Endress+Hauser Levelflex FMP56, Levelflex FMP57 Operating Instructions Manual

Page 1
BA01009F/00/EN/15.16 71344082
01.01.zz (Device firmware)
Products Solutions Services
Operating Instructions
Levelflex FMP56, FMP57 PROFIBUS PA
Guided wave radar
Page 2
Order code:
Ext. ord. cd.:
Ser. no.:
www.endress.com/deviceviewer
Endress+Hauser Operations App
XXXXXXXXXXXX
XXXXX-XXXXXX
XXX.XXXX.XX
Serial number
1.
3.
2.
A0023555
Page 3

Table of contents

Table of contents
1 Important document information .... 5
1.1 Document function ..................... 5
1.2 Symbols .............................. 5
1.2.1 Safety symbols .................. 5
1.2.2 Electrical symbols ................ 5
1.2.3 Tool symbols .................... 6
1.2.4 Symbols for certain types of
information .................... 6
1.2.5 Symbols in graphics ............... 6
1.2.6 Symbols at the device ............. 7
1.3 Supplementary documentation ............. 8
1.3.1 Safety Instructions (XA) ............ 9
2 Basic safety instructions ........... 12
2.1 Requirements for the personnel ........... 12
2.2 Designated use ....................... 12
2.3 Workplace safety ...................... 13
2.4 Operational safety ..................... 13
2.5 Product safety ........................ 13
2.5.1 CE mark ...................... 13
2.5.2 EAC conformity ................. 13
3 Product description ................ 14
3.1 Product design ........................ 14
3.1.1 Levelflex FMP56/FMP57 ......... 14
3.1.2 Electronics housing .............. 15
3.2 Registered trademarks .................. 16
4 Incoming acceptance and product
identification ..................... 17
4.1 Incoming acceptance ................... 17
4.2 Product identification .................. 17
4.2.1 Nameplate .................... 18
5 Storage, Transport ................ 19
5.1 Storage conditions ..................... 19
5.2 Transport product to the measuring point .... 19
6 Mounting ......................... 20
6.1 Mounting requirements ................. 20
6.1.1 Suitable mounting position ........ 20
6.1.2 Applications with restricted
mounting space ................. 22
6.1.3 Notes on the mechanical load of the
probe ........................ 23
6.1.4 Notes on the process connection .... 27
6.1.5 Securing the probe .............. 31
6.1.6 Special mounting conditions ....... 33
6.2 Mounting the device ................... 37
6.2.1 Required mounting tools .......... 37
6.2.2 Shortening the probe ............. 37
6.2.3 Mounting the device ............. 39
6.2.4 Mounting the "Sensor remote"
version ....................... 40
6.2.5 Turning the transmitter housing .... 42
6.2.6 Turning the display module ........ 42
6.3 Post-installation check .................. 43
7 Electrical connection .............. 44
7.1 Connection conditions .................. 44
7.1.1 Terminal assignment ............. 44
7.1.2 Cable specification ............... 45
7.1.3 Device plug connectors ........... 46
7.1.4 Power supply .................. 47
7.1.5 Overvoltage protection ........... 47
7.2 Connecting the device .................. 48
7.2.1 Pluggable spring-force terminals .... 49
7.3 Post-connection check .................. 49
8 Operation options ................. 51
8.1 Overview ............................ 51
8.1.1 Local operation ................. 51
8.1.2 Operation with remote display and
operating module FHX50 .......... 52
8.1.3 Remote operation ............... 52
8.2 Structure and function of the operating
menu .............................. 54
8.2.1 Structure of the operating menu .... 54
8.2.2 User roles and related access
authorization .................. 56
8.2.3 Write protection via access code ..... 57
8.2.4 Disabling write protection via access
code ......................... 58
8.2.5 Deactivation of the write protection
via access code ................. 58
8.2.6 Write protection via write protection
switch ........................ 59
8.2.7 Enabling and disabling the keypad
lock ......................... 61
8.3 Display and operating module ............ 62
8.3.1 Display appearance .............. 62
8.3.2 Operating elements .............. 65
8.3.3 Entering numbers and text ........ 66
8.3.4 Opening the context menu ......... 68
8.3.5 Envelope curve on the display and
operating module ............... 69
9 Integration into a PROFIBUS
network .......................... 70
9.1 Overview of the device database files (GSD) .. 70
9.2 Set device address ..................... 70
9.2.1 Hardware adressing ............. 70
9.2.2 Software addressing ............. 70
Endress+Hauser 3
Page 4
Table of contents
10 Commissioning via wizard ......... 72
11 Commissioning via operating
menu ............................. 73
11.1 Installation and function check ............ 73
11.2 Setting the operating language ............ 73
11.3 Configuration of a level measurement ...... 74
11.4 Recording the reference curve ............ 76
11.5 Configuration of the on-site display ........ 77
11.5.1 Factory settings of the on-site
display for level measurements ..... 77
11.5.2 Adjustment of the on-site display ... 77
11.6 Configuration management .............. 78
11.7 Protection of the settings against
unauthorized changes .................. 79
12 Diagnostics and troubleshooting ... 80
12.1 General trouble shooting ................ 80
12.1.1 General errors .................. 80
12.1.2 Parametrization errors ........... 81
12.2 Diagnostic information on local display ...... 82
12.2.1 Diagnostic message .............. 82
12.2.2 Calling up remedial measures ...... 84
12.3 Diagnostic event in the operating tool ....... 85
12.4 Diagnostic list ........................ 85
12.5 List of diagnostic events ................. 86
12.6 Event logbook ........................ 87
12.6.1 Event history ................... 87
12.6.2 Filtering the event logbook ........ 88
12.6.3 Overview of information events ..... 88
12.7 Firmware history ...................... 90
15.2 Communication-specific accessories ....... 100
15.3 Service-specific accessories .............. 100
15.4 System components ................... 100
16 Operating menu .................. 101
16.1 Overview of the operating menu (display
module) ........................... 101
16.2 Overview of the operating menu (operating
tool) .............................. 108
16.3 "Setup" menu ........................ 114
16.3.1 "Mapping" wizard ............... 121
16.3.2 "Analog input 1 to 6" submenu ..... 122
16.3.3 "Advanced setup" submenu ........ 124
16.4 "Diagnostics" menu .................... 167
16.4.1 "Diagnostic list" submenu ......... 169
16.4.2 "Event logbook" submenu ......... 170
16.4.3 "Device information" submenu ..... 171
16.4.4 "Measured values" submenu ....... 173
16.4.5 "Analog input 1 to 6" submenu ..... 175
16.4.6 "Data logging" submenu .......... 177
16.4.7 "Simulation" submenu ........... 180
16.4.8 "Device check" submenu .......... 185
16.4.9 "Heartbeat" submenu ............ 187
Index ................................. 188
13 Maintenance ...................... 91
13.1 Exterior cleaning ...................... 91
14 Repairs ........................... 92
14.1 General information on repairs ............ 92
14.1.1 Repair concept ................. 92
14.1.2 Repairs to Ex-approved devices ..... 92
14.1.3 Replacement of an electronics
module ....................... 92
14.1.4 Replacement of a device .......... 92
14.2 Spare parts .......................... 93
14.3 Return .............................. 93
14.4 Disposal ............................ 93
15 Accessories ....................... 94
15.1 Device-specific accessories ............... 94
15.1.1 Weather protection cover ......... 94
15.1.2 Mounting bracket for the electronics
housing ...................... 95
15.1.3 Extension rod / centering HMP40 ... 96
15.1.4 Mounting kit, isolated ............ 97
15.1.5 Remote display FHX50 ........... 98
15.1.6 Overvoltage protection ........... 99
Page 5
Levelflex FMP56, FMP57 PROFIBUS PA Important document information
DANGER
WARNING
CAUTION
NOTICE

1 Important document information

1.1 Document function

These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.

1.2 Symbols

1.2.1 Safety symbols

Symbol Meaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in personal injury.

1.2.2 Electrical symbols

Symbol Meaning
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential equalization line or a star grounding system depending on national or company codes of practice.
Endress+Hauser 5
Page 6
Important document information Levelflex FMP56, FMP57 PROFIBUS PA
A
1.
1.

1.2.3 Tool symbols

Symbol Meaning
Torx screwdriver
A0013442
Flat blade screwdriver
A0011220
Cross-head screwdriver
A0011219
Allen key
A0011221
Hexagon wrench
A0011222

1.2.4 Symbols for certain types of information

Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Notice or individual step to be observed
, 2., 3.… Series of steps
Result of a step
Help in the event of a problem
Visual inspection

1.2.5 Symbols in graphics

Symbol Meaning
1, 2, 3 ... Item numbers
, 2., 3.… Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
Page 7
Levelflex FMP56, FMP57 PROFIBUS PA Important document information
-
.
Symbol Meaning
Hazardous area
Indicates a hazardous area.
Safe area (non-hazardous area)
Indicates the non-hazardous area.

1.2.6 Symbols at the device

Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables.
Endress+Hauser 7
Page 8
Important document information Levelflex FMP56, FMP57 PROFIBUS PA

1.3 Supplementary documentation

Document Purpose and content of the document
Technical Information TI01004F (FMP56, FMP57)
Brief Operating Instructions KA01073F (FMP56/FMP57, PROFIBUS PA)
Description of Device Parameters GP01001F (FMP5x, PROFIBUS PA)
Special documentation SD00326F
Special documentation SD01872F
Planning aid for your device
The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
Guide that takes you quickly to the 1st measured value
The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning.
Reference for your parameters
The document provides a detailed explanation of each individual parameter in the operating menu. The description is aimed at those who work with the device over the entire life cycle and perform specific configurations.
Functional Safety Manual
The document is part of the Operating Instructions and serves as a reference for application-specific parameters and notes.
Manual for Heartbeat Verification and Heartbeat Monitoring
The document contains descriptions of the additonal parameters and technical data which are available with the Heartbeat Verification and Heartbeat Monitoring application packages.
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer : Enter the serial number from the nameplate (www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate.
Page 9
Levelflex FMP56, FMP57 PROFIBUS PA Important document information

