Emerson QF125L, QF115LE, QF145L, QF205L, QF175L User Manual

...
Copeland Scroll
TM
Fusion Compressor
For Refrigeration Applications
User Manual
About Emerson Climate Technologies
Emerson Climate Technologies, a business segment of EmersonTM, is the world’s leading provider of heating, air­conditioning and refrigeration solutions for residential, industrial, and commercial applications. It combines best-in-class technology with proven engineering, design, distribution, educational and monitoring services to provide customized, integrated climate-control solutions for customers worldwide. Emerson Climate Technologies’ innovative solutions, which include industry-leading brand Copeland Scroll™, improve human comfort, safeguard food and protect the environment. For more information, visit EmersonClimateAsia.com.
Leading Innovation in Scroll Semi-Hermetic Technology
Emerson realized an increasing need for a versatile, reliable, quiet, lightweight, serviceable compressor for the Cold Room market and set out to develop a solution for this need. In the development process, the company brought together 70 years of semi-hermetic compressor expertise and 25 years of leadership in scroll technology. What came out of this endeavor is the newly-designed Copeland Scroll Fusion compressor which combines Emerson’s revolutionary scroll technology along with the serviceability of a traditional semi-hermetic compressor.
Table of Contents
Safety Information 04
Features and Benefits 05
Nomenclature 05
Operating Envelopes 06
Technical Data 07
Dimensional Drawings 10
Wiring Diagram 14
Contact Lists 24
Emerson Climate Technologies, with our partners,
will provide global solutions to improve human comfort,
safeguard food and protect the environment.
Our Vision:
Do not run the compressor with air. When operating
with air, the diesel effect may occur – i.e. the air sucked in may mix with oil and gas. Such a mixture could explode due to high temperature in the scroll discharge port and thereby destroy the compressor and cause injury or death.
Open the discharge and suction shut-off valve before
starting the compressor. It is of vital importance that the discharge shut-off valve is fully opened before the compressor is started. If the discharge valve is closed or partly-closed, an unacceptable pressure accompanied by a proportionately high temperature will develop.
All local safety regulations must be observed.
Electrical Shock
Turn off electrical supply and power before servicing.
Use this equipment only in a grounded system.
Refer to the applicable system-wiring diagram as shown
in this manual.
Use Personal Safety Equipment
The new compressor contains oil and dry air under a
pressure of 2.0 bar. While releasing pressure before installation, the oil drain plug may pop out under pressure and oil could spurt out.
Safety gloves, protective clothing, safety boots and
protective eyewear should be worn where necessary.
CAUTION
This icon indicates instructions to avoid property damage and possible personal injury.
WARNING
This icon indicates instructions to avoid personal injury and material damage.
ELECTRICAL SHOCK
This icon indicates operations with a danger of electric shock.
Safety Information
CopelandTM brand products semi-hermetic compressors are manufactured according to international safety standards. Particular emphasis has been placed on the user’s safety. This user manual should be retained throughout the lifetime of the compressor.
Safety instructions must be followed by all users before compressor operation. Only quali ed and authorized personnel
are permitted to do installation, commissioning and repairing of this compressor. Electrical connections must be made
by quali ed electrical personnel.
Caution
Make sure that the compressor is upright and there are
no collisions or tilting during transit.
Use only refrigerants and oils approved by Emerson.
Make sure that the supply power, voltage, frequency
and phase are exactly as per the speci cations on the
compressor nameplate.
The dry air inside the compressor should be evacuated
before installation. The compressor comes charged with dry air at a pressure of 2.0 bar.
Do Not:
Use the compressor to de-pressurize (to evacuate) a
refrigeration system.
Start the compressor when it is under vacuum.
Conduct a test without connecting the compressor to
a system.
Start the compressor without a refrigerant charge.
Operate a compressor beyond its approved application
envelope.
Touch the compressor or pipes when the compressor
is running. High/low temperature may cause burns/ frostbite.
Release refrigerant into the environment without using
appropriate refrigerant recovery unit and methods when removing refrigerant from the system.
When operating the compressor or checking a
refrigeration system leakage, do not exceed operating pressures out of the application envelope.
ICON DEFINITION
Product Description
Nomenclature
Features and Bene ts
Emerson’s Copeland Scroll technology
Serviceability in the  eld
CoreSense™ Diagnostics
Integrated vapor injection technology
Wide range envelope and ef cient operation
Ability to handle various refrigerants
Copeland ScrollTM Fusion was crafted speci cally to adhere to the refrigeration industry’s need for  eld serviceable solutions. In addition, it is specially designed for medium and low temperature refrigeration with the ability to handle various refrigerants.
Q F 1 8 5 L E-T W D-2 0 2
Family
Q – Copeland Scroll Fusion
Scroll Displacement
(cc/rev)
Bill of Material
Type of Oil
Code Description
E POE Blank Mineral Oil
Intelligence and Motor Protection
Code Type
W CoreSense™
Application Range Code Application Approved Refrigerants F Full Range R22/R404A
Low/Med/High
Model VariationAMotor Types
Code Phase
T 3
Typical Electrical Codes Code 60 Hz 50 Hz
D 460-3 380/420-3
7 380-3 –
Note: QF205 has low temperature model only.
