
L00-FMxxxxxx-07-00-00-yy-007
58Endress+Hauser
Page 59
Micropilot M FMR244 HART 4 to 20 mACommissioning
Move mode
Then press
•
shifts the curve to the right.
O
•
shifts the curve to the left.
S
Vertical Zoom mode
Press
F
options.
•
increases the vertical scale.
O
•
reduces the vertical scale.
S
The display icon shows the current zoom factor ( to ).
to switch to Move mode. Either or is displayed.
F
S
once more to switch to Vertical Zoom mode. is displayed. You now have the following
S
O
O
L00-FMxxxxxx-07-00-00-yy-008
L00-FMxxxxxx-07-00-00-yy-009
ENDRESS + HAUSER
–
+
Exiting the navigation
•Press
•Press
reactivate the "recording curve" (0E2) function does the Micropilot use the standard display
again.
⇒
E
again to run through the different modes of the envelope curve navigation.
F
and S to exit the navigation. The set increases and shifts are retained. Only when you
O
⇓
After 3 s, the following message appears
Endress+Hauser59
Page 60
CommissioningMicropilot M FMR244 HART 4 to 20 mA
6.5Basic Setup with the Endress+Hauser operating
program
To carry out the basic setup with the operating program, proceed as follows:
• Start the operating program and establish a connection.
• Select the "basic setup" function group in the navigation window.
The following display appears on the screen:
Basic Setup step 1/4:
•media type
–if "liquid" is selected in the "media type" function for level measurement in liquids
–if "solid" is selected in the "media type" function for level measurement in solids
!
Note!
Each parameter that is changed must be confirmed with the RETURN key!
•The "Next" button moves you to the next screen display:
MicropilotM-en-319
60Endress+Hauser
Page 61
Micropilot M FMR244 HART 4 to 20 mACommissioning
Basic Setup step 2/4:
• Enter the application parameters:
– Tank shape
– Medium property
– Process cond.
MicropilotM-en-302
Basic Setup step 3/4:
If "dome ceiling", "horizontal cyl", "..." is selected in the "tank shape" function, the following
display appears on the screen:
• Empty calibr.
• Full calibr.
MicropilotM-en-303
Endress+Hauser61
Page 62
CommissioningMicropilot M FMR244 HART 4 to 20 mA
Basic Setup step 4/4:
• This step starts the tank mapping
• The measured distance and the current measured value are always displayed in the header
MicropilotM-en-304
6.5.1Signal analysis via envelope curve
After the basic setup, an evaluation of the measurement using the envelope curve is recommended.
MicropilotM-en-306
!
62Endress+Hauser
Note!
If the level of echo is very weak or there is a heavy interference echo, an orientation of the
Micropilot can help optimise the measurement (increase of the useful echo/reduction of the
interference echo).
Page 63
Micropilot M FMR244 HART 4 to 20 mACommissioning
6.5.2User-specific applications (operation)
For details of setting the parameters of user-specific applications, see separate documentation
BA00291F/00/EN "Description of Instrument Functions" on the enclosed CD-ROM.
Endress+Hauser63
Page 64
MaintenanceMicropilot M FMR244 HART 4 to 20 mA
7Maintenance
The Micropilot M measuring instrument requires no special maintenance.
Exterior cleaning
When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the
surface of the housing and the seals.
Replacing seals
The process seals of the sensors must be replaced periodically, particularly if molded seals (aseptic
construction) are used. The period between changes depends on the frequency of cleaning cycles
and on the temperature of the measured substance and the cleaning temperature.
Repairs
The Endress+Hauser repair concept assumes that the measuring devices have a modular design and
that customers are able to undertake repairs themselves (→ ä 75, "Spare Parts"). Please contact
Endress+Hauser Service for further information on service and spare parts.
Repairs to Ex-approved devices
When carrying out repairs to Ex-approved devices, please note the following:
• Repairs to Ex-approved devices may only be carried out by trained personnel or by
Endress+Hauser Service.
• Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA) and
certificates.
• Only use original spare parts from Endress+Hauser.
• When ordering a spare part, please note the device designation on the nameplate. Only replace
parts with identical parts.
• Carry out repairs according to the instructions. On completion of repairs, carry our the specified
routine test on the device.
• Only Endress+Hauser Service may convert a certified device into a different certified variant.
• Document all repair work and conversions.
Replacement
After a complete Micropilot or electronic module has been replaced, the parameters can be
downloaded into the instrument again via the communication interface. Prerequisite to this is that
the data were uploaded to the PC beforehand using the FieldCare.