1.3.1 Safety Instructions (XA)

Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They are an integral part of the Operating Instructions.
Feature 010 Approval Available for Feature 020: "Power Supply; Output"
BA ATEX II 1G Ex ia IIC T6 Ga • FMP56
• FMP57
BB ATEX II 1/2G Ex ia IIC T6 Ga/Gb • FMP56
• FMP57
BE ATEX II 1D Ex t IIIC Da • FMP56
• FMP57
BF ATEX II 1/2D Ex t IIIC Da/Db • FMP56
• FMP57
BG ATEX II 3G Ex nA IIC T6 Gc • FMP56
• FMP57
BH ATEX II 3G Ex ic IIC T6 Gc • FMP56
• FMP57
B2 ATEX II 1/2G Ex ia IIC T6 Ga/Gb, 1/2D Ex ia IIIC Da/Db • FMP56
• FMP57
B3 ATEX II 1/2G Ex d[ia] IIC T6 Ga/Gb, 1/2 D Ex t IIIC
Da/Db
CD CSA C/US DIP Cl.II,III Div.1 Gr.E-G • FMP56
C2 CSA C/US IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 Div.2, Ex ia • FMP56
C3 CSA C/US XP Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 Div.2, Ex d • FMP56
FB FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia, NI Cl.1 Div.2 • FMP56
FD FM XP Cl.I,II,III Div.1 Gr.A-G, AEx d, NI Cl.1 Div.2 • FMP56
FE FM DIP Cl.II,III Div.1 Gr.E-G • FMP56
GA EAC Ex ia IIC T6 Ga • FMP56
GB EAC Ex ia IIC T6 Ga/Gb • FMP56
IA IEC Ex ia IIC T6 Ga • FMP56
IB IEC Ex ia IIC T6 Ga/Gb • FMP56
IE IEC Ex t IIIC Da • FMP56
IF IEC Ex t IIIC Da/Db • FMP56
IG IEC Ex nA IIC T6 Gc • FMP56
IH IEC Ex ic IIC T6 Gc • FMP56
I2 IEC Ex ia IIC T6 Ga/Gb, Ex ia IIIC Da/Db • FMP56
• FMP56
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
• FMP57
1)
A
XA00496F XA01125F XA01126F XA00516F -
XA00496F XA01125F XA01126F XA00516F -
XA00501F XA00501F XA00501F XA00521F XA00501F
XA00501F XA00501F XA00501F XA00521F XA00501F
XA00498F XA01130F XA01131F XA00518F XA01132F
XA00498F XA01130F XA01131F XA00518F -
XA00502F XA00502F XA00502F XA00522F -
XA00503F XA00503F XA00503F XA00523F XA01136F
XA00529F XA00529F XA00529F XA00570F XA00529F
XA00530F XA00530F XA00530F XA00571F XA00530F
XA00529F XA00529F XA00529F XA00570F XA00529F
XA00531F XA00531F XA00531F XA00573F XA00531F
XA00532F XA00532F XA00532F XA00572F XA00532F
XA00532F XA00532F XA00532F XA00572F XA00532F
XA01380F XA01380F XA01380F XA01381F XA01380F
XA01380F XA01380F XA01380F XA01381F XA01380F
XA00496F XA01125F XA01126F XA00516F -
XA00496F XA01125F XA01126F XA00516F -
XA00501F XA00501F XA00501F XA00521F XA00501F
XA00501F XA00501F XA00501F XA00521F XA00501F
XA00498F XA01130F XA01131F XA00518F XA01132F
XA00498F XA01130F XA01131F XA00518F -
XA00502F XA00502F XA00502F XA00522F -
2)
B
3)
C
4)/G 5)
E
6)/L 7)
K
Endress+Hauser 9
Page 10
Important document information Levelflex FMP56, FMP57 PROFIBUS PA
Feature 010 Approval Available for Feature 020: "Power Supply; Output"
I3 IEC Ex d [ia] IIC T6 Ga/Gb, Ex t IIIC Da/Db • FMP56
• FMP57
KA KC Ex ia IIC T6 Ga • FMP56
• FMP57
KB KC Ex ia IIC T6 Ga/Gb • FMP56
• FMP57
MA INMETRO Ex ia IIC T6 Ga • FMP56
• FMP57
ME INMETRO Ex t IIIC Da • FMP56
• FMP57
MH INMETRO Ex ic IIC T6 Gc • FMP56
• FMP57
NA NEPSI Ex ia IIC T6 Ga • FMP56
• FMP57
NB NEPSI Ex ia IIC T6 Ga/Gb • FMP56
• FMP57
NF NEPSI DIP A20/21 T85…90oC IP66 • FMP56
• FMP57
NG NEPSI Ex nA II T6 Gc • FMP56
• FMP57
NH NEPSI Ex ic IIC T6 Gc • FMP56
• FMP57
N2 NEPSI Ex ia IIC T6 Ga/Gb, Ex iaD 20/21 T85…90°C • FMP56
• FMP57
N3 NEPSI Ex d[ia] IIC T6 Ga/Gb, DIP A20/21 T85…90°C
IP66
• FMP56
• FMP57
8A FM/CSA IS+XP Cl.I,II,III Div.1 Gr.A-G • FMP56
• FMP57
1)
A
XA00503F XA00503F XA00503F XA00523F XA01136F
XA01169F - XA01169F - -
XA01169F - XA01169F - -
XA01038F XA01038F XA01038F - XA01038F
XA01043F XA01043F XA01043F - XA01043F
XA01040F XA01040F XA01040F - XA01040F
XA00634F XA00634F XA00634F XA00640F XA00634F
XA00634F XA00634F XA00634F XA00640F XA00634F
XA00637F XA00637F XA00637F XA00643F XA00637F
XA00635F XA00635F XA00635F XA00641F XA00635F
XA00635F XA00635F XA00635F XA00641F XA00635F
XA00638F XA00638F XA00638F XA00644F XA00638F
XA00639F XA00639F XA00639F XA00645F XA00639F
XA00531F XA00532F
2)
B
XA00531F XA00532F
3)
C
XA00531F XA00532F
4)/G 5)
E
XA00572F XA00573F
6)/L 7)
K
XA00531F XA00532F
1) A: 2-wire; 4-20mA HART
2) B: 2-wire; 4-20mA HART, switch output
3) C: 2-wire; 4-20mA HART, 4-20mA
4) E: 2-wire; FOUNDATION Fieldbus, switch output
5) G: 2-wire; PROFIBUS PA, switch output
6) K: 4-wire 90-253VAC; 4-20mA HART
7) L: 4-wire 10,4-48VDC; 4-20mA HART
For certified devices the relevant Safety Instructions (XA) are indicated on the nameplate.
Page 11
Levelflex FMP56, FMP57 PROFIBUS PA Important document information
Ex-marking in case of connected FHX50 remote display
If the device is prepared for the remote display FHX50 (product structure: feature 030: Display, Operation", option L or M), the Ex marking of some certificates changes according to the following table
Feature 010 ("Approval") Feature 030 ("Display, Operation") Ex-marking
BE L or M ATEX II 1D Ex ta [ia] IIIC T
BF L or M ATEX II 1/2 D Ex ta [ia Db] IIIC Txx°C Da/Db
BG L or M ATEX II 3G Ex nA [ia Ga] IIC T6 Gc
BH L or M ATEX II 3G Ex ic [ia Ga] IIC T6 Gc
B3 L or M ATEX II 1/2G Ex d [ia] IIC T6 Ga/Gb,
IE L or M IECEx Ex ta [ia] IIIC T500 xx°C Da
IF L or M IECEx ta [ia Db] IIIC Txx°C Da/Db
IG L or M IECEx Ex nA [ia Ga] IIC T6 Gc
IH L or M IECEx Ex ic [ia Ga] IIC T6 Gc
I3 L or M IECEx Ex d [ia] IIC T6 Ga/Gb,
1)
:
xx°C Da
500
ATEX II 1/2D Ex ta [ia Db] IIIC Txx°C Da/Db
IECEx Ex ta [ia Db] IIIC Txx°C Da/Db
1) The marking of certificates not mentioned in this table are not affected by the FHX50.
Endress+Hauser 11
Page 12
Basic safety instructions Levelflex FMP56, FMP57 PROFIBUS PA

2 Basic safety instructions

2.1 Requirements for the personnel

The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function
and task. Are authorized by the plant owner/operator.
Are familiar with federal/national regulations.
Before starting work, read and understand the instructions in the manual and
supplementary documentation as well as the certificates (depending on the application). Follow instructions and comply with basic conditions.
The operating personnel must fulfill the following requirements:
Are instructed and authorized according to the requirements of the task by the facility's
owner-operator. Follow the instructions in this manual.

2.2 Designated use

Application and measured materials
The measuring device described in these Operating Instructions is intended only for level measurement of bulk solids. Depending on the version ordered the device can also measure potentially explosive, flammable, poisonous and oxidizing materials.
Observing the limit values specified in the "Technical data" and listed in the Operating Instructions and supplementary documentation, the measuring device may be used for the following measurements only:
Measured process variables: level
Calculated process variables: Volume or mass in arbitrarily shaped vessels (calculated
from the level by the linearization functionality)
To ensure that the measuring device remains in proper condition for the operation time:
Use the measuring device only for measured materials against which the process-
wetted materials are adequately resistant. Observe the limit values in "Technical data".
Incorrect use
The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
For special measured materials and cleaning agents, Endress+Hauser is glad to provide
assistance in verifying the corrosion resistance of wetted materials, but does not accept any warranty or liability.
Residual risk
The electronics housing and its built-in components such as display module, main electronics module and I/O electronics module may heat to 80 °C (176 °F) during operation through heat transfer from the process as well as power dissipation within the electronics. During operation the sensor may assume a temperature near the temperature of the measured material.
Danger of burns due to heated surfaces!
For high process temperatures: Install protection against contact in order to prevent
burns.
Page 13
Levelflex FMP56, FMP57 PROFIBUS PA Basic safety instructions

2.3 Workplace safety

For work on and with the device:
Wear the required personal protective equipment according to federal/national
regulations.

2.4 Operational safety

Risk of injury.
Operate the device in proper technical condition and fail-safe condition only.
The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers.
If, despite this, modifications are required, consult with the manufacturer.
Repair
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
Observe federal/national regulations pertaining to repair of an electrical device.
Use original spare parts and accessories from the manufacturer only.
Hazardous area
To eliminate a danger for persons or for the facility when the device is used in the hazardous area (e.g. explosion protection, pressure vessel safety):
Based on the nameplate, check whether the ordered device is permitted for the
intended use in the hazardous area. Observe the specifications in the separate supplementary documentation that is an
integral part of these Instructions.

2.5 Product safety

This measuring device is designed in accordance with good engineering practice to meet state-of-the-art safety requirements, has been tested, and left the factory in a condition in which it is safe to operate. It meets general safety standards and legal requirements.

2.5.1 CE mark

The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.

2.5.2 EAC conformity

The measuring system meets the legal requirements of the applicable EAC guidelines. These are listed in the corresponding EAC Declaration of Conformity together with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark.
Endress+Hauser 13
Page 14
Product description Levelflex FMP56, FMP57 PROFIBUS PA
1
2
5
3
4

3 Product description

3.1 Product design

3.1.1 Levelflex FMP56/FMP57

A0012470
 1 Design of the Levelflex
1 Electronics housing 2 Process connection (here as an example: flange) 3 Rope probe 4 End-of-probe weight 5 Rod probe
Page 15
Levelflex FMP56, FMP57 PROFIBUS PA Product description
Esc
+
E
1
2
3
4
5
6
9
7
8

3.1.2 Electronics housing

A0012422
 2 Design of the electronics housing
1 Electronics compartment cover 2 Display module 3 Main electronics module 4 Cable glands (1 or 2, depending on instrument version) 5 Nameplate 6 I/O electronics module 7 Terminals (pluggable spring terminals) 8 Connection compartment cover 9 Grounding terminal
Endress+Hauser 15
Page 16
Product description Levelflex FMP56, FMP57 PROFIBUS PA

3.2 Registered trademarks

PROFIBUS
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
KALREZ®, VITON
Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA
TEFLON
Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA
TRI CLAMP
Registered trademark of Alfa Laval Inc., Kenosha, USA
®
®
®
®
Page 17

Levelflex FMP56, FMP57 PROFIBUS PA Incoming acceptance and product identification

DELIVERYNOTE
1 = 2
DELIVERYNOTE
Madein Germany, 79689 Maulburg
4 Incoming acceptance and product
identification

4.1 Incoming acceptance

Is the order code on the delivery
A0015502
A0022480
A0022486
note (1) identical to the order code on the product sticker (2)?
Are the goods undamaged?
A0015502
A0022489
Do the nameplate data match the
A0015502
A0022491
ordering information on the delivery note?
Is the DVD (operating tool)
A0015502
present? If required (see nameplate): Are the Safety Instructions (XA) present?
A0022494
If one of the conditions does not comply, contact your Endress+Hauser distributor.

4.2 Product identification

The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer ( www.endress.com/deviceviewer ): All information about the measuring device is displayed.
• Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed.
Endress+Hauser 17
Page 18
Incoming acceptance and product identification Levelflex FMP56, FMP57 PROFIBUS PA
20
21
22
24
25
23
26
1
2
3 4
5
6
7
8
9
10
19
18
17
16
15
14
Ext. ord. cd.:
Order code: Ser. no.:
LN =
Lref =
Mat.:
Date:
FW:
Dev.Rev.:
DeviceID:
Ta:
if modification see sep. label
X =
MWP:
12
11
47 (1.85)
92 (3.62)
mm (in)
13

4.2.1 Nameplate

A0010725
 3 Nameplate of the Levelflex
1 Device name 2 Address of manufacturer 3 Order code 4 Serial number (Ser. no.) 5 Extended order code (Ext. ord. cd.) 6 Process pressure 7 Gas phase compensation: reference distance 8 Certificate symbol 9 Certificate and approval relevant data 10 Degree of protection: e.g. IP, NEMA 11 Document number of the Safety Instructions: e.g. XA, ZD, ZE 12 2-D matrix code (QR code) 13 Modification mark 14 Manufacturing date: year-month 15 Permitted temperature range for cable 16 Geräterevision (Dev.Rev.) 17 Additional information about the device version (certificates, approvals, communication): e.g. SIL, PROFIBUS 18 Firmware version (FW) 19 CE mark, C-Tick 20 DeviceID 21 Material in contact with process 22 Permitted ambient temperature (Ta)
23 Size of the thread of the cable glands 24 Length of probe 25 Signal outputs 26 Operating voltage
Only 33 digits of the extended order code can be indicated on the nameplate. If the extended order code exceeds 33 digits, the rest will not be shown. However, the complete extended order code can be viewed in the operating menu of the device in the Extended order code 1 to 3 parameter.
Page 19
Levelflex FMP56, FMP57 PROFIBUS PA Storage, Transport

5 Storage, Transport

5.1 Storage conditions

• Permitted storage temperature: –40 to +80 °C (–40 to +176 °F)
• Use the original packaging.