Warning
Operating Envelopes
QF115/QF125/QF145/QF175/QF185
QF205
Nameplate Information
Figure 1. Nameplate and nameplate location
Technical Data
20100-10-20-30-40-50
0
10
20
30
40
50
60
70
Note: 20oC Return Gas Temperature. No Fan Cooling
Condensing Temperature
o
C Condensing Temperature
R404A
R22
-32
o
C Low Temperature
Showcase
-25
o
C Low Temperature
Cold Room
-12
o
C Medium Temperature
Showcase
-7
o
C Medium Temperature
Cold Room
Evaporating TemperatureoC
Model
R22 QF115L QF125L QF145L QF175L QF185L QF205L
R404A QF115LE QF125LE QF145LE QF175LE QF185LE QF205LE
Displacement m
3
/h 19.3 21.1 23.5 26.4 30.4 36.9
MOC
1
TWD 50 Hz A
24 25 27 32 33 25
LRA
2
80 80 80 105 105 105
Motor Speed 50 Hz rpm 2,900
Crankcase Heater
Power W 60
Voltage V 220
Oil Charge
Initial
L
2.66
Recharge 2.54
Service Valves
Suction
in
1-1/8
Discharge 1
Dimensions
Length
mm
675
Width 355
Height 389
Base Mounting
Length
mm
350
Width 200
Bolt M10
Weight
Net
kg
130
Gross 140
Notes: 1. MOC: Maximum Operating Current
2. LRA: Locked Rotor Current
3. QF205LE has low temperature model only
50 Hz
R22/R404A
R22/R404A
R22 / R404A
Evaporating TemperatureoC
-32
o
C Low Temperature
Showcase
-25
o
C Low Temperature
Cold Room
Note: 20oC Return Gas Temperature. No Fan Cooling
20100-10-20-30-40-50
0
10
20
30
40
50
60
70
Note: 20oC Return Gas Temperature. No Fan Cooling
Condensing Temperature
o
C Condensing Temperature
o
C
R404A
R22
-32
o
C Low Temperature
Showcase
-25
o
C Low Temperature
Cold Room
-12
o
C Medium Temperature
Showcase
-7
o
C Medium Temperature
Cold Room
Evaporating TemperatureoC
20100-10-20-30-40-50
0
10
20
30
40
50
60
70
Mounting Parts
Caution
To minimize vibration and start/stop impulses, fl exible
mountings should be used. Because Copeland Scroll™ Fusion has scroll hermetic compressor level of vibration, grommets are delivered. A compressor may be rigidly mounted (i.e. without grommet) - in which case, more shock and vibration will be transmitted to the frame.
To ensure proper lubrication of moving parts, the compressor should be installed with four mountings in the same plane.
Mounting Kit Part Code: 027-0443-00
Installation
Compressor Handling
Deliver y
Please check carefully for unforeseen damage. Any shortage or damage should be reported to the delivering carrier. Heavy equipment should be left on its shipping
base until it is moved to the  nal location.
The packing list included with each shipment should be carefully checked to determine if all parts and equipment
have been received. De ciencies should be immediately reported in writing to your local Emerson Sales Of ce.
Standard delivery
Suction and discharge shut-off valves
Oil charge, oil sight glass
Oil level sensor
Oil differential pressure switch
Oil temperature sensor
Plate heat exchanger
Electronic expansion valve
Crankcase heater
CoreSense™ Diagnostics
Holding charge of up to 2.0 bar (dry air)
For other accessories, please check the packing list
Packaging
All compressors are individually packed. Accessories may be mounted or delivered loose. Please pay attention to stacking layers. Stacking in transit should not be more than two layers and stacking in-store should not be more than three layers. The packaging must be kept dry and without damage at all times.
Transport
Compressors should be moved only with mechanical handling equipment appropriate for the weight involved. For safety reasons, one lifting eye should be
 tted before moving a compressor (M16x2.0). Please
refer to the illustrations on Figure 3 to see how to lift the compressor safely.
The compressors must not be lifted by the service valves or other accessories. Otherwise damage or refrigerant leaks may occur.
Figure 4. Mounting Kit
Figure 3. Compressor lifting method
Lifting eye
M16x2.0 Thread
Lifting eye
Warning
The compressor is supplied with an initial oil charge. Mineral oils are approved for R22 application, and Karamay
32BYMO is  lled ex-factory. The standard oil charge for use
with R404A is a polyester (POE) lubricant Emkarate RL 32-
3MAF. In the  eld, the oil level could be topped up with
Mobile EAL Arctic 22 CC if 3MAF is not available.
Do not mix ester oils with mineral oil and/or alkyl benzene when using chlorine-free (HFC) refrigerants. See
nameplate for original oil charge in litres. A  eld recharge
is from 50-100 ml less than the original charge.
Oil must be drained from both the high and low sides of the compressor whenever oil is changed.
One disadvantage of POE is that it is far more hygroscopic than mineral oil (see Figure 2). Brief exposure to ambient air causes
POE to absorb suf cient moisture to make it un t for use in a
refrigeration system. Since POE holds moisture more readily
than mineral oil, it is more dif cult to remove it through the
use of a vacuum. Compressors supplied by Emerson Climate Technologies contain oil with low moisture content, and this may rise during the system assembling process. POE oil should not be exposed to the atmosphere for longer than 15
minutes. A  lter drier is installed to help maintain moisture
level in the oil less than 50 ppm. If oil is charged into a system, it is recommended to use POE with a moisture content no higher than 50 ppm.
Maximum Operating Pressures
A high-pressure control with a maximum cut-out setting of 28 bar(g) is required. The high-pressure cut-
out should have a manual reset feature for the highest level of system protection.
The low-pressure cut-out should be set as high as possible in all applications. For medium temperature applications, the normal minimum is 2.5 bar(g) which corresponds to -10oC for R22 and -16oC for R404A.
For low temperature applications the minimum cut-out setting should not be lower than 0.3 bar(g) for a compressor using R404A, and should not be lower than 0.1 bar(g) for a compressor using R22. The cut-out point of the LP switch must be calibrated using an accurate suction
pressure gauge
rather than the scale on the switch which is
provided for rough
setting only.
The Copeland Scroll™ Fusion compressor should NEVER be allowed to run in a vacuum. The low­pressure cut-out should have a manual reset feature for the highest level of system protection.
The maximum pressure for leak testing should be no higher than 22.5 bar(g).
Approved Refrigerants and Oil
Refrigerants R404A and R22 are approved for use with Copeland Scroll Fusion. Application with other refrigerants may be possible in special cases. Please contact an Emerson Climate Technologies Application Engineer.
