Emerson Rosemount 1495, Rosemount 1496 Quick Start Manual

Quick Start Guide
00825-0100-4792, Rev. BB
February 2014
Rosemount 1495 Orifice Plate Rosemount 1496 Orifice Flange Union
Quick Start Guide
February 2014
NOTICE
This installation guide provides basic guidelines for Rosemount 1495 Conditioning Orifice Plate. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the 1495 reference manual (document number 00809-0100-4792) for more instruction. This manual is also available electronically on www.rosemount.com.
Process leaks may cause harm or result in death
To avoid process leaks, only use gaskets designed to seal with the corresponding flange and o-rings to seal process connections.
Contents
Primary element location . . . . . . . . page 3
Primary element orientation . . . . . page 3
Primary element installation . . . . . . page 4
Product certifications . . . . . . . . . . . . page 7
February 2014
30 degrees
Recommended
Zone 120 degrees
30 degrees
F
l
o
w
F
lo
w
Recommended
Zone 90 degrees
45 degrees
45 degrees
F
l
o
w
Quick Start Guide
Step 1: Primary element location
To obtain published accuracy for a 1495 Orifice Plate, sufficient straight run is required to produce a fully developed flow profile. Please see Appendix B of the Rosemount 1495 Orifice Plate Manual (00809-0100-4792) for a list of required straight pipe recommendations based on ISO 5167, AGA Report No. 3, and ASME MFC 3M Standards. Shorter straight runs are possible, but accuracy will be affected per the Standards. Consult the Factory for further information.
Step 2: Primary element orientation
Horizontal pipe installation
Gas Steam
FLOW
Liquid
Quick Start Guide
FLOW
Flow
Flow
HI Instrument
Line
LO Transmitter Connection
LO Instrument Line
Flow
* Bring height of HI instrument line to the same height as
LO instrument line before running down to the transmitter
HI Instrument Line
LO Transmitter Connection
LO Instrument Line
Vertical pipe installation
Gas Steam
February 2014
*
Liquid
Step 3: Primary element installation
Note
For the 1496 Flange Union refer to the Rosemount 1495 Orifice Plate reference manual (document number 00809-0100-4792).
Use the following steps to install the 1495 Orifice Plate (paddle or universal plate style).
1. Determine Location and Orientation (see
2. Install the Orifice Plate
page 3).
February 2014
Nuts
Transmitter
Stud Pipe Section
1595
(1)
Jackscrew (2)
Plug (2)
Nut
Gasket (2)
Jackscrew Nut
F
lo
w
(1) The installation drawings applies when using the Rosemount 3051S, Rosemount 3051C,
and Rosemount 3095MV transmitter. See the following documents for quick installation instruction of the transmitters. Rosemount 3051S: document number 00825-0100-4801 Rosemount 3051C: document number 00825-0100-4001 Rosemount 3095MV: document number 00825-0100-4716
Jackscrew
Nut
a. Depressurize the line using site-specific requirements. b. Loosen all studs and nuts.
c. Remove the studs in one-half of the flange union. d. Spread flange union by turning jackscrews clockwise. e. Install the new plate or remove the existing plate for replacement or
inspection.
f. Install the new gaskets when installing the plate. It is recommended that
new gaskets be installed each time the orifice flange union is separated. g. Center the plate in the pipe I.D. h. Release the flange union by turning the jackscrews counter-clockwise. i. Replace the studs. j. Tighten studs in a star pattern.
Figure 1. Rosemount 1495 installation
Quick Start Guide
Quick Start Guide
Nuts
Tra ns mit te r
Stud
Pipe Section
Nuts
Jackscrew Nut
(1) The installation drawings applies when using the Rosemount 3051S, Rosemount 3051C,
and Rosemount 3095MV transmitter. See the following documents for quick installation instruction of the transmitters. Rosemount 3051S: document number 00825-0100-4801 Rosemount 3051C: document number 00825-0100-4001 Rosemount 3095MV: document number 00825-0100-4716
Jackscrew
1495
(1)
Figure 2. Rosemount 1495 with plate holder (PH) installation
February 2014
Product certifications
Approved manufacturing locations
Rosemount Inc. — Chanhassen, Minnesota USA
European Directive information
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office.
European Pressure Equipment Directive (PED) (97/23/EC)
Rosemount 1495 Orifice Plate — Sound Engineering Practice (SEP) Pressure Transmitter — See appropriate Pressure Transmitter QIG
Hazardous locations certifications
For information regarding the electronics product certification, see the appropriate transmitter QIG.
?00825-0100-4792088J
Quick Start Guide
00825-0100-4792, Rev. BB
February 2014
Rosemount Inc.
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 906-8889
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0743
Emerson Process Management GmbH & Co. OHG
Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390, F49 (8153) 939172
Beijing Rosemount Far East Instrument Co., Limited
No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233 F (86) (10) 6422 8586
© 2014 Rosemount Inc. All rights reserved. All marks property of owner. The Emerson logo is a trade mark and service mark of Emerson Electric Co Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Modbus® is a registered trademark of the Modbus Organization, Inc.
Loading...