Measurement can continue without having to carry out a new setup.
• You may have to activate linearisation (see BA00291F/00/EN on the enclosed CD-ROM).
• You may need to record the tank map again (see Basic Setup).
After an antenna component or electronic has been replaced, a new calibration must be carried out.
This is described in the repair instructions.
64Endress+Hauser
Page 65
Micropilot M FMR244 HART 4 to 20 mAAccessories
ENDRESS+HAUSER
MICROPILOT II
IP 65
Order Code:
Ser.-No.:
Messbereich
Measuring range
U 16...36V DC
4...20 mA
max.20 m
Made in Germany Maulburg
T >70°C :
A
t >85°C
8Accessories
Various accessories, which can be ordered separately from Endress+Hauser, are available for the
Micropilot M.
8.1Weather protection cover
A Weather protection cover made of stainless steel is recommended for outdoor mounting (order
code: 543199-0001). The shipment includes the protective cover and tension clamp.
240 (9.45)
ENDRESS+HAUSER
MICROPILOT II
O
rde
r C
S
o
e
de
r
.-N
o
.:
M
e
s
sb
M
e
e
re
a
su
ich
r
in
g
r
U
1
6...3
4...2
0
:
a
n
g
e
m
a
x.
2
0
6
m
V
D
m
C
A
T>
A
7
0
°C
:
t
F12 /T12 housing
>
8
5
°
C
Made in Germany Maulburg
70 (2.76)
mm (in)
8.2Commubox FXA195 HART
For intrinsically safe communication with FieldCare via the USB interface.
For details refer to TI00404F/00/EN.
135 (5.31)
95 (3.74)
45°
L00-FMR2xxxx-00-00-06-en-001
8.3Commubox FXA291
The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface
(= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a
notebook. For details refer to TI00405C/07/EN.
!
Note!
For the instrument you need the "ToF Adapter FXA291" as an additional accessory.
8.4ToF Adapter FXA291
The ToF Adapter FXA291 connects the Commubox FXA291 via the USB interface of a personal
computer or a notebook for the instrument. For details refer to KA00271F/00/A2.
Endress+Hauser65
Page 66
AccessoriesMicropilot M FMR244 HART 4 to 20 mA
ENDRESS+HAUSER
IP 65
Order Code:
Ser.-No.:
Messbereich
Measuring range
U 16...36V DC
4...20 mA
max.20 m
Made in Germany Maulburg
T >70°C :
A
t >85°C
8.5Remote display FHX40
Wall-mounting
(withoutmounting bracket)
Separate housing
FHX40 (IP 65)
Cable
122 (4.8)
106 (4.71)
O
r
d
er
C
S
e
r
.
-N
M
es
sb
M
e
a
s
u
U
4
ENDRESS+HAUSER
o
d
e
o
.:
e
re
ic
h
r
i
ng
r
1
6
.
..
.
..2
0
:
a
n
g
e
m
a
x
.
20
36
m
V
D
m
C
A
T>7
A
Micropilot M
Levelflex M
Prosonic M
0
°
C
:
t >85
°C
Made in Germany Maulburg
122
(4.8)
(0.25)
150 (5.91)
80
(3.51)
120 (4.72)
6,3
82 (3.23)
mm (in)
Technical data (cable and housing) and product structure:
Max. cable length20 m (66 ft)
Temperature range-30 °C to +70 °C (-22 °F to +158 °F)
Degree of protectionIP65/67 (housing); IP68 (cable) acc. to IEC 60529
A Non-hazardous area
2 ATEX II 2G Ex ia IIC T6
3 ATEX II 2D Ex ia IIIC T80°C
G IECEx Zone1 Ex ia IIC T6/T5
S FM IS Cl. I Div.1 Gr. A-D, zone 0
U CSA IS Cl. I Div.1 Gr. A-D, zone 0
N CSA General Purpose
K TIIS Ex ia IIC T6
C NEPSI Ex ia IIC T6/T5
Y Special version, TSP-no. to be spec.
020Cable
1 20m / 65ft: for HART
5 20m / 65ft: for PROFIBUS PA/FOUNDATION Fieldbus
9 Special version, TSP-no. to be spec.
030Additional option
A Basic version
B Mounting bracket, pipe 1"/ 2"
Y Special version, TSP-no. to be spec.
995Marking
FHX40 -Complete product designation
1 Tagging (TAG), see additional spec.
For connection of the remote display FHX40 use the cable which fits the communication version of
the respective instrument.