5.2 Transport product to the measuring point

WARNING
L
Housing or probe may be damaged or break away.
Risk of injury!
Transport the measuring device to the measuring point in its original packaging or at
the process connection. Do not fasten lifting devices (hoisting slings, lifting eyes etc.) at the housing or the
probe but at the process connection. Take into account the mass center of the device in order to avoid unintended tilting. Comply with the safety instructions, transport conditions for devices over 18kg
(39.6lbs) (IEC61010).
A0013920
A0014264
Endress+Hauser 19
Page 20
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
A
C
1 32
4
B

6 Mounting

6.1 Mounting requirements

6.1.1 Suitable mounting position

A0021468
 4 Mounting requirements for Levelflex
Mounting distances
• Distance (A) between wall and rod or rope probe: – for smooth metallic walls: > 50 mm (2 in) – for plastic walls: > 300 mm (12 in) to metallic parts outside the vessel – for concrete walls: > 500 mm (20 in), otherwise the available measuring range may be
reduced.
• Distance (B) between rod or rope probe and internal fittings in the vessel: > 300 mm (12 in)
• When using more than one Levelflex: Minimum distance between the sensor axes: 100 mm (3.94 in)
• Distance (C) from end of probe to bottom of the vessel: – Rope probe: > 150 mm (6 in) – Rod probe: > 10 mm (0.4 in)
Page 21
Levelflex FMP56, FMP57 PROFIBUS PA Mounting
Additional conditions
• When mounting in the open, a weather protection cover (1) may be installed to protect the device against extreme weather conditions.
• In metallic vessels: Preferably do not mount the probe in the center of the vessel (2), as this would lead to increased interference echoes. If a central mounting position can not be avoided, it is crucial to perform an interference echo suppresion(mapping) after the commissioning of the device.
• Do not mount the probe in the filling curtain (3).
• Avoid buckling the rope probe during installation or operation (e.g. through product movement against silo wall) by selecting a suitable mounting location.
• Check the probe regularly for defects.
With suspended rope probes (probe end not fixed at the bottom) the distance between the probe rope and internal fittings in the tank must not fall below 300 mm (12") during the entire process. A sporadic contact between the probe weight and the cone of the vessel, however, does not influence the measurement as long as the dielectric constant of the medium is at least DC = 1.8.
When mounting the electronics housing into a recess (e.g. in a concrete ceiling), observe a minimum distance of 100 mm (4 inch) between the cover of the terminal compartment / electronics compartment and the wall. Otherwise the connection compartment / electronics compartment is not accessible after installation.
Endress+Hauser 21
Page 22
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
A
B
C
C
r = 100 (4)
min
r = 100 (4)
min
6 Nm (4.42 lbf ft)
6 Nm (4.42 lbf ft)
6 Nm (4.42 lbf ft)
6 Nm (4.42 lbf ft)

6.1.2 Applications with restricted mounting space

Mounting with remote sensor
The device version with a remote sensor is suited for applications with restricted mounting space. In this case the electronics housing is mounted at a separate position from which it is easier accessible.
A0014794
A Angled plug at the probe B Angled plug at the electronics housing C Length of the remote cable as ordered
• Product structure, feature 600 "Probe Design": – Option MB "Sensor remote, 3m/9ft cable" – Option MC "Sensor remote, 6m/18ft cable" – Option MB "Sensor remote, 9m/27ft cable"
• The remote cable is supplied with these device versions Minimum bending radius: 100 mm (4 inch)
• A mounting bracket for the electronics housing is supplied with these device versions. Mounting options: – Wall mounting – Pipe mounting; diameter: 42 to 60 mm (1-1/4 to 2 inch)
• The connection cable has got one straight and one angled plug (90°). Depending on the local conditions the angled plug can be connected at the probe or at the electronics housing.
Probe, electronics and connection cable are adjusted to match each other. They are marked by a common serial number. Only components with the same serial number shall be connected to each other.
Page 23
Levelflex FMP56, FMP57 PROFIBUS PA Mounting

6.1.3 Notes on the mechanical load of the probe

Tensile load limit of rope probes
Sensor Feature 060 Probe Tensile load limit [kN] Max. rupture load [kN]
FMP56 LA, LB Rope 4mm (1/6") 316 12 20
NB, NE Rope 6mm (1/4") PA>Steel 12 20
FMP57 LA, LB Rope 4mm (1/6") 316 12 20
LC, LD Rope 6mm (1/4") 316 30 42
NB, NE Rope 6mm (1/4") PA>Steel 12 20
NC, NF Rope 8mm (1/3") PA>Steel 30 42
1) The ceiling of the silo must be designed to withstand this load.
1)
Tensile load
Bulk solids exert tensile forces on rope probes whose height increases with:
• the length of the probe, i.e. max. cover
• the bulk density of the product,
• the silo diameter and
• the diameter of the probe rope
Since the tensile forces are also heavily dependent on the viscosity of the product, a higher safety factor is necessary for highly viscous products and if there is a risk of cornice buildup. In critical cases it is better to use a 6 mm rope instead of a 4 mm one.
The same forces also act on the silo cover. On a fixed rope, the tensile forces are definitely greater, but this can not be calculated. Observe the tensile strength of the probes.
Options for reducing the tensile forces:
• Shorten the probe.
• If the maximum tensile load is exceeded, check whether it would be possible to use a non-contact Ultrasonic or Level-Radar device.
The following diagrams show typical loads for frequently occurring bulk solids as reference values. The calculation is performed for the following conditions:
• Calculation according to DIN 1055, Part 6 for the cylindrical part of the silo.
• Suspended probe (probe end not fixed at the bottom)
• Free-flowing bulk solid, i.e. mass flow. A calculation for core flow is not possible. In the event of collapsing cornices, considerably higher loads can occur.
• The specification for tensile forces contains the safety factor 2 (in addition to the safety factors already taken into account by DIN 1055), which compensates for the normal fluctuation range in pourable bulk solids.
Endress+Hauser 23
Page 24
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
0 5 10 15 20 25 30 35
0
10
20
30
40
50
60
F [kN]
6 mm
L [m]
F [kN]
4 mm
0
4
8
12
16
20
24
28
32
36
40
A
B
C
D
F [kN]
6 mm
L [m]
F [kN]
4 mm
0 5 10 15 20 25 30 35
A
B
C
0
2
4
6
8
10
12
14
16
18
0
2
4
6
8
10
12
D
A0017170
 5 Silica sand in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm
(0,24 in) and 4mm (0,16 in)
A Silo diameter 12 m (40 ft) B Silo diameter 9 m (30 ft) C Silo diameter 6 m (20 ft) D Silo diameter 3 m (10 ft)
 6 Polyethylene pellets in silo with smooth metallic walls; tensile load as a function of level L for rope
diameters 6mm (0,24 in) and 4mm (0,16 in)
A Silo diameter 12 m (40 ft) B Silo diameter 9 m (30 ft) C Silo diameter 6 m (20 ft) D Silo diameter 3 m (10 ft)
A0017171
Page 25
Levelflex FMP56, FMP57 PROFIBUS PA Mounting
F [kN]
6 mm
L [m]
F [kN]
4 mm
A
B
C
D
0 5 10 15 20 25 30 35
0
4
8
12
16
20
24
28
32
36
0
4
8
12
16
20
24
F [kN]
6 mm
L [m]
F [kN]
4 mm
A
B
C
D
0 5 10 15 20 25 30 35
0
10
20
30
40
50
60
0
4
8
12
16
20
24
28
32
36
40
A0017172
 7 Wheat in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm
(0,24 in) and 4mm (0,16 in)
A Silo diameter 12 m (40 ft) B Silo diameter 9 m (30 ft) C Silo diameter 6 m (20 ft) D Silo diameter 3 m (10 ft)
 8 Cement in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm
A Tank diameter 12 m (40 ft) B Tank diameter 9 m (30 ft) C Tank diameter 6 m (20 ft) D Tank diameter 3 m (10 ft)
(0,24 in) and 4mm (0,16 in)
A0017173
Endress+Hauser 25
Page 26
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
Bending strength of rod probes
Sensor Feature 060 Probe Bending strength [Nm]
FMP57 AE, AF Rod 16mm (0.63") 316L 30
Page 27
Levelflex FMP56, FMP57 PROFIBUS PA Mounting

6.1.4 Notes on the process connection

Probes are mounted to the process connection with threaded connections or flanges. If during this installation there is the danger that the probe end moves so much that it touches the tank floor or cone at times, the probe must, if necessary, be shortened and fixed down →  31.
Threaded connection
A0015121
 9 Mounting with threaded connection; flush with the container ceiling
Seal
The thread as well as the type of seal comply to DIN 3852 Part 1, screwed plug form A.
They can be sealed with the following types of sealing rings:
• Thread G3/4": According to DIN 7603 with the dimensions 27 x 32 mm
• Thread G1-1/2": According to DIN 7603 with the dimensions 48 x 55 mm
Please use a sealing ring according to this standard in the form A, C or D and of a material that is resistant to the application.
Endress+Hauser 27
Page 28
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
£150 (6)
H
ø 150 (6)£
Nozzle mounting
A0015122
Length H of the rigid part of the rope probe
Probe H
FMP56,  rope 4 mm (0.16 in) 94 mm (3.7 in)
FMP57,  rope 4 mm (0.16 in) 120 mm (4.7 in)
FMP57,  rope 6 mm (0.24 in) 135 mm (5.3 in)
• Permissible nozzle diameter: ≤ 150 mm (6 in). For larger diameters the near range measuring capability may be reduced. For nozzles ≥ DN300: →  30.
• Permissible nozzle height
2)
: ≤ 150 mm (6 in). For a larger height the near range measuring capability may be reduced. Larger nozzle heights may be possible in special cases (see section "Rod extension/ centering HMP40 for FMP57").
• The end of the nozzle should be flush with the tank ceiling in order to avoid ringing effects.
With thermally insulated vessels the nozzle should also be insulated in order to prevent condensate formation.
2) Larger nozzle heights on request
Page 29
Levelflex FMP56, FMP57 PROFIBUS PA Mounting
Rod extension/centering HMP40 for FMP57
For FMP57 with rope probes the rod extension/centering HMP 40 is available as an accessory →  96. It has to be used if otherwise the probe rope comes into contact with the lower edge of the nozzle.
For FMP57 with rope probes the rod extension/centering HMP 40 is available as an accessory. It has to be used if otherwise the probe rope comes into contact with the lower edge of the nozzle.
This accessory consists of the extension rod corresponding to the nozzle height, on which a centering disk is also mounted if the nozzles are narrow or when working in bulk solids. This component is delivered separately from the device. Please order the probe length correspondingly shorter.
Centering disks with small diameters (DN40 and DN50) may only be used if there is no significant build-up in the nozzle above the disk. The nozzle must not become clogged by the product.
Endress+Hauser 29
Page 30
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
1
2
3
4
Installation in nozzles ≥ DN300
If installation in ≥ 300mm/12" nozzles is unavoidable, installation must be carried out in accordance with the following sketch.
A0014199
1 Lower edge of the nozzle 2 Approx. flush with the lower edge of the nozzle (± 50 mm/2") 3 Plate 4 Pipe  150 to 180 mm (6 to 7 inch)
Nozzle diameter Plate diameter
300 mm (12") 280 mm (11")
≥ 400 mm (16") ≥ 350 mm (14")
Page 31
Levelflex FMP56, FMP57 PROFIBUS PA Mounting
1
A
C
B
2

6.1.5 Securing the probe

Securing rope probes
A0012609
A Sag of the rope: ≥ 1 cm per 1m of the probe length (0.12 inch per 1 ft of the probe length) B Reliably grounded end of probe C Reliably isolated end of probe 1: Mounting and contact with a bolt 2 Mounting kit isolated
• The end of the probe needs to be secured under the following conditions: – if otherwise the probe sporadically comes into contact with the wall of the vessel, the
outlet cone, internal fittings or other parts of the installation.
– if otherwise the probe sporadically gets close to a concrete wall (minimum distance 0.5
m / 20 inch).
• The end of probe can be secured at its internal thread – rope 4 mm (1/6"), 316: M 14 – rope 6 mm (1/4"), 316: M 20 – rope 6mm (1/4"), PA>steel: M14 – rope 8mm (1/3"), PA>steel: M20
• Preferably use the 6 mm (1/4") rope probe due to the higher tensile strength when fixing a rope probe.
• The fixing must be either reliably grounded or reliably insulated. If it is not possible to mount the probe weight with a reliably insulated connection, it can be secured using an isolated eyelet, which is available as an accessory.
• In the case of a grounded fixing the search for a positive end-of-probe signal must be activated. Otherwise an automatic probe length correction is impossible. Navigation: Expert → Sensor → EOP evaluation → EOP search mode Setting: Positive EOP option
• In order to prevent an extremely high tensile load (e.g. due to thermal expansion) and the risk of rope crack, the rope has to be slack. Make the rope longer than the required measuring range such that there is a sag in the middle of the rope that is ≥ 1cm/(1 m rope length) [0.12 inch/(1 ft rope length)]. Tensile load limit of rope probes: →  23
Endress+Hauser 31
Page 32
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
mm (in)
ø a
ø b
»50 (1.97)
1
2
3
»50 (1.97)
4
5
6
ø<25 (1.0)
3 (0.12)»
Securing rod probes
• For WHG approvals: For probe lengths ≥ 3 m (10 ft) a support is required.
• In general, rod probes must be supported if there is a horizontal flow (e.g. from an agitator) or in the case of strong vibrations.
• Rod probes may only be supported at the end of the probe.
1 Probe rod, uncoated 2 Sleeve bored tight to ensure electrical contact between the rod and sleeve! 3 Short metal pipe, e.g. welded in place 4 Probe rod, coated 5 Plastic sleeve, e.g. PTFE, PEEK or PPS 6 Short metal pipe, e.g. welded in place
NOTICE
Poor grounding of the end of probe may cause measuring errors.
Apply a narrow sleeve which has good electrical contact to the probe.
NOTICE
Welding may damage the main electronics module.
Before welding: Ground the probe and dismount electronics.
A0012607
Page 33
Levelflex FMP56, FMP57 PROFIBUS PA Mounting
≥≥100
4
≥≥100
4
mm(in)
ø80...150 (ø3.2...6)
1
3
2

