Emerson NXL UPS Systems User Manual

Liebert® NXL™ Battery System
Installation Manual
AC Power For Business-Critical Continuity™
The following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions applicable to battery cabinets may be found in Important Safety
Instructions beginning on page 1.
WARNING
!
Internal battery strapping must be verified prior to moving a battery cabinet (after initial installation).
• Battery cabinets contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT prior to moving battery cabinets (after initial installation).

CONTACTING LIEBERT FOR SUPPORT

To contact the Liebert Services section of Emerson Network Power for information or repair service in the United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of startup services, repair services, preventive maintenance plans and service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area.
For LGS to assist you promptly, have the following information available:
Part Numbers:
Serial Numbers:
Rating:
Date Purchased:
Date Installed:
Location:
Battery Voltage:
Battery Reserve Time:
Product Warranty Registration
To register for warranty protection, visit the Service and Support section of our Web site at:
www.liebert.com
Click on Product Registration and fill out the form.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.1 Battery Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.1 Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.2 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.3 Raised Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 System Composition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.0 BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Power Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.1 Connected System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.2 Stand-Alone System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.3 Attached/Detached System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4.4 MBD voltage sense leads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.5 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5 Control Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6 Alber Monitoring System—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7 External Battery Room Temperature Sensor—Optional. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.0 INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.0 S
PECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
FIGURES
Figure 1 Shipping bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2 Battery cabinets connected, attached to UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 3 Battery cabinets connected, detached from UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 4 Battery cabinets connected, with Module Battery Disconnect, attached to UPS . . . . . . . . . . . . . . 8
Figure 5 Battery cabinets connected, with Module Battery Disconnect, detached from UPS. . . . . . . . . . . . 8
Figure 6 Battery cabinets connected, detached from Module Battery Disconnect, detached from UPS . . . 9
Figure 7 Stand-alone battery cabinets, with Module Battery Disconnect, detached from UPS . . . . . . . . . . 9
Figure 8 Stand-alone battery cabinets, no Module Battery Disconnect, detached from UPS . . . . . . . . . . . 10
Figure 9 Wiring external interface board in UPS to battery interface board in battery cabinet . . . . . . . . 12
Figure 10 Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet . . . . . . . . . . . . . . . . . . 13
Figure 11 Battery temperature sensor control connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 12 Outline drawing, Liebert Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 13 Main components, Liebert Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 14 Terminal details, Liebert Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
i
Figure 15 Outline drawing, 250-400kVA, Liebert Module Battery Disconnect . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 16 Terminal detail drawing, Liebert Module Battery Disconnect. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 17 Outline drawing, 500-750kVA, Liebert Module Battery Disconnect . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 18 Wide junction cabinet terminal wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 19 Liebert NXL Narrow Junction Cabinet—terminal detail and outline drawing . . . . . . . . . . . . . . 22
Figure 20 Liebert NXL Battery Cabinet control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 21 Liebert NXL Module Battery Disconnect control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 22 Voltage sense wire harness top input and bottom input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 23 Liebert NXL Module Battery Disconnect CAN wire harness connection . . . . . . . . . . . . . . . . . . . 26
Figure 24 Attached battery cabinet connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 25 Ground strap location for connected cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 26 Battery cabinet interconnection wiring to 250-400kVA UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 27 Liebert NXL Module Battery Disconnect interconnect wiring to 250-400kVA UPS. . . . . . . . . . . 29
Figure 28 Liebert NXL Battery Cabinet interconnect wiring to Liebert NXL Junction Cabinet . . . . . . . . . 30
Figure 29 Liebert NXL UPS to Liebert NXL Module Battery Disconnect to wide Liebert NXL
Junction Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 30 Liebert NXL UPS to Liebert NXL Module Battery Disconnect to Liebert NXL
Battery Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 31 Alber battery monitoring connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 32 Battery Interface Board wiring to multiple battery cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 33 Alber battery monitoring assembly diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 34 Alber Battery Monitoring transformer location and battery configuration. . . . . . . . . . . . . . . . . . 36
TABLES
Table 1 Liebert-supplied interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 2 Liebert-supplied interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 3 Liebert-supplied interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 4 Liebert-supplied interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 5 Liebert-supplied interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 6 Alber battery monitoring assembly connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 7 Liebert NXL Battery Cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 8 Liebert NXL Module Battery Disconnect Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 9 Liebert NXL Junction Cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 10 Alber battery monitoring option specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 11 Currents for Liebert NXL Module Battery Disconnect Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 12 Battery cabinet internal breaker selection based on 5 min EOD, amps . . . . . . . . . . . . . . . . . . . . 40
Table 13 Liebert NXL Battery Cabinet approximate weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 14 Approximate weights, Liebert NXL Module Battery Disconnect and Liebert NXL
Junction Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 15 Recommended conduit and cable sizes for Liebert NXL Module Battery Disconnect . . . . . . . . . 41
Table 16 Battery torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 17 Torque specifications, unless otherwise labeled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
ii

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation of your Liebert NXL to the sections that apply to your installation, before working with the battery system. Retain this manual for use by installing personnel.
!
battery cabinet and accessories. Read this manual thoroughly, paying special attention
WARNING
Risk of electrical shock. Can cause personal injury or death.
Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system. Only properly trained and qualified personnel wearing appropriate personal protective equipment should be involved in installing the Liebert NXL Battery system or preparing the system for installation.
Special care must be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal. Be constantly aware that the battery system contains high DC as well as AC voltages. Check for voltage with AC and DC voltmeters before making contact.
Observe all DC safety precautions before working on or near the DC system.
Follow all battery safety precautions when installing, charging or servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns.
The following precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If it is grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and mainte­nance.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
WA R N I N G
!
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage, personal injury and death.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and recycled or discarded in accordance with federal, state and local regulations. Because lead is a toxic substance, lead-acid batteries must be recycled rather than discarded.
Do not dispose of a battery in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.
WARNING
!
Risk of electric shock. Can cause personal injury or death.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
1
WARNING
!
Risk of heavy unit falling over. Can cause equipment damage, injury or death.
Exercise extreme care when handling battery cabinets to avoid equipment damage or injury to personnel. The battery system cabinets weigh from 3760 to 5750 lb. (1706 to 2608kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.
WARNING
!
Risk of electric shock. Can cause equipment damage, personal injury or death.
The area around the battery system must be kept free of puddles of water, excess moisture and debris.
Observe all precautions in the Operation and Maintenance Manual, SL 25425, before as well as during all installation and maintenance procedures. Observe all battery safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the batteries.
All power and control wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with the NEC and applicable local codes.
When performing maintenance with any part of the equipment under power, service personnel and test equipment must be standing on rubber mats. The service personnel must wear insulating shoes for isolation from direct contact with the floor (earth ground).
One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident.
NOTE
Liebert Corporation neither recommends nor knowingly sells this product for use with life support or other FDA-designated “critical” devices.
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.
2

1.0 MECHANICAL INSTALLATION

1.1 Introduction

This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NXL battery equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing engineer. The particular conditions of each site will determine the applicability of such procedures.
NOTICE
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.

