Bulletin 75.2
D103095X012
March 2021
Type Dosaodor-D
Type Dosaodor-D Odorant Injection System
Figure 1. Type ROC809 Remote Telemetry Unit
Figure 2. Standard Wick Insert Figure 3. Type Dosaodor-D Pneumatic Panel
Introduction
Type Dosaodor-D is a computerized odorant injection
system for natural gas using patented solenoid
injector technology that eliminates the need for
plunger pumps.
Automatic calibration during operation adjusts for any
changes in mechanical components and also detects
failures for alarming. Report by exception alarming is a
congurable option.
The solenoid injectors provide odorant injection
accuracy to be maintained over the entire ow range
of the system, approaching innite turn down.
The system can also be configured to use
redundant injectors and/or an emergency backup or
bypass absorption system.
Type Dosaodor-D
Specications
The Specications section on this page provides the ratings and other specications for Type Dosaodor-D.
Pneumatic Panel:
Material
Stainless steel plate
Installation
Wall mount
Weight
55 to 100 lbs / 25 to 45 kg
(based on configuration)
Overpressure Relief Valve
Stainless Steel with Following Rating Options:
200 psi / 13.8 bar
550 psi / 37.9 bar
870 psi / 60.0 bar
Electrical Protection
Explosion proof
Class I, Division 1 and 2 - Groups B, C, D
Class I, Zone 1 and 2 - Groups IIB+H2, IIA
Mechanical Connections
Odorant Inlet and Discharge
1/4 in. / 6.4 mm OD Tube fitting (double ferrule)
Gas Inlet and Discharge
3/8 in. / 10 mm OD Tube fitting (single ferrule)
Maximum Working Pressure
Supply: 1450 psi / 100 bar
Injection: 870 psi / 60.0 bar
Odorant Flow Rate
0.13 to 3.70 gal/hr / 0.5 to 14.0 l/hr
(0.89 to 24.97 lbs/hr at 6.75 lbs/gal)
Temperature Range
14 to 140°F / -10 to 60°C
Solenoid Valves:
Body Material
304 Stainless steel
Gasket Material
Fluorocarbon (FKM)
Valve Operation
Electromagnetic
Maximum Working Pressure
870 psi / 60.0 bar
Power Requirements
12 Vdc
Electrical Protection
Explosion proof
Class I, Division 1 - Groups A, B, C, D
Stabilizer Filter Type SA/2:
Body Material
Steel
Maximum Working Pressure
1450 psi / 100 bar
Gasket Material
Nitrile (NBR) rubber
Type ROC809 Remote Telemetry Unit:
Refer to Type ROC809 technical specifications.
please go to:
http://www.emersonprocess.com/remote/
Odorant Calibration Cylinder:
Body Material
304 Stainless steel
Maximum Working Pressure
870 psi / 60.0 bar
Maximum Emergency Design Pressure
1450 psi / 100 bar
2
Real time and historical data can be read locally or
remotely by a laptop computer using ROCLINK 800
conguration software, or remotely using third party
SCADA products utilizing ROC or modbus protocol.
ROCLINK 800 software is available for complete
conguration and operation of the system including:
• Display of real time and historical data
• Configuration of alarms
• Archival of historical data
Benets
• Uniform distribution of odorant due to frequent
smaller injections and enhanced absorption from
the wick insertion.
• High turndown ratio. For example, one specific
configuration would evenly distribute odorant at
flow rates from 2000 to 1,000,000 SCFH / 53.6 to
26,800 Nm3/h without mechanical adjustment.
• Automatic calibration of injection system during
normal operation ensuring consistent odorization.
• Environmentally friendly with no venting of gas or
odorant while operating.
• Extremely low maintenance cost.
• Variety of redundancy and backup options for
reliable odorization.
• User friendly configuration software.
• Standard and scalable hardware platform that
supports additional station I/O for AGA flow
calculations and PID control algorithms.
Operation
The Type Dosaodor-D odorant injection system operates
on the basic principle of a fixed differential pressure and
orifice used to measure a non-compressible fluid.
Fixed differential pressure is maintained using double
cut regulation by fixed differential pressure regulators
(Type SA/2 regulators) which reference P2 and reduce
the inlet pressure of a regulating station to
P2 + ΔP. ΔP = 8.7 to 21.7 psi / 0.60 to 1.5 bar,
ΔPmax = 21.7 psi / 1.5 bar (an alternate high
pressure source can be used). This pressure loading
of the odorant calibration cylinder filled with odorant
is used to inject liquid odorant into the downstream
pipeline through an on/off valve (the fixed orifice
with a known flow coefficient that is controlled by the
automated system. The objective of the automated
control system is to maintain an injection rate specified
(1)
)
Type Dosaodor-D
Figure 4. Type Dosaodor-D Intrinsically Safe Panel
by the user which is proportional to the gas flow.
Accuracy of injection is accomplished utilizing relatively
small injections which are automatically resized over a
wide range dependent upon variations in the gas flow.
This results in a turn down ratio for the system that can
exceed 500:1 (the addition of a simple by-pass system
utilizing the odorant storage tank can allow the turn down
ratio to approach infinity). An odorant calibration cylinder
with a fixed volume is utilized to recalibrate the injection
valve flow coefficient each time the odorant calibration
cylinder is refilled.
During the refill cycle the pressure used for injection is
relieved into the downstream pipeline which eliminates
venting of gas to atmosphere or an expansion tank.
Liquid odorant refill of the odorant calibration cylinder is
typically accomplished by using all or some part of the
+ ΔP pressure to load the odorant storage tank thus
P
2
pushing the liquid out of the tank and into the odorant
calibration cylinder, ΔP = 8.7 to 21.7 psi / 0.60 to 1.5 bar.
Since the unit uses only pressure for injection there
are few moving parts in the system resulting in very
little maintenance. Relatively low cost options for both
automated and emergency redundancy for odorization
are also available.
1. Although the valve orice is xed for a specic application the valve can be adjusted manually to accommodate ow rates as small as 2 MSCFH to over 33,000 MSCFH with one injector.
3
Type Dosaodor-D
HAZARDOUS AREA
REGULATING STATION
P1 P2
SAFE AREA
SIGNALS FROM
FLOW COMPUTER
LIQUID
INJECTION POINT
TYPE ROC809
PNEUMATIC PANEL
ODORANT
TANK
Figure 5. General Installation Schematic
The gas flow rate is obtained through either a corrected
gas volume pulse input or an instantaneous flow rate
analog input (4 to 20mA) signal. The gas flow rate can
also be configured manually to a fixed value. Odorant
injection rate is then calculated using accumulated flow
in order to reduce variability.
In cases where the station does not have a flow
computer, the Type ROC809 can be connected directly
to a pulse output from the turbine or an analog output
from a differential pressure transmitter (Rosemount
Types 3051, 3095, etc.).
4