6.1.6 Special mounting conditions

Concrete silos
Installation, for example, into a thick concrete ceiling should be made flush with the lower edge. Alternatively, the probe can also be installed into a pipe that must not protrude over the lower edge of the silo ceiling. The pipe should be kept at a minimum length. Installation suggestions see diagram.
A0014138
1 Metal sheet 2 Metal tube 3 Extension rod / Centering HMP40 (see "Accessories")
Note for installations with rod extension/center washer (accessories): Strong dust generation can lead to build-up behind the center washer. This can cause an interference signal. For other installation possibilities please contact Endress+Hauser.
Endress+Hauser 33
Page 34
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
Ø16
(Ø0.63)
Ø16.5(0.65)
Ø<26
(Ø<1.02)
mm(in)
Installation from the side
A0014140
• If installation from above is not possible, the Levelflex can also be mounted from the side.
• In this case, always fix the rope probe →  31 .
• Support rod probe if the lateral loadbearing capacity is exceeded →  26. Only fix rod probes at the probe end →  31.
Page 35
Levelflex FMP56, FMP57 PROFIBUS PA Mounting
1
2
Non-metallic vessels
A0012527
1 Non-metallic vessel 2 Metal sheet or metal flange
To ensure reliable measurements in non-metallic vessels:
• Select an instrument version with metal flange (minimum size DN50/2").
• Or: mount a metal sheet with a diameter of at least 200 mm (8 in) to the probe at the process connection. Its orientation must be perpendicular to the probe.
Endress+Hauser 35
Page 36
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
MAX
1
3
MAX
2
40(1.57)
40(1.57)
MAX
mm(in)
MAX
1
3
2
Vessels with heat insulation
If process temperatures are high, the device must be included in normal tank insulation to prevent the electronics heating up as a result of heat radiation or convection. The insulation may not exceed beyond the points labeled "MAX" in the drawings.
A0014653
 10 Process connection with thread - FMP56, FMP57
1 Tank insulation 2 Compact device 3 Sensor remote (feature 600)
 11 Process connection with flange - FMP57
1 Tank insulation 2 Compact device 3 Sensor remote (feature 600)
A0014654
Page 37
Levelflex FMP56, FMP57 PROFIBUS PA Mounting

6.2 Mounting the device

6.2.1 Required mounting tools

• For mounting thread 3/4": Hexagonal wrench 36 mm
• For mounting thread 1-1/2": Hexagonal wrench 55 mm
• To shorten rod or coax probes: Saw
• To shorten rope probes: – Allen key AF 3 mm (for 4mm ropes) or AF 4 mm (for 6 mm ropes) – Saw or bolt cutter
• For flanges and other process connections: appropriate mounting tools
• To turn the housing: Hexagonal wrench 8 mm

6.2.2 Shortening the probe

When shortening the probe: Enter the new length of probe into the Quick Setup which can be found in the electronics housing behind the display module.
A0014241
Shortening rod probes
Rod probes must be shortened if the distance to the container floor or outlet cone is less than 10 mm (0.4 in). The rods of a rod probe are shortened by sawing at the bottom end.
Rod probes of FMP52 can not be shortened as they are coated.
Shortening rope probes
Rope probes must be shortened if the distance to the container floor or outlet cone is less than 150 mm (6 in).
Endress+Hauser 37
Page 38
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
B
A
C
A0021693
Rope material A B C Torque for set screws
316 4 mm (0.16 in) 40 mm (1.6 in) 3 mm 5 Nm (3.69 lbf ft)
316 6 mm (0.24 in) 55 mm (2.2 in) 4 mm 15 Nm (11.06 lbf ft)
PA > steel 6 mm (0.24 in) 40 mm (1.6 in) 3 mm 5 Nm (3.69 lbf ft)
PA > steel 8 mm (0.31 in) 55 mm (2.2 in) 4 mm 15 Nm (11.06 lbf ft)
1. Using an Allen key, loosen the set screws at the end-of-probe weight. Note: The set screws have got a clamping coating in order to prevent accidental loosening. Thus an increased torque might be necessary to loosen them.
2. Remove released rope from the weight.
3. Measure off new rope length.
4. Wrap adhesive tape around the rope at the point to be shortened to prevent it from fanning out.
5. Saw off the rope at a right angle or cut it off with a bolt cutter.
6. Insert the rope completely into the weight.
7. Screw the set screws into place. Due to the clamping coating of the setscrews application of a screw locking fluid is not necessary.
Page 39
Levelflex FMP56, FMP57 PROFIBUS PA Mounting

6.2.3 Mounting the device

Mounting devices with thread
A0012528
Devices with mounting thread are screwed into a welding boss or a flange and are usually also secured with these.
• Tighten with the hexagonal nut only: – Thread 3/4": Hexagonal wrench 36 mm – Thread 1-1/2": Hexagonal wrench 55 mm
• Maximum permissible torque: – Thread 3/4": 45 Nm – Thread 1-1/2": 450 Nm
• Recommended torque when using the supplied aramid fibre seal and a process pressure of 40 bar (580 psi): – Thread 3/4": 25 Nm – Thread 1-1/2": 140 Nm
• When installing in metal containers, take care to ensure good metallic contact between the process connection and container.
Flange mounting
If a seal is used, be sure to use unpainted metal bolts to ensure good electrical contact between probe flange and process flange.
Mounting rope probes
NOTICE
Electrostatic discharges may damage the electronics.
Earth the housing before lowering the rope into the vessel.
Endress+Hauser 39
Page 40
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
*
*
A0012529
When lowering the rope probe into the vessel, observe the following:
• Uncoil rope and lower it slowly and carefully into the vessel.
• Do not kink the rope.
• Avoid any backlash, since this might damage the probe or the vessel fittings.
Mounting rope probes in a partially full silo
It is not always possible to empty a silo which is already in operation. If a minimum of 2/3 of the silo is empty, it is possible to install the probe into the partially filled silo. If possible, make a visual check after the installation to see that the rope has not tangled or is lying such that it can knot when the level falls. Before full accuracy is obtained the probe rope must hang fully extended.

6.2.4 Mounting the "Sensor remote" version

This section is only valid for devices of the version "Probe Design" = "Sensor remote" (feature 600, option MB/MC/MD).
For the version "Probe design" = "Sensor remote" the following is supplied:
• The probe with the process connection
• The electronics housing
• The mounting bracket for wall or pipe mounting of the electronics housing
• The connection cable (length as ordered). The cable has got one straight and one angled plug (90°). Depending on the local conditions the angled plug can be connected at the probe or at the electronics housing.
CAUTION
L
The plugs of the connection cable may be damaged by mechanical stress.
Mount the probe and the electronics housing tightly before connecting the cable.
Lay the cable such that it is not exposed to mechanical stress. Minimum bending
radius: 100 mm (4"). When connecting the cable: Connect the straight plug before the angled one. Torque
for both coupling nuts: 6 Nm.
Probe, electronics and connection cable are adjusted to match each other. They are marked by a common serial number. Only components with the same serial number shall be connected to each other.
If the measuring point is exposed to strong vibrations, an additional locking compound (e.g. Loctite 243) can be applied at the plug connectors.
Page 41
Levelflex FMP56, FMP57 PROFIBUS PA Mounting
122 (4.8)
52 (2)
86
(3.4)
70
(2.8)
140 (5.5)
158 (6.2)
175 (6.9)
A B
ø42...60
(1.65...2.36)
A
B
C
C
r = 100 (4)
min
r = 100 (4)
min
6 Nm (4.42 lbf ft)
6 Nm (4.42 lbf ft)
6 Nm (4.42 lbf ft)
6 Nm (4.42 lbf ft)
Mounting the electronics housing
A0014793
 12 Mounting the electronics housing using the mounting bracket; dimensions: mm (in)
A Wall mounting B Pipe mounting
Connecting the cable
Required tools:
Open-end wrench 18AF
 13 Connecting the cable. There are the following possibilities:
A Angled plug at the probe B Angled plug at the electronics housing C Length of the remote cable as ordered
A0014794
Endress+Hauser 41
Page 42
Mounting Levelflex FMP56, FMP57 PROFIBUS PA
max.350°
8mm
8mm
+
E
1
3mm

6.2.5 Turning the transmitter housing

To provide easier access to the connection compartment or display module, the transmitter housing can be turned:
A0013713
1. Unscrew the securing screw using an open-ended wrench.
2. Rotate the housing in the desired direction.
3. Tighten the securing screw (1,5 Nm for plastics housing; 2,5 Nm for aluminium or stainless steel housing).

6.2.6 Turning the display module

1. If present: Loosen the screw of the securing clamp of the electronics compartment cover using an Allen key and turn the clamp 90° conterclockwise.
2. Unscrew cover of the electronics compartment from the transmitter housing.
3. Pull out the display module with a gentle rotation movement.
4. Rotate the display module into the desired position: Max. 8 × 45 ° in each direction.
5. Feed the spiral cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment until it engages.
6. Screw the cover of the electronics compartment firmly back onto the transmitter housing.
7. Tighten the securing clamp again using the Allen key (Torque: 2.5 Nm).
A0013905
Page 43
Levelflex FMP56, FMP57 PROFIBUS PA Mounting

6.3 Post-installation check

Is the device undamaged (visual inspection)?
m
Does the device conform to the measuring point specifications?
For example:
• Process temperature
m
• Process pressure (refer to the chapter on "Material load curves" of the "Technical Information" document)
• Ambient temperature range
• Measuring range
Are the measuring point identification and labeling correct (visual inspection)?
m
Is the device adequately protected from precipitation and direct sunlight?
m
Are the securing screw and securing clamp tightened securely?
m
Endress+Hauser 43
Page 44
Electrical connection Levelflex FMP56, FMP57 PROFIBUS PA
1
3
+
+
2
4
FIELDBUS
2-channel overvoltage protection
-
-
[17]
4-20mA/
4-20mA/
B
1
1
+
+
2
2
FIELDBUS
Spare part
71023457
PA/FF
[06/07]
FIELDBUS
-
-
1
3
+
+
2
4
PA/FF
10 mm
Spare part
71108xxx
2- wire level
4-20 mA PFS
FIELDBUS
[26/27]
open
-
-
A
4
1
1
2
3
6
5
3+
3+
4-
4-
!

7 Electrical connection

7.1 Connection conditions

7.1.1 Terminal assignment

PROFIBUS PA / FOUNDATION Fieldbus
 14 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus
A Without integrated overvoltage protection B With integrated overvoltage protection 1 Cable screen: Observe cable specifications 2 Switch output (open collector): Terminals 3 and 4 3 PROFIBUS PA / FOUNDATION Fieldbus: Terminals 1 and 2 4 Terminal for potential equalization line 5 Cable entries 6 Overvoltage protection module
A0011341
Page 45
Levelflex FMP56, FMP57 PROFIBUS PA Electrical connection
3+
+
-
4-
3+
2
1
+
4-
Connection examples for the switch output
A0015909
 15 Connection of a relay
Suitable relays (examples):
• Solid-state relay: Phoenix Contact OV-24DC/480AC/5 with mounting rail connector UMK-1 OM-R/AMS
• Electromechanical relay: Phoenix Contact PLC-RSC-12DC/21
 16 Connection of a digital input
1 Pull-up resistor 2 Digital input
A0015910
For optimum interference immunity we recommend to connect an external resistor (internal resistance of the relay or Pull-up resistor) of < 1 000 Ω.

7.1.2 Cable specification

Devices without integrated overvoltage protection Pluggable spring-force terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
Devices with integrated overvoltage protection Screw terminals for wire cross-sections 0.2 to 2.5 mm2 (24 to 14 AWG)
• For ambient temperature TU≥60 °C (140 °F): use cable for temperature TU +20 K.
PROFIBUS
Use a twisted, screened two-wire cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning", PNO Guideline 2.092 "PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
Endress+Hauser 45
Page 46
Electrical connection Levelflex FMP56, FMP57 PROFIBUS PA
2
1
3
4
4
2
3
1

7.1.3 Device plug connectors

For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening the housing.
Pin assignment of the M12 plug connector
Pin Meaning
1 Signal +
2 not connected
3 Signal -
4 Ground
A0011175
Pin assignment of the 7/8" plug connector
Pin Meaning
1 Signal -
2 Signal +
3 Not connected
4 Screen
A0011176
Page 47
Levelflex FMP56, FMP57 PROFIBUS PA Electrical connection

7.1.4 Power supply

PROFIBUS PA, FOUNDATION Fieldbus
"Power supply; Output"
E: 2-wire; FOUNDATION Fieldbus, switch output G: 2-wire; PROFIBUS PA, switch output
1) Feature 020 of the product structure
2) Feature 010 of the product structure
3) Input voltages up to 35 V will not spoil the device.
Polarity sensitive No
FISCO/FNICO compliant according to IEC 60079-27
1)
Yes
"Approval"
• Non-Ex
• Ex nA
• Ex nA[ia]
• Ex ic
• Ex ic[ia]
• Ex d[ia] / XP
• Ex ta / DIP
• CSA GP
• Ex ia / IS
• Ex ia + Ex d[ia] / IS + XP
2)
Terminal voltage
9 to 32 V
9 to 30 V
3)

7.1.5 Overvoltage protection

If the measuring device is used for level measurement in flammable liquids which requires the use of overvoltage protection according to DIN EN 60079-14, standard for test procedures 60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be ensured by an integrated or external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel 2 × 0.5 Ω max.
Threshold DC voltage 400 to 700 V
Threshold impulse voltage < 800 V
Capacitance at 1 MHz < 1.5 pF
Nominal arrest impulse voltage (8/20 μs) 10 kA
External overvoltage protection
HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection.
For detailed information please refer to the following documents:
• HAW562: TI01012K
• HAW569: TI01013K
Endress+Hauser 47
Page 48
Electrical connection Levelflex FMP56, FMP57 PROFIBUS PA
1.
2.
3.
10 (0.4)
10 (0.4)
mm (in)
4.
5.
5.

