Endress+Hauser Levelflex M FMP41C Operating Instructions Manual

BA276F/00/en/11.06 No. 52021033
Valid as of software version V 01.04.00 (amplifier) V 01.04.00 (communication)
Operating Instructions
Levelflex M FMP41C
6
Brief overview Levelflex M FMP41C with HART/4...20 mA
2 Endress + Hauser
Brief overview
For quick and simple commissioning:
Safety Instructions ä 6
Explanation of the warning symbols
You can find special instructions at the appropriate position in the chapter in
question. The positions are indicated with the icons Warning #, Caution " and
Note !.
Æ
Installation ä 12
The steps for installing the device and installation conditions (e.g. dimensions)
can be found here.
Æ
Wiring ä 22
The device is virtually completely wired on delivery.
Æ
Display and Operating Elements ä 28
An overview of the position of the display and operating elements can be found
here.
Æ
Commissioning via Display VU331 ä 41
In the "Commissioning" section, you learn how to switch on the device and
check the functioning.
Æ
Commissioning via Operating Software ToF Tool ä 54
In the "Commissioning" section, you learn how to switch on the device and
check the functioning.
Additional information on the operation of the ToF Tool can be found in the
operating instructions BA224F/00.
Æ
Fault Tracking / Trouble Shooting ä 65
If faults occur during operation, use the checklist to localise the cause.
Here you can find measures you can take yourself to take remedial action
against the fault.
Æ
Index ä 89
You can find important terms and keywords on the individual sections here.
Use the keyword index to find quickly and efficiently the information you need.
Levelflex M FMP41C with HART/4...20 mA Brief overview
Endress + Hauser 3
Brief operating instructions
L00-FMP40xxx-19-0 0-00-en-012
!
Note! This operating manual explains the installation and initial start-up for the level transmitter measuring device. All functions that are required for a typical measuring task are taken into account here. In addition, the Levelflex M provides many other functions that are not included in this operating manual, such as optimising the measuring point and converting the measured values.
An overview of all device functions can be found on ä 84.
An extensive description of all device functions can be found in BA245F – "Description of the instrument functions" on the enclosed CD-ROM.
Operating Instructions can also be found on our homepage: www.endress.com
E
+
-
+
E
+
-
E
E
-
… …
… …
KA 189F/00/a2/11.05 52012501
52012501
100%
0%
F
E
UB
LN
D
L
Levelflex M - Brief operating instructions
input E (see sketch)
input F (see sketch) displayed
D and L are
confirm
or specify range
suggestion
000 measured value
Group selection
00 basic setup
01 safety settings
09 display
04 linearisation
05 extended calibr.
0C system parameters
092 language
0A diagnostics
0A0 present error
002 tank properties
004 process cond.
005 empty calibr.
006 full calibr.
008 dist./ meas value
051 check distance
003 medium property
052 range of mapping
053 start mapping
008 dist./ meas value
- envel. curve
- substracted signal
- mapping
- single curve
- cyclic
= 100: unlocked ¹ 100: locked
09A plot settings
09B recording curve
0A1 previous error
0A4 unlock parameter
(333 = reset customer parameters)
0A3 reset
min. level
threaded connection
(G 1
: reference point of measurement
¾or BSP
¾orG ½)
¾or1½NPT
03 length adjustment
030 end of probe
031 probe length
032 probe
033 probe length
034 determine length
- unknown
- 1.4 … 1.6
- 1.6 … 1.9
- 1.9 … 2.5
-4…7
-2.5…4
->7
0E envelope curve
Contrast: +or +
- standard
- aluminium tank
- plastic tank
- bypass/pipe
- coax-probe
- concrete wall
- standard
- fast change
- test: no filter
- slow change
- free
- tie down isolated
- tie down gnd.
If shortened
please enter probe lengthhere.