1.2 Preliminary Checks

Before installing the battery equipment, please carry out the following preliminary checks:
• Visually examine the equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.
• Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the back of the main door.
• Verify that the battery room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.
Mechanical Installation

1.3 Environmental Considerations

1.3.1 Battery Room

Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical battery manufacturer performance data are quoted for an operating temperature between 20 and 25°C (68 and 77°F). Operating above this range will reduce the battery life while operation below this range will reduce the battery capacity.
Battery Temperature
In a normal installation, the battery temperature should be kept between 15°C and 25°C (59 and 77°F).
NOTE
Keep batteries away from main heat sources or main air inlets etc.

1.3.2 Storage

Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and or heat sources (see Table 7).
NOTICE
An unused battery must be recharged periodically as recommended by the battery manufacturer.
3

1.4 Positioning

The cabinet is structurally designed to handle lifting from the base.
Access to the power terminals, auxiliary terminals blocks and power switches is from the front and top.
Removable panels on the top are secured to the chassis by screws. The door can be opened to give access to the power connections bars, auxiliary terminal blocks and power isolators. The front door can be opened at 180° for better service and more flexibility in installations.

1.4.1 Moving the Cabinets

The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors).
Ensure that the cabinet weight is within the designated surface weight loading (kg/cm dling equipment. See Table 4 for weight details.
Ensure any lifting equipment used in moving the battery equipment has sufficient lifting capacity.
Battery system equipment can be handled by means of a forklift or similar equipment.
Because the weight distribution in the cabinet is uneven, use extreme care during handling and transporting.
Mechanical Installation
2
) of any han-
When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15 degrees tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.
Handling the unit with straps is not authorized.
WARNING
!
Risk of heavy unit falling over. Can cause equipment damage, injury or death.
Exercise extreme care when handling battery cabinets to avoid equipment damage or injury to personnel. The battery system cabinets weigh from 3760 to 5750 lb. (1706 to 2608).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.
The battery ships with extra bolts installed on the interior doors. Once the cabinet is in the final posi­tion, these bolts can be removed. See Figure 1
4
Figure 1 Shipping bolts
Shipping Bolts
Shipping Bolts
Shipping Bolts
Mechanical Installation
Shipping Bolts
Shipping Bolts

1.4.2 Clearances

Liebert NXL has no ventilation grilles at either side or at the rear of the battery system equipment. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the cabinet and the ceiling of the room in which it is installed to permit adequate circulation of air coming out of the unit.

1.4.3 Raised Floor Mounting

If the equipment is to be placed on a raised floor, it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal.
Shipping
Shipping Bolts
Bolts
* Doors removed for clarity
Shipping Bolts

1.5 System Composition

A battery system can consist of a number of equipment cabinets, depending on the individual system design requirements - e.g., Battery Cabinet, Module Battery Disconnect, Junction Cabinet. Refer to
3.0 - Installation Drawings for the positioning of the cabinets described below.
5

2.0 BATTERY INSTALLATION

2.1 Safety

Special care should be taken when working with the batteries associated with the Liebert NXL Bat­tery System equipment. When all the cells are connected together, the battery terminal voltage will exceed 400V and is potentially lethal. A primary safety consideration is to install the battery equip­ment in an isolated area, accessible only to properly trained and qualified maintenance personnel.
WARNING
!
Risk of electric shock. Can cause equipment damage, personal injury or death.
Hazardous battery voltage present behind covers. No user-serviceable parts are located behind covers that require a tool for removal. Only properly trained and qualified service personnel are authorized to remove such covers or perform installation or maintenance.
The following general battery safety precautions and warnings must be observed at all times:
• A battery can present risk of electric shock or burn from high short circuit currents.
• When connected in a string, the voltage will exceed 400VDC. This voltage is potentially lethal. Always observe high-voltage precautions.
• Eye protection must be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches, necklaces, bracelets and all other metal objects.
• Use only tools with insulated handles.
• Wear appropriate personal protective equipment when handling batteries.
• If a battery leaks electrolyte or is otherwise physically damaged, it should be placed in a container resistant to wire and disposed of in accordance with local regulations.
• If electrolyte comes into contact with the skin, the affected area should be washed immedi­ately with plenty of clean water.
• Batteries must always be disposed of according to local environmental laws.
• When replacing batteries, use the same number and type that were originally fitted.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if the battery is grounded. If it is grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock.
• Battery support tray must be used whenever a battery tray is being pulled out.
Battery Installation

2.2 Layout

Depending on the site layout, the Battery cabinets can be installed in any of several ways:
Connected—Multiple Battery cabinets bolted together
Stand-Alone—Cabinet not bolted to Liebert NXL equipment
Attached—Battery Cabinets are bolted to a Liebert NXL UPS
Detached—Battery Cabinets are not bolted to a Liebert NXL UPS
See Figures 2 through 8.
6

Figure 2 Battery cabinets connected, attached to UPS

Battery Installation
Liebert
NXL UPS
Battery Strings with a Module Battery Disconnect can have a maximum of four battery cabinets.
Additional
Liebert
NXL
Battery
Cabinet

Figure 3 Battery cabinets connected, detached from UPS

Liebert
NXL
Battery
Cabinet
Liebert
NXL
Battery
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL UPS
Maximum of four battery cabinets in parallel. The junction cabinet allows for sufficient conduit landing space. It is required for systems of 500kVA or above.
Liebert
NXL UPS
Additional
Liebert
NXL
Battery
Cabinet
Narrow
Junction
Cabinet
Liebert
NXL
Battery
Cabinet
Liebert
NXL
Battery
Cabinet
Narrow
Junction
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL UPS
7

Figure 4 Battery cabinets connected, with Module Battery Disconnect, attached to UPS

Battery Installation
Liebert
NXL UPS
Liebert
NXL Module Battery
Disconnect
Cabinet
Liebert
NXL
Battery
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Battery Strings with a Module Battery Disconnect can have a maximum of four battery cabinets.
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL
Battery
Cabinet
Liebert
NXL Module Battery
Disconnect
Cabinet
Liebert
NXL UPS

Figure 5 Battery cabinets connected, with Module Battery Disconnect, detached from UPS

Battery Strings with a Module Battery Disconnect can have a maximum of four battery cabinets.
Liebert
NXL UPS
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL Module Battery
Disconnect
Cabinet
Liebert
NXL
Battery
Cabinet
Liebert
NXL Battery Cabinet
Liebert
NXL Module Battery
Disconnect
Cabinet
Additional
Liebert
NXL Battery Cabinet
Liebert
NXL UPS
8
Battery Installation

