Emerson TCL User Manual

Model TCL
Total Chlorine Analyzer
Instruction Manual
PN 51-TCL-1056/rev.D May 2011
1.00ppm
25.0°c
WARNING
Making cable connections to and servicing this instrument require access to shock haz­ard level voltages which can cause death or serious injury.
Be sure to disconnect all hazardous voltage before opening the enclosure.
Relay contacts made to separate power sources must be disconnected before servic­ing.
Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local codes.
Unused cable conduit entries must be securely sealed by non-flammable closures to provide enclosure integrity in compliance with personal safety and environmental pro­tection requirements.
The unused conduit openings need to be sealed with NEMA 4X or IP65 conduit plugs to maintain the ingress protection rating (IP65).
For safety and proper performance this instrument must be connected to a properly grounded three-wire power source.
Proper relay use and configuration is the responsibility of the user.
No external connection to the instrument of more than 69VDC or 43V peak allowed with the exception of power and relay terminals. Any violation will impair the safety protection provided
Do not operate this instrument without front cover secured. Refer installation, operation and servicing to qualified personnel.
ESSENTIAL INSTRUCTIONS
READ THIS PAGE BEFORE PROCEEDING!
Rosemount Analytical designs, manufactures, and tests its products to meet many national and international stan­dards. Because these instruments are sophisticated techni­cal products, you must properly install, use, and maintain them to ensure they continue to operate within their normal specifications. The following instructions must be adhered to and integrated into your safety program when installing, using, and maintaining Rosemount Analytical products. Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property damage; damage to this instrument; and warranty invalidation.
• Read all instructions prior to installing, operating, and servicing the product. If this Instruction Manual is not the correct manual, telephone 1-800-654-7768 and the requested manual will be provided. Save this Instruction Manual for future reference.
• If you do not understand any of the instructions, contact your Rosemount representative for clarification.
• Follow all warnings, cautions, and instructions marked on and supplied with the product.
• Inform and educate your personnel in the proper installa­tion, operation, and maintenance of the product.
• Install your equipment as specified in the Installation Instructions of the appropriate Instruction Manual and per applicable local and national codes. Connect all products to the proper electrical and pressure sources.
• To ensure proper performance, use qualified personnel to install, operate, update, program, and maintain the product.
• When replacement parts are required, ensure that quali­fied people use replacement parts specified by Rosemount. Unauthorized parts and procedures can affect the product’s performance and place the safe oper­ation of your process at risk. Look alike substitutions may result in fire, electrical hazards, or improper operation.
• Ensure that all equipment doors are closed and protec­tive covers are in place, except when maintenance is being performed by qualified persons, to prevent electri­cal shock and personal injury.
WARNING
This product is not intended for use in the light indus­trial, residential or commercial environment, per the instrument’s certification to EN50081-2.
Emerson Process Management
2400 Barranca Parkway Irvine, CA 92606 USA Tel: (949) 757-8500 Fax: (949) 474-7250
http://www.raihome.com
© Rosemount Analytical Inc. 2011
CAUTION
SENSOR/PROCESS APPLICATION COMPATIBILITY
Wetted materials may not be compatible with process com position and operating conditions. Application compat ibility is entirely the responsibility of the user.
DANGER
HAZARDOUS AREA INSTALLATION
Installations near flammable liquids or in haz­ardous area locations must be carefully eval­uated by qualified on site safety personnel. This device is not
Intrinsically Safe or
Explosion Proof.
To secure and maintain an intrinsically safe installation, the certified safety barrier, trans­mitter, and sensor combi nation must be used. The installation system must comply with the governing approval agency (FM, CSA or BASEEFA/CENELEC) hazardous area classification requirements. Consult your analyzer/transmitter instruc tion manual for details.
Proper installation, operation and servicing of this device in a Hazardous Area Instal ­lation is entirely the responsibility of the user.
About This Document
This manual contains instructions for installation and operation of the Model TCL1056 Total Chlorine Analyzer.
The following list provides notes concerning all revisions of this document.
Rev. Level
Date Notes
A 7/07 This is the initial release of the product manual. The manual
has been reformatted to reflect the Emerson documentation style and updated to reflect any changes in the product offering.
B 11/07 Page 3 additions to 1.3 Specifications, page 5 changes to the
Analyzer (option selection) table, page 14 updated the caution box and page 15 updated section 4.3.3.
C 7/10 Updated DNV logo.
D 5/11 Revised Sec. 1, specs 1.3, replaced fig 3-3, revised sec. 4.3.3
wiring, replaced fig 4.4. add to digital communication sec 8.0, revise sec. 11.6.
