Notes on printingAll descriptions, technical details and illustrations refer to the version of the gen-
E136457 / i03
This documentation and parts thereof are subject to copyright. Any use or modification beyond the restrictions of the Copyright Act is forbidden and subject to
penalty without the consent of ENDRESS Elektrogerätebau GmbH.
This applies in particular to copies, translations, microfilming, as well as storage
and processing in electronic systems.
erator for printing.
We reserve the right to make modifications in terms of ongoing technical development. This operating manual does not include technical modifications that occurred after printing.
The colours in this operating manual do not always comply completely with the
actual designs due to technical printing reasons.
Tab. 8-2 Operating display on the control module.49
Tab. 13-1 Troubleshooting.72
Tab. 14-1 Power generator technical data.73
5
Page 6
About this manual
2About this manual
We would like to explain to you the safe and correct use of your generator in the
best possible way through this operating manual. To do this we have oriented
ourselves to the new European standard DIN EN 82079-1 for preparing the user
manuals.
It is absolutely essential for safe and appropriate use that you read through this
manual very carefully and understand it before using the device for the first time.
Your observance of it creates the foundation for,
•avoiding dangers for yourself and others,
•reducing repair costs and downtimes as well as
•increasing the reliability and service life of the generator.
Not only this manual but also the laws, regulations, guidelines, and standards applicable in the country of use must be observed.
This document only describes the safe operation of the generator when used as
a complete unit. The following also includes detailed technical operating instructions that are binding with regard to using the device's specific components.
This documentation and also the product described in it are subject to a continuous improvement process. In doing this we ensure that the full product is compliant with the current safety requirements and the current state-of-the-art. The
respective most up to date language version of the operating manual and the
original operating manual can be found on our website
www.endressparts.com
2.1Constituent parts of the documentation
Apart from this operating manual, the following documents are part of your device’s complete documentation:
•Operating and maintenance manual for the engine (FPT-Iveco)
•Documentation of the electrical generator (MECC ALTE company, on CDROM)
•POWERLOCK BOX operating and maintenance manual (optional)
NOTICE!
The complete documentation is an integral part of the device and you must
adhere to it.
► All of the integral parts of the documentation must always be accessible to
the operating personnel and they should be kept with the device.
2.2Using this operating manual
In order to increase the legibility, comprehensibility and transparency of
the document, certain information is highlighted or identified according a
uniform system. The following particularly belong in this category:
6
Page 7
Examples:
About this manual
signs warning about dangers to life and limb
Safety and warning notices are necessary at all locations where there is potential
danger from the device which cannot be eliminated by design or operational
measures. We restricted ourselves to the permitted minimum in order to place
the required distinctive warning notices at the correct point in time without impairing the legibility and comprehensibility of the operating manual. This is according
to the regulations contained in the international standard DIN ISO 3864 describes a fixed rule for all safety and warning notices, as shown in the following
example.
DANGER!
Electrical voltage
Risk of suffering potentially deadly electrocution by touching live parts
► Only use undamaged connecting lines
► Avoid all damp / wetness when connecting consumers
► Never operate the power generator with an opened control panel
The standard mentioned classifies the safety risks according to different risk potentials. To understand and avoid dangers to one’s health and even life, please
be sure to read the explanations given in Chapter 4.1 .
Safety symbols
These warning notices are usually used in a safety symbol which also emphasises the type of danger; see next example. A list of the safety symbols used in this
operating manual can be found in Chapter Fig. 3-1 . The safety symbols never
stand alone.
Notices on avoidance of damage to the device
According to DIN ISO 3864, notices which warn against false operation and possible damage to the device or to the equipment used should be clearly distinguishable from previously named warning notices in as far there is no danger to
health. An example of such a notice can be seen here:
NOTICE!
Use of wrong or outdated fuel damages or destroys the engine.
► Only use released diesel fuel.
► Observe the shelf life of the fuel according to the supplier.
► Observe the Operating manual from the engine manufacturer
Symbols and formattings in the text
In order to increase the legibility, comprehensibility and transparency of the document, various information and activities are awarded uniformly repeating bullets
or formattings. The following example shows presentation of a sequence of actions with established work steps:
Example: Prerequisites which must be fulfilled before starting any sequence of actions
1. Action steps according to a fixed sequence.
2. The action steps must be fully completed.
3. The sequence must be observed.
7
Page 8
About this manual
Results of the action which should be achieved after performing the sequence of
action.
Additional notices for operation or for function of a unit are marked with the
adjacent symbol.
NOTICE!
The adjacent symbol is situated anywhere where the supplier documentation must be read and observed and refers to,
► appropriate information,
►tasks or
► action steps.
References to details and components in figures are made with blue bordered
position numbers in the text such as the example of CE signs on the type plate
demonstrates, see Fig. 3-1 .
8
Page 9
Product identification
3Product identification
3.1Welcome to ENDRESS!
We are pleased that you have made the decision to purchase a ENDRESS
power generator. You have purchased a high-performance product into
which we have embodied decades of our experience and have integrated
many functions oriented on daily use. Through careful selection of high
quality components and materials in combination with the proverbial Swabian engineering performance you have in your possession a device which
will operate reliably for many years, also under the hardest of operating
conditions.
3.2Your product
Customer serviceIn order to precisely identify your device there is a type plate attached to the Gen-
erators (see Fig. 3-1 ), which includes details about the device designation and
"S/N" serial number. If you have any questions about device details, functions or
notices concerning operation, please contact our
Customer service: Tel. +49 (0)7123 9737-44
Email: service@endress-stromerzeuger.de
You will find competent contact persons there, also concerning original spare
parts and wear parts. (see also Chapter 15 )
Type plateThe type plate shown below is a representation of the adhesive label placed on
the device. Please be prepared, when contacting our service team, to assist us
in exactly identifying your device. Refer to your generator's operating instructions
for further information about finding the type plate.
Fig. 3-1 Example of a type plate
3.2.1A device description and intended use
As part of network backup, the power generator creates electricity that can be
used in alternating operation as an “on-site operation” OR as a “building supply”
(IT-TN version).
Your power generator creates electricity for the “on-site operation” mode as part
of a network backup operation, through which you can supply a mobile distribution system with electricity. This enables mobile use of commercially available
electrical devices with single-phase 230 V AC / 50 Hz or three-phase 400V AC /
50 Hz (depending on the equipment being used).
9
Page 10
Product identification
Your power generator has been designed for manual or automatic operation (remote start) with one or more electrical consumers. To protect against electric
shock (i.e. current flowing through your body), automatic switch-off according to
DIN VDE 0100-551: 2017-02 is used as the protective separation measure. The
protective conductor system from the attached consumers will take over the
earthing function. The terminal strip (Fig. 6-4 ) is used for connecting a suitable
earth (e.g. an earthing stake). Proper is needed and it must be done by a qualified electrician.
In “building supply” mode (see Chapter 8.2 , the power generator serves as an
emergency power supply for a stationary system through a flexible cable connection. For this, there is a separate CEE 400 V / 50 Hz socket with white colour
marking.
Your generator consists of an AC generator driven by a combustion engine that
is bolted onto it. This unit is mounted elastically inside a closed, sound-insulated
housing, and vibration dampers are used to ensure low vibration.
The unit generates AC (three-phase) current with a nominal voltage of 400 V at
50 Hz. More detailed technical data can be found in Chapter 14 . An integrated
voltage regulator ensures that the stability of the generated voltage is within the
nominal rotational speed range. Power is taken through a spray-water-protected
Schuko socket with nominal voltage of 230 V / 50 Hz 1~ or CEE sockets for 230
V / 50 Hz / 1~ or 400 V / 50 Hz / 3~ (see Fig. 6-4 ).
The generator is only to be used outdoors within the indicated voltage, output,
and nominal RPM ranges (see type plate).
The power generator must never be used for direct feed into other power distribution systems (e.g. public power supply) or be used with other power generation
systems (e.g. other power generators).
The generator is not to be used in explosion-prone environments.
The generator is not to be used in environments where there is a risk of fire.
The generator must be operated according to the specifications in the technical
documentation.
Every inappropriate use or all activities on the generator that are not described
in this manual is prohibited misuse beyond the manufacturer’s legally defined
limits of liability.
10
3.2.2Foreseeable misuse
Apart from the description of appropriate use, the lawmaker also requires
concrete references to the results of “reasonably foreseeable misuse“. In
a case of incorrect use or inappropriate handling of the generator the manufacturer's EU Declaration of Conformity, and automatically thereby also
the operating licence, are nullified. For products with a manufacturer’s warranty the manufacturer will reject any claims made under warranty for da mages which were caused by misuse and its direct as well as indirect
consequences.
In particular unauthorised misapplications include:
•operation of the generator takes place without valid checks for
–electrical safety
–checking that the stipulated servicing and maintenance work has been
done
•operation of the generator taking place without the protective equipment installed by the manufacturer
•constructional or electrical modifications were made to the generator
Page 11
Product identification
•software was modified or changes were made to the generator's factory settings
•use of the generator by inadequately instructed operating personnel
Furthermore at all costs avoid the following Misuses:
•Never refuel the generator’s own tank when the engine is running. The vibrations and strong exhaust streams during operation can lead to fuel spillage.
This leads to an increased risk of explosion and fire and therefore danger to
operating personnel, the environment and the device.
•Never refuel the generator’s own tank when it is hot. Overflowing fuel and exhaust fuel vapours can ignite on hot parts of the device.
•Never open the generator’s tank cover whilst it is running or if it is hot. Overflowing hot fuel and escaping fuel vapours can ignite on the device’s hot
parts.
•The generator is never to be connected up to another energy distribution system (e.g. public power supply) or to other power generating systems (e.g.
other generators, solar plants, etc.). To start with this is usually not permitted
by . In both cases this will inevitably lead to severe damage and possibly also
severe injury.
•Never place the generator in explosion-prone environments. The individual
components of the generator are not designed to be EX-protected.
•Never operate the generator in rooms, narrow pits or vehicles. The combustion exhaust gases contain poisonous substances including the odourless
but deadly gas carbon monoxide (CO) which, when breathed in, can accumulate in cases of poor air circulation to reach deadly concentrations. Also a
lack of fresh air circulation leads to overheating and possible damage to the
generator right through to destruction.