7.2 Connecting the device

WARNING
L
Explosion hazard!
Comply with the relevant national standards.
Observe the specifications in the Safety Instructions (XA).
Only use the specified cable glands.
Check whether the supply voltage matches the specifications on the nameplate.
Before connecting the device: Switch the supply voltage off.
Before switching on the supply voltage: Connect the potential bonding line to the
exterior ground terminal.
Required tools and accessories:
• For instruments with safety pin for the lid: AF 3 Allen key
• Wire stripping pliers
• When using stranded wires: Wire end sleeves.
A0012619
1. Loosen the screw of the securing clamp of the connection compartment cover and turn the clamp 90° counterclockwise.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing ring from the cable entry.
4. Strip the cable.
5. Strip the cable ends 10 mm (0.4 in). For stranded cables, also attach wire end ferrules.
6. Firmly tighten the cable glands.
Page 49
Levelflex FMP56, FMP57 PROFIBUS PA Electrical connection
2
1
4
3
mm(in)
3(0.12)
7.
A0013837
Connect the cable in accordance with the terminal assignment →  44.
8. When using screened cable: Connect the cable screen to the ground terminal.
9. Screw the cover onto the connection compartment.
10. For instruments with safety pin for the lid: Adjust the safety pin so that its edge is over the edge of the display lid. Tighten the safety pin.

7.2.1 Pluggable spring-force terminals

Instruments without integrated overvoltage protection have pluggable spring-force terminals. Rigid conductors or flexible conductors with cable sleeve can directly be inserted and are contacted automatically.
To remove cables from the terminal: Press on the groove between the terminals using a flat-tip screwdriver ≤ 3 mm (0.12 inch) while pulling the cables out of the terminals.
A0013661

7.3 Post-connection check

Are cables or the device undamaged (visual inspection)?
m
Do the cables comply with the requirements?
m
Do the cables have adequate strain relief?
m
Are all cable glands installed, firmly tightened and correctly sealed?
m
Does the supply voltage match the specifications on the transmitter nameplate?
m
Is the terminal assignment correct →  44?
m
Endress+Hauser 49
Page 50
Electrical connection Levelflex FMP56, FMP57 PROFIBUS PA
If required: Is the protective earth connected correctly ?
m
If supply voltage is present: Is the device ready for operation and do values appear on the display
m
module?
Are all housing covers installed and firmly tightened?
m
Is the securing clamp tightened correctly?
m
Page 51
Levelflex FMP56, FMP57 PROFIBUS PA Operation options

8 Operation options

8.1 Overview

8.1.1 Local operation

Operation with
Order code for "Display; Operation"
Display elements
Operating elements
Additional functionality
Pushbuttons Touch Control
Option C "SD02" Option E "SD
A0032219 A0032221
4-line display 4-line display
white background lighting; switches to red in event of device error
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F) The readability of the display may be impaired at temperatures outside the temperature range.
local operation with 3 push buttons (, ,)external operation via touch control; 3 optical
keys: , , 
Operating elements also accessible in various hazardous areas
Data backup function The device configuration can be saved in the display module.
Data comparison function The device configuration saved in the display module can be compared to the current device configuration.
Data transfer function The transmitter configuration can be transmitted to another device using the display module.
Endress+Hauser 51
Page 52
Operation options Levelflex FMP56, FMP57 PROFIBUS PA
3
2
1
ENDRESS + HAUSER
T
PROFIBUS DP
PROFIBUS PA
1
2
3
5
4 4 4

8.1.2 Operation with remote display and operating module FHX50

A0013137
 17 FHX50 operating options
1 Housing of the remote display and operating module FHX50 2 Display and operating module SD02, push buttons; cover must be removed 3 Display and operating module SD03, optical keys; can be operated through the glass of the cover

8.1.3 Remote operation

Via PROFIBUS PA protocol
A0015775
1 Segment coupler 2 Computer with Profiboard/Proficard and operating tool (e.g. FieldCare) 3 PLC (Progrommable Logic Controller) 4 Transmitter 5 Additional functions (valves etc.)
Page 53
Levelflex FMP56, FMP57 PROFIBUS PA Operation options
+
E
12
3
Via service interface (CDI)
A0014019
1 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface) 2 Commubox FXA291 3 Computer with "FieldCare" operating tool
Endress+Hauser 53
Page 54
Operation options Levelflex FMP56, FMP57 PROFIBUS PA

8.2 Structure and function of the operating menu

8.2.1 Structure of the operating menu

Menu Submenu /
parameter
Language
Commissioning
Setup Parameter 1
Diagnostics Diagnostic list Contains up to 5 currently active error
5)
Expert
Contains all parameters of the device (including those which are already contained in one of the above submenus). This menu is organized according to the function blocks of the device.
The parameter of the Expert menu are described in: GP01018F (PROFIBUS PA)
2)
... Parameter N
Advanced setup Contains further submenus and
Event logbook
Device information Contains information needed to identify
Measured values Contains all current measured values.
Data logging Contains the history of the individual
Simulation Used to simulate measured values or
Device check Contains all parameters needed to check
Heartbeat
System Contains all general device parameters
Sensor Contains all parameters needed to
Output Contains all parameters neeed to
1)
4)
Meaning
Defines the operating language of the on-site display.
Opens the interactive wizard for a guided commissioning of the device. As a rule, no additional settings in the other menus are required after the completion of the wizard.
When all these parameters have been assigned appropriate values, the measured should be completely configured in a standard application.
parameters:
• to adapt the device to special measuring conditions.
• to process the measured value (scaling, linearization).
• to configure the signal output.
messages.
3)
Contains the last 20 messages (which are no longer active).
the device.
measuring values.
output values.
the measurement capability of the device.
Contains all wizards for the Heartbeat Verification and Heartbeat Monitoring application packages.
which do not affect the measurement or the communication interface.
configure the measurement.
configure the switch output (PFS).
Page 55
Levelflex FMP56, FMP57 PROFIBUS PA Operation options
Menu Submenu /
parameter
Communication Contains all parameters needed to
Diagnostics Contains all parameters needed to detect
1) In case of operation via operating tools (e.g. FieldCare), the "Language" parameter is located at "Setup →  Advanced setup → Display"
2) only for operation via a FDT/DTM system
3) only available with local operation
4) only available for operation via DeviceCare or FieldCare
5) On entering the "Expert" menu, an access code is always requested. If a customer specific access code has not been defined, "0000" has to be entered.
Meaning
configure the digital communication interface.
and analyze operational errors.
Endress+Hauser 55
Page 56
Operation options Levelflex FMP56, FMP57 PROFIBUS PA

8.2.2 User roles and related access authorization

The two user roles Operator and Maintenance have different write access to the parameters if a device-specific access code has been defined. This protects the device configuration via the local display from unauthorized access →  57.
Access authorization to parameters
User role Read access Write access
Without access
code
(from the factory)
Operator --
Maintenance
If an incorrect access code is entered, the user obtains the access rights of the Operator role.
The user role with which the user is currently logged on is indicated by the Access status display parameter (for display operation) or Access status tooling parameter (for tool operation).
With access code Without access
code
(from the factory)
With access code
Page 57
Levelflex FMP56, FMP57 PROFIBUS PA Operation options

8.2.3 Write protection via access code

Using the device-specific access code, the parameters for the measuring device configuration are write-protected and their values can no longer be changed via local operation.
Define access code via local display
1. Navigate to: Setup → Advanced setup → Administration → Define access code → Define access code
2. Define a max. 4-digit numeric code as an access code.
3. Repeat the same code in Confirm access code parameter.  The -symbol appears in front of all write-protected parameters.
Define access code via operating tool (e.g. FieldCare)
1. Navigate to: Setup → Advanced setup → Administration → Define access code
2. Define a max. 4-digit numeric code as an access code.  Write protection is active.
Parameters that can always be changed
The write protection does not include certain parameters that do not affect the measurement. Despite the defined access code, they can always be modified, even if the other parameters are locked.
If no key is pressed for 10 minutes in the navigation and editing mode, the device automatically locks the write-protected parameters. If the user goes from the navigation and editing mode back to the measured value display mode, the device automatically locks the write-protected parameters after 60 s.
• If write access is activated via access code, it can be also be deactivated only via the access code →  58.
• In the "Description of Device Parameters" documents, each write-protected parameter is identified with the -symbol.
Endress+Hauser 57
Page 58
Operation options Levelflex FMP56, FMP57 PROFIBUS PA

8.2.4 Disabling write protection via access code

If the write-protected by a device-specific access code and its value cannot be changed at the moment using the local display →  57.
The locking of the write access via local operation can be disabled by entering the device­specific access code.
-symbol appears on the local display in front of a parameter, the parameter is
1. After you press , the input prompt for the access code appears.
2. Enter the access code.  The -symbol in front of the parameters disappears; all previously write-
protected parameters are now re-enabled.

8.2.5 Deactivation of the write protection via access code

Via local display
1. Navigate to Setup → Advanced setup → Administration → Define access code → Define access code
2. Enter 0000.
3. Repeat 0000 in Confirm access code parameter.  The write protection is deactivated. Parameters can be changed without entering
an access code.
Via operating tool (e.g. FieldCare)
1. Navigate to Setup → Advanced setup → Administration → Define access code
2. Enter 0000.  The write protection is deactivated. Parameters can be changed without entering
an access code.
Page 59
Levelflex FMP56, FMP57 PROFIBUS PA Operation options
+
E
3 mm
XXXXXXXXXXXXX
WPCDI
OFF
ON

8.2.6 Write protection via write protection switch

Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu - except for the "Contrast display" parameter - to be locked.
The parameter values are now read only and cannot be edited any more (exception "Contrast display" parameter):
• Via local display
• Via PROFIBUS PA protocol
• Via PROFIBUS DP protocol
1. Loosen the securing clamp.
2. Unscrew the housing cover.
3. Pull out the display module with a gentle rotation movement. To make it easier to access the lock switch, attach the display module to the edge of the electronics compartment.
 Display module is attached to the edge of the electronics compartment.
A0026157
A0013909
Endress+Hauser 59
Page 60
Operation options Levelflex FMP56, FMP57 PROFIBUS PA
X X XX X X XX X
20.50
XX
XX
4. Installing the lock switch (WP) on the main electronics module in the ON position enables the hardware write protection. Installing the lock switch (WP) on the main electronics module in the OFF position (factory setting) disables the hardware write protection.
 If the hardware write protection is enabled: The Hardware locked option is
displayed in the Locking status parameter. In addition to this, the -symbol appears in the header of the measured value display and in the navigation view in front of the parameters.
A0015870
If the hardware write protection is disabled: No option is displayed in the Locking status parameter. The -symbol disappears in the header of the measured value display and in the navigation view in front of the parameters.
5. Feed the spiral cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment in the desired direction until it engages.
6. Screw the electronics compartment cover closed and tighten the securing clamp.
Page 61
Levelflex FMP56, FMP57 PROFIBUS PA Operation options

8.2.7 Enabling and disabling the keypad lock

The keypad lock allows to disable access to the entire operating menu via local operation. Thus navigating through the operating menu or modifying the values of individual
parameters is no longer possible. Only the measured values on the measured value display can be read off.
The keylock is enabled and disabled via a context menu.
Enabling the keylock
For the SD03 display:
The keylock is automatically activated:
• If the device has not been operated via the display for > 1 minute.
• After a restart of the device.
To activate the keylock manually:
1. The device is in the measured value display. Press  for at least 2 seconds.  A context menu appears.
2. Select Keylock on from the context menu.  The keylock is enabled.
When attempting to access the operating menu while the keylock is enabled, the
Keylock on message appears.
Disabling the keylock
1. The keylock is enabled. Press  for at least 2 seconds.  A context menu appears.
2. Select Keylock off from the context menu.  The keylock is disabled.
Endress+Hauser 61
Page 62
Operation options Levelflex FMP56, FMP57 PROFIBUS PA
3.1
3.2
2.1
2.2
2.4
2.5
1.1
1.2
1.3
1.4
2.3
2.6
1
2
3
45
ESC
OPEN
OPEN
E
ABC_
DEFG
User
HIJK
LMNO
PQRS
TUVW
XYZ
Aa1
3
4
0
1 2
9
5
6
8
7
20

