Table 3010-bay, single-phase, no transformer unit Type N (& UPS model number digit 9 = N). . . . . . . . 72
Table 3110-bay, single-phase, no transformer unit Type R (& UPS model number digit 9 = R) . . . . . . . . 73
Table 3210-bay, single-phase, no transformer unit Type F (& UPS model number digit 9 = F) . . . . . . . . 74
Table 3316-bay, single-phase, no transformer unit Type N (& UPS model number digit 9 = N). . . . . . . . 75
Table 3416-bay, single-phase, no transformer unit Type R (& UPS model number digit 9 = R) . . . . . . . . 76
Table 3516-bay, single-phase, no transformer unit Type F (& UPS model number digit 9 = F) . . . . . . . . 77
Table 3612-bay, single-phase, transformer-based unit Type N (& UPS model number 9 = N) . . . . . . . . . 78
Table 3712-bay, single-phase, transformer-based unit Type R (& UPS model number 9 = R). . . . . . . . . . 79
Table 3812-bay, single-phase, transformer-based unit Type F (& UPS model number 9 = F) . . . . . . . . . . 80
Table 3916-bay, single-phase, transformer-based unit Type N (& UPS model number 9 = N) . . . . . . . . . 81
Table 4016-bay, single-phase, transformer-based unit Type R
Table 4116-bay, single-phase, transformer-based unit Type F (& UPS model number 9 = F) . . . . . . . . . . 83
Table 4210-bay, two-phase, no transformer unit Type N (& UPS model number 9 = N) . . . . . . . . . . . . . . 84
Table 4310-bay, two-phase, no transformer unit Type R (& UPS model number 9 = R) . . . . . . . . . . . . . . 85
Table 4410-bay, two-phase, no transformer unit Type F (& UPS model number 9 = F). . . . . . . . . . . . . . . 86
Table 4516-bay, two-phase, no transformer, unit Type N (& UPS model number 9 = N) . . . . . . . . . . . . . 87
Table 4616-bay, two-phase, no transformer unit Type R (& UPS model number 9 = R) . . . . . . . . . . . . . . 88
Table 4716-bay, two-phase, no transformer unit Type F (& UPS model number 9 = F). . . . . . . . . . . . . . . 89
(& UPS model number 96 = R). . . . . . . . . 82
v
vi
IMPORTANT SAFETY INSTRUCTIONS
!
!
!
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety, installation and operating
instructions before operating the SolaHD S5KC modular UPS system. Adhere to all warnings on the
unit and in this manual. Follow all operating and user instructions. Individuals must fully
understand this equipment to install and operate it.
This product is designed for commercial/industrial use only. It is not intended for use with life support
or other designated critical devices. Maximum load must not exceed that shown on the rating label.
Install and operate the unit only in an indoor clean environment, free from conductive contaminants,
moisture, flammable liquids, gases and corrosive substances. This SolaHD S5KC contains no user
serviceable parts other than the user replaceable modules. Refer all faults to your local dealer, local
Emerson representative or the Emerson SolaHD service group.
The SolaHD S5KC UPS system is designed for use on a properly earthed (grounded) “TN” electrical
supply, for installation by qualified personnel. A qualified electrician must review and approve
customer supplied wiring, circuit breakers, and intended loads and verify correct input, output, and
earth connections to ensure compliance with the technical standards and local electrical codes of
practice. Installation instructions and warning notices are found in this manual.
WARNING
Risk of electric shock. Can cause equipment damage, injury and death.
The battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed before replacing the battery pack:
• Wear rubber gloves and boots
• Remove rings, watches and other metal objects.
• Use tools with insulated handles.
• Do not lay tools or other metal objects on the batteries.
• If the battery kit is damaged in any way or shows signs of leakage, contact your local
Emerson representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.
Important Safety Instructions
WARNING
Risk of electric shock and fire. Can cause equipment damage, injury and death.
Although the SolaHD S5KC UPS has been designed and manufactured to ensure personal
safety, improper use can result in electrical shock or fire. To ensure safety, observe the
following precautions:
• Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
• Do not place the SolaHD S5KC where it might be damaged.
WARNING
Risk of electric shock. Can cause equipment damage, injury and death.
This UPS contains no user-serviceable parts except for the user-replaceable module
assemblies. The UPS On/Off push button does not electrically isolate internal parts.