Figure 6 Battery cabinets connected, detached from Module Battery Disconnect, detached from UPS

Liebert
Battery Strings with a Module
Liebert
NXL UPS
NXL Module Battery
Disconnect
Cabinet
Narrow
Junction
Cabinet
Liebert
NXL
Battery
Cabinet
Battery Disconnect can have a maximum of four battery cabinets. The junction cabinet is used to allow for sufficient conduit landing space and is required for systems of 500kVA or above.
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL Battery Cabinet
Narrow
Junction
Cabinet
Liebert
NXL Module Battery
Disconnect
Cabinet

Figure 7 Stand-alone battery cabinets, with Module Battery Disconnect, detached from UPS

Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL UPS
Battery Strings with a Module Battery Disconnect can have a maximum of four battery cabinets. The junction cabinet provides sufficient conduit landing space and is required for all systems in this configuration.
Liebert
NXL UPS
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL Module Battery
Disconnect
Cabinet
Liebert
NXL
Battery
Cabinet
Wide
Junction
Cabinet
Wide
Junction
Cabinet
Liebert
NXL
Battery
Cabinet
Liebert
NXL Module Battery
Disconnect
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL UPS
9
Battery Installation

Figure 8 Stand-alone battery cabinets, no Module Battery Disconnect, detached from UPS

Maximum of four battery cabinets. The junction cabinet provides sufficient conduit landing space and is required for all systems in this configuration.

2.3 Cable Entry

Cables may enter the battery cabinet from either the top or the bottom. Cable entry is made possible by installing conduit to the removable plate fitted at the top or bottom. See 3.0 - Installation Draw- ings.
Liebert
NXL UPS
Additional
Liebert
NXL
Battery
Cabinet
Wide
Junction
Cabinet
Liebert
NXL
Battery
Cabinet
Liebert
NXL
Battery
Cabinet
Wide
Junction
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL UPS

2.4 Power Connection

Depending on the site layout, the Battery cabinets can be cabled several ways. See Figures 2 through 8.

2.4.1 Connected System

For cabinets that have been ordered as connected (battery cabinets will bolt to each other), the posi­tive and negative busbars can be bolted together using the supplied bus bar connector extensions. See Figure 24

2.4.2 Stand-Alone System

For cabinets that are ordered as stand-alone, customer must supply all the interconnecting cables and hardware. See Table 15 for current ratings and recommended cable sizes.

2.4.3 Attached/Detached System

For battery cabinets that are connecting to a Liebert NXL UPS, Liebert NXL MBD cabinet or Liebert NXL Junction cabinet (see Figures 2 through 6), cables will run from the positive and negative bus­bars of the adjacent battery cabinet to the positive and negative DC connections of UPS, MBD or Junction cabinet.
For attached systems (the cabinets bolt to each other) the cables can run internal to the cabinets and will be supplied.
For detached systems (the cabinets do not bolt to each other), the cables must be run outside the cab­inets. The customer must supply all the interconnecting cables and hardware. See Table 15 for cur­rent ratings and recommended cable sizes.
10

2.4.4 MBD voltage sense leads

For ease of installation, the power cables from the battery cabinets can be installed on either the top or bottom breaker busbars (depending if top or bottom entry is used). The voltage sense leads need to be connected to the busbars on the input of the circuit breaker (busbars that have the cables from the battery system connected.) See Figure 22.
WARNING
!
Risk of electric shock. Can cause equipment damage, personal injury or death.
Hazardous battery voltage may be present on busbar. Install battery voltage sense leads before connecting the positive and negative power cables.

2.4.5 Grounding

For cabinets that have been ordered as connected or attached, the ground cables and hardware will be supplied. See Figure 25 for location of cabinet-to-cabinet grounding.
For cabinets ordered as detached or stand-alone, customer must supply the cables and hardware. See Table 15 for current ratings and recommended cable sizes.

2.5 Control Connection

Each Liebert NXL Battery Cabinet and Liebert NXL Module Battery Disconnect (MBD) contains a Battery Interface Board (BIB). See 3.0 - Installation Drawings. All cabinets in a system must have their Battery Interface boards connected in series. See Figure 14 for battery cabinet details and Figure 16 for MBD details.
Battery Installation
NOTE
Care must be taken to route the control cables away from high voltage cables or busbars.
11
Battery Installation

Figure 9 Wiring external interface board in UPS to battery interface board in battery cabinet

Detail A
TB1154A
EXT BATT
CAN
Detail A
+24V
TB1154A
GND
TB1154
CANL
CANH
External Interface Board (in UPS)
CANH
CANL
(in Battery Cabinet and MBD)
Detail B
GND
+24V
TB1154
Battery Interface Board
Detail B
12

Figure 10 Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet

Liebert
Liebert
NXL UPS
NXL
Battery
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Battery Installation
Ext. Interface
Board (EIB)
Liebert
NXL UPS
TB1154
CAN Cable CAN Cable
Liebert
Module Battery
Disconnect
NXL
Bat. Interface
Board (BIB)
TB1154
Liebert
Battery
Cabinet
Bat. Interface
NXL
Board (BIB)
TB1154
Additional
Liebert
NXL
Battery
Cabinet
Cabinet
Ext. Interface
Board (EIB)
TB1154
CAN Cable CAN Cable CAN Cable
The CAN cables must be two, twisted pair, shielded 18AWG (Belden 9156 or equivalent). All intercon­necting cables and hardware for connected and attached cabinets will be provided.
Bat. Interface
Board ( BIB)
TB1154
Bat. Interface
Board (BIB)
TB1154
Bat. Interface
Board ( BIB)
TB1154
NOTICE
Risk of improper installation. Can cause equipment damage. During system commissioning, Liebert Services will set the jumpers on the EIB and the BIB.
If another battery cabinet is added to the system after commissioning, it is imperative that Liebert Services reset the jumpers on the EIB board and the BIB board.
13

2.6 Alber Monitoring System—Optional

The Liebert matching battery cabinet allows installing an optional Alber battery monitoring system in the cabinet. The Alber battery monitoring continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Additional capabilities include automatic internal DC resistance tests and trend analysis providing the ability to analyze perfor­mance and aid in troubleshooting.
The Alber monitoring system is installed inside the battery cabinet (see Figure 33). The monitoring system requires approximately 0.5A, single-phase power.
This power can come from the output of the UPS the battery cabinet is suppling (see Figure 33).
The Alber monitoring system consists of a Controller Module and Data Collector Module (see Figure 31). One Controller Module can monitor up to six (6) battery cabinets with a Data Collector Module installed. The Battery cabinet with the Controller Module (battery cabinet #1) must be install in the position closest to the UPS.
For details about operating the Alber system, see the Alber Monitoring System manual, available at the Liebert Web Site, www.liebert.com