•For the same reasons of risk, never divert exhaust gases for the purposes of
heating rooms or vehicles.
•Never clean the generator with the aid of a high pressure cleaner or a strong
jet of water.
•Never allow water to find its way inside the generator. Never pour water over
the generator and never clean it using a water hose or a high pressure cleaner.
•Never operate the generator in any area where it could be flooded by high
water or any other events. The device's protection class (see Chapter 14 )
allows operation with spray water, however not in the case of floods.
11
Page 12
Product identification
3.3Scope of delivery of your generator
Apart from the technical documentation mentioned in Chapter 2.1 the following
items are Scope of delivery of your generator:
ItemName
Earth stake with connection cable
Key for POWERLOCK BOX (optional)
Universal key for access hatch
Filling aid with hopper
Technical documentation, see Chapter 2.1
Fig. 3-2 Included with delivery
12
Page 13
Product identification
3.4Labels on the generator
An important part of the operating manual is the labelling and notices on your
generator. These labels must not be removed and must always be maintained in
legible condition. If there is damage to a Labels can be ordered from our customer service team. The following figures and tables show the stipulated attachment
point and a brief explanation of the labels.
Fig. 3-3 Labels on the device
13
Page 14
Product identification
ItemlabelMeaning
Mandatory sign
Read the operating manual
before starting up
Note
Operate the power genera-
tor only with the mainte-
nance hatches closed.
Note
Crane loading lug
Example of maximum de-
vice weight
Note
Noise emissions
Warning
Burn hazard
Hot surfaces
Type plate
Example:
Note
2-way fuel valve
External tank
Internal tank
Note
Fuel quality
and tank contents
14
Prohibition signs
No smoking!
Open flame prohibited!
Page 15
Product identification
ItemlabelMeaning
POWERLOCK sticker
Open, connect and discon-
nect only when de-ener-
gized.
The connection terminal is
for potential equalization
(left) with IT networks and
for earthing (right) with TN
networks.
DGUV instruction on
Generators
of Version C
Death hazard
Live parts when opening the
cover
The EMERGENCY STOP
switch turns off the power
generator immediately if
there is an emergency.
Warning symbols
Dangerous voltage
For electricians only
Brief operating manual
Warning notices
Do not use starting aids!
Explosion hazard
Tab. 3-1 Labels on the device
15
Page 16
For your safety
4For your safety
The following chapter describes basic Safety instructions for safe operation of
your generator. Your device is a very high-performance electrical machine which
is potentially dangerous when operated if it has not been installed, commissioned, used, serviced and repaired according to the operating manual. If necessary, the operating manual will also include different supplements that depend on
the country of use, in addition to the present one.
Operation, use, servicing as well as any work with or on the generator is therefore
only permitted by such persons who have read this chapter and have put its provisions into practice!
Concrete warning notices can also be found regarding basic safety instructions
further on in this operating manual. These are always placed in an explanatory
text immediately before the description of work steps which can be dangerous if
the warning notice is not observed. Read the following sections for correct and
rapid understanding of these safety and warning notices. They describe their
systematic structure as well as the meaning of markings and symbols.
4.1Safety symbols
The safety symbol indicates graphically that a source of danger exists. We
use the internationally valid safety symbols from ISO 7010 for rapid and
unique classification of the respective dangerous situation. In the following there is a description of the warning symbols used in this operating
manual with an explanation about the respective dangerous situations.
Warning of a general hazard
This warning symbol indicates activities where several causes can lead to risks.
The concrete danger must be respectively more clearly specified by further notices.
Warning of a dangerous electrical voltage
This warning symbol is indicates activities where the danger of electric shock exists, possibly with lethal consequences.
Warning of potentially explosive materials
This warning symbol indicates activities where the danger of an explosion exists,
possibly with lethal consequences.
Warning of toxic substances
This warning symbol indicates activities where a risk of poisoning exists, possibly
with lethal consequences.
16
Page 17
For your safety
Warning of corrosive substances
This warning symbol indicates activities where a risk of chemical burns to the environment as well as people exists, possibly with lethal consequences.
Warning of environmentally damaging substances
This warning symbol indicates activities where a risk of contaminating the environment exists, possibly with catastrophic consequences.
Warning of hot surfaces
This warning symbol indicates activities during which there is the danger of
burns, possibly with lasting consequences.
Warning of a suspended load
This warning symbol indicates activities where the danger of falling loads exists,
possibly with lethal consequences.
Warning of automatically starting machines
This warning symbol indicates activities where a danger of being injured by selfstarting machines exists, possibly with lethal consequences.
17
Page 18
For your safety
4.2General safety instructions
ENDRESS Generators are designed to operate electrical equipment with
appropriate power output requirements. Other uses can lead to severe injury to operating personnel and people nearby. There is also increased risk
of damage to the generator and further property damage.
DANGER!
Mortal danger due to an electric shock if live parts are touched.
► Never operate the device if it is in a damaged condition.
► Never operate the electrical consumers and connecting cable (power con-
suming equipment) in a damaged condition.
► Never feed directly into existing networks that are already connected to a
power source (e.g. power supplier, solar plant, etc.).
► Never operate the device with wet hands.
Most injuries and equipment damage can be avoided if all instructions given in
this manual and all instructions attached to the device are followed.
The Generators must not be modified in any way, not even temporarily. This pose
a death hazard to operating and deployed personnel and damage to the generator and the consumers being used.
Operating company and Operating personnel are to use the Generators only according to regulations contained in the entire technical documentation (hereinafter referred to as appropriate use).
Every instance of inappropriate use and all activities on the Generators that are
not described in this manual are prohibited misuse beyond the legally defined
limits of the manufacturer’s liability. In return all claims for damages and warranty
claims against ENDRESS-Elektrogerätebau GmbH that are associated with misuse are null and void.
18
4.3Residual risks
As a manufacturer of EU-compliant machines, ENDRESS make great efforts to create designs which already eliminate possible risk potentials at
the design stage. If this is not possible without significantly impairing the
functions of a device, we implement suitable protective measures protect
the user from injury.
If there are still some residual risks associated with working with the device, we clearly advise the user about these sources of danger, possible
consequences as well as measures to avoid such dangers.
The residual dangers were analyzed and Residual dangers identified during the
development and design of your Generators by means of a danger analysis according to DIN EN 60204, DIN EN ISO 12100 and DIN EN ISO 8528-13.
References to general sources of danger can be found in chapters 4 and 5 .
From Chapter 6 one can find concrete warning notices placed before every action step which represents a residual risk.
The exact structure and contents of warning notices are defined in the
ISO 3864 series of standards and follow an established identification marking required to immediately be able to estimate the degree of the respective
danger. Exactly impress upon yourself the identification marking of the
Page 19
For your safety
four different danger levels in order to be able to reliably assess the dangers associated with the individual operating states and action steps when
reading the operating manual.
DANGER!
DANGER describes a danger which represents a high level of risk,
can lead to death or severe injuries,
► The individual points provide instructions and
► notices as aids to avoid the danger
► or to reduce the risk to an acceptable level.
WARNING!
WARNING describes a danger which represents a medium level of
risk,which can lead to death or severe injuries,when not avoided.
► The individual points provide instructions and
► notices as aids to avoid the danger
► or to reduce the risk to an acceptable level.
CAUTION!
CAUTION describes a danger which represents a low level of risk,
can lead to minor or medium level injuries
► The individual points provide instructions and
► notices as aids to avoid the danger
► or to reduce the risk to an acceptable level.
when not avoided.
when not avoided.
which
which
NOTICE!
ATTENTION! describes a situation or action that might result in damage to
equipment and/or malfunctions if it is not prevented.
► The individual points provide instructions and notices
► as an aid to avoid or prevent damage to equipment.
DANGER!
Mortal danger due to an electric shock if live parts are touched.
► Never operate the device if it is in a damaged condition.
► Never operate the electrical consumers and connecting cable (power con-
suming equipment) in a damaged condition.
► Never feed directly into existing networks that are already connected to a
power source (e.g. power supplier, solar plant, etc.).
► Never operate the device with wet hands.
19
Page 20
For your safety
DANGER!
Engine exhaust gases contain poisonous and partially invisible gases such
as carbon monoxide (CO) and carbon dioxide (CO2).
Risk of death due to poisoning or asphyxiation.
► Ensure that there is good ventilation during the whole period of operation.
► Only operate the generator in the open.
► Never direct the exhaust gases into rooms or pits.
DANGER!
Danger of severe or mortal injuries being incurred from falling loads.
► Never stand under or close to a suspended load, also not to provide assis-
tance.
► Ensure that there is no person in the area of swivel of the lifting device.
► Use all suitable measures to prevent the suspended load from swaying.
DANGER!
Leaking engine oil and fuel can burn or explode.
A risk of suffering severe even deadly burns.
► Prevent engine oil or fuel from leaking out.
► Never open the tank cover during operation or when it is hot.
► Remove leaked operating fluids immediately and appropriately.
► Never use an additional starting aid.
► Smoking, naked flames and sparks are forbidden.
DANGER!
Hot parts can ignite flammable and explosive materials.
A risk of suffering severe even deadly burns.
► Never operate the generator in the vicinity of combustible or flammable ma-
terials.
► Never operate the generator in an environment prone to an explosion.
WARNING!
There is a risk of explosion and fire in the case of inappropriate handling
and spark development when working with the battery.
Danger from spraying sulphuric acid. Danger of suffering severe even deadly
burns and chemical burns. Danger of being blinded.
► Never lay electrically conductive parts on the starter battery.
► Flames, sparks, an open light and smoking are prohibited.
► Avoid sparks when handling cables and electrical devices, as well as electro-
static discharge.
► Avoid short-circuits.
► Wear acid-resistant protective clothing.
20
Page 21
For your safety
WARNING!
Escaping corrosive acid fumes or sulphuric acid during and after the
charging process. A risk of suffering severe or even deadly burns.
► Only work with acid-resistant protective equipment.
► Clean surfaces covered in acid immediately using adequate amounts of wa-
ter.
► Only charge the starter battery in a well ventilated environment.
CAUTION!
Certain surfaces on the device can get very hot whilst it is running.
Risk of burns
► Never touch any engine parts (in particular the exhaust system) for a few min-
utes after ceasing operation.
► Always leave hot engine parts to cool down before touching them.
CAUTION!