All service and maintenance operations must be performed by properly trained and qualified
personnel. Under no circumstances should unqualified or unauthorized personnel attempt to
gain access to the internal portions of the SolaHD S5KC.
1SOLA HD® S5KC
™
Important Safety Instructions
ELECTROMAGNETIC COMPATIBILITY—The SolaHD S5KC complies with the limits of
Category C2, pursuant to IEC/EN/AS 62040-2, and for a Class A digital device, pursuant to Part 15 of
FCC rules. Operation is subject to the following conditions:
• The output cables shall be no longer than 10m (32ft).
• This device may not cause harmful interference.
• This device must accept any interference received, including interference that may cause
undesired operation. Operating this device in a residential area is likely to cause harmful
interference that users must correct at their own expense.
The SolaHD S5KC complies with the requirements of EMC Directive 2004/108/EC and the published
technical standards. Continued compliance requires installation in accordance with these
instructions and use of accessories approved by Emerson.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C
(32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and
corrosive substances.
Do not continue to use the UPS if the front panel indications are not in accordance with these
operating instructions or the UPS performance alters in use. Refer all faults to your local service
dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from the batteries. Proper disposal of
batteries is required. Refer to your local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,
for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half
wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption. Turn Off and isolate
the UPS before cleaning it. Use only a soft dry cloth; never use liquid or aerosol cleaners.
Information for the Protection of the Environment
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic
cards, electronic components). The components removed must be taken to specialized collection and
disposal centers.
NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD
APPLIANCES—This product has been supplied from an environmentally aware
manufacturer that complies with the Waste Electrical and Electronic Equipment
(WEEE) Directive 2002/96/CE.
The crossed-out trash bin symbol at right is placed on this product to encourage
users to recycle components and units whenever possible. Please be
environmentally responsible and recycle this product through your recycling
facility at its end of life. Do not dispose of this product as unsorted municipal
waste. Follow local municipal waste ordinances for proper disposal provisions to
reduce the environmental impact of waste electrical and electronic equipment (WEEE).
For information regarding the scrapping/disposal of this equipment, please browse
www.solahd.com (Products section or Contact us section) or call Emerson’s worldwide technical
support.
• Toll-Free in North America: 1-800-377-4384
• Outside North America: +1-847-268-6651
•Email: solahd.technicalservices@emerson.com
SOLA HD® S5KC
™
2
GLOSSARYOF SYMBOLS
!
PbH2SO4
-
+
R
Glossary of Symbols
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
Toggle between On and Off
Standby
Do not dispose of in normal waste stream
3SOLA HD® S5KC
™
1.0PRODUCT INTRODUCTION
Congratulations on your purchase of the SolaHD S5KC Uninterruptible Power System (UPS). As
with every other SolaHD product, we stand behind our quality. If you have any questions concerning
this UPS, please feel free to contact your local dealer or SolaHD representative or call the appropriate
Technical Support number listed on the back of this manual.
To ensure proper installation and operation of this unit, please read this manual thoroughly.
The installation must be completed by trained professionals and follow all local codes. General
operation of the units can be conducted without any specialized training.
This chapter provides the system description, features, operating principle, operating mode, main
components and specifications of the SolaHD S5KC UPS.
1.1System Description
The SolaHD S5KC power system is a modular UPS designed to provide high reliability. It is intended
for use with workstations, servers, networks, telecoms and other sensitive electronic equipment. It
provides continuous, high-quality AC power to your equipment, protecting it from any power
disturbance due to blackouts, brownouts, surges or noise interference.
The SolaHD S5KC UPS is an easily adaptable UPS system. By simply installing additional power or
battery modules, you can expand your current system capacity, extend your backup runtime, or
provide redundancy. The SolaHD S5KC UPS user interface enables the user to configure the
operation according to application requirements. It also informs the user on the status of the UPS and
keeps a log of events.
Product Introduction
The SolaHD S5KC series UPS contains both transformer-free and transformer-based UPS frames.
The use of the transformer-free or transformer-based frames is dependent upon the specific
application requirements. The appearance of the different frames is shown in Figures 1 through 4.