Caution
Caution
Warning
Caution
Caution
Moisture Absorption
@ 25
o
C & 50% RH
Figure 2. Absorption of moisture in ester oil in comparison to mineral oil in ppm by weight at 25°C and 50% relative humidity.
POE
Mineral Oil
1500
1000
500
50 100 150 200 300250
hours
PPM
Figure 7. Piping guideline
To disconnect:
Reclaim refrigerant from both the high and low side of the system. Cut tubing near compressor.
To reconnect:
Recommended brazing material is one with minimum 45% silver or silver braze material with fl ux. Insert tubing
stubs into  tting and connect to the system with tubing connectors. Follow instructions on Brazing.
Piping Connections
Copeland Scroll™ Fusion has very low vibration characteristics, so discharge and suction vibration eliminators should not be necessary in the majority of installations. The suction, discharge and liquid pipes should all have sections running close to the compressor body in parallel with the shaft to absorb any startup or shutdown torsion. Vibration is much lower than those found in equivalent piston compressors, and discharge
pulsations are negligible due to the muffl ing effect of the
discharge cover.
Recommended minimum straight length from discharge
valve to  rst bending point is 200 mm, minimum bending
radius is 60 mm.
For ease of service, a minimum space of 500 mm between top cap surface to casing wall is recommended. Refer to Figure 7.
Vapor Injection and Liquid Line Temperatures
Copeland Scroll Fusion compressor package applies vapor injection technology to improve LT operational
ef ciency and provides a reliable LT envelope. Vapor
injection sub cools the main liquid line and compressor oil using the integrated plate heat exchanger economizer. The subcooling of liquid line calls for these recommendations:
1. Liquid line pipe connecting the economizer to the evaporator expansion valve has to be well insulated separately. See Liquid Line Insulation for insulation thickness.
2. The lower liquid line temperature can increase the evaporator expansion valve capacities. Please follow valve manufacturers recommended liquid temperature correction factors for proper selection of evaporator expansion valve. Refer to catalogue or contact your
local Emerson sales of ce for liquid line temperatures.
No. Connection/Port Size No. Connection/Port Size
1 DPS (differential pressure switch) 3/4”-16UNF 2 Plug low-pressure connection 1/4”-18NPTF
3 Bolt-mounting M10 4 Plug oil drain 1/4”-18NPTF
5 Nut-oil out  tting M16 6 Connector DLT/VIT/VOT/optical OLS/DPS
7 Connector E XV/oil temperature sensor 8 Screw grounding M5
9 Connector optional 10 Nut- oil in  tting M16
11 Liquid out 3/4” 12 Liquid in 3/4”
13 DLT sensor 14 Vapor out temperature sensor
15 Nut- EVI  tting M20 16 EXV Coil
17 Vapor in temperature sensor 18 Optical oil level sensor 7/8”-14UNF
19 Built-in oil screen M20 20 Oil level sight glass
21 Crankcase heater 22 Low pressure port
23 Suction valve 28.7 ID 24 Plug high-pressure connection 1/4”-18NPTF
25 Discharge valve 25.7 ID 26 High pressure port
Notes: SL: Suction Line
DL: Discharge Line
Piping Connection and Compressor Installation
Brazing
It is important to fl ow nitrogen through the system
while brazing all joints during the system assembly process. Nitrogen displaces the air and prevents the formation of copper oxides in the system.
Recommended brazing materials: any material is
recommended, preferably with a minimum of 45% sil ver.
Be sure valves I.D. and connecting tube O.D. are
clean prior to assembly. If oil  lm is present, wipe with denatured alcohol, Dichlorotrifl uoroethane or other
suitable solvent.
Using a double-tipped torch apply heat in Area 1. As
tube approaches brazing temperature, move torch
fl ame to Area 2.
Heat Area 2 until braze temperature is attained,
moving torch up and down and rotating around tube as necessary to heat tube evenly. Add braze material to
the joint while moving torch around joint to fl ow braze
material around circumference.
After brazing material fl ows around joint, move torch to
heat Area 3.
This will draw the braze material down into the joint.
The time spent heating Area 3 should be minimal.
As with any brazed joint, overheating may be
detrimental to the  nal results.
When welding the discharge line connection pipe to the
discharge service valve, the O-ring must be replaced with a new one. Replacement O-ring can be found on the accessory bag.
If the suction and discharge shut-off valve bolts or
rotary valve joint are released while brazing the shut-off valves, replace the shut-off valve spacer or O-ring. The non-metal valve spacer and O-ring must be oiled prior to assembly.
Figure 6. Compressor connection and ports. For identifi cation refer to the Table on the next page.
Dimensional Drawings
Figure 5. Brazing
Compressor
Valve
{
{
Area3Area2Area
1
Connecting
Tube
All dimensions are in mm
High Pressure and Low Pressure Cut-out Settings
A high-pressure control with a maximum cut-out setting of 28 bar(g) is required. The high-pressure cut-out should have a manual reset feature for the highest level of system protection.
The low-pressure cut-out should be set as high as possible in all applications. For medium temperature applications the normal minimum is 2.5 bar(g) which corresponds to -10oC with R22 and -16˚C with R404A. For low temperature applications the minimum cut­out setting should not be lower than 0.3 bar(g) for a compressor using R404A, and should not be lower than
0.1 bar(g) for a compressor using R22. The cut-out point
of the LP switch must be set using an accurate suction pressure gauge rather than the scale on the switch which is provided for rough setting only.
Warning
Copeland Scroll Fusion compressor should NEVER be allowed to run in a vacuum.
The low-pressure cut-out should have a manual reset feature for the highest level of system protection.
Liquid Solenoid Valve
A liquid line solenoid valve is effective in keeping liquid out of the low side when the system cycles on the thermostat. The solenoid should be installed close to the expansion valve to keep the main volume of the liquid line on the high side of the system during off periods. All solenoid valves leak slightly and may not be 100% effective in keeping liquid in the high side during extended shutdown periods which can occur in cold rooms used for storing seasonal products. In most cases, opening and closing the solenoid valve when the compressor starts and stops provides adequate protection from liquid migration to the compressor crankcase.
