Fisher® regulators must be installed,
operated, and maintained in accordance
with federal, state, and local codes, rules
and regulations, and Fisher instructions.
If the regulator vents gas or a leak
develops in the system, service to the unit
may be required. Failure to correct trouble
could result in a hazardous condition.
Call a gas service person to service
the unit. Only a qualied person must
install or service the regulator.
Introduction
Scope of Manual
This instruction manual provides instructions and a
parts list for the S203 Series relief monitor regulators.
Description
The S203 Series allows single-unit overpressure
protection. The regulators also minimize the venting of
large volumes of gas to the atmosphere.
Type S203—Spring-loaded regulator with open
throat construction that gives internal registration of
downstream pressure. Outlet pressure is from 2 to
30-inches w.c. (5 to 75 mbar) in ve ranges.
Type S203H—Same as Type S203 but with outlet
pressure from 1 to 3.25 psig (0,07 to 0,22 bar) in
two ranges.
Type S203P-1—Spring loaded regulator with blocked
throat and blocked pitot tube construction for use with
a downstream control line.
Type S203P-2—Same as Type S203P-1 but with stem
seal O-ring for positive seal.
Type S203P-3—Same as Type S203P-1 but with stem
seal O-ring and wiper ring for dirty gas applications.
www.emersonprocess.com/regulators
D400010X012
S203 Series
Specications
Body Sizes and End Connection Style
1-1/2, 1-1/2 x 2, or 2-inch body with
NPT connections
Maximum Allowable Inlet Pressure (Body Rating)
See Table 3
Maximum Allowable Casing Pressure
15 psig (1,0 bar) casing pressure
Maximum Operating Outlet Pressure to Avoid
Internal Part Damage
Approximately 7-inches w.c. to 1 psig
(17 mbar to 0,07 bar) over outlet setting
1. The pressure/temperature limits in this instruction manual or any applicable standard limitation should not be exceeded.
(1)
Specications
The Specications section list the specications for the
S203 Series. The following information is stamped
on the regulator at the factory: type number, date of
manufacture, outlet pressure range, port (seat ring) size,
monitor spring part number, and monitor spring range.
Principle of Operation
The following describes operation through internal
registration as shown in Figure 3. A unit with a
downstream control line operates the same except
that the throat and pitot tube are blocked, and a
downstream control line is tapped into the lower casing
and the monitor spring case.
Downstream pressure registers under the main
regulator diaphragm through the turbo-booster tube
in the throat and on the monitor diaphragm assembly
through the pitot tube. Inlet pressure registers on both
sides of the monitor piston through a registration hole in
the center resulting in balanced operation. Thus, under
normal conditions, as downstream pressure uctuates
due to load changes the main regulator disk and monitor
piston both move toward or away from the seat ring.
If the downstream pressure reaches overpressure
conditions (7-inches w.c. to 1 psig (17 mbar to 0,07 bar))
above the outlet pressure setting — depending on the
main regulator spring), the internal relief valve opens.
At the same time, downstream pressure on the monitor
diaphragm moves the monitor piston closer to the seat
ring restricting the port. This minimizes or prevents
Outlet Pressure Ranges
2-inches w.c. to 3.25 psig (5 mbar to 0,22 bar)
Seat Ring Port Diameters
(1)
1/4, 3/8, 1/2, 3/4, 1, and 1-3/16-inches
(6,4; 9,5; 13; 19; 25; and 30 mm)
Temperature Capabilities
–20° to 170°F (–29° to 77°C)
Pressure Registration
Types S203 and S203H: internal
Type S203P: downstream control line
Approximate Weight
27 pounds (12 kg)
further ow through the port, enabling the relief valve to
relieve the downstream overpressure conditions.
The combination of the restriction in the relief valve
(key 94, Figure 4) and the positioning of the monitor
piston near the inlet side of the seat ring limits the
maximum downstream pressure and the related ow
through the relief valve to the values indicated in Table 1.
As downstream pressure drops back to normal, the relief
valve closes and the monitor piston moves away from
the seat ring automatically restoring normal operation.