reference
point of
measurement
F = measuring span
E = empty distance (= zero)
UB = upper blocking distance
LN = probe length
L = level
D = distance
Brief overview Levelflex M FMP41C with HART/4...20 mA
4 Endress + Hauser
Levelflex M FMP41C with HART/4...20 mA Table of contents
Endress + Hauser 5
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 6
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Installation, commissioning and operation . . . . . . . . 6
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Notes on safety conventions and icons . . . . . . . . . . . 7
2 Identification . . . . . . . . . . . . . . . . . . . . 8
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . 11
2.4 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 11
3 Installation . . . . . . . . . . . . . . . . . . . . . 12
3.1 Incoming acceptance, transport, storage . . . . . . . . . 12
3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 13
3.3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4 Turn housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 21
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 22
4.1 Quick wiring guide . . . . . . . . . . . . . . . . . . . . . . . . 22
4.2 Connecting the measuring unit . . . . . . . . . . . . . . . 24
4.3 Recommended connection . . . . . . . . . . . . . . . . . . 27
4.4 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 27
4.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 27
5 Operation . . . . . . . . . . . . . . . . . . . . . . 28
5.1 Quick operation guide . . . . . . . . . . . . . . . . . . . . . . 28
5.2 Display and operating elements . . . . . . . . . . . . . . . 30
5.3 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.4 Display and acknowledging error messages . . . . . . 35
5.5 HART communication . . . . . . . . . . . . . . . . . . . . . . 36
6 Commissioning. . . . . . . . . . . . . . . . . . 38
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.2 Switching on the measuring device . . . . . . . . . . . . 38
6.3 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.4 Basic Setup with the VU331 . . . . . . . . . . . . . . . . . 41
6.5 Blocking distance . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.6 Envelope curve with VU331 . . . . . . . . . . . . . . . . . 51
6.7 Function "envelope curve display" (0E3) . . . . . . . . 52
6.8 Basic Setup with the ToF Tool . . . . . . . . . . . . . . . . 54
7 Maintenance. . . . . . . . . . . . . . . . . . . . 60
8 Accessories. . . . . . . . . . . . . . . . . . . . . 61
9 Trouble-shooting . . . . . . . . . . . . . . . . 65
9.1 Trouble-shooting instructions . . . . . . . . . . . . . . . . 65
9.2 System error messages . . . . . . . . . . . . . . . . . . . . . . 66
9.3 Application errors . . . . . . . . . . . . . . . . . . . . . . . . . 68
9.4 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
9.5 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.7 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.8 Contact addresses of Endress+Hauser . . . . . . . . . . . 76
10 Technical data . . . . . . . . . . . . . . . . . . . 77
10.1 Additional technical data . . . . . . . . . . . . . . . . . . . . 77
11 Appendix. . . . . . . . . . . . . . . . . . . . . . . 84
11.1 Operating menu HART (Display modul), ToF Tool . 84
11.2 Description of functions . . . . . . . . . . . . . . . . . . . . . 86
11.3 Function and system design . . . . . . . . . . . . . . . . . . 86
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Safety instructions Levelflex M FMP41C with HART/4...20 mA
6 Endress + Hauser
1 Safety instructions
1.1 Designated use
The Levelflex M FMP41C is a compact level transmitter for the continuous measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry.
1.2 Installation, commissioning and operation
The Levelflex M has been designed to operate safely in accordance with current technical, safety and EU standards. If installed incorrectly or used for applications for which it is not intended, however, it is possible that application-related dangers may arise, e.g. product overflow due to incorrect installation or calibration. For this reason, the instrument must be installed, connected, operated and maintained according to the instructions in this manual: personnel must be authorised and suitably qualified. The manual must have been read and understood, and the instructions followed. Modifications and repairs to the device are permissible only when they are expressly approved in the manual.
1.3 Operational safety
Hazardous areas
Measuring systems for use in hazardous environments are accompanied by separate "Ex documentation", which is an integral part of this Operating Manual. Strict compliance with the installation instructions and ratings as stated in this supplementary documentation is mandatory.
• Ensure that all personnel are suitably qualified.
• Observe the specifications in the certificate as well as national and local regulations.
Levelflex M FMP41C with HART/4...20 mA Safety instructions
Endress + Hauser 7
1.4 Notes on safety conventions and icons
In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin.
Safety conventions
#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the instrument
"
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or incorrect functioning of the instrument
!
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation or may lead to an instrument response which is not planned
Explosion protection
0
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous area
-
Explosion hazardous area
Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring entering areas with the designation “explosion hazardous areas” must conform with the stated type of protection.
.
Safe area (non-explosion hazardous area)
Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in safe areas still require a certificate if their outputs run into explosion hazardous areas
Electrical symbols
%
Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied
&
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or supplied
)
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of an earth grounding system
*
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection to the equipment
+
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential line according to national or company practice
Temperature resistance of the connection cables
States, that the connection cables must be resistant to a temperature of at least 85 °C.
t >85°C
Identification Levelflex M FMP41C with HART/4...20 mA
8 Endress + Hauser
2 Identification
2.1 Device designation
2.1.1 Nameplate
The following technical data are given on the instrument nameplate:
L00-FMP4xxxx-18-00- 00-en-001
Fig. 1: Information on the nameplate of the Levelflex M FMP41C (example)
2.1.2 Ordering structure
This overview does not mark options which are mutually exclusive.
Ordering structure Levelflex M FMP41C
Made in Germany D-79689 Maulburg
Dat./Insp.:
Order Code:
IP68 / NEMA 6P
Ser.-No.:
4-wire
ENDRESS+HAUSER
t >85°C
TA > 70°C:
D01301-A
if modification see sep. label
X=
Patents
LEVELFLEX-M
90 253 V AC 3,5VA 10,5 32VDC 1W 16 3 V DC 0,8W
Profibus PA Foundation Fieldbus
LN= PN=
4 20 mA HART 2-wire
Order No
(see Order Information)
Communication variant and supply voltage
Serial number
Reference to additional
safety-relevant documentation
Designation according to Directive 94/9/EC
and designation of protection
10 Approval:
A Non-hazardous area
F Non-hazardous area, WHG
1 ATEX II 1/2G EEx ia IIC T6
Note safety instruction (XA) (electristatic charging)!