2.7 External Battery Room Temperature Sensor—Optional

For systems that do not use Liebert NXL battery cabinets, but have an MBD connected to a battery string, an optional temperature sensor can be installed to monitor the ambient room temperature. This sensor is connected to the BIB in the MBD cabinet (see Figure 11). This sensor will allow the Liebert NXL UPS to perform temperature compensation charging.
Battery Installation

Figure 11 Battery temperature sensor control connection

Battery Interface Board
P1153
(inside MBD Cabinet)
TB1154
14

3.0 INSTALLATION DRAWINGS

Figure 12 Outline drawing, Liebert Battery Cabinet

56.3
(1430)
27.7
(705)
Installation Drawings
16.6
(422)
3.7
(95)
28.7
(730)
Front
CG
1.6
(40)
Typ
42.8
(1088)
76.8
(1950)
3.7
(95)
33.5
(850)
CG
Right Side View
64.1
(1629)
3
(76)
11.2
(285)
8.8
(223)
11.2
(285)
6.4
(161)
8.3
(210)
TOP VIEW
(Doors Open)
Bottom View
NOTE:
1. All dimensions are in in. (mm)
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are with side panels. The width is 55.1" (1400mm) without side panels.
8.The depth dimension includes the front door and rear panel.
15

Figure 13 Main components, Liebert Battery Cabinet

Battery Service
Tray
Battery Service
Tray Supports
Installation Drawings
Negative Battery Bus
Positive Battery Bus
High Voltage Control Cable Trough
Low Voltage Control Cable Trough
Location for Optional Alber Monitoring
Equipment
Battery Breaker
Battery Interface Board (BIB)
Front View
Batteries (Typical View Shown)
SLOT IN SUPPORT IS SECURED BY SCREW-IN CONNECTOR AT CORNER OF BATTERY SERVICE TRAY
Ground Bus
NOTCHED END OF SUPPORT SLIPS INTO SLOT AT BATTERY RAIL ABOVE
SERVICE TRAY SUPPORTS ANGLED OUT TO PROVIDE BATTERY CLEARANCE
SERVICE TRAY INSTALLED
BATTERY TRAY EXTENDED ONTO SERVICE TRAY
16

Figure 14 Terminal details, Liebert Battery Cabinet

See Bus Termination Detail
Negative Term. Bus (-)
Positive Term. Bus (+)
Installation Drawings
Top Vi ew
+
Ground Bus (See Detail)
Front View
* Doors And Covers Removed for Clarity
Note:
1. All dimensions are in inches (mm)
2.. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in separate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring must be in accordance with national and local electrical codes.
Right Side View
-
1.75 (45)
.56
(14)
Ground Bus Detail
Bus Termination Detail
.53
(14)
1.75 (45)
1.75 (45)
1.75 (45)
1.75 (45)
17

Figure 15 Outline drawing, 250-400kVA, Liebert Module Battery Disconnect

62.3
(1583)
Top View
With Door Open
30.9
(785)
33.5
(850)
Installation Drawings
76.9
(1952)
Front View
CG
14.4
(367)
CG
37.9
(962)
4.1
(104)
19.0
(483)
Right Side View
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are without side panels. The width is 32.1" (815mm) with side panels.
8.The depth dimension includes the front door and rear panel.
18

Figure 16 Terminal detail drawing, Liebert Module Battery Disconnect

2.00 (51)
DETAIL A
1.25 (32)
2.00 (51)
1.75 (44)
.56 (14)
76.86
(1952)
72.74
(1848)
57.87
(1470)
55.28
(1404)
Installation Drawings
Ground Bus (Note 9)
Breaker Top Busbars (+/-) (Note 8)
B
1.75 (44)
.56
(14)
1.75 (44)
28.01 (711)
.56
(14)
DETAIL B
Notes:
1. All dimensions are in in. (mm)
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring is to be in accordance with national and local electrical codes.
8. Cables from battery system can be connected to either breaker top or bottom busbars.
9. Ground bus shown in factory-installed location, optional gnd bus mount location located near bottom of cabinet.
11.86 (301)
.00 (0)
A
Breaker Bottom Busbars (+/-) (Note 8)
Note 9
19

Figure 17 Outline drawing, 500-750kVA, Liebert Module Battery Disconnect

63.4
(1609)
Top V ie w
With Door Open)
Installation Drawings
76.9
(1952)
30.9
(785)
CG
33.5
(850)
CG
39.0
(990)
16.2
(410)
19.4
(494)
Front View Right Side View
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are without side panels. The width is 32.1" (815mm) with side panels.
8.The depth dimension includes the front door and rear panel.
20

Figure 18 Wide junction cabinet terminal wiring

Installation Drawings
.56 (14)
2.2 (55)
18 Places
Typ
30.9 (785)
2.2 (55)
16 Places
2.2 (55)
18 Places
Negative BusGround Bus Positive Bus
.56
(14) Typ
Positive Bus
1.8 (45)
16 Places
2.2 (55)
18 Places
.56
(14) Typ
1.7 (44) X 0.7 (18) Slot 16 Places
Typ. Each Busbar
2.2 (55)
16 Places
33.5 (805)
76.9
(1952)
Ground Bus
41.3
Negative Bus
7.4
(189)
8.7
(221)
9.0
(228)
Front View
Notes:
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are without side panels. The width is 32.1" (815mm) with side panels.
8.The depth dimension includes the front door and rear panel.
(1050)
13.7
(348)
Right Side
View
13.6
(346)
21

Figure 19 Liebert NXL Narrow Junction Cabinet—terminal detail and outline drawing

s
)
.56 (14)Typ
O
Positive Bus Bottom
.56 (14)Typ
O
Terminal Details
4.4
(112)
11 .4
(290)
(178)
7
1.75 (44)Typ
2 (51) Typ
1.75 (44)Typ
Installation Drawings
(661)
Front View
Outline Drawing
26.0
37.3
(948)
49.1
(1248)
Positive Bus
Negative Bus
Ground Bus
Right Side
1.75 (44)Typ
1.75
(44) TYP
Positive
Bus Top
2 (51) Typ
.56 (14)Typ
O
Ground Bus
Bus Detail
.56
(14)
TYP
1.25 (32) X 0.5 (13)
Slot 8 Places Typ ica l
Mounting Slots 8 Places Typic al
Negative
Bus Top
Negative Bus Bottom
76.8
(1950
WARNING!!!
Unit Removal and Unit Mobility Instructions
Brackets MUST remain attached to the frame until
uch time that the unit is being located in its final installed position. (The final installation will always require the unit to be bolted to another Liebert NXL product.) Failure to comply with these instructions could result in equipment damage and/or injury to personnel
38.3
(973)
7.9
(201)
15.5
(393)
38.3
(973)
Front View
33.5
( 850)
Right Side
15.1
(382)
22