66Endress+Hauser
Page 67
Micropilot M FMR244 HART 4 to 20 mATrouble-shooting
9Trouble-shooting
9.1Trouble-shooting instructions
Micropilot M FMR 2xx -Trouble Shooting
Instrument does
not respond
Check voltage and
compare it with the
specifications on the
nameplate.
ok
Check the polarity
of the voltage.
ok
Not ok
Not ok
Connect the
correct voltage
Correct the polarity
Instrument works?Ready
No
Instrument works?
No
Yes
Yes
Ready
Values on display
invisible
No
Output current
< 3,6 mA ?
HART
communication
does not
function
Communication
PA does not
function
Check power connection
to electronic board
Yes
Contrast:
Not ok
Check plug contact
of the display.
Output current between
3.6 …22mA ?
Yes
Check cabling
Possibly defective electronics
Contact E+H Service
Is the communication
Yes
resistor installed
according to the
OM?
Is the Commubox
connected according
to the OM?
Is the switch on the
Commubox for
selecting HART/Intensor
in the correct position?
Yes
Check cabling +
terminator
Not ok
Connect plug
ok
FO+
ok
ok
ok
ok
ok
ok
ok
Not ok
Connect the plug
correctly
Yes
The display is possibly defective.
Not ok
Not ok
Not ok
Not ok
Not ok
Contact E+H Service
Correct the
cabling
Install the resistor
(see the OM)
Connect the
Commubox
(see the OM)
Set the switch
correctly
Correct cabling +
terminator
No
Instrument works?
No
Display works?
No
Current is ok?Ready
No
Communication ok?
No
Communication ok?
No
Communication ok
No
Communication ok?
No
Yes
Ready
Ready
Yes
Ready
Yes
Yes
Ready
Yes
Ready
Yes
?
Ready
Contact E+H Service
Yes
Ready
Check screening
Communication
via Service adapter
does not function
Instrument
measures
incorrectly
EMC interference?
Yes
Check configuration
of COM port on PC
Yes
Check basic setup
Proceed according
to section
'Trouble shooting’ in OM
Yes
(see OM Section
'Connection’)
No
Not ok
Correct configuration
Not ok
Repeat
basic setup
ok
Communication ok?
No
Communication ok?
No
Measurement ok?
No
Yes
Ready
Contact E+H Service
Yes
Ready
Contact E+H Service
Yes
Ready
L00-FMR2xxxx-19-00-00-en-010
Endress+Hauser67
Page 68
Trouble-shootingMicropilot M FMR244 HART 4 to 20 mA
9.2System error messages
CodeDescriptionPossible causeRemedy
A102checksum error
general reset & new
calibr.required
W103 initialising - please wait EEPROM storage not yet finishedwait some seconds; if warning
A106downloading please wait processing data downloadwait until warning disappears
A110checksum error
general reset & new
calibr.required
A111electronics defect RAM defectivereset;
A113electronics defect RAM defectivereset;
A114electronics defect EEPROM defectreset;
A115electronics defect /error
power supply
A116download error
repeat download
A121electronics defect no factory calibration existant;
W153 initialising - please wait initialisation of electronicswait some seconds; if warning
A155electronics defect hardware problemreset;
A160checksum error
general reset & new
calibr.required
A164electronics defect hardware problemreset;
A171electronics defect hardware problemreset;
A231sensor 1 defect
check connection
W511 no factory calibration ch1 factory calibration has been deletedrecord new factory calibration
A512recording of mapping please
wait
A601linearisation ch1 curve not
monotone
device has been powered off before data
could be stored;
emc problem;
EEPROM defect
device has been powered off before data
could be stored;
emc problem;
EEPROM defect
general hardware problem / too low
power supply
checksum of stored data not correctrestart download of data
EEPROM defective
device has been powered off before data
could be stored;
emc problem;
EEPROM defect
HF module or electronics defectiveexchange HF module or electronics
mapping activewait some seconds until alarm
linearisation not monotonously increasing correct linearisation table
reset;
avoid emc problem;
if alarm prevails after reset,
exchange electronics
prevails, exchange electronics
reset;
avoid emc problem;
if alarm prevails after reset,
exchange electronics
if alarm prevails after reset,
exchange electronics
if alarm prevails after reset,
exchange electronics
if alarm prevails after reset,
exchange electronics
reset;
if alarm prevails after reset,
exchange electronics / higher
supply voltage
contact service
prevails, power off device and
power on again
if alarm prevails after reset,
exchange electronics
reset;
avoid emc problem;
if alarm prevails after reset,
exchange electronics
if alarm prevails after reset,
exchange electronics
if alarm prevails after reset,
exchange electronics
disappears
68Endress+Hauser
Page 69
Micropilot M FMR244 HART 4 to 20 mATrouble-shooting
CodeDescriptionPossible causeRemedy
W611 less than 2 linearisation
points for channel 1
W621 simulation ch. 1 on simulation mode is activeswitch off simulation mode
E641no usable echo
channel 1
check calibr.