8.3 Display and operating module

8.3.1 Display appearance

A0012635
 18 Appearance of the display and operation module for on-site operation
1 Measured value display (1 value max. size)
1.1 Header containing tag and error symbol (if an error is active)
1.2 Measured value symbols
1.3 Measured value
1.4 Unit 2 Measured value display (1 bargraph + 1 value)
2.1 Bargraph for measured value 1
2.2 Measured value 1 (including unit)
2.3 Measured value symbols for measured value 1
2.4 Measured value 2
2.5 Unit for measured value 2
2.6 Measured value symbols for measured value 2 3 Representation of a parameter (here: a parameter with selection list)
3.1 Header containing parameter name and error symbol (if an error is active)
3.2 Selection list;  marks the current parameter value. 4 Input matrix for numbers 5 Input matrix for alphanumeric and special characters
Page 63
Levelflex FMP56, FMP57 PROFIBUS PA Operation options
Display symbols for the submenus
Symbol Meaning
Display/operation
Is displayed:
• in the main menu next to the selection "Display/operation"
A0011975
• in the header, if you are in the "Display/operation" menu
Setup
Is displayed:
• in the main menu next to the selection "Setup"
A0011974
• in the header, if you are in the "Setup" menu
Expert
Is displayed:
• in the main menu next to the selection "Expert"
A0011976
• in the header, if you are in the "Expert" menu
Diagnostics
Is displayed:
• in the main menu next to the selection "Diagnostics"
A0011977
• in the header, if you are in the "Diagnostics" menu
Status signals
"Failure"
A device error is present. The measured value is no longer valid.
A0013956
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
A0013958
• Outside of the configuration carried out by the user (e.g. level outside configured span)
"Maintenance required"
Maintenance is required. The measured value is still valid.
A0013957
Display symbols for the locking state
Symbol Meaning
Display parameter
Marks display-only parameters which can not be edited.
A0011978
Device locked
• In front of a parameter name: The device is locked via software and/or hardware.
• In the header of the measured value screen: The device is locked via hardware.
A0011979
Endress+Hauser 63
Page 64
Operation options Levelflex FMP56, FMP57 PROFIBUS PA
Measured value symbols
Symbol Meaning
Measured values
Level
A0011995
Distance
A0011996
Current output
A0011998
Measured current
A0011999
Terminal voltage
A0012106
Temperature of the electronics or the sensor
A0012104
Measuring channels
Measuring channel 1
A0012000
Measuring channel 2
A0012107
Status of the measured value
Status "Alarm"
The measurment is interrupted. The output assumes the defined alarm value. A diagnostic message is generated.
A0012102
Status "Warning"
The device continues measuring. A diagnostic message is generated.
A0012103
Page 65
Levelflex FMP56, FMP57 PROFIBUS PA Operation options
+
+
+
++

8.3.2 Operating elements

Key Meaning
Minus key
For menu, submenu
Moves the selection bar upwards in a picklist.
A0013969
For text and numeric editor
In the input mask, moves the selection bar to the left (backwards).
Plus key
For menu, submenu
Moves the selection bar downwards in a picklist.
A0013970
For text and numeric editor
In the input mask, moves the selection bar to the right (forwards).
Enter key
For measured value display
• Pressing the key briefly opens the operating menu.
• Pressing the key for 2 s opens the context menu.
For menu, submenu
• Pressing the key briefly Opens the selected menu, submenu or parameter.
• Pressing the key for 2 s for parameter:
A0013952
A0013971
A0013953
A0013954
A0013955
If present, opens the help text for the function of the parameter.
For text and numeric editor
• Pressing the key briefly – Opens the selected group. – Carries out the selected action.
• Pressing the key for 2 s confirms the edited parameter value.
Escape key combination (press keys simultaneously)
For menu, submenu
• Pressing the key briefly – Exits the current menu level and takes you to the next higher level. – If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s returns you to the measured value display ("home position").
For text and numeric editor
Closes the text or numeric editor without applying changes.
Minus/Enter key combination (press and hold down the keys simultaneously)
Reduces the contrast (brighter setting).
Plus/Enter key combination (press and hold down the keys simultaneously)
Increases the contrast (darker setting).
Minus/Plus/Enter key combination (press and hold down the keys simultaneously)
For measured value display
Enables or disables the keypad lock.
Endress+Hauser 65
Page 66
Operation options Levelflex FMP56, FMP57 PROFIBUS PA
3
2
1
4
3
4
0
1 2
9
5
6
8
7
20
ABC_
DEFG
User
HIJK
LMNO
PQRS
TUVW
XYZ
Aa1
3
2
1
4
0
9
.
XYZ
ABC
_
Aa1

8.3.3 Entering numbers and text

Numeric editor Text editor
A0013999
1
Editing view
2
Display area of the entered values
3
Input mask
4
Operating elements
A0013941
Input mask
The following input symbols are available in the input mask of the numeric and text editor:
Numeric editor symbols
Symbol Meaning
Selection of numbers from 0 to 9.
A0013998
Inserts decimal separator at the input position.
A0016619
Inserts minus sign at the input position.
A0016620
Confirms selection.
A0013985
Moves the input position one position to the left.
A0016621
Exits the input without applying the changes.
A0013986
Clears all entered characters.
A0014040
Text editor symbols
Symbol Meaning
Selection of letters from A to Z
A0013997
Toggle
• Between upper-case and lower-case letters
• For entering numbers
A0013981
• For entering special characters
Page 67
Levelflex FMP56, FMP57 PROFIBUS PA Operation options
Confirms selection.
A0013985
Switches to the selection of the correction tools.
A0013987
Exits the input without applying the changes.
A0013986
Clears all entered characters.
A0014040
Correction symbols under
Clears all entered characters.
A0013989
Moves the input position one position to the right.
A0013991
Moves the input position one position to the left.
A0013990
Deletes one character immediately to the left of the input position.
A0013988
Endress+Hauser 67
Page 68
Operation options Levelflex FMP56, FMP57 PROFIBUS PA
XXXXXXXXXX
kg/h
20.50
Setup
Conf.backupdisp
Simulation

8.3.4 Opening the context menu

Using the context menu, the user can call up the following menus quickly and directly from the operational display:
• Setup
• Conf. backup disp.
• Simulation
Calling up and closing the context menu
The user is in the operational display.
1. Press  for 2 s.  The context menu opens.
A0014003-EN
2. Press  +  simultaneously.  The context menu is closed and the operational display appears.
Calling up the menu via the context menu
1. Open the context menu.
2. Press  to navigate to the desired menu.
3. Press  to confirm the selection.  The selected menu opens.
Page 69
Levelflex FMP56, FMP57 PROFIBUS PA Operation options
E
+
(2s)
E
2x
E
+
-
+
+
-
+
E
+
-
+

8.3.5 Envelope curve on the display and operating module

In order to assess the measuring signal, the envelope curve and - if a mapping has been recorded - the mapping curve can be displayed:
A0014277
Endress+Hauser 69
Page 70
Integration into a PROFIBUS network Levelflex FMP56, FMP57 PROFIBUS PA
2
98
3
4
5 6
7
8
1
DIP
ON
2
98
3
4
5 6
7
8
1
DIP
ON
2 + 8 = 10

9 Integration into a PROFIBUS network

9.1 Overview of the device database files (GSD)

Manufacturer ID 17 (0x11)
Ident number 0x1558
Profile version 3.02
GSD file Information and files under:
GSD file version

9.2 Set device address

www.endress.com
www.profibus.org
A0015686
 19 Address switches in terminal compartment

9.2.1 Hardware adressing

1. Set switch 8 to "OFF".
2. Define the address with switches 1 to 7 according to the table below.
The address change becomes effective after 10 seconds. The device restarts automatically.
Switch 1 2 3 4 5 6 7
Value in position "ON" 1 2 4 8 16 32 64
Value in position "OFF" 0 0 0 0 0 0 0
A0015902
 20 Example of hardware addressing: switch 8 is in position "OFF"; switches 1 to 7 define the address.

9.2.2 Software addressing

1. Set switch 8 to "ON".
2. The device restarts automatically. The address remains the same as before (factory setting: 126).
3. Set the required address via the operating menu: Setup → Device address
Page 71
Levelflex FMP56, FMP57 PROFIBUS PA Integration into a PROFIBUS network
2
98
3
4
5 6
7
8
1
DIP
ON
A0015903
 21 Example of software addressing; switch 8 is in position "ON"; the address is defined in the operating menu
(Setup → Device address)
Endress+Hauser 71
Page 72
Commissioning via wizard Levelflex FMP56, FMP57 PROFIBUS PA
1

10 Commissioning via wizard

A wizard guiding the user through the initial setup is available in FieldCare and DeviceCare.
1. Connect the device to FieldCare or DeviceCare →  52.
2. Open the device in FieldCare or DeviceCare.  The dashboard (home page) of the device appears:
A0025866
1 "Commissioning" button calls up the wizard.
3. Click on "Commissioning" to call up the wizard.
4. Enter or select the appropriate value for each parameter. These values are immediately written to the device.
5. Click "Next" to switch to the next page.
6. After finishing the last page, click "End of sequence" to close the wizard.
If the wizard is cancelled before all necessary parameters have been set, the device may be in an undefined state. A reset to the default settings is recommended in this case.
Page 73
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu
X X XX X X XX X
20.50
Operation Setup
Main menu
0104-1
Language
English
Español Français
Language
English
Deutsch
Ã
0104-1
Ã
Español Français
Language
English
Deutsch
0104-1
Betrieb Setup
Hauptmenü
Sprache
Deutsch
0104-1
XXXX

11 Commissioning via operating menu

11.1 Installation and function check

Make sure that all final checks have been completed before you start up your measuring point:
• Checklist "Post-installation check" →  43
• Checklist "Post-connection check" →  49

11.2 Setting the operating language

Factory setting: English or ordered local language
Endress+Hauser 73
 22 Using the example of the local display
A0013996
Page 74
Commissioning via operating menu Levelflex FMP56, FMP57 PROFIBUS PA
F
L
D
E
20 mA 100%
4 mA 0%
LN
R

11.3 Configuration of a level measurement

A0012838
 23 Configuration parameters for level measurements in solids
LN Length of probe R Reference point of the measurement D Distance L Level E Empty calibration (= Zero point) F Full calibration (= Span)
If for rope probes the DC value is less than 7, then measurement is not possible in the area of the straining weight. In these cases, the maximum recommended value for the empty calibration E is LN - 250 mm (LN - 10 in).
1. Setup → Device tag  Enter tag for measuring point.
2. Navigate to: Setup → Device address  Enter bus address of the device (only in case of software addressing).
3. Navigate to: Setup → Distance unit  Select distance unit.
4. Navigate to: Setup → Bin type  Select bin type.
5. Navigate to: Setup → Empty calibration  Enter the distance E between the reference point R and the minimum level (0%).
6. Navigate to: Setup → Full calibration  Enter distance F between the minimum (0%) and maximum (100%) level.
7. Navigate to: Setup → Level  Displays the measured level L.
8. Navigate to: Setup → Distance  Displays the distance D between the reference point R and the level L.
9. Navigate to: Setup → Signal quality  Displays the signal quality of the level echo.
Page 75
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu
10. For operation via local display: Navigate to: Setup → Mapping → Confirm distance  Compare the displayed distance to the real distance in order to start the
recording of the mapping curve if required.
11. For operation via operating tool: Navigate to: Setup → Confirm distance  Compare the displayed distance to the real distance in order to start the
recording of the mapping curve if required.
Endress+Hauser 75
Page 76
Commissioning via operating menu Levelflex FMP56, FMP57 PROFIBUS PA

11.4 Recording the reference curve

After the configuration of the measurement it is recommended to record the current envelope curve as a reference curve. The reference curve can be used later on in the process for diagnostic purposes. To record the reference curve use the Save reference
curve parameter.
Navigation in the menu
Expert → Diagnostics → Envelope diagnostics → Save reference curve
Meaning of the options
• No No action
• Yes The current envelope curve is saved as reference curve.
In devices which have been delivered with software version 01.00.zz, this submenu is only visible for the "Service" user role.
The reference curve can only be displayed in the envelope curve diagram of FieldCare after it has been loaded from the device into FieldCare. This is performed by the "Load Reference Curve" function in FieldCare:
 24 The "Load Reference Curve" function
Page 77
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu

11.5 Configuration of the on-site display

11.5.1 Factory settings of the on-site display for level measurements

Parameter Factory setting for devices with 1 current
output
Format display 1 value, max. size 1 value, max. size
Value 1 display Level linearized Level linearized
Value 2 display Distance Distance
Value 3 display Current output 1 Current output 1
Value 4 display None Current output 2
Factory setting for devices with 2 current outputs

11.5.2 Adjustment of the on-site display

The on-site display can be adjusted in the following menu: Setup → Advanced setup → Display
Endress+Hauser 77
Page 78
Commissioning via operating menu Levelflex FMP56, FMP57 PROFIBUS PA

