• Installation, commissioning, operation and maintenance of the measuring system may
be carried out only by specially trained technical personnel.
• The technical personnel must be authorized by the plant operator to carry out the
specified activities.
• The electrical connection may be performed only by an electrical technician.
• The technical personnel must have read and understood these Operating Instructions
and must follow the instructions contained therein.
• Faults at the measuring point may only be rectified by authorized and specially trained
personnel.
Repairs not described in the Operating Instructions provided must be carried out only
directly at the manufacturer's site or by the service organization.
2.2 Designated use
2.2.1 Non-hazardous atmosphere
Liquiline CM44x is a multichannel controller for connecting digital sensors with
Memosens technology in non-hazardous environments.
The device is designed for use in the following applications:
• Water and wastewater
• Power stations
• Chemical industry
• Other industrial applications
2.2.2 Hazardous environment in accordance with cCSAus Class I Div.
2
Please pay attention to the control drawing and specified operating conditions in the
‣
appendix of this manual and follow the instructions.
2.2.3 Non-designated use
Use of the device for any purpose other than that described, poses a threat to the safety of
people and of the entire measuring system and is therefore not permitted.
The manufacturer is not liable for damage caused by improper or non-designated use.
2.3 Workplace safety
As the user, you are responsible for complying with the following safety conditions:
• Installation guidelines
• Local standards and regulations
• Regulations for explosion protection
Electromagnetic compatibility
• The product has been tested for electromagnetic compatibility in accordance with the
applicable international standards for industrial applications.
• The electromagnetic compatibility indicated applies only to a product that has been
connected in accordance with these Operating Instructions.
2.Ensure that electrical cables and hose connections are undamaged.
3.Do not operate damaged products, and protect them against unintentional operation.
4.Label damaged products as defective.
During operation:
If faults cannot be rectified:
‣
products must be taken out of service and protected against unintentional operation.
CAUTION
L
Cleaning not switched off during calibration or maintenance activities
Risk of injury due to medium or cleaning agent!
If a cleaning system is connected, switch it off before removing a sensor from the
‣
medium.
If you wish to check the cleaning function and have therefore not switched off the
‣
cleaning system, wear protective clothing, goggles and gloves or take other appropriate
measures.
2.5 Product safety
2.5.1 State of the art
The product is designed to meet state-of-the-art safety requirements, has been tested, and
left the factory in a condition in which it is safe to operate. The relevant regulations and
international standards have been observed.
2.5.2 IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
8Endress+Hauser
Liquiline CM442/CM444/CM448Device description
12
3
4
5
6
2
3
45
6
789
10
11
1
3 Device description
3.1 Housing closed
1Display
2Weather protection cover (optional)
3Navigator
4Sensor cable or current output cable
5Power supply cable
6Soft keys, assignment depends on menu
A0025813
1Mounted on a post
3.2 Housing open
A0039719
2Example of a four-channel device with an open display cover (without wiring)
1Display cable7Threaded bolt for protective ground connection
2Basic module8Extension power unit with internal cable
3Extension modules (optional)9M12 connectors for sensor connection
(optional)
4Shock protection, dummy cover and end cover10Distributor terminals for user-defined use
5Extension backplane11Storage slot for SD card
6Cable mounting rail
1)
Endress+Hauser9
1)Example: you want to loop the signal from the alarm relay to a siren and a lamp. The terminals on the
alarm relay only accommodate one cable. Route the signal from the alarm relay to a terminal on the
distributor block. The block's terminals are all interconnected. You therefore have 3 additional terminals on
this block from where you can carry the signal forward to the consumer (siren, lamp etc.). The signal can
be multiplied in this way.
Device descriptionLiquiline CM442/CM444/CM448
BASE2-E
Slots
1
2
1
2
1
2
1
2
Ports
2DS2DS2DS2AI2AO4R
1
2
Sensor 1
Sensor 1
Sensor 1
Sensor 2
Sensor 2
Sensor 2
1
2
1
2
1
2
1
2
3
4
3.3 Slot and port assignment
3Slot and port assignment of the hardware modules
• Inputs are assigned to measuring channels in the
ascending order of the slots and ports.