Table 1Frame designation
UPS Model Number Digits 1-4Frame TypeFrame Rating
S5KCA or S5KCE10 Bay Transformer-free15kVA redundant
S5KCB or S5KCF16 Bay Transformer-free20kVA redundant
S5KCC12 Bay Transformer-based15kVA redundant
S5KCD16 Bay Transformer-based20 kVA redundant
SOLA HD® S5KC
™
4
Figure 116-bay transformer-free UPS
Manual Bypass Breaker
(under the cover)
Input Breaker
(under the cover)
User Interface
Module
Power, Battery
or Charger
Modules
Battery
Modules
POD
Ports
RS-232
Port
Dry
Contacts
Intelligent Card
Slots
Power Input and
Output Terminals
System Enabling
Breaker
Output Breaker
USB
Port
External Battery
Cabinet
Connector
Front View - Bezels RemovedRear View
POD
Breakers
Manual Bypass
Breaker (under
the cover)
Input Breaker
(under the cover)
User Interface
Module
Power,
Battery or
Charger
Modules
Battery
Modules
POD
Port
RS-232
Port
Dry
Contacts
Intelligent Card
Slots
Power Input and
Output Terminals
System Enabling
Breaker
Output
Breaker
USB
Port
External Battery
Cabinet
Connector
Front View - Bezels Removed
Rear View
System Control Module
(under the cover)
POD Breakers
Product Introduction
Figure 210-bay transformer-free UPS
5SOLA HD® S5KC
™
Figure 312-bay transformer-based UPS
Manual Bypass Breaker
(under the cover)
User Interface
Module
Power, Battery
or Charger
Modules
Battery
Modules
POD Port
RS-232
Port
Dry
Contacts
Intelligent Card
Slots
Power Input
and Output
Terminals
System Enabling
Breaker
Output
Breaker
USB Port
External Battery
Cabinet
Connector
Front View - Bezels RemovedRear View
POD Breaker
Input
Breaker
Product Introduction
SOLA HD® S5KC
™
6
Figure 416-bay transformer-based UPS
Manual Bypass
Breaker (under
the cover)
User Interface
Module
Power, Battery
or Charger
Modules
Battery
Modules
Front View - Bezels Removed
POD
Port
RS-232
Port
Dry
Contacts
Intelligent Card
Slots
Power Input
and Output
Terminals
System Enabling
Breaker
Output
Breaker
USB Port
External Battery
Cabinet
Connector
Rear View
Input
Breaker
Product Introduction
7SOLA HD® S5KC
™
1.2Features
SolaHD S5KC UPS
• Flexible extension of capacity, up to 15 or 20kVA modular power, depending upon frame rating
• N + 1 redundancy, improving availability
• Module design, modules hot-swappable by user
• Redundant intelligent module, providing redundant communication path
• Intelligent battery management
• External large battery assemblies can be connected
• Internal automatic and manual bypass
• Transformer-based UPS frames provide output isolation transformer
• Optional 10A battery charger module
• Continuous system monitoring
• User-friendly interface with audible alarms and event logs
• Supporting hot-pluggable and online update
• Compatible with backup generators
Standard Components
•UPS frame
• User interface module: for comprehensive user indications and programmable controls
• System control modules and system monitor module: for system monitoring and communications
• Power modules: for power conditioning
• Battery modules: for backup power
• Charger module: option for charging batteries and long run time applications
• External battery cabinet: extends system run time
Product Introduction
Communications
• Dry contacts
•IntelliSlot
•USB port
®
communication ports
SOLA HD® S5KC
™
8
1.3Operating Principle
The operating principle of the SolaHD S5KC UPS is shown in Figure 5.
Figure 5Operating principle diagram
Input
Product Introduction
Manual Bypass
Output
EMI
Filter
Power
Module(s)
EMI
Filter
Output and
Bypass
Contactor
Output
Transformer
Transformer models
Battery
Module(s)
have an output isolating
transformer
System Control
Module
System Monitor
Module
Wiring
Power
Control
User
Interface
Control
Interface
Communication
The SolaHD S5KC UPS is composed of AC input, EMI filter, power module(s), battery module(s), user
interface, control interface, system control module, output and bypass contactor, manual bypass,
output transformer (certain frames only) and AC output.
9SOLA HD® S5KC
™
1.4Operating Modes
The SolaHD S5KC UPS is a true online double-conversion system, having the following operating
modes:
•Normal Mode
• Backup Mode
•Auto Restart Mode
• Bypass Mode
Normal Mode
The power module rectifiers derive power from a utility AC source and supply regulated DC power to
the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment.
The battery charger is in the power module and maintains a float-charge on the batteries of the UPS;
additionally, the optional charger module can also charge the batteries to maintain a quicker
recharge time for long backup time applications.
