Please allow us to congratulate you on choosing a Liebert manufactured Uninterruptible Power System.
If this is your first Liebert UPS, we cordially welcome you to a lifetime relationship of after-sales support
designed to keep your Liebert UPS and your systems permanently at their peak performance.
If you already own and use a Liebert UPS, then we are doubly honoured by your decision to continue this
valued relationship.
Our philosophy is reflected in our mission statement “Keeping Business in Business,” and with this we strive
to contribute to the growth & success of your business.
Please give us your valued feedback to help us realise our mission.
200kVA module for Europe and Middle East, 400V/230V output
OptionsModel IdentificationNote
Narrow battery cabinetNXA0BCNSpecify: UPS kVA rating,
Wide battery cabinetNXA0BCW
Battery Circuit Breaker Box NXA0BCBSpecify UPS kVA rating
Battery Start KitNXA0UFXBB—
Battery Ground Fault detection kitNXA0UFXBGF—
Battery temperature probe (for external battery) NXA0UFXBTS—
Maintenance bypass cabinet (separate bypass input) NXA0MBXSpecify total system kVA
Transformer cabinet NXA0TCXSpecify UPS kVA & I/O Voltage
Fan Redundancy kit NXA0UFXRFSpecify UPS kVA rating
Seismic Anchor kit NXA0UFXSAN—
Bypass current sharing inductanceNXA0UFXBK—
Dual bus control cable 05-10-15 metr esNXA0UFXDSpecify length in metres
Parallel control cable kit 05-10-15 metresNXA0UFXPSpecify length in metres
Relay Card (On Bat, Bat Low, On Byp, Sum, UPS Fail)
Relay Card 4 (4 sets On Bat, bat Low)
Webbrowser/TCPIP/SNMP Card
Jbus/Modbus Card
RAM - Remote Alarm MonitorNXA0CFXRAM Requires RELAYCARD-INT
Modem cardNXA0CFXMOD—
Large Battery Cabinet NXA0NBCL—
Maintenance bypass cabinet (separate bypass input)NXA0NMBX—
Transformer cabinetNXA0NTCX—
Air Filter (One Filter)NXA0UFXARF—
Dual Bus Extension Kit 50-150 Meters NXXXXMLBSKIT(XXX: 050 or 150)- 'Specify Length in metres.
Individual Battery MonitoringBDS 40 or BDS 256Specify number of blocks. Consult Emerson
RELAYCARD-INT
MULTIPORT 4
OCWEB-LB
OC485CARD
3, 4 or 5-shelves
fuse or circuit breaker protection
Intellislot plug-in cards—3 slots available.
Used for extension in length or dual bus
arrangement between Nx and non-Nx
sources'
Network Power representatives for complete
configuration
ix
x
SAFETY PRECAUTIONS
This manual contains information concerning the installation and operation of this Emerson Network
Power Liebert NX Uninterruptible Power System (UPS).
This manual should be read before commencing installation.
The UPS must be commissioned and serviced by an engineer approved by the manufacturer (or
agent).
Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of warranty.
The Liebert NX has been designed for Commercial/Industrial use only, and is not recommended for
use in life support applications.
This is a low emission CLASS A Uninterruptible Power System (UPS) product. In a residential environment, this product may nevertheless cause radio interference, in which case, the user may be
required to take additional measures.
Conformity and Standards
This equipment complies with CE directives 73/23 & 93/68 (LV Safety) and 89/336 (EMC), with Australia and New Zealand EMC Framework (C-Tick) and with the following product standards for Uninterruptible Power System (UPS).
• EN / IEC / AS 62040-1-1—General and safety requirements for use in operator access area
• EN / IEC / AS 62040-2—EMC requirements; Class A compliant
• EN / IEC / AS 62040-3—Performance requirements and test methods
For more details, see 10.0 - Technical Specifications
Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.
WARNING
!
High Leakage Current
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA for 30-80kVA, less than
2000mA for 100-120kVA. models and less than 2500mA for 140-200kVA models.
Transient and steady-state earth leakage currents, which may occur when starting the
equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional
pulses (class A) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with the local electrical code of practice.
WARNING
!
Back-Feed Protection Notice
This UPS is fitted with a voltage-free contact closure signal for use with an external
automatic disconnect device (supplied by others) to protect against back-feeding voltage into
the bypass input. If this signal is not used by the installer, a label must be added at the
external bypass input disconnect device to warn service personnel that the circuit is
connected to a UPS.
The text to use is the following or equivalent:
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS
CIRCUIT.
1
User-Serviceable Parts
All equipment maintenance and servicing procedures involving internal access requires the use of a
tool and should be carried out only by trained personnel. There are no user-serviceable parts behind
covers requiring a tool for removal.
This UPS is fully compliant with safety regulations for equipment located in an operator accessible
area. Hazardous voltage is present within the UPS and battery enclosure but out of reach of non-service personnel. Contact with hazardous voltage is minimized by housing live parts behind safety panels that require a tool for their removal. No risk exists to any personnel when operating the
equipment in the normal manner, following the recommended operating procedures.
Battery Voltage Exceeds 400VDC
All physical battery maintenance and servicing requires the use of a tool or a key and should be carried out only by trained personnel.
WARNING
!
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the battery terminal voltage will exceed 400VDC and is potentially
lethal.
Battery manufacturers supply details of the necessary precautions to be observed when working on,
or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all
times.
Attention should be paid to the recommendations concerning local environmental conditions and the
provision of protective clothing, first aid and fire-fighting facilities.
2
1.0SINGLE MODULE UPS INSTALLATION
1.1Introduction
This following section describes the requirements that must be taken into account when planning the
positioning and cabling of the Liebert NX uninterruptible power supply and related equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing
engineer. The particular conditions of each site will determine the applicability of such procedures.
WARNING
!
Professional Installation Required
Do not apply electrical power to the UPS equipment before being authorised to do so by the
commissioning engineer.
The UPS equipment shall be installed by a qualified electrical tradesperson in accordance
with the information contained in this manual. All equipment not referred to this manual is
shipped with details of its own mechanical and electrical installation.
NOTE
Three-phase, 4-wire input supply required.
The standard Liebert NX UPS is suitable for connection to 3-phase, 4-wire (+ Earth) TN, TT
and IT AC power distribution systems (IEC60364-3). Optional 3-wire to 4-wire conversion
transformers are available. If it is used in IT AC power distribution systems, a 4-pole circuit
breaker must be used on the input and refer to the relative IT Systems’ standard
Single Module UPS Installation
WARNING
!