Adjacent example:
"CH1: 1:1 pH glass" means:
Channel 1 (CH1) is slot 1 (basic module) : Port 1 (input
1), pH glass sensor
• Outputs and relays are named according to their
function, e.g. "current output", and are displayed in
ascending order with the slot and port numbers
4Slot and port assignment on the
display
10Endress+Hauser
Liquiline CM442/CM444/CM448Device description
12
3
4
43
42 41
Relay 1
Relay 2
Relay 3
Relay 4
Slot
Slot 4
Port 1
Pin 41
BASE2-E2DS
4R
2AO
43
42414342 41
43
42 41
43
42 41
3.4 Terminal diagram
The unique terminal name is derived from:
Slot no. : Port no. : Terminal
Example, NO contact of a relay
Device with 4 inputs for digital sensors, 4 current outputs and 4 relays
• Base module BASE2-E (contains 2 sensor inputs, 2 current outputs)
• 2DS module (2 sensor inputs)
• 2AO module (2 current outputs)
• 4R module (4 relays)
5Creating a terminal diagram using the example of the NO contact (terminal 41) of a relay
A0039621
Endress+Hauser11
Incoming acceptance and product identificationLiquiline CM442/CM444/CM448
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
1.Verify that the packaging is undamaged.
Notify the supplier of any damage to the packaging.
Keep the damaged packaging until the issue has been resolved.
2.Verify that the contents are undamaged.
Notify the supplier of any damage to the delivery contents.
Keep the damaged goods until the issue has been resolved.
3.Check that the delivery is complete and nothing is missing.
Compare the shipping documents with your order.
4.Pack the product for storage and transportation in such a way that it is protected
against impact and moisture.
The original packaging offers the best protection.
Make sure to comply with the permitted ambient conditions.
If you have any questions, please contact your supplier or your local Sales Center.
4.2 Product identification
4.2.1 Nameplate
The nameplate provides you with the following information on your device:
• Manufacturer identification
• Order code
• Extended order code
• Serial number
• Firmware version
• Ambient and process conditions
• Input and output values
• Activation codes
• Safety information and warnings
Compare the information on the nameplate with the order.
‣
4.2.2 Product identification
Product page
www.endress.com/cm442
www.endress.com/cm444
www.endress.com/cm448
Interpreting the order code
The order code and serial number of your product can be found in the following locations:
• On the nameplate
• In the delivery papers
Obtaining information on the product
1.Go to www.endress.com.
12Endress+Hauser
Liquiline CM442/CM444/CM448Incoming acceptance and product identification
2.Call up the site search (magnifying glass).
3.Enter a valid serial number.
4.Search.
The product structure is displayed in a popup window.
5.Click on the product image in the popup window.
A new window (Device Viewer) opens. All of the information relating to your
device is displayed in this window as well as the product documentation.
Manufacturer's address
Endress+Hauser Conducta GmbH+Co. KG
Dieselstraße 24
D-70839 Gerlingen
4.3 Scope of delivery
The scope of delivery comprises:
• 1 multichannel controller in the version ordered
• 1 mounting plate
• 1 wiring label (attached at the factory to the inside of the display cover)
• 1 printed copy of the Brief Operating Instructions in the language ordered
If you have any queries:
‣
Please contact your supplier or local sales center.
4.4 Certificates and approvals
4.4.1
The product meets the requirements of the harmonized European standards. As such, it
complies with the legal specifications of the EU directives. The manufacturer confirms
successful testing of the product by affixing to it the mark.
4.4.2 EAC
The product has been certified according to guidelines TP TC 004/2011 and TP TC
020/2011 which apply in the European Economic Area (EEA). The EAC conformity mark
is affixed to the product.
4.4.3 cCSAus
The device has been certified with regard to its electrical safety and for NI Class I Div. 2
cCSAus explosion-proof environments. It meets the requirements in accordance with:
• CLASS 2252 06 - Process Control Equipment
• CLASS 2252 86 - Process Control Equipment - Certified to US Standards
• CLASS 2258 03 - Process Control Equipment - Intrinsically Safe and Non-incendive
Systems - For Hazardous Locations
• CLASS 2258 83 - Process Control Equipment - Intrinsically Safe and Non-incendive
Systems - For Hazardous Locations - Certified to US Standards
• FM3600
• FM3611
• FM3810
• UL50E
• IEC 60529
• CAN/CSA-C22.2 No. 0
mark
Endress+Hauser13
Incoming acceptance and product identificationLiquiline CM442/CM444/CM448
• CAN/CSA C22.2 No. 94
• CSA Std. C22.2 No. 213
• CAN/CSA-C22.2 No. 61010-1
• CAN/CSA-C22.2 No. 60529
• UL/ANSI/ISA 61010-1
• ANSI - ISA 12 12 01
4.4.4 MCERTS
CM442 only
The device has been assessed by Sira Certification Service and complies with "MCERTS
Performance Standards for Continuous Water Monitoring Equipment, Part 2: online
analysers, Version 3.1, dated August 2010"; Certificate No.: Sira MC140246/01.