A high device weight. Risk of crushing from improper handling during operation or transport.
► Only lift the generator with the aid of all handles provided or by using a suit-
able hoist.
► During transport on vehicles, ensure that there is the prescribed load secur-
ing in place.
► With it in a raised condition, never come close to or stand under the genera-
tor.
NOTICE!
Leaking engine oil and operating fluids can contaminate the soil and
groundwater.
► Ensure that the generator is transported horizontally and mounted.
► Make all efforts, at all costs, to prevent escaping of operating fluids.
► Dispose of contaminated soil immediately and according to regulations.
NOTICE!
Use of wrong or outdated fuel damages or destroys the engine.
► Only use the fuel displayed on the sign (Tab. 3-1 ).
► Observe the possibly enclosed documentation for the fuel release of the en-
gine manufacturer
► Observe the shelf life of the fuel according to the supplier.
► Observe the engine operating manual.
21
Page 22
For your safety
NOTICE!
Excessive heat or moisture can destroy the device.
► Always ensure that there is a good supply of air and heat removal.
► Never operate the generator in rooms or narrow pits.
► Never clean the device with the aid of a strong jet of water or high pressure
cleaner.
► Never allow water to find its way inside the generator.
Your Generators is a complex machine, the operation and maintenance of
which requires exact knowledge of its functions and danger potentials.
Therefore any work with or on the device, of any kind, may only be performed by authorised and instructed operating personnel.
Quite apart from the authorisation which the operating company of the device must issue, only such persons may operate or service the device who
fulfil the following criteria. They are designated in this operating manual as
operating personnel.
The authorised operating personnel must:
•be of age.
•be trained in First Aid and be able to provide it.
•be familiar with the accident prevention regulations and safety instructions
relevant to the Generators and be able to apply them.
•have read Chapter 4 , have understood the contents and are able to use and
implement them in practice.
•be trained and instructed according to the rules of conduct in the case of malfunctions.
•have the physical and mental abilities to carry out their responsibilities, tasks,
and activities on the Generators.
•be trained and instructed in their responsibilities, tasks and activities on the
Generators.
•have understood the entire technical documentation concerning their responsibilities, tasks and activities on the Generators and be able to implement
these in practice.
4.5Danger zones and work areas
In order to be able to consider all of a machi ne's safety aspects and to comply with the safety and health protection requirements of the applicable
standards and EU directives, we have assessed the use of your Generators
in all of the phases that it will go through during its product service life
(product life cycle). The following zones were defined on the Generators for
this purpose: The danger zones and work places (work areas) around the
generator are determined by the activities to be undertaken within the various phases in individual life cycles:
•Working zone: In this zone on and around the Generators (approx. 1 metre
radius) the trained operating personnel (see Chapter 4.4 ) may operate and
inspect the device in compliance with all of the safety and operating instructions given in the technical documentation. All other people (especially minors and people with disabilities) must remain outside this working zone.
•Danger zone: This zone must be kept free of all personnel during all phases
of use and service life of the device. Any work in this zone is only to be undertaken by specially trained specialists if it is essential for the fulfilling of the
task and if all of the protective equipment (PPE) needed is used. You must
always comply with the following limits:
23
Page 24
For your safety
Product's service life phase Danger zone
Transport and installationwithin a radius of 1m around or below the de-
vice
Operationwithin the outer limits of the device
Service and maintenanceWithin the outer limits of the device when
switched on Generators
Tab. 4-1 Danger zone on Generators
24
Page 25
Checking the electrical safety
5Checking the electrical safety
Checking electrical safety requires different measures that are only to be
taken by authorized personnel. In doing so the pertinent VDE provisions,
EN and DIN standards, in their valid versions, must be observed. For use
at construction or assembly sites, the DGUV Information 203-032 edition of
May 2016 must be observed. It defines special protective measures and
rules of conduct for the commissioning and corresponding marking on the
device.
You must especially never use defective or damaged consumers, cable connections or plug connectors, etc. (current-consuming equipment). They must be
checked for proper condition at regular intervals (see Tab. 5-1 )
On-site operation
earthingThe "on-site operation" mode (see Chapter 8.2.1 ), has been designed for man-
ual or automatic (remote start) operation with one or more electrical consumers.
To protect against electric shock (current flow through your body), the protective
separation measure with equipotential bonding according to DIN VDE 0100-551:
2017-02 is used. The protective conductor system of the attached consumer
equipment takes over the function of the potential equalization device. The terminal (Fig. 6-4 ) is connected with this Potential equalization device connected.
An earthing device is not needed in the "on-site operation" mode.
Your Generators corresponds to a Version A generator according to DGUV Information 032-203 issued in May 2016 when it is in “on-site operation" mode. A corresponding marking can be found on the device (see Fig. 3-3 ):
We strongly recommend that you also comply with the requirements of DGUV Information 203-032 for other purposes.
DANGER!
Dangerous electrical voltages will be present if several consumables are
connected up without a working personal safety device.
Mortal danger from electrocution
► Never operate multiple consumables from the Generators without additional
RCDs (residual current circuit breaker) for the second and each additional
consumable.
► Check the personal protection according to the check intervals given in Tab.
5-1 .
Supplying power to a building
earthingIn “building supply" mode (see Chapter 8.2.2 ) your Generators has been de-
signed as a replacement network supply for feeding into stationary installations
such as residential houses or public facilities. Suitable on-site protective measures must be implemented to protect against electric shock (current flow
through your body). The generator is earthed through the power supply cable's
and this earths the stationary system.
25
Page 26
Checking the electrical safety
In addition to the details given above, the electrical safety of the Generators is to
be checked by a qualified electrician at regular intervals. The periods between
testing must be established in such a way that the Generators and all work equipment to be connected can, based on current general knowledge, operational experience or specific evidence, be safe to use in the period between the two
inspections. (Examples in TRBS 1201, implementation instructions for §5 of
BGV/GUV-V A3, BGI 594, BGI 608, Appendix 2, recommendation of BGI/GUV-I
5090 “Repeated testing of mobile electrical equipment“).
NOTICE!
The operator is responsible for defining and adhering to the test intervals
. Above all one must ensure observance of the respectively valid national
regulations.
This responsibility also extends to any additional equipment installed in
conjunction with the device.
We recommend the following checks and intervals as general guideline values:
WhenWhat / howWho
First start-up at the operating location
•See Chapter 7 and follow the operating manual in the
supplier documentation.
•Visual inspection for externally visible defects such as
transport damage.
Start-up on a daily basis •See Chapter 7.3 and follow the operating manual in the
supplier documentation.
•Visual inspection for externally visible defects (such as
damaged insulation, connectors, cable; leaks, noise)
•If the Generators is fitted with insulation monitoring and/
or an RCD, the operating personnel must run functional
tests on the safety equipment (see Chapter 7.8 ). The
operating personnel must be trained to do this.
Retest no later than
once every six months
•According to BGI/GUV-I 5090 “Repeated testing of mobile electrical equipment“)
•Sample test report according to
DGUV information 203-032 *)
*) Download as a text file under → www.dguv.de Webcode:
d138299
Tab. 5-1 Recommended test intervals
Operating
personnel
Operating
personnel
Qualified
electrician
26
Page 27
6Description of the device
6.1Views
The following section provides an overview of the designation and location
of the most important components of your generator. It is important to ensure that you are familiar with these in order to further understand the described functions and operating steps and to be able to perform them
safely. Ignoring this manual can cause severe injury or death, and/or damage to the power generator and connected consumers.
To make it easy to find the operating elements and components, the individual
views of the power generator are designated throughout the following descriptions and instructions, as can be seen in the following illustration.
Description of the device
Fig. 6-1 Views of the generator
27
Page 28
Description of the device
6.2Exhaust gas and battery side components
28
Fig. 6-2 Components on the connecting side
Compartment for device documentationMaintenance hatch
Drain screw for collection panTank filling port
Engine air filterOil dipstick
Pre-filter
Page 29
Description of the device
6.3Components on the maintenance side
Fig. 6-3 Components on the maintenance side
FPT drive engineSynchronous generator
Base frame with tank and collection panStarter battery
Main battery switchForklift pockets with edge protection
29
Page 30
Description of the device
6.4Components for operating panel and switch box
Fig. 6-4 Components for operating panel and external switch box
Control module E-MCS 7.0Test button for 300 mA differential cur-
rent release
Controls ON/OFF switchInsulation monitoring
Main switchCircuit breaker 16 A/4-pin for socket
(with IT/TN 32A)
Circuit breaker 1-pin RCD (30 mA) for
socket
Circuit breaker 63A / 4-pin for socket
(not on IT/TN)
RCD (residual current circuit breaker)
30 mA for sockets
EMERGENCY STOP switch
CEE socket 400V 63A 6h red* OR
CEE socket 400V / 125A 1h white**
Operating mode selection switch (IT/TN
version)
IT/IN version: *active only during on-site operation **active only during with building supply
30
Horn
Page 31
NOTES
Description of the device
31
Page 32
Commissioning
7Commissioning
The following chapter explains the basic procedure for initial or repeated
generator start-ups in “direct supply" mode. Perform the following described steps when you put your generator into operation for the first time
or again after transport.
NOTICE!
For start-up and operation of a Generators on building and assembly sites,
Deutsche Gesetzliche Unfallversicherung (DGUV) in DGUV Information
203-032, the May 2016 edition, requires observance of special protective
measures and behaviour regulations.
Be sure to refer to the following section for a summary of this DGUV information. It supplements the operating manual for this special application.
We also urgently advise observance of relevant DGUV information under
comparable operating conditions.
We recommend that you read DGUV Information 203-032 before starting the initial commissioning. When in doubt, consult a qualified electrician.
32
Page 33
Commissioning
Fig. 7-1 Setting up personal protection measures (source: DGUV)
33
Page 34
Commissioning
7.1Transporting and preparing your generator
Choose the transport vehicle and lifting gear so that the generator can be moved
safely at all times according to its total mass (see Chapter 14 ). The unit's solid
base frame allows it to be lifted and transported by a forklift. Alternatively, loading
by crane is also possible after the crane eyes have been installed correctly.
Ensure that all of the power generator’s maintenance hatches and covers are securely closed.
Conditions The ground at the installation site must be even and be capable of bearing
the load.
The generator is turned off.
The generator has cooled down
DANGER!