11.6 Configuration management

After commissioning, you can save the current device configuration, copy it to another measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Configuration backup display → Configuration management
Meaning of the options
Cancel No action is executed and the user exits the parameter.
Execute backup A backup copy of the current device configuration in the HistoROM (built-in in the device) is saved to the display module of the device. The backup copy comprises the transmitter and sensor data of the device.
Restore The last backup copy of the device configuration is copied from the display module to the HistoROM of the device. The backup copy comprises the transmitter and sensor data of the device.
Duplicate The transmitter configuration is duplicated to another device using the transmitter display module. The following parameters, which characterize the individual measuring point are not included in the transmitted configuration: Medium type
Compare The device configuration saved in the display module is compared to the current device configuration of the HistoROM. The result of this comparison is displayed in the Comparison result parameter.
Clear backup data The backup copy of the device configuration is deleted from the display module of the device.
While this action is in progress, the configuration cannot be edited via the local display and a message on the processing status appears on the display.
If an existing backup is restored to a different device using the Restore option, it may occur that some device functionalities are no longer available. In some cases even a device reset →  164 will not restore the original status.
In order to transmit a configuration to a different device, the Duplicate option should always be used.
Page 79
Levelflex FMP56, FMP57 PROFIBUS PA Commissioning via operating menu

11.7 Protection of the settings against unauthorized changes

There are two ways to protect the settings against unauthorized changes:
• Via parameter settings (software locking) →  57
• Via locking switch (hardware locking) →  59
Endress+Hauser 79
Page 80
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA

12 Diagnostics and troubleshooting

12.1 General trouble shooting

12.1.1 General errors

Error Possible cause Remedial action
Device does not respond. Supply voltage not connected. Connect the correct voltage.
The cables do not contact the terminals properly.
Values on the display invisible
"Communication error" is indicated on the display when starting the device or connecting the display
CDI communication does not work.
Device measures incorrectly. Parametrization error Check and adjust parameterization.
Contrast setting is too weak or too strong.
The plug of the display cable is not connected correctly.
Display is defective. Replace display.
Electromagnetic interference Check grounding of the device.
Broken display cable or display plug. Exchange display.
Wrong setting of the COM port on the computer.
Ensure electrical contact between the cable and the terminal.
• Increase contrast by pressing  and  simultaneously.
• Decrease contrast by pressing  and  simultaneously.
Connect the plut correctly.
Check the setting of the COM port on the computer and change it if necessary.
Page 81
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting

12.1.2 Parametrization errors

Parametrization errors for level measurements
Error Possible cause Remedial action
Measured value wrong If measured distance(Setup
→ Distance) matches the real distance: Calibration error
If measured distance (Setup → Distance) does not match the real distance: An interference echo affects the measurement.
No change of the measured value when emptying/filling the tank
The diagnostic message Echo lost appears after switching on the supply voltage.
Device displays a level when the tank is empty.
Wrong slope of the level in the entire measuring range
An interference echo affects the measurement.
Build-up at the probe. Clean the probe.
Error in the echo tracking Deactivate echo tracking (Expert
Noise level to high during initialization phase.
Incorrect probe length • Carry out probe length correction
Wrong bin property selected. Set Bin type parameter (→  115)
• Check and adjust the Empty calibration parameter (→  115) if necessary.
• Check and adjust the Full calibration parameter (→  116) if necessary.
• Check and adjust linearization if necessary (Linearization submenu (→  132)).
Perform mapping (Confirm distance parameter (→  118)).
Perform mapping (Confirm distance parameter (→  118)).
→ Sensor → Echo tracking → Evaluation mode = History off).
Enter Empty calibration parameter (→  115) again.
(Confirm probe length parameter (→  147)).
• Carry out mapping over entire probe while the tank is empty (Confirm distance parameter (→  118)).
correctly.
Endress+Hauser 81
Page 82
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA
1
4
3
X X X X X X XX X X X X X X X XX X
2
S
S
XX
20.50
5
X
i
S801
Menu
Supply voltage

12.2 Diagnostic information on local display

12.2.1 Diagnostic message

Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the measured value display.
Measured value display in alarm condition Diagnostic message
A0013939-EN
1
Status signal
2
Status symbol (symbol for event level)
3
Status symbol with diagnostics event
4
Event text
5
Operating elements
Status signals
"Failure"
A device error is present. The measured value is no longer valid.
A0013956
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
A0013958
• Outside of the configuration carried out by the user (e.g. level outside configured span)
"Maintenance required"
Maintenance is required. The measured value is still valid.
A0013957
Status symbol (symbol for event level)
"Alarm" status
The measurement is interrupted. The signal outputs take on the defined alarm condition.
A0013961
A diagnostic message is generated.
"Warning" status
The device continues to measure. A diagnostic message is generated.
A0013962
Page 83
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting
Diagnostics event and event text
The fault can be identified using the diagnostics event. The event text helps you by providing information about the fault. In addition, the corresponding symbol is displayed before the diagnostics event.
Diagnostics event
Status symbol Status signal Event number Event text
Example
A0013962 A0013958
441 Curr.output 1
3-digit number
If two or more diagnostic messages are pending simultaneously, only the message with the highest priority is shown. Additional pending diagnostic messages can be shown in Diagnostic list submenu (→  169).
Past diagnostic messages that are no longer pending are shown as follows:
• On the local display: in Event logbook submenu (→  170)
• In FieldCare: via the "Event List /HistoROM" function.
Operating elements
Operating functions in menu, submenu
Plus key
Opens the message about the remedial measures.
A0013970
Enter key
Opens the operating menu.
A0013952
Endress+Hauser 83
Page 84
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA
X X XX X X XX X XX X X X X XX X
S
S
XX
20.50
X
i
S801
Menu
S
(ID:203)
S801 0d00h02m25s
1
2
4
6
3 5
Increase supply voltage
S801 Supply voltage
Diagnostic list
Diagnostics 1
Diagnostics 2 Diagnostics 3
Supply voltage
Supply voltage

12.2.2 Calling up remedial measures

 25 Message for remedial measures
1 Diagnostic information 2 Short text 3 Service ID 4 Diagnostic behavior with diagnostic code 5 Operation time of occurrence 6 Remedial measures
The user is in the diagnostic message.
1. Press  ( symbol).  Diagnostic list submenu opens.
2. Select the desired diagnostic event with  or  and press  .  The message for the remedial measures for the selected diagnostic event opens.
3. Press  +  simultaneously.  The message for the remedial measures closes.
The user is in the Diagnostics menu at an entry for a diagnostics event, e.g. in Diagnostic list submenu or in Previous diagnostics.
1. Press .  The message for the remedial measures for the selected diagnostic event opens.
2. Press  +  simultaneously.  The message for the remedial measures closes.
A0013940-EN
Page 85
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting

12.3 Diagnostic event in the operating tool

If a diagnostic event is present in the device, the status signal appears in the top left status in the operating tool along with the corresponding symbol for event level in accordance with NAMUR NE 107:
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
Calling up remedial measures
1. Navigate to the Diagnostics menu.  In the Actual diagnostics parameter, the diagnostic event is shown with event
text.
2. On the right in the display range, hover the cursor over the Actual diagnostics parameter.
 A tool tip with remedial measures for the diagnostic event appears.

12.4 Diagnostic list

In the Diagnostic list submenu, up to 5 currently pending diagnostic messages can be displayed. If more than 5 messages are pending, the messages with the highest priority are shown on the display.
Navigation path
Diagnostics → Diagnostic list
Calling up and closing the remedial measures
1. Press .  The message for the remedial measures for the selected diagnostic event opens.
2. Press  +  simultaneously.  The message about the remedial measures closes.
Endress+Hauser 85
Page 86
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA

12.5 List of diagnostic events

Diagnostic
number
Diagnostic of sensor
003 Broken probe detected 1. Check map
046 Build-up detected Clean sensor F Alarm
104 HF cable and check sealing
105 HF cable 1. Tighten HF cable connection
106 Sensor 1. Check sensor
Diagnostic of electronic
242 Software incompatible 1. Check software
252 Modules incompatible 1. Check electronic modules
261 Electronic modules 1. Restart device
262 Module connection 1. Check module connections
270 Main electronic failure Change main electronic module F Alarm
271 Main electronic failure 1. Restart device
272 Main electronic failure 1. Restart device
273 Main electronic failure 1. Emergency operation via display
275 I/O module failure Change I/O module F Alarm
276 I/O module failure 1. Restart device
282 Data storage 1. Restart device
283 Memory content 1. Transfer data or reset device
311 Electronic failure 1. Transfer data or reset device
311 Electronic failure Maintenance required!
Diagnostic of configuration
410 Data transfer 1. Check connection
412 Processing Download Download active, please wait C Warning
Short text Remedy instructions Status
signal
[from the
factory]
F Alarm
2. Check sensor
F Alarm
1. Dry HF cable connection
2. Change HF cable
F Alarm
2. Check sensor
3. Change HF cable
F Alarm
2. Check HF cable
3. Contact service
F Alarm
2. Flash or change main electronics module
F Alarm
2. Change I/O or main electronic module
F Alarm
2. Check electronic modules
3. Change I/O Modul or main electronics
F Alarm
2. Change electronic modules
F Alarm
2. Change main electronic module
F Alarm
2. Contact service
F Alarm
2. Change main electronics
F Alarm
2. Change I/O module
F Alarm
2. Contact service
F Alarm
2. Contact service
F Alarm
2. Contact service
M Warning
1. Do not perform reset
2. Contact service
F Alarm
2. Retry data transfer
Diagnostic
behavior
[from the
factory]
Page 87
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting
Diagnostic
number
435 Linearization Check linearization table F Alarm
437 Configuration
438 Dataset 1. Check data set file
482 Block in OOS Set Block in AUTO mode F Alarm
484 Simulation failure
485 Simulation measured
494 Switch output
495 Simulation diagnostic
497 Simulation block
585 Simulation distance Deactivate simulation C Warning
Diagnostic of process
801 Energy too low Increase supply voltage S Warning
825 Operating temperature 1. Check ambient temperature
825 Operating temperature F Alarm
921 Change of reference 1. Check reference configuration
936 EMC interference Check installation on EMC F Alarm
941 Echo lost Check parameter 'DC value' F Alarm
942 In safety distance 1. Check level
943 In blocking distance Reduced accuracy
944 Level range Reduced accuracy
950 Advanced diagnostic 1
Short text Remedy instructions Status
1. Restart device
incompatible
mode
value
simulation
event
output
to 2 occured
2. Contact service
2. Check device configuration
3. Up- and download new configuration
Deactivate simulation C Alarm
Deactivate simulation C Warning
Deactivate simulation switch output C Warning
Deactivate simulation C Warning
Deactivate simulation C Warning
2. Check process temperature
2. Check pressure
3. Check sensor
2. Check safety distance
3. Reset self holding
Check level
Level at process connection
Maintain your diagnostic event M Warning
signal
[from the
factory]
F Alarm
M Warning
S Warning
S Warning
S Alarm
S Warning
S Warning
Diagnostic
behavior
[from the
factory]
1)
1)
1)
1) Diagnostic behavior can be changed.

12.6 Event logbook

12.6.1 Event history

A chronological overview of the event messages that have occurred is provided in the Event list submenu
3) This submenu is only available for operation via local display. In the case of operation via FieldCare, the event list can be displayed with the "Event List / HistoROM" functionality of FieldCare.
Endress+Hauser 87
3)
.
Page 88
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA
Navigation path
Diagnostics → Event logbook → Event list
A maximum of 100 event messages can be displayed in chronological order.
The event history includes entries for:
• Diagnostic events
• Information events
In addition to the operation time of its occurrence, each event is also assigned a symbol that indicates whether the event has occurred or is ended:
• Diagnostic event – : Event has occurred – : Event has ended
• Information event
: Event has occurred
Calling up and closing the remedial measures
1. Press .  The message for the remedial measures for the selected diagnostic event opens.
2. Press  +  simultaneously.  The message about the remedial measures closes.

12.6.2 Filtering the event logbook

Using the Filter options parameter, you can define which category of event messages is displayed in the Event list submenu angezeigt werden.
Navigation path
Diagnostics → Event logbook → Filter options
Filter categories
• All
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
• Information

12.6.3 Overview of information events

Info number Info name
I1000 --------(Device ok)
I1089 Power on
I1090 Configuration reset
I1091 Configuration changed
I1092 Trend data deleted
I1110 Write protection switch changed
I1137 Electronic changed
I1151 History reset
I1154 Reset terminal voltage min/max
I1155 Reset electronic temperature
I1156 Memory error trend
I1157 Memory error event list
Page 89
Levelflex FMP56, FMP57 PROFIBUS PA Diagnostics and troubleshooting
Info number Info name
I1185 Display backup done
I1186 Restore via display done
I1187 Settings downloaded with display
I1188 Display data cleared
I1189 Backup compared
I1256 Display: access status changed
I1264 Safety sequence aborted
I1335 Firmware changed
I1397 Fieldbus: access status changed
I1398 CDI: access status changed
I1512 Download started
I1513 Download finished
I1514 Upload started
I1515 Upload finished
Endress+Hauser 89
Page 90
Diagnostics and troubleshooting Levelflex FMP56, FMP57 PROFIBUS PA

12.7 Firmware history

Date Software
version
07.2011 01.00.zz Original software BA01009F/00/EN/10.10 GP01001F/00/EN/10.10 TI01004F/00/EN/13.11
02.2015 01.01.zz • Support of SD03
1) contains information on the Heartbeat wizards which are available in the latest DTM version for DeviceCare and FieldCare.
Modifications Documentation (FMP56, FMP57, PROFIBUS)
Operating Instructions Description of Parameters Technical Information
• additional languages
• HistoROM functionality enhanced
• "Advanced Diagnostic" function block integrated
• Improvements and bugfixes
BA01009F/00/EN/14.14 BA01009F/00/EN/15.16
GP01001F/00/EN/13.14 TI01004F/00/EN/17.14
1)
TI01004F/00/EN/20.16
The firmware version can explicitly be ordered via the product structure. In this way it is possible to ensure compatibility of the firmware version with an existing or planned system integration.
1)
Page 91
Levelflex FMP56, FMP57 PROFIBUS PA Maintenance

13 Maintenance

The measuring device requires no special maintenance.