14Endress+Hauser
Liquiline CM442/CM444/CM448Installation
H5678I
GF
E
D
C
A
1234B
162 (6.38)
14 (0.55)
Ø4 (0.16)
Ø9 (0.35)
199 (7.38)128 (5.04)
237 (9.33)
194 (7.64)
76 (2.99)
95 (3.74)
80 (3.15)
190 (7.48)
3 (0.12)
4 x 6.5 (0.26)
170 (6.69)
125 (4.92)
5 Installation
5.1 Installation conditions
5.1.1 Dimensions
Endress+Hauser15
6Dimensions of field housing in mm (inch)
5.1.2 Mounting plate
7Mounting plate, dimensions in mm (in)
A0012396
A0012426
InstallationLiquiline CM442/CM444/CM448
320 (12.6)
270 (10.6)
300 (11.8)
80 (3.15)
170 (6.69)
170 (6.69)
80 (3.15)
8 x Ø 7 (0.28)
1
2
3
4
56
7
8
5.1.3 Protective cover
NOTICE
Effect of climatic conditions (rain, snow, direct sunlight etc.)
Impaired operation to complete transmitter failure are possible!
Always use the weather protection cover (accessory) when installing the device
‣
outdoors.
A0012428
8Dimensions in mm (in)
5.2 Mounting the measuring device
5.2.1 Post mounting
You require the post mounting kit (optional) to mount the unit on a pipe, post or
railing (square or circular, clamping range 20 to 61 mm (0.79 to 2.40")).
2.Slide the device downwards in the guide on the mounting rail until it clicks into place.
InstallationLiquiline CM442/CM444/CM448
≥ 340 (13.4)
≥
150 (5.91)
1
3
4
2
5.2.3 Wall mounting
A0027798
16Wall mounting
A0012686
15Installation clearance in mm (in)
1)
The size of the drill holes depends on the wall plugs used. The wall plugs and screws must be provided by the
customer.
1Wall
2
4 drill holes
3Mounting plate
4Screws Ø 6 mm (not part of scope of supply)
1)
17Wall mounting
A0027799
18Attach the device and click it into place
A0027797
1.Place the device on the mounting plate.
2.Slide the device downwards in the guide on the mounting rail until it clicks into place.
5.2.4 Disassembly (for conversion, cleaning etc.)
NOTICE
The device can be damaged if dropped
When pushing the housing out of the holder, secure the housing to prevent it from
‣
falling. If possible, ask a second person to help you.
18Endress+Hauser
Liquiline CM442/CM444/CM448Installation
A0025890
19Disassembling
20Disassembling
1.Hold down the latch.
2.Push up the device to remove it from the holder.
3.Remove the device towards the front.
5.3 Post-installation check
1.After installation, check the transmitter for damage.
2.Check whether the transmitter is protected against precipitation and direct sunlight
(e.g. by the weather protection cover).
A0025891
Endress+Hauser19
Electrical connectionLiquiline CM442/CM444/CM448
1
3
2
USB
31
32
250 ... 500 Ω
FXA291
Master class 1
(PLC, DCS)
TT
Ethernet
PROFIBUS DP
(RS485)
Master class 2 (FieldCare, PDM)
6 Electrical connection
6.1 Connection conditions
6.1.1 Via HART (e.g. via HART modem and FieldCare)
21HART using modem
1Device module Base2-L, -H or -E: current output 1 with HART
2
HART modem for connection to PC, e.g. Commubox FXA191 (RS232) or FXA195 1) (USB)
3HART handheld terminal
1)
Switch position "on" (substitutes the resistor)
6.1.2 Via PROFIBUS DP
A0039620
22PROFIBUS DP
TTerminating resistor
20Endress+Hauser
A0039617
Liquiline CM442/CM444/CM448Electrical connection
FXA291
Ethernet
Modbus Master / Gateway
TT
Modbus RS485
(RTU, ASCII)
FieldCare/
Webbrowser
FXA291
Ethernet
Ethernet client
6.1.3 Via Modbus RS485
A0039615
23Modbus RS485
TTerminating resistor
6.1.4 Via Ethernet: web server/Modbus TCP/PROFINET/
EtherNet/IP
A0039616
24Modbus TCP or EtherNet/IP or PROFINET
6.2 Connecting the measuring device
WARNING
L
Device is live!
