Levelflex FMP56, FMP57 PROFIBUS PAImportant document information
DANGER
WARNING
CAUTION
NOTICE
1 Important document information
1.1 Document function
These Operating Instructions contain all the information that is required in various phases
of the life cycle of the device: from product identification, incoming acceptance and
storage, to mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal.
1.2 Symbols
1.2.1 Safety symbols
SymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will
result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.2.2 Electrical symbols
SymbolMeaning
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other
connections.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a
potential equalization line or a star grounding system depending on national or
company codes of practice.
Endress+Hauser5
Page 6
Important document informationLevelflex FMP56, FMP57 PROFIBUS PA
A
1.
1.
1.2.3 Tool symbols
SymbolMeaning
Torx screwdriver
A0013442
Flat blade screwdriver
A0011220
Cross-head screwdriver
A0011219
Allen key
A0011221
Hexagon wrench
A0011222
1.2.4 Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Notice or individual step to be observed
, 2., 3.…Series of steps
Result of a step
Help in the event of a problem
Visual inspection
1.2.5 Symbols in graphics
SymbolMeaning
1, 2, 3 ...Item numbers
, 2., 3.…Series of steps
A, B, C, ...Views
A-A, B-B, C-C, ...Sections
6Endress+Hauser
Page 7
Levelflex FMP56, FMP57 PROFIBUS PAImportant document information
-
.
SymbolMeaning
Hazardous area
Indicates a hazardous area.
Safe area (non-hazardous area)
Indicates the non-hazardous area.
1.2.6 Symbols at the device
SymbolMeaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables.
Endress+Hauser7
Page 8
Important document informationLevelflex FMP56, FMP57 PROFIBUS PA
Description of Device Parameters
GP01001F (FMP5x, PROFIBUS PA)
Special documentation
SD00326F
Special documentation
SD01872F
Planning aid for your device
The document contains all the technical data on the device and provides
an overview of the accessories and other products that can be ordered for
the device.
Guide that takes you quickly to the 1st measured value
The Brief Operating Instructions contain all the essential information
from incoming acceptance to initial commissioning.
Reference for your parameters
The document provides a detailed explanation of each individual
parameter in the operating menu. The description is aimed at those who
work with the device over the entire life cycle and perform specific
configurations.
Functional Safety Manual
The document is part of the Operating Instructions and serves as a
reference for application-specific parameters and notes.
Manual for Heartbeat Verification and Heartbeat Monitoring
The document contains descriptions of the additonal parameters and
technical data which are available with the Heartbeat Verification and
Heartbeat Monitoring application packages.
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate
or scan the 2-D matrix code (QR code) on the nameplate.
8Endress+Hauser
Page 9
Levelflex FMP56, FMP57 PROFIBUS PAImportant document information
1.3.1 Safety Instructions (XA)
Depending on the approval, the following Safety Instructions (XA) are supplied with the
device. They are an integral part of the Operating Instructions.
I3IEC Ex d [ia] IIC T6 Ga/Gb, Ex t IIIC Da/Db• FMP56
• FMP57
KAKC Ex ia IIC T6 Ga• FMP56
• FMP57
KBKC Ex ia IIC T6 Ga/Gb• FMP56
• FMP57
MAINMETRO Ex ia IIC T6 Ga• FMP56
• FMP57
MEINMETRO Ex t IIIC Da• FMP56
• FMP57
MHINMETRO Ex ic IIC T6 Gc• FMP56
• FMP57
NANEPSI Ex ia IIC T6 Ga• FMP56
• FMP57
NBNEPSI Ex ia IIC T6 Ga/Gb• FMP56
• FMP57
NFNEPSI DIP A20/21 T85…90oC IP66• FMP56
• FMP57
NGNEPSI Ex nA II T6 Gc• FMP56
• FMP57
NHNEPSI Ex ic IIC T6 Gc• FMP56
• FMP57
N2NEPSI Ex ia IIC T6 Ga/Gb, Ex iaD 20/21 T85…90°C• FMP56
• FMP57
N3NEPSI Ex d[ia] IIC T6 Ga/Gb, DIP A20/21 T85…90°C
IP66
• FMP56
• FMP57
8AFM/CSA IS+XP Cl.I,II,III Div.1 Gr.A-G• FMP56
• FMP57
1)
A
XA00503F XA00503F XA00503F XA00523F XA01136F
XA01169F -XA01169F --
XA01169F -XA01169F --
XA01038F XA01038F XA01038F -XA01038F
XA01043F XA01043F XA01043F -XA01043F
XA01040F XA01040F XA01040F -XA01040F
XA00634F XA00634F XA00634F XA00640F XA00634F
XA00634F XA00634F XA00634F XA00640F XA00634F
XA00637F XA00637F XA00637F XA00643F XA00637F
XA00635F XA00635F XA00635F XA00641F XA00635F
XA00635F XA00635F XA00635F XA00641F XA00635F
XA00638F XA00638F XA00638F XA00644F XA00638F
XA00639F XA00639F XA00639F XA00645F XA00639F
XA00531F
XA00532F
2)
B
XA00531F
XA00532F
3)
C
XA00531F
XA00532F
4)/G 5)
E
XA00572F
XA00573F
6)/L 7)
K
XA00531F
XA00532F
1)A: 2-wire; 4-20mA HART
2)B: 2-wire; 4-20mA HART, switch output
3)C: 2-wire; 4-20mA HART, 4-20mA
4)E: 2-wire; FOUNDATION Fieldbus, switch output
5)G: 2-wire; PROFIBUS PA, switch output
6)K: 4-wire 90-253VAC; 4-20mA HART
7)L: 4-wire 10,4-48VDC; 4-20mA HART
For certified devices the relevant Safety Instructions (XA) are indicated on the
nameplate.
10Endress+Hauser
Page 11
Levelflex FMP56, FMP57 PROFIBUS PAImportant document information
Ex-marking in case of connected FHX50 remote display
If the device is prepared for the remote display FHX50 (product structure: feature 030:
Display, Operation", option L or M), the Ex marking of some certificates changes according
to the following table
BFL or MATEX II 1/2 D Ex ta [ia Db] IIIC Txx°C Da/Db
BGL or MATEX II 3G Ex nA [ia Ga] IIC T6 Gc
BHL or MATEX II 3G Ex ic [ia Ga] IIC T6 Gc
B3L or MATEX II 1/2G Ex d [ia] IIC T6 Ga/Gb,
IEL or MIECEx Ex ta [ia] IIIC T500 xx°C Da
IFL or MIECEx ta [ia Db] IIIC Txx°C Da/Db
IGL or MIECEx Ex nA [ia Ga] IIC T6 Gc
IHL or MIECEx Ex ic [ia Ga] IIC T6 Gc
I3L or MIECEx Ex d [ia] IIC T6 Ga/Gb,
1)
:
xx°C Da
500
ATEX II 1/2D Ex ta [ia Db] IIIC Txx°C Da/Db
IECEx Ex ta [ia Db] IIIC Txx°C Da/Db
1)The marking of certificates not mentioned in this table are not affected by the FHX50.
Endress+Hauser11
Page 12
Basic safety instructionsLevelflex FMP56, FMP57 PROFIBUS PA
2 Basic safety instructions
2.1 Requirements for the personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill
the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function
‣
and task.
Are authorized by the plant owner/operator.
‣
Are familiar with federal/national regulations.
‣
Before starting work, read and understand the instructions in the manual and
‣
supplementary documentation as well as the certificates (depending on the
application).
Follow instructions and comply with basic conditions.
‣
The operating personnel must fulfill the following requirements:
Are instructed and authorized according to the requirements of the task by the facility's
‣
owner-operator.
Follow the instructions in this manual.
‣
2.2 Designated use
Application and measured materials
The measuring device described in these Operating Instructions is intended only for level
measurement of bulk solids. Depending on the version ordered the device can also
measure potentially explosive, flammable, poisonous and oxidizing materials.
Observing the limit values specified in the "Technical data" and listed in the Operating
Instructions and supplementary documentation, the measuring device may be used for the
following measurements only:
Measured process variables: level
‣
Calculated process variables: Volume or mass in arbitrarily shaped vessels (calculated
‣
from the level by the linearization functionality)
To ensure that the measuring device remains in proper condition for the operation time:
Use the measuring device only for measured materials against which the process-
‣
wetted materials are adequately resistant.
Observe the limit values in "Technical data".
‣
Incorrect use
The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
For special measured materials and cleaning agents, Endress+Hauser is glad to provide
‣
assistance in verifying the corrosion resistance of wetted materials, but does not accept
any warranty or liability.
Residual risk
The electronics housing and its built-in components such as display module, main
electronics module and I/O electronics module may heat to 80 °C (176 °F) during operation
through heat transfer from the process as well as power dissipation within the electronics.
During operation the sensor may assume a temperature near the temperature of the
measured material.
Danger of burns due to heated surfaces!
For high process temperatures: Install protection against contact in order to prevent
Wear the required personal protective equipment according to federal/national
‣
regulations.
2.4 Operational safety
Risk of injury.
Operate the device in proper technical condition and fail-safe condition only.
‣
The operator is responsible for interference-free operation of the device.
‣
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
If, despite this, modifications are required, consult with the manufacturer.
‣
Repair
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
‣
Observe federal/national regulations pertaining to repair of an electrical device.
‣
Use original spare parts and accessories from the manufacturer only.
‣
Hazardous area
To eliminate a danger for persons or for the facility when the device is used in the
hazardous area (e.g. explosion protection, pressure vessel safety):
Based on the nameplate, check whether the ordered device is permitted for the
‣
intended use in the hazardous area.
Observe the specifications in the separate supplementary documentation that is an
‣
integral part of these Instructions.
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet
state-of-the-art safety requirements, has been tested, and left the factory in a condition in
which it is safe to operate. It meets general safety standards and legal requirements.
2.5.1 CE mark
The measuring system meets the legal requirements of the applicable EC guidelines. These
are listed in the corresponding EC Declaration of Conformity together with the standards
applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
2.5.2 EAC conformity
The measuring system meets the legal requirements of the applicable EAC guidelines.
These are listed in the corresponding EAC Declaration of Conformity together with the
standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark.