Danger of severe or mortal injuries being incurred from falling loads.
► Never stand under or close to a suspended load, also not to provide assis-
tance.
► Ensure that there is no person in the area of swivel of the lifting device.
► Use all suitable measures to prevent the suspended load from swaying.
NOTICE!
Leaking engine oil and operating fluids can contaminate the soil and
groundwater.
► Ensure that the generator is transported horizontally and mounted.
► Make all efforts, at all costs, to prevent escaping of operating fluids.
► Dispose of contaminated soil immediately and according to regulations.
Transporting by lifting forks
Transport by crane1. Screw the included crane lugs onto the top of the power generator (if they are
1. Align the lifting forks (e.g. forklift) with the position of the forklift pockets Fig.
6-3 off.
2. Insert the lifting forks as far as possible because of the machine’s heavy
weight.
3. Raise the power generator slowly and evenly.
4. Move the power generator slowly into its place of use.
5. Lower the device slowly and evenly.
6. Remove the lifting forks.
The unit has been transported and positioned at its work site.
not already mounted).
34
2. To the crane loading lugs, fasten a lifting mechanism approved for the high
device weight.
3. Secure the lifting mechanism against falling out.
4. Raise the power generator slowly and evenly.
5. Move the power generator slowly into its place of use.
6. Lower the device slowly and evenly.
Page 35
7. Unhook the lifting device.
The unit has been transported and positioned at its work site.
7.2Refuelling your generator
Proceed as follows to the generator.
Conditions The generator is turned off.
The generator has cooled down.
There must be an adequate air supply and air removal.
All power consuming equipment must be disconnected or switched off.
DANGER!
Leaking engine oil and fuel can burn or explode.
A risk of suffering severe even deadly burns.
► Prevent engine oil or fuel from leaking out.
► Never open the tank cover during operation or when it is hot.
► Remove leaked operating fluids immediately and appropriately.
► Never use an additional starting aid.
► Smoking, naked flames and sparks are forbidden.
Commissioning
Refuelling the generator
NOTICE!
Leaking fuel can contaminate soil and groundwater.
► Take note of the residual quantity in the tank and its maximum filling capacity.
► Always bear in mind that the fuel gauge reacts only after a time delay.
► Fill the tank to a maximum of 95%.
► Always use a filling aid (e.g. funnel).
NOTICE!
Use of wrong or outdated fuel damages or destroys the engine.
► Only use the fuel displayed on the sign (Tab. 3-1 ).
► Observe the possibly enclosed documentation for the fuel release of the en-
gine manufacturer
► Observe the shelf life of the fuel according to the supplier.
► Observe the engine operating manual.
1. Put the Fuel tap in “INTERNAL TANK” position.
2. Screw off the tank cover (Fig. 6-2 ).
3. Insert filler aid into the filler neck.
4. Fill with fuel slowly and evenly.
5. Observe the tank gauge (Fig. 6-2 ), so as not to overfill the tank.
6. Remove the filler nozzle.
7. Reinstall the tank cover.
The generator is now refuelled.
35
Page 36
Commissioning
7.3Starting the generator
Power generator start-up in manual control mode (see Chapter 8.1 ) is described here.
Proceed as follows to start the power generator from the E-MCS 7.0 control module of the operating panel.
Fig. 7-2 Manually starting and stopping the power generator
Conditions The electrical safety has been checked (see Chapter 5 ).
The fuel tank is full enough.
The coolant level is adequate (fill with coolant before first start-up; for this,
see the engine’s operating and maintenance manual).
The oil level is adequate (fill with engine oil before initial use, see the engine
operating and maintenance manual).
There is adequate air supply and air removal.
The main battery switch must be in the “ON” position.
DANGER!
Leaking engine oil and fuel can burn or explode.
A risk of suffering severe even deadly burns.
► Prevent engine oil or fuel from leaking out.
► Never open the tank cover during operation or when it is hot.
► Remove leaked operating fluids immediately and appropriately.
► Never use an additional starting aid.
► Smoking, naked flames and sparks are forbidden.
36
Page 37
Commissioning
DANGER!
Engine exhaust gases contain poisonous and partially invisible gases such
as carbon monoxide (CO) and carbon dioxide (CO2).
Risk of death due to poisoning or asphyxiation.
► Ensure that there is good ventilation during the whole period of operation.
► Only operate the generator in the open.
► Never direct the exhaust gases into rooms or pits.
Starting the engine1. Turn the selection switch in position 2 “on-site operation” (IT/IN version
only).
2. Turn the controller’s switch into the “ON" position.
The control module's display will come on and the controller will run up.
3. Wait until the start screen is displayed (see Fig. 8-4 ).
4. Set up "Manual" mode on the display by pressing the mode button (right arrow) once.
5. Press the “Start” button once.
The engine will start up after the preheating phase.
The engine has started.
The green control LED shows you whether the Generators is ready.
Familiarize yourself with the complete operating procedure for the E-MCS 7.0
control module before initial commissioning of the power generator, see Chapter
8.1 .
NOTICE!
Do not apply load to the generator immediately after a cold start.
► Allow the generator engine to warm up for a few minutes before switching on
a load when the generator has not been operating for more than eight hours
(or for very low external temperatures).
7.4Low load diesel engine operation
Internal combustion engines normally run most economically and environmentally friendly when they have reached their optimum operating temperature (with a
coolant temperature from approx. 80°C). Prolonged operation well below the operating temperature or without a specific minimum load will have a negative effect
on the service life. Incomplete combustion processes inside the engine will cause
more and more deposits to form within the engine. If this operating state continues for too long or it is not compensated for by regular phases running at full load,
this might result in a total engine failure and high repair costs in the worst case.
NOTICE!
Damage to the drive motor or other components in the generator that were
caus ed by low load op eration that is co ntrary to our reco mmendations (see
below) and/or those of the engine manufacturer will void any warranty or
liability claims.
37
Page 38
Commissioning
NOTICE!
Avoid, as far as possible, short-term operation or operation without a load
or with a basic load that is too low. Follow these recommendations if the
engine manufacturer does not provide detailed information or he provides
different information:
► Run your power generator at a minimum of 30% - 40% of the rated output
(see Technical Data).
► Avoid short-term operations where the engine does not reach its operating
temperature.
► Run the engine under maximum load for at least one hour at regular inter-
vals (monthly).
► Take note of the instructions provided by the engine manufacturer
7.5Turning off your power generator
Switch off your power generator as follows:
Conditions Any hazards that might be caused by interrupting the power supply have
been eliminated.
Anyone who might be affected by shutting down the power supply has been
informed.
The power generator is in manual control mode (see Chapters 7.3 and 8.1 .
Switching the generator off
1. Press the Fig. 7-2 button once.
a) If the button Fig. 7-2 is pressed a second time after Step 1, the engine
stops immediately without a cool-down phase. (not recommend-ed!).
The engine will go into the cool-down phase (“Cool-down” on the display)
and shuts off automatically in about two minutes.
2. Use the Fig. 7-2 switch to switch the controls to “0”.
The generator is switched off and secured.
7.6Turn off your generator in the event of an EMER-
GENCY
Your power generator is equipped with an EMERGENCY STOP switch. In an
emergency, it allows you to turn the machine off immediately to prevent further
hazards.
CAUTION!
The EMERGENCY-STOP smash button is only to be used in the event of a
dangerous situation arising in an emergency.
Risk of injuries if consumers are suddenly switch off.
► Always switch off the generator normally as described in Chapter 7.5 .
ConditionsIt must always be possible to actuate the EMERGENCY STOP switch without
any preconditions. Ensure that the EMERGENCY STOP switch is easily accessible at all times.
EMERGENCY STOP 1. Push down or hit the red EMERGENCY STOP button.
The engine will stop.
38
Page 39
Commissioning
The horn gives off a continuous warning tone.
The control module locks the power generator against further operation.
The EMERGENCY STOP switch's latching function is blocking the Generators
against restart.
The EMERGENCY STOP switch is locked in its actuated state. The generator
can only be switched back on again after the hazard has been eliminated and if
the EMERGENCY STOP switch is unlocked manually. How to unlock the EMERGENCY STOP switch:
Conditions The hazard or cause of the EMERGENCY STOP process has been eliminat-
ed.
All of the connected consumers are disconnected or switched off.
Removing the
EMERGENCY STOP
1. Gently turn the red button on the EMERGENCY STOP switch left or right.
The red button unlocks and springs back into normal position.
The Generators is now ready for operation again and can be restarted, see
Chapter 7.3 .
39
Page 40
Commissioning
7.7Connection of power consuming equipment
DANGER!
Mortal danger due to an electric shock if live parts are touched.
► Never operate the device if it is in a damaged condition.
► Never operate the electrical consumers and connecting cable (power con-
suming equipment) in a damaged condition.
► Never feed directly into existing networks that are already connected to a
power source (e.g. power supplier, solar plant, etc.).
► Never operate the device with wet hands.
DANGER!
There will be no RCD personal protection during operation if the earthing
of the Generators is faulty.
Mortal danger from electrocution
► The use of an RCD (FI circuit breaker) for personal protection requires proper
earthing of the Generators and this must be undertaken by a qualified electrician before the initial commissioning.
► The effectiveness of this protective measure should be regularly checked by
an electrician.
► Check the personal protection according to the check intervals given in Tab.
5-1 .
You can connect consumers with Schuko or CEE plugs to the following sockets:
40
Page 41
Commissioning
Fig. 7-3 Connecting consumers
ONLY supplying power to a buildingRCD
CEE socket 400V / 125A / 3~ / 1h300 mA*
ONLY on-site operationRCD
CEE socket 400V / 32A / 3~ / 6h30mA
CEE socket 230V / 16A / 3~ / 6h30mA
CEE socket 400V / 63A / 3~ / 6h300 mA*
CEE socket 400V / 16A / 3~ / 6h30mA
Schuko attachment sockets 230 V / 16 A / 1~30mA
Terminal strip 5-pin (ACCESS FOR ELECTRICIANS ONLY)300 mA*
POWERLOCK BOX (option, see Chapter 9.1 )300 mA*
*NO PERSONAL PROTECTION
41
Page 42
Commissioning
Connect a consumer to the power generator as follows:
Conditions The generator is started and brought up to operating temperature (see Chap-
ter 7.3 ).