Installation
Personal injury or system damage
may result if this regulator is installed,
without appropriate overpressure
protection, where service conditions
could exceed the limits given in the
Specications section. Regulator
installations should be adequately
protected from physical damage.
All vents should be kept open to permit
free ow of gas to the atmosphere.
Protect openings against entrance of
rain, snow, insects, or any other foreign
material that may plug the vent or vent
line. On outdoor installations, point
the spring case and monitor casing
vent downward to allow condensate to
!
(1)
WARNING
2
TYPE NUMBER
S203, S203P
S203H/
S203P
S203 Series
Table 1. Maximum Downstream Pressure Build-up and Relief Valve Flow
RELIEF MONITOR
SPRING PART
NUMBER
(COLOR CODE)
1L255727132
(Green)
1L255827132
(Red)
1L255927132
(Blue)
1V2242270120.5 to 1.0 psig (0,03 to 0,07 bar)3.0 (0,21)02200 (59)
1V224227012
(Silver)
OUTLET PRESSURE RANGE,
INCHES W.C. (mbar)
Up to 5 (Up to 12)0.8 (0,05)0950 (26)
4 to 9.5 (10 to 24)1.0 (0,07)11000 (27)
8 to 14 (20 to 35)1.25 (0,09)21200 (32)
8 to 12 (20 to 30)1.4 (0,10)01350 (36)
10 to 20 (25 to 50)1.8 (0,12)11600 (43)
14 to 28 (35 to 70)2.8 (0,19)21900 (51)
11 to 21 (27 to 52)2.2 (0,15)01800 (48)
18 to 33 (45 to 82)3.0 (0,21)12000 (54)
28 to 45 (70 to 112)3.8 (0,26)22200 (59)
0.75 to 1.6 psig (0,05 to 0,11 bar)4.0 (0,28)12500 (67)
1.25 to 2.25 psig (0,09 to 0,16 bar)5.0 (0,35)23000 (80)
1.25 to 3.25 psig (0,09 to 0,22 bar)6.0 (0,41)33000 (80)
MAXIMUM
DOWNSTREAM
PRESSURE BUILD-UP,
PSIG (bar)
NUMBER
OF LOWER
SPRING SEATS
REQUIRED
MAXIMUM FLOW
THROUGH RELIEF
VALVE, SCFH (Nm3/h) OF
0.6 SPECIFIC GRAVITY
NATURAL GAS
Table 2. Main Spring Pressure Ranges
TYPE
NUMBER
S203,
S203P
S203H/
S203P
SPRING RANGE,
INCHES W.C. (mbar)
2 to 4.5
3.5 to 6.5
5 to 9
8.5 to 18
14 to 30
1 to 2 psig
1.5 to 3.25 psig
(5 to 11)
(9 to 16)
(12 to 22)
(21 to 45)
(35 to 75)
1. Maximum emergency outlet (casing) pressure for S203 Series is 15 psig (1,03 bar).
MAXIMUM INLET PRESSURE, PSIG (bar)
Types S203, S203PType S203H
125
125
100
60
25
13
(8,6)
(8,6)
(6,9)
(4,1)
(1,7)
(0,90)
125
125
100
60
30
14
(8,6)
(8,6)
(6,9)
(4,1)
(2,1)
(0,97)
(1)
drain (see Figure 2). This minimizes the
possibility of freezing and of water or
other foreign materials entering the vent
and interfering with proper operation.
Under enclosed conditions or indoors,
escaping gas may accumulate and be
an explosion hazard. In these cases,
the vents should be piped away from the
regulator to the outdoors.
D
VENT
VENT
C
VENT
E
POINT VENT DOWN
A4196
VENT
F
Figure 2. Various Vent Positions
CAUTION
Like most regulators, S203 Series
regulators have an outlet pressure rating
lower than their inlet pressure rating.
Overpressuring any portion of the
regulators beyond the limits in Tables 3
and 4 may cause leakage, damage to
regulator parts, or personal injury due to
bursting of pressure-containing parts.