Endress+Hauser13
Page 14
Product descriptionLevelflex FMP56, FMP57 PROFIBUS PA
1
2
5
3
4
3 Product description
3.1 Product design
3.1.1 Levelflex FMP56/FMP57
A0012470
1Design of the Levelflex
1Electronics housing
2Process connection (here as an example: flange)
3Rope probe
4End-of-probe weight
5Rod probe
1Electronics compartment cover
2Display module
3Main electronics module
4Cable glands (1 or 2, depending on instrument version)
5Nameplate
6I/O electronics module
7Terminals (pluggable spring terminals)
8Connection compartment cover
9Grounding terminal
Endress+Hauser15
Page 16
Product descriptionLevelflex FMP56, FMP57 PROFIBUS PA
3.2 Registered trademarks
PROFIBUS
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
KALREZ®, VITON
Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA
TEFLON
Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA
TRI CLAMP
Registered trademark of Alfa Laval Inc., Kenosha, USA
®
®
®
®
16Endress+Hauser
Page 17
Levelflex FMP56, FMP57 PROFIBUS PAIncoming acceptance and product identification
DELIVERYNOTE
1 = 2
DELIVERYNOTE
Madein Germany, 79689 Maulburg
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
Is the order code on the delivery
A0015502
A0022480
A0022486
note (1) identical to the order
code on the product sticker (2)?
Are the goods undamaged?
A0015502
A0022489
Do the nameplate data match the
A0015502
A0022491
ordering information on the
delivery note?
Is the DVD (operating tool)
A0015502
present?
If required (see nameplate): Are
the Safety Instructions (XA)
present?
A0022494
If one of the conditions does not comply, contact your Endress+Hauser distributor.
4.2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
( www.endress.com/deviceviewer ): All information about the measuring device is
displayed.
• Enter the serial number from the nameplates into the Endress+Hauser Operations App
or scan the 2-D matrix code (QR code) on the nameplate with the Endress+HauserOperations App: all the information for the measuring device is displayed.
Endress+Hauser17
Page 18
Incoming acceptance and product identificationLevelflex FMP56, FMP57 PROFIBUS PA
20
21
22
24
25
23
26
1
2
3
4
5
6
7
8
9
10
19
18
17
16
15
14
Ext. ord. cd.:
Order code:
Ser. no.:
LN =
Lref =
Mat.:
Date:
FW:
Dev.Rev.:
DeviceID:
Ta:
if modification
see sep. label
X =
MWP:
12
11
47 (1.85)
92 (3.62)
mm (in)
13
4.2.1 Nameplate
A0010725
3Nameplate of the Levelflex
1Device name
2Address of manufacturer
3Order code
4Serial number (Ser. no.)
5Extended order code (Ext. ord. cd.)
6Process pressure
7Gas phase compensation: reference distance
8Certificate symbol
9Certificate and approval relevant data
10 Degree of protection: e.g. IP, NEMA
11 Document number of the Safety Instructions: e.g. XA, ZD, ZE
12 2-D matrix code (QR code)
13 Modification mark
14 Manufacturing date: year-month
15 Permitted temperature range for cable
16 Geräterevision (Dev.Rev.)
17 Additional information about the device version (certificates, approvals, communication): e.g. SIL, PROFIBUS
18 Firmware version (FW)
19 CE mark, C-Tick
20 DeviceID
21 Material in contact with process
22 Permitted ambient temperature (Ta)
23 Size of the thread of the cable glands
24 Length of probe
25 Signal outputs
26 Operating voltage
Only 33 digits of the extended order code can be indicated on the nameplate. If the
extended order code exceeds 33 digits, the rest will not be shown. However, the
complete extended order code can be viewed in the operating menu of the device in
the Extended order code 1 to 3 parameter.
18Endress+Hauser
Page 19
Levelflex FMP56, FMP57 PROFIBUS PAStorage, Transport
5 Storage, Transport
5.1 Storage conditions
• Permitted storage temperature: –40 to +80 °C (–40 to +176 °F)
• Use the original packaging.
5.2 Transport product to the measuring point
WARNING
L
Housing or probe may be damaged or break away.
Risk of injury!
Transport the measuring device to the measuring point in its original packaging or at
‣
the process connection.
Do not fasten lifting devices (hoisting slings, lifting eyes etc.) at the housing or the
‣
probe but at the process connection. Take into account the mass center of the device in
order to avoid unintended tilting.
Comply with the safety instructions, transport conditions for devices over 18kg
‣
(39.6lbs) (IEC61010).
A0013920
A0014264
Endress+Hauser19
Page 20
MountingLevelflex FMP56, FMP57 PROFIBUS PA
A
C
132
4
B
6 Mounting
6.1 Mounting requirements
6.1.1 Suitable mounting position
A0021468
4Mounting requirements for Levelflex
Mounting distances
• Distance (A) between wall and rod or rope probe:
– for smooth metallic walls: > 50 mm (2 in)
– for plastic walls: > 300 mm (12 in) to metallic parts outside the vessel
– for concrete walls: > 500 mm (20 in), otherwise the available measuring range may be
reduced.
• Distance (B) between rod or rope probe and internal fittings in the vessel: >
300 mm (12 in)
• When using more than one Levelflex:
Minimum distance between the sensor axes: 100 mm (3.94 in)
• Distance (C) from end of probe to bottom of the vessel:
– Rope probe: > 150 mm (6 in)
– Rod probe: > 10 mm (0.4 in)
20Endress+Hauser
Page 21
Levelflex FMP56, FMP57 PROFIBUS PAMounting
Additional conditions
• When mounting in the open, a weather protection cover (1) may be installed to protect
the device against extreme weather conditions.
• In metallic vessels: Preferably do not mount the probe in the center of the vessel (2), as
this would lead to increased interference echoes.
If a central mounting position can not be avoided, it is crucial to perform an interference
echo suppresion(mapping) after the commissioning of the device.
• Do not mount the probe in the filling curtain (3).
• Avoid buckling the rope probe during installation or operation (e.g. through product
movement against silo wall) by selecting a suitable mounting location.
• Check the probe regularly for defects.
With suspended rope probes (probe end not fixed at the bottom) the distance
between the probe rope and internal fittings in the tank must not fall below 300 mm
(12") during the entire process. A sporadic contact between the probe weight and the
cone of the vessel, however, does not influence the measurement as long as the
dielectric constant of the medium is at least DC = 1.8.
When mounting the electronics housing into a recess (e.g. in a concrete ceiling),
observe a minimum distance of 100 mm (4 inch) between the cover of the terminal
compartment / electronics compartment and the wall. Otherwise the connection
compartment / electronics compartment is not accessible after installation.
Endress+Hauser21
Page 22
MountingLevelflex FMP56, FMP57 PROFIBUS PA
A
B
C
C
r= 100 (4)
min
r= 100 (4)
min
6 Nm
(4.42 lbf ft)
6 Nm
(4.42 lbf ft)
6 Nm
(4.42 lbf ft)
6 Nm
(4.42 lbf ft)
6.1.2 Applications with restricted mounting space
Mounting with remote sensor
The device version with a remote sensor is suited for applications with restricted mounting
space. In this case the electronics housing is mounted at a separate position from which it
is easier accessible.
A0014794
AAngled plug at the probe
BAngled plug at the electronics housing
CLength of the remote cable as ordered
• The remote cable is supplied with these device versions
Minimum bending radius: 100 mm (4 inch)
• A mounting bracket for the electronics housing is supplied with these device versions.
Mounting options:
– Wall mounting
– Pipe mounting; diameter: 42 to 60 mm (1-1/4 to 2 inch)
• The connection cable has got one straight and one angled plug (90°). Depending on the
local conditions the angled plug can be connected at the probe or at the electronics
housing.
Probe, electronics and connection cable are adjusted to match each other. They are
marked by a common serial number. Only components with the same serial number
shall be connected to each other.
Since the tensile forces are also heavily dependent on the viscosity of the product, a higher
safety factor is necessary for highly viscous products and if there is a risk of cornice
buildup. In critical cases it is better to use a 6 mm rope instead of a 4 mm one.
The same forces also act on the silo cover. On a fixed rope, the tensile forces are definitely
greater, but this can not be calculated. Observe the tensile strength of the probes.
Options for reducing the tensile forces:
• Shorten the probe.
• If the maximum tensile load is exceeded, check whether it would be possible to use a
non-contact Ultrasonic or Level-Radar device.
The following diagrams show typical loads for frequently occurring bulk solids as reference
values. The calculation is performed for the following conditions:
• Calculation according to DIN 1055, Part 6 for the cylindrical part of the silo.
• Suspended probe (probe end not fixed at the bottom)
• Free-flowing bulk solid, i.e. mass flow. A calculation for core flow is not possible. In the
event of collapsing cornices, considerably higher loads can occur.
• The specification for tensile forces contains the safety factor 2 (in addition to the safety
factors already taken into account by DIN 1055), which compensates for the normal
fluctuation range in pourable bulk solids.
Endress+Hauser23
Page 24
MountingLevelflex FMP56, FMP57 PROFIBUS PA
05101520253035
0
10
20
30
40
50
60
F[kN]
6 mm
L [m]
F[kN]
4 mm
0
4
8
12
16
20
24
28
32
36
40
A
B
C
D
F[kN]
6 mm
L [m]
F[kN]
4 mm
05101520253035
A
B
C
0
2
4
6
8
10
12
14
16
18
0
2
4
6
8
10
12
D
A0017170
5Silica sand in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm
(0,24 in) and 4mm (0,16 in)
ASilo diameter 12 m (40 ft)
BSilo diameter 9 m (30 ft)
CSilo diameter 6 m (20 ft)
DSilo diameter 3 m (10 ft)
6Polyethylene pellets in silo with smooth metallic walls; tensile load as a function of level L for rope
diameters 6mm (0,24 in) and 4mm (0,16 in)
ASilo diameter 12 m (40 ft)
BSilo diameter 9 m (30 ft)
CSilo diameter 6 m (20 ft)
DSilo diameter 3 m (10 ft)
A0017171
24Endress+Hauser
Page 25
Levelflex FMP56, FMP57 PROFIBUS PAMounting
F[kN]
6 mm
L [m]
F[kN]
4 mm
A
B
C
D
05101520253035
0
4
8
12
16
20
24
28
32
36
0
4
8
12
16
20
24
F[kN]
6 mm
L [m]
F[kN]
4 mm
A
B
C
D
05101520253035
0
10
20
30
40
50
60
0
4
8
12
16
20
24
28
32
36
40
A0017172
7Wheat in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm
(0,24 in) and 4mm (0,16 in)
ASilo diameter 12 m (40 ft)
BSilo diameter 9 m (30 ft)
CSilo diameter 6 m (20 ft)
DSilo diameter 3 m (10 ft)
8Cement in silo with smooth metallic walls; tensile load as a function of level L for rope diameters 6mm
ATank diameter 12 m (40 ft)
BTank diameter 9 m (30 ft)
CTank diameter 6 m (20 ft)
DTank diameter 3 m (10 ft)
(0,24 in) and 4mm (0,16 in)
A0017173
Endress+Hauser25
Page 26
MountingLevelflex FMP56, FMP57 PROFIBUS PA
Bending strength of rod probes
SensorFeature 060ProbeBending strength [Nm]
FMP57AE, AFRod 16mm (0.63") 316L30
26Endress+Hauser
Page 27
Levelflex FMP56, FMP57 PROFIBUS PAMounting
6.1.4 Notes on the process connection
Probes are mounted to the process connection with threaded connections or flanges. If
during this installation there is the danger that the probe end moves so much that it
touches the tank floor or cone at times, the probe must, if necessary, be shortened and
fixed down → 31.