13.1 Exterior cleaning

When exterior-cleaning the device, always use cleaning agents that do not attack the surface of the hosuing and the seals.
Endress+Hauser 91
Page 92
Repairs Levelflex FMP56, FMP57 PROFIBUS PA

14 Repairs

14.1 General information on repairs

14.1.1 Repair concept

The Endress+Hauser repair concept assumes that the devices have a modular design and that repairs can be done by the Endress+Hauser service or specially trained customers.
Spare parts are contained in suitable kits. They contain the related replacement instructions.
For more information on service and spare parts, contact the Service Department at Endress+Hauser.

14.1.2 Repairs to Ex-approved devices

When carrying out repairs to Ex-approved devices, please note the following:
• Repairs to Ex-approved devices may only be carried out by trained personnel or by the Endress+Hauser Service.
• Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA) and certificates.
• Only use original spare parts from Endress+Hauser.
• When ordering a spare part, please note the device designation on the nameplate. Only replace parts with identical parts.
• Carry out repairs according to the instructions. On completion of repairs, carry out the specified routine test on the device.
• Only Endress+Hauser Service may convert a certified device into a different certified variant.
• Document all repair work and conversions.

14.1.3 Replacement of an electronics module

If an electronics module has been replaced, it is not necessary to perform a new basic setup as the calibration parameters are stored in the HistoROM which is located in the housing. However, after exchanging the main electronics module it may be necessary to record a new mapping (interference echo suppression).

14.1.4 Replacement of a device

After a complete device or electronic module has been replaced, the parameters can be downloaded into the instrument again in one of the following ways:
• Via the display module Condition: The configuration of the old device has been saved in the display module →  161.
• Via FieldCare Condition: The configuration of the old device has been saved to the computer via FieldCare.
You can continue to measure without carrying out a new setup. Only a linearization and a tank map (interference echo suppression) have to be recorded again.
Page 93
Levelflex FMP56, FMP57 PROFIBUS PA Repairs
002847-A
Spare parts for: Levelflex FMP5x Ser.-no.:
8A21AC098AF4
Cover (front) Cover (right)
IO module
Display
Sensor
Pos. no.
1 2
3 4 5 6
Spare part
Spare no./structure
Main electr.
Additional information: www.endress.com/deviceviewer
71023451
XPF0001-
XPF0002- / XPF0003-
7102345171023451
71023451 71023451
3
4
1
5
2
6

14.2 Spare parts

• A few interchangeable measuring device components are identified by a spare part nameplate. This contains information about the spare part.
• The connection compartment cover of the device contains a spare part nameplate that includes the following information: – A list of the most important spare parts for the measuring device, including their
ordering information.
– The URL for the W@M Device Viewer (www.endress.com/deviceviewer):
There, all spare parts for the measuring device are listed, including the order code, and can be ordered. If available, the corresponding Installation Instructions can also be downloaded there.
A0014979
 26 Example for spare part nameplate in connection compartment cover
Measuring device serial number:
• Is located on the device and spare part nameplate.
• Can be read out via the "Serial number" parameter in the "Device information" submenu.

14.3 Return

The measuring device must be returned if it is need of repair or a factory calibration, or if the wrong measuring device has been delivered or ordered. Legal specifications require Endress+Hauser, as an ISO-certified company, to follow certain procedures when handling products that are in contact with the medium.
To ensure safe, swift and professional device returns, please refer to the procedure and conditions for returning devices provided on the Endress+Hauser website at
http://www.endress.com/support/return-material

14.4 Disposal

Observe the following notes during disposal:
• Observe valid federal/national regulations.
• Ensure proper separation and reuse of the device components.
Endress+Hauser 93
Page 94
Accessories Levelflex FMP56, FMP57 PROFIBUS PA
222 (8.74)
298.5 (11.8) 273.7 (10.8)
255.1 (10)
156 (6.14)
a
164 (6.46)
b
35°
65°
55°

15 Accessories

15.1 Device-specific accessories

15.1.1 Weather protection cover

Accessory Description
Weather protection cover
 27 Weather protection cover; Dimensions: mm (in)
a 37,8 mm (1,5 in) b 54 mm (2,1 in)
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory
Enclosed", option PB "Weather Protection Cover"). Alternatively, it can be separately ordered as an accessory; order code 71162242.
A0015466
A0015472
Page 95
Levelflex FMP56, FMP57 PROFIBUS PA Accessories
122 (4.8)
52 (2)
86
(3.4)
70
(2.8)
140 (5.5)
158 (6.2)
175 (6.9)
A B
ø42...60
(1.65...2.36)

15.1.2 Mounting bracket for the electronics housing

Accessory Description
Mounting bracket for the electronics housing
 28 Mounting bracket for the electronics housing; Dimensions: mm (in)
A Wall mounting B Pipe mounting
For the "Sensor remote" device version (see feature 060 of the product structure), the mounting bracket is part of
the delivery. If required, it can also be ordered as an accessory (order code 71102216).
A0014793
Endress+Hauser 95
Page 96
Accessories Levelflex FMP56, FMP57 PROFIBUS PA
1
2
3

15.1.3 Extension rod / centering HMP40

Accessory Description
Extension rod / centering HMP40
• can be used for: FMP57
• Admissible temperature at lower nozzle edge: – without center
washer: no limitation
– with center washer:
-40 to 150 °C (-40 to 302 °F)
• Additional information: SD01002F
1 Nozzle height 2 Extension rod 3 Center washer
010 Approval:
A A: Non-hazardous area
M M: FM DIP Cl.II Div.1 Gr.E-G N.I., zone 21,22
P P: CSA DIP Cl.II Div.1 Gr.G + coal dust N.I.
S S: FM Cl.I, II, III Div.1 Gr.A-G N.I., zone 0,1,2,20,21,22
U U: CSA Cl.I, II, III Div.1 Gr.A-G N.I., zone 0,1,2
1 1: ATEX II 1G
2 2: ATEX II 1D
A0013597
020 Extension rod; nozzle height:
1 115mm; 150-250mm / 6-10"
2 215mm; 250-350mm / 10-14"
3 315mm; 350-450mm / 14-18"
4 415mm; 450-550mm / 18-22"
9 Special version, TSP-no. to be spec.
030 Center washer:
A Not selected
B DN40 / 1-1/2", inside-d. = 40-45mm, PPS
C DN50 / 2", inside-d. = 50-57mm, PPS
D DN80 / 3", inside-d. = 80-85mm, PPS
E DN80 / 3", inside-d. = 76-78mm, PPS
G DN100 / 4", inside-d. = 100-110mm, PPS
H DN150 / 6", inside-d. = 152-164mm, PPS
J DN200 / 8", inside-d. = 210-215mm, PPS
K DN250 / 10", inside-d. = 253-269mm, PPS
Y Special version, TSP-no. to be spec.
Page 97
Levelflex FMP56, FMP57 PROFIBUS PA Accessories
D
1
2

15.1.4 Mounting kit, isolated

Accessory Description
Mounting kit, isolated
can be used for
• FMP50
• FMP51
• FMP54
• FMP56
• FMP57
A0013586
 29 Scope of supply of the mounting kit:
1 Insulating sleeve 2 Eye-bolt
For reliably insulated fixing of the probe. Maximum process temperature: 150 °C (300 °F)
For rope probes 4 mm (¹⁄₆ in) or 6 mm (1/4 in) with PA>steel:
• Diameter D = 20 mm (0.8 in)
• Order-No.: 52014249
For rope probes 6 mm (¹⁄₄ in) or 8 mm (1/3 in) with PA>steel:
• Diameter D = 25 mm (1 in)
• Order-No.: 52014250
Due to the risk of electrostatic charge, the insulating sleeve is not suitable for use in hazardous areas. In these cases the fixing must be reliably grounded.
The mounting kit can also be ordered directly with the device (see the
Levelflex product structure, feature 620 "Accessory Enclosed", option PG "Mounting kit, isolated, rope").
Endress+Hauser 97
Page 98
Accessories Levelflex FMP56, FMP57 PROFIBUS PA

15.1.5 Remote display FHX50

Accessory Description
Remote display FHX50
A0019128
• Material: – Plastics PBT – CF3M (similar to 316L/1.4404) – Aluminum (in preparation)
• Ingress protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for the display modules: – SD02 (push buttons) – SD03 (touch control)
• Connection cable: – Cable with M12 plug; supplied with the FHX50; up to 30 m (98 ft) – Customer supplied standard cable; up to 60 m (196 ft)
• Ambient temperature: –40 to 80 °C (–40 to 176 °F)
• If the remote display is to be used, the device must be ordered in the version "Prepared for display FHX50"
(feature 030, option L or M). For the FHX50, on the other hand, the option A: "Prepared for display FHX50" has to be selected in feature 050: "Option Measurement Device".
• If a device has not been ordered in the version "Prepared for display FHX50", but is nevertheless to be equipped with an FHX50, it is essential to select the option B: "Not prepared for display FHX50" in feature 050: "Option Measurement Device" of the FHX50. In this case, a retrofit kit, needed to prepare the device for the remote display, is supplied together with the FHX50.
For transmitters with approval, application of the FHX50 may be restricted. A device may only be retrofitted with
the FHX50 if option L or M ("Prepared for FHX50") is quoted under Basic specifications, position 4 "Display, operation" in the associated Safety Instructions (XA). In addition to this, observe the Safety Instructions (XA) of the FHX50.
Do not retrofit transmitters with:
• approval for use in areas with combustible dusts (Dust-Ex approval)
• type of protection Ex nA
For details refer to the document SD01007F.
Page 99
Levelflex FMP56, FMP57 PROFIBUS PA Accessories

15.1.6 Overvoltage protection

Accessory Description
Overvoltage protection for 2-wire-devices OVP10 (1 channel) OVP20 (2 channel)
A0021734
Technical data
• Resistance per channel: 2 * 0.5 Ω
• Threshold DC voltage: 400 to 700 V
• Threshold impulse voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal arrest impulse voltage (8/20 μs): 10 kA
• Suited for wire cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
Ordering with device
The overvoltage protection module is preferably ordered with the device. See product structure, feature 610 "Accessory mounted", option NA "Overvoltage protection". Separate ordering of the module is only necessary if a device is to retrofitted with the overvoltage protection.
Order code for retrofitting
• For 1-channel devices (feature 020, option A) OVP10: 71128617
• For 2-channel devices (feature 020, option B, C, E or G) OVP20 : 71128619
Hosuing lid for retrofitting
In order to keep the necessary safety distances, the housing lid needs to be replaced if the device is retrofitted with the overvoltage protection. Depending on the housing type, the order code of the suitable lid is as follows:
• GT18 housing: Lid 71185516
• GT19 housing: Lid 71185518
• GT20 housing: Lid 71185516
Restrictions for retrofitting
Depending on the approval of the transmitter the usage of the OVP module may be restricted. A device may only be retrofitted with an OVP module if the option NA (overvoltage protection) is quoted unter Optional Specifications in the Safety Instructions (XA) pertaining to the device.
For details refer to SD01090F.
max
Endress+Hauser 99
Page 100
Accessories Levelflex FMP56, FMP57 PROFIBUS PA

15.2 Communication-specific accessories

Accessory Description
Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser
Common Data Interface) to the USB interface of a computer. Order code: 51516983
For details refer to Technical Information TI00405C

15.3 Service-specific accessories

Accessory Description
FieldCare / DeviceCare Endress+Hauser's FDT-based Plant Asset Management tool.
Helps to configure and maintain all field devices of your plant. By supplying status information it also supports the diagnosis of the devices.
For details refer to Operating Instructions BA00027S and BA00059S.

15.4 System components

Accessory Description
Graphic Data Manager Memograph M
The graphic data manager Memograph M provides information on all the relevant process variables. Measured values are recorded correctly, limit values are monitored and measuring points analyzed. The data are stored in the 256 MB internal memory and also on an SD card or USB stick.
For details refer to Technical Information TI00133R and Operating
Instructions BA00247R
Loading...