Liquid Line Insulation
Copeland Scroll™ Fusion compressors have many characteristics found on two-stage piston compressors, among them, a cold liquid line after the heat exchanger. The cold liquid is very important for improving the system
capacity and ef ciency, and any increase in liquid line
temperature after the heat exchanger is a system loss.
The liquid line should therefore be insulated with tightly-fitted closed cell foam. The wall thickness of
the insulation should be at least 10 mm for medium temperature applications and >15 mm for low temperature applications. In some low temperature applications, an uninsulated liquid line could even cause ice formation, and in humid environments condensation will occur. The line connecting the receiver to the inlet of the heat exchanger does not require insulation.
Pumpdown Cycle
Pumpdown cycles are widely applied in systems with reciprocating compressors. Copeland Scroll Fusion compressors have inherently superior liquid handling capability, so a pumpdown at each thermostat cycle is not recommended. A pumpdown cycle before defrost will be helpful in reducing the defrost time. Copeland Scroll Fusion compressors are  tted with a spring loaded low-leak check valve under the discharge service valve, so an external check valve should not be necessary. When
pumpdown  nishes, the compressor will stop and contain
a very large volume of high pressure gas in the top cap area. This refrigerant will quickly leak back to suction and
will cause a signi cant pressure rise that could reset the
low pressure switch. The control circuit should not allow the compressor to restart; restart should only occur when the thermostat closes.
Figure 8. Schematic Diagram
High Pressure and Low Pressure switches must be  tted by
the system manufacturer and connected to the pressure ports shown in the compressor outline drawing on Figure 6. HP and LP cut-out switches must be electrically connected as shown in the wiring diagram on Figure 10.
Electrical Installation
The compressor is supplied with a wiring diagram inside the terminal box cover as shown in Figure
10. Fuses and circuit breakers must be installed in accordance with local electrical regulations. The terminal box has an IP54 rating.
Electrical Shock
Conductor Cables! Electrical Shock! Shut Off Power before High potential testing
The compressor and accessories are tested for leakage to ground before shipping. Disconnect the control board
PWR and DEMAND connections to avoid any risk of damage during high potential testing.
Three-phase Motors
All compressors can be started direct on line only.
Control Board Connection
The control board, which is mounted in the terminal box, monitors the compressor sensors, protects the compressor, drives the electronic expansion valve and displays useful information in a seven segment display. Three red LEDs indicate the status of the CCC (compressor contractor coil), Alarm and a relay which is connected to the black terminal block. The board is powered via a transformer with a nominal output of 16 VAC. When correctly wired and powered up the board goes through
a self checking routine and displays a fl ashing 0. If the
display is blank, check the power supply on the PWR, the transparent fuse, the transformer input and output, and the white fuse. The transparent fuse (250 V 2A) protects the transformer and other on-board electronic components. The white fuse (250 V 1A) protects the system control circuit and the on-board relays from external short circuits.
Wiring Diagram and Wiring Instruction
The position of the 4-Bit Dip Switch in the terminal box and the recommended wiring diagrams are shown in Figures 9 and 10.
Warning
CoreSense™ Diagnostics
The CoreSense Diagnostics module in the terminal box monitors several sensors and protects the compressor from the following malfunctions:
Reverse rotation by oil differential pressure switch
Compressor not pumping by oil differential pressure
switch
High discharge temperature by discharge port
temperature sensor
High oil temperature by oil temperature sensor
Low oil level by optical oil level sensor
Motor overheat by embedded four thermistors
High pressure – cut-out to be connected by system
manufacturer or installer
Low pressure – cut-out to be connected by system
manufacturer or installer
Warning
Fusion Control Box Wiring Standard
According to Figure 11, there are 4 joints at the bottom of the control box. Each joint has dedicated wires to be assembled. Table 1 explains the function, requirement and connection method of each joint and wires inside. Wire C, D and G have been pre-wired in factory. C (Black) and D (Orange) are for compressor start/stop feedback input, connecting to “Demand” (Blue) connectors. G (Red) is wire of power input for Alarm Devices, connecting to “Alarm”
Figure 9. CoreSense™ Diagnostics Board
TXV: Thermostatic Expansion Valve Fusion Standard BOM
VI: Vapor Injection EXV: Electronic Expansion Valve
Note: Sight glass is provided and installed as standard ex-factory only in
TWD models
(Orange) connector. The wire size for these three pre­wirings is 18AWG.
Figure 12, on the other hand, shows the recommended wiring sequence for the control box.
CoreSense Diagnostics module is functioned to record latest 10 alarm histories. By pushing one button on the board, the user can check the alarm codes from latest to distant in sequence on LED display. The display starts from “H” and ends with “h”. When alarm code is blank, the display will show “0” instead.
Figure 10. Wiring Diagram
Wiring Diagram Wiring Instruction
Figure 11. CoreSense™ Wiring and Joints
Step 1: Connect Compressor Motor Wires
Step 3: Connect “CCC” Terminal Wires
Step 4: Connect “Alarm” Terminal Wires
Step 2: Connect “PWR” Terminal Wires
Figure 12. CoreSense™ Recommended Wiring Sequence
L
H G F D BE C A
J
I
4 3 2 1
K
Crankcase Heaters
Crankcase heaters are very effective in keeping liquid out of the compressor and are recommended for all installations. The heater should be on when the compressor is stopped.
At the time of initial startup, or after any extended pe­riod without power, the heater should be energized 12 hours before starting the compressor. Long off periods are common in cold stores holding seasonal products, so it is particularly important to turn on power to the unit 12 hours before restarting after a long idle period. A 220 V 60 W heater is supplied as standard equipment.
Startup and Operation
Leak / Pressure Testing
The compressor has been pressure tested in the factory. It is not necessary for the system manufacturer or installer to pressure test or leak-test the compressor again although the compressor will normally be exposed to the pressure used as part of system testing. Consider personal safety requirements and refer to nameplate test pressures prior to testing.