Threaded connection
A0015121
9Mounting with threaded connection; flush with the container ceiling
Seal
The thread as well as the type of seal comply to DIN 3852 Part 1, screwed plug form A.
They can be sealed with the following types of sealing rings:
• Thread G3/4": According to DIN 7603 with the dimensions 27 x 32 mm
• Thread G1-1/2": According to DIN 7603 with the dimensions 48 x 55 mm
Please use a sealing ring according to this standard in the form A, C or D and of a material
that is resistant to the application.
Endress+Hauser27
Page 28
MountingLevelflex FMP56, FMP57 PROFIBUS PA
£150 (6)
H
ø 150 (6)£
Nozzle mounting
A0015122
Length H of the rigid part of the rope probe
ProbeH
FMP56, rope 4 mm (0.16 in)94 mm (3.7 in)
FMP57, rope 4 mm (0.16 in)120 mm (4.7 in)
FMP57, rope 6 mm (0.24 in)135 mm (5.3 in)
• Permissible nozzle diameter: ≤ 150 mm (6 in).
For larger diameters the near range measuring capability may be reduced.
For nozzles ≥ DN300: → 30.
• Permissible nozzle height
2)
: ≤ 150 mm (6 in).
For a larger height the near range measuring capability may be reduced.
Larger nozzle heights may be possible in special cases (see section "Rod extension/
centering HMP40 for FMP57").
• The end of the nozzle should be flush with the tank ceiling in order to avoid ringing
effects.
With thermally insulated vessels the nozzle should also be insulated in order to
prevent condensate formation.
2)Larger nozzle heights on request
28Endress+Hauser
Page 29
Levelflex FMP56, FMP57 PROFIBUS PAMounting
Rod extension/centering HMP40 for FMP57
For FMP57 with rope probes the rod extension/centering HMP 40 is available as an
accessory → 96. It has to be used if otherwise the probe rope comes into contact with
the lower edge of the nozzle.
For FMP57 with rope probes the rod extension/centering HMP 40 is available as an
accessory. It has to be used if otherwise the probe rope comes into contact with the lower
edge of the nozzle.
This accessory consists of the extension rod corresponding to the nozzle height, on
which a centering disk is also mounted if the nozzles are narrow or when working in
bulk solids. This component is delivered separately from the device. Please order the
probe length correspondingly shorter.
Centering disks with small diameters (DN40 and DN50) may only be used if there is
no significant build-up in the nozzle above the disk. The nozzle must not become
clogged by the product.
Endress+Hauser29
Page 30
MountingLevelflex FMP56, FMP57 PROFIBUS PA
1
2
3
4
Installation in nozzles ≥ DN300
If installation in ≥ 300mm/12" nozzles is unavoidable, installation must be carried out in
accordance with the following sketch.
A0014199
1Lower edge of the nozzle
2Approx. flush with the lower edge of the nozzle (± 50 mm/2")
3Plate
4Pipe 150 to 180 mm (6 to 7 inch)
Nozzle diameterPlate diameter
300 mm (12")280 mm (11")
≥ 400 mm (16")≥ 350 mm (14")
30Endress+Hauser
Page 31
Levelflex FMP56, FMP57 PROFIBUS PAMounting
1
A
C
B
2
6.1.5 Securing the probe
Securing rope probes
A0012609
ASag of the rope: ≥ 1 cm per 1m of the probe length (0.12 inch per 1 ft of the probe length)
BReliably grounded end of probe
CReliably isolated end of probe
1:Mounting and contact with a bolt
2Mounting kit isolated
• The end of the probe needs to be secured under the following conditions:
– if otherwise the probe sporadically comes into contact with the wall of the vessel, the
outlet cone, internal fittings or other parts of the installation.
– if otherwise the probe sporadically gets close to a concrete wall (minimum distance 0.5
m / 20 inch).
• The end of probe can be secured at its internal thread
– rope 4 mm (1/6"), 316: M 14
– rope 6 mm (1/4"), 316: M 20
– rope 6mm (1/4"), PA>steel: M14
– rope 8mm (1/3"), PA>steel: M20
• Preferably use the 6 mm (1/4") rope probe due to the higher tensile strength when
fixing a rope probe.
• The fixing must be either reliably grounded or reliably insulated. If it is not possible to
mount the probe weight with a reliably insulated connection, it can be secured using an
isolated eyelet, which is available as an accessory.
• In the case of a grounded fixing the search for a positive end-of-probe signal must be
activated. Otherwise an automatic probe length correction is impossible.
Navigation: Expert → Sensor → EOP evaluation → EOP search mode
Setting: Positive EOP option
• In order to prevent an extremely high tensile load (e.g. due to thermal expansion) and
the risk of rope crack, the rope has to be slack. Make the rope longer than the required
measuring range such that there is a sag in the middle of the rope that is ≥ 1cm/(1 m
rope length) [0.12 inch/(1 ft rope length)].
Tensile load limit of rope probes: → 23
Endress+Hauser31
Page 32
MountingLevelflex FMP56, FMP57 PROFIBUS PA
mm (in)
ø a
ø b
»50 (1.97)
1
2
3
»50 (1.97)
4
5
6
ø<25 (1.0)
3 (0.12)»
Securing rod probes
• For WHG approvals: For probe lengths ≥ 3 m (10 ft) a support is required.
• In general, rod probes must be supported if there is a horizontal flow (e.g. from an
agitator) or in the case of strong vibrations.
• Rod probes may only be supported at the end of the probe.
1Probe rod, uncoated
2Sleeve bored tight to ensure electrical contact between the rod and sleeve!
3Short metal pipe, e.g. welded in place
4Probe rod, coated
5Plastic sleeve, e.g. PTFE, PEEK or PPS
6Short metal pipe, e.g. welded in place
NOTICE
Poor grounding of the end of probe may cause measuring errors.
Apply a narrow sleeve which has good electrical contact to the probe.
‣
NOTICE
Welding may damage the main electronics module.
‣
Before welding: Ground the probe and dismount electronics.
A0012607
32Endress+Hauser
Page 33
Levelflex FMP56, FMP57 PROFIBUS PAMounting
≥≥100
4
≥≥100
4
mm(in)
ø80...150
(ø3.2...6)
1
3
2
6.1.6 Special mounting conditions
Concrete silos
Installation, for example, into a thick concrete ceiling should be made flush with the lower
edge. Alternatively, the probe can also be installed into a pipe that must not protrude over
the lower edge of the silo ceiling. The pipe should be kept at a minimum length.
Installation suggestions see diagram.
A0014138
1Metal sheet
2Metal tube
3Extension rod / Centering HMP40 (see "Accessories")
Note for installations with rod extension/center washer (accessories): Strong dust
generation can lead to build-up behind the center washer. This can cause an interference
signal. For other installation possibilities please contact Endress+Hauser.
Endress+Hauser33
Page 34
MountingLevelflex FMP56, FMP57 PROFIBUS PA
Ø16
(Ø0.63)
Ø16.5(0.65)
Ø<26
(Ø<1.02)
mm(in)
Installation from the side
A0014140
• If installation from above is not possible, the Levelflex can also be mounted from the
side.
• In this case, always fix the rope probe → 31 .
• Support rod probe if the lateral loadbearing capacity is exceeded → 26. Only fix rod
probes at the probe end → 31.
34Endress+Hauser
Page 35
Levelflex FMP56, FMP57 PROFIBUS PAMounting
1
2
Non-metallic vessels
A0012527
1Non-metallic vessel
2Metal sheet or metal flange
To ensure reliable measurements in non-metallic vessels:
• Select an instrument version with metal flange (minimum size DN50/2").
• Or: mount a metal sheet with a diameter of at least 200 mm (8 in) to the probe at the
process connection. Its orientation must be perpendicular to the probe.
Endress+Hauser35
Page 36
MountingLevelflex FMP56, FMP57 PROFIBUS PA
MAX
1
3
MAX
2
40(1.57)
40(1.57)
MAX
mm(in)
MAX
1
3
2
Vessels with heat insulation
If process temperatures are high, the device must be included in normal tank
insulation to prevent the electronics heating up as a result of heat radiation or
convection. The insulation may not exceed beyond the points labeled "MAX" in the
drawings.
• For mounting thread 3/4": Hexagonal wrench 36 mm
• For mounting thread 1-1/2": Hexagonal wrench 55 mm
• To shorten rod or coax probes: Saw
• To shorten rope probes:
– Allen key AF 3 mm (for 4mm ropes) or AF 4 mm (for 6 mm ropes)
– Saw or bolt cutter
• For flanges and other process connections: appropriate mounting tools
• To turn the housing: Hexagonal wrench 8 mm
6.2.2 Shortening the probe
When shortening the probe: Enter the new length of probe into the Quick Setup
which can be found in the electronics housing behind the display module.
A0014241
Shortening rod probes
Rod probes must be shortened if the distance to the container floor or outlet cone is less
than 10 mm (0.4 in). The rods of a rod probe are shortened by sawing at the bottom end.
Rod probes of FMP52 can not be shortened as they are coated.
Shortening rope probes
Rope probes must be shortened if the distance to the container floor or outlet cone is less
than 150 mm (6 in).