MODEL TCL TABLE OF CONTENTS
MODEL TCL
TOTAL CHLORINE ANALYZER
TABLE OF CONTENTS
Section Title Page
1.0 DESCRIPTION AND SPECIFICATIONS................................................................. 1
1.1 Features and Applications ...................................................................................... 2
1.2 Specifications — Sample Conditioning System ...................................................... 3
1.3 Specifications — Model 1056 Analyzer ................................................................... 3
1.4 Specifications — Model 499ACL-02 Sensor............................................................ 4
1.5 Performance Specifications — Complete System ................................................. 4
1.6 Ordering Information and Accessories ................................................................... 5
2.0 PRINCIPLES OF OPERATION .............................................................................. 7
3.0 INSTALLATION ...................................................................................................... 8
3.1 Unpacking and Inspection ...................................................................................... 8
3.2 Installation................................................................................................................ 8
4.0 WIRING .................................................................................................................. 13
4.1 Prepare Analyzer Conduit Openings ....................................................................... 13
4.2 Provide Power to the Sample Conditioning System ................................................ 13
4.3 Make Power, Alarm, Output, and Sensor Connections in the Analyzer................... 14
4.4 Sensor Wiring .......................................................................................................... 15
5.0 START-UP .............................................................................................................. 19
5.1 Prepare the Reagent ............................................................................................... 19
5.2 Zero the Sensor....................................................................................................... 19
5.3 Start Sample Flow.................................................................................................... 19
5.4 Begin Operation and Calibrate the Sensor.............................................................. 19
6.0 DISPLAY AND OPERATION .................................................................................. 20
6.1 Display..................................................................................................................... 20
6.2 Keypad..................................................................................................................... 21
6.3 Programming the Analyzer — Tutorial.................................................................... 22
6.4 Security.................................................................................................................... 23
6.5 Using Hold ............................................................................................................... 24
6.6 Configuring the Main Display................................................................................... 25
7.0 PROGRAMMING THE ANALYZER ....................................................................... 26
7.1 General.................................................................................................................... 26
7.2 Default Setting ......................................................................................................... 26
7.3 Configuring, Ranging and Simulating Outputs........................................................ 29
7.4 Configuring Alarms and Assigning Setpoints ........................................................... 32
7.5 Configuring the Measurement ................................................................................. 36
7.6 Configuring Temperature Related Settings .............................................................. 38
7.7 Configuring Security Settings................................................................................... 39
7.8 Resetting the Analyzer............................................................................................. 40
i
ii
MODEL TCL TABLE OF CONTENTS
TABLE OF CONTENTS CONT'D.
8.0 DIGITAL COMMUNICATIONS ................................................................................ 41
9.0 CALIBRATION ....................................................................................................... 42
9.1 Introduction.............................................................................................................. 42
9.2 Calibrating Temperature .......................................................................................... 42
9.3 Calibrating Total Chlorine......................................................................................... 44
9.4 Calibrating Analog Outputs ...................................................................................... 47
10.0 MAINTENANCE ..................................................................................................... 49
10.1 Analyzer................................................................................................................... 50
10.2 Total Chlorine Sensors............................................................................................. 50
10.3 Sample Conditioning System................................................................................... 52
10.4 Simulating Inputs ..................................................................................................... 54
11.0 TROUBLESHOOTING ........................................................................................... 59
11.1 Overview.................................................................................................................. 59
11.2 Using the Diagnostic Feature .................................................................................. 59
11.3 Troubleshooting When a Fault Message is Showing............................................... 60
11.4 Troubleshooting When a Warning Message is Showing ......................................... 62
11.5 Troubleshooting When no Error Message is Showing............................................ 63
11.6 Simulating Temperature........................................................................................... 67
12.0 RETURN OF MATERIAL ........................................................................................ 68
12.1 General.................................................................................................................... 68
12.2 Warranty Repair....................................................................................................... 68
12.3 Non-Warranty Repair............................................................................................... 68
LIST OF TABLES
Number Title Page
7-1 Default Settings ...................................................................................................... 27-28
10-1 Spare Parts ............................................................................................................. 51
10-2 Replacement Parts and Reagent for Sample Conditioning System ....................... 58
MODEL TCL TABLE OF CONTENTS
LIST OF FIGURES
Number Title Page
2-1 Schematic of Sample Conditioning System and Analyzer .................................... 7
3-1 Panel Mount Dimensions ....................................................................................... 9
3-2 Pipe and Wall Mounting Dimensions ...................................................................... 10
3-3 Installing the Sample Conditioning Enclosure......................................................... 11
3-4 TCL Case Dimensions ............................................................................................ 12
3-5 Reagent Tubing Assembly ...................................................................................... 12
4-1 Power Wiring .......................................................................................................... 13
4-2 Location of power connector on power supply board. ............................................ 14
4-3 Analog output connections...................................................................................... 15
4-4 Wiring Sensor with Optimum EMI/RFI or Variopol Cable to Model 1056 Analyzer.... 16
4-5 Wiring Sensor with Standard Cable to Model 1056 Analyzer.................................. 16
6-1 Main Display .......................................................................................................... 20
6-2 Programming Screen Showing Item List................................................................. 20
6-3 Arrow Bar ............................................................................................................................................ 20
6-4 Analyzer keypad .................................................................................................... 21
6-5 Navigation keys....................................................................................................... 21
7-1 High Alarm Logic .................................................................................................... 33
7-2 Low Alarm Logic...................................................................................................... 33
7-3 Operation of the interval timer................................................................................. 33
9-1 Determination of Total Chlorine .............................................................................. 44
9-2 Sensor Current as a Function of Total Chlorine Concentration .............................. 44
10-1 Sensor Board Connections .................................................................................... 49
10-2 Sensor Parts ........................................................................................................... 51
10-3 Replacing Reagent Tubing...................................................................................... 52
10-4 Replacing Sample Tubing ....................................................................................... 53
10-5 Peristaltic Pump Tubing .......................................................................................... 54
10-6 Pump Cover ............................................................................................................ 54
10-7 Removing the Cover ............................................................................................... 54
10-8 Inserting New Tube ................................................................................................. 54
10-9 Replace the Cover .................................................................................................. 55
10-10 Bottom of the Cover ................................................................................................ 55
10-11 Tracks .....................................................................................................................55
10-12 Disconnection ......................................................................................................... 56
10-13 Removal of Screws ................................................................................................. 56
10-14 Connect the Air Inlet and Outlet Tubing to the Air Pump......................................... 56
10-15 Schematic ............................................................................................................... 56
10-16 Remove the Air Inlet Fitting..................................................................................... 57
10-17 Slide Pump Assembly Out of the Airp Pump Body.................................................. 57
iii
MODEL TCL SECTION 1
DESCRIPTION AND SPECIFICATIONS
1
SECTION 1.