3 ATEX II 2G EEx em (ia) IIC T6
Note safety instruction (XA) (electristatic charging)!
5 ATEX II 1/2G EEx ia IIC T6, ATEX II 1/3D
Note safety instruction (XA) (electristatic charging)!
6 ATEX II 1/2G EEx ia IIC T6, WHG
Note safety instruction (XA) (electristatic charging)!
7 ATEX II 1/2G EEx d (ia) IIC T6
Note safety instruction (XA) (electristatic charging)!
8 ATEX II 1/2G EEx ia IIC T6, ATEX II 1/3D, WHG
Note safety instruction (XA) (electristatic charging)!
G ATEX II 3G EEx nA II T6
S FM IS Cl.I,II,III Div.1 Gr.A-G N.I.
T FM XP Cl.I,II,III Div.1 Gr.A-G
N CSA General Purpose
U CSA IS Cl.I,II,III Div.1 Gr.A-D,G + coal dust, N.I.
V CSA XP Cl.I,II,III Div.1 Gr.A-D,G + coal dust, N.I.
K TIIS Ex ia IIC T4
L TIIS Ex d (ia) IIC T4
YSpecial version
FMP41C- Product designation (part 1)
Levelflex M FMP41C with HART/4...20 mA Identification
Endress + Hauser 9
Ordering structure Levelflex M FMP41C (continued)
20 Probe:
A ..... mm, rope PFA>316, 150mm, Center rod, nozzle height max 150mm
B ..... mm, rope PFA>316, 300mm, Center rod, nozzle height max 300mm
C ..... mm, rope PFA>316, 450mm, Center rod, nozzle height max 450mm
D ..... inch, rope PFA>316, 6inch, Center rod, nozzle height max 6inch
E ..... inch, rope PFA>316, 12inch, Center rod, nozzle height max 12inch
G ..... inch, rope PFA>316, 18inch, Center rod, nozzle height max 18inch
K ..... mm, rod PFA>316L
M ..... inch, rod PFA>316L
Y Special version
30 Process Connection:
AEK 1-1/2" 150lbs, PTFE >316/316L flange ASME B16.5
AFK 2" 150lbs, PTFE >316/316L flange ASME B16.5
AGK 3" 150lbs, PTFE >316/316L flange ASME B16.5
AHK 4" 150lbs, PTFE >316/316L flange ASME B16.5
AJK 6" 150lbs, PTFE >316/316L flange ASME B16.5
AQK 1-1/2" 300lbs, PTFE >316/316L flange ASME B16.5
ARK 2" 300lbs, PTFE >316/316L flange ASME B16.5
ASK 3" 300lbs, PTFE >316/316L flange ASME B16.5
ATK 4" 300lbs, PTFE >316/316L flange ASME B16.5
CEK DN40 PN16-40, PTFE >316L flange EN1092-1 (DIN2527 C)
CFK DN50 PN10-40, PTFE >316L flange EN1092-1 (DIN2527 C)
CGK DN80 PN10/16, PTFE >316L flange EN1092-1 (DIN2527 C)
CHK DN100 PN10/16, PTFE >316L flange EN1092-1 (DIN2527 C)
CJK DN150 PN10/16, PTFE >316L flange EN1092-1 (DIN2527 C)
CSK DN80 PN25/40, PTFE >316L flange EN1092-1 (DIN2527 C)
CTK DN100 PN25/40, PTFE >316L flange EN1092-1 (DIN2527 C)
KEK 10K 40, PTFE >316L flange JIS B2220
KFK 10K 50, PTFE >316L flange JIS B2220
KGK 10K 80, PTFE >316L flange JIS B2220
KHK 10K 100, PTFE >316L flange JIS B2220
30 Process Connection:
MRK DIN11851 DN50 PN40, PTFE >316L
TCK Clamp ISO2852 1-1/2", PTFE >316L
TDK Clamp ISO2852 2", PTFE >316L
TFK Clamp ISO2852 3", PTFE >316L
TJK Clamp ISO2852 1-1/2", PTFE >316L
TKK DRD 65mm PN40, PTFE >316L
TLK Clamp ISO2852 2", PTFE >316L, 3A EHEDG
TNK Clamp ISO2852 3", PTFE >316L, 3A EHEDG
UPK Universal adapter 44mm, PTFE >316L
UQK Universal adapter 44mm, PTFE >316L, EHEDG 3A
YY9 Special version
FMP41C- Product designation (part 2)
Identification Levelflex M FMP41C with HART/4...20 mA
10 Endress + Hauser
Ordering structure Levelflex M FMP41C (continued)
40 Power Supply; Output:
B 2-wire; 4…20mA HART
D 2-wire; PROFIBUS PA
F 2-wire; FOUNDATION Fieldbus
G 4-wire 90...250VAC; 4...20mA HART
H 4-wire 10.5...32VDC; 4...20mA HART
Y Special version
50 Operation:
1 W/o display, via communication
2 4-line display VU331, Envelope curve display on site
3 Prepared for FHX40, Remote display (accessory)
9 Special version
60 Type of Probe:
1 Compact, basic version
3 Remote, cable 3m, top entry
4 Remote, cable 3m, side entry
9Special version
70 Housing:
A F12 Alu, coated IP68 NEMA6P
B F23 316L IP68 NEMA6P
C T12 Alu, coated IP68 NEMA6P, Separate conn. compartment
D T12 Alu, coated IP68 NEMA6P + OVP, Separate conn. compartment,
OVP = overvoltage protection
YSpecial version
80 Cable Entry:
2 Gland M20 (EEx d > thread M20)
3Thread G1/2
4Thread NPT1/2
5Plug M12
6Plug 7/8"
9Special version
90 Additional Option:
A Basic version
Y Special version
FMP41C- Complete product designation
Please enter probe length in mm or inch / 0.1 inch
mm
inch / 0.1 inch
probe length LN ä 14
Levelflex M FMP41C with HART/4...20 mA Identification
Endress + Hauser 11
2.2 Scope of delivery
"
Caution! It is essential to follow the instructions concerning the unpacking, transport and storage of measuring instruments given in the chapter "Incoming acceptance, transport, storage" on ä 12!