Figure 14. Sensor Location
Differential Oil Pressure Sensor
Optical Oil Level Sensor
Discharge Port Temp. Sensor
Vapor In Temp.
Sensor
Vapor Out
Temp. Sensor
Gland
(Waterproof)
Number
Gland 1 Gland 2 Gland 3 Gland 4
Gland Description
For “PWR” and “Demand” Connector’s Wires
For “CCC” Connector’s Wires
For “Alarm” Connector’s Wires
For Compressor Motor Power Supply Wires
One jacket line with two wires goes through the joint
One jacket line with two wires goes through the joint
One jacket line with two wires goes through the joint
One jacket (PVC) line with four wires goes through the joint
Wire Function
A(Red) and B(Black): Controller Power Supply Input(220-240VAC 50/60Hz)
E(Brown) and F(Blue): Compressor Diagnostic/ Protection Contact Output
H(Brown): Output For Alarm Devices
I, J, K: Compressor Motor Power Supply
L: Earth Wire
Wire Connection
Wires A and B: “PWR” (Green) connectors
Wires E and F: “CCC” (Green) connectors
Wire H: “Alarm” (Orange) connectors
N/A
Gland Internal
Diameter Range
5-10 mm 5-10 mm 5-10 mm 18-25mm
Jacket Line
Requirement
Internal wire size: 18-20 AWG
Internal wire seize: 8 AWG or above (4 wires in total)
Recommended wire size: 18 AWG
Rated voltage: 300V/500V
Rated voltage: 600V/1000V
Reverse rotation and lack of pumping have the same symptoms: the discharge pressure does not rise and the suction pressure does not fall. If the control module senses that the differential pressure switch has not closed after a short time delay, the compressor will stop, an error message will be displayed on the control board, and a timer will be started. Three more attempts will be made to start and if differential pressure is not established, the compressor will be locked out. The alarm contact will close and can be used by the installer to turn on a light, sound a bell, etc. The alarm contact is voltage-free allowing
maximum fl exibility with regard to the type of alarm
device that can be connected. The alarm relay contact is rated at 250 VAC 1A and 30 VDC 1A.
High discharge temperatures often occur when the system is short of refrigerant: suction temperature rises,
bubbles form in the liquid line and there is insuf cient
liquid to feed the injection EXV properly. The control module will stop the compressor, display a fault code and close the alarm relay. After a time delay, the compressor
will restart. High discharge temperature alarms indicate a serious system problem, and corrective action must be taken to avoid long term compressor damage and possible product loss.
Oil stored in compressor high side oil tank keeps same pressure and temperature as discharge gas. When oil flows from oil tank to bearing, it goes through the heat exchanger in a separate passage for cooling. High oil temperature could cause to lubricating deterioration as well as bearing failure. If the oil temperature goes to its upper limitation, the control module will display an alarm code. If oil temperature continues to increase up to a setting point, compressor will be tripped, and could restart after time delay.
Warning
Oil level is monitored by an optical sensor in the high side oil sump. If the level falls to the minimum allowable, a timer will start and the compressor will be stopped if
suf cient oil has not returned to the sump in one minute.
Figure 13. Terminal Box Location For Wiring
Remove Terminal Box Cover for Customer Wiring
M25, 6 Sensors
M20, EXV Wires
M20, Motor Power
3xM16, Other Wires
Table 1: Glands and Wires
Warning
Warning
Warning
Oil Temperature Sensor
Two restarts will be attempted after short delays, and if the oil level does not recover, the compressor will be stopped and locked out. An alarm message will be displayed and the alarm relay will close.
Motor overheat may occur when the suction gas temperature is abnormally high, mass flow is low and discharge pressure is also high. Four thermistors are embedded in the windings and monitored by the control module. If the module senses that the winding temperature is high, it will stop the compressor and start a timer. A restart will be attempted when the windings have cooled and the timer has timed out. The compressor will not be locked out, but the cause of overheat must be investigated to prevent long term compressor damage. Motor overheat can be caused by a mechanical problem, which, if not
recti ed quickly, could cause complete compressor failure
and system contamination. Common mechanical problems that lead to motor trips include worn bearings or worn scroll sets as a result of overheating.
Oil may not be visible when compressor is stopped. Run compressor until conditions are stable. Oil level should be between 1/4 and 3/4 sight glass.
Checking Thermistors and Sensors
Table 2 provides resistance values of the thermistors at several useful temperatures.
Use a voltage no higher than 3 VDC when testing.
An ice bath can be used at 0oC and boiling water can be used at 100oC.
Table 2. Thermistors
Location
Temperature
0
o
C 25oC 100oC
Discharge 326 K Ohm 100 K Ohm 7 K Ohm
Oil 326 K Ohm 100 K Ohm 7 K Ohm
Vapor In 28 K Ohm 10 K Ohm 950 Ohm
Vapor Out 28 K Ohm 10 K Ohm 950 Ohm
For the motor thermistor chain, the trip resistance is >
4.5 K Ohms and the reset resistance is < 2.75 K Ohms. Resistance at room temperature should be < 500 Ohms. If the oil level switch is not functioning correctly, the optical part can be easily changed without breaking into the system. Malfunction is also possible if the lens is coated by system contaminants. The lens will need to be removed and cleaned to restore correct operation.
Warning
Caution
Caution
Caution
Maintenance
Refrigerant Exchange
Quali ed refrigerants and oils were indicated on page 8. It is not necessary to replace the refrigerant with a new one unless contamination due to an error such as topping up the system with an incorrect refrigerant is suspected. To verify correct refrigerant composition, a sample can be taken for chemical analysis. A check can be made during shut down by comparing the refrigerant temperature and pressure using precision measurements at a location in the system where liquid and vapor phases are present and when the temperatures have been stable.
In the event that the refrigerant needs replacing, the charge should be recovered using a suitable recovery machine.