DESCRIPTION AND SPECIFICATIONS
MEMBRANE-COVERED AMPEROMETRIC SENSOR.
NO TOOLS REQUIRED to change membrane.
MAINTENANCE TAKES ONLY A FEW MINUTES a month.
VARIOPOL CONNECTOR OPTION allows the sensor to be replaced without removing and
rewiring cable.
Model 1056 Chlorine Analyzer
Model TCL Sample Conditioning System
Model 499A CL-02 Sensor
LARGE, PROGRAMMABLE, BACK-LIT DISPLAY with easy to use interface.
TWO INDEPENDENT ANALOG OUTPUTS.
FOUR FULLY PROGRAMMABLE RELAYS optional.
DIGITAL COMMUNICATIONS (HART OR PROFIBUS DP) optional.
NO METAL WETTED PARTS. Ideal for seawater.
LOW SAMPLE FLOW (about 15 mL/minute) means little waste.
REAGENT-BASED SYSTEM measures true total chlorine.
FIVE GALLONS OF REAGENT lasts two months.
1.1 FEATURES
MODEL TCL SAMPLE CONDITIONING SYSTEM
The sample conditioning system permits a single sen­sor to measure total chlorine in water. The sample con­ditioning system continuously injects a solution of acetic acid (vinegar) and potassium iodide into the sample. The acid lowers the pH to between 3.5 and 4.5 and allows total chlorine in the sample to quantitatively react with the potassium iodide to produce iodine. The sensor measures the iodine concentration, and the analyzer displays the total oxidant concentration in ppm as Cl2.
MODEL 1056 CHLORINE ANALYZER
The Model 1056-24 chlorine analyzer is designed for the continuous determination of chlorine in water. It is used with the Model 499ACL-02 sensor and TCL sam­ple conditioning system.
The Model 1056 analyzer is housed in a weatherproof, corrosion-resistant, NEMA 4X enclosure. It is suitable for wall, panel, or pipe mounting. Operation of the ana-
lyzer is through a membrane keypad. A back-lit, six line display shows the total chlorine reading and tem­perature in 0.6 inch (15 mm) high characters. The dis­play can be customized to show other information, for example, output signal and diagnostics.
Menu screens for calibrating and programming are simple an intuitive. Plain language prompts in six lan­guages guide the user through procedures. Information and diagnostic screens as well as basic trouble-shooting guidelines are available at the touch of a button.
The Model 1056 has two isolated, continuously vari­able 4-20 mA outputs. Outputs can be assigned to total chlorine concentration or to temperature. Digital communications, HART or Profibus DP, are available as options.
Four fully programmable alarm relays are available as an option. Relays can be assigned to total chlorine concentration or temperature. A relay can also be
2
MODEL TCL SECTION 1
DESCRIPTION AND SPECIFICATIONS
used to signal a fault condition. A fault alarm activates when an analyzer or sensor fault occurs.
When used for the determination of total chlorine, the Model 1056 analyzer is a single input instrument. The ana­lyzer is also available in a dual input version, where the second input can be pH, conductivity, dissolved oxygen, chlorine, or turbidity. For more information about the dual input option, refer to product data sheet PDS 71-1056.
MODEL 499A CL-02 SENSOR
The Model 499ACL-02 total chlorine sensor is used in the TCL sample conditioning system. Although the sensor is called a chlorine sensor, it really measures iodine. The iodine comes from the reaction between oxidants in the sample and the acetic acid/potassium iodide reagent added by the sample conditioning system.
The sensor consists of a gold cathode and a silver anode in an electrolyte solution. A silicone membrane, permeable to iodine, is stretched over the cathode. The analyzer applies a voltage to the cathode sufficiently negative to reduce all the iodine reaching it. Because the concentra-
tion of iodine in the sensor is always zero, a concentration gradient continuously forces iodine from the sample through the membrane into the sensor.