Incorrect connection may result in injury or death!
The electrical connection may be performed only by an electrical technician.
‣
The electrical technician must have read and understood these Operating Instructions
‣
and must follow the instructions contained therein.
Prior to commencing connection work, ensure that no voltage is present on any cable.
‣
Endress+Hauser21
Electrical connectionLiquiline CM442/CM444/CM448
1.
2.
3.
4.
≤180°
NOTICE
The device does not have a power switch!
Provide a protected circuit breaker in the vicinity of the device at the place of
‣
installation.
The circuit breaker must be a switch or power switch, and must be labeled as the circuit
‣
breaker for the device.
At the supply point, the power supply must be isolated from dangerous live cables by
‣
double or reinforced insulation in the case of devices with a 24 V supply voltage.
6.2.1 Opening the housing
NOTICE
Pointed or sharp tools
If unsuitable tools are used, they can scratch the housing or damage the seal, and thus
have a negative impact on the leak-tightness of the housing!
Do not use pointed or sharp objects,e.g. knives, to open the housing.
‣
Only use a suitable Phillips screwdriver.
‣
25Releasing housing screws in a diagonally
opposite sequence with Phillips screwdriver
26Opening display cover, max. opening angle
180˚ (depends on installation position)
1.Release the housing screws on a step-by-step basis. Start with any screw of your
choice. Then release the screw diagonally opposite this screw etc.
2.To close the housing: tighten the screws in a similar step-by-step, diagonally opposite
sequence.
22Endress+Hauser
Liquiline CM442/CM444/CM448Electrical connection
1324
1
2
3
4
6.2.2 Cable mounting rail
A0025171
27Cable mounting rail and associated function
1Cable mounting rail3Additional threaded bolts for ground connections
2Threaded bolt (protective ground connection,
central grounding point)
4Cable clamps (fixing and grounding the sensor
cables)
6.2.3 Connecting the cable shield
If possible, only use terminated original cables. The sensor, fieldbus and Ethernet
cables must be shielded cables.
Cable sample (does not necessarily correspond to the original cable supplied)
28Terminated cable
1Outer shield (exposed)
2Cable cores with ferrules
3Cable sheath (insulation)
1)Please note the instructions in the "Ensuring the degree of protection" section (→ 38)
29Insert the cable
4Grounding clip
30Tighten screw (2 Nm)
The cable shield is grounded using
the grounding clamp.
1)
1.Release a suitable cable gland on the bottom of the housing and remove the dummy
plug.
2.Making sure the gland is facing the right direction, thread the gland onto the cable
end and pull the cable through the entry and into the housing.
3.Route the cable in the housing in such a way that the exposed cable shield fits into
one of the cable clamps and the cable cores can be easily routed as far as the
connection plug on the electronics module.
4.Screw the cable clamp on.
5.Clamp the cable into place.
6.Then tighten the screw of the cable clamp again.
7.Connect cable cores as per the wiring diagram.
8.Tighten the cable gland from outside.
Endress+Hauser23
Electrical connectionLiquiline CM442/CM444/CM448
6.2.4 Cable terminals
Plug-in terminals for Memosens and PROFIBUS/RS485 connections
Insert the cable until the limit
Press the screwdriver against
‣
the clip (opens the terminal).
After connection, make sure that every cable end is securely in place. Terminated
cable ends, in particular, tend to come loose easily if they have not been correctly
inserted as far as the limit stop.
‣
stop.
Remove the screwdriver (closes
‣
the terminal).
All other plug-in terminals
Press the screwdriver against
‣
the clip (opens the terminal).
Insert the cable until the limit
‣
stop.
Remove the screwdriver (closes
‣
the terminal).