All power consuming equipment is disconnected or switched off.
All circuit breakers in the fusebox are in “ON” position.
The control module’s green control LED goes on.
The sockets and connected consumers are supplied with voltage.
Connecting consumers
1. Turn the locking ring on the socket’s splash guard anti-clockwise to the stop.
2. Fold the splash guard aside with one hand.
3. Use your other hand to insert the plug from the consumer to be connected
into the socket to the stop.
4. Firmly screw the locking ring clockwise on the consumer’s plug.
The consumer is connected to the power generator and ready to use.
NOTICE!
If the control module display shows the home screen (also see Chapter 8.1
), you can read the power of the operated consumers from the representation.
42
Page 43
Commissioning
7.8Residual current circuit breaker (RCD)
The residual current circuit breaker (RCD) protects against dangerous
body currents in compliance with DIN VDE 0100-551. This version of the
generator according to DGUV information 203-032 is classified as a Version
C generator for commissioning and operation on building and installation
sites and it has the following marking:
It is essential to observe the regulations and safety instructions of the DGUV information 203-032 mentioned in order to achieve protection for all people working in the connected distributor network.
We strongly recommend that you also comply with the requirements of DGUV Information 203-032 for other purposes.
DANGER!
There will be no RCD personal protection during operation if the earthing
of the Generators is faulty.
Mortal danger from electrocution
► The use of an RCD (FI circuit breaker) for personal protection requires proper
earthing of the Generators and this must be undertaken by a qualified electrician before the initial commissioning.
► The effectiveness of this protective measure should be regularly checked by
an electrician.
► Check the personal protection according to the check intervals given in Tab.
5-1 .
The operating personnel must press the test button on the residual current protection device (RCD) () before every start to check the mechanical release
function.
43
Page 44
Commissioning
Fig. 7-4 Built-in types of residual current circuit breaker (RCD)
Testing the RCD The generator is running
1. Move the FI circuit breaker into POS I.
2. Press the test button.
The switch position indicates the result:
SymbolMeaning
POS ICircuit breaker does not trip.
FI circuit breaker is defective.
POS 0Circuit breaker trips.
FI circuit breaker is working correctly.
The device has been tested in compliance with DIN VDE 0100-551.
1. Move the circuit breaker back into POS I to be able to operate consumers
from the generator again.
44
Page 45
Testing the differential current release
Commissioning
Fig. 7-5 Differential current release
Do as follows to test that the differential current release is responding correctly:
The generator is running.
1. Move the main switch into POS I.
2. Press the differential current release test switch.
The circuit breaker position shows the test result.
SymbolMeaning
POS ICircuit breaker does not trip.
FI circuit breaker is defective.
POS 0Circuit breaker trips.
FI circuit breaker is working correctly.
The device has been tested in compliance with DIN VDE 0100-551.
1. Move the circuit breaker back into POS I to be able to operate consumers
from the generator again.
In “building supply” mode, the white feed socket (Fig. 7-3 Connecting consumers) is secured against overload and short circuit by the main switch. The integrated differential current release is only for protecting the system. Due to its
electrical design, it offers NO PERSONAL PROTECTION! For this, be sure to
follow the instructions in Chapter 8.2 .
45
Page 46
The device in-use
8The device in-use
8.1Operating the E-MCS 7.0 control module
We will explain in detail how to operate the power generator from the control module in the following chapter, 7.3 and under various operating con-
ditions. You will also learn how to display and edit various operating
parameters and error messages.
The uses different control modes. The control mode that is currently being used
is shown in the top line of the display, see Fig. 8-1 . Change modes by pressing
the buttons on the control panel Fig. 8-2 on the control module.
Fig. 8-1 Control module’s display
Control mode - Controller off
The ““ displayed in the top line of the display indicates that the Generators
can neither be started manually from the control module nor automatically due to
a problem caused by the supply distributor. This mode is reserved for maintenance and configuration work or if starting the Generators must be prevented under all circumstances.
NOTICE!
Automatic grid switching is deactivated in the ““ control mode.
The power generator will not start if the power supply has failed.
► Use only the ““ control mode for temporary purposes and only if starting
the Generators must be prevented.
► After you have finished accessing the unit, you must ensure that the control
module is back in the ““ mode.
Control mode - Manual operation
The manual is indicated by ““ being displayed in the top line of the display,
see Fig. 8-1 . The power generator can be switched on and off manually and other functions can also be controlled in this mode.
NOTICE!
46
Automatic grid switching is deactivated in the ““ control mode.
The power generator will not start if the power supply has failed.
► Only use the manual control mode for temporary purposes or if automatic
mains switching is not needed.
► After you have finished accessing the unit, you must ensure that the control
module is back in the ““ mode.
Page 47
The device in-use
Control mode - Automatic
The Automatic control mode is indicated by ““ being displayed in the top
line of the display. The generator will start automatically in this mode as soon as
the integrated mains monitoring system detects a power grid fault. However,
some functions such as resetting the warning tone can still be used.
Controller switched off
If the 7.3 switch is in “0” position, the controls for the Generators are completely
shut off. The power generator cannot be started neither automatically nor
manually in this mode.
DANGER!
Dangerous electrical voltage is still present even when the power generator is switched off
Mortal danger from electric shock if live parts are touched.
► Access only for electricians in areas marked with an adjacent warning sym-
bol.
► Maintenance on the generator is only to be done after an electrician has
switched off the power generator and it is completely voltage-free.
8.1.1Operating panel for control module E-MCS 7.0
Description and function of the operating buttons
Fig. 8-2 Control module’s control panel
47
Page 48
The device in-use
ItemButtonDescription
START ENGINE Press this button to start the power generator if control
mode is selected (also see )
SWITCH OFF ENGINE Press this button oncein control mode and
the control module will start the power generator’s cool-down phase, and
it will be switched off afterwards. If this button is pressed for a 2nd time,
then the control module will skip the cool-down phase and the power generator will be switched off immediately (NOT RECOMMENDED!).
RESETTING A FAULT Press the button to acknowledge an alarm message displayed on the screen and to turn off the horn. Inactive alarms are
immediately faded out on the display and the status of the active alarms
changes to “acknowledged" so that this will be faded out immediately after the cause is eliminated.
RESETTING THE HORN Press this button to deactivate the horn output
without acknowledging the alarm.
SELECTING A CONTROL MODE Pressthis button to switch between
the or ) control modes. The buttons will only be functional if
Fig. 8-4 is displayed in the main window on the control screen. If necessary, you should press the button repeatedly until the main window is
displayed.
SELECTION SWITCH FOR GENERATOR MODE OR POWER GRID
MODE
Press this button to supply the connected distributor network from the
power generator in control mode, or the connected distributor network through the public power grid.
MENU SELECTION
This function can only be enabled by service personnel.
ENTER BUTTON
Use this button to confirm or quit editing a setting.
MOVING BETWEEN THE SCREEN PAGES
Press these buttons to move between the different windows displayed on
the screen.
Tab. 8-1 Control buttons on the control module
48
Fig. 8-3 Operating display on the control module
Page 49
ItemDescription
GENERATOR STATUS DISPLAY There are two statuses: Unit OK (display is green), and
Unit Fault (display is red). The green LED lights up if voltage from the generator is present
and the voltage parameters are within the limit values. After the button is pressed (FAULT
RESET), it starts to glow continuously (if an alarm is still active) or goes out (if no alarm is
still active).
LOAD The green LED lights up if there is voltage present from the generator and the measured parameters lie within the limit values.
GRID STATUS DISPLAY There are two statuses: Grid OK (display is green), and Grid Fault
(display is red). The green LED lights up if voltage from the grid is present and the voltage
parameters are within the limit values. After the button is pressed (FAULT RESET), it
starts to glow continuously (if an alarm is still active) or goes out (if no alarm is still active).
The device in-use
Tab. 8-2 Operating display on the control module
8.1.2Display window on the control module’s screen
The control module screen shows you different Information about operating statuses, measured values, error messages and statistical data is shown in a structured form in the display windows. Press the arrow buttons Fig. 8-2 to move
around the different display windows.
You will find a detailed list with all event and error messages in the appendix.
alarm listIf an alarm is triggered, the alarm list will be displayed on the screen and you
should select the entry that is preceded by an *. Acknowledge the alarms as follows:
1. If there are several entries present should use the arrow keys to select the
entry that you want.
2. Press the button to acknowledge the alarm.
The * character will disappear.
The entry will only disappear after the error has been eliminated.
49
Page 50
The device in-use
50
Fig. 8-4 Sample from control module’s display screen
8.2Select operating mode (II / TN-S)
The following section explains the precise procedure for operating the generator under different operating conditions. Your generator has a changeover device that allows you to use the generator in two different modes:
•Operation for supplying a mobile distribution system
•Building supply for supplying a stationary system
Selection of the right operating mode is specified based on the purpose.
Page 51
The device in-use
NOTICE!
Press the operating mode selection switch (Fig. 6-4 ) ONLY when the power
generator is not running!
► The correct operating mode (building supply or on-site operation) must be
selected before you start the generator.
8.2.1Direct supply mode
The generator is designed for use with one or more electrical consumers (as per
VDE 100, Part 551) in “on-site operation". The protective conductor of the ground
contact socket assumes the function of the potential equalization line. Current
consumption in “on-site operation" mode occurs through several sockets with
blue colour identification (230V / 50 Hz / 1~) or red colour identification (400V /
50 Hz / 3~), see Fig. 7-3 . Use the selection switch Fig. 6-4 to select “on-site operation" mode.
NOTICE!
Insulation monitoring must be always be checked before starting your daily work in "Direct supply" mode.
► Always follow the working steps described in Chapter 8.3 BEFORE you con-
nect up consumables or make cable connections to the sockets.
Follow the working steps for starting the generator described in Chapter 7.3 .
Follow the work steps for connecting consumers described in Chapter 7.7 .
8.2.2Building supply operating mode
The “building supply" operating mode is used to supply stationary systems such
as residential houses or public facilities. The generator serves as the emergency
power supply to maintain power if the public power supply fails.
NOTICE!
For further steps it is assumed that the building is equipped with an emergency power supply, which was installed by a specialist company under
the supervision of an electrician and that this was implemented in compliance with VDE 0100 Part 551 and VDN.
DANGER!