Endress+Hauser37
Page 38
MountingLevelflex FMP56, FMP57 PROFIBUS PA
B
A
C
A0021693
Rope materialABCTorque for set screws
3164 mm (0.16 in)40 mm (1.6 in)3 mm5 Nm (3.69 lbf ft)
3166 mm (0.24 in)55 mm (2.2 in)4 mm15 Nm (11.06 lbf ft)
PA > steel6 mm (0.24 in)40 mm (1.6 in)3 mm5 Nm (3.69 lbf ft)
PA > steel8 mm (0.31 in)55 mm (2.2 in)4 mm15 Nm (11.06 lbf ft)
1.Using an Allen key, loosen the set screws at the end-of-probe weight. Note: The set
screws have got a clamping coating in order to prevent accidental loosening. Thus an
increased torque might be necessary to loosen them.
2.Remove released rope from the weight.
3.Measure off new rope length.
4.Wrap adhesive tape around the rope at the point to be shortened to prevent it from
fanning out.
5.Saw off the rope at a right angle or cut it off with a bolt cutter.
6.Insert the rope completely into the weight.
7.Screw the set screws into place. Due to the clamping coating of the setscrews
application of a screw locking fluid is not necessary.
38Endress+Hauser
Page 39
Levelflex FMP56, FMP57 PROFIBUS PAMounting
6.2.3 Mounting the device
Mounting devices with thread
A0012528
Devices with mounting thread are screwed into a welding boss or a flange and are usually
also secured with these.
• Tighten with the hexagonal nut only:
– Thread 3/4": Hexagonal wrench 36 mm
– Thread 1-1/2": Hexagonal wrench 55 mm
• Recommended torque when using the supplied aramid fibre seal and a process
pressure of 40 bar (580 psi):
– Thread 3/4": 25 Nm
– Thread 1-1/2": 140 Nm
• When installing in metal containers, take care to ensure good metallic contact
between the process connection and container.
Flange mounting
If a seal is used, be sure to use unpainted metal bolts to ensure good electrical contact
between probe flange and process flange.
Mounting rope probes
NOTICE
Electrostatic discharges may damage the electronics.
Earth the housing before lowering the rope into the vessel.
‣
Endress+Hauser39
Page 40
MountingLevelflex FMP56, FMP57 PROFIBUS PA
*
*
A0012529
When lowering the rope probe into the vessel, observe the following:
• Uncoil rope and lower it slowly and carefully into the vessel.
• Do not kink the rope.
• Avoid any backlash, since this might damage the probe or the vessel fittings.
Mounting rope probes in a partially full silo
It is not always possible to empty a silo which is already in operation. If a minimum of
2/3 of the silo is empty, it is possible to install the probe into the partially filled silo. If
possible, make a visual check after the installation to see that the rope has not
tangled or is lying such that it can knot when the level falls. Before full accuracy is
obtained the probe rope must hang fully extended.
6.2.4 Mounting the "Sensor remote" version
This section is only valid for devices of the version "Probe Design" = "Sensor remote"
(feature 600, option MB/MC/MD).
For the version "Probe design" = "Sensor remote" the following is supplied:
• The probe with the process connection
• The electronics housing
• The mounting bracket for wall or pipe mounting of the electronics housing
• The connection cable (length as ordered). The cable has got one straight and one angled
plug (90°). Depending on the local conditions the angled plug can be connected at the
probe or at the electronics housing.
CAUTION
L
The plugs of the connection cable may be damaged by mechanical stress.
Mount the probe and the electronics housing tightly before connecting the cable.
‣
Lay the cable such that it is not exposed to mechanical stress. Minimum bending
‣
radius: 100 mm (4").
When connecting the cable: Connect the straight plug before the angled one. Torque
‣
for both coupling nuts: 6 Nm.
Probe, electronics and connection cable are adjusted to match each other. They are
marked by a common serial number. Only components with the same serial number
shall be connected to each other.
If the measuring point is exposed to strong vibrations, an additional locking
compound (e.g. Loctite 243) can be applied at the plug connectors.
40Endress+Hauser
Page 41
Levelflex FMP56, FMP57 PROFIBUS PAMounting
122 (4.8)
52 (2)
86
(3.4)
70
(2.8)
140 (5.5)
158 (6.2)
175 (6.9)
AB
ø42...60
(1.65...2.36)
A
B
C
C
r= 100 (4)
min
r= 100 (4)
min
6 Nm
(4.42 lbf ft)
6 Nm
(4.42 lbf ft)
6 Nm
(4.42 lbf ft)
6 Nm
(4.42 lbf ft)
Mounting the electronics housing
A0014793
12Mounting the electronics housing using the mounting bracket; dimensions: mm (in)
AWall mounting
BPipe mounting
Connecting the cable
Required tools:
Open-end wrench 18AF
13Connecting the cable. There are the following possibilities:
AAngled plug at the probe
BAngled plug at the electronics housing
CLength of the remote cable as ordered
A0014794
Endress+Hauser41
Page 42
MountingLevelflex FMP56, FMP57 PROFIBUS PA
max.350°
8mm
8mm
+
E
–
1
3mm
6.2.5 Turning the transmitter housing
To provide easier access to the connection compartment or display module, the transmitter
housing can be turned:
A0013713
1.Unscrew the securing screw using an open-ended wrench.
2.Rotate the housing in the desired direction.
3.Tighten the securing screw (1,5 Nm for plastics housing; 2,5 Nm for aluminium or
stainless steel housing).
6.2.6 Turning the display module
1.If present: Loosen the screw of the securing clamp of the electronics compartment
cover using an Allen key and turn the clamp 90° conterclockwise.
2.Unscrew cover of the electronics compartment from the transmitter housing.
3.Pull out the display module with a gentle rotation movement.
4.Rotate the display module into the desired position: Max. 8 × 45 ° in each direction.
5.Feed the spiral cable into the gap between the housing and main electronics module
and plug the display module into the electronics compartment until it engages.
6.Screw the cover of the electronics compartment firmly back onto the transmitter
housing.
7.Tighten the securing clamp again using the Allen key (Torque: 2.5 Nm).
A0013905
42Endress+Hauser
Page 43
Levelflex FMP56, FMP57 PROFIBUS PAMounting
6.3 Post-installation check
Is the device undamaged (visual inspection)?
m
Does the device conform to the measuring point specifications?
For example:
• Process temperature
m
• Process pressure (refer to the chapter on "Material load curves" of the "Technical Information"
document)
• Ambient temperature range
• Measuring range
Are the measuring point identification and labeling correct (visual inspection)?
m
Is the device adequately protected from precipitation and direct sunlight?
m
Are the securing screw and securing clamp tightened securely?
m
Endress+Hauser43
Page 44
Electrical connectionLevelflex FMP56, FMP57 PROFIBUS PA
1
3
+
+
2
4
FIELDBUS
2-channel overvoltage protection
-
-
[17]
4-20mA/
4-20mA/
B
1
1
+
+
2
2
FIELDBUS
Sparepart
71023457
PA/FF
[06/07]
FIELDBUS
-
-
1
3
+
+
2
4
PA/FF
10 mm
Spare part
71108xxx
2- wirelevel
4-20mA PFS
FIELDBUS
[26/27]
open
-
-
A
4
1
1
2
3
6
5
3+
3+
4-
4-
!
7 Electrical connection
7.1 Connection conditions
7.1.1 Terminal assignment
PROFIBUS PA / FOUNDATION Fieldbus
14Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus
AWithout integrated overvoltage protection
BWith integrated overvoltage protection
1Cable screen: Observe cable specifications
2Switch output (open collector): Terminals 3 and 4
3PROFIBUS PA / FOUNDATION Fieldbus: Terminals 1 and 2
4Terminal for potential equalization line
5Cable entries
6Overvoltage protection module
For optimum interference immunity we recommend to connect an external resistor
(internal resistance of the relay or Pull-up resistor) of < 1000 Ω.
7.1.2 Cable specification
• Devices without integrated overvoltage protection
Pluggable spring-force terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Devices with integrated overvoltage protection
Screw terminals for wire cross-sections 0.2 to 2.5 mm2 (24 to 14 AWG)
• For ambient temperature TU≥60 °C (140 °F): use cable for temperature TU +20 K.
PROFIBUS
Use a twisted, screened two-wire cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions
BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning",
PNO Guideline 2.092 "PROFIBUS PA User and Installation Guideline" and
IEC 61158-2 (MBP).
Endress+Hauser45
Page 46
Electrical connectionLevelflex FMP56, FMP57 PROFIBUS PA
2
1
3
4
4
2
3
1
7.1.3 Device plug connectors
For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be
connected without opening the housing.
3)Input voltages up to 35 V will not spoil the device.
Polarity sensitiveNo
FISCO/FNICO compliant
according to IEC 60079-27
1)
Yes
"Approval"
• Non-Ex
• Ex nA
• Ex nA[ia]
• Ex ic
• Ex ic[ia]
• Ex d[ia] / XP
• Ex ta / DIP
• CSA GP
• Ex ia / IS
• Ex ia + Ex d[ia] / IS + XP
2)
Terminal voltage
9 to 32 V
9 to 30 V
3)
7.1.5 Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires
the use of overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be ensured
by an integrated or external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as
PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel2 × 0.5 Ω max.
Threshold DC voltage400 to 700 V
Threshold impulse voltage< 800 V
Capacitance at 1 MHz< 1.5 pF
Nominal arrest impulse voltage (8/20 μs)10 kA
External overvoltage protection
HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection.
For detailed information please refer to the following documents:
• HAW562: TI01012K
• HAW569: TI01013K
Endress+Hauser47
Page 48
Electrical connectionLevelflex FMP56, FMP57 PROFIBUS PA
1.
2.
3.
10 (0.4)
10 (0.4)
mm (in)
4.
5.
5.
7.2 Connecting the device
WARNING
L
Explosion hazard!
Comply with the relevant national standards.
‣
Observe the specifications in the Safety Instructions (XA).
‣
Only use the specified cable glands.
‣
Check whether the supply voltage matches the specifications on the nameplate.
‣
Before connecting the device: Switch the supply voltage off.
‣
Before switching on the supply voltage: Connect the potential bonding line to the
‣
exterior ground terminal.
Required tools and accessories:
• For instruments with safety pin for the lid: AF 3 Allen key
• Wire stripping pliers
• When using stranded wires: Wire end sleeves.
A0012619
1.Loosen the screw of the securing clamp of the connection compartment cover and
turn the clamp 90° counterclockwise.
2.Unscrew the connection compartment cover.