Battery Hazards
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the battery terminal voltage will exceed 400VDC and is hazardous.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Remove rings, watches and all other metal objects.
Use only tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed
immediately with water.
1.2Preliminary Checks
Before installing the UPS, please carry out the following preliminary checks:
1. Visually examine the UPS and battery equipment for transit damage, both internally and
externally. Report any damage to the shipper immediately.
2. Verify that the correct equipment is being installed. The equipment supplied has an identification
tag on the back of the main door reporting: the type, size and main calibration parameters of the
UPS.
3
1.3Location
1.3.1UPS Room
The UPS and its internal battery is intended for indoor installation and should be located in an environment with clean air and with adequate ventilation to keep the ambient temperature within the
specified operating range (see Table 33).
All models in the Liebert NX UPS range are air-cooled with the aid of internal fans. Cold air enters
through ventilation grilles at the front of the cabinet for NXa 30-120kVA and through ventilation
grilles located at the front and bottom of the cabinet for NXa 140-200kVA. Hot air is released through
grilles at the top. Do not cover the ventilation openings.
If necessary to avoid room temperature build-up, install a system of room extractor fans. Optional air
filters are available if the UPS is to operate in a dusty environment.
The UPS heat dissipation detailed in Table 34 can be used as a guide for air conditioning sizing,
depending on the selected mode of operation:
• Normal Mode (VFI SS 111 Double Conversion UPS)
• ECO Mode (VFD SS 311 Stand By UPS)
If in doubt use Normal Mode figures.
NOTE
The UPS is suitable for mounting on concrete or other non-combustible surface only.
Single Module UPS Installation
1.3.2External Battery Room
Batteries should be mounted in an environment where the temperature is consistent and even over
the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical
battery manufacturer performance data are quoted for an operating temperature between 20 and
25°C (68 and 77°F). Operating above this range will reduce the battery life while operation below this
range will reduce the battery capacity. In a normal installation the battery temperature is maintained between 15°C and 25°C (59 and 77°F). Keep batteries away from main heat sources or main air
inlets etc.
Where the batteries are located externally to the main UPS cabinet, a battery protection device
(e.g., fuses or circuit breakers) must be mounted as close as possible to the batteries themselves, and
connected using the most direct route possible.
1.3.3Storage
Should the equipment not be installed immediately, it must be stored in a room for protection against
excessive humidity and or heat sources (see Table 33).
CAUTION
!
An unused battery must be recharged periodically per battery manufacturer
recommendation. Temporarily connecting the UPS to a suitable AC supply mains and
activating it for the time required for recharging the batteries can achieve this.
4
1.4Positioning
The cabinet is mounted on four casters for ease of positioning and for moving short distances. Jacking
feet are provided to prevent the UPS from moving once it has been wheeled to its final position.
For optimal design life, the place chosen must offer:
•Easy connection
• Enough space to easily work on the UPS
• Sufficient air exchange of enough to dispel heat produced by UPS
• Protection against atmospheric agents
• Protection against excessive humidity and very high heat sources
• Protection against dust
• Compliance with the current fire prevention requirements
• Operating environment temperature between 20°C and 25°C (68 and 77°F). The batteries are at
maximum efficiency in this temperature range (see Table 33).
The UPS cabinet is constructed around a steel chassis with removable panels. The top and side panels
are secured to the chassis by screws.
Access to the power terminals, auxiliary terminals blocks and power switches is from the front. Operational status and alarm information is provided through the front door operator control panel. Models 40kVA and below house both the power components and an internal battery. Cooling air enters in
the front of the NXa 30-120kVA and the front and bottom of NXa 140-200kVA; it is exhausted out the
top of each.
1.4.1System Cabinets
A UPS may comprise a number of cabinets, depending on design requirements (e.g., UPS cabinet, external battery cabinet, external bypass cabinet). In general, all the Liebert cabinets used in a particular
installation are of the same height and designed to be positioned side-by-side to form a matching array.
Refer to 5.0 - Installation Drawings for assistance on positioning the cabinets described below.
Single Module UPS Installation
1.4.230 to 40kVA UPS
The UPS consist of a single cabinet, which uses typically forty (40) 12V battery blocks, fitted internally and connected in series to provide a nominal battery voltage.
the batteries fitted.
An extended battery option is available. This comprises a separate cabinet containing additional batteries that can be connected to the UPS to increase its battery run time. Battery cabinets and batteries are usually shipped separately.
1.4.360-200kVA UPS
The 60 to 200kVA consist of a single cabinet without any internal battery. Usually, with 60 to 200kVA
UPS installations, the batteries are contained in a purpose-built battery cabinet, which sits alongside
the main UPS equipment. Batteries are accessible in the external cabinet from the front, making it
unnecessary to allow for side access.
1.4.4Moving the Cabinets
WARNING
!
Ensure that the UPS weight is within the designated surface weight loading of any handling equipment. See Table 35.
UPS and optional cabinets (battery cabinets, top cable entry cabinets, etc.) can be handled by means
of a forklift or similar equipment.
The UPS cabinet also can be moved short distances by its casters.
Ensure that any equipment used to move the UPS cabinet has sufficient lifting capacity.
The UPS is fitted with casters. Take care to prevent the NX from moving when unbolting the
unit from its shipping pallet. Ensure that adequate personnel and lifting aids are available
when removing the shipping pallet.
The UPS may be shipped without
NOTE
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a
minimum.
5
1.4.5Clearances
The Liebert NX has no ventilation grilles at either side of the UPS. To enable routine tightening of
power terminations within the UPS, in addition to meeting any local regulations, Liebert recommends providing adequate clearance in the front of the equipment for unimpeded passage of personnel with the doors fully opened. It is important to leave 800mm (31.5") clearance above the UPS to
permit adequate circulation of air coming out of the unit.
1.4.6Access
The component layout of the UPS supports front and top access while servicing, diagnosing and
repairing the UPS, thus reducing the space requirement for side and rear access.
1.4.7Final Positioning
The UPS cabinets are fitted with casters on the base to allow ease of movement and positioning.
WARNING
!
Casters are strong enough for movement across even surfaces only. Caster failure could occur
if they are subjected to shock loading.
When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS
will remain stationary and stable.