24Endress+Hauser
Liquiline CM442/CM444/CM448Electrical connection
N/- L/+
PE
85
85
86
86
SD
Display
Sensor supply
+
+
–
Service
PK
GY
PK
GY
1
2
–
L
N
*
Power
L/+
N/–
PE
+
–
A
B
41
43
42
Alarm
31
31
32
32
0/4 ... 20 mA
+
+
–
–
HART
+
–
A
B
Sensor 2
Ethernet
87
88
97
98
87
88
97
98
BN
WH
GN
YE
BN
WH
GN
YE
Sensor 1
1
2
12
3
4
5
6.2.5 Connecting the supply voltage for the CM442
A0039627
31Connecting power supply on the BASE2-H or -
L
HPower unit 100 to 230 VAC
LPower unit 24 VAC or 24 VDC
32Overall wiring diagram for BASE2-H or -L
A0039625
Connecting the supply voltage
1.Route the power supply cable into the housing through the suitable cable entry.
2.Step 2 applies only to the 100 to 230 V AC power unit.
Connect the protective ground of the power unit to the threaded bolt specially
provided on the cable mounting rail.
3.Protective ground or grounding provided by customer (absolutely essential for 24 Vpower unit, additionally recommended for 100 to 230 V AC power unit): Provide
a ground cable (min. 0.75 mm2 (corresponding to 18 AWG))1! Guide the ground
cable also through the cable entry and connect it to the threaded bolt on the cable
mounting rail.
4.Connect the cable cores L and N (100 to 230 V AC) or + and ‐ (24 V DC) to the plugin terminals on the power unit in accordance with the wiring diagram.
1Protective ground of power unit
2Serrated washer and nut
3Protective ground / ground cable, provided by
1)For a fuse with a rating of 10 A. For a fuse with a rating of 16 A, the protective ground / ground cable
must have a cross-sectional area of at least 1.5 mm2 ( 14 AWG).
Endress+Hauser25
Electrical connectionLiquiline CM442/CM444/CM448
L+ N- PE
A
B
85
85
86
86
SD
Display
Sensor supply
+
+
–
Service
PK
GY
PK
GY
1
2
–
+
–
A
B
41
43
42
Alarm
31
31
32
32
0/4 ... 20 mA
+
+
–
–
HART
+
–
A
B
Sensor 2
Ethernet
87
88
97
98
87
88
97
98
BN
WH
GN
YE
BN
WH
GN
YE
Sensor 1
1
2
L/+
N/–
*
Power
L/+
N/–
PE
Power
(internal)
B
NOTICE
Protective ground/ground cable with end sleeve or open cable lug
The cable can become loose. Loss of the protective function!
To connect the protective ground or ground cable to the threaded bolt, only use a cable
‣
with a closed cable lug as per DIN 46211, 46225, form A.
Never connect the protective ground or ground cable to the threaded bolt with an end
‣
sleeve or an open cable lug!
6.2.6 Connecting the supply voltage for the CM444 and the CM448
A0039626
34Power supply connection on the BASE2-E
AInternal power supply cable
BExtension power unit
35Overall wiring diagram for BASE2-E and
extension power unit (B)
Connecting the supply voltage
1.Route the power supply cable into the housing through the suitable cable entry.
2.Step 2 applies only to the 100 to 230 V AC power unit.
Connect the protective ground of the power unit to the threaded bolt specially
provided on the cable mounting rail.
3.Protective ground or grounding provided by customer (absolutely essential for 24 Vpower unit, additionally recommended for 100 to 230 V AC power unit): Provide
a ground cable (min. 0.75 mm2 (corresponding to 18 AWG))1! Guide the ground
26Endress+Hauser
cable also through the cable entry and connect it to the threaded bolt on the cable
mounting rail.
4.Connect the cable cores L and N (100 to 230 V AC) or + and ‐ (24 V DC) to the plugin terminals on the power unit in accordance with the wiring diagram.
A0039624
Liquiline CM442/CM444/CM448Electrical connection
12
3
4
5
1Protective ground of power unit
2Serrated washer and nut
3Protective ground / ground cable, provided by
1)For a fuse with a rating of 10 A. For a fuse with a rating of 16 A, the protective ground / ground cable
must have a cross-sectional area of at least 1.5 mm2 ( 14 AWG).
1)
NOTICE
Protective ground/ground cable with end sleeve or open cable lug
The cable can become loose. Loss of the protective function!
To connect the protective ground or ground cable to the threaded bolt, only use a cable
‣
with a closed cable lug as per DIN 46211, 46225, form A.
Never connect the protective ground or ground cable to the threaded bolt with an end
‣
sleeve or an open cable lug!