3.Push the cable through the cable entry. To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4.Strip the cable.
5.Strip the cable ends 10 mm (0.4 in). For stranded cables, also attach wire end
ferrules.
Connect the cable in accordance with the terminal assignment → 44.
8.When using screened cable: Connect the cable screen to the ground terminal.
9.Screw the cover onto the connection compartment.
10. For instruments with safety pin for the lid: Adjust the safety pin so that its edge is
over the edge of the display lid. Tighten the safety pin.
7.2.1 Pluggable spring-force terminals
Instruments without integrated overvoltage protection have pluggable spring-force
terminals. Rigid conductors or flexible conductors with cable sleeve can directly be inserted
and are contacted automatically.
To remove cables from the terminal: Press on the groove between the terminals using a
flat-tip screwdriver ≤ 3 mm (0.12 inch) while pulling the cables out of the terminals.
A0013661
7.3 Post-connection check
Are cables or the device undamaged (visual inspection)?
m
Do the cables comply with the requirements?
m
Do the cables have adequate strain relief?
m
Are all cable glands installed, firmly tightened and correctly sealed?
m
Does the supply voltage match the specifications on the transmitter nameplate?
m
Is the terminal assignment correct → 44?
m
Endress+Hauser49
Page 50
Electrical connectionLevelflex FMP56, FMP57 PROFIBUS PA
If required: Is the protective earth connected correctly ?
m
If supply voltage is present: Is the device ready for operation and do values appear on the display
m
module?
Are all housing covers installed and firmly tightened?
white background lighting; switches to red in
event of device error
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
local operation with 3 push buttons (, ,)external operation via touch control; 3 optical
keys: , ,
Operating elements also accessible in various hazardous areas
Data backup function
The device configuration can be saved in the display module.
Data comparison function
The device configuration saved in the display module can be compared to the current device
configuration.
Data transfer function
The transmitter configuration can be transmitted to another device using the display module.
Endress+Hauser51
Page 52
Operation optionsLevelflex FMP56, FMP57 PROFIBUS PA
3
2
1
ENDRESS + HAUSER
T
PROFIBUS DP
PROFIBUS PA
1
2
3
5
444
8.1.2 Operation with remote display and operating module FHX50
A0013137
17FHX50 operating options
1Housing of the remote display and operating module FHX50
2Display and operating module SD02, push buttons; cover must be removed
3Display and operating module SD03, optical keys; can be operated through the glass of the cover
8.1.3 Remote operation
Via PROFIBUS PA protocol
A0015775
1Segment coupler
2Computer with Profiboard/Proficard and operating tool (e.g. FieldCare)
3PLC (Progrommable Logic Controller)
4Transmitter
5Additional functions (valves etc.)
1Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface)
2Commubox FXA291
3Computer with "FieldCare" operating tool
Endress+Hauser53
Page 54
Operation optionsLevelflex FMP56, FMP57 PROFIBUS PA
8.2 Structure and function of the operating menu
8.2.1 Structure of the operating menu
MenuSubmenu /
parameter
Language
Commissioning
SetupParameter 1
DiagnosticsDiagnostic listContains up to 5 currently active error
5)
Expert
Contains all parameters of the device
(including those which are already contained
in one of the above submenus). This menu is
organized according to the function blocks of
the device.
The parameter of the Expert menu are
described in:
GP01018F (PROFIBUS PA)
2)
...
Parameter N
Advanced setupContains further submenus and
Event logbook
Device information Contains information needed to identify
Measured valuesContains all current measured values.
Data loggingContains the history of the individual
SimulationUsed to simulate measured values or
Device checkContains all parameters needed to check
Heartbeat
SystemContains all general device parameters
SensorContains all parameters needed to
OutputContains all parameters neeed to
1)
4)
Meaning
Defines the operating language of the
on-site display.
Opens the interactive wizard for a guided
commissioning of the device.
As a rule, no additional settings in the
other menus are required after the
completion of the wizard.
When all these parameters have been
assigned appropriate values, the
measured should be completely
configured in a standard application.
parameters:
• to adapt the device to special
measuring conditions.
• to process the measured value (scaling,
linearization).
• to configure the signal output.
messages.
3)
Contains the last 20 messages (which are
no longer active).
the device.
measuring values.
output values.
the measurement capability of the
device.
Contains all wizards for the HeartbeatVerification and Heartbeat Monitoring
application packages.
which do not affect the measurement or
the communication interface.
DiagnosticsContains all parameters needed to detect
1)In case of operation via operating tools (e.g. FieldCare), the "Language" parameter is located at "Setup →
Advanced setup → Display"
2)only for operation via a FDT/DTM system
3)only available with local operation
4)only available for operation via DeviceCare or FieldCare
5)On entering the "Expert" menu, an access code is always requested. If a customer specific access code has
not been defined, "0000" has to be entered.
Meaning
configure the digital communication
interface.
and analyze operational errors.
Endress+Hauser55
Page 56
Operation optionsLevelflex FMP56, FMP57 PROFIBUS PA
8.2.2 User roles and related access authorization
The two user roles Operator and Maintenance have different write access to the
parameters if a device-specific access code has been defined. This protects the device
configuration via the local display from unauthorized access → 57.
Access authorization to parameters
User roleRead accessWrite access
Without access
code
(from the factory)
Operator--
Maintenance
If an incorrect access code is entered, the user obtains the access rights of the Operator
role.
The user role with which the user is currently logged on is indicated by the Accessstatus display parameter (for display operation) or Access status tooling parameter
(for tool operation).
Using the device-specific access code, the parameters for the measuring device
configuration are write-protected and their values can no longer be changed via local
operation.
2.Define a max. 4-digit numeric code as an access code.
Write protection is active.
Parameters that can always be changed
The write protection does not include certain parameters that do not affect the
measurement. Despite the defined access code, they can always be modified, even if the
other parameters are locked.
If no key is pressed for 10 minutes in the navigation and editing mode, the device
automatically locks the write-protected parameters. If the user goes from the navigation
and editing mode back to the measured value display mode, the device automatically locks
the write-protected parameters after 60 s.
• If write access is activated via access code, it can be also be deactivated only via the
access code → 58.
• In the "Description of Device Parameters" documents, each write-protected
parameter is identified with the -symbol.
Endress+Hauser57
Page 58
Operation optionsLevelflex FMP56, FMP57 PROFIBUS PA
8.2.4 Disabling write protection via access code
If the
write-protected by a device-specific access code and its value cannot be changed at the
moment using the local display → 57.
The locking of the write access via local operation can be disabled by entering the devicespecific access code.
-symbol appears on the local display in front of a parameter, the parameter is
1.After you press , the input prompt for the access code appears.
2.Enter the access code.
The -symbol in front of the parameters disappears; all previously write-
protected parameters are now re-enabled.
8.2.5 Deactivation of the write protection via access code
8.2.6 Write protection via write protection switch
Unlike parameter write protection via a user-specific access code, this allows write access
to the entire operating menu - except for the "Contrast display" parameter - to be locked.
The parameter values are now read only and cannot be edited any more (exception
"Contrast display" parameter):
• Via local display
• Via PROFIBUS PA protocol
• Via PROFIBUS DP protocol
1.Loosen the securing clamp.
2.Unscrew the housing cover.
3.Pull out the display module with a gentle rotation movement. To make it easier to
access the lock switch, attach the display module to the edge of the electronics
compartment.
Display module is attached to the edge of the electronics compartment.
A0026157
A0013909
Endress+Hauser59
Page 60
Operation optionsLevelflex FMP56, FMP57 PROFIBUS PA
X X XX X X XXX
20.50
XX
XX
4.Installing the lock switch (WP) on the main electronics module in the ON position
enables the hardware write protection. Installing the lock switch (WP) on the main
electronics module in the OFF position (factory setting) disables the hardware write
protection.
If the hardware write protection is enabled: The Hardware locked option is
displayed in the Locking status parameter. In addition to this, the -symbol
appears in the header of the measured value display and in the navigation view
in front of the parameters.
A0015870
If the hardware write protection is disabled: No option is displayed in the Lockingstatus parameter. The -symbol disappears in the header of the measured value
display and in the navigation view in front of the parameters.
5.Feed the spiral cable into the gap between the housing and main electronics module
and plug the display module into the electronics compartment in the desired
direction until it engages.
6.Screw the electronics compartment cover closed and tighten the securing clamp.
The keypad lock allows to disable access to the entire operating menu via local operation.
Thus navigating through the operating menu or modifying the values of individual
parameters is no longer possible. Only the measured values on the measured value display
can be read off.
The keylock is enabled and disabled via a context menu.
Enabling the keylock
For the SD03 display:
The keylock is automatically activated:
• If the device has not been operated via the display for > 1 minute.
• After a restart of the device.
To activate the keylock manually:
1.The device is in the measured value display.
Press for at least 2 seconds.
A context menu appears.
2.Select Keylock on from the context menu.
The keylock is enabled.
When attempting to access the operating menu while the keylock is enabled, the
Keylock on message appears.
Disabling the keylock
1.The keylock is enabled.
Press for at least 2 seconds.
A context menu appears.
2.Select Keylock off from the context menu.
The keylock is disabled.
Endress+Hauser61
Page 62
Operation optionsLevelflex FMP56, FMP57 PROFIBUS PA
3.1
3.2
2.1
2.2
2.4
2.5
1.1
1.2
1.3
1.4
2.3
2.6
1
2
3
45
ESC
OPEN
OPEN
E
ABC_
DEFG
User
HIJK
LMNO
PQRS
TUVW
XYZ
Aa1
3
4
0
12
9
5
6
8
7
20
8.3 Display and operating module
8.3.1 Display appearance
A0012635
18Appearance of the display and operation module for on-site operation
1Measured value display (1 value max. size)
1.1 Header containing tag and error symbol (if an error is active)
1.2 Measured value symbols
1.3 Measured value
1.4 Unit
2Measured value display (1 bargraph + 1 value)
2.1 Bargraph for measured value 1
2.2 Measured value 1 (including unit)
2.3 Measured value symbols for measured value 1
2.4 Measured value 2
2.5 Unit for measured value 2
2.6 Measured value symbols for measured value 2
3Representation of a parameter (here: a parameter with selection list)
3.1 Header containing parameter name and error symbol (if an error is active)
3.2 Selection list; marks the current parameter value.
4Input matrix for numbers
5Input matrix for alphanumeric and special characters
• Pressing the key briefly
– Exits the current menu level and takes you to the next higher level.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s returns you to the measured value display
("home position").
