Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion and/or re
causing property damage and personal injury
or death.
Tartarini™ regulators must be installed,
operated, and maintained in accordance
with federal, state, and local codes, rules
and regulations, and Emerson Process
Management Regulator Technologies, Inc.
(Regulator Technologies) instructions.
If the product vents gas or a leak develops in
the system, service to the unit may be required.
Failure to correct trouble could result in a
hazardous condition.
Call a gas service person to service the
unit. Only a quali ed person must install or
service the product.
Introduction
Scope of the Manual
This manual provides instructions for installation,
adjustment, maintenance, and parts ordering information
for the Type FL relief valve or backpressure regulator
with a Type PRX/182 pilot sold in North America. Any
accessories used with this relief valve or backpressure
regulator are covered in their respective manuals.
Description
The Type FL relief valve or backpressure regulator are
accurate pilot-operated, relief valve or backpressure
regulators designed for high-pressure transmission/city gate,
large capacity distribution systems, and power plant feeds.
The Type FL relief provides smooth, reliable operation, tight
shutoff, and long life. The main valve actuator moves in
response to the pilot loading pressure to control upstream
system pressure.
Figure 1. Type FL Relief Valve or Backpressure Regulator
with PRX Series Pilot
Principle of Operation
A pressure relief valve is a throttling pressure control
device that opens and closes to ensure the inlet pressure
does not rise above a predetermined pressure. Tartarini™
relief valves cannot be used as ASME safety relief valves.
A backpressure regulator is a device that controls and
responds to changes in the upstream pressure. It functions
the same as a relief valve in such a way that it opens on
increasing upstream pressure.
Relief Valve
As long as the inlet pressure is below the set pressure,
the pilot control spring keeps the pilot valve plug closed. Inlet
pressure passes through the restrictor and registers as loading
pressure on the main valve diaphragm chamber. Force from
D103582X012
www.tartarini-naturalgas.com
Page 2
Type FL
Specications
The Specications section gives some general specications for the Type FL relief valve or backpressure regulator.
The nameplates give detailed information for a particular relief valve or backpressure regulator as it comes from
the factory.
Body Sizes
Type FL: NPS 1, 2, 3, 4, 6, 8, and 10 /
DN 25, 50, 80, 100, 150, 200, and 250
Main Valve End Connection Style and
Pressure Ratings
CL300 RF: 740 psig / 51.0 bar
CL600 RF: 1480 psig / 102 bar
(1)
(3)
(3)
Maximum Inlet and Outlet (Casing) Pressure
1480 psig / 102 bar
(3)
Minimum Buildup Pressure (Refer to Table 2)
Set Pressure Ranges
See Table 2
(1)
Temperature Capabilities
Nitrile (NBR) or Fluorocarbon (FKM) Disk:
-4 to 140°F / -20 to 60°C
Nitrile (NBR) Disk:
-20 to 140°F / -29 to 60°C
Approximate Weights (Including Pilot)
Type FL
NPS 1 / DN 25: 68 pounds / 31 kg
NPS 2 / DN 50: 132 pounds / 60 kg
NPS 3 / DN 80: 326 pounds / 148 kg
NPS 4 / DN 100: 443 pounds / 201 kg
NPS 6 / DN 150: 1058 pounds / 480 kg
NPS 8 / DN 200: 1367 pounds / 620 kg
NPS 10 / DN 250: 2623 pounds / 1190 kg
Pilot Spring Case Vent Connection
1/4 NPT tapping in pilot body
Pressure Registration
External through upstream control line. Pilot
spring case connection / Pilot body “B” port vent
connection 1/4 NPT tapping.
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Type PRX Fluorocarbon (FKM) elastomer is limited to 0°F / -18°C.