E651level in safety distance - risk
of overspill
E671linearisation ch1 not
complete, not usable
W681 current ch1 out of range current out of range (3.8 mA to 20.5 mA) check calibration and linearisation
number of entered linearisation points < 2 correct linearisation table
echo lost due to application conditions or
built up on antenna
level in safety distancealarm will disappear as soon as level
linearisation table is in edit modeactivate linearisation table
check installation;
optimize orientation of antenna;
clean antenna (cf. OM)
leaves safety distance;
Endress+Hauser69
Page 70
Trouble-shootingMicropilot M FMR244 HART 4 to 20 mA
9.3Application errors in liquids
ErrorOutputPossible causeRemedy
A warning or alarm
has occurred
Depending on the configurationSee table of error
messages (→ ä 68)
1. See table of error messages
(→ ä 68)
Measured value
(000) is incorrect
No change off
measured value on
filling/emptying
F m/ft
D m/ft (008)
E m/ft
100%
expected
actual
0%t
L00-FMR2xxxx-19-00-00-en-019
100%
actual
Measured distance
(008) OK?
Measurement in bypass
→
or stilling well?
An interference echo
may have been
evaluated.
Interference echo from
installations, nozzle or
extension on the
antenna
no
no
yes →1. Check empty calibr. (005) and
full calibr. (006).
2. Check linearisation:
level/ullage (040)
→
max. scale (046)
→
diameter vessel (047)
→
Check table
→
↓
yes →1. Is bypass or stilling well selected
in tank shape (002)?
2. Is the pipe diameter (007)
correct?
↓
yes
1. Carry out tank mapping
→
basic setup
→
1. Carry out tank mapping
basic setup
→
2. If necessary, clean antenna
3. If necessary, select better
mounting position
expected
0%t
L00-FMR2xxxx-19-00-00-en-014
→
70Endress+Hauser
Page 71
Micropilot M FMR244 HART 4 to 20 mATrouble-shooting
ErrorOutputPossible causeRemedy
If the surface is not
calm (e. g. filling,
emptying, agitator
running), the
measured value
jumps sporadically
to a higher level
100%
actual
expected
0%t →
L00-FMR2xxxx-19-00-00-en-015
100%
actual
Signal is weakened by
the rough surface – the
interference echoes are
sometimes stronger
1. Carry out tank mapping
→
basic
setup
2. Set the process cond. (004) to
"turb. surface" or "agitator"
3. Increase the output damping
(058)
4. Optimise the orientation
(→ ä 73)
5. If necessary, select a better
mounting position and/or larger
antenna
During filling/
emptying the
measured value
jumps ownwards
E641 (loss of echo)
expected
0%t →
L00-FMR2xxxx-19-00-00-en-016
100%
expected
actual
0%t →
L00-FMR2xxxx-19-00-00-en-017
100%
eingetreten
E 641
erwartet
Multiple echoesyes
Level echo is too weak.
yes
Possible causes:
• Rough surface due to
filling/ emptying
• Agitator running
•Foam
1. Check the tank shape (002), e. g.
→
"dome ceiling" or "horizontal
cyl"
2. In the range of the blocking dist.
(059) there is no echo evaluation
Adapt the value
→
3. If possible, do not select central
installation position
4. Perhaps use a stilling well
1. Check application arameters
→
(002), (003) and (004)
2. Optimise alignment (→ ä 73)
3. If necessary, select a better
installation position and/or larger
antenna
0%t →
L00-FMR2xxxx-19-00-00-en-018
Endress+Hauser71
Page 72
Trouble-shootingMicropilot M FMR244 HART 4 to 20 mA
9.4Application errors in solids
ErrorOutputPossible causeRemedy
A warning or alarm
has occurred
Depending on the configurationSee table of error
messages (→ ä 68)
1. See table of error messages
(→ ä 68)
Measured value
(000) is incorrect
No change off
measured value on
filling/emptying
F m/ft
D m/ft (008)
E m/ft
100%
expected
actual
0%t
L00-FMR250xx-19-00-00-en-019
100%
actual
expected
0%t
L00-FMR250xx-19-00-00-en-014
Measured distance
(008) OK?