For text and numeric editor
Closes the text or numeric editor without applying changes.
Minus/Enter key combination (press and hold down the keys
simultaneously)
Reduces the contrast (brighter setting).
Plus/Enter key combination (press and hold down the keys
simultaneously)
Increases the contrast (darker setting).
Minus/Plus/Enter key combination (press and hold down the keys
simultaneously)
For measured value display
Enables or disables the keypad lock.
Endress+Hauser65
Page 66
Operation optionsLevelflex FMP56, FMP57 PROFIBUS PA
3
2
1
4
3
4
0
12
9
5
6
8
7
20
ABC_
DEFG
User
HIJK
LMNO
PQRS
TUVW
XYZ
Aa1
3
2
1
4
…
0
9
.
–
XYZ
ABC
_
…
Aa1
8.3.3 Entering numbers and text
Numeric editorText editor
A0013999
1
Editing view
2
Display area of the entered values
3
Input mask
4
Operating elements
A0013941
Input mask
The following input symbols are available in the input mask of the numeric and text editor:
Numeric editor symbols
SymbolMeaning
Selection of numbers from 0 to 9.
A0013998
Inserts decimal separator at the input position.
A0016619
Inserts minus sign at the input position.
A0016620
Confirms selection.
A0013985
Moves the input position one position to the left.
8.3.5 Envelope curve on the display and operating module
In order to assess the measuring signal, the envelope curve and - if a mapping has been
recorded - the mapping curve can be displayed:
A0014277
Endress+Hauser69
Page 70
Integration into a PROFIBUS networkLevelflex FMP56, FMP57 PROFIBUS PA
2
98
3
4
5 6
7
8
1
DIP
ON
2
98
3
4
5 6
7
8
1
DIP
ON
2 + 8 = 10
9 Integration into a PROFIBUS network
9.1 Overview of the device database files (GSD)
Manufacturer ID17 (0x11)
Ident number0x1558
Profile version3.02
GSD fileInformation and files under:
GSD file version
9.2 Set device address
• www.endress.com
• www.profibus.org
A0015686
19Address switches in terminal compartment
9.2.1 Hardware adressing
1.Set switch 8 to "OFF".
2.Define the address with switches 1 to 7 according to the table below.
The address change becomes effective after 10 seconds. The device restarts automatically.
Switch1234567
Value in position "ON"1248163264
Value in position "OFF"0000000
A0015902
20Example of hardware addressing: switch 8 is in position "OFF"; switches 1 to 7 define the address.
9.2.2 Software addressing
1.Set switch 8 to "ON".
2.The device restarts automatically. The address remains the same as before (factory
setting: 126).
3.Set the required address via the operating menu: Setup → Device address
70Endress+Hauser
Page 71
Levelflex FMP56, FMP57 PROFIBUS PAIntegration into a PROFIBUS network
2
98
3
4
5 6
7
8
1
DIP
ON
A0015903
21Example of software addressing; switch 8 is in position "ON"; the address is defined in the operating menu
(Setup → Device address)
Endress+Hauser71
Page 72
Commissioning via wizardLevelflex FMP56, FMP57 PROFIBUS PA
1
10 Commissioning via wizard
A wizard guiding the user through the initial setup is available in FieldCare and
DeviceCare.
1.Connect the device to FieldCare or DeviceCare → 52.
2.Open the device in FieldCare or DeviceCare.
The dashboard (home page) of the device appears:
A0025866
1"Commissioning" button calls up the wizard.
3.Click on "Commissioning" to call up the wizard.
4.Enter or select the appropriate value for each parameter. These values are
immediately written to the device.
5.Click "Next" to switch to the next page.
6.After finishing the last page, click "End of sequence" to close the wizard.
If the wizard is cancelled before all necessary parameters have been set, the device
may be in an undefined state. A reset to the default settings is recommended in this
case.
72Endress+Hauser
Page 73
Levelflex FMP56, FMP57 PROFIBUS PACommissioning via operating menu
X X XX X X XXX
20.50
Operation
Setup
Main menu
0104-1
Language
English
Español
Français
Language
English
Deutsch
Ã
0104-1
Ã
Español
Français
Language
English
Deutsch
0104-1
Betrieb
Setup
Hauptmenü
Sprache
Deutsch
0104-1
XXXX
11 Commissioning via operating menu
11.1 Installation and function check
Make sure that all final checks have been completed before you start up your measuring
point:
• Checklist "Post-installation check" → 43
• Checklist "Post-connection check" → 49
11.2 Setting the operating language
Factory setting: English or ordered local language
Endress+Hauser73
22Using the example of the local display
A0013996
Page 74
Commissioning via operating menuLevelflex FMP56, FMP57 PROFIBUS PA
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
11.3 Configuration of a level measurement
A0012838
23Configuration parameters for level measurements in solids
LN Length of probe
RReference point of the measurement
DDistance
LLevel
EEmpty calibration (= Zero point)
FFull calibration (= Span)
If for rope probes the DC value is less than 7, then measurement is not possible in the
area of the straining weight. In these cases, the maximum recommended value for the
empty calibration E is LN - 250 mm (LN - 10 in).
1.Setup → Device tag
Enter tag for measuring point.
2.Navigate to: Setup → Device address
Enter bus address of the device (only in case of software addressing).
3.Navigate to: Setup → Distance unit
Select distance unit.
4.Navigate to: Setup → Bin type
Select bin type.
5.Navigate to: Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
6.Navigate to: Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
7.Navigate to: Setup → Level
Displays the measured level L.
8.Navigate to: Setup → Distance
Displays the distance D between the reference point R and the level L.
9.Navigate to: Setup → Signal quality
Displays the signal quality of the level echo.
74Endress+Hauser
Page 75
Levelflex FMP56, FMP57 PROFIBUS PACommissioning via operating menu
10. For operation via local display:
Navigate to: Setup → Mapping → Confirm distance
Compare the displayed distance to the real distance in order to start the
recording of the mapping curve if required.
11. For operation via operating tool:
Navigate to: Setup → Confirm distance
Compare the displayed distance to the real distance in order to start the
recording of the mapping curve if required.
Endress+Hauser75
Page 76
Commissioning via operating menuLevelflex FMP56, FMP57 PROFIBUS PA
11.4 Recording the reference curve
After the configuration of the measurement it is recommended to record the current
envelope curve as a reference curve. The reference curve can be used later on in the
process for diagnostic purposes. To record the reference curve use the Save reference
curve parameter.
Navigation in the menu
Expert → Diagnostics → Envelope diagnostics → Save reference curve
Meaning of the options
• No
No action
• Yes
The current envelope curve is saved as reference curve.
In devices which have been delivered with software version 01.00.zz, this submenu is
only visible for the "Service" user role.
The reference curve can only be displayed in the envelope curve diagram of FieldCare
after it has been loaded from the device into FieldCare. This is performed by the "Load
Reference Curve" function in FieldCare:
24The "Load Reference Curve" function
76Endress+Hauser
Page 77
Levelflex FMP56, FMP57 PROFIBUS PACommissioning via operating menu
11.5 Configuration of the on-site display
11.5.1 Factory settings of the on-site display for level measurements
ParameterFactory setting for devices with 1 current
output
Format display 1 value, max. size1 value, max. size
Value 1 display Level linearizedLevel linearized
Value 2 display DistanceDistance
Value 3 display Current output 1Current output 1
Value 4 display NoneCurrent output 2
Factory setting for devices with 2 current
outputs
11.5.2 Adjustment of the on-site display
The on-site display can be adjusted in the following menu:
Setup → Advanced setup → Display
Endress+Hauser77
Page 78
Commissioning via operating menuLevelflex FMP56, FMP57 PROFIBUS PA
11.6 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
• Cancel
No action is executed and the user exits the parameter.
• Execute backup
A backup copy of the current device configuration in the HistoROM (built-in in the
device) is saved to the display module of the device. The backup copy comprises the
transmitter and sensor data of the device.
• Restore
The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter and sensor data of
the device.
• Duplicate
The transmitter configuration is duplicated to another device using the transmitter
display module. The following parameters, which characterize the individual measuring
point are not included in the transmitted configuration:
Medium type
• Compare
The device configuration saved in the display module is compared to the current device
configuration of the HistoROM. The result of this comparison is displayed in the
Comparison result parameter.
• Clear backup data
The backup copy of the device configuration is deleted from the display module of the
device.
While this action is in progress, the configuration cannot be edited via the local
display and a message on the processing status appears on the display.
If an existing backup is restored to a different device using the Restore option, it may
occur that some device functionalities are no longer available. In some cases even a
device reset → 164 will not restore the original status.
In order to transmit a configuration to a different device, the Duplicate option should
always be used.
78Endress+Hauser
Page 79
Levelflex FMP56, FMP57 PROFIBUS PACommissioning via operating menu
11.7 Protection of the settings against unauthorized
changes
There are two ways to protect the settings against unauthorized changes:
• Via parameter settings (software locking) → 57
• Via locking switch (hardware locking) → 59
Endress+Hauser79
Page 80
Diagnostics and troubleshootingLevelflex FMP56, FMP57 PROFIBUS PA
12 Diagnostics and troubleshooting
12.1 General trouble shooting
12.1.1 General errors
ErrorPossible causeRemedial action
Device does not respond.Supply voltage not connected.Connect the correct voltage.
The cables do not contact the
terminals properly.
Values on the display
invisible
"Communication error" is
indicated on the display when
starting the device or
connecting the display
CDI communication does not
work.
Device measures incorrectly.Parametrization errorCheck and adjust parameterization.
Contrast setting is too weak or too
strong.
The plug of the display cable is not
connected correctly.
Display is defective.Replace display.
Electromagnetic interferenceCheck grounding of the device.
Broken display cable or display plug.Exchange display.
Wrong setting of the COM port on
the computer.
Ensure electrical contact between the
cable and the terminal.
• Increase contrast by pressing and
simultaneously.
• Decrease contrast by pressing and
simultaneously.
Connect the plut correctly.
Check the setting of the COM port on
the computer and change it if necessary.
80Endress+Hauser
Page 81
Levelflex FMP56, FMP57 PROFIBUS PADiagnostics and troubleshooting
12.1.2 Parametrization errors
Parametrization errors for level measurements
ErrorPossible causeRemedial action
Measured value wrongIf measured distance(Setup
→ Distance) matches the real
distance:
Calibration error
If measured distance (Setup
→ Distance) does not match the real
distance:
An interference echo affects the
measurement.
