Specification for SiteI/O 10/0
DESCRIPTION: The SiteI/O 10/0 is part of the SiteI/O-Line, which allows a complete SiteScan
monitoring/control system to be built a piece at a time. It is a 32 bit microprocessor-based device
designed to monitor up to ten analog, digital, and/or dry contact type signals. Individual hardware
jumpers set signal-type selections. Screw terminal blocks are provided to terminate power,
communication, and input signal wiring.
DIMENSIONS: Module: 7.5” H x 11.3125” W x 2.75” D
19.05 cm H x 28.73 cm W x 7 cm D
Enclosure: 20" H x 18" W x 2.87" D
(Painted Steel) 508mm x 457.2mm x 72.89mm
See Enclosure Diagrams for mounting options.
POWER: 24VAC ± 10%, 50-60 Hz., 20 VA power consumption
(120/24VAC 40VA Transformer available)
INPUTS: Ten universal inputs, configurable for 0-5VDC, 0-20mA, or thermistor.
ENVIRONMENTAL
OPERATING RANGE: 0° to 130° F (-17.8° to 54.4° C), 10 to 90% relative humidity, non-condensing
COMMUNICATION: One (1) CMnet EIA-485 Port - Control Module network screw terminals
Switch selectable baud rates ARC156 / 9600 or 38.4bps
Recommended wire is: MAGNUM Cable pn A3-ARC-156-2
(10) Analog and/or Digital - screw terminals
Jumper Selectable inputs
Thermistor - 10k ohm @ 77° F, 25°C
0 to 5 VDC - 10k ohm max source impedance
4 to 20mA - 24VDC loop power, 250 ohm input
Dry Contact - 0.5mA sense current
MEMORY: 1 MB Flash Memory, 1 MB Non-volatile battery backed RAM.
PROTECTION: Voltage, current, and ESD protection on incoming power.
BATTERY: Seven-year lithium battery provides a minimum of 10,000 hours of data
retention during power outages.
Liebert Corporation Page 1 of 6 SL-28077 Rev.4; 7/03
Specification for SiteI/O 10/0
DIAGNOSTIC LED's:
Power: Indicates power on condition
Tx: Indicates data transmitted on the CMnet
Rx: Indicates data received on the CMnet
Error: Indicates an error within the SiteI/O 10/0
Run: Indicates operating condition of the SiteI/O 10/0
LISTED BY: UL 916 (PAZX), cUL C22.2 No. 205-M19 (PAZX7), FCC Part 15 – Subpart B –
Class A
MODULE DIMENSIONS AND LAYOUT
CMnet
Port
Keypad Display
Port
CMnet Mode
Jumper
13/16"
3cm
Run
OpenEnergy
88FO
E143900
TYPE: 008 102
R
Module
Address
10's 1's
Run and Power
Error
TM
LEDs
CAUTION:
ToR educe The Risk
ofFireorElectricShock,
DoNo tInterconnect
Output s of Di ffere nt Cla ss 2 C ircuit s
Power
On Off
24Vac, 50-60Hz
20VA,0.83A
Use Cop per
ConductorsOnly
Access
Port
Gnd
24Vac
Class2
Power
Access
Port
71/2"
19.05cm
33/4"
9.5cm
23/4"
7cm
Power Switch
11 5/16"
28.73cm
I/O
IN-1
B
IN-2
IN-3
A
IN-4
IN-5
B
IN-6
IN-7
A
IN-8
IN-9
B
IN-10
Expa nsion
Inputs
5VMax, 20mA
Max
UniversalInput
Mode Select
Thermistor/ 0-20
dry-contact
A-InputSignal
B - Gnd/Loop Pow er
Expa nsion
Net+
CMnet
Net-
Shield
Auxiliary
Device
Port
CMnet Mode
9600/
ARC156K
38.4K
1A
2
3A
4B
5A
6B
7
8B
9A
10
11 A
12 B
13 A
14 B
15
16 B
17 A
18
19 A
20 B
Baud Rate
Switch
0-5Vdc
mA
I/O
Rx Tx
SiteI/O 10/0
Liebert
ManagementEquipm ent
38.4k
CMnet baud
Format
9600
Format Button
Liebert Corporation Page 2 of 6 SL-28077 Rev.4; 7/03