The reduction of iodine in the sensor generates a current directly proportional to the diffusion rate of iodine through the membrane, which is directly proportional to the concen­tration of iodine in the sample. Because the iodine concen­tration depends on the amount of total chlorine in the sample, the sensor current is ultimately proportional to the total chlorine concentration.
The permeability of the membrane to iodine is a function of temperature. A Pt100 RTD in the sensor measures the tem­perature, and the analyzer uses the temperature to compen­sate the total chlorine reading for changes in membrane permeability.
Sensor maintenance is fast and easy. Replacing the mem­brane requires no special tools or fixtures. Simply place the membrane assembly on the cathode and screw the retainer in place. Installing a new membrane and replenishing the electrolyte takes only a few minutes.
3
Case: Polycarbonate NEMA 4X/CSA 4 (IP65). Dimensions: 6.10 x 6.10 x 5.15 in. (155 x 155 x 131 mm) Conduit openings: Accepts PG13.5 or 1/2 in. conduit
fittings
Display: Monochromatic back-lit LCD. Main character
height 0.6 in (15mm). Display is user-programable
Languages: English, German, Italian, Spanish, French,
Portuguese
Ambient temperature and humidity: 32 to 131°F (0 to
55°C); RH 5 to 95% (con-condensing)
Storage temperature: -4 to 140°F (-20°C and 60°C)
Power: Code -01: 115/230 VAC ±15%, 50/60 Hz. 10 W.
Code -03: 85 to 265 VAC, 47.5 to 65.0 Hz, 15 W (includes four relays)
Equipment protected by double insulation
RFI/EMI: EN-61326 LVD: EN-61010-1
Outputs: Two 4-20 mA or 0-20 mA isolated outputs.
Continuously adjustable. Linear or logarithmic. Maximum load 550 ohms. Output dampening with time constant of 5 sec is user-selectable.
Alarms relays (analyzer option -03 only): Four alarm
relays for process measurement(s) or temperature. Any relay can be configured as a fault alarm instead of a process alarm. Each relay can be configured inde­pendently and each can be programmed with interval timer settings.
Relays: Form C, SPDT, epoxy sealed
Relay Contact ratings:
5 A at 28 VDC or 300 VAC (resistive) 1/8 HP at 120/240 VAC.
Terminal Connections Rating: Power connector
(3-leads): 18-12 AWG wire size. Current output con­nectors (2-leads): 24-16 AWG wire size. Alarm relay terminal blocks: 18-16 AWG wire size
Weight/Shipping Weight: (rounded up to nearest lb or
nearest 0.5 kg): 1.5 kg (3 lb)/2.0 kg (4 lb)
MODEL TCL SECTION 1
DESCRIPTION AND SPECIFICATIONS
1.3 SPECIFICATIONS — MODEL 1056 ANALYZER
1.2 SPECIFICATIONS — SAMPLE CONDITIONING SYSTEM
GENERAL
Enclosure: Fiberglass reinforced polyester, NEMA 3
(IP53) suitable for marine environments
Dimensions: 14.5 x 13.0 x 8.6 in. (369 x 329 x 218 mm) Mounting: Wall Ambient Temperature: 32° - 122°F (0 - 50°C) Ambient Humidity: 0 - 90% (non-condensing) Power: 115 Vac, 6.9 W, 50/60 Hz;
230 Vac, 7.0 W, 50/60 Hz
Hazardous Location: The TCL sample conditioning sys-
tem has no hazardous location approvals.
Pumps:
EN 809:1998
Weight/Shipping Weight: 14 lb/16 lb (6.5 kg/7.5 kg)
SAMPLE REQUIREMENTS
Inlet Connection: compression fitting, accepts 1/4 in. OD
tubing
Drain Connection: 3/4 in. barbed fitting (must drain to
open atmosphere)
Inlet Pressure: <100 psig (791 kPa abs) Flow: at least 0.25 gph (15 mL/min) Temperature: 32 - 122°F (0 - 50°C) Total Alkalinity: <300 mg/L as CaCO3. For samples con-
taining <50 mg/L alkalinity, consult the factory.
SAMPLE CONDITIONING SYSTEM
Reagent: Potassium iodide in vinegar. Reagent Usage: 5 gallons lasts approximately 60 days. Reagent Pump: Fixed speed peristaltic pump, about
0.2 mL/min
Sample Pump: Fixed speed peristaltic pump, about 11 mL/min
Hazardous Location Approvals - Applies to analyzer
only.
Class I, Division 2, Groups A, B, C, & D Class Il, Division 2, Groups E, F, & D Class Ill T4 Tamb= 50
°C
Evaluated to the ANSI/UL Standards. The ‘C’ and ‘US’ indi­cators adjacent to the CSA Mark signify that the product has been evaluated to the applicable CSA and ANSI/UL Standards, for use in Canada and the U.S. respectively
4
MODEL TCL SECTION 1
DESCRIPTION AND SPECIFICATIONS
1.4 SPECIFICATIONS — MODEL 499ACL-02 SENSOR
1.5 PERFORMANCE SPECIFICATIONS — COMPLETE SYSTEM
Wetted Parts: Gold, Noryl
®
1
(PPO), Viton
®
2
, EPDM, Silicone
Dimensions: 1.0 x 5.6 in. (25.4 x 143 mm)
Cable: 25 ft. (7.6m) standard
Pressure Rating: 0 to 65 psig (101 to 549 kPa)
Temperature Rating: 32 to 122°F (0 to 50°C)
Electrolyte Capacity: Approximately 25 mL
Electrolyte Life: Approximately 4 months
Weight/Shipping Weight: 1 lb/3 lb (0.5 kg/1.5 kg)
1
Noryl is a registered trademark of General Electric.