An interference echo
may have been
→
evaluated.
Interference echo from
installations, nozzle or
build up on the antenna
→
no
yes →1. Check empty calibr. (005) and
full calibr. (006).
2. Check linearisation:
level/ullage (040)
→
max. scale (046)
→
Check table
→
↓
yes
1. Carry out tank mapping
→
basic setup
→
1. Carry out tank mapping
basic setup
→
2. If necessary, use top target
positioner to aim antenna better
to product surface (avoidance of
interference echo) (→ ä 73)
3. If necessary, clean antenna
4. If necessary, select better
mounting position
During filling or
emptying the
measured value
jumps sporadically
to a higher level
E641 (loss of echo)
100%
actual
expected
0%t →
L00-FMR250xx-19-00-00-en-015
100%
actual
E 641
expected
0%t →
L00-FMR250xx-19-00-00-en-018
Signal is weakened
(e. g. by fluidisation of
the surface, extreme
dust formation) – the
interference echoes are
sometimes stronger
Level echo is too weak.
Possible causes:
• fluidisation of the
surface
• extreme dust
formation
• angle of repose
yes
1. Carry out tank mapping
setup
2. Increase the output damping
(058)
3. Optimise the orientation
(→ ä 73)
4. If necessary, select a better
mounting position and/or larger
antenna
1. Check application arameters
→
(00A), (00B) and (00C)
2. Optimise alignment (→ ä 73)
3. If necessary, select a better
installation position and/or larger
antenna
→
basic
72Endress+Hauser
Page 73
Micropilot M FMR244 HART 4 to 20 mATrouble-shooting
9.5Orientation of the Micropilot
For orientation a marker is found on the flange or threaded boss of the Micropilot. During
installation this must be oriented as follows (→ ä 10):
• In tanks: to the vessel wall
• In stilling wells: to the slots
• In bypass pipes: vertical to the tank connectors
After commissioning the device, the echo quality indicates whether a sufficiently large measuring
signal is obtained. If necessary, the quality can be optimised later. Vice versa, the presence of an
interference echo can be used to minimise this by optimum orientation. The advantage of this is that
the subsequent tank mapping uses a somewhat lower level that causes an increase in the strength
of the measuring signal.
Proceed as follows:
#
Warning!
Subsequent alignment can lead to personal injury. Before you unscrew or loosen the process
connection, make sure that the vessel is not under pressure and does not contain any injurious
substances.
1.It is best to empty the container so that the bottom is just covered. However, alignment can be
carried out even if the vessel is empty.
2.Optimisation is best carried out with the aid of the envelope graph in the display or the
FieldCare.
3.Unscrew the flange or loosen the threaded boss by a half a turn.
4.Turn the flange by one hole or screw the threaded boss by one eighth of a turn. Note the echo
quality.
5.Continue to turn until 360° is reached.
6.Optimum alignment:
level echo: highest value
level echo
L00-FMRxxxxx-19-00-00-en-002
Vessel partly full, no interference echo obtained
level echo: highest value
false echo: smallest value
level echofalse echo
L00-FMRxxxxx-19-00-00-en-003
Vessel partly full, interference echo obtained
Endress+Hauser73
Page 74
Trouble-shootingMicropilot M FMR244 HART 4 to 20 mA
echo: highest value
echo tank bottom
L00-FMRxxxxx-19-00-00-en-004
Vessel empty, no interference echo
false echo: smallest value
echo tank bottomfalse echo
Vessel empty, interference echo obtained
7.Fix the flange or threaded boss in this position. If necessary, replace the seal.
8.Carry out tank mapping, → ä 54.
L00-FMRxxxxx-19-00-00-en-005
74Endress+Hauser
Page 75
Micropilot M FMR244 HART 4 to 20 mATrouble-shooting
9.6Spare Parts
An overview of the spare parts for your device is available in the internet at www.endress.com.
To obtain information on the spare parts, proceed as follows:
1.Go to "www.endress.com" and select your country.
2.Click "Instruments".
3.Enter the product name into the "product name" field.
4.Select the device.
5.Click the "Accessories/Spare parts" tab.
6.Select the required spare parts (You may also use the overview drawing on the right side of the
screen.)
When ordering spare parts, always quote the serial number indicated on the nameplate. As far as
necessary, the spare parts also include replacement instructions.