No change of the measured
value when emptying/filling
the tank
The diagnostic message
Echo lost appears after
switching on the supply
voltage.
Device displays a level when
the tank is empty.
Wrong slope of the level in
the entire measuring range
An interference echo affects the
measurement.
Build-up at the probe.Clean the probe.
Error in the echo trackingDeactivate echo tracking (Expert
Noise level to high during
initialization phase.
Incorrect probe length• Carry out probe length correction
Wrong bin property selected.Set Bin type parameter (→ 115)
• Check and adjust the Emptycalibration parameter (→ 115) if
necessary.
• Check and adjust the Full calibration
parameter (→ 116) if necessary.
• Check and adjust linearization if
necessary (Linearization submenu
(→ 132)).
Enter Empty calibration parameter
(→ 115) again.
(Confirm probe length parameter
(→ 147)).
• Carry out mapping over entire probe
while the tank is empty (Confirmdistance parameter (→ 118)).
correctly.
Endress+Hauser81
Page 82
Diagnostics and troubleshootingLevelflex FMP56, FMP57 PROFIBUS PA
1
4
3
X X X XX X XXXX X X XX X XXX
2
S
S
XX
20.50
5
X
i
S801
Menu
Supply voltage
12.2 Diagnostic information on local display
12.2.1 Diagnostic message
Faults detected by the self-monitoring system of the measuring device are displayed as a
diagnostic message in alternation with the measured value display.
Measured value display in alarm conditionDiagnostic message
A0013939-EN
1
Status signal
2
Status symbol (symbol for event level)
3
Status symbol with diagnostics event
4
Event text
5
Operating elements
Status signals
"Failure"
A device error is present. The measured value is no longer valid.
A0013956
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
A0013958
• Outside of the configuration carried out by the user (e.g. level outside configured span)
"Maintenance required"
Maintenance is required. The measured value is still valid.
A0013957
Status symbol (symbol for event level)
"Alarm" status
The measurement is interrupted. The signal outputs take on the defined alarm condition.
A0013961
A diagnostic message is generated.
"Warning" status
The device continues to measure. A diagnostic message is generated.
A0013962
82Endress+Hauser
Page 83
Levelflex FMP56, FMP57 PROFIBUS PADiagnostics and troubleshooting
Diagnostics event and event text
The fault can be identified using the diagnostics event. The event text helps you by
providing information about the fault. In addition, the corresponding symbol is displayed
before the diagnostics event.
Diagnostics event
Status symbolStatus signalEvent numberEvent text
↓↓↓
Example
A0013962 A0013958
441Curr.output 1
3-digit number
If two or more diagnostic messages are pending simultaneously, only the message with the
highest priority is shown. Additional pending diagnostic messages can be shown in
Diagnostic list submenu (→ 169).
Past diagnostic messages that are no longer pending are shown as follows:
• On the local display:
in Event logbook submenu (→ 170)
• In FieldCare:
via the "Event List /HistoROM" function.
Operating elements
Operating functions in menu, submenu
Plus key
Opens the message about the remedial measures.
A0013970
Enter key
Opens the operating menu.
A0013952
Endress+Hauser83
Page 84
Diagnostics and troubleshootingLevelflex FMP56, FMP57 PROFIBUS PA
X X XX X X XXXXX X X X X XXX
S
S
XX
20.50
X
i
S801
Menu
S
(ID:203)
S801 0d00h02m25s
1
2
4
6
3
5
Increase supply voltage
S801 Supply voltage
Diagnostic list
Diagnostics 1
Diagnostics 2
Diagnostics 3
Supply voltage
Supply voltage
12.2.2 Calling up remedial measures
25Message for remedial measures
1Diagnostic information
2Short text
3Service ID
4Diagnostic behavior with diagnostic code
5Operation time of occurrence
6Remedial measures
The user is in the diagnostic message.
1.Press ( symbol).
Diagnostic list submenu opens.
2.Select the desired diagnostic event with or and press .
The message for the remedial measures for the selected diagnostic event opens.
3.Press + simultaneously.
The message for the remedial measures closes.
The user is in the Diagnostics menu at an entry for a diagnostics event, e.g. in Diagnosticlist submenu or in Previous diagnostics.
1.Press .
The message for the remedial measures for the selected diagnostic event opens.
2.Press + simultaneously.
The message for the remedial measures closes.
A0013940-EN
84Endress+Hauser
Page 85
Levelflex FMP56, FMP57 PROFIBUS PADiagnostics and troubleshooting
12.3 Diagnostic event in the operating tool
If a diagnostic event is present in the device, the status signal appears in the top left status
in the operating tool along with the corresponding symbol for event level in accordance
with NAMUR NE 107:
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
Calling up remedial measures
1.Navigate to the Diagnostics menu.
In the Actual diagnostics parameter, the diagnostic event is shown with event
text.
2.On the right in the display range, hover the cursor over the Actual diagnostics
parameter.
A tool tip with remedial measures for the diagnostic event appears.
12.4 Diagnostic list
In the Diagnostic list submenu, up to 5 currently pending diagnostic messages can be
displayed. If more than 5 messages are pending, the messages with the highest priority are
shown on the display.
Navigation path
Diagnostics → Diagnostic list
Calling up and closing the remedial measures
1.Press .
The message for the remedial measures for the selected diagnostic event opens.
2.Press + simultaneously.
The message about the remedial measures closes.
Endress+Hauser85
Page 86
Diagnostics and troubleshootingLevelflex FMP56, FMP57 PROFIBUS PA
825Operating temperature 1. Check ambient temperature
825Operating temperatureFAlarm
921Change of reference1. Check reference configuration
936EMC interferenceCheck installation on EMCFAlarm
941Echo lostCheck parameter 'DC value'FAlarm
942In safety distance1. Check level
943In blocking distanceReduced accuracy
944Level rangeReduced accuracy
950Advanced diagnostic 1
Short textRemedy instructionsStatus
1. Restart device
incompatible
mode
value
simulation
event
output
to 2 occured
2. Contact service
2. Check device configuration
3. Up- and download new
configuration
Deactivate simulationCAlarm
Deactivate simulationCWarning
Deactivate simulation switch output CWarning
Deactivate simulationCWarning
Deactivate simulationCWarning
2. Check process temperature
2. Check pressure
3. Check sensor
2. Check safety distance
3. Reset self holding
Check level
Level at process connection
Maintain your diagnostic eventMWarning
signal
[from the
factory]
FAlarm
MWarning
SWarning
SWarning
SAlarm
SWarning
SWarning
Diagnostic
behavior
[from the
factory]
1)
1)
1)
1)Diagnostic behavior can be changed.
12.6 Event logbook
12.6.1 Event history
A chronological overview of the event messages that have occurred is provided in the
Event list submenu
3)This submenu is only available for operation via local display. In the case of operation via FieldCare, the event list can be displayed with the "Event
List / HistoROM" functionality of FieldCare.
Endress+Hauser87
3)
.
Page 88
Diagnostics and troubleshootingLevelflex FMP56, FMP57 PROFIBUS PA
Navigation path
Diagnostics → Event logbook → Event list
A maximum of 100 event messages can be displayed in chronological order.
The event history includes entries for:
• Diagnostic events
• Information events
In addition to the operation time of its occurrence, each event is also assigned a symbol
that indicates whether the event has occurred or is ended:
• Diagnostic event
–: Event has occurred
–: Event has ended
• Information event
: Event has occurred
Calling up and closing the remedial measures
1.Press .
The message for the remedial measures for the selected diagnostic event opens.
2.Press + simultaneously.
The message about the remedial measures closes.
12.6.2 Filtering the event logbook
Using the Filter options parameter, you can define which category of event messages is
displayed in the Event list submenu angezeigt werden.
Navigation path
Diagnostics → Event logbook → Filter options
Filter categories
• All
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
• Information
12.6.3 Overview of information events
Info numberInfo name
I1000--------(Device ok)
I1089Power on
I1090Configuration reset
I1091Configuration changed
I1092Trend data deleted
I1110Write protection switch changed
I1137Electronic changed
I1151History reset
I1154Reset terminal voltage min/max
I1155Reset electronic temperature
I1156Memory error trend
I1157Memory error event list
88Endress+Hauser
Page 89
Levelflex FMP56, FMP57 PROFIBUS PADiagnostics and troubleshooting
Info numberInfo name
I1185Display backup done
I1186Restore via display done
I1187Settings downloaded with display
I1188Display data cleared
I1189Backup compared
I1256Display: access status changed
I1264Safety sequence aborted
I1335Firmware changed
I1397Fieldbus: access status changed
I1398CDI: access status changed
I1512Download started
I1513Download finished
I1514Upload started
I1515Upload finished
Endress+Hauser89
Page 90
Diagnostics and troubleshootingLevelflex FMP56, FMP57 PROFIBUS PA
Operating InstructionsDescription of Parameters Technical Information
• additional languages
• HistoROM functionality
enhanced
• "Advanced Diagnostic"
function block integrated
• Improvements and
bugfixes
BA01009F/00/EN/14.14
BA01009F/00/EN/15.16
GP01001F/00/EN/13.14TI01004F/00/EN/17.14
1)
TI01004F/00/EN/20.16
The firmware version can explicitly be ordered via the product structure. In this way it
is possible to ensure compatibility of the firmware version with an existing or planned
system integration.
1)
90Endress+Hauser
Page 91
Levelflex FMP56, FMP57 PROFIBUS PAMaintenance
13 Maintenance
The measuring device requires no special maintenance.
13.1 Exterior cleaning
When exterior-cleaning the device, always use cleaning agents that do not attack the
surface of the hosuing and the seals.
Endress+Hauser91
Page 92
RepairsLevelflex FMP56, FMP57 PROFIBUS PA
14 Repairs
14.1 General information on repairs
14.1.1 Repair concept
The Endress+Hauser repair concept assumes that the devices have a modular design and
that repairs can be done by the Endress+Hauser service or specially trained customers.
Spare parts are contained in suitable kits. They contain the related replacement
instructions.
For more information on service and spare parts, contact the Service Department at
Endress+Hauser.
14.1.2 Repairs to Ex-approved devices
When carrying out repairs to Ex-approved devices, please note the following:
• Repairs to Ex-approved devices may only be carried out by trained personnel or by the
Endress+Hauser Service.