Figure 20 Liebert NXL Battery Cabinet control wiring

H
1- BRKR- NEG
Installation Drawings
CAN CABLE TO BE RUN INTROUGH CLOSEST TO THE FRONT OFTHE UNIT
TROUG
THERMISTOR
THIS END FIELD-CONNECTED TO OTHER CABINET
24V (RED)
GND (BL K)
CANH (WHT)
CANL (BLK)
CAN CABLE (Belkin 9156 Or Equivalent)
BATTERY VOLTAGE SENSE CABLE
3-BRKR-POS
(BLK)
1 2 3
P1152
TB1158 ( BATTERY MONITORING SYSTEM )
TB1154
1 2 3 4
24V (RED)
P1153
GND (BLK)
AUX. CONTACT 1
AUX. CONTACT 1
AUX. CONTACT 1
UVR TRIP - Optional
(RED)
TB1150
CANL ( BLK)
CANH (WHT)
UVR TRIP- Optional
1 2 3 4 5
7 6 5 4 3 2 1
TB1151
TB1156
2 1
Control Wiring Diagram
BATTERY INTERFACE BOARD (BIB)
1
NOTES USE WIRETIE AS NECCESSARY FOR ROUTINGAND
1
SECURING WIRE HARNESSES.
Liebert NXL Battery Cabinet Control Wiring Routing
23

Figure 21 Liebert NXL Module Battery Disconnect control wiring

NOTE: Voltage sense leads are to be placed on side of breaker receiving power from battery cabinets.
TERMINAL RINGS SHIPPED LOOSE AND CONNECTED IN FIELD
NEG (BLK)
POS (RED)
Installation Drawings
+24V (RED)
GND (BLK)
CANH (WHT)
CANL (BLK)
THERMISTOR (optional)
THIS END IS FIELD-CONNECTED TO THE OTHER CABINET
BATTV (BLK)
BATTV (RED)
1 2 3
P1152
P1153
TB1158 ( BATTERY MONITORING SYSTEM )
TB1154
1 2 3 4
AUX. CONTACT 1
AUX. CONTACT 1
1 2 3 4 5
TB1150
AUX. CONTACT 1
TB1156
REFERENCE OF UVR TRIP WIRE HARNESS ( SUPPLIED WITH BREAKER )
REFERENCE OF AUX. CONTACT 1 WIRE HARNESS (SUPPLIED WITH BREAKER)
UVR TRIP - Optional
UVR TRIP - Optional
7 6 5 4 3 2 1
TB1151
BATTERY INTERFACE BOARD (BIB)
2 1
CAN CABLE (Belkin 9156 Or Equalivent)
GND (BLK)
+24V (RED)
CANL (BLK)
CANH (WHT)
24

Figure 22 Voltage sense wire harness top input and bottom input

Terminal Rings of Voltage Sense Wire Harness are to be field-connected with M6 hardware
Input Side of Breaker
Red
Blk
Voltage Sense Wire Harness
Installation Drawings
Voltage Sense Wire Harness is factory-connected at this end
TOP INPUT FEED MOUNTING INSTALLATION
Battery Interface Board (BIB)
NOTE: Voltage sense leads are to be placed on side of breaker receiving power from battery cabinets.
Battery Interface Board (BIB)
Voltage Sense Wire Harness is factory-connected at this end
Voltage Sense Wire Harness
Red
Input Side of Breaker
BOTTOM INPUT FEED MOUNTING INSTALLATION
25
Blk
Terminal Rings of Voltage Sense Wire Harness are to be field-connected with M6 hardware

Figure 23 Liebert NXL Module Battery Disconnect CAN wire harness connection

Use wire tie to secure wire harnesses to lances on tie bracket
CAN Cable
Installation Drawings
TB1154 Terminal Battery Interface Board (BIB) (Plug supplied with BIB)
26

Figure 24 Attached battery cabinet connections

S

Figure 25 Ground strap location for connected cabinets

FRONT SIDE OF UNITS
Installation Drawings
Jumper Busbars (supplied with battery cabinet)
Jumper Busbars (supplied with battery cabinet)
REFERENCE OF CORNER-POST OF CONNECTED CABINET
BATTERY CABINET
B
Typical Ground Strap Installation
For Battery Cabinets
( ALL GROUNDING OF BATTERY CABINETS TO BE
INTERNAL AND CONNECTEDATTHE CORNER-POSTS )
Cabinet-to-Cabinet
Bolting Instructions
DETAIL B
27

Figure 26 Battery cabinet interconnection wiring to 250-400kVA UPS

Installation Drawings
B1
A1
B2
A2

Table 1 Liebert-supplied interconnect wiring

Run From To Conductors
A1 - DC+ Busbar Battery Cabinet - DC+ Busbar Positive Power - RH Mount/Stand Alone
B1 UPS - DC- Busbar Battery Cabinet - DC- Busbar Negative Power - RH Mount/Stand Alone
A2 - DC+ Busbar Battery Cabinet - DC+ Busbar Positive Power - Left Mount
B2 UPS - DC- Busbar Battery Cabinet - DC- Busbar Negative Power - Left Mount
C UPS - Ground Battery Cabinet - Ground Ground *
UPS - External Interface
D
Board (EIB)
* This is used only for detached cabinets. If the cabinets are attached, use the grounding shown in Figure 25.
Battery Cabinet - Battery Interface Board (BIB)
28
CAN Control Cables
Installation Drawings

Figure 27 Liebert NXL Module Battery Disconnect interconnect wiring to 250-400kVA UPS

A2
B2
UPS - Rear View DC Bus Connections
D
A1,2
Top Feed
Top
A1
B1
C
Feed
Bottom Feed
C
A1, 2
B1, 2
Top Feed
D
Bottom Feed
C
B1, 2
Bottom Feed
Module Battery Disconnect
UPS

Table 2 Liebert-supplied interconnect wiring

Run From To Conductors
A1 UPS - DC+ Busbar MBD - DC + Busbar Positive Power - Right Mount
B1 UPS - DC- Busbar MBD - DC - Busbar Negative Power - Right Mount
A2 UPS - DC+ Busbar MBD - DC + Busbar Positive Power - Left Mount
B2 UPS - DC- Busbar MBD - DC - Busbar Negative Power - Left Mount
C * UPS - GROUND MBD - GROUND Ground
D UPS - External Interface Board (EIB) MBD - Battery Interface Board (BIB) CAN Control Cables
* This is used only for detached cabinets. If the cabinets are attached, use the grounding shown in Figure 25.
29
Installation Drawings

Figure 28 Liebert NXL Battery Cabinet interconnect wiring to Liebert NXL Junction Cabinet