Endress+Hauser75
Page 76
Trouble-shootingMicropilot M FMR244 HART 4 to 20 mA
9.7Return
The following procedures must be carried out before a transmitter is sent to Endress+Hauser e. g.
for repair or calibration:
• Remove all residue which may be present. Pay special attention to the gasket grooves and crevices
where fluid may be present. This is especially important if the fluid is dangerous to health, e. g.
corrosive, poisonous, carcinogenic, radioactive, etc.
• Always enclose a duly completed "Declaration of contamination" form (a copy of the "Declaration
of contamination" is included at the end of this operating manual). Only then can Endress+Hauser
transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as per
EN 91/155/EEC.
Additionally specify:
• An exact description of the application.
• The chemical and physical characteristics of the product.
• A short description of the error that occurred (specify error code if possible)
• If necessary, give the error code.
9.8Disposal
In case of disposal please seperate the different components according to their material consistence.
9.9Software history
DateSoftware version Changes to softwareDocumentation
12.200001.01.00Original software.
Operated via:
– ToF Tool from version 1.5
– Commuwin II (from version 2.07-3)
– HART communicator DXR275
(from OS 4.6) withRev. 1, DD 1.
05.2002
03.2003
01.200501.02.04Function "echo lost" improved
03.200601.04.00• Function: detection windowg
10.200601.05.00Support of additional HF modules integrated.
01.02.00
01.02.02
• Function group: envelope curve display
• Katakana (japanese)
• current turn down (HART only)
• the customer tank map can be edited
• length of antenna extension FAR10 can be entered
directly
Operated via:
– ToF Tool from version 3.1
– Commuwin II (from version 2.08-1)
– HART communicator DXR375 with Rev. 1, DD 1.
Operated via:
– ToF Tool from version 4.2
– FieldCare from version 2.02.00
– HART-Communicator DXR375 with Rev. 1, DD 1.
• Function: media type
BA221F/00/EN/01.01
52006323
BA221F/00/EN/03.03
52006323
BA221F/00/EN/12.05
52006322
BA291F/00/EN/08.06
71030727
9.10Contact addresses of Endress+Hauser
Contact addresses can be found on our homepage "www.endress.com/worldwide". If you have any
questions, please do not hesitate to contact your Endress+Hauser representative.
76Endress+Hauser
Page 77
Micropilot M FMR244 HART 4 to 20 mATechnical data
10Technical data
10.1Additional technical data
10.1.1Input
Measured variableThe measured variable is the distance between a reference point and a reflective surface (i. e.
medium surface).
The level is calculated based on the tank height entered.
The level can be converted into other units (volume, mass) by means of a linearization (32 points).
Operating frequencyK-band
Up to 8 Micropilot M transmitters can be installed in the same tank because the transmitter pulses
are statistically coded.
ransmitting power
Distance
1 m (3.3 ft)< 12 nW/cm
5 m (16 ft)< 0.4 nW/cm
max. measuring range = 20 m (66 ft) / 40 m (131 ft)measuring range = 70 m (230 ft)
Average energy density in beam direction
2
2
10.1.2Output
Output signal4…20 mA (invertible) with HART protocol
Signal codingFSA ±0.5 mA over currency signal
Data transmission rate1200 Baud
Galvanic isolationYes (IO-Module)
Signal on alarmError information can be accessed via the following interfaces:
• Local display:
– Error symbol (→ ä 36)
– Plain text display
• Current output, signal on error can be selected (e. g. according to NAMUR recommendation
NE43).
• Digital interface
< 64 nW/cm
< 2.5 nW/cm
2
2
LinearizationThe linearization function of the Micropilot M allows the conversion of the measured value into any
unit of length or volume. Linearization tables for calculating the volume in cylindrical tanks are preprogrammed. Other tables of up to 32 value pairs can be entered manually or semi-automatically.
• no major interference reflections inside the signal beam
Maximum measured errorTypical statements for reference conditions, include linearity, repeatability, and hysteresis:
• Not for max. measuring range = 70 m (230 ft)
– to 1 m (3.3 ft): ±10 mm (±0.39 in)
• For max. measuring range = 40 m (131 ft)
– to 10 m (33 ft): ±3 mm (±0.12 in)
– ex 10 m (33 ft): ±0.03 % of measuring range
• For max. measuring range = 70 m (230 ft)
– to 1 m (3.3 ft): ±30 mm (±1.18 in)
– ex 1 m (3.3 ft): ±15 mm (±0.59 in) or 0.04 % of measuring range, whatever is larger
ResolutionDigital / analog in % 4…20 mA: 1mm / 0.03 % of measuring range
Reaction timeThe reaction time depends on the parameter settings (min. 1 s). In case of fast level changes, the
instrument needs the reaction time to indicate the new value.