• Comply with the prevailing standards, national Ex-area regulations, safety instructions
(XA) and certificates.
• Only use original spare parts from Endress+Hauser.
• When ordering a spare part, please note the device designation on the nameplate. Only
replace parts with identical parts.
• Carry out repairs according to the instructions. On completion of repairs, carry out the
specified routine test on the device.
• Only Endress+Hauser Service may convert a certified device into a different certified
variant.
• Document all repair work and conversions.
14.1.3 Replacement of an electronics module
If an electronics module has been replaced, it is not necessary to perform a new basic setup
as the calibration parameters are stored in the HistoROM which is located in the housing.
However, after exchanging the main electronics module it may be necessary to record a
new mapping (interference echo suppression).
14.1.4 Replacement of a device
After a complete device or electronic module has been replaced, the parameters can be
downloaded into the instrument again in one of the following ways:
• Via the display module
Condition: The configuration of the old device has been saved in the display module
→ 161.
• Via FieldCare
Condition: The configuration of the old device has been saved to the computer via
FieldCare.
You can continue to measure without carrying out a new setup. Only a linearization and a
tank map (interference echo suppression) have to be recorded again.
• A few interchangeable measuring device components are identified by a spare part
nameplate. This contains information about the spare part.
• The connection compartment cover of the device contains a spare part nameplate that
includes the following information:
– A list of the most important spare parts for the measuring device, including their
ordering information.
– The URL for the W@M Device Viewer (www.endress.com/deviceviewer):
There, all spare parts for the measuring device are listed, including the order code, and
can be ordered. If available, the corresponding Installation Instructions can also be
downloaded there.
A0014979
26Example for spare part nameplate in connection compartment cover
Measuring device serial number:
• Is located on the device and spare part nameplate.
• Can be read out via the "Serial number" parameter in the "Device information"
submenu.
14.3 Return
The measuring device must be returned if it is need of repair or a factory calibration, or if
the wrong measuring device has been delivered or ordered. Legal specifications require
Endress+Hauser, as an ISO-certified company, to follow certain procedures when handling
products that are in contact with the medium.
To ensure safe, swift and professional device returns, please refer to the procedure and
conditions for returning devices provided on the Endress+Hauser website at
http://www.endress.com/support/return-material
14.4 Disposal
Observe the following notes during disposal:
• Observe valid federal/national regulations.
• Ensure proper separation and reuse of the device components.
Endress+Hauser93
Page 94
AccessoriesLevelflex FMP56, FMP57 PROFIBUS PA
222 (8.74)
298.5 (11.8)273.7 (10.8)
255.1 (10)
156 (6.14)
a
164 (6.46)
b
35°
65°
55°
15 Accessories
15.1 Device-specific accessories
15.1.1 Weather protection cover
AccessoryDescription
Weather protection cover
27Weather protection cover; Dimensions: mm (in)
a37,8 mm (1,5 in)
b54 mm (2,1 in)
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory
Enclosed", option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71162242.
A0015466
A0015472
94Endress+Hauser
Page 95
Levelflex FMP56, FMP57 PROFIBUS PAAccessories
122 (4.8)
52 (2)
86
(3.4)
70
(2.8)
140 (5.5)
158 (6.2)
175 (6.9)
AB
ø42...60
(1.65...2.36)
15.1.2 Mounting bracket for the electronics housing
AccessoryDescription
Mounting bracket for the
electronics housing
28Mounting bracket for the electronics housing; Dimensions: mm (in)
AWall mounting
BPipe mounting
For the "Sensor remote" device version (see feature 060 of the product structure), the mounting bracket is part of
the delivery. If required, it can also be ordered as an accessory (order code 71102216).
A0014793
Endress+Hauser95
Page 96
AccessoriesLevelflex FMP56, FMP57 PROFIBUS PA
1
2
3
15.1.3 Extension rod / centering HMP40
AccessoryDescription
Extension rod / centering
HMP40
• can be used for:
FMP57
• Admissible
temperature
at lower nozzle edge:
– without center
washer:
no limitation
– with center washer:
-40 to 150 °C
(-40 to 302 °F)
• Additional information:
SD01002F
1Nozzle height
2Extension rod
3Center washer
010 Approval:
AA: Non-hazardous area
MM: FM DIP Cl.II Div.1 Gr.E-G N.I., zone 21,22
PP: CSA DIP Cl.II Div.1 Gr.G + coal dust N.I.
SS: FM Cl.I, II, III Div.1 Gr.A-G N.I., zone 0,1,2,20,21,22
UU: CSA Cl.I, II, III Div.1 Gr.A-G N.I., zone 0,1,2
11: ATEX II 1G
22: ATEX II 1D
A0013597
020 Extension rod; nozzle height:
1115mm; 150-250mm / 6-10"
2215mm; 250-350mm / 10-14"
3315mm; 350-450mm / 14-18"
4415mm; 450-550mm / 18-22"
9Special version, TSP-no. to be spec.
030 Center washer:
ANot selected
BDN40 / 1-1/2", inside-d. = 40-45mm, PPS
CDN50 / 2", inside-d. = 50-57mm, PPS
DDN80 / 3", inside-d. = 80-85mm, PPS
EDN80 / 3", inside-d. = 76-78mm, PPS
GDN100 / 4", inside-d. = 100-110mm, PPS
HDN150 / 6", inside-d. = 152-164mm, PPS
JDN200 / 8", inside-d. = 210-215mm, PPS
KDN250 / 10", inside-d. = 253-269mm, PPS
YSpecial version, TSP-no. to be spec.
96Endress+Hauser
Page 97
Levelflex FMP56, FMP57 PROFIBUS PAAccessories
D
1
2
15.1.4 Mounting kit, isolated
AccessoryDescription
Mounting kit, isolated
can be used for
• FMP50
• FMP51
• FMP54
• FMP56
• FMP57
A0013586
29Scope of supply of the mounting kit:
1Insulating sleeve
2Eye-bolt
For reliably insulated fixing of the probe.
Maximum process temperature: 150 °C (300 °F)
For rope probes 4 mm (¹⁄₆ in) or 6 mm (1/4 in) with PA>steel:
• Diameter D = 20 mm (0.8 in)
• Order-No.: 52014249
For rope probes 6 mm (¹⁄₄ in) or 8 mm (1/3 in) with PA>steel:
• Diameter D = 25 mm (1 in)
• Order-No.: 52014250
Due to the risk of electrostatic charge, the insulating sleeve is not suitable for use
in hazardous areas. In these cases the fixing must be reliably grounded.
The mounting kit can also be ordered directly with the device (see the
• Material:
– Plastics PBT
– CF3M (similar to 316L/1.4404)
– Aluminum (in preparation)
• Ingress protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for the display modules:
– SD02 (push buttons)
– SD03 (touch control)
• Connection cable:
– Cable with M12 plug; supplied with the FHX50; up to 30 m (98 ft)
– Customer supplied standard cable; up to 60 m (196 ft)
• Ambient temperature: –40 to 80 °C (–40 to 176 °F)
• If the remote display is to be used, the device must be ordered in the version "Prepared for display FHX50"
(feature 030, option L or M). For the FHX50, on the other hand, the option A: "Prepared for display FHX50" has
to be selected in feature 050: "Option Measurement Device".
• If a device has not been ordered in the version "Prepared for display FHX50", but is nevertheless to be equipped
with an FHX50, it is essential to select the option B: "Not prepared for display FHX50" in feature 050: "Option
Measurement Device" of the FHX50. In this case, a retrofit kit, needed to prepare the device for the remote
display, is supplied together with the FHX50.
For transmitters with approval, application of the FHX50 may be restricted. A device may only be retrofitted with
the FHX50 if option L or M ("Prepared for FHX50") is quoted under Basic specifications, position 4 "Display,
operation" in the associated Safety Instructions (XA).
In addition to this, observe the Safety Instructions (XA) of the FHX50.
Do not retrofit transmitters with:
• approval for use in areas with combustible dusts (Dust-Ex approval)
• type of protection Ex nA
For details refer to the document SD01007F.
98Endress+Hauser
Page 99
Levelflex FMP56, FMP57 PROFIBUS PAAccessories
15.1.6 Overvoltage protection
AccessoryDescription
Overvoltage protection for
2-wire-devices
OVP10 (1 channel)
OVP20 (2 channel)
A0021734
Technical data
• Resistance per channel: 2 * 0.5 Ω
• Threshold DC voltage: 400 to 700 V
• Threshold impulse voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal arrest impulse voltage (8/20 μs): 10 kA
• Suited for wire cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
Ordering with device
The overvoltage protection module is preferably ordered with the device. See product structure, feature 610
"Accessory mounted", option NA "Overvoltage protection". Separate ordering of the module is only necessary if a
device is to retrofitted with the overvoltage protection.
Order code for retrofitting
• For 1-channel devices (feature 020, option A)
OVP10: 71128617
• For 2-channel devices (feature 020, option B, C, E or G)
OVP20 : 71128619
Hosuing lid for retrofitting
In order to keep the necessary safety distances, the housing lid needs to be replaced if the device is retrofitted with
the overvoltage protection. Depending on the housing type, the order code of the suitable lid is as follows:
• GT18 housing: Lid 71185516
• GT19 housing: Lid 71185518
• GT20 housing: Lid 71185516
Restrictions for retrofitting
Depending on the approval of the transmitter the usage of the OVP module may be restricted. A device may only be
retrofitted with an OVP module if the option NA (overvoltage protection) is quoted unter Optional Specifications in
the Safety Instructions (XA) pertaining to the device.
For details refer to SD01090F.
max
Endress+Hauser99
Page 100
AccessoriesLevelflex FMP56, FMP57 PROFIBUS PA
15.2 Communication-specific accessories
AccessoryDescription
Commubox FXA291Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser
Common Data Interface) to the USB interface of a computer.
Order code: 51516983
For details refer to Technical Information TI00405C
Helps to configure and maintain all field devices of your plant. By supplying status
information it also supports the diagnosis of the devices.
For details refer to Operating Instructions BA00027S and BA00059S.
15.4 System components
AccessoryDescription
Graphic Data Manager
Memograph M
The graphic data manager Memograph M provides information on all the relevant
process variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on an SD card or USB stick.
For details refer to Technical Information TI00133R and Operating
Instructions BA00247R
100Endress+Hauser
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.