The scope of delivery consists of:
• Assembled instrument
• 2 ToF Tool - FieldTool
®
Package CD-ROMs
– CD 1: ToF Tool - FieldTool
®
Program Program including Device Descriptions (device drivers) for all Endress+Hauser devices wich are operable using ToF Tool
– CD 2: ToF Tool - FieldTool
®
Documentation Documentation for all Endress+Hauser devices wich are operable using ToF Tool)
• Accessories (→ Chap. 8).
Accompanying documentation:
• Short manual (basic setup/troubleshooting): housed in the instrument
• Operating manual (this manual)
• Approval documentation: if this is not included in the operating manual.
!
Note! The operating manual BA245F - "Description of Instrument functions" you can be found on the enclosed CD-ROM.
2.3 Certificates and approvals
CE mark, declaration of conformity
The device is designed to meet state-of-the-art safety requirements, has been tested and left the factory in a condition in which it is safe to operate. The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
2.4 Registered trademarks
KALREZ®, VITON®, TEFLON
®
Registered trademark of the company, E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP
®
Registered trademark of the company, Ladish & Co., Inc., Kenosha, USA
HART
®
Registered trademark of HART Communication Foundation, Austin, USA
ToF
®
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
PulseMaster
®
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
Installation Levelflex M FMP41C with HART/4...20 mA
12 Endress + Hauser
3 Installation
3.1 Incoming acceptance, transport, storage
3.1.1 Incoming acceptance
Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
3.1.2 Transport
"
Caution! Follow the safety instructions and transport conditions for instruments of more than 18 kg. Do not lift the measuring instrument by its probe rod in order to transport it.
3.1.3 Storage
Pack the measuring instrument so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C…+80 °C.
Levelflex M FMP41C with HART/4...20 mA Installation
Endress + Hauser 13
3.2 Installation conditions
3.2.1 Dimensions
Housing dimensions
Dimensions for the process connection and the probe type ä 14.
L00-F12xxxx-06-00-00 -en-001
L00-T12xxxx-06-00- 00-en-001
L00-F23xxxx-06-00-00 -en-001
ENDRESS+HAUSER
65
78
max. 110
85
150
Ø 129
(Aluminium)
F12 housing
ENDRESS+HAUSER
78
85
65
162
max. 100 94
Ø 129
(Aluminium)
T12 housing
max. 94
104
Ø 129
150
40
(316L)
F23 housing
Installation Levelflex M FMP41C with HART/4...20 mA
14 Endress + Hauser
Levelflex M FMP41C - process connection, probe type
Housing dimensions ä 13
L00-FMP41xxx-06-00-0 0-en-001
Fig. 2: Dimensions Levelflex M FMP41C
88
88
123
2765
80
Ø 76
4 x Ø 8,5
118
24
Ø 42
Ø 60
100
Ø 76
Ø 81
62
165/315/465
Flange DN 40200
or equivalent
Endress+Hauser
universal
adapter
reference point of
measurement
rope: Ø 4 mm/0.20
rope probe rod probe
Ø 16/0.63(incl. insulation)
Ø 22/0.87(incl. insulation)
probe length LN
F12 / T12 / F23 housing
1 ½"/2"/3"
Clamp
DN 50
dairy coupling
72
70.3 (1
½")
70.5(2"/3")
70
80
Ø 21.3
Type of Probe
(see feature 70 in Ordering structure
”)
Variant “3”:
remote electronic
Variant “4”:
remote electronic with angled adaptor
18 (1½")
22.6 (2"/3")
Levelflex M FMP41C with HART/4...20 mA Installation
Endress + Hauser 15
3.3 Installation
3.3.1 Mounting kit
In addition to the tool needed for flange mounting, you will require the following tool:
• 4 mm Allen wrench for turning the housing.
3.3.2 Mounting probes
"
Caution! If there is a risk of electrostatic discharge from the product, then both processconnection and rope must be earthed before the probe is lowered into the silo.