There is NO PERSONAL PROTECTION on the generator's side when using
the power supply socket as no RCD (residual current circuit breaker) is installed!
Mortal danger from electrocution
► Installation and commissioning is only to be undertaken by a qualified elec-
trician
► Personal protection (RCD) must be ensured on-site.
► Check the personal protection according to the check intervals given in Tab.
5-1 .
51
Page 52
The device in-use
The supply into the stationary system is through a flexible connection line
(H07RN-F or comparable) in the supply distributor installed on-site through the
CEE power socket (Fig. 7-3 with white colour marking). All other sockets are not
usable in this operating mode.
Ensure that the flexible connection line is suitable for the selected operating conditions and power output requirements.
ConditionsThe following requirements must be met:
Generator is ready for operation.
The selection switch for the supply distributor is in the "Network" or "0" posi-
tion.
WARNING!
Danger from machines suddenly starting up.
Risk of severe or even mortal injuries.
► You must ensure that all consumers in the stationary system's distribution
network are switched off or disconnected from the network BEFORE you
switch the supply distributor over to emergency power.
► Take note of the instructions in the supply distributor's operating manual.
Create the power
feed connection
NOTICE!
Ensure that there is a clockwise rotating field applied to the feed distributor
at the sides of the emergency power infeed. The rotational field must be
checked by a qualified electrician if there is no appropriate direction of rotation indicator on the supply distributor, (see Fig. 8-5 ).
Proceed as follows to create a power feed connection between the generator and
the on-site installed feed distributor:
1. Connect the flexible connection cable to the CEE socket with white colour
code Fig. 7-3 .
2. Connect the flexible connection line with the power socket to the on-site installed feed distributor.
3. Use the selection switch to choose the “building supply" operating mode Fig.
6-4 .
4. Start the generator, see Chapter 7.3 .
5. Set the selection switch on the supply distributor to “emergency power" position.
The emergency power supply is created.
The stationary system is fed by the generator.
52
Page 53
The device in-use
Fig. 8-5 TN system / TT system version example
53
Page 54
The device in-use
8.3Insulation monitoring
“On-site operation” mode is equipped with insulation monitoring with
shut-off. The insulation monitoring provides electrical safety to the generator and to all connected consumers and cable connections during continuous operation.
A possible insulation fault is displayed in two stages:
1. Yellow warning light with warning tone:
a) There is an insulation fault with transfer resistance lower than 46 kΩ but
higher than 23 kΩ in a current circuit of the power generator, the cable
network or a connected consumer.
Result: Operation is still possible, and the main line circuit breaker is still
on. However, the cause of the insulation fault must be fixed soon. If the
insulation fault occurs only in connection with a specific consumer or cable connection, the corresponding part must not continue to be used.
If the fault continues to occur after all consumers have been unplugged,
immediately contact service personnel.
2. Red warning light with warning tone:
a) There is an insulation fault with transfer resistance lower than 23 kΩ in a
current circuit of the power generator, the cable network or a connected
consumer.
Result: Operation is no longer possible, and insulation monitoring trips
the main line circuit breaker. The power generator cannot be operated
again until the cause of the insulation fault is fixed.If the insulation fault
occurs only in connection with a specific consumer or cable connection,
the corresponding part must not continue to be used.
If the fault continues to occur after all consumers have been unplugged,
immediately contact service personnel.
WARNING!
Change in the hazardous situation when using the insulation monitoring
option.
Electric shock hazard if consumers are connected wrong
► If you have selected the “insulation monitoring” option, your power generator
becomes a Version A device (also see Fig. 3-3 ).
► Always follow the instructions from the DGUV for Version A power generators
(see infographic Fig. 7-1 and Chapter 7.7 ).
NOTICE!
The operating personnel must check the function before every start-up by
pressing the insulation monitoring test button (see Chapter 5 Checking the
electrical safety as well).
54
Page 55
Fig. 8-6 Insulation monitoring
Test the insulation monitoring function as follows:
Conditions The generator has started and is running.
The device in-use
1. Disconnect all of the consumers from the generator's sockets.
2. Make sure all circuit breakers are turned on (switch in POS-I).
3. Press the test knob for a few seconds.
The lamps and the position of the line circuit breaker indicate the result of the
test.
LampResultMeaning
Lights yellow
and red
Line circuit breaker jumps to
POS 0
stays offLine circuit breaker remains
in POS 1
stays offLine circuit breaker jumps to
POS 0
The insulation monitoring function has been successfully tested.
1. Press the button to reset the horn.
2. After inspection, the reset button must be pressed and the circuit breaker
must be put into POS-1 in order to operate the device again.
Insulation monitoring during opera-
With the following instructions you will learn how your generator detects an insulation fault of a connected consumable during operation and how it protects you.
tion
Conditions The generator has started and is running.
Line circuit breaker is in POS I.
Insulation monitoring
is OK
Insulation monitoring
is defective
Lamp defective
1. Use a socket to connect a consumer to the generator.
The lamp and and the position of the line circuit breaker indicate the result
of the test:
55
Page 56
The device in-use
LampResultMeaning
No signal
lamp goes on
YELLOW
signal lamp
goes on
YELLOW
and RED signal lamps go
on
If an insulation fault exists and the unit was previously OK when tested without a
device connected (see above), the insulation fault has been caused by the device.
1. Use its operating switch to switch off the consumable.
2. Disconnect the consumer from the generator's socket.
3. Press the button to reset the horn.
4. Press the reset button to reset the insulation monitoring system.
5. Move the line circuit breaker into POS I.
Your generator is ready to use again.
Line circuit breaker remains
in POS 1
Line circuit breaker remains
in POS 1
Line circuit breaker jumps to
POS 0
No insulation fault detected
Consumer has an insulation
fault (≤ 23kΩ)
Insulation fault (≤ 46 kΩ > 23
kΩ)
Insulation fault (≤ 23 kΩ)
WARNING!
Risk of touching surfaces that are live due to faulty insulation.
Danger of electric shock if a second insulation fault occurs.
► The relevant consumable is not to be used any more after an insulation fault
has been determined.
► Secure the defective consumable effectively against reuse by third parties.
► Replace the consumer or have it repaired by a qualified electrician.
8.42-way fuel valve
When supplying fuel, you can choose between the internal tank and an external refuelling device. To change refuelling methods, there is a 2-way tap
behind the maintenance hatch on the maintenance side of the power generator.
Do as follows to operate the power generator with an external refuelling device:
Conditions An external fuel tank equipped with a refuelling device (see instructions be-
low) is available.
The fuel tank is full enough.
The power generator’s internal tank is full enough.
56
Page 57
The device in-use
DANGER!
Fire and explosion hazard from leaking fuel
Risk of severe to deadly burns.
► Prevent fuel from leaking.
► Keep the refuelling device’s fuel cannister firmly closed.
► When changing the fuel cannister, stay as far away as possible from the pow-
er generator.
► Remove unneeded fuel cannisters from the power generator’s work area im-
mediately.
► Smoking, naked flames and sparks are forbidden.
Connect refuelling
device
Fig. 8-7 Refuelling device connection
1. Remove the stoppers from the hose holes on the base frame.
2. Make sure the 2-way tap’s lever is in internal tank position (“INSIDE”).
3. Remove the dummy plugs from the feed and return connections. .
4. Guide the ready-made fuel hoses for the refuelling device though the holes
and screw them as follows to the connections on the 3-way tap:
a) Connect the fuel feed hose.
b) Connect the fuel return hose.
5. Put the lever for the 2-way tap in “OUTSIDE” position.
6. Start the generator (see Chapter 7.3 ) and wait for the RPM to stabilize.
The refuelling device is attached. The power generator is supplied with fuel
through the refuelling device.
57
Page 58
The device in-use
NOTICE!
When the lever of the 2-way fuel tap is in “OUTSIDE” position with the engine running, without the refuelling device connected, air can get into the
engine’s fuel system.
The drive engine shuts off for lack of fuel.
► Do not put the 2-way fuel tap into “OUTSIDE” position until the refuelling de-
vice is securely connected.
Do as follows to disconnect the refuelling device:
Conditions The internal tank is full enough.
The power generator is switched off.
Disconnecting the
refuelling device
1. Turn the lever of the 2-way fuel tap to “INSIDE” position.
The engine is supplied with fuel from its own tank.
2. Remove the fuel hoses of the external refuelling device from the connections.
.
3. Close the connections with the dummy plugs.
4. Insert the stoppers back into the base frame’s hose holes.
The refuelling device is disconnected.
8.5HARTING remote starting device
The optionally installed HARTING® socket allows you to turn your power
generator on and off remotely in connection with a suitable external installation (such as a control station).
WARNING!
Beware of machines starting in automatic mode.
Risk of severe injury or death.
► Do not make the remote start connection unless the power generator is com-
pletely ready to operate and all maintenance covers and hoods are closed.
► Only then, start the controls in automatic mode.
► Take suitable measures to make nearby operating personnel aware of the
automatic operation.
NOTICE!
Important information in the documentation for the additional components.
► Always observe the further instructions and handling guidelines in the docu-
mentation for the external component or installation.
58
Page 59
The device in-use
Setting up the remote start connec-
Do as follows to operate the power generator from the remote starting device:
tion
Fig. 8-8 Remote starting device with HARTING® socket
Conditions The power generator is ready for operation.
The starter battery is properly connected.
All consumers are switched off or disconnected from the generator.
Disconnecting the
remote start connection
1. Firmly press the locking bracket Fig. 8-8 toward the power generator.
2. Open the HARTING® socket’s safety cap Fig. 8-8 upward.
3. Push the HARTING® plug of the external connection cable onto the HARTING® socket until the stop.
4. Pull the locking bracket Fig. 8-8 toward the HARTING® plug to lock it.
The remote starting device is ready to operate.
NOTICE!
Further steps for starting and stopping the power generator are in the operating manual for the external component or installation.
NOTICE!
If the remote starting device is connected, the power generator CANNOT be
turned off from the control module ( see Cha pte r 8. 1 ). Use the EMERGENCY
STOP switch if an emergency occurs (see Chapter 7.6 ).
Do as follows to disconnect the remote start connection remote control after the generator has been switched off:
1. Firmly press the locking bracket Fig. 8-8 toward the power generator.
2. Pull the HARTING® plug of the external connection cable out of the HARTING® socket.
3. Close the HARTING® socket’s safety cap Fig. 8-8 downward.
4. Pull the locking bracket Fig. 8-8 toward you to lock the safety cap.
The remote start connection is disconnected.