Backup Mode
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains
energy from the battery modules. The output power will not be interrupted during the failure or
restoration of the AC utility/mains source.
Auto Restart Mode
Product Introduction
After a power outage and complete battery discharge, and once AC utility is restored, the UPS will
automatically restart and resume supplying power to connected equipment. This feature is enabled at
the factory, but can be disabled by the user. The user can also program two auto restart delay settings
from the LCD:
• Battery capacity level (%)
• Countdown timer
Bypass Mode
The bypass provides an alternate path for power to the connected equipment and operates in the
following manner:
• Automatic: In the event of an internal fault or should the inverter overload capacity be exceeded,
the UPS performs an automatic transfer of the connected equipment from the inverter to the
bypass source.
• Manual: Should the UPS need to be taken out of service for limited maintenance or repair,
manual activation of the bypass will cause an immediate transfer of the equipment from the
inverter to the bypass source.
This section provides a general description of each component and its functions. Please review this
section carefully, as it will give you a better understanding of how the UPS operates.
1.5.1UPS Frame
The UPS frames are shown in Figure 6.
Figure 6UPS frames, bezels removed
Product Introduction
NOTE
In Figure 6, the power module and battery module are extended for illustration purposes only.
Extending more than one module at a time could cause the unit to tip over.
All UPS components are located in the SolaHD S5KC frame. The front of the UPS consists of a series
of metal bezels. By grasping these bezels from the sides and pulling straight out, you can remove the
bezel to reveal the battery/power module bays. The standard-model frame provides cooling fans and a
manual bypass breaker on its top; the transformer-model frame provides a manual bypass breaker on
its bottom and fans on both top and bottom. The user interface module is located above the
power/battery module bays for easy access, operation and for viewing UPS operating information. On
the lower right part of the user interface module, you will see the system control module bays.
11SOLA HD® S5KC
™
1.5.2User Interface Module
Handle
Green Status LED
Yellow Fault LED
Securing Hole
Locking Lever
The user interface module is shown in Figure 7.
Figure 7User interface module
The user interface module is the primary source of communication between the UPS and the user.
The user interface module permits:
• Viewing the UPS status
• Configuring the system
• Reviewing the event log
• Silencing the audible alarm
Refer to 4.0 - Operation and Display Panel for details on operating the user interface module.
1.5.3System Control Module and System Monitor Module
Product Introduction
The system control module and the system monitor module are the communication backbone of the
UPS. They gather input from all modules and process the data to control the operation of the system,
including monitoring the condition of each module. Except for the silkscreen, the appearance of the
system control module and the system monitor module is as shown in Figure 8.
Figure 8SolaHD S5KC system control module and the system monitor module
Under normal operation, the green status LED will blink and the yellow fault LED will be Off. For
any other condition, refer to 5.0 - Troubleshooting.
SOLA HD® S5KC
™
12
1.5.4Power Module
Yellow Fault LED
Locking Lever
FRONT VIEW
Fan
Green Status LED
Green Status LED
Yellow Fault LED
Locking Lever
FRONT VIEW
The power module is shown in Figure 9.
Figure 9SolaHD S5KC power module
Each power module is an independent 5kVA unit, consisting of a power factor corrected rectifier,
battery charger and inverter, with associated monitoring and control circuitry. The modules are
connected in parallel for greater capacity and/or redundancy.
The power modules may be added or replaced on-line with no interruption or danger to the connected
equipment or user.
1.5.5Battery Module
The battery module is shown in Figure 10.
Product Introduction
Figure 10 Battery module appearance
When AC utility fails, the battery module will supply power to the load. Each battery module contains
six individual 12V, valve-regulated lead-acid (VRLA) battery blocks. Two battery modules are
connected in series to form a battery string.
Each battery module has monitoring and controls to isolate the battery module in the event of a
battery failure. The battery strings are connected in parallel to provide backup time and/or
redundancy.
NOTE
Two battery modules must be installed in the same row to make a complete battery string.
The battery modules may be added or replaced on-line with no interruption or danger to the
connected equipment, provided that the UPS is not operating on battery.
Under normal operation, the green status LED will blink continuously and the yellow fault LED will
be Off. For any other condition, refer to 5.0 - Troubleshooting.
13SOLA HD® S5KC
™
1.5.6Charger Module
Green Status LED
Yellow Fault LED
EBC Breaker
Figure 11 shows the charger module.