When R22 in a system with mineral oil is to be replaced with R407C or R404A, the oil must also be changed. Please refer to Technical Information “Refrigerant changeover from HCFC to HFC Refrigerants”.
Replacing Compressor
Rotalock valves should be re-torqued periodically to ensure that leak tightness is maintained. All gaskets and
 ttings should be inspected for signs of leaks and repaired
if necessary. Electrical connections should be checked for tightness. All wires should be clamped securely and routed away from hot surfaces to prevent damage from vibration and heat.
Some minor repairs like sensor replacement can be done while the compressor is still under pressure. To replace components that are under pressure, shut down the compressor, wait 15 seconds, and turn off all power. Close the service valves, recover the refrigerant and change the faulty component. Evacuate the compressor only, open the service valves, and recharge the same quantity of refrigerant that was recovered.
Change the accumulator after replacing a compressor with
a burned out motor. The accumulator oil return ori ce or
screen may be plugged with debris or may become plugged. This will result in starvation of oil to the new compressor and a second failure.
I
n the case of a motor burnout, the majority of contaminated
oil will be removed with the compressor. The rest of the oil
is cleaned through the use of suc tion and liquid line  lter
The maximum pressure for leak testing should be no higher than 22.5 bar(g).
Use only dry nitrogen or dry air for system pressure testing. DO NOT USE other industrial gases.
If using dry air do not include the compressor in the
pressure test – isolate it  rst. Never add refrigerant to the
test gas (as leak indicator).
System Evacuation and Dehydration
Before the installation is put into operation, remove the holding charge then evacuate with a vacuum pump. Proper evacuation reduces residual moisture to 50 ppm. The installation of adequately sized access valves at the furthest point from the compressor in the suction and liquid lines is advisable. To achieve undisturbed operati on, the compressor valves are closed and the system is evacuated down to 0.3 mbar / 0.225 Torr. Pressure must be measured using a vacuum pressure (Torr) gauge on the access valves and not on the vacuum pump; this serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump. Then the compressor must be evacuated. Due to the factory holding charge of dry air, the compressor is under pressure (about 1-2.5 bar), this is to indicate the compressor does not leak.
Preliminary Check
Discuss installation details with the installer. If possible, obtain drawings, wiring diagrams, etc. It is ideal to use a checklist but always check the following:
Visual check of the electrics, wiring, fuses etc.
Visual check of the plant for leaks, loose  ttings such
as TXV bulbs etc.
Compressor oil level
Calibration of HP and LP switches and any pressure
actuated valves
Check setting and operation of all safety features and
protection devices
All valves in the correct running position
Pressure and compound gauges  tted
Correctly charged with refrigerant
Compressor electrical isolator location & position
Never install a system in the  eld and leave it unattended
when it has no charge, a holding charge, or with the service valves closed without securely electrically locking out the system. This will prevent unauthorized personnel from accidentally operating the system and potentially ruining
the compressor by operating with no refrigerant fl ow.
Do not start the compressor while the system is in a vacuum.
Refrigerant Charging
P
C Board should be powered to close EXV before charging. The system should be liquid-charged through the liquid-receiver shut-off valve or through a valve in the
liquid line. The use of a  lter drier in the charging line is
highly recommended. Because scrolls have discharge check valves, systems should be liquid-charged on both the high and low sides simultaneously to ensure that a positive refrigerant pressure is present in the compressor before it runs.
Charging quantity can be determined by referring to system discharge and suction pressures. Another very useful parameter is the liquid line temperature which has been listed in the Fusion Catalogue. At a measured condensing temperature and an evaporating temperature, the liquid line temperature should be around Emerson‘s recommendation value within +5K tolerance.
The majority of the charge should be placed in the high side
of the system to prevent bearing washout during  rst-time
start on the assembly line or on site.
Do not operate with a restricted suction. Do not operate with the low-pressure cut-out bridged. Do not operate compressor without enough system charge to maintain at least 0.3 bar suction pressure. Allowing pressure to drop below 0.3 bar for more than a few seconds may overheat scrolls and cause early drive bearing damage. If the suction pressure is low on startup, and top up of the refrigerant charge is required, it is preferable to bleed liquid slowly into the suction line of a running compressor than to risk overheating by vapour charging.
The system should be liquid-charged through the liquid­receiver shut-off valve or through a valve in the liquid
line. The use of a  lter drier in the charging line is highly
recommended. The majority of the charge should be placed in the high side of the system to prevent bearing
washout during  rst-time start on the assembly line.
Initial Startup
It is important to ensure that new compressors are not subjected to liquid abuse. Turn the crankcase heater on 12 hours before starting the compressor..
Warning
Warning
Warning
driers. A 100% activated alumina suction line  lter drier is
recommended but must be removed after 72 hours. It is highly recommended that the suction accumulator be replaced if the system contains one. This is because the accumulator oil-return
ori ce or screen may be plugged with debris or may become
plugged shortly after a compressor failure. This will result in starvation of oil to the replacement compressor and a second failure. When a single compressor or tandem is exchanged in
the  eld, it is possible that a major portion of the oil may still
be in the system. While this may not affect the reliability of the replacement compressor, the extra oil will add to rotor drag and increase power usage.
Lubrication and Oil Removal
Do not mix up ester oils with mineral oil and/or alkyl benzene when used with chlorine-free (HFC) refrigerants. The compressor is supplied with an initial oil charge. The standard oil charge for use with refrigerants R404A is a polyolester (POE) lubricant Emkarate RL 32 3MAF.
In the  eld, the oil level could be topped up with Mobil
EAL Arctic 22 CC if 3MAF is not available. The standard mineral oil for R22 is Karamay 32BYMO. Therefore it is
recommended that a properly sized  lter drier is installed
in all POE systems. This will maintain the moisture level in the oil to less than 50 ppm.