59
Page 60
Optional fittings
9Optional fittings
9.1Powerlock-Box
The POWERLOCK BOX allows secure connection of powerful consumers
through individual cores with current strength up to 660 A. It therefore has
comparable output data to a traditional terminal strip, but it has the advantage of tool-free connection without an electrical expert.
To connect single cores to the POWERLOCK BOX, it must be equipped with the
right power connectors.
WARNING!
Hot arcs can occur when connecting or disconnecting under voltage.
Burn or electric shock hazard.
► Always de-energize the POWERLOCK BOX before opening or closing the
cover.
► Always de-energize the POWERLOCK BOX before inserting or removing the
plugs.
Fig. 9-1 POWERLOCK BOX
Do as follows to connect consumers through the POWERLOCK BOX to the power generator:
Conditions The circuit breaker for the POWERLOCK BOX (see power generator operat-
ing manual) is in “0” or “OFF” position.
The consumer to be connected is shut off.
Step by step1. Turn the locks left and right of the cover flap using the included square
wrench in the direction of the arrow.
2. Open the cover flap of the POWERLOCK BOX.
3. FIRST connect the plug of the PE conductor (protective earth) to the left plug
connection.
4. Insert the POWERLOCK plug connector to the connection into the provided
bushing in the POWERLOCK BOX, and lock it with a 45° clockwise turn.
5. Proceed in exactly the same way in the specified sequence with the other
POWERLOCK plug connectors.
60
Page 61
Optional fittings
6. Then secure all locks by turning the lock with the square wrench anti-clockwise to the stop.
7. Switch the circuit breaker for the POWERLOCK BOX to position “1” or “ON”.
The consumer is securely connected and can be operated.
NOTICE!
If one of the plug connections or the lock cannot be locked, one of the previous plug connections has not been locked properly.
► Turn each plug connector to the stop before inserting the next one.
► Never turn the main switch back on before all plug connectors and the lock
have been properly locked.
To undo the POWERLOCK connection, perform the steps in reverse order. Before that, be sure to turn off the affected consumer and set the circuit breaker for
the POWERLOCK BOX to “0” or “OFF” position.
9.2Dummy load
The power generator has a dummy load with an output adapted to the drive
engine. This is electrical load resistance that automatically creates a base
load as soon as the engine is running below the specified load limit.
During extended operation at low load, deposits form in the engine that,
with time, cause increased wear and possibly severe engine damage. Automatic switch-on of the dummy load increases the burn temperature
enough that the deposits are completely removed. The control electronics
turn the dummy load off automatically as soon as a consumer with adequate power is connected to the power generator. This ensures that the
generator’s full power is available at all times.
The dummy load is controlled automatically and requires no intervention by operating personnel. You can tell the dummy load is active when the control module
display shows power output when no or only minor consumers are turned on (in
the example below, 3 kW).
Fig. 9-2 Display with dummy load operating
61
Page 62
Optional fittings
9.3External battery charging
The additional option for external battery charging ensures that the drive
engine’s starter battery is permanently charged. This increases safety of
use by enabling trouble-free engine start-up (if the starter battery is in perfect condition). With this option, your Generators has an integrated automatically operated battery charger that is supplied with a 230 V AC
connection.
WARNING!
Escaping corrosive acid fumes or sulphuric acid during and after the
charging process. A risk of suffering severe or even deadly burns.
► Only work with acid-resistant protective equipment.
► Clean surfaces covered in acid immediately using adequate amounts of wa-
ter.
► Only charge the starter battery in a well ventilated environment.
WARNING!
Conditions
During the charging process, never undo the cable connections to the
starter battery. Before you start the power generator, you must end the
charging process and let the starter battery rest with good ventilation for
about 30 minutes.
Do as follows to charge your Generators’s starter battery through external battery
charging:
62
Fig. 9-3 230 V feed plug for battery charger
The Generators is ready to operate.
The starter battery is connected as specified to the drive engine’s current cir-
cuit.
Page 63
Optional fittings
1. Turn the locking ring on the feed plug clockwise to the stop to remove the
plug’s cover.
2. Connect the feed plug using a commercially available Schuko connection cable to an existing 230 V AC network.
The The battery charger turns on automatically.
The starter battery is charged.
NOTICE!
The battery charger automatically transitions to charge retention when the
set end-of-discharge voltage is reached. When the charging system is intact, overcharging is not possible, and the charge connection to the Generators can remain until next use.
63
Page 64
Maintenance
10Maintenance
Generators maintenance is described in this section. It may only be performed by qualified specialist personnel.
Maintenance and repair which is neither described in this operating manual
nor in the possibly also delivered operating and maintenance instructions
may only be undertaken by authorized service personnel from the manufacturer.
10.1Maintenance plan
Maintenance on the generator mainly involves work on the drive engine
and some work on the other equipment.
NOTICE!
Always follow the accompanying operating and maintenance manual provided by the engine manufacturer doing maintenance on the drive engine.
An overview of the schedule and scope of necessary maintenance can be found
in the maintenance plan in the engine manufacturer’s operating and maintenance manual.
10.2Maintenance work
Only authorised personnel are allowed to carry out maintenance tasks.
Carry out all of the maintenance work listed in the maintenance plan according to the instructions given in the accompanying operating and maintenance instructions provided by the engine manufacturer. This operating
manual merely describes the instructions that differ from or go beyond
those instructions.
DANGER!
Mortal danger from unintentional generator start up.
Danger of burns and being caught by rotating parts.
► Before accessing the generator you must switch it off and secure it so that
unintentional starting of the machine is prevented under all circumstances.
(see Chapter 8.1 as well).
CAUTION!
Certain surfaces on the device can get very hot whilst it is running.
Risk of burns
► Never touch any engine parts (in particular the exhaust system) for a few min-
utes after ceasing operation.
► Always leave hot engine parts to cool down before touching them.
64
NOTICE!
Also always read about the checking and maintenance work which concerns the electrical safety of the generators in the chapter “Checking the
electrical safety“.
Page 65
Maintenance
10.3Starter battery
10.3.1Replacing the battery
WARNING!
There is a risk of explosion and fire in the case of inappropriate handling
and spark development when working with the battery.
Danger from spraying sulphuric acid. Danger of suffering severe even deadly
burns and chemical burns. Danger of being blinded.
► Never lay electrically conductive parts on the starter battery.
► Flames, sparks, an open light and smoking are prohibited.
► Avoid sparks when handling cables and electrical devices, as well as electro-
static discharge.
► Avoid short-circuits.
► Wear acid-resistant protective clothing.
Conditions
Fig. 10-1 Starter battery (illustration similar)
Change the starter battery as follows:
Power generator is switched off (7.3 switchis in the “OFF” position)
Battery disconnection switch is in “OFF” position ()
You are wearing personal safety equipment.
Feed plug disconnected from the integrated battery charger.
1. Interrupt the battery circuit from the main switch (position Fig. 10-1
2. Pull off the terminal protection cap (if present) from the battery’s negative terminal and the negative cable Fig. 10-1 must always be the FIRST cable to
be disconnected from the battery.
3. Pull off the terminal protection cap (if present) from the battery’s positive terminal and remove the positive cable Fig. 10-1 from the battery LAST.
65
Page 66
Maintenance
4. Undo both fastening nuts and remove the battery’s holding bracket. Fig.
10-1
5. Remove the battery from the power generator.
The starter battery is now removed.
6. Prepare a new starter battery (follow the battery manufacturer’s instructions).
7. Place the starter battery in the battery compartment.
8. Use the retaining bracket to secure the starter battery in placeFig. 10-1 .
9. FIRST attach the positive cable Fig. 10-1 to the positive pole of the battery
and then pull the red terminal protection cap over the terminal, if necessary.
10. LAST attach the negative cable Fig. 10-1 to the negative terminal of the battery and then pull the terminal protection cap over the terminal, if necessary.
11. Turn the battery disconnection switch to ON (position Fig. 10-1 )
The starter battery has been replaced. The generator can now be started.
10.4Engine oil
The drive motor for your generator, like every internal combustion engine,
requires the required engine oil for cooling and inner cooling. It is also very
important to use the correct engine oil, both for refilling and when changing the oil, and to adhere the stipulated maintenance intervals. Refer to the
accompanying operating and maintenance instructions provided by the
engine manufacturer for all necessary information.
10.4.1Changing the engine oil
In contrast to the operating and maintenance manual for the engine, your power
generator has a built in suction pump for engine oil. All engine components important for changing engine oil and oil filters can be reached through the large
maintenance hatches on the connection and maintenance side, see Fig. 6-2 and
Fig. 6-3 .
NOTICE!
Leaking engine oil contaminates the soil and groundwater.
► Use a suitable oil catching receptacle.
► Old oil is a special waste and may only be disposed of over suitably qualified
collection points.
CAUTION!
The engine and operating equipment on the generator can get very hot
while running.
Risk of burns
► Never touch any engine parts (in particular the exhaust system) for a few min-
utes after ceasing operation.
► Allow the engine to cool off for at least five minutes before changing or check-
ing the engine oil.
66
Page 67
Maintenance
To suction out used oil, you also need an oil-resistant hose whose diameter corresponds to the pump opening (see - ) a suitable oil collection pan (not included
with delivery).Below, only the procedures that differ from the engine operating
manual are explained.
Fig. 10-2 Manual oil scavenger pump
ConditionsEnsure that the following prerequisites are met before you change the engine oil:
The generator is turned off.
When it is still hot: Wait until the engine oil has cooled down to approx. 30°C
– 50°C.
Let the cold engine appropriately warm up.
Do as follows to suction up the used oil:
1. Open the shut-off valve by pressing the valve anti-clockwise and downward.
2. Guide the hose into a suitable oil collection container.
3. Move the suction pump’s hand grip Fig. 10-2 up and down until no more used
oil comes from the engine.
4. Move the hand grip Fig. 10-2 to the bottom position.
The engine’s used oil has been suctioned out.
NOTICE!
The other procedures for changing the engine oil correspond with the details given in the engine's operating and maintenance instructions. Take
note of the other maintenance and disposal of operating equipment instructions that can be found there.