Insert probe
• Uncoil rope and lower it slowly and carefully into the silo.
• Do not kink the rope
• Avoid any backlash, since this mightdamage the probe or the silo fittings.
!
Note!
– Flanges: bolt the flange in positionbefore
inserting the cable into the silo.
– Be sure to use unpainted metal bolts
toensure good electrical contact betweenprobe flange and process flange.
L00-FMP4xxxx-17-00- 00-en-056
Uncoil rope and lower probe slowly and carefully into the silo
Installation Levelflex M FMP41C with HART/4...20 mA
16 Endress + Hauser
3.3.3 General instructions
Normally use rod or coax probes for liquids. Rope probes are used in liquids for measuring ranges > 4m and with restricted ceiling clearance which does not allow the installation of rigid probes.
Minimum distance B of the probe to the container wall:
The wall clearance can be chosen as desired as long as the probe does not touch the tank wall.
!
Note!
• There should be no metallic parts or persons moving when installation is made in plastic tanks, also on the outside of the tank at a distance of 300 mm to the probe.
• There should no bridges to the wall created by soiling or highly viscous media.
Mounting location
• Do not mount rod or rope probes in the filling curtain (3).
• Mount rod and rope probes away from the wall (B) at such a distance that, in the event of build-up on the wall, there is still a minimum distance of 100 mm between the probe and the build-up.
• Mount rod and rope probes as far away as possible from installed fittings. "Mapping " must be carried out during commissioning in the event of distances < 300 mm.
• Minimum distance of probe end to the container floor (C): – Rope probe: 150 mm – Rod probe: 50 mm
• When installing outdoors, it is recommended that you use a protective cover (1) see Accessories on ä 61.
L00-FMP4xxxx-17-00-00-xx-007
B
C
12
Other installations
• Select the mounting location such that the distance to internals (5) (e.g. limit switch, struts) > is 300 mm over the entire length of the probe, also during operation.
• Probe must within the measuring span not touch any internals during operation.
Optimization options
• Interference echo suppression: Measurement can be optimised by electronically tuning out interference echoes.
L00-FMP41Cxx-17-00-0 0-xx-001
5
Levelflex M FMP41C with HART/4...20 mA Installation
Endress + Hauser 17
Type of probe mounting
• When installing in plastic tanks, the nozzle must have at least DN50/2". The appropriate flange must be used as the process connection.
• For nozzles up to 450 mm high, select the length of the centering rod appropriate for the nozzle height when using rope probes.
• Use spring washers (1) (see Figure below). Note! It is recommended to retighten the flange bolts periodically, depending on process temperature and pressure. Recommended torque: 60...100 Nm.
• After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment.
L00-FMP41Cxx-17-0 0-00-en-005
The coupling nut must be tightened using a torque of 5 up to a maximum of 10 Nm when installing the FMP41C in the universal adapter ("Welding boss for adapter 43 mm" ä 61).
Supporting probes against warping
For WHG or Ex approval: For probe lengths 3 m a support is required (see figure).
L00-FMP4xxxx-17-00- 00-en-065
1
£ 450 mm / 18
spring washers
Ø <25 mm
>50 mm
Probe rod c (FMP 41 C)
oated
Short metal pipe e.g. welded in place
Plastic sleeve e.g. PTFE, PEEK or PPS
e.g. 3 mm
Installation Levelflex M FMP41C with HART/4...20 mA
18 Endress + Hauser
3.3.4 Special instructions
When installing in stirring tanks, observe lateral load of probes. Possibly check whether a non­contact process, ultrasound or radar would not be better suited, above all if the stirrer generates large mechanical loads on the probe.
Installation in horizontal cylindrical and standing tanks
• Use a rod probe for measuring ranges up to 4 m. For anything over this or if there is too free cover space use a rope probe.
• Any distance from wall, as long as occasional contact is prevented.
L00-FMP4xxxx-17-00-00-yy-049
1
Installation in stilling well or bypass
• Rod and rope probes can also be installed in pipes (stilling well, bypass).
• When installing in metal pipes up to DN 150/ 6", the measuring sensitivity of the device increases such that liquids as of DK 1.4 can be measured.
• Welded joints that protrude up to approx. 5 mm/0.2" inwards do not influence measurement.
L00-FMP4xxxx-17-00-00-yy-023
Levelflex M FMP41C with HART/4...20 mA Installation
Endress + Hauser 19
3.3.5 Notes on special installation situations
Installation at an angle
• For mechanical reasons, the probe should be installed as vertically as possible.
• Installation with a deviation up to approx. 5° from the vertical axis is permitted for probes up to approx. 1 m in length.
L00-FMP4xxxx-17-00- 00-de-048
0...5
°
max. 1 m
Fixing rope probe
• The end of the probe needs to be secured if the probe would otherwise touch the silo wall, the cone or another part, or the probe comes closer than 0.5 m to a concrete wall. This is what the internal thread in the probe weight is intended for: – for 4 mm rope: M 14 – for 6 mm rope: M 20
• Preferably use the 6 mm rope probe due to the higher tensile strength when fixing a rope probe.