6.3 Connecting the sensors
6.3.1 Sensor types with Memosens protocol
Sensors with Memosens protocol
Sensor typesSensor cableSensors
Digital sensors without
additional internal power
supply
Digital sensors with
additional internal power
supply
With plug-in
connection and
inductive signal
transmission
Fixed cableConductivity sensors with inductive measurement of
Fixed cable• Turbidity sensors
• pH sensors
• ORP sensors
• Combined sensors
• Oxygen sensors (amperometric and optical)
• Conductivity sensors with conductive measurement
of conductivity
• Chlorine sensors (disinfection)
conductivity
• Sensors for interface measurement
• Sensors for measuring the spectral absorption
coefficient (SAC)
• Nitrate sensors
• Optical oxygen sensors
• Ion-sensitive sensors
Endress+Hauser27
Electrical connectionLiquiline CM442/CM444/CM448
The following rule applies if connecting CUS71D sensors:
• CM442
• Only one CUS71D is possible; an additional sensor is not permitted.
• The second sensor input may also not be used for another type of sensor.
• CM444
No restrictions. All the sensor inputs can be used as required.
• CM448
• If a CUS71D is connected, the number of sensor inputs that can be used is limited to a
maximum of 4.
• Of these, all 4 inputs can be used for CUS71D sensors.
• Every combination of CUS71D and other sensors is possible, provided that the total
number of connected sensors does not exceed 4.
6.3.2 Connecting the sensors
Types of connection
• Direct connection of the sensor cable to the terminal connector of the sensor module
2DS or of the base module-L, -H or -E (→ 37 ff.)
• Optional: Sensor cable plug connected to the M12 sensor socket on the underside of the
device
With this type of connection, the device is already wired at the factory (→ 40).
1.Sensor cable connected directly
Connect the sensor cable to the Memosens terminal connector of the sensor module
2DS or of the module Base2-L, -H or -E.
2.When connecting via M12 connector
Connect the sensor connector to an M12 sensor socket which has been previously
installed or is supplied on delivery.
28Endress+Hauser
Liquiline CM442/CM444/CM448Electrical connection
98 97 88 87
86 85 86 85
BN
WH
GN
YE
Sensor
98 97 88 87
86 85 86 85
GN
YE
Sensor
PK
GY
85 86
85
2DS
1
2
86
97 88 8798
97 88 8798
Sensor 1
Sensor 2
PK
GY
GN
YE
BN
WH
GN
YE
Sensor
Sensor
Sensor cable connected directly
37sensors without additional supply voltage
39sensors with and without additional supply
voltage at sensor module 2DS
A0039629
38sensors with additional supply voltage
A0033206
A0039622
Endress+Hauser29
Electrical connectionLiquiline CM442/CM444/CM448
85 86
85
1
2
86
97 88 8798
Sensor 1
PK
GY
GN
YE
BN
WH
1
6
4
1
NC
2
3
5
7
4
6
2
NC
1
7
5
3
connection via M12 plug-in connection
Device versions with a pre-installed
M12 socket are ready-wired upon
delivery.
Version without a pre-installed M12
socket
1.Insert an M12 socket (accessory)
into a suitable opening in the
base of the housing.
2.Connect the cable to a
Memosens terminal as per the
wiring diagram.
Connecting the sensor
Plug the connector of the sensor
‣
cable (→ 40item 1) directly into
the M12 socket.
Please note the following:
• The internal device wiring is always
the same regardless of what kind of
sensor you connect to the M12
socket (plug&play).
• The signal or power supply cables are
assigned in the sensor head in such a
way that the PK and GY power supply
cables are either used (e.g. optical
sensors) or not (e.g. pH or ORP
sensors).
6.4 Connecting additional inputs, outputs or relays
WARNING
L
Module not covered
No shock protection. Danger of electric shock!
Change or extend the hardware: always fill the slots from left to right. Do not leave any
‣
gaps.
If all of the slots are not occupied: always insert a dummy cover or end cover in the slot
‣
to the right of the last module(→ 2, 9). This ensures that the unit is shockprotected.
Always ensure shock protection is guaranteed particularly in the case of relay modules
‣
(2R, 4R, AOR).
If additional shields are required, connect them with PE centrally in the control cabinet
‣
via terminal blocks supplied by the customer.
30Endress+Hauser
Loading...
+ 136 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.