3. At average ambient temperature.
4. Meets or exceeds ANSI/FCI 70-3 Class VI/VII leakage limits at maximum operating differential pressure.
(1)(2)
(4)
Table 1. Pilot Set Pressure Control
PILOT CONTROL INFORMATION
RELIEF SET
PILOT TYPE
PRX/182
PRX-AP/182435 to 116030.0 to 80.0GD27379X012Clear0.3358.513.94100116080.01480102
2
PRESSURE RANGE
Part NumberColor
psigbarInchmmInchmmpsigbarpsigbar
29 to 1162.0 to 8.0GD25522X012Black0.1573.992.1654.9
73 to 2905.0 to 20.0GD25520X012Gold0.1975.002.0151.1
217 to 60915.0 to 42.0GD25519X012Red0.2365.992.0151.1
Wire DiameterFree Length
Maximum
Operating
Pressure
60942.0
Maximum
Emergency
Pressure
1480102
Page 3
Type FL
PORT BEXHAUST
SPRINGCASE VENT
PORT A
PORT L
PORT S
PORT A
SPRING
CASE VENT
PORT B
EXHAUST
PORT L
PORT S
M1205
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE
Figure 2. Type FL Relief Valve or Backpressure Regulator Operational Schematic
Table 2. Pilot Set Pressure Build Up
BUILD-UP OVER
SET PRESSURE
PILOT TYPE
SET PRESSURE CONTROL
RANGE, SPRING PART NUMBER
AND COLOR
SET PRESSURE
(1)
NEEDED TO BEGIN
OPENING VALVE
(2)
psigbarpsigbarpsigbarpsigbar
302.11.20.082.80.191.00.69
PRX/182
29 to 116 psig / 2.0 to 8.0 bar
GD25522X012
Black
73 to 290 psig / 5.0 to 20.0 bar
GD25520X012
Gold
604.11.70.123.70.261.00.69
805.51.90.134.00.281.00.69
1006.92.80.195.00.351.00.69
755.22.30.165.10.352.10.14
1006.92.50.175.90.412.10.14
15010.33.50.246.80.472.10.14
20013.84.00.288.00.552.10.14
25017.24.00.288.90.612.10.14
22515.54.00.2810.20.702.70.19
217 to 609 psig / 15.0 to 42.0 bar
GD25519X012
Red
30020.74.00.2810.50.722.70.19
40027.64.10.2810.70.742.70.19
45031.04.30.3011.00.762.70.19
45031.04.30.3011.00.763.30.23
PRX-AP/182
435 to 1160 psig / 30.0 to 80.0 bar
GD27379X012
Clear
50034.54.50.3111.10.773.30.23
60041.45.10.3511.10.773.30.23
105072.45.10.3511.10.773.30.23
1. Set Pressure is de ned as the pressure at which the pilot starts-to-discharge.
2. Crack Point Pressure of the main valve of the inlet pressure build-up over the set pressure at which the main valve starts audible ow.
3. Inlet pressure build-up over the set pressure for the main valve to achieve wide-open ow capacity.
BUILD-UP OVER
SET PRESSURE
NEEDED TO FULLY
OPEN MAIN VALVE
PRESSURE DROP
BELOW SET
PRESSURE NEEDED
(3)
TO RESEAT PILOT
3
Page 4
Type FL
the main spring, in addition to pilot loading pressure, provide
loading pressure to keep the main valve diaphragm and plug
assembly tightly shut off.
When the inlet pressure rises above the set pressure,
the pressure on the pilot diaphragm overcomes the pilot
control spring and opens the pilot valve plug. The pilot
then exhausts the loading pressure from the main valve
diaphragm chamber. The pilot continuously exhausts gas
when the inlet pressure is above the set pressure. The inlet
pressure unbalance overcomes the main spring force and
opens the diaphragm and plug assembly.
As the inlet pressure drops below the set pressure, the pilot
control spring closes the pilot valve plug and the exhaust to
atmosphere stops. Force from the main spring, along with pilot
loading pressure, pushes the diaphragm and plug assembly
onto the knife-edged seat, producing tight shutoff.