A
B
B
C
A
C

Table 3 Liebert-supplied interconnect wiring

Run From To Conductors
A Battery Cabinet Negative Bus Junction Negative Bus Negative DC Power
B Battery Cabinet Positive Bus Junction Positive Bus Positive DC Power
C * Battery Cabinet Ground Junction Ground Ground
* For detached units only
30
Installation Drawings
Figure 29 Liebert NXL UPS to Liebert NXL Module Battery Disconnect to wide Liebert NXL Junction
Cabinet
UPS
G
D1 D2
E1 E2
F
G
A2
Module Battery Disconnect
A1
D2
D1
C
F
B2
B1
A1 A2
E1
E2
C
Wide Junction Cabinet

Table 4 Liebert-supplied interconnect wiring

Run From To Conductors
A1 MBD - DC Positive Busbar Junction Positive Busbar Positive - Top Feed
A2 MBD - DC Positive Busbar Junction Positive Busbar Positive - Bottom Feed
B1 MBD - DC Negative Busbar Junction Negative Busbar Negative - Top Feed
B2 MBD - DC Negative Busbar Junction Negative Busbar Negative - Bottom Feed
C * MBD Ground Junction - Ground Ground
D1 UPS - DC Positive Busbar MBD - DC Positive Busbar Positive - Top Feed
D2 UPS - DC Positive Busbar MBD - DC Positive Busbar Positive - Bottom Feed
E1 UPS - DC Negative Busbar MBD - DC Negative Busbar Negative - Top Feed
E2 UPS - DC Negative Busbar MBD - DC Negative Busbar Negative - Bottom Feed
F * UPS Ground MBD Ground Ground
G UPS - External Interface Board (EIB) MBD - Battery Interface Board (BIB) CAN Control Cables
* For detached units only
B1 B2
31
Installation Drawings

Figure 30 Liebert NXL UPS to Liebert NXL Module Battery Disconnect to Liebert NXL Battery Cabinet

A2
B2
F
E
UPS - Rear View
DC Bus Connections
UPS
D
B1
A1
C
Bottom Feed
Top Feed A1, A2, E
To p
C,H
Feed
C,H
Bottom Feed A1,2,E
Modular Battery Disconnect
F, B 1 , B 2
To p Feed
D,G
B1,2
F
Bottom Feed
Battery Cabinet

Table 5 Liebert-supplied interconnect wiring

Run From To Conductors
A1 UPS - DC+ Busbar MBD - DC+ Busbar
B1 UPS - DC- Busbar MBD - DC- Busbar
A2 UPS - DC+ Busbar MBD - DC+ Busbar Positive Power - Left Mount
B2 UPS - DC- Busbar MBD - DC- Busbar Negative Power - Left Mount
C* UPS - Ground MBD - Ground Ground
UPS - External Interface
D
Board (EIB)
MBD - Battery Interface Board (BIB) CAN Control Cables
E MBD - DC+ Busbar Battery Cabinet - DC+ Busbar Positive Power
F MBD - DC- Breaker Battery Cabinet - DC- Busbar Negative Power
MBD - Battery Interface
G
Board (BIB)
Battery Cabinet - Battery Interface Board (BIB)
H* MBD - Ground Battery Cabinet - Ground Ground
* For detached units only
Positive Power - RH Mount/ Stand-Alone
Negative Power - RH Mount/ Stand-Aone
CAN Control Cables
F
E
G
H
32

Figure 31 Alber battery monitoring connections

r
Installation Drawings
Input Fuse for Alber Power
Alber Controller Module
Alber Data Collector Module
T
R
A
Y
#
1
T
R
A
Y
#
1
0
T
R
A
Y
#
2
T
R
A
Y
#
9
T
R
A
Y
#
3
T
R
A
Y
#
8
T
T
R
A
Y
#
4
T
R
A
Y
#
R
A
Y
#
7
5
T
R
A
Y
#
6
Alber Power Transforme
33

Figure 32 Battery Interface Board wiring to multiple battery cabinets

Installation Drawings
MODULE#4
COLLECTION
BDS-40 DATA
BATTERY
CABINET #4
MODULE#3
COLLECTION
BDS-40 DATA
BATTERY
CABINET #3
MODULE#2
COLLECTION
BDS-40 DATA
BATTERY
CABINET #2
TX
---
---
TX
RX
---
---
TX
RX
---
---
RX
INPUT
24VAC
INPUT
24VAC
24VAC
INPUT
---
---
TX
RX
#2
RX
24VAC
---
RESE T
RESE T
MAJOR NO
TB1158
MINOR NC
MI NO R NO
MAJOR CM
MAJO R NC
24VAC #1
LAN/LOCAL
ETHERNET
---
BATTERY CABINET #1
BOARD
BATTERY
INTERFACE
INPUT
+24 VAC
TX
TELCO
MINOR CM
#6
#5
#4
24VAC
24VAC
24VAC
#3
24VAC
60 HZ
23 0V AC
BDS-40 DATA CONTROLLER
MODULE#1
BDS-40 DATA COLLECTION
UPS
CABINET
60 HZ
230 VAC
60 HZ
480VA C
(Opt iona l)
34

Figure 33 Alber battery monitoring assembly diagram

r
UPS Output - Phase A Use Pilot Hole on Busba r.
UPS Output - Phase C Use Pilot Hole on Busbar.
250, 300, & 400 KVA UPS MODULE
. .
FUSEBLOCK INSTALLATION
Harness factory-installed. Verify transformer connection Prior to startup. See diagram below.
ALBER BAT TERY
MONITORING XFMR
F4
F5
NXL BATTERY CABINET
Locate fuse label as close to fuses as possible
Mount fuses to corner post in input/output compartment of UPS module. Choose best location based on bottom or top power cabling.
Connect cables from UPS output busbars to fuse block
This harness is intended for use only when battery cabinet is connected directly to UP S. For all other instances, customer must supply wire.
F75
F76
UPS MODULE OUTPUT
Installation Drawings
Secure supplied wire harness to busbar with supplied hardwa
Wire Harness
V_OUT_A
V_OUT_C
TOP TERMI NALS
FROM F5 FUSE IN B AT CAB
270 V
208 V
240 V
200 V
0 V
BOTTOM TERMINALS
FROM F4 FUSE IN B AT CAB
300 V
0 V
200 V
208 V
240 V
270 V
300 V
XFMR CONNECTION DIAGRAM
230 V
X2
X1

Table 6 Alber battery monitoring assembly connections

Input
Voltage
600 0 (Top) 300 (Top) to 0 (Bottom) 300 (Bottom) 2.25 A, 600VAC
480 0 (Top) 240 (Top) to 0 (Bottom) 240 (Bottom) 1.25 A, 600VAC
380 0 (Top) 300 (Top) to 208 (Bottom) 300 (Bottom) 1 A, 600VAC
208 0 (Top)
Alber Transformer-2
(Wht) Jumper
0 (Top) to 0 (Bottom) and
208 (Top) to 208 (Bottom)
Alber Transformer-1
(Blk)
208 (Top) 0.75A, 600VAC
F4-F5
Fuse Rating
35