Figure 11 Appearance of the charger module
In AC mains mode, the charger module charges the system battery modules or external battery
cabinet. Each charger module is rated to deliver 10A charging current. The charger module has an
independent control function and maintains real-time communication with the system and the
battery modules to ensure stable charging and fault protection.
The charger module may be added or replaced on-line with no interruption or danger to the user,
connected battery system or connected equipment.
1.5.7External Battery Cabinet (EBC)
The external battery cabinet is divided into nine rows: the upper seven rows are for use with the
intelligent battery modules, and the lower two are used for overcurrent protection for each battery
cabinet. For normal operation, two battery modules must be inserted in the same row of the frame to
create a complete string. The battery module strings work in parallel to provide longer backup time
for the UPS. A SolaHD S5KC can be configured with, at most, four external battery cabinets.
An external battery cabinet is shown in Figure 12.
Product Introduction
Figure 12 External battery cabinet
SOLA HD® S5KC
™
14
2.0INSTALLATION
12" (305mm)
39" (1000mm)
This chapter describes UPS installation, including installation preparation, unloading the UPS,
mechanical installation, installing modules and cable connection.
2.1Unpacking Inspection
Upon receiving the UPS, uncrate it and conduct the following checks:
• Inspect the UPS appearance for shipping damage. Report any shipping damage to the carrier and
send a copy to your Emerson
• Check against the delivery list to ensure that the package contains the correct number and type of
accessories. If there is any discrepancy, contact the distributor immediately.
2.1.1Installation Environment
NOTE
Operating the UPS in temperatures above 77°F (25°C) will reduce battery life.
The UPS environment must be free of conductive contaminants and excessive moisture (water and
condensation), flammable vapors, chemical fumes, corrosive gases and liquids.
2.1.2Installation Tools
The tools required to properly set up your UPS are listed below:
• Pallet jack
• 17mm (11/16") wrench or socket
• 13mm (1/2") wrench or socket
• 10mm wrench or socket
• #1 and #3 Phillips screwdrivers
• Torque wrench
®
representative.
Installation
2.1.3Installation Site
Consider the weight and size of the SolaHD S5KC when deciding where to install the unit. Verify that
the floor can support the weight of a fully loaded unit, any accessories and external cabinets.
Verify that the UPS will be in a well-ventilated area with at least 12 inches (305mm) clearance
behind it. The UPS is air-cooled, utilizing internal fans. Air is drawn into the front of the UPS and is
exhausted through ventilation grilles in the back. The UPS should also have at least 39 inches (1m)
clearance in front for service and to meet many local and national building codes.
Figure 13 Front and rear installation clearances
15SOLA HD® S5KC
™
2.2Unloading the UPS
Sola S5KC
Detail A
A
Pallet
Mounting Bolts
(2 each side)
Mounting Bracket
(1 each side)
The unit frame is bolted to the shipping pallet to ensure safety during shipping. Emerson
recommends keeping the unit bolted to the pallet and using a pallet jack to transport the unit to its
installation location.
NOTE
This UPS is very heavy. At least two people should assist in unloading it from the pallet.
To unload the UPS:
1. Move the UPS to its installation site and remove the package paper.
2. Use a 17mm (11/16") wrench, to remove the four mounting bolts from the pallet brackets (see
Figure 14).
3. Remove the mounting brackets from the UPS with a 10mm wrench or socket or a #3 Phillips
screwdriver.
Figure 14 Remove the mounting brackets
Installation
4. Raise the four leveling feet to provide clearance between the pallet and the UPS frame.
5. Connect the ramp to the UPS pallet, as shown in Figure 15.
6. Roll the UPS slowly down the ramp until it is on a level surface, as shown in Figure 15.
Figure 15 Connect the ramp and remove UPS
SOLA HD® S5KC
™
16
2.3Mechanical Installation
Lower nut is bonded to
leveling foot; used to raise
and lower foot
Upper nut is threaded on
leveling foot; used to hold
foot height
716mm
(28.19")
340mm
(13.39")
M10
screw
Floor-Mounting Hole Layout
Mounting Bolt
Mounting
Bracket
Two installation modes are available for the SolaHD S5KC UPS: tower installation and rack
installation.
2.3.1Tower Installation
1. Once the UPS is in the desired location, adjust the leveling feet to secure its position, as shown in
Figure 16.
a. Use an open end wrench to turn the lower nut to raise or lower the leveling foot.
b. After the unit is level, tighten the upper nut against the frame to prevent the height from
changing.