• The fixing must be either reliably grounded or reliably insulated (see "Accessories" on ä 64)! If it is not possible to mount the probe weight with a safe earthed connection, it can be secured using an isolated eyelet, which is available as an accessory (see ä 64).
• In order to prevent an extremely high tensile load and the risk of rope crack, the rope has to be slack. Make the rope longer than the required measuring range such that there is a sag in the middle of the rope that is ≥ 1cm/m (1"/100") of the rope length.
L00-FMP4xxxx-17-00- 00-de-019
sag of the rope:
1cm/m of the rope
length
Installation Levelflex M FMP41C with HART/4...20 mA
20 Endress + Hauser
3.3.6 Installation for difficult to access process connections
Installation with remote electronic
• Follow installation instructions on ä 16
• Mount housing on a wall or pipe as shown in the diagram.
L00-FMP4xxxx-17-00- 00-en-015
!
Note! The protective hose cannot be disassembled at these points (1).
The ambient temperature for the connecting line (2) between the probe and the electronics must not be greater than 105°C. The version with remote electronics consists of the probe, a connecting cable and the housing. If they are ordered as a complete unit they will be delivered assembled and cannot be separated.
150
ENDRESS+HAUSER Levelflex M
65 78
Ø 129
85
150
ENDRESS+HAUSER Levelflex M
65 78
Ø 129
85
52
52
150
max. 80
min. 30
96
94
94
88
88
123
2765
112
190
75
Ø 76
1
1
4 x Ø 8,5
1
1
2
pipe
wall
Note min. bend radius!
Ø 21.3
Levelflex M FMP41C with HART/4...20 mA Installation
Endress + Hauser 21
3.4 Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position:
• Undo the fixing screws (1)
• Turn the housing (2) in the required direction
• Tighten up the fixing screws (1).
L00-FMP41Cxx-17-00 -00-de-002
3.5 Post-installation check
After the measuring instrument has been installed, perform the following checks:
• Is the measuring instrument damaged (visual check)?
• Does the measuring instrument correspond to the measuring point specifications such as process temperature/pressure, ambient temperature, measuring range, etc.?
• Are the measuring point number and labeling correct (visual check)?
• Is the measuring instrument adequately protected against rain and direct sunlight (see ä 61)?
90°90
°
90°90
°
90°90
°
1
1
2
2
F12/F23 housing T12 housing
allen key 4 mm/0.1
Wiring Levelflex M FMP41C with HART/4...20 mA
22 Endress + Hauser
4 Wiring
4.1 Quick wiring guide
Wiring in F12/F23 housing
L00-FMP41Cxx-04-00-0 0-en-001
Made in Germany D-79689 Maulburg
Dat./Insp.:
Order Code:
IP68 / NEMA 6P
Ser.-No.:
4-wire
ENDRESS+HAUSER
t>85°C
TA > 7 0°C:
D01301-A
if modification see sep. label
X=
Patents
LEVELFLEX-M
90 253 VAC 1VA 10,5 32VDC1W 16 3 VDC 0,8W
Profibus PA Foundation Fieldbus
LN= PN=
4 20 mA HART 2-wire
1234
#
4
5
6
2
3
7
7
1
7
8
-
-
"
56
I+ I-
1
2
L-
L+
12
L1/L+ N/L-
3
4
I+
I-
E
N
D
R
E
S
S
+
H
A
U
S
E
R
ENDRESS+HAUSER
Sealed terminal compartment
Before connection please note the following:
The power supply must be identical to the data on the nameplate (1).
Switch off power supply before connecting up the device.
Connect Equipotential bonding to transmitter ground terminal (7) before connecting up the device.
Tighten the locking screw (8): It forms the connection between the probe and the housing ground potential.
When you use the measuring system in hazardous areas, make sure you comply with national standards and the specifications in the safety instructions (XAs). Make sure you use the specific cable gland.
On devices supplied with a certificate, the explosion protection is designed as follows:
Housing F12/F23 - EEx ia: Power supply must be intrinsically safe (not for dust-Ex).
The electronics and the current output are galvanically separated from the probe circuit.
Connect up the Levelflex M as follows:
Unscrew housing cover (2).
Remove any display (3) if fitted.
Remove cover plate from terminal compartment (4).
Pull out terminal module slightly using "pulling loop" (only 2-wire).
Only ground screening of the line (7) on sensor side.
Make connection (see pin assignment).
Re-insert terminal module.
Tighten cable gland (6). Max. torque 10...12 Nm!
Tighten screws on cover plate (4).
Insert display if fitted.
Screw on housing cover (2). (on dust-Ex torque 40 Nm).
Switch on power supply.
Insert cable (5) through gland (6). A standard installation cable is sufficient if only the analogue signal is used. Use a screened cable when working with a superimposed communications signal (HART).
Unplug display connector!
Caution!