Figure 34 Alber Battery Monitoring transformer location and battery configuration

Y
Y
Installation Drawings
REAR OF TRAY
+
-
JAR 1
+
-
JAR 2
TRAY #1
+
+
-
JAR 3
-
JAR 4
FRONT OF TRAY
T
R
A
Y
#
1
T
R
A
Y
#
1
0
T
R
A
Y
#
2
T
R
A
Y
#
9
T
R
A
Y
#
3
T
R
A
Y
#
8
T
T
R
A
Y
#
4
T
R
A
Y
#
R
A
Y
#
7
5
T
R
A
Y
#
6
ALBER INPUT TRANSFORMER
REAR OF TRAY
+
JAR 5
+
JAR 6
+
JAR 7
TRAY #2TRAY #3
+
JAR 8
FRONT OF TRAY
REAR OF TRAY
+
JAR 9
+
JAR 10
+
JAR 11
+
JAR 12
FRONT OF TRAY
REAR OF TRAY
+
JAR 13
+
JAR 14
+
TRAY #4
JAR 15
+
-
-
-
-
-
-
-
-
-
-
-
-
JAR 16
FRONT OF TRAY
REAR OF TRAY
+
JAR 40
+
JAR 39
+
JAR 38
TRAY #10TRAY #9TRAY #8TRAY #5
+
JAR 37
FRONT OF TRAY
REAR OF TRAY
+
JAR 36
+
JAR 35
+
JAR 34
+
JAR 33
FRONT OF TRAY
REAR OF TRAY
+
JAR 32
+
JAR 31
+
JAR 30
+
JAR 29
FRONT OF TRAY
REAR OF TRAY
+
JAR 20
+
JAR 19
+
JAR 18
+
JAR 17
FRONT OF TRAY
-
-
-
-
-
-
-
-
REAR OF TRAY
-
+
-
JAR 28
-
+
-
JAR 27
TRAY #7
+
+
-
JAR 26
-
-
­JAR 25
FRONT OF TRA
REAR OF TRAY
-
+
-
JAR 24
-
+
-
JAR 23
TRAY #6
+
+
-
JAR 22
-
-
­JAR 21
FRONT OF TRA
JAR (BATTERY) CONFIGURATION
36

4.0 SPECIFICATIONS

Table 7 Liebert NXL Battery Cabinet specifications

Battery Cabinet Parameters Values
Minimum EOD Voltage, VDC
Battery Discharging Max current (EOD), A See Table 12
Physical Parameters and Standards
without side panels attached 55.1 (1400)
Front Door Opening (for serviceability)
Degree of Protection for UPS Enclosure
Environmental
Storage Temperature Range, °F (°C)
Operating Temperature Range, °F (°C)
Maximum Altitude Above MSL, ft (m)
Battery Type VRLA (Valve Regulated Lead Acid)
Nominal Battery Bus, VDC
Battery Float Voltage, VDC
480V
540V
384V (for VRLA / Flooded Lead Acid)
Width, in. (mm)
Depth, in. (mm) 33.5 (850)
Height, in. (mm) 76.8 (1950)
Weight, lb (kg) approx. Table 13
Color Charcoal (ZP-0420)
More than 180°
IP 20 (with and without front door open)
UL 1778
CSA 22.2 107.3
Standards & Conformities
Minimum Clearance, Top 24" (610mm)
Minimum Clearance, Back 0"
Minimum Clearance, Sides 0"
Location of Cable Entrance Top or Bottom
74°F to 80°F (23-27°C) for optimal battery life
74°F to 80°F (23-27°C) for optimal battery life
Relative Humidity
1% Maximum kW derate / 100m rise between 1500-3000m
FCC Part 15, Class A
ISTA Procedure 1H
WEEE
-13°F to 158°F (-25°C to 70°C)
32°F to 104°F (0 to 40°C)
up to 95% Non-Condensing
(Operating and Non-Operating)
4920 (1500) (as per IEC 62040/3) -
Specifications
37

Table 8 Liebert NXL Module Battery Disconnect Cabinet

Battery Parameters Value
Nominal Battery Bus, VDC 480V
Battery Float Voltage, VDC 540V
Minimum EOD Voltage, VDC
Battery Discharging Max current (EOD), A See Table 11
384V (for VRLA / Flooded Lead Acid)
Physical Parameters and Standards
without side panels attached
Width in. (mm)
30.9 (785)
Depth, in. (mm) 33.5 (850)
Height, in. (mm) 76.8 (1950)
Weight, lb (kg) approx. See Table 14
Color Charcoal (ZP-0420)
Front Door Opening (for serviceability) More than 180°
Degree of Protection for UPS Enclosure IP 20 (with and without front door open)
UL 1778
CSA 22.2 107.3
Standards & Conformities
Minimum clearance, Top) 24" (610mm)
Minimum clearance, Back) 0"
Minimum clearance, Sides) 0"
Location of cable entrance Top or Bottom
FCC Part 15, Class A
ISTA Procedure 1H
WEEE
Environmental Parameters
Storage Temperature Range, °F (°C) -13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F (°C) 32°F to 104°F (0 to 40°C)
Relative Humidity
Maximum 95% Non-Condensing
(Operating and Non-Operating)
4920 (1500) (as per IEC 62040/3) -
Maximum Altitude Above Mean Sea Level, ft (m)
1% Max kW derate / 100m rise between
1500-3000m
Specifications
38

Table 9 Liebert NXL Junction Cabinet specifications

Battery Specifications Value
Nominal Battery Bus, VDC 480V
Battery Float Voltage, VDC
Minimum EOD Voltage, VDC
Battery Discharging Max current (EOD), A Table 11
Physical Parameters and Standards
Narrow Liebert NXL Junction Cabinet, Width,
without side panels, in (mm)
Wide Liebert NXL Junction Cabinet, Width,
without side panels, in (mm)
Depth, in (mm) 33.5 (850)
Height, in (mm)
Weight, lb (kg) approx. Table 14
Color Charcoal (ZP-0420)
Degree of Protection for UPS Enclosure IP 20
384V (for VRLA / Flooded Lead Acid)
15.5 (393)
30.9 (785)
76.8 (1950)
UL 1778
CSA 22.2 107.3
Standards and Conformities
Minimum clearance, Top 24" (610mm)
Minimum clearance, Back 0"
Minimum clearance, Sides 0"
Location of cable entrance Top or Bottom
Environmental Parameters
FCC Part 15, Class A
ISTA Procedure 1H
Storage Temperature Range, °F (°C) -13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F (°C) 32°F to 104°F (0 to 40°C)
Relative Humidity
Maximum Altitude above MSL, ft (m)
1% maximum kW derate / 328ft rise between 4900-9800ft
Maximum 95% Non-Condensing
(Operating and Non-Operating)
4920 (1500) (as per IEC 62040/3) -
(100m rise between 1500-3000m)
Specifications
540V
WEEE