Backpressure Regulator
As long as inlet pressure remains below setpoint, the pilot
control spring keeps the pilot valve plug closed. Inlet pressure
passes through the upper port around the upper portion of the
valve plug and then through the hollow passage in that valve
plug. Force from the main spring, in addition to pilot loading
pressure, provide downward loading pressure to keep the main
valve diaphragm and plug assembly tightly shut off. When inlet
pressure rises above the set pressure, pressure on the pilot
diaphragm overcomes the control spring to close the upper
port and stroke the valve plug to open the lower port. The pilot
exhausts loading pressure from the main valve diaphragm
chamber. Inlet pressure unbalance overcomes the main spring
force to open the diaphragm and plug assembly.
or pressure-limiting devices to prevent service
conditions from exceeding those limits. Also,
be sure the installation is in compliance with
all applicable codes and regulations.
Additionally, physical damage to the relief
valve or backpressure regulator could break
the pilot off the main valve, causing personal
injury and property damage due to bursting
of pressure-containing parts. To avoid such
injury and damage, install the regulator in a
safe location.
1. Only personnel qualied through training and
experience should install, operate, and maintain a relief
valve or backpressure regulator. Before installation,
make sure that there is no damage to, or debris in
the main valve body or pilot. Also, make sure that all
tubing and piping are clean and unobstructed.
CAUTION
After assembly, check for shutoff and
leakage to atmosphere.
2. A Type FL relief valve or backpressure regulator may
be installed in any orientation, as long as ow through
matches the direction of the arrow on the main
valve body.
3. Apply a good grade of pipe compound to the external
pipeline threads for a screwed body, or use suitable
line gaskets for a anged body. Use approved piping
procedures when installing the valve.
While the main valve is throttling, the upper port of the pilot
stays closed. The pilot exhausts only when it repositions the
main valve. As inlet pressure drops below setpoint, the pilot
control spring overcomes the diaphragm force to stroke the
valve plug down to close the lower port and open the upper
port. Force from the main spring, along with pilot loading
pressure, pushes the diaphragm and plug assembly onto the
knife-edged seat, producing tight shutoff.
Installation
WARNING
!
Personal injury or equipment damage, due
to bursting of pressure-containing parts may
result if this relief valve or backpressure
regulator is overpressured or is installed
where service conditions could exceed the
limits given in the Specication section and
on the appropriate nameplate, or where
conditions exceed any rating of the adjacent
piping or piping connections. To avoid such
injury or damage, provide pressure-relieving
WARNING
!
When used in relief valve service, the Type FL
main valve and pilot both exhaust gas. In
hazardous or ammable gas service, personal
injury, death, or property damage may occur
due to re or explosion of vented gas that
has accumulated. To prevent such injury or
damage, provide piping or tubing to vent the
gas to a safe location. The exhaust piping
must be designed and installed to guard
against excessive ow restriction. This piping
must be protected against condensation or
debris that could clog it.
For safety during shutdown, vent valves
are required immediately upstream
and downstream of the main valve on a
backpressure or bypass installation.
4. If system operation during maintenance is required,
install isolating and vent valves as needed.
4
Page 5
Type FL
5. If the vent assembly (key 12, Figure 7) remains in the
pilot body, then it must be pointed down if possible or
otherwise protected. If the exhaust is to be piped to
the main valve exhaust or remotely vented, remove
the vent assembly and install tubing or piping into
the 1/4 NPT pilot exhaust connection. There are two
vent connections need to be piped away. Protect the
open end of the exhaust pipe by installing a screened
vent cap.
6. The pilot spring case vent (key 12, Figure 7) must be
kept open to atmospheric pressure. Protect the vent
assembly from icing, moisture, or debris that may cause
blockage, as required. To change the vent orientation,
twist the vent assembly in the spring case. To remotely
vent the pilot spring case, pilot body vent need to be pipe
away as well and install tubing or piping into the 1/4 NPT
spring case vent tapping. Protect the open end of the
vent line by installing a screened vent cap.
7. The Type PRX pilot connections are 1/4 NPT. Connect
the inlet control (sense) line from the “A” port, Figure 6
(key 55), on the bottom of the Type PRX pilot to a straight
run of pipe 6 to 10 pipe diameters from the relief valve or
backpressure regulator inlet as shown in Figure 2, using
3/8 inch / 9.5 mm or larger outside diameter tubing. If such
a distance is not practical, connect the control line away
from elbows, swages, nipples, or any area where abnormal
ow velocities occur.