If the moisture content of the oil in a refrigeration system reaches unacceptably high levels, corrosion and copper plating may occur. The system should be evacuated down to
0.3 mbar or lower. If there is uncertainty as to the moisture content in the system, an oil sample should be taken and tested for moisture. Sight glass/moisture indicators currently available can be used with the HFC refrigerants and lubricants; however, the moisture indicator will just show the moisture content of the refrigerant. The actual moisture level of POE would be higher than what the sight glass indicates.
Oil Additives
Although Emerson Climate Technologies cannot comment on any specific product, from our own testing and past experience, we do not recommend the use of any additives to reduce compressor bearing losses or for any other purpose. Furthermore, the long term chemical stability of any additive in the presence of refrigerant, low and high temperatures, and materials commonly found in refrigeration systems is complex and difficult to evaluate without rigorously controlled chemical laboratory testing.
Warning
Warning
Warning
Warning Warning
The use of additives without adequate testing may result in malfunction or premature failure of components in the system and, in specific cases, in voiding the warranty on the component.
Unbrazing System Components
Oil-refrigerant mixtures are highly fl ammable. Remove all refrigerant before opening the system. Avoid working with
an unshielded fl ame in a refrigerant charged system. Before
opening up a system, it is important to remove all refrigerant from both the high and low sides of the system. If the refrigerant charge is removed from a scroll-equipped unit from the high side only, it is possible for the scrolls to seal, preventing pressure equalization through the compressor. This may leave the low side shell and suction line tubing pressurized. If a brazing torch is applied to the low side while
the low side shell and suction line contain pressure, the pressurized refrigerant and oil mixture could ignite when
it escapes and comes in contact with the brazing fl ame. To
prevent this occurrence, it is important to check both the high and low sides with manifold gauges before unbrazing. Instructions should be provided in appropriate product literature and assembly (line repair) areas. If compressor removal is required, the compressor should be cut out of
system instead of unbrazing.
Dismantling and Disposal
Removing oil and refrigerant
Do not disperse in the environment.
Use the correct equipment and method of removal.
Dispose of oil and refrigerant properly.
Dispose of compressor properly.
Appendix
Fault Diagnostic Code
Code Description Status Compressor Action
0 ON Normal compressor operation Normal Normal compressor operation
0 FLASH Normal compressor off Normal Normal compressor standby
0 FLASH
If it fl ashes during operation, follow
Emerson Wiring Diagram
Fault EXV will not work so compressor must stop
1 FLASH Motor overheat Fault
Compressor shutdown and automatic reset after 10 min
delay
2 FLASH High discharge temperature Fault
Compressor shutdown and automatic reset after 10 min
delay
3 FLASH Low oil level Fault
Compressor shutdown and automatic reset after 5 min
delay
4 FLASH Low Oil Differential Pressure (HP - LP) Fault
Compressor shutdown and automatic reset after 3 min
delay
5 FLASH Motor Thermistor failure Fault
Compressor shutdown and automatic reset after 10 min
delay
6 FLASH
Discharge port temperature sensor
failure
Fault
Compressor shutdown and automatic reset after 5 min
delay under open/short circuit failure / 10 min delay under
other failure mode
7 FLASH PHE inlet temperature sensor failure Fault Compressor don’t shutdown
8 FLASH PHE outet temperature sensor failure Fault Compressor don’t shutdown
9 FLASH
Oil temperature sensor failure or high oil
temperature
Fault
Compressor don’t shutdown under oil temperature sensor
failure, but oil temperature protection function fail .
Show alarming under high oil temperature, compressor
shutdown if oil temperature continue to increase and
automatic reset after 10 min delay
3 and F Alternate display Less oil level, still OK but soon dangerous Normal Show alarming and continue running. Give precaution
5 to 9 Number FLASH All sensors Fault
When power on 1st time, if any sensor among motor
thermistor, discharge temperature sensor, PHE inlet
temperature sensor, PHE outlet temperature sensor and oil
temperature sensor is wrong, immediately locked
3
Number
FLASH/'.' on
Low oil level/Require manual reset Fault
The 4th low oil level in 1 hour, compressor shutdown and
locked, manual reset (cut off power)
4
Number
FLASH/'.' on
Low differential oil pressure/require
manual reset
Fault
The 4th low differential pressure in 1 hour, compressor
shutdown and locked
Fault diagnostic code is visible through
a transparent window on the cover
The code and description can be found
inside of the cover
Warning
Tool List
Components
Item No.
on Page 11
(Table)
Tool
No.
Tool
Description
Tool
Specication
Torque Value
(N.m)
Pressure Differential Sensor (Mechanical Part, Lower Cover)
1 8, 29
Metric Hexagon
Socket,
Torque Wrench
1'' 100–110
Three-phase Terminal Plate 1, 28 10 mm 12–15
PTC Thermistor 1, 28 10 mm 12–15
Oil Charge Fitting Plug (Lower Cover)
2 2, 29 18 mm 32–42
Oil Drain Oil Fitting Plug (Lower Cover)
4 2, 29 18 mm 32–42
Lower Cover Bolts 3, 29 16 mm 57–68
Check Valve Bolts 2, 29 18 mm 90–100
Suction Valve Bolts 2, 29 18 mm 90–100
Oil Drain Oil Fitting Plug (Oil screen, Top Cap)
19 4, 29 26 mm 130–140
Oil Sight Glass Bolts 20 5 10 mm 7.5–10
Oil Charge Fitting Plug (Top Cap)
24 2, 29 18 mm 32–42
1, 2, 3, 4, 5, 6
9, 10 11
7
15 18
13,14
16,17
19
20
21
22
23
24
25
26
27
8
12283031
29
Components
Item No.
on Page 11
(Table)
Tool
No.