Table 10 Alber battery monitoring option specifications

Electrical Data Value
Input Voltage 220-600VAC
Input Current < 0.5A
Frequency 60Hz

Table 11 Currents for Liebert NXL Module Battery Disconnect Cabinet

UPS Rating
250 225 615 700
300 270 737 800
400 360 981 1000
500 450 1224 1600
625 562.5 1526 1600
750 675 1828 2000
Max Battery Current
at End of Discharge
External Breaker
Trip AmpskVA kW
39

Table 12 Battery cabinet internal breaker selection based on 5 min EOD, amps

Model
Number
Code Battery Type
PR UPS12-300MR 5 580 363 400
RR UPS12-350MR 5 672 420 450
UR UPS12-400MR 5 770 481 500
WR UPS12-490MR 5 840 525 600
XR UPS12-540MR 5 952 595 600
PX HX300-FR 5 591 369 400
RX HX330-FR 5 678 424 450
UX HX400-FR 5 771 482 500
WX HX500-FR 5 941 588 600
Battery Currents for Various Discharge Times
Discharge Time (Min)
Watts to Discharge
to 1.60V in 5 min. Amps @ EOD
Required Breaker
Thermal Trip Amps

Table 13 Liebert NXL Battery Cabinet approximate weights

Battery
Code
PR
Manufacturer Battery Model
UPS12-300MR 3910 (1774)
Total Weight
lb (kg)
RR UPS12-350MR 4265 (1935)
UR UPS12-400MR 4600 2087)
C&D
Batteries
WR UPS12-490MR 5545 (2515)
XR UPS12-540MR 5545 (2515)
PX
RX HX330-FR 4200 (1905)
UX HX400-FR 4760 (2159)
Enersys
HX300-FR 3760 (1706)
WX HX500-FR 5750 (2608)
Specifications
Table 14 Approximate weights, Liebert NXL Module Battery Disconnect and Liebert NXL
Junction Cabinets
Module Battery
Disconnect Cabinet Junction Cabinet
Cabinet Size Weight, lb (kg) Cabinet Size Weight, lb (kg)
250-400kVA 544 (247) Narrow 255 (115)
500-750kVA 544 (247) Wide 400 (180)
40
Specifications

Table 15 Recommended conduit and cable sizes for Liebert NXL Module Battery Disconnect

Nominal Selection Alternate Selection
UPS
Size,
kVA
250kVA
300kVA
400kVA
500kVA
625kVA
750kVA
The recommendations in this table are guidelines only and are superseded by local regulations and codes of practice where applicable:
1. Take special care when determining the size of the neutral cable, because current circulating on the neutral cable may be greater than
2. The ground conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The ground cable connecting
3. Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.
4. When laying the power cables, do not form coils. Coiling power cables increases the likelihood of electromagnetic interference.
Top Cable Entry Input
Wire & Conduit
Wires, G THW / FMC
(2) 2.5C 2-350kcmil,
#1/0AWG
(2) 2.5C 2-500kcmil,
#1/0AWG
(3) 2.5C 2-500kcmil,
#4/0AWG
(4) 3C 2-750kcmil,
#4/0AWG
(4) 3C 2-750kcmil,
#4/0AWG
(5) 3.5C 2-750kcmil,
250kcmil
nominal current in the case of non-linear loads. Refer to the values given in the UPS electrical characteristics in this table.
the UPS to the main ground system must follow the most direct route possible.
Bottom Cable Entry Input
Wire & Conduit
Wires, G THW / RNC
(3) 2C 2-#4/0AWG,
#1/0AWG
(3) 2C 2-250kcmil,
#1/0AWG
(4) 2.5C 2-250kcmil,
#4/0AWG
(4) 3.5C 2-750kcmil,
#4/0AWG
(4) 3.5C 2-750kcmil,
#4/0AWG
(5) 3.5C 2-750kcmil,
250kcmil
Top Cable Entry Input
Wire & Conduit
Wires, G THW / FMC
(2) 2.5C 2-350kcmil,
#1/0AWG
(2) 2.5C 2-500kcmil,
#1/0AWG
(3) 2.5C 2-500kcmil,
#4/0AWG
(5) 2.5C 2-500kcmil,
#4/0AWG
(5) 2.5C 2-500kcmil,
#4/0AWG
(6) 3C 2-500kcmil,
250kcmil
Bottom Cable Entry Input
Wire & Conduit
Wires, G THW / RNC
(3) 2C 2-#4/0AWG,
#1/0AWG
(3) 2C 2-250kcmil,
#1/0AWG
(4) 2.5C 2-250kcmil,
#4/0AWG
(5) 3C 2-500kcmil,
#4/0AWG
(5) 3C 2-500kcmil,
#4/0AWG
(6) 3C 2-500kcmil,
250kcmil

Table 16 Battery torque values

Battery
Code Manufacturer Battery Model
PR
UPS12-300MR 110 (12.4)
RR UPS12-350MR 110 (12.4)
UR UPS12-400MR 110 (12.4)
C&D Batteries
WR UPS12-490MR 110 (12.4)
XR UPS12-540MR 110 (12.4)
PX
RX HX330-FR 65 (7.3)
UX HX400-FR 65 (7.3)
Enersys
HX300-FR 65 (7.3)
WX HX500-FR 65 (7.3)
Torque Value
in-lb (Nm)

Table 17 Torque specifications, unless otherwise labeled

Nut and Bolt Combinations
Electrical Connections
with Belleville Washers
lb-in (Nm)
Bolt Shaft Size
Grade 2 Standard
lb-in (Nm)
1/4 53 (6.0) 46 (5.2)
5/16 107 (12) 60 (6.8)
3/8 192 (22) 95 (11)
1/2 428 (48) 256 (29)
Circuit Breakers with Compression Lugs (For Power Wiring)
Current Rating lb-in (Nm)
400 - 1200 Amps 300 (34)
Circuit Breakers with Compression Lugs (For Control Wiring)
AWG Wire Size or Range lb-in (Nm)
#22 - #14 3.5 to 5.3 (0.4 to 0.6)
41
Notes
Specifications
42
Ensuring The High Availability 0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@emersonnetworkpower.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
SL-25430_REV01_06-08
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
AC Power
Connectivity
DC Power
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.
Embedded Computing Embedded Power Power Switching & Controls Monitoring
Outside Plant
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Loading...