If the regulator is exposed to an
overpressure condition, it should be
inspected for any damage that may
have occurred. Regulator operation
below these limits does not preclude
the possibility of damage from external
sources or from debris in the pipeline.
3
S203 Series
Before installing the regulator, check for damage which
might have occurred in shipment. Also check for dirt
or foreign matter which may have accumulated in the
regulator body or in the pipeline. Apply pipe compound
to the male threads of the pipeline and install the
regulator so that ow is in the direction of the arrow cast
on the body. The diaphragm casing assembly can be
rotated to any position relative to the body. Loosen the
two cap screws holding the union ring (key 18, Figure 4)
in order to rotate the diaphragm casing assembly.
Do not install the regulator in a location where there
can be excessive water accumulation, such as directly
beneath a downspout.
The regulator vent is 1-inch FNPT and the monitor vent
is 1/4-inch FNPT. The vent openings are screened to
prevent insects from entering. On outdoor installations,
the vent opening must be pointing down, see Figure 2, for
protection against the elements and to allow condensate
to drain.
Indoor installations require a separate vent line be run
from each vent to a safe outdoor location. The vent
lines should be of as large diameter pipe as practical
with a minimum number of bends. Remove the vent
screen when attaching the piping to the vent. A weather
resistant vent assembly, such as Fisher® Type Y602,
should be installed at the end of each vent piping
with the vent assembly opening pointing down. The
vent assembly should be in a protected location as
explained above for regulators installed outdoors.
A program of regular inspection of the vent opening
should be established to see that it has not become
plugged by foreign material. On some installations,
such as in areas of heavy snowfall, it may be
necessary to install the regulator beneath a protective
hood. If other protection is provided from the elements,
the vent should be pointing or sloping down sufciently
to allow any condensate to drain.
It is advisable that the downstream piping be the same
size as the regulator outlet for a minimum distance of
18-inches (457 mm) or to the meter inlet. Replace the
regulator if water gets into the spring case or the lower
casing to the regulator.
Downstream Control Line
The Types S203P-1, -2, and -3 units must be installed
with an external downstream control line. Install the
control line before putting the regulator into operation or
the regulator will remain wide-open. The downstream
control line should be pipe of at least 1/2-inch
(13 mm) diameter and connected to a straight section
of outlet piping 5 to 10 pipe diameters downstream of
the regulator. A hand valve should be installed in this
section of the control line. This hand valve can be
throttled down to dampen out pulsations which may
cause instability or cycling of the regulator. However, the
control line hand valve must never be closed completely
during operation. Since the throat is blocked to isolate
the main diaphragm and a sealing screw (key 99,
Figure 5) in the pitot tube isolates the monitor
diaphragm, install a tee in the control line between the
regulator and the hand valve. Then run one line from
the tee to the connection in the lower casing assembly
which is tapped in the S203P Series and another line
from the tee to the tapped connection (key 46, Figure 4)
in the monitor spring case.
Startup
CAUTION
Pressure gauges should always be used
to monitor downstream or control line
pressures during startup. Downstream
or control line pressure must never
exceed the setpoint (dictated by the
spring setting) by more than 2 psi
(0,14 bar) (light diaphragm plate) or 3 psi
(0,21 bar) (heavy plate). If it does, the
valve seat and/or diaphragm plate may
be damaged. Procedures used in putting
the regulator into operation must be
planned accordingly if the downstream
system is pressurized by another
regulator or by a manual bypass.
If the downstream system is not pressurized by
another regulator or manual bypass valve, use the
following procedure:
1. Open the hand valve in the control line
(Type S203P-1, -2, or -3).
2. Slowly open the upstream shutoff valve.
3. Slowly open the downstream shutoff valve.
4. If the regulator (with a downstream control line) has
a tendency to pulsate, throttle down the hand valve
in the control line, but never close it completely
while the regulator is in operation.
5. Check all connections for leaks.
6. Light the appliance pilots.
Adjustment
To increase the outlet pressure setting of the regulator,
compress the main spring (key 2, Figure 4) by removing
the closing cap (key 4, Figure 4) and turning the adjusting
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.