Tool
Description
Tool
Specication
Torque Value
(N.m)
Oil Level Sensor 18
Opening Wrench
29 mm 130–140
Discharge Valve (Rotate) 25 50 mm 54–60
Rotalock Nut for Oil Out Tube 5 9 22 mm 25–30
Rotalock Nut for Oil In Tube 10 9 22 mm 25–30
Nuts of Tube-Oil Pulsation 9 22 mm 25–30
EVI Rotalock Nut 15 11 24 mm 40–50
Pressure Differential Sensor (Mechanical Part, Lower Cover)
1 12 1'' 100–110
Terminal Box Cover Screws 13
Cross Screwdriver
H3/6'' 1–2
Screw - CoreSense™ Connect to Terminal Box
14 H3/6'' 1–2
CoreSense Terminal Connectors
30 Voltage Tester M3 N/A
Transformer Bolts 15, 28
Metric Internal
Hexagon Socket,
Torque Wrench
3 mm 3.40–5.10
Thrust Plate Bolts 16, 28 4 mm 5.65–7.75
Oil Separator Bolts 17, 28 4 mm 5–6
Bolt - Terminal Box Connect to Body
18, 28 5 mm 3.40–5.10
Top Cap Bolts 19, 29 10 mm 80–90
Top Cap and Lower Cover 22 Flat Chisel N/A
Top Cap and Lower Cover 23 Rubber Hammer N/A
Top Cap 27 Special Bolts M12 N/A
HVE Holder 25, 28
Special Socket,
Torque Wrench
12–15
Scroll Set 26 Torque Wrench M10 N/A
Screw-Upper Counterweight 24 Opening Wrench 13 mm 12–15
For Torque Wrench 20 Connecting Piece 1/2 to 3/8 N/A
For Socket 28
Torque Wrench
5–25
For Socket 29 30–150
For Torque Wrench 31 Extension Bars N/A
—— 21
Offset Socket Screw
Key Set
1.5 to 10 mm
For Teardown
Only
Asia 02 B04 10 – R00 Issued 07/2016 – GSCAA032
Emerson, CoreSense Diagnostics and Copeland Scroll Fusion are trademarks of Emerson Electric Co. or one of its af liated companies. ©2013 Emerson Climate Technologies, Inc. All rights reserved.
EmersonClimateAsia.com
Asia Pacific Headquarters
Emerson Climate Technologies
Suite No. 2503-8, 25/F, Exchange Tower, 33 Wang Chiu Road, Kowloon Bay, Kowloon, Hong Kong Tel: (852) 2866 3108 Fax: (852) 2520 6227
Australia
Emerson Climate Technologies Australia Pty Ltd
356 Chisholm Road Auburn NSW 2144, Australia Tel: (612) 9795 2800 Fax: (612) 9738 1699
China - Beijing
Emerson Climate Technologies (Suzhou) Co. Ltd Beijing Sales Office
Room 1017 JianWei Building, 66 Nan Lishi Road, XiCheng District, Beijing, PRC Tel: (8610) 5763 0488 Fax: (8610) 5763 0499
China - Guangzhou
Emerson Climate Technologies (Suzhou) Co. Ltd Guangzhou Sales Office
508-509 R&F Yinglong Plaza, No. 76 Huangpu Road West, Guangzhou, PRC Tel: (8620) 2886 7668 Fax: (8620) 2886 7622
China - Shanghai
Emerson Climate Technologies (Suzhou) Co. Ltd Shanghai Sales Office
7F, Emerson Building, 1582 Gumei Rd, Shanghai, PRC Tel: (8621) 3338 7333
India - Mumbai
Emerson Climate Technologies (India) Ltd
Delphi B-Wing, 601-602, 6th Floor Central Avenue, Hiranandani Business Park, Powai, Mumbai 400076 Tel: (9122) 2500 6630 / 2500 6632 Fax: (9122) 2500 6570
India - PUNE
Emerson Climate Technologies (India) Ltd
Plot No. 23, Rajiv Gandhi Infotech Park, Phase - II, Hinjewadi, Pune 411 057, Maharashtra, India Tel: (9120) 2553 4988 Fax: (9120) 2553 6350
Indonesia
PT Emerson Indonesia
BSD Taman Tekno 8 Jl. Tekno Widya Blok H10 No 2 & 3 Tangerang Selatan 15314 Indonesia Tel: (6221) 2666244
Fax: (6221) 2666245
Japan
Emerson Japan Ltd
Shin-yokohama Tosho Building No. 3-9-5 Shin-Yokohama, Kohoku-ku Yokohama 222-0033 Japan Tel: (8145) 475 6371 Fax: (8145) 475 3565
Malaysia
Emerson Electric (Malaysia) Sdn. Bhd.
Level M2, Blk A, Menara PKNS-PJ Jalan Yong Shook Lin 46050 Petaling Jaya, Selangor, Malaysia Tel: (603) 7949 9222 Fax: (603) 7949 9333
Middle East & Africa
Emerson Climate Technologies
PO Box 26382 Jebel Ali Free Zone – South Dubai, UAE Tel: (9714) 811 8100 Fax: (9714) 886 5465
Philippines
Emerson Climate Technologies
10/F SM Cyber West Avenue, EDSA cor. West Avenue, Barangay Bungad, Diliman, Quezon City 1105 Philippines Tel: (632) 689 7200
South Korea
Emerson Electric Korea Ltd.
3F POBA Gangnam Tower 343, Hakdong-ro, Gangnam-gu, Seoul 135-820, Republic of Korea Tel: (822) 3483 1500 Fax: (822) 592 7883
Taiwan
Emerson Electric (Taiwan) Co. Ltd
3F No. 2 DunHua South Road Sec.1, Taipei (105), Taiwan Tel: (8862) 8161 7688 Fax: (8862) 81617614
Thailand - Bangkok
Emerson Electric (Thailand) Ltd
34th Floor, TCIF Tower, 1858/133, Bangna Trad, Bangkok 10260, Thailand Tel: (662) 716 4700 Fax: (662) 751 4241
Vietnam
Emerson Climate Technologies - Vietnam
Suite 307-308, 123 Truong Dinh St., Dist.3 Ho Chi Minh, Vietnam Tel: (84) 908 009 189
Contact Lists
Scan With Your Smartphone For More Information
Loading...