1.4.8Floor Anchoring
Single Module UPS Installation
Diagrams in 5.0 - Installation Drawings show the location of the holes in the base plate through
which the equipment may be bolted to the floor. If the equipment is to be installed on a raised floor it
should be mounted on a pedestal suitably designed to accept the equipment point loading.
1.4.9Cable Entry
Cables can enter the Liebert NX UPS and battery cabinet from below. Cable entry is made possible by
removing a blanking piece fitted at the bottom of equipment to reveal the cable entry hole.
Top Cable Entry—Optional
Optionally a top cable entry extension may be used. The cabinet extends the overall width of the UPS
and permits connection of all incoming AC/DC power cables from above.
The top cable entry option is fitted on the side of the UPS cabinet and is supplied without side panels;
the side cover from the UPS being used.
The cabinet with cables coming in from the top for the 30-40 kVA UPS must be positioned on the left
side; the cabinet for the 60 to 200 kVA UPS can be positioned on either side.
This facilitates cable entry through the top metal panel after the appropriate cable entry holes have
been cut.
NOTE
The top cable entry also includes the power connection cables between the cabinet and the UPS.
1.5External Protective Devices
Circuit breakers or other protective devices must be installed in the AC supply, external to the UPS.
This chapter provides guidelines for qualified installers who must have knowledge of local wiring
practices pertaining to the equipment to be installed.
6
1.5.1Rectifier and Bypass Input
Overcurrent protection must be installed at the distribution panel of the incoming main supply. The
protection must discriminate with the power cables current capacity and with the overload capacity of
the system (see Table 38). As a guideline, a thermomagnetic circuit breaker, with an IEC 60947-2
trip curve C (normal) for 125% of the current listed in Table 1 is suitable.
Split-Bypass—If a split-bypass is used, install separate protective devices for the rectifier and for
the bypass in the incoming mains distribution panel.
NOTE
Rectifier and bypass input sources must be referenced to the same neutral potential.
NOTE
Earth Leakage (RCD)
Any residual current detector (RCD) installed upstream of the UPS input supply must be:
For IT power systems, four-pole protective devices must be used, external to the UPS, both
upstream of the input distribution panel and downstream (toward the load).
• sensitive to DC unidirectional pulses (Class A)
• insensitive to transient current pulses, and
• must have an average sensitivity, adjustable between 0.3 and 1A.
Single Module UPS Installation
Figure 1Residual current circuit breakers (RCCB) symbols
To avoid false alarms, earth leakage monitoring devices when used in systems with split-bypass input
or when used in paralleled UPS configurations, must be located upstream of the common neutral
sinking point. Alternatively, the device must monitor the combined four-wire rectifier and splitbypass input currents.
The residual earth current introduced by the RFI suppression filter inside the UPS is greater than
3.5mA, 1000mA for 30-80kVA, 2000mA for 100-120kVA models and less than 2500mA for
140-200kVA models. Liebert recommends verifying the selectivity with all other differential devices
both upstream of the input distribution board and downstream (toward the load).
1.5.2External Battery
The UPS and its associated batteries are protected against overcurrents through a DC compatible disconnect device.
1.5.3UPS Output
Any external distribution board used for load distribution shall be fitted with protective devices that
discriminate with those used at the bypass input to the UPS and with the UPS overload characteristics (see Table 38).
7
1.6Power Cables
The cable design must comply with the voltages and currents provided in this section, follow local wiring practices and take into consideration the environmental conditions (temperature and physical
support media).
For cable entry terminal, refer to Figures 43, 48, 52 and 56.
WARNING
!
Table 1Maximum steady state AC and DC currents
RATING
Before starting the UPS, ensure that you are aware of the location and operation of the
external isolators that connect the ups input/bypass supply to the mains distribution panel.
Check that these supplies are electrically isolated and post any necessary warning signs to
prevent their inadvertent operation.
UPS 30/40 kVAUPS 60-80 kVAUPS 100-120 kVAUPS 140-200 kVA
1320(52)1500 (59)
M8: 13 (2.9)
M10: 26 (5.8)
WARNING
!
Failure to follow adequate earthing procedures may result in electromagnetic interference or
in hazards involving electric shock and fire.
8
1.6.1Cable Termination
NOTE
Once the equipment has been finally positioned and secured, connect the power cables as described in
the following procedure.
Refer to the appropriate cable connection drawing in 5.0 - Installation Drawings.
1. Verify that the UPS equipment is isolated from its external power source and all the UPS power
2. Open the door to the UPS cabinet and remove one of the two protective cover to gain access to the
3. Connect the safety earth and any necessary bonding earth cables to the copper earth busbar
The operations described in this section must be performed by authorised electricians or
qualified technical personnel. If you have any difficulties, do not hesitate to contact our
Customer Service and Support Department. See the back page of this manual for contact
information.
isolators are open. Check that these supplies are electrically isolated and post any necessary
warning signs to prevent their inadvertent operation.
desired connection bars.
• the lower protective cover houses the 60-200kVA connection bars
• the left protective cover houses the 30-40kVA connection bars
The protective cover on the UPS cabinet of 60 to 200kVA models must be removed after the
handles on the power isolators have been removed.
located on the floor of the equipment below the power connections. All cabinets in the UPS must
be connected to the user’s ground connection.
Single Module UPS Installation
NOTE
The earthing and neutral bonding arrangement must be in accordance with local and national
codes of practice.
Identify and make power connections for incoming cables according to one of the two procedures
below, depending on the type of installation.
Common Input Connections
4. For common bypass and rectifier inputs, connect the AC input supply cables between the mains
distribution panel and the UPS input (U1-V1-W1-N terminals) and tighten the connections to
5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm for M10 bolts. Ensure correct phase rotation.
Split-Bypass Connections
5. If a split-bypass configuration is used, connect the AC input supply cables to the rectifier input
busbars (U1-V1-W1-N terminals) and the AC bypass supply cables to the bypass input
(U3-V3-W3-N terminals) and tighten the connections to 5Nm for M6 bolts, to 13Nm for M8 bolts
or to 26Nm (M10 bolt). Ensure correct phase rotation.
NOTE
For split-bypass operation, ensure that the linking busbars between bypass and rectifier input
are removed.
The AC input and the AC bypass supplies must be referenced to the same neutral point.