Note!
plant ground
test sockets (output current)
power power
display unit,
recorder, PCS
2-wire-version 4-wire-version
If 4-wire for dust-Ex-applications is used, the current output is .intrinsically save
AC / DCDC
plant ground
0...20mA
Levelflex M FMP41C with HART/4...20 mA Wiring
Endress + Hauser 23
Wiring in T12 housing
L00-FMP41Cxx-04-0 0-00-en-002
Made in Germany D-79689 Maulburg
Dat./Insp.:
Order Code:
IP68 / NEMA 6P
Ser.-No.:
4-wire
ENDRESS+HAUSER
t>85°C
TA > 7 0°C:
D01301-A
if modification see sep. label
X=
Patents
LEVELFLEX-M
90 253 V AC 1VA 10,5 32VDC1W 16 3 V DC 0,8W
Profibus PA Foundation Fieldbus
LN= PN=
4 20 mA HART 2-wire
2
-
-
1234
4
3
1
5
1
2
L-
L+
7
8
3
4
I+
I-
Caution!
"
Before connection please note the following:
The power supply must be identical to the data on the nameplate (1).
Switch off power supply before connecting up the device.
Connect Equipotential bonding to transmitter ground terminal (7) before connecting up the device.
Tighten the locking screw (8): It forms the connection between the probe and the housing ground potential.
When you use the measuring system in hazardous areas, make sure you comply with national standards and the specifications in the safety instructions (XAs). Make sure you use the specific cable gland.
Connect up the Levelflex M as follows:
Before unscrew housing cover (2) at seperate connection room turn off the power supply!
Insert cable (3) through gland (4).
Only ground screening of the line (5) on sensor side.
Make connection (see pin assignment).
Tighten cable gland (4). Max. torque 10...12 Nm!
Screw on housing cover (2) (on dust-Ex torque 40 Nm).
Switch on power supply.
A standard installation cable is sufficient if only the analogue signal is used. Use a screened cable when working with a superimposed communications signal (HART).
plant ground
test sockets (output current)
power
2-wire-version
Wiring Levelflex M FMP41C with HART/4...20 mA
24 Endress + Hauser
4.2 Connecting the measuring unit
Terminal compartment
Three housings are available:
• Aluminium housing F12 with additionally sealed terminal compartment for: –standard, – EEx ia.
• Aluminium housing T12 with separate terminal compartment for: –standard, – EEx e, – EEx d – EEX ia (with overvoltage protection).
• Stainless steel 316L housing F23 for: –standard, – EEx ia.
After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment.
L00-FMR2xxxx-04-00-0 0-en-019
The instrument data are given on the nameplate together with important information regarding the analog output and voltage supply. Housing orientation regarding the wiring see "Turn housing" on ä 21.
Load HART
Minimum load for Hart communication: 250
Ground connection
It is necessary to make a good ground connection to the ground terminal on the outside of the housing, in order to achieve EMC security.
Cable gland
Terminals
for wire cross-sections of 0.5...2.5 mm
2
1 1
2 2
3 3
4 4
1
2
3
4
sealed terminal compartment
F12 housing F23 housing
T12 housing
Type Clamping area
Standard, EEx ia, IS Plastic M20x1.5 5...10 mm
EEx em, EEx nA Metal M20x1.5 7...10.5 mm
Levelflex M FMP41C with HART/4...20 mA Wiring
Endress + Hauser 25
Cable entry
Cable gland: M20x1.5 Cable entry: G ½ or ½ NPT
Supply voltage
HART, 2-wire
The following values are the voltages across the terminals directly at the instrument:
HART residual ripple, 2-wire: U
ss
200 mV
HART, 4-wire active
HART residual ripple, 4-wire, DC version: U
ss
= 2 V, voltage incl. ripple within the permitted
voltage (10.5...32 V).
Power consumption
min. 60 mW, max. 900 mW
Current consumption
Communication
Current
consumption
Terminal voltage
minimal maximal
HART
standard
4mA 16V 36V
20 mA 7.5 V 36 V
EEx ia
4mA 16V 30V
20 mA 7.5 V 30 V
EEx em
EEx d
4mA 16V 30V
20 mA 11 V 30 V
Fixed current, adjustable e.g. for solar power operation (measured value transferred at HART)
standard 11 mA 10 V 36 V
EEx ia 11 mA 10 V 30 V
Fixed current for HART Multidrop mode
standard 4 mA
1)
1) Start up current 11 mA.
16 V 36 V
EEx ia 4 mA
1)
16 V 30 V
Version Voltage Max. load
DC 10.5...32 V 600
AC 85...253 V 600
Communication
Current
consumption
Current consumption
Power consumption
HART, 2-wire 3.6…22 mA
HART, 4-wire (90...250 V
AC
) 2.4...22 mA ~ 3...6 mA / ~ 3.5 VA
HART, 4-wire (10,5...32 V
DC
) 2.4...22 mA ~ 100 mA / ~ 1 W
Wiring Levelflex M FMP41C with HART/4...20 mA
26 Endress + Hauser
Overvoltage protection
If the measuring device is used for the level measurement in flammable liquids which requires the use of an overvoltage protection according to DIN EN 60079-14, standard for testprocedures DIN IEC 60060-1 (10 kA, Puls 8/20 µs) it has to be ensured that
• the measuring device with integrated overvoltage protection with gas discharge tubes within the T12-enclosure is used, refer to product overview on ä 8
or
• this protection is achieved by the use of other appropriate measures (external protection devices e.g. HAW262Z).