2
Viton is a registered trademark of DuPont Performance Elastomers.
Linear Range: 0 to 20 ppm (mg/L) as Cl2(for higher ranges, consult factory)
Linearity (per ISO 15839): 0-10 ppm: 2%; 0-20 ppm: 3%
Response Time: Following a step change in concentration, the reading reaches 90% of final value within 7 minutes at
25°C.
Drift: At about 1.5 ppm in clean water and constant temperature, drift is typically less 0.05 ppm over two weeks.
Detection Limit (per ISO 15839): 0.02 ppm (mg/L) in clean water at room temperature
MODEL TCL SECTION 1
DESCRIPTION AND SPECIFICATIONS
1.6 ORDERING INFORMATION AND ACCESSORIES
Model TCL Reagent-Based Chlorine System. The TCL is used for the continuous determination of total chlorine in water. The TCL consists of a sample conditioning system, a reagent carboy, a sensor, and an analyzer. Reagents must be ordered separately. Regent kits for 0-5 ppm and 0-10 ppm chlorine are available. For higher ranges, consult the factory. See ACCESSORIES - Sample Conditioning System.
CODE SENSOR (optional selection)
30 499ACL-02-54 sensor with standard cable 31 499ACL-02-54-60 sensor with optimum EMI/RFI cable 32 499ACL-02-54-VP sensor with Variopol 6.0 fitting (interconnecting cable must be ordered separately)
CODE POWER (required selection)
11 115 V 50/60 Hz
12 230 V 50/60 Hz
CODE ANALYZER (optional selection)
270 1056-01-24-38-AN analyzer, no alarm relays, analog outputs 271 1056-01-24-38-HT analyzer, no alarm relays, HART 272 1056-01-24-38-DP analyzer, no alarm relays, Profibus DP 273 1056-03-24-38-AN analyzer, with alarm relays, analog outputs 274 1056-03-24-38-HT analyzer, with alarm relays, HART 275 1056-03-24-38-DP analyzer, with alarm relays, Profibus DP
MODEL
TCL REAGENT-BASED CHLORINE SYSTEM
PN Description Weight* Ship Weight**
24134-00 Air pump, 115 Vac, 50/60 Hz 1 lb (0.5 kg) 1 lb (0.5 kg) 24134-01 Air pump, 230 Vac, 50/60 Hz 1 lb (0.5 kg) 1 lb (0.5 kg) 9160578 Air pump repair kit 1 lb (0.5 kg) 1 lb (0.5 kg) 9322052 Check valve for air injection line 1 lb (0.5 kg) 1 lb (0.5 kg)
24153-00 Carboy for reagent, 5 gal/19 L, includes cap 4 lb (1.5 kg) 5 lb (2.0 kg)
9100204 Fuse, 0.25 A, 250 V, 3AG, slow blow for option -11 (115 Vac) 1 lb (0.5 kg) 1 lb (0.5 kg) 9100132 Fuse, 0.125 A, 250 V, 3AG, slow blow for option -12 (230 Vac) 1 lb (0.5 kg) 1 lb (0.5 kg) 9380094 Reagent pump, 115 Vac, 50/60 Hz 1 lb (0.5 kg) 2 lb (1 kg) 9380095 Reagent pump, 230 Vac, 50/60 Hz 1 lb (0.5 kg) 2 lb (1 kg)
9380091 Reagent pump replacement tubing 1 lb (0.5 kg) 2 lb (1 kg) 24151-00 Reagent tubing replacement kit 1 lb (0.5 kg) 2 lb (1 kg) 24135-00 Reagent uptake tubing, 6 ft (1.8 m), includes weight 1 lb (0.5 kg) 2 lb (1 kg)
9380090 Sample pump, 115 Vac, 50/60 Hz 1 lb (0.5 kg) 2 lb (1 kg)
9380093 Sample pump, 230 Vac, 50/60 Hz 1 lb (0.5 kg) 2 lb (1 kg)
9380092 Sample pump replacement tubing 1 lb (0.5 kg) 2 lb (1 kg) 24152-00 Sample tubing replacement kit 1 lb (0.5 kg) 2 lb (1 kg)
ACCESSORIES — SAMPLE CONDITIONING SYSTEM
PN Description Weight* Ship Weight**
24165-00 Acetic acid, 2 x 2.5 gal (9.5 L) bottles/case, with 25 g potassium iodide 45 lb (20.5 kg) 48 lb (22.0 kg)
(0-5 ppm total chlorine)
24165-01 Acetic acid, 2 x 2.5 gal (9.5 L) bottles/case, with 50 g potassium iodide 45 lb (20.5 kg) 48 lb (22.0 kg)
(0-10 ppm total chlorine)
24164-00 Potassium iodide, 25 g, sufficient for 5 gallons (19 L) of vinegar 1 lb (0.5 kg) 1 lb (0.5 kg)
(0-5 ppm total chlorine)
24164-01 Potassium iodide, 50 g, sufficient for 5 gallons (19 L) of vinegar 1 lb (0.5 kg) 1 lb (0.5 kg)
(0-10 ppm total chlorine)
*Weights are rounded up to the nearest whole pound or 0.5 kg.