Influence of ambiente
temperature
The measurements are carried out in accordance with EN61298-3:
• Digital output HART:
– average T
: 2 mm (0.08 in) /10 K, max. 5 mm (0.2 in) over the entire temperature range
K
-40 °C to +80 °C (-40 to +176 °F)
• Current output (additional error, in reference to the span of 16 mA):
– Zero point (4 mA)
average T
: 0,03 %/10 K, max. 0,45 % over the entire temperature range -40 °C to +80 °C
K
(-40 to +176 °F)
– Span (20 mA)
average T
: 0,09 %/10 K, max. 0,95 % over the entire temperature range -40 °C to +80 °C
K
(-40 to +176 °F)
Effect of gas phaseHigh pressures reduce the propagation velocity of the measuring signals in the gas/vapor above the
fluid. This effect depends on the gas/vapor and is particularly large for low temperatures. This
results in a measuring error that gets bigger as the distance increases between the device zero point
(flange) and product surface. The following table illustrates this measured error for a few typical
gases/vapors (with regard to the distance; a positive value means that too large a distance is being
measured):
Gas phaseTemperaturePressure
°C°F1 bar (14.5 psi)10 bar (145 psi)50 bar (725 psi)100 bar (1450 psi)160 bar (2320 psi)
Air
Nitrogen
Hydrogen2068-0.01 %0.10 %0.61 %1.2 %2.00 %
20680.00 %0.22 %1.2 %2.4 %3.89 %
200392-0.01 %0.13 %0.74 %1.5 %2.42 %
400752-0.02 %0.08 %0.52 %1.1 %1.70 %
200392-0.02 %0.05 %0.37 %0.76 %1.23 %
400752-0.02 %0.03 %0.25 %0.53 %0.86 %
78Endress+Hauser
Page 79
Micropilot M FMR244 HART 4 to 20 mATechnical data
Gas phaseTemperaturePressure
°C°F1 bar (14.5 psi)10 bar (145 psi)50 bar (725 psi)100 bar (1450 psi)160 bar (2320 psi)
Water
(saturated
steam)
1002120.20 %————
180356—2.1 %———
263505——8.6 %——
310590———22 %—
364687————41.8 %
!
Note!
When the pressure is known and constant, this measured error can, for example, be compensated
by means of linearization.
10.1.5Operating conditions: Environment
Ambient temperature rangeAmbient temperature for the transmitter: -40 °C to +80 °C (-40 °F to +176 °F) or
-50 °C to +80 °C (-58 °F to +176 °F) . The functionality of the LCD display may be limited for
temperatures Ta < -20 °C (-4 °F) and Ta > +60 °C (+140 °F). A weather protection cover should
be used for outdoor operation if the instrument is exposed to direct sunlight.
Storage temperature-40 °C to +80 °C (-40 °F to +176 °F) or -50 °C to +80 °C (-58 °F to +176 °F).
Climate classDIN EN 60068-2-38 (test Z/AD)
Vibration resistanceDIN EN 60068-2-64 / IEC 68-52-64:
• FMR230/231, FMR240/244/245 with 40 mm (1½") antenna:
20 to 2000 Hz, 1 (m/s²)²/Hz
Cleaning of the antennaThe antenna can get contaminated, depending on the application. The emission and reception of
microwaves can thus eventually be hindered. The degree of contamination leading to an error
depends on the medium and the reflectivity, mainly determined by the dielectric constant
medium tends to cause contamination and deposits, cleaning on a regular basis is recommended.
Care has to be taken not to damage the antenna in the process of a mechanical or hose-down
cleaning (eventually connection for cleaning liquid). The material compatibility has to be considered
if cleaning agents are used! The maximum permitted temperature at the flange should not be
exceeded.
r. If the
ε
Electromagnetic compatibility • Electromagnetic compatibility in accordance with all the relevant requirements of the EN61326
series and NAMUR recommendation (NE21). For details refer to the Declaration of Conformity.
Maximum deviation < 0.5 % of the span.
• A standard installation cable is sufficient if only the analogue signal is used. Use a screened cable
when working with a superimposed communications signal (HART).
Endress+Hauser79
Page 80
Technical dataMicropilot M FMR244 HART 4 to 20 mA
10.1.6Operating conditions: Process
Process temperature range /
Process pressure limits
Note!