Startup and Shutdown
CAUTION
If pressure is introduced rst to the main
valve before the pilot, the main valve may
go wide-open and subject the downstream
system to full inlet pressure.
Note
The maximum inlet pressure for specic
constructions are given in Table 1. Use a
pressure gauge to monitor inlet pressure
during startup.
Relief Installation
Startup
1. Close vent valve (not shown).
2. Slowly open block valve and hand valve, if installed.
3. Adjust the pilot as needed.
Shutdown
1. Close block valve and hand valve, if installed.
2. Slowly open vent valve (not shown).
Backpressure Installation
Startup
1. Close upstream and downstream vent valves
(not shown).
2. Slowly open upstream block valve rst and then slowly
open downstream block valve.
3. Adjust the pilot as needed. If the pilot is not piped
downstream, make sure the pilot exhaust is pointed in
the correct direction.
Shutdown
1. Close upstream block valve rst and then close the
downstream block valve.
2. Open downstream and upstream vent valves
(not shown).
Pilot Adjustment (See Figure 7)
If set pressure adjustment is necessary, monitor relief (inlet)
pressure with a gauge during the adjustment procedure.
Loosen the locknut (key 2). Turn the adjusting screw (key 1)
into the spring case to increase the set pressure. Turn
the adjusting screw out of the spring case to decrease the
set pressure. When adjustment is completed, tighten the
locknut to lock the adjusting screw in position.
The adjustment of the relief valve or backpressure
regulator is performed by means of the pilot adjusting
screw, which varies the compression of the control spring.
Maintenance
The relief valve and backpressure regulator parts are subject to
normal wear and must be inspected periodically and replaced
as necessary. The frequency of inspection and replacement
depends on the severity of service conditions and on applicable
federal, state and local codes and regulations. Use only
replacement parts manufactured or furnished by Tartarini™.
WARNING
!
To avoid personal injury or property damage
from sudden release of pressure, isolate
the relief valve or backpressure regulator
from the pressure system, and release all
pressure from the pilot and main valve before
performing maintenance operations.
To prevent personal injury or damage to the
equipment during storage, installation or
maintenance operations, proper supports
shall be used to keep the Type FL relief valve
or backpressure regulator from rolling while
it is sitting on a at surface.
5
Page 6
Type FL
38
TOP VIEW
L1
37A
LEGACY TRAVEL INDICATOR DETAIL
40
34
38
36
35
33
L1
S1
L1
38
TOP VIEW
37B
IMPROVED TRAVEL INDICATOR DETAIL
40
34
38
36
66
35
33
L1
S1
P1764
APPLY LUBRICANT (L) / SEALANT (S)
L1 = LITHIUM HYDROXYSTEGRATE NLGI 2 GRADE GREASE
S1 = ANAEROBIC METHACRYLATE SEALANT FOR NUTS AND BOLTS
1. Lubricant and sealant must be selected such that they meet the temperature requirements.
(1)
:
Figure 3. Type FL Travel Indicator Assembly
Main Valve (Refer to Figure 5)
Main Valve Pad/Disk Replacement
1. Remove outlet ange (key 22) by removing socket head
screws (key 5).
2. Remove pad/disk holder assembly and O-ring (key 18).
For NPS 8 and 10 / DN 200 and 250, the pad/disk
holder remains attached to the outlet ange and no
dismounting is necessary.
3. Remove pad/disk (key 20) from pad/disk holder
(key 19) by removing socket head screw (key 25)
and pad/disk retainer (key 21), replace pad/disk
if necessary.
4. Reinstall the pad.
5. Reassemble in reverse order. Refer to Table 3 for torque
values. Tighten all bolts using a star pattern and repeat
2 to 3 times to ensure proper torque.