Figure 16 Adjust the leveling feet
Installation
2. For added stability or earthquake-resistant installations, the shipping brackets can be used to
secure the unit to the floor.
a. Drill holes 10.3mm (13/32") in the floor for stationary mounting; these will accommodate the
mounting bolts removed from the pallet. Refer Figure 17 for the layout.
b. Use the mounting screws to install the mounting brackets on the front and rear of the UPS.
c.Secure the mounting brackets to the floor with the mounting bolts (see Figure 17).
For greater stability, use a higher-grade bolt.
Figure 17 Installation position and drilling hole dimensions for stationary mounting
17SOLA HD® S5KC
™
2.3.2Rack Installation
A
Detail A
Floating Nut
B
Detail B
Screw,16 places
Tray
1. Install the cage nuts on the corresponding positions in the rack, as shown in Figure 18.
a. Install cage nuts in the two lower square holes of 1U space and in the two upper square holes
of 2U space of all four rack posts. These cage nuts will secure the optional shelf that will
support the weight of the SolaHD S5KC.
b. Install a cage nut in the middle square hole of 4U, 6U, 10U, 12U spaces, respectively, again in
all four posts. The cage nuts will help secure the UPS in the rack.
Figure 18 Install cage nuts
Installation
2. Install the rack-mount shelf on the corresponding position between 1U space and 2U space on the
Figure 19 Install the tray
3. Install the guide rails (ramp) in the mounting slot at the front of the tray, as shown in Figure 20.
SOLA HD® S5KC
bottom of the rack, as shown in Figure 19.
™
18
Figure 20 Install the guide rails
C
Guide
Rail
Mounting Slot
Insert one end
of the guide rail
into the mounting
slot on the tray
Detail C
Bracket
Screw
(8 Places)
Detail Area
Installation
4. Unscrew the 10 screws on the front of the two side panels of the UPS frame.
5. Use those screws to attach the brackets to each side of the UPS frame, as shown in Figure 21.
Figure 21 Install the brackets
19SOLA HD® S5KC
™
6. Push the SolaHD S5KC frame slowly into the enclosure from the front, as shown in Figure 22. The
Push the
UPS frame
into the
rack.
Front
of
Rack
Front
of
UPS
Panel
Screw
(8 Places)
Detail Area
rear of the UPS goes into the rack first when installing through the front of the rack.
Figure 22 Push the UPS frame into the rack
7. Use eight panel screws to secure the UPS frame to the rack posts, as shown in Figure 23.
Installation
NOTE
It might be necessary to use the leveling feet to get the holes to align
Figure 23 Fix the UPS frame
SOLA HD® S5KC
™
20
8. Use four screws to install the metal plate (accessory in the rack-mount kit) on the corresponding
Square Hole
(2 Places)
Detail Area
Metal Plate
Mounting Screw
(4 Places)
Bezel
position on the lower front part of the UPS frame
9. Insert the provided bezel into the square holes of the metal plate, as shown in Figures 24 and 25.
Figure 24 Install the metal plate
Installation
The installation is complete, as shown in Figure 25.
Figure 25 Installation completed
21SOLA HD® S5KC
™
2.4Module Installation
1. Push module slowly into
the bay until it is 1/3 in.
2. Raise the face
of the module.
4. Push module quickly and
firmly into the bay.
3. Continue pushing module slowly
until about 2" (50mm) remains out.
The SolaHD S5KC ships from the factory configured (modules prepopulated) and tested as a system
to the customer’s requirements. If any modules were removed to facilitate ease of installation, follow
the steps below to reinsert them properly.
2.4.1Installing Power Module, Battery Module and Charger Module
1. Lift module to appropriate bay, resting end of module on bay shelf.
NOTE
Use caution not to rest the module on any of the bezels, this could damage the bezel.
Two battery modules must be installed in the same row to complete the battery string.
2. Push the module into the bay slowly. The module will be locked until 1/3 is in.
a. At this point, lift the module up and continue pushing it until about 5cm of the module is still
out of the bay.
b. Push it firmly and smoothly to ensure that the module is fully inserted, as shown in
Figure 26.
Figure 26 Insert the power module, battery module and charger module
Installation
3. Use a #2 Phillips screwdriver to install the module-securing bracket, and then press the lever
down into the bracket, as shown in Figure 27.
SOLA HD® S5KC
™
22
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.