5
6
ACCESSORIES — Sensor
PN DESCRIPTION WEIGHT* SHIP WEIGHT*
23501-02 Total Chlorine Membrane, includes one membrane assembly and 1 lb (0.5 kg) 1 lb (0.5 kg)
one O-ring
23502-02 Total Chlorine Membrane Kit, includes 3 membrane assemblies and 1 lb (0.5 kg) 1 lb (0.5 kg)
three O-rings
9210438 Total Chlorine Sensor Fill Solution, 4 oz (120 mL) 1 lb (0.5 kg) 2 lb (1.0 kg)
ACCESSORIES — 1055-24 Analyzer
PN DESCRIPTION WEIGHT* SHIP WEIGHT*
9240048-00 Tag, stainless steel, specify marking 1 lb (0.5 kg) 1 lb (0.5 kg)
23820-00 Pipe mounting kit
2 lb (1.0 kg) 3 lb (1.5 kg)
ACCESSORIES — 54eA Analyzer
PN DESCRIPTION WEIGHT* SHIP WEIGHT*
2002577 Wall and two inch pipe mounting kit
2 lb (1.0 kg) 3 lb (1.5 kg)
23545-00 Panel mounting kit
2 lb (1.0 kg) 3 lb (1.5 kg)
23554-00 Cable glands, kit (Qty 5 of PG 13.5) 1 lb (0.5 kg) 1 lb (0.5 kg)
9240048-00 Stainless steel tag (specify marking) 1 lb (0.5 kg) 1 lb (0.5 kg)
*Weights are rounded up to the nearest whole pound or 0.5 kg.
FOR FIRST TIME VARIOPOL INSTALLATIONS
PART # DESCRIPTION
23747-06 Interconnecting cable, VP 6, 2.5 ft (0.8 m)
23747-04 Interconnecting cable, VP 6, 4 ft (1.2m)
23747-02 Interconnecting cable, VP 6, 10 ft (3.0 m)
23747-07 Interconnecting cable, VP 6, 15 ft (4.6 m)
23747-08 Interconnecting cable, VP 6, 20 ft (6.1 m)
23747-09 Interconnecting cable, VP 6, 25 ft (7.6 m)
23747-10 Interconnecting cable, VP 6, 30 ft (9.1 m)
23747-03 Interconnecting cable, VP 6, 50 ft (15.2 m)
23747-11 Interconnecting cable, VP 6, 100 ft (30.5 m)
Total chlorine by definition is the iodine pro­duced in a sample when it is treated with potassium iodide at a pH between 3.5 and 4.5. Typically, acetic acid (or vinegar) is used to adjust the pH.
The total chlorine analyzer consists of a sam­ple conditioning system, which injects the reagent into the sample, and a sensor and analyzer, which measure the amount of iodine produced. Figure 2-1 shows the sample condi­tioning system. The sample enters the sample conditioning enclosure and flows to an over­flow sampler from which the sample pump takes suction. Excess sample drains to waste. At the same time, the reagent pump draws reagent, a solution of potassium iodide in vinegar, from the reagent carboy and injects it into the suction side of the sample pump. The sample and reagent mix as they pass through the pump, and total chlorine in the sample is converted to the chemically equivalent amount of iodine. The flow rates are 11 mL/min for the sample and 0.2 mL/min for the reagent.
The treated sample next enters the flow cell. Bubbles injected into the flow cell produce turbulence, which improves the stability of the reading. A membrane-covered amperometric sensor in the flow cell measures the concentration of iodine. The analyzer receives the raw signal from the sensor and displays the concentration of total chlorine. Display units are ppm (mg/L) chlorine as Cl2. The treated sample leaves the flow cell and drains to waste along with the excess sample.
SECTION 2. PRINCIPLES OF OPERATION
MODEL TCL SECTION 2
PRINCIPLES OF OPERATION
FIGURE 2-1. Schematic of Sample Conditioning
System and Analyzer.
7
3.1 UNPACKING AND INSPECTION
Inspect the shipping containers. If there is damage, contact the shipper immediately for instructions. Save the boxes. If there is no apparent damage, unpack the containers. Be sure all items shown on the packing list are pres­ent. If items are missing, notify Rosemount Analytical immediately.
3.2 INSTALLATION.
3.2.1 General Information
1. Although the analyzer and sample conditioning system are suitable for outdoor use, do not install them in direct sunlight or in areas of extreme temperature.
2. Install the analyzer and sample conditioning system in an area where vibration and electromagnetic and radio frequency interference are minimized or absent.
3. Keep the analyzer and sensor wiring at least one foot from high voltage conductors. Be sure there is easy access to the analyzer and sample conditioning system.