Main Valve Diaphragm Maintenance
1. Place main valve with inlet side up.
2. Remove the travel indicator assembly by removing the
indicator cover (key 40) and indicator bushing (key 38).
Check O-ring (key 37B), replace if necessary. Remove
the indicator support (key 36). Check O-ring (key 35),
replace if necessary. Lift out indicator stem assembly
(keys 33 and 34).
3. Remove inlet ange (key 1) by removing socket head
cap screws (key 5). Due to force created by the spring
(key 6), take care when removing inlet ange.
4. Lift out spring (key 6). Remove hex head cap screws,
washers, and nuts (keys 9, 14, and 15). Lift off the
inlet cover (key 11).
5. Remove diaphragm assembly by removing screws
(key 27) to separate the outlet and the inlet plates
(keys 12 and 8). Check diaphragm (key 10) and O-rings
(keys 26 and 28) for damage and replace if necessary.
6
Page 7
Type FL
Check sleeve (key 16) seating surface for damage. Check
O-rings (keys 3 and 4) and anti-friction rings (key 2),
replace if necessary.
6. Reassemble in reverse order. Refer to Table 3 for torque
values. Tighten all bolts using a star pattern and repeat
2 to 3 times to ensure proper torque.
Type FL Travel Indicator Maintenance
A new and improved version of the travel indicator has
been phased in during 2013. The new version improves the
O-ring stem seal to minimize leakage and extend service
life. The components of the legacy and new versions are
not interchangeable. If maintenance is performed on the
travel indicator, it is recommended to replace the entire travel
indicator assembly with the new version. Part numbers for
the assemblies are shown in the parts list. Figure 3 shows
the difference between the designs. The spare parts kits will
support either design. Take care to use the correct O-ring
(key 37A or 37B) when performing maintenance, see parts list
for the appropriate part number.
2. Loosen travel indicator bushing (key 38) and remove it
by sliding it over the travel indicator stem (key 34).
3. Remove indicator tting (key 36) and inspect O-ring
(key 35). Remove O-ring (key 37B) and back-up rings
(key 66). Replace and lubricate O-ring if damaged.
Pull up on the travel indicator stem (key 34) to force the
spring collet (key 33) out of the diaphragm head groove.
Examine these parts and the stem for wear and replace
if necessary.
4. Insert the travel indicator stem (key 34) and spring
collet (key 33) back into the diaphragm head groove.
Replace the indicator tting (key 36) and O-ring
(key 35) and tighten with a reference torque of
3.7 foot-pounds / 5.0 N•m.
5. Lubricate the O-ring (key 37B) and back-up rings
(key 66, 2 required). Place one back-up ring on the
stem (key 34) followed by the O-ring and then the other
back-up ring. Push into groove of the indicator tting
(key 36).
6. Slide the travel indicator bushing (key 38) over the
travel indicator stem (key 34) and tighten rmly
in place.
7. Replace the travel indicator cover (key 40) and tighten
rmly in place.
Type PRX/182 Pilot Maintenance (Figure 7)
Lower Diaphragm Maintenance
1. Disconnect pilot and remove it from the line.
2. Remove machine screws (key 10) from lower cover
(key 21) and the separate lower cover from the body
(key 16).
3. Use a wrench to hold the stem (key 23) and break loose
the stem nut (key 20). Remove the stem nut and washer
(key 11).
4. Remove the diaphragm plate (key 13), diaphragm
(key 14), lower diaphragm plate (key 15), and O-ring
(key 18). Inspect parts for damage or wear, replace
if necessary.
5. Lightly lubricate the O-ring (key 25). Place O-ring
over the stem (key 23) and press it down into the body
(key16).
6. Lightly lubricate the rims of the diaphragm (key 14) and
place it on top of the lower diaphragm plate (key 15).
Set the diaphragm plate (key 13) on the diaphragm
(key 14).
7. Lightly lubricate the O-ring (key 18) and place it in the
lower cover (key 21).
8. Place the washer (key 11) and stem nut (key 20) on
the stem (key 23) and tighten. If also performing Upper
Case Maintenance, skip to step 2 of the Upper Case
Maintenance section.