The specific range may be reduces by the selected process condition. The pressure rating (PN)
specified on the flanges refers to a reference temperature of 20 °C (68 °F), for ASME flanges to
100 °F. Observe pressure temperature dependency.
The pressure values permitted at higher temperatures can be found in the following standards:
• EN1092-1: 2001 Tab. 18
With regard to their temperature stability properties, the materials 1.4404 and 1.4435 are
grouped under 13E0 in EN1092-1 Tab. 18. The chemical composition of the two materials can
be identical.
• ASME B16.5a - 1998 Tab. 2-2.2 F316
• ASME B16.5a - 1998 Tab. 2.3.8 N10276
• JIS B 2220
Type of antennaSealTemperaturePressureWetted parts
VStandard,
completely
PTFE
encapsulated
SStandard,
PP clad
↑Ordering information → ä 7
FKM Viton
GLT
Silicone-40 °C to +80 °C
-40 °C to +130 °C
(-40 °F to +266 °F)
(-40 °F to +176 °F)
-1 to 3 bar
(-14.5 to 43.5 psi)
PTFE (conform to FDA 21
CFR 177.1550 and USP
<88> Class VI),
Viton, PVDF
PP, Silicone, PBT
Dielectric constant• in a stilling well:
• in free space:
r ≥ 1.9
ε
r ≥ 1.4
ε
80Endress+Hauser
Page 81
Micropilot M FMR244 HART 4 to 20 mATechnical data
Made in GermanyMaulburg
Made in GermanyMaulburg
Made in GermanyMaulburg
10.1.7Mechanical construction
Weight• F12/T12 housing: approx 2.5 kg
Material
(not in contact with process)
Materials of T12 and F12 housing (seawater-resistant, powder-coated)
T12 housing
(Aluminium)(Aluminium)
4
1
1
ENDRESS+HAUSER
O
r
d
e
r
C
S
o
d
e
e
r
.-
:
N
o
.:
M
e
s
s
b
M
e
e
r
a
e
s
i
c
u
h
r
in
g
r
a
n
g
e
U
m
1
a
6
x
...
.
4
2
3
.
0
urg
6
..
m
2
V
lb
0
m
D
C
au
A
IP 65
yM
T>
A
an
7
0
m
°
C
:
er
t
>
8
5
in G
°
C
deaM
3
7
2
3
987
5
6
Pos. PartMaterial
1T12 and F12 housingAlSi10Mg
Cover (Display)AlSi10Mg
SealingFa. SHS: EPDM 70pW FKN
2
WindowESG-K-Glass (Toughened safety glass)
Sealing of the glassSilicone sealing compound Gomastit 402
Declaration of Hazardous Material and De-Contamination
Erklärung zur Kontamination und Reinigung
Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA#
RA No.
Because of legal regulations and for the safety of our employees and operating equipment, we need the "Declaration of Hazardous Material
and De-Contamination", with your signature, before your order can be handled. Please make absolutely sure to attach it to the outside of the
packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, benötigen wir die unterschriebene
"Erklärung zur Kontamination und Reinigung", bevor Ihr Auftrag bearbeitet werden kann. Bringen Sie diese unbedingt außen an der
Verpackung an.
Used as SIL device in a Safety Instrumented System / Einsatz als SIL Gerät in Schutzeinrichtungen
clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
Bitte geben Sie die von E+H mitgeteilte Rücklieferungsnummer (RA#) auf allen Lieferpapieren an und vermerken Sie diese
auch außen auf der Verpackung. Nichtbeachtung dieser Anweisung führt zur Ablehnung ihrer Lieferung.
Serial number
Seriennummer ________________________
Process data/Prozessdaten
Medium and warnings
Warnhinweise zum Medium
Medium /concentration
Medium /Konzentration
Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
Please tick should one of the above be applicable, include safety data sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.
Description of failure / Fehlerbeschreibung __________________________________________________________________________
“We hereby certify that this declaration is filled out truthfully and completely to the best of our knowledge.We further certify that the returned
parts have been carefully cleaned. To the best of our knowledge they are free of any residues in dangerous quantities.”
“Wirbestätigen
w
eiter, dass die zurückgesandten Teile sorgfältig gereinigt wurden und nach unserem besten Wissen frei von Rückständen in gefahrbringen-
der Menge sind.”
P/SF/Konta XV
(
place, date / Ort, Datum)
Firma ___
Adresse
bestätigen, die vorliegende Erklärung nach unserem besten Wissen wahrheitsgetreu und vollständig ausgefüllt zu haben. Wir