4. The analyzer is suitable for panel, pipe or wall mounting. The sample conditioning enclosure must be mount­ed on a wall. Provide adequate room beneath the enclosure for the 5-gallon reagent carboy.
5. Be sure that the distance between the analyzer and sample conditioning cabinet does not exceed the length of the sensor cable.
3.2.2 Install the Analyzer
1. Refer to the appropriate figure for installation details.
2. See section 4.1 for more information about the conduit openings.
3. See Section 4.2 for wiring instructions.
SECTION 3. INSTALLATION
MODEL TCL SECTION 3
INSTALLATION
CAUTION
The TCL Total Chlorine sample conditioning system
is NOT suitable for use in hazardous areas.
Type of Mounting Figure
Panel 3-1
Wall or Pipe 3-2
8
MODEL TCL SECTION 3
INSTALLATION
Bottom View
Front View
Side View
FIGURE 3-1 PANEL MOUNTING DIMENSIONS
INCH
MILLIMETER
154.9
6.1
154.9
6.1
126.4
5.0
17.13
1.1
126.4
5.0
)
(
76.2
3.0
41.4
1.6
152.73
6.0
9
Bottom View
Front View
Side View
Side View
Wall / Surface Mount
Pipe Mount
154.9
6.1
102
4.0
187
7.4
154.9
6.1
232
9.1
33.5
1.3
130
5.1
165
6.5
232
9.1
130
5.1
33.5
1.3
165
6.5
108.9
4.3
45.21
1.8
80.01
3.2
71.37
2.8
10
INCH
MILLIMETER
FIGURE 3-2 PIPE AND WALL MOUNTING DIMENSIONS
(Mounting bracket PN:23820-00)
MODEL TCL SECTION 3
INSTALLATION
3.2.3 Install the Sample Conditioning Enclosure
1. Refer to Figures 3-3, 3-4, and 3-5 for installation details.
2. Connect the sample line to the sample conditioning system. Use ¼-inch OD hard plastic or stainless steel tubing. If dechlorinated water is being measured, provide a way for occasionally substituting a chlorinated water sample for the dechlorinated sample. Chlorinated water is needed to calibrate the sensor and to check its response.
3. If a grab sample tap is not already available, install one in the process piping. Choose a point as close as pos­sible to the sample line supplying the TCL. Be sure that opening the sample valve does not appreciably alter the flow of sample to the instrument.
4. Connect the drain to a length of ¾-inch ID flexible plastic tubing. The sample must drain to open atmosphere.
5. Find the reagent tubing and fitting in the plastic bag taped to the inside of the enclosure door. Screw the reagent fitting onto the bulkhead fitting at the bottom left of the enclosure. Pass the reagent tubing through the hole in the carboy cap. Be sure the plastic weight will be inside the carboy when the cap is in place. Attach the reagent tubing to the barbed connector. See Figure 3-5.
6. Place the blue plastic carboy beneath the enclosure. Screw the cap and tubing assembly on to the carboy. To prepare reagent, see Section 5.2.
3.2.4 Install the Sensor
1. From inside the sample conditioning enclosure, thread the sensor cable or VP cable through the gland on the upper left side. Leave about one foot of cable inside the enclosure.
2. Wire the cable to the analyzer. Refer to Section 4.4.
3. Remove the nut and adapter from the flow cell. Slip the nut over the end of the sensor. Thread the adapter onto the sensor. Hand tighten only. If you are using a VP cable, connect the cable to the sensor. The connec­tor and receptacle are keyed to ensure proper mating. Once the key has slid into place, tighten the connec­tion by turning the knurled ring clockwise. Remove the protective cap from the end of the sensor.
4. Insert the sensor in the flow cell. Hand tighten the nut.
FIGURE 3-3. Installing the Sample Conditioning Enclosure
11
analyzer
sensor cable
TCL
sample inlet 1/4
inch OD tubing
sample tap
process piping
enclosure
drain 3/4 inch ID barbed fitting
reagent
bottle
MODEL TCL SECTION 3
INSTALLATION
FIGURE 3-4. TCL Case Dimensions
INCH
MILLIMETER
FIGURE 3-5. Reagent tubing assembly
12
13
MODEL TCL SECTION 4
WIRING
SECTION 4. WIRING
4.1 PREPARE ANALYZER CONDUIT OPENINGS
The analyzer enclosure has six conduit openings. Four conduit openings are fitted with conduit plugs.
Conduit openings accept 1/2-inch conduit fittings or PG 13.5 cable glands. To keep the case watertight, block unused openings with NEMA 4X or IP65 conduit plugs.
NOTE
Use watertight fittings and hubs that comply with the requirements of UL514B. Connect the conduit hub to the conduit before attaching the fitting to the analyzer (UL508-26.16).
4.2 PROVIDE POWER TO THE SAMPLE CONDITIONING SYSTEM
NOTE
1. Be sure the pump switches on the wiring access panel are in the off position.
2. Remove the four screws securing the wiring access panel. Pull the panel out of the way to reveal the power terminal strip.