67
Page 68
Maintenance
10.5Checking the coolant
We have filled your power generator’s cooling circuit with premium coolant that
ensures long-term material compatibility, and protection from corrosion and frost.
The specification G12+ additive is free of nitrite, amine, phosphate and silicate
and is mixed to ensure frost protection to at least a –25°C ambient temperature.
So as not to impair the protective effect, use only a maximum 50% mixture for
refilling.
NOTICE!
Follow the engine’s operating and maintenance manual for all work on the
cooling system.
In deviation from this, follow these instructions:
► Check the coolant level only from the surge tank (Fig. Fig. 10-3 ) near the ra-
diator. The fluid level should always be between the Maximum and Minimum marks.
► If the tank is empty, the cooling system must be ventilated!
CAUTION!
Hot surfaces and hot, pressurized fluid. Burn hazard.
► Never open the radiator cap when the engine is running or is hot.
► Before opening the radiator cap, let the engine cool down.
► Open the radiator cap slowly, so that the overpressure in the tank can dissi-
pate slowly.
68
Fig. 10-3 Checking the coolant
Page 69
11Storage
Storage
It is important to store the device at a suitable storage location as soon as your
generator is no longer being used.
•The storage location must be roofed and must not be subjected to standing
water, aggressive vapours or soiling as well as major accumulation of dust.
•Protect your device with a cover made out of breathable material.
•Ensure that the storage temperature and air humidity lie within the specified
limits (see Technical data).
NOTICE!
Due to the limited shelf life of the different operating fluids, it is important
for decommissioning for more than one month that additional measures
for storage are taken. While doing this observe the instructions given in the
attached operating and maintenance instructions from the engine manufacturer.
69
Page 70
Disposal
12Disposal
Your device, which is an electrical or electronic device, is subject to European Directive 2012/19/EU (“WEEE directive“) which is implemented in Germany in national law through the decree regulating the use of dangerous substances in
electrical and electronic equipment (ElektroStoffV). This regulates disposal and
use of recycling waste electrical equipment. The adjacent icon with a crossed-out
wastebasket on your device states that it must not be disposed of in the household waste at the end of its service life.
As a private end-user (a so-called b2c customer) there are free collecting points
(recycling centre) near you for electrical equipment as well as possible also other
collection points available for reuse of devices. The addresses can be obtained
from your city or communal authority. In as far as the old electrical and electronic
equipment contains personal data, you are responsible yourself for its deletion
before giving it back.
Pure b2b devices (devices which, for appropriate use, or exclusively are only
used the commercial area) must not be disposed of over public collecting points
in Germany and further EU countries. Speak to your authorised ENDRESS generator dealer about handing back your recycling waste electrical equipment. The
dealer is also your point of contact for any differing regulations on the respective
country of deployment. There are also possible agreements in the purchase contract to observe.
Please observe the pertinent environmental protection regulations when disposing of the old oil. We recommend bringing the oil in a closed container to an old
oil collection centre for disposal. Never put used engine oil in the domestic waste.
Storage or introduction of old oil into nature is associated with very high fines.
An inappropriately disposed of battery can greatly damage the environment.
Give back your old battery directly free of charge to your dealer when purchasing
a new one.
Always observe the valid local regulations and laws concerning correct disposal
of all old parts and operating materials. Please contact your ENDRESS service
partner for a replacement.
70
Page 71
13Troubleshooting
The following table is an aid for you to use in a case where faults arise
during use. Based on experience a number of malfunctions can already be
removed by operating personnel or the possible causes limited. In all other
cases contact your service partner as described in the table. The same applies for faults which are not listed in the table.
If a fault cannot be rectified using the measures described here, you must shut
down your Generators and secure it against further use. Contact your service
partner and give him an explanation, not only of the symptoms but also the possible causes which you can already exclude based upon the table. The fault can
often be identified over the telephone or through a written exchange with our specialists.
NOTICE!
The following table does not make any claims to completeness and does
not mention any faults which can be caused by operating error.
► In order to avoid operating errors, please exactly follow the instructions in the
existing and delivered documentation.
► See the event and error lists in the Appendix.
Troubleshooting
MalfunctionPossible causeCorrection
The engine turns but does
not start (electrical start).
The engine turns but does
not start (manual start).
The controller is being operated incorrectly.
Maintenance of the engine was inadequate.
The oil level monitor actuates.Check oil level and refill if
Too little fuel in the tank.Refuel
The fuel filter is clogged.Replace the fuel filter.
Bad fuel in the tank.Replace the fuel, change the
The EMERGENCY-STOP button is still
locked in place
The battery connecting cables are unclamped.
Starter battery is dischargedRecharge the starter battery
Too little fuel in the tank.Refuel:
Look at the operating instructions.
Look at the engine maintenance instructions.
necessary.
fuel filter and clean out the
fuel tank if necessary
Unlock the EMERGENCYSTOP button.
Clamp or screw on the battery connecting cables.
The engine starts briefly
and then shuts down.
Tank ventilation is blocked.Contact your service partner.
The oil level is too low.Add oil.
The fuel filter is clogged.Replace the fuel filter.
71
Page 72
Troubleshooting
MalfunctionPossible causeCorrection
The engine does not rotate
No or insufficient voltage
available during idling
without a load.
Strong voltage fluctuations occur.
The engine smokes.
The starter battery is discharged or defective (only for electrical starting)
Clean the battery poles,
check teh starter battery and
recharge or replace, check
the recharging circuit
Starter defectiveReplace the starter
Engine is mechanically blockedContact your service partner
The rotational speed of the engine was
Contact your service partner.
adjusted afterwards.
The electronic controller has been al-
Contact your service partner.
tered.
The electronic controller is defective.Contact your service partner.
The engine runs irregularly.Contact your service partner.
Speed controller working erratically or
Contact your service partner.
insufficiently.
Too much oil in the engine.Drain off an excess oil.
Paper element of the air filter is dirty or
oil-soaked.
Foam element of the air filter is dirty or
dry.
Clean paper element or replace if necessary.
Clean foam element and if
necessary moisten.
Operation under extreme climatic conditions
Adapt the usage for the climatic conditions or terminate
it
The power output remains
significantly below the
nominal output
The generator has been poorly serviced
The generator has reached its wear
Perform maintenance work
Contact your service partner
limit.
Generator is not running
smoothly.
The generator is loaded beyond its
nominal output load.
Reduce power draw.
The oil pressure is too low.Insufficient engine oil in the engine.Refill with engine oil.
Generator does not start
automatically.
Remote start connection is faulty or
connection has not been made
Tab. 13-1 Troubleshooting
Remake the remote start connection
Please contact our customer service for further fault diagnosis as well as procurement of original spare parts and wear parts at
Customer service: Tel. +49 7123 973744
Email: service@endress-stromerzeuger.de
Have the item and serial number of your device ready for identification. You will
find these details on the type plate (see Fig. 3-1 ).
72
Page 73
Technical data
14Technical data
You can find the relevant technical data for your generator in the following
table.
NameValueUnit
ESE 67 IW/RSESE 90 IW/RSESE 110 IW/RS
Continuous power output [PRP] 3~
Maximum output [LTP] 3~
1)
1)
60 / 4880 / 64110 / 88[kVA / kW]
66 / 52.888 / 70.46.25 / 5[kVA / kW]
Nominal output factor ~3 / 1~0.8[cosφ]
Nominal frequency50[Hz]
Nominal speed1,500[min-1]
Nominal voltage 3~ / 1~400 / 230[V]
Nominal current [PRP] 3~ / 1~86.6115 .5144.3[A]
Empty weight (approx.)1,7901,8902,000[kg]
EngineOil quantity (including oil filter)12.8[l]
Internal tank content430[l]
Fuel consumption (at a 75% load)
Running time (at 75% load) approx.
2)
2)
13.015.418.5[l/h]
33.127.923.2[h]
Length 2,900[mm]
Width 1,090[mm]
Height 1,925[mm]
Noise pressure level at the workplace L
3)
Sound pressure level at a distance of 7m
4)
L
pA
3)
Sound power level L
WA
pA
838685[db (A)]
666969[db (A)]
919494[db (A)]
Protection Class for the generatorIP23IP23IP23
1)
Measured under standard reference conditions
2)
Average value; deviations might occur in specific cases, and are therefore non-binding
3)
Measured at a distance of 1 m and a height of 1.6 m in accordance with ISO 3744 (Part 10)
4)
Measured in accordance with ISO 3744 (Part 10)
Tab. 14-1 Power generator technical data
73
Page 74
Technical data
standard reference
conditions
Power reduction
ambient conditions
The information given in the table applies to the following operating conditions
(standard reference conditions):
NameValueUnit
Set-up height above sea level100[m]
Ambient temperature25[°C]
Relative Air humidity30[%]
The usable power output can deviate from the nominal values depending on the
actual operating conditions. The following table provides guide points:
Reference valuePower output
reduction
Set-up height above sea level1 %100 m
Ambient temperature4 %10°C
The following table shows you the applicable Operating conditions for running
the generator:
NameValueUnit
Set-up height above sea levelmax. 2,000[m]
Ambient temperature-20 to +40[°C]
Relative air humiditymax. 95, non-
condensing
Tilt anglemax. 20[°]
for each ad-
ditional
[%]
74
Page 75
15Replacement parts
Maintenance and replacement parts can be obtained quickly and easily
from your responsible ENDRESS service partner or ENDRESS dealer. You
can alternatively obtain support from our central customer service
by telephone: +49 (0) 71239737-44
by email: service@endress-stromerzeuger.de
Have the item and serial number of your device ready for identification.
As a registered user you can obtain rapid and uncomplicated access to a range
of services over our home page to obtain suitable original spare parts for maintenance and repair work. Using your internet browser please go to
https://endressparts.com
and click on the area “Documentation and replacement parts“.
Replacement parts
Fig. 15-1 Spare parts over endressparts.com
75
Page 76
Replacement parts
NOTES
76
Page 77
Keyword index
Replacement parts
A
Air filter 28
Air humidity 74
alarm list 49
ambient conditions 74
Ambient temperature 74
B
Base frame 29
Battery charger 63
Brief operating manual 15
C
Change the fuel source 56
Charge retention 62
Control mode 46
AUTO 47
MANUAL 46
OFF 46
switching 48
control module 46
Customer service 75