Figure 4 Compressor Module Dimensions, in. (mm) ............................................................................................ 7
Figure 5 Compressor Module Gas and Oil Flow Diagram and Safety Shutdowns .............................................. 8
Figure 6 Brushless DC Fan ............................................................................................................................... 10
Figure 7 Basic Fan Control System ..................................................................................................................10
Figure 8 Optional Customer-Installed High Temperature Fan Control System ................................................. 11
Figure 9 Oil Cooling and Thermal Valve ............................................................................................................. 11
Figure 10 Motor Control ......................................................................................................................................12
Figure 14 Gas Inlet Block and Screen ................................................................................................................21
Figure 15 Scavenge Line Orice ......................................................................................................................... 21
TABLES
Table 1 Inlet and discharge pressure limits ........................................................................................................5
Table 2 Typical Compressor Module power supply requirements ....................................................................13
SZO modules are intended for use with clean, dry gas in applications with moderate ambient
temperatures. Oil thermal bypass valve setpoint is 200°F. Most SZO module applications use
PAO oil.
SZV modules keep discharge gas temperatures elevated to help with dewpoint control. SZV
modules insulate the separators and use a 250°F oil thermal bypass valve. In cold ambient,
and SZV module should be used with an enclosure. Most SZV module applications use PAG
oil.
Refer to Copeland Scroll Gas Compression Module Performance Program for all details.
iv 2008SSD-34 (5/11)
Single-Compressor Module Important Safety Information
importaNt safety iNformatioN
This manual contains important instructions for installation, operation and maintenance of your Copeland
Scroll® Compressor Module.
WARNING
The Compressor Module must be installed ONLY in systems that have been designed by
qualied engineering personnel. The system must conform to all applicable local and national
regulations and safety standards.
These instructions are intended to assist in the installation and operation of the Compressor
Module and MUST be kept with the Compressor.
Service and maintenance of the Compressor Module must be performed by qualied technicians
only. Service and maintenance must conform to all applicable local and national regulations and
safety standards.
Thoroughly review this manual, all instructions and hazard warnings before performing any work
on the Compressor Module.
Maintain all Compressor Module operation and hazard warning labels.
WARNING
Flammable gas can form explosive mixtures with air. Explosive gases can cause property
damage, serious personal injury or death.
WARNING
Failure to disconnect and lockout electrical power from the Compressor Module before attempting
maintenance can cause shock, burns, severe personal injury or death.
WARNING
Loosening or removing pressure-containing components from the Compressor Module when it is
in operation can cause major property damage, serious personal injury or death.
Failure to relieve system pressure prior to performing service or maintenance on the Compressor
Module can cause property damage or serious personal injury.
CAUTION
Extreme heat can cause personal injury or property damage.
CAUTION
Always use a lifting device capable of supporting the full weight of the Compressor Module or
component being lifted.
Handling or lifting heavy assemblies can cause personal injury or property damage.
1 2008SSD-34 (5/11)
Single-Compressor Module Important Safety Information
safety symbols usediN this maNual
SAFETY ALERT SYMBOL
When you see this symbol on the Compressor Module or in this manual, look for one of the
following words and be aware of the potential for personal injury or property damage.
WARNING
A Warning describes hazards that CAN or WILL cause serious personal injury, death or major
property damage.
CAUTION
A Caution describes hazards that CAN cause personal injury or property damage.
NOTE
A Note indicates special instructions that are very important and must be followed.
2 Form No. 2008SSD-34 (5/11)
Single-Compressor Module Introduction
1.0 iNtroduCtioN
The Copeland Scroll® SZO22 Compressor Module comes equipped with one Copeland Scroll®
Compressor designed for Class I, Division II applications. The Compressor Module is designed for
assembly into a Compressor Package ready for service in the eld; the completed housing is done by
equipment Packagers. This section provides an overview of these components.
These terms are used throughout this manual:
• Compressor Module - the SZO22 Compressor Module shown in Section 1.1
• Compressor - a Copeland Scroll® Compressor
• Compressor Package - the entire assembly, including the Compressor Module, ready for service in
the eld
• Packagers - the company that prepares the Compressor Module for service
• VFD - Variable Frequency Drive used to power a variable speed Compressor Module
1.1 The Compressor Module
The Compressor Module consists of one Compressor and the other components shown in Figure 1.
Figure 1 Compressor Module Components
3 2008SSD-34 (5/11)
Single-Compressor Module Introduction
1.2 The Compressor
The Compressor refers to the Copeland Scroll® Compressor. Figure 2 shows a cross-section of a
Compressor and its key components.
The Compressor Package consists of the Compressor Module housed in an assembly ready for service
in the eld. Equipment Packagers customize the assembly and complete the fabrication for Compressor
Modules for each application. Figure 3 shows a simplied example of a Compressor Package.
Figure 3 Typical Compressor Package
Control and
power panel
Oil
cooler
Inlet gas scrubber
for liquid removal
Gas aftercooler
(if applicable)
Compressor
Module
4 Form No. 2008SSD-34 (5/11)
Single-Compressor Module Installation
2.0 iNstallatioN
2.1 Installation Guidelines
2.1.1 Required Component—Inlet Gas Scrubber
An appropriate inlet gas scrubber is REQUIRED to remove liquids from the gas prior to compression. If
there is potential for liquid slugging, a suitable trap must be installed to prevent liquid from ooding and
damaging the Compressor.
NOTE
Failing to use an appropriate inlet gas scrubber to remove liquids from the gas prior to
compression can cause ooding and damage the Compressor.
2.1.2 General Installation Guidelines
Follow these general guidelines for installation:
• The Compressor Module must be installed and operated in compliance with all applicable codes and
regulations.
• The system must be installed on a level surface.
• Install pipe unions or anges to connect the system to the inlet and discharge piping for ease of
service.
• Install isolation valves on the inlet and discharge piping.
• A common ground must be connected between the Compressor Module and the
Compressor Package chassis. This ground must comply with the National Electric Code (NEC) and
any other applicable codes.
• Solid debris also must be removed from the gas prior to compression. When required, use a
5 to 10-micron inlet lter to remove debris from the gas stream. The degree of ltration required
depends on the specic application.
2.2 Inlet and Discharge Pressures
Refer to Table 1 for acceptable inlet and discharge pressure levels.
Table 1 Inlet and discharge pressure limits
TypeLevelOperating Guidelines
Minimum Inlet
Pressure
Maximum Inlet
Pressure
Discharge
Pressure
Range
Minimum
Differential
Pressure
0.75 psig / 2" water
column (model specic)
10 / 25 psig
(model specic)
70 psig
to
190 psig
(depends on model)
70 psi
Consult factory for operations below 0.0 psig.
Operation at pressures above 25 psig will result in:
• Excessive oil carryover
• Loss of oil from the Compressor Module
When the discharge pressure of the Compressor Module reaches
the maximum, which ranges from 70 to 190 psig, depending on the
model (see Compressor Module Nomenclature on page iv):
• The Compressor Module goes into high discharge pressure
recycle if equipped.
• The Compressor Module’s bypass regulator diverts gas from the
high-pressure side to the low-pressure side of the module.
All Compressor Modules must be equipped with pressure-limiting
or relief devices.
A minimum pressure differential of 70 psi between inlet and
discharge pressure is required for proper operation.
5 2008SSD-34 (5/11)
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.