3. Insert the power cable through the strain relief connection labeled power (see Figure 3-4). Wire the power cable to the terminal strip as shown in Figure 4-1. Do not apply 230 Vac power to a 115 Vac TCL (Model option
-11). Doing so will damage the instrument.
4. Leave the pump power switches off until ready to start up the unit. See Section 5.
FIGURE 4-1. Power Wiring
Model option -11 115 Vac only Model option -12 230 Vac only
Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local code.
WARNING
RISK OF ELECTRICAL SHOCK
Provide a switch or breaker to disconnect the sample conditioning cabinet from the main power supply. Install the switch or breaker near the unit and identify if as the disconnecting device for the sample conditioning system.
14
MODEL TCL SECTION 4
WIRING
4.3 MAKE POWER, ALARM, OUTPUT, AND SENSOR CONNECTIONS IN THE ANALYZER
4.3.1 Power
Wire AC mains power to the power supply board, which is mounted vertically on the left hand side of the analyzer enclosure. The power connector is at the top of the board. Unplug the connector from the board and wire the power cable to it. Lead connections are marked on the connector. (L is live or hot; N is neutral, the ground connection has the standard symbol.)
AC power wiring should be 14 gauge or greater. Run the power wiring through the conduit opening nearest the power terminal. Provide a switch or breaker to disconnect the analyzer from the main power supply. Install the switch or breaker near the analyzer and label it as the disconnecting device for the analyzer.
Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local code.
WARNING
RISK OF ELECTRICAL SHOCK
If your 1056 analyzer does not have alarm relays (options -270, -271, or -272) you must set the black and red AC power switch located below the power terminal to the correct AC voltage. The analyzer is shipped with the switch in the 230 VAC position. For operation at 110-120 VAC, slide the switch upward so that 115 VAC is showing.
If your 1056 analyzer has
alarm relays (options -273, -274, or -275) there is no switch setting to make. The
analyzer automatically detects the AC voltage.
CAUTION
4.3.2 Analog output wiring
Two analog current outputs are located on the main circuit board, which is attached to the inside of the enclosure door. Figure 4-3 shows the location of the terminals. The connectors can be detached for wiring. TB-1 is output 1. TB-2 is output 2. Polarity is marked on the circuit board.
For best EMI/RFI protection, use shielded output signal cable enclosed in earth-grounded metal conduit.
Keep output signal wiring separate from power wiring. Do not run signal and power or relay wiring in the same conduit or close together in a cable tray.
FIGURE 4-2. Analog output connections. The analog outputs are on the main board near the hinged end of the enclosure door.
MODEL TCL SECTION 4
WIRING
15
4.4 SENSOR WIRING
1. Shut off power to the analyzer.
2. Locate the chlorine signal board.
3. Insert the sensor cable through the conduit opening nearest the chlorine board.
4. Slide the board forward to gain access to the wires and terminal screws.
5. Connect the sensor cable to the chlorine board. Refer to Figure 4-4 or 4-5.
6. Once the cable has been connected, slide the board fully into the enclosure while taking up the excess
cable through the conduit opening. If you are using a cable gland, tighten the gland nut to secure the cable and ensure a sealed enclosure.
Slot 1 (left) Slot 2 (center) Slot 3 (right)
communication input 1 (chlorine) input 2 (optional)
4.3.3 Alarm wiring.
The alarm relay terminal strip is located just below the power connector on the power supply board. See Figure 4-3.
Keep alarm relay wiring separate from signal wiring. Do not run signal and power or relay wiring in the same conduit or close together in a cable tray.
WARNING
Exposure to some chemicals may degrade the sealing properties used in the following devices: Zettler Relays (K1-K4) PN AZ8-1CH12DSEA
FIGURE 4-3. Alarm relay connections.
16
MODEL TCL SECTION 4
WIRING
4.5 APPLY POWER TO THE ANALYZER AND COMPLETE QUICK START
1. Once all wiring connections are secured and verified, apply power to the analyzer.
2. When the analyzer is powered up for the first time, Quick Start screens appear. Using Quick Start is easy.
a. A backlit field shows the position of the cursor.
b. To move the cursor left or right, use the keys to the left or right of the ENTER key. To scroll up or down or to increase
or decrease the value of a digit, use the keys above and below the ENTER key. Use the left and right keys to move
the decimal point.
c. Press ENTER to store a setting. Press EXIT to leave without storing changes. Pressing EXIT also returns the
display to the initial Quick Start screen.
d. A vertical black bar with a downward pointing arrow on the right side of the screen means there are more items to
display. Continue scrolling down to display all the items. When you reach the bottom of the list, the arrow will point up.
FIGURE 4.4. Wiring Sensor with Optimum EMI/RFI or Variopol Cable to Model 1056 Analyzer
FIGURE 4.5 Wiring Sensor with Standard Cable to Model 1056 Analyzer
3. Choose the desired language. Scroll down to display more choices.
4. Choose total chlorine for sensor 1 (S1).
5. Choose the desired units for chlorine.
Language
Francais Espanol Deutsch
English
S1 Measurement Free Chlorine pH Independ. Free Cl Total Chlorine Monochloramine
Total Chlorine
Units
mg/L
ppm
Loading...
+ 54 hidden pages