4.2.1 HART connection with Endress+Hauser RMA422 / RN221N
L00-FMR2xxxx-04-00-0 0-en-009
4.2.2 HART connection with other supplies
L00-FMR2xxxx-04-00-0 0-en-008
4...20 mA
1
234
ENDRESS + HAUSER RMA 422
Commubox FXA1
91/
FXA1
95
RMA422 RN221N
HART
DXR375
1
# % &
Copy
G H I
P Q R S
, ( )
A B C
Paste
Page
On
Page
Up
DeleteBksp
Insert
J K L
T UV
_ < >
D E F
Hot Key
+ Hot Key
M N O
W XY Z
+ * /
4
7
.
2
5
8
0
375
FIELD COMMUNICATOR
3
6
9
-
FMP40:LIC0001 ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
dsdmdm df das. asdas fa asas la.
FXA193
- ToF Tool ­Fieldtool Package
- FieldCare
- ToF Tool ­Fieldtool Package
- FieldCare
1
234
HART
DXR375
1
# % &
Copy
G H I
P Q R S
, ( )
A B C
Paste
Page On
Page Up
DeleteBksp
Insert
J K L
T UV
_ < >
D E F
Hot Key
+ Hot Key
M N O
W XY Z
+ * /
4
7
.
2
5
8
0
375
FIELD COMMUNICATOR
3
6
9
-
FMP40:LIC0001 ONLINE
1 GROUP SELECT
2 PV 8.7 m
HELP SAVE
dsdmdm df das. asdas fa asas la.
- ToFTool ­Fieldtool Package
- FieldCare
- ToFTool ­Fieldtool Package
- Fieldcare
Commubox FXA191/FXA195
FXA193
≥Ω250
PLC
DC power supply
unit
or
4...20 mA
Levelflex M FMP41C with HART/4...20 mA Wiring
Endress + Hauser 27
"
Caution! If the HART communication resistor is not built into the supply unit and the HART interface is to be used, it is necessary to insert a communication resistor of 250 into the 2-wire line.
4.3 Recommended connection
4.3.1 Equipotential bonding
Connect the Equipotential bonding to the external ground terminal (1) of the transmitter.
L00-FMP41Cxx-17-0 0-00-en-003
4.3.2 Wiring screened cable
"
Caution! In Ex applications, the instrument must only be grounded on the sensor side. Further safety instructions are given in the separate documentation for applications in explosion hazardous areas.
4.4 Degree of protection
• with closed housing tested according to – IP68, NEMA6P (24 h at 1.83 m under water surface) – IP66, NEMA4X
• with open housing: IP20, NEMA1 (also ingress protection of the display)
4.5 Post-connection check
After wiring the measuring instrument, perform the following checks:
• Is the terminal allocation correct (see ä 22 and ä 23)?
• Is the cable gland tight?
• Is the housing cover screwed tight?
• If auxiliary power is available: Is the instrument ready for operation and is the liquid crystal display visible?
1
1
F12/F23 housing T12 housing
Operation Levelflex M FMP41C with HART/4...20 mA
28 Endress + Hauser
5Operation
5.1 Quick operation guide
L00-FMP4xxxx-19-00- 00-en-001
X
X
X
X
S
SS
O
OO
FF
>3 s
F
...
2x
ENDRESS + HAUSER
E
+
...
...
Selection and configuration in Operation menu:
Group Selection
Function Group
unction
Note!
Selection menus:
function
Typing in numerals and text:
numeral / text
function
function
Group selection
Measured value display
1.) Change from Measured Value Display to by pressing
2.) Press or to select the required (e.g.. "basic setup (00)") and confirm by pressing (e.g. "tank shape (002)") is selected.
The active selection is marked by a in front of the menu text.
3.) Activate Edit mode with or .
a) Select the required in selected (e.g. "tank shape (002)") with or . b) confirms selection appears in front of the selected parameter c) confirms the edited value system quits Edit mode d) / (= ) interrupts selection system quits Edit mode
a) Press or to edit the first character of the (e.g. "empty calibr. (005)") b) positions the cursor at the next character (a) until you have completed your input c) if a symbol appears at the cursor, press to accept the value entered
system quits Edit mode
d) / (= ) interrupts the input,
4) Press to select the next (e.g. "medium property (003)")
5) Press / (= ) once return to previous (e.g. "tank shape (002)")
Press / (= ) twice return to
6) Press / (= ) to return to
F
SO
O
SO
F
S
X
S
F
S
F F OS X
OS
F
OX
F OS X OS OX
➜✔
First f
continue with
system quits Edit mode
Parameter
Return to Group Selection
basic setup
safety settings
linearisation
extended calibr.
tank shape
Standard aluminium tank plastic tank bypass / pipe coax probe concrete wall
medium property
Loading...
+ 64 hidden pages