9. Insert washers (key 11) and machine screws (key 10) in
the lower cover (key 21) and tighten uniformly to ensure
proper seal.
Upper Diaphragm Maintenance
1. Disconnect pilot and remove it from the line.
2. Loosen locknut (key 2) and back out adjusting screw
(key 1) until compression is removed from the spring.
Remove cap (key 3).
3. Lift the upper spring seat (key 6), spring (key 7), and
O-ring (key 4) out of the spring case (key 8). Inspect
O-ring and replace if necessary.
4. Remove the machine screws (key 10) and the washers
(key 11), separate the spring case (key 8) from the body
(key 16), and lift the lower spring seat (key 9) away from
upper diaphragm nut (key 26). Use a wrench to hold
stem (key 23) securely while removing the upper
diaphragm nut.
CAUTION
Always remove spring (key 7) tension before
performing maintenance on this unit. To
remove spring tension, loosen locknut (key 2)
and back out adjusting screw (key 1) until
compression is removed from the spring.
5. Remove remaining loose components: washer
(key 11), upper diaphragm plate (key 13), diaphragm
(key 14), disk holder (key 22), and O-ring (key 18).
Inspect diaphragm and O-ring for damage or wear,
and replace if necessary.
7
Page 8
Type FL
6. Remove orice (key 19) and O-ring (key 17). Inspect
the parts for damage or wear, and replace if necessary.
Lightly lubricate the O-ring and place in the body (key 16).
Install the orice.
7. Set the disk holder (key 22) in the body (key 16).
8. Lightly lubricate the rims of the diaphragm plate (key 14).
Position the diaphragm convolution facing down, make
sure that the diaphragm is not deformed and is properly
installed. Take the diaphragm (key 14) and place it in the
body (key 16) on top of the disk holder (key 22).
9. Set the upper diaphragm plate (key 13) on top of the
diaphragm (key 14).
10. Place washer (key 11) and stem nut (key 26) on the stem
(key 23) and tighten using a wrench to hold the stem.
11. Place the upper spring seat (key 9) on the upper
diaphragm nut (key 26) and mount the spring case
(key 8) on top of the body (key 24) and the diaphragm
(key 14).
12. Place washers (key 11) and uniformly tighten the machine
screws (key 10) to hold the body (key 24) and spring case
(key 8) together.
13. Install spring (key 7) and upper spring seat (key 6) on
top of the lower spring seat (key 9) inside the spring case
(key 8). Install Cap (key 3).
14. Screw in adjusting screw (key 1) at desired spring
compression and use the lock nut (key 2) to lock the
adjusting screws position. Refer to Pilot Adjustment
section (page 5) to adjust pilot settings.
Parts Ordering
Each relief valve or backpressure regulator is assigned
a serial number, which can be found on the nameplate.
Refer to the number when contacting your local Sales
Ofce for technical information or when ordering parts.
When ordering replacement parts, reference the key number
of each needed part as found in the following parts list.
Separate kit containing all recommended spare parts
is available.
Parts List
Type FL Main Valve (Figure 5)
Key Description Part Number
Start-Up Repair Kit(includes keys 4, 18, 20, 46, and 47.
Not all parts are used for all sizes.) See Table 4
Parts kit (includes keys 2, 3, 4, 10,
18, 20, 26, 28, 35, 37B, and 47.)
Not all parts are used for all sizes.) See Table 5
Travel Indicator Kit (includes keys 33, 34, 35,
36, 37B, 38, 39, and 40.) See Table 6
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Shanghai 201206, China
Tel: +86 21 2892 9000
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100
For further information visit www.emersonprocess.com/regulators
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Tartarini is a mark of O.M.T. Ofcina Meccanica Tartarini s.r.l.,
a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and
maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
Natural Gas Technologies
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Singapore 128461, Singapore
Tel: +65 6770 8337
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Chartres 28008, France
Tel: +33 2 37 33 47 00
TESCOM
Emerson Process Management
Tescom Corporation
USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238
+1 800 447 1250
Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287