Frequency Converter Mode
If a frequency converter configuration is used, connect the AC input supply cables to the rectifier
input busbars (U1-V1-W1-N terminals). Torque to 5Nm for M6 bolts, to 13Nm for M8 bolts or to
26Nm (M10 bolt). Ensure correct phase rotation. There will not be any AC bypass supply cables to the
bypass input (U3-V3-W3-N terminals) and tighten the connections.
NOTE
For frequency converter operation, ensure that the linking busbars between bypass and rectifier
input are removed.
9
Single Module UPS Installation
Output System Connections
6. Connect the system output cables between the UPS output (U2-V2-W2-N terminals) and the
critical load and tighten the connections to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm for
M10 bolts. Ensure correct phase rotation.
External UPS Battery Connection (60kVA Models and Above, Option for 30-40kVA Models)
Connect the battery cables between the UPS terminals (+\-) and its associated battery circuit
breaker. Observe the battery cable polarity.
NOTE
When connecting the cables between the battery extremities to the circuit breaker always
connect the circuit breaker end of the cable first.
WARNING
!
If the load equipment will not be ready to accept power on the arrival of the commissioning
engineer, ensure that the system output cables are safely isolated at their ends.
Internal UPS Battery Connection (30/40kVA only)
7. The battery consists of a series string connection of 5 x 8 (or 10) x 12V 6-cell battery blocks.
a. Ensure that the eight (or 10) battery blocks in each tier (tray) are interconnected.
b. Connect the positive and negative cables to the UPS terminals.
c.Plug in the cables between the tiers.
d. Ensure correct polarity battery string series connections (i.e., intertier and
interblock connections are from positive to negative terminals.
WARNING
!
Hazardous Battery Terminal Voltage 480VDC
Ensure correct polarity of string end connections to the UPS terminals, i.e., positive to
positive and negative to negative, but leave these UPS terminal cables disconnected until
connection is authorised by the commissioning engineer.
Ensure correct polarity of string end connections to the battery circuit breaker and from the
battery circuit breaker to the UPS terminals, i.e., positive to positive and negative to negative,
but disconnect one or more battery cell links in each tier.
Do not reconnect these links and do not close the battery circuit breaker before authorised by
the commissioning engineer.
8. Refit all protective covers removed for cable installation.
10
1.7Control Cables and Communication
1.7.1Monitor Board Features
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker, battery temperature sensor), communicate with a personal
computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).
The monitor board, arranged for this purpose, is located on the rear of the operator access door. The
main features are:
• Input and Output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
The black square ( )
on each s lot indi cates P in 1.
X4
J24
X6
PWR
Modem
SNMP Card
X4
X5
11
1.8Dry Contacts
The UPS provides input dry contacts and output dry contacts.
1.8.1Input Dry Contacts
There are several input dry contacts at the X3 slot.
X3 Ancillary Control and Alarms
X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts
The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, pushin terminal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS
when connection between the relevant terminal and the +12V terminal is altered. Cables connected to
X3 IN DRY must be segregated from power circuits (for screening purposes), double insulated and of a
typical 0.5 to 1mm
respectively.
Figure 3Input dry contacts
12V
2
cross-section area for maximum runs between 25 and 50 meters (82-164 ft),
Single Module UPS Installation
12V12V
12V
X3
J4J26J30J10
12V
BtG
GEN
ENV
12V
GND
T_IT
AUX_I
T_OT
AUX_O
FUSE
F_FAN
OL
GND
Table 3Input dry contacts at X3
Position
J4.1ENV
J4.2BtGBattery Ground Fault Detection (NC)
J4.3GEN
J4.4+12V+12V Power
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
Name
Description
3
Battery Room Alarm (NC)
1,2
On Generator (NO)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.
- Must be configured by software before becoming active
Name
Description
1
Input transformer overtemperature (NC)
1
Output Transformer Overtemperature (NC)
Single Module UPS Installation
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.
1.8.3External Circuit-Breaker Interface
J10 is the interface to any external battery circuit breaker (BCB).
Table 5
Position
J10.1DRVBCB Driver Signal - Output (N.O.)
J10.2FBBCB Contact State - Input (N.O.)
J10.3GNDPower Ground
J10.4OL
External circuit-breaker interface
Name
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
Description
BCB On-Line - Input - This pin will become active when
BCB interface is connected. (N.O.)
2
2
13
1.8.4Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 4 and Table 6)
Single Module UPS Installation
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.
Figure 4Output dry contacts and EPO wiring for firmware before M162
J13
BFP_C
BFP_S
BFP_O
J21J25J25
INV_S
INV_C
INV_O
ACF_C
ACF_S
ACF_O
Table 6Output dry contact relays for firmware before M162
PositionName
J13.2BFP_OBypass feedback protection relay; normally ope n. Closed when bypass SCR is shorted.
J13.3BFP_SBypass feedback protection relay center
J13.4BFP_CBypass feedback protection relay; normally closed. Open when bypass SCR is shorted.
J21.2INV_OInverter mode relay; normally open. Closed when UPS is in inverter mode.
J21.3INV_SInve rter mode relay center
J21.4INV_CInverter mode relay; normally closed. Open when UPS is in inverter mode.
J25.2ACF_OMain input fault relay; normally open. Closed when main input is in fault.
J25.3ACF_SMain input fault relay center
J25.4ACF_CMain input fault relay; normally closed. Open when main input is in fault.
Description
2
+12V
X2X1
EPO-LEPO-H
Figure 5EPO wiring for firmware M200 or later
J28
EPO-NOEPO-NC
1.8.5Emergency Power Off Input
The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel
or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 4, is the remote EPO input interface. The EPO has an NO/NC contact
point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1
If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the
auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop
X2
14
Single Module UPS Installation
switch between these two terminals using shielded cable (see Figure 4 and Table 7). If this function
is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed.
Table 7EPO input contact relays
PositionName
J28.1EPO_NC EPO Activated when opened to J28.2
J28.2EPO_NCEPO Activated when opened to J28.1
J28.3EPO_NOEPO Activated when sh orted to J28.4
J28.4EPO_NOEPO Activated when sh orted to J28.3
Description
NOTE
The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass.
It does not internally disconnect the input power supply. To disconnect ALL power to the UPS,
open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor
board and must remain installed if using NC contacts.
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 0.5-1.5mm
2
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
X5: Auxiliary DC Power Output
Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maximum current is 500mA.
X6: Analog Input Interface
Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%.
• X6 pin 1: Not used
• X6 pin 2: +12V
• X6 pin 3: ENV-T – environment temperature detection
• X6 pin 4: GND
X7: External Battery Temperature Detector Interface
Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see
Figure 26).
Pin reference:
• X7 pin 1: Not used
• X7 pin 2: +12V (Power supply for Temperature Monitoring Probe)
• X7 pin 3: BAT-T (Battery Temperature signal)
• X7 pin 4: GND
15
Serial Ports RS232-1 and RS232-2
RS232-1 provides serial data and is intended for direct use with Liebert MultiLink monitoring and
server shutdown software.
RS232-2 provides serial data and is intended for use by authorized commissioning and service personnel.
These serial ports are shared with the optional Web browser, SNMP, ModBus and relay cards. Refer
to Table 31 regarding compatibility of simultaneous use.
Intellislot Web Browser, SNMP, ModBus and Relay Cards Interface
There are three interface slots available for optional Web browser, SNMP, ModBus and Relay cards
as illustrated in 9.0 - Options—For Assembly Inside the UPS Cabinet.
1.8.6External Bypass Switch Interlock
EXT-Maint X3-1&2 on UPS Parallel Board M3 (leave open if no external bypass switch is used)
Provides external maintenance bypass interlock protection for the UPS. Short circuit means external
bypass closed.
EXT-Out (X3-3&4) on UPS Parallel Board (leave shorted if no external output switch is used). Provides external output interlock protection for paralleled UPS modules. Short circuit means external
output switch closed.
Single Module UPS Installation
NOTE
UPS Parallel Board M3 is located behind protective covers accessible after opening the UPS
front door—removal of this barrier requires the use of a tool and is restricted to service
personnel.
NOTE
Jumper JP1 (located next to X3) needs to be removed for X3:3&4 to work properly.
16
2.0BATTERY INSTALLATION
2.1Introduction
The UPS battery bank consists of battery blocks connected in series to provide a D.C. string voltage as
required by the UPS converter. The 'AUTONOMY TIME' (the time during which the battery can
maintain supply to the load in the event of a mains failure) is limited by the ampere-hour capacity of
the battery blocks and in some cases this results in several strings being connected in parallel.
The NX 30-40kVA has internal batteries, but longer run time is available by using an external battery cabinet.
The battery cabinet will be supplied in one of the following forms:
1. Complete installation, comprising the battery cabinet, batteries and protective device.
2. Battery cabinets and protective device only—batteries supplied by others
3. Battery cabinet only—batteries and circuit breaker supplied by others.
NOTE
30kVA to 40kVA UPS models contain an internal battery compartment that can accommodate
up to 42 blocks 24 Ah/12V batteries.
The battery bank may be disconnected from the UPS for maintenance or service. The circuit breaker
can be switched ON or OFF manually and further battery isolation control is achieved through the
use of either a battery circuit-breaker undervoltage coil or through an automatic contactor inside the
UPS.
Battery Installation
17
2.2Safety
Special care should be taken when working with the batteries associated with the Liebert NX UPS
system. When all the cells are connected together, the battery terminal voltage is potentially hazardous. The battery installation must be segregated from all but appropriately qualified maintenance
personnel by locating the cells in a key-lockable cabinet or in a purpose-designed, dedicated battery
room.
!
Battery Installation
NOTE
Full safety instructions concerning the use and maintenance of UPS batteries are provided in
the appropriate battery manufacturers manuals. The battery safety information contained in
this section relates to key considerations that must be taken into account during the
installation design process and might affect the design outcome depending on localised
conditions.
WARNING
Hazardous battery voltage present behind covers
No user-serviceable parts are located behind covers that require a tool for their removal. Only
qualified service personnel are authorised to remove such covers.
When using internal batteries in 30 and 40kVA units, the batteries are always connected
through power fuses to the UPS and to the segregated terminal bars available for connection
to an external battery.
Isolate any internal battery connections before attempting to access the segregated terminal
bars available for connection to an external battery.
The following general battery safety precautions and warnings should be observed at all
times:
• A battery can present risk of electric shock or burn from high- short-circuit currents.
• The full nominal string voltage, when the battery blocks are interconnected, is 480VDC,
which is hazardous
• Only qualified personnel should install or service batteries.
• Eye protection should be worn to prevent injury from electrical arcs.
• Remove rings, watches, necklaces, bracelets and all other metal objects.
• Use only tools with insulated handles.
• Wear rubber gloves and a rubber apron when handling batteries.
• If a battery leaks electrolyte or is otherwise damaged, it should be placed in a container
resistant to sulfuric acid and disposed of in accordance with local regulations.
• If electrolyte comes into contact with the skin the affected area should be washed immediately with plenty of clean water.
• Batteries must always be disposed of according to local environmental laws.
• When replacing batteries, use the same number and type that were originally fitted.
• Disconnect charging source before connecting or disconnecting battery terminals.
• Determine whether the battery is inadvertently grounded. If it is inadvertently grounded,
remove the source of the ground. Contact with any part of a grounded battery can result in
electrical shock.
2.3Battery Cabinet
2.3.1Introduction
This cabinet can also be used in conjunction additional cabinets, to provide the necessary accommodation required by the larger cells associated with system’s having a long autonomy time.
Where two (or more) cabinets are used they are positioned alongside each other and secured and
bonded together. If the cabinet(s) is located immediately adjacent to the main UPS equipment the two
units are bolted together.
18
2.3.2Temperature Considerations
Valve-regulated, lead acid battery cells are sensitive to ambient temperature and should be operated
between 15°C and 25°C (59-77°F). Battery capacity is increased by 1% for every 1°C (2°F) increase in
temperature up to 25°C (77°F). Battery life is reduced at temperatures above 25°C (77°F).
When batteries are mounted in the same room as the UPS unit, it is the battery that dictates the
designed maximum ambient temperature, not the UPS. — i.e. in the case of valve-regulated cells, the
ambient room temperature should be kept between 15°C and 25°C (59-77°F), and not between 0°C
and 40°C (32-104°F) (which is the specified main equipment operating temperature range). Temperature deviations are permissible for short periods, provided the average temperature does not exceed
25°C (77°F).
2.3.3Dimensions
The external dimensions are shown in Table 8. These are the same height and depth as the UPS
module and provide a matching appearance when bolted together. All cabinets are fitted with doors,
which must be fully opened in order to fit or remove the batteries. The door swing must therefore be
taken into consideration when planning the positioning of the cabinets.
2.3.4 Weight
The unladen weight is shown below in Table 8. When designing the battery installation the weight of
the batteries and cables must be added to the unladen weight. This is particularly important when
placing the NX on a raised floor.
Table 8Dimensions and weight
Rated Service
ModelUPS Ratings
30kVA
Narrow
Cabinet
Wide
Cabinet
Large
Cabinet
40kVA
60kVA
80kVA
30kVA
40kVA
60kVA
80kVA
100kVA
120kVA
140kVA
160kVA
200kVA
Current (In)
125A
200A
125A
200A
400A
500A
Rated
Uninterrupted
Current (IU)
160A
250A
160A
250A
400A
500A
External Cabinet
WxDxH, mm (in)
828x825x1600
(32.6x32.4x63)
1490x825x1600
(58.7x32.4x63)
1490x825x1800
(58.7x32.4x76.9)
Battery Installation
Cabinet Weight
Without Batteries,
kg (lb)
200 (441)
270 (595)
305 (672)
2.3.5Circuit Breaker Features
In 30 to 40kVA models fitted with internal battery and in all models fitted with a Battery Start kit,
the UPS is fitted with an internal contactor for automatic connection and disconnection of the batteries. External battery banks connected to such models generally are protected by a standard battery
circuit breaker (with status contacts and without undervoltage trip coil). Refer to 2.5 - Battery Con-trol for details.
When no internal contactor for automatic disconnection is installed in the UPS module, the external
battery disconnection is performed by fitting a Circuit Breaker Controller Board and an undervoltage
coil to the battery circuit breaker.
The circuit breaker can then be manually closed once the DC busbar is above the ‘low battery; trip
voltage. Once closed, the circuit breaker can be opened manually at any time and is tripped automatically by the UPS module following certain fault occurrences, an emergency power off command or if
low/high DC busbar voltage is detected. Refer to 2.5 - Battery Control for details.
19
2.3.6Moving the Battery Cabinets
WARNING
!
Ensure that the weight is within the designated surface weight loading of any handling equipment.
See Table 8 for weight details.
Battery cabinets can be handled by means of a fork lift or similar equipment.
Ensure any lifting equipment used in moving the cabinet has sufficient lifting capacity.
NOTE
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a
minimum.
When the equipment has been finally positioned ensure the adjustable feet are set so that the
battery cabinet will remain stationary and stable.
2.3.7Cable Entry
Cables enter the battery cabinet from either the top or the bottom. Cable entry is made possible by
removing a blanking piece fitted at the bottom to reveal the cable entry hole.
Battery Installation
20
2.3.8General Arrangement Drawings
Refer to Figures 6 through 10 for general arrangement of battery cabinet models.
Figure 6Narrow battery cabinet with top and bottom cable entry locations
Battery Installation
1600
828
FRONT VIEW
566,5
FRONT VIEW
Door Open
825
SIDE VIEW
5563055
55
TOP
VIEW
66055
96,5
250
100
BOTTOM
VIEW
BACK VIEW
21
Figure 7Narrow battery cabinet with top cable entry location
Top
Top
Cable Entry
100x250 mm
(3.9x9.8")
225
(8.8")
Front
96,5
(3.8")
Battery Installation
Front
Front
22
Figure 8Wide battery cabinet with top and bottom cable entry locations
1600
Battery Installation
825
Side ViewSide View
100
603
70
603
100
Front View
1490
Top View
55
630
23
55
55
1321
Bottom View
55
Figure 9Wide battery cabinet with bottom cable entry location
265
152
150
Battery Installation
150
270
270
Bottom View
Front View
24
Figure 10 Wide battery cabinet with fuse or optional circuit breaker locations
Battery Installation
Bottom Cable entry
Top Cable
entry
Adjustable
Fixing Feet
Output
busbar
connections
Battery
Circuit Breaker
BCB
controller board
Fuses
(alternative
to BCB)
25
Figure 11 Large battery cabinet dimensions
Top View
Battery Installation
552
180
116
300660300116
Front
1800
825
Side
55
55
55630
130
1488
270691
660.5660.555
270
Bottom View
26
130
150
567
Figure 12 Large battery cabinet with fuse or optional circuit breaker location s
Battery Installation
Fuses
(alternative
to BCB)
Output
busbar
connections
Battery
Circuit Breaker
BCB
controller board
27
Figure 13 SENXA0NBCN4LCB.eps
Battery Installation
W001
W001
W001
W001
W002
W001
W001
W002
W002
W001
W001
W002
W001W001
W001W001
BCB
SPACE
W002
W001
W001
Tray in Layer 3
Tray in Layer 4
W001W001
W001
W001
W001
W001
W001
W001
W002
W001
W001
W001W001
Tray in Layer 1Tray in Layer 2
W001W001
W001W001
W001
W001
BCB(125/200A)
W102
W101
RED
BLACK
N
V<
P
N.O.
TO UPS
FRONT VIEW
W301
X102-1
X102-2
W302
X101-1
X101-3
X100-2
X100-1
X100-4
X100-3
X102-3
X102-4
Layer 4
BCB Control board
X108-1
TO UPS
X108-3
X108-2
X106-3
X106-2
X106-1
X105-3
X105-2
X105-1
X104-3
X104-2
X104-1
X103-3
X103-2
X103-1
Layer 3
Layer 2
Layer 1
J1
Temp. channels reserved for Batt. cabinet Paralleling
BLUE
RED
GREEN
GREEN
GND
BLUE
OUT
P12
Temp. transport
RED
NOTE:
1. Please refer to BCB BOX user instructions for cable connection.
3. Used for: NPX-100; UH12V140/A; UH12V200/A; UPS12-100; UPS12-140; UPS12-170; UPS12-200.
2. If no internal Control board used, temp. transport cables should be connected
directly to external BCB control board. Meanwhile, the undervoltage release function
for the internal BCB is not needed.
28
Figure 14 SENXA0NBCN4LF
Battery Installation
W002
W001
W001
W001W001
Tray in Layer 3
Tray in Layer 4
W001
W001
W001
W002
W001
W001
W001
W001
W001
W001
W001
W001
Tray in Layer 1Tray in Layer 2
W001
W001
W001
W001
W001
W001
W001
W001
W001
W002
W002
W002
W002
W001
W001
W001
W001
W001
W001
W001
W001
W003
BCB
SPACE
FRONT VIEW
Layer 4
Layer 3
Layer 2
Layer 1
(Anderson connector)
PP120/180-BLACK
W006W005
(Bussmann Fuses)
FWP-120A/200A
W004
TO BCB BOX
TO BCB BOX
GREEN
J1
BLUE
GND
OUT
P12
Temp. transport
RED
(Anderson connector)
PP120/180-RED
29
2. Used for: NPX-100; UH12V140/A; UH12V200/A; UPS12-100; UPS12-140; UPS12-170;
1. When fuses are used for overcurrent protection, the temp.signals shall go
directly to the control board in external BCB BOX.
NOTE:
UPS12-200.
Figure 15 SENXA0NBCN5LCB
Battery Installation
W001
W001
W001
W001
W002
W002
W002
W002
W001
W001
W001
W001
W001
W002
W001
Tray in Layer 3
W001W001
W001
W001
W001
W001
W001
W002
W002
W002
W001
W001
W001
W001
Tray in Layer 2
Tray in Layer 1
W001W001
W001W001
Tray in Layer 5Tray in Layer 4
W001W001
BCB(125/200A)
W001
W001
W101
W001
W001
N.O.
V<
BCB
SPACE
FRONT VIEW
X108-3
X108-2
Layer 4
X106-3
X106-2
X106-1
X105-3
X105-2
X105-1
X104-3
X104-2
X104-1
X103-3
X103-2
X103-1
BLUE
RED
Layer 5
W102
W301
X102-1
X102-2
X101-1
X101-3
X100-2
X100-1
X100-4
X100-3
X102-3
X102-4
BCB Control board
X108-1
RED
BLACK
N
P
GREEN
Temp. channels reserved for Batt. cabinet Paralleling
Layer 3
GREEN
Layer 2
J1
GND
BLUE
OUT
P12
Temp. transport
RED
Layer 1
TO UPS
30
W302
TO UPS
NOTE:
2. If no internal Control board used, temp. transport cables should be connected directly
to external BCB control board. Meanwhile, the undervoltage release function for the
internal BCB is not needed.
1. Please refer to BCB BOX user instructions for cable connection.
Figure 16 SENXA0NBCN5LF
Battery Installation
W001
W001
W001
W001
W002
W002
W002
W002
W001
W001
W001
W001
W001
W002
W001
Tray in Layer 3
W001
W001
W001
W001
W001
W001
W001
W002
W002
W002
W001
W001
W001
W001
Tray in Layer 2
Tray in Layer 1
W001W001
W001
W001
BCB
SPACE
W001
Tray in Layer 5Tray in Layer 4
W001
W001
W001
W001
W001
FRONT VIEW
Layer 5
Layer 4
Layer 3
Layer 2
Layer 1
(Anderson connector)
W005
W003
PP120/180-BLACK
W006
W004
(Bussmann Fuses)
FWP-120A/200A
TO BCB BOX
TO BCB BOX
GREEN
J1
BLUE
GND
OUT
P12
Temp. transport
RED
(Anderson connector)
PP120/180-RED
31
NOTE:
1. When fuses are used for overcurrent protection, the temp.signals shall go directly to the
control board in external BCB BOX.
2. Used for: UH12V100/A; NPX-150; NPL24-12,38-12; S512/38; 12XLB150; P12V570,875; L12V32.
Figure 17 SENXA0NBCWXX3LCB
Battery Installation
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001W001
W001
W001
W001W001
W001W001
W001
W001
W002
W002
W001
W001
W001
W001
Tray in Layer 1
W001
W001
W001
W001
W001
W001
Tray in Layer 3
W001
BCB(125/200A)
W001
TO UPS
W001
N.O.
V<
N
P
W001
W102
W101
RED
W301
BLACK
X102-1
X102-2
W302
X101-1
X101-3
X100-2
X100-1
X100-4
X100-3
X102-3
X102-4
Tray in Layer 2
BCB Control board
X108-1
X108-2
TO UPS
W001
X108-3
X106-3
X106-2
X106-1
X105-3
X105-2
X105-1
X104-3
X104-2
X104-1
X103-3
X103-2
X103-1
RED
BLUE
W001
Temp. channels reserved for Batt. cabinet Paralleling
GREEN
GREEN
W002
W001W001
W002
3. Used for: A412/32 G6.
2. If no internal Control board used, temp. transport cables should be
connected directly to external BCB control board. Meanwhile, the
undervoltage release function for the internal BCB is not needed.
1. Please refer to BCB BOX user instructions for cable connection.
NOTE:
BCB
SPACE
J1
GND
BLUE
OUT
RED
P12
Temp. transport
Layer 3
Tray master
Layer 2
Tray master
FRONT VIEW
Layer 1
Tray master
32
Figure 18 SENXA0NBCWXX3LF
Battery Installation
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
Tray in Layer 1
W001
W001
W001
W001
W001W001
W001
W001
W001W001
W001W001
W002
W002
W001
W001
W001
W001W001
W002
W002
Meanwhile, the undervoltage release function for the internal
BCB is not needed.
3. Used for: A412/32 G6.
2. If no internal Control board used, temp. transport cables
should be connected directly to external BCB control board.
1. Please refer to BCB BOX user instructions for cable connection.
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
Tray in Layer 2
W102
W101
W001
W001
W001
Tray in Layer 3
W001
W001
W001
NOTE:
BCB
SPACE
(Anderson connector)
W003
W005
W004
W006
PP120/180-BLACK
(Bussmann Fuses)
FWP-120A/200A
TO BCB BOX
TO BCB BOX
BLUE
GREEN
RED
J1
GND
OUT
P12
Temp. transport
Layer 3
Tray master
Layer 2
Tray master
FRONT VIEW
Layer 1
Tray master
(Anderson connector)
PP120/180-RED
33
Figure 19 SENXA0NBCWXX4LCB_2x4
Battery Installation
W001
Tray slaveTray master
BCB
W001
W001
W001
W001W001
SPACE
W002
W004
W001
W001
Tray in Layer 3
W001
Tray slave
W004
W003
W002
Tray slaveTray master
W001
Tray in Layer 1
W001
W001
Tray slaveTray master
W001
W001
W001
W001
W001
W001
W003
W004
W003
W001W001
W001
W002
Tray in Layer 4
W001
Tray master
W001W001
BCB(125/200A)
W001
W001
N.O.
V<
BCB
Layer 4
SPACE
W004
Tray master
Layer 3
1. Please refer to BCB BOX user instructions for cable connection.
NOTE:
Tray master
connected directly to external BCB control board. Meanwhile, the
3. Used for: UH12V270/A,310/A,370/A,500/A; UPS12-270,310,370,475;
undervoltage release function for the internal BCB is not needed.
Layer 1
Tray slave
Layer 1
Tray master
2. If no internal Control board used, temp. transport cables should be
Temp. channels reserved for Batt. cabinet Paralleling
BLUE
GREEN
GREEN
W001
W301
RED
BLACK
N
P
X102-1
X102-2
X101-1
X101-3
X100-2
X100-1
X100-4
X100-3
X102-3
X102-4
BCB Control board
X108-1
X108-2
X108-3
TO UPS
W302
TO UPS
34
Figure 20 SENXA0NBCWXX4LCB_4x2
Battery Installation
W001
Tray s laveTray master
W001
W001
Tray in Layer 3
Tray in Layer 4
W002
Tray masterTray slave
W001
W001
W001
W001
W002
BCB
SPACE
W002
W002
W001
W001
W001
W001
W001
W001
W002
Tray in Layer 1
Tray in Layer 2
W003
Tray masterTray slave
Tray s lave
Tray master
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W002
W002
W002
W002
BCB(125/200A)
W101
W102
X106-3
X106-2
X106-1
W301
BLACK
RED
N
V<
P
N.O.
X102-1
X102-2
W302
X101-1
X101-3
X100-2
X100-1
X100-4
X100-3
X102-3
X102-4
TO UPS
BCB Control board
X108-1
TO UPS
X108-3
X108-2
X105-3
X105-2
X105-1
X104-3
X104-2
X104-1
X103-3
X103-2
X103-1
RED
BCB
SPACE
J1
Temp. channels reserved for Batt. cabinet Paralleling
BLUE
RED
P12
GND
OUT
Temp. transport
Layer 4
Tray master
BLUE
GREEN
GREEN
Layer 3
NOTES:
1. Please refer to BCB BOX user instructions for cable connection.
2. If no internal Control board used, temp. transport cables should be connected directly
to external BCB control board. Meanwhile, the undervoltage release function for the internal BCB is not needed.
3. Used for: A412/85 F10.
Layer 1
Layer 2
Tray slave
Tray slave
FRONT VIEW
Layer 1
Layer 2
Tray master
Tray master
Tray master
35
Figure 21 SENXA0NBCWXX4LF_2x4
Battery Installation
W001
W003
W001
Tray in Layer 3
Tray masterTray slave
W001
Tray slave
W001
W001W001
BCB
W001
W001W001
Tray in Layer 1
W002
SPACE
W001
W002
W004
W004
W001W001
Tray masterTray slave
W001
W001
W001
W001
W001
W001
W003
W001W001
W004
W003
W001
W002
W001
BCB
Layer 4
W004
NOTES:
1. Please refer to BCB BOX user instructions for cable connection.
2. If no internal Control board used, temp. transport cables should be connected
directly to external BCB control board. Meanwhile, the undervoltage release
function for the internal BCB is not needed.
3. Used for: UH12V270/A,310/A,370/A,500/A; UPS12-270,310,370,475; A412/50,65 G6;
NPL65-12; NPL78-12; NPL100-12; 1290S.
SPACE
Layer 2
Layer 1
Tray slave
Tray slave
FRONT VIEW
Layer 3
Tray master
Layer 2
Tray master
Layer 1
Tray master
Tray master
Tray in Layer 4
W001
Tray master
W001
W001
W001
Tray in Layer 2
Tray masterTray slave
W001W001
W001
W001
W101
W102
(Anderson connector)
W003
W005
W004
PP120/180-BLACK
W006
(Bussmann Fuses)
FWP-120A/200A
TO BCB BOX
TO BCB BOX
GREEN
J1
BLUE
RED
GND
OUT
P12
Temp. transport
(Anderson connector)
PP120/180-RED
36
Figure 22 SENXA0NBCWXX4LF_4x2
Battery Installation
W001
Tray s laveTray master
W001
W001
Tray in Layer 3
Tray in Layer 4
W002
Tray masterTray slave
W001
W001
W001
W001
W002
BCB
SPACE
W002
W002
W001
W001
W001
W001
W001
W001
W002
Tray in Layer 1
Tray masterTray slave
Tray s lave
Tray in Layer 2
Tray master
W001
W003
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W001
W002
W002
W002
W002
W005
W003
W101
W102
(Anderson connector)
PP120/180-BLACK
W006
W004
(Anderson connector)
PP120/180-RED
(Bussmann Fuses)
FWP-120A/200A
TO BCB BOX
TO BCB BOX
37
GREEN
NOTES:
1. Please refer to BCB BOX user instructions for cable connection.
2. If no internal Control board used, temp. transport cables should be connected
directly to external BCB control board. Meanwhile, the undervoltage release
function for the internal BCB is not needed.
3. Used for: A412/85 F10.
BCB
SPACE
Layer 2
Layer 1
Tray slave
Tray slave
J1
BLUE
GND
RED
OUT
P12
Temp. transport
Layer 4
Tray master
Layer 3
Layer 2
Tray master
Tray master
FRONT VIEW
Layer 1
Tray master
2.4Battery Power Cables
2.4.1Connection Principles
The following notes, in conjunction with the diagrams, illustrate the broad principles to be followed
when fitting and connecting the majority of battery installations.
2.4.2Fitting the Batteries
1. In general, at least 10mm (3/8") must be left unobstructed on all vertical sides of the battery
blocks to permit free air movement around the cells.
2. Clearance should be allowed between the top of the cells and the underside of the shelf above (this
is necessary for monitoring and servicing the cells).
3. When installing the batteries on racks always work from the bottom shelf upwards to prevent
raising the centre of gravity.
2.4.3Connecting the Battery
1. When the battery cabinet is installed on a raised floor the battery power cables and optional
circuit breaker control cables can be routed to the UPS cabinet via the floor of the cabinet. If the
UPS and battery cabinet are located adjacent to each other and located on a solid floor these
cables can be passed between the cabinets via the lifting apertures located in the lower sides of
the cabinets.
2. In general it is recommended that the inter-connecting cables be fitted to the batteries within
their particular level before fitting the inter-level connecting cables, followed finally by the cables
to the circuit breaker.
3. An insulating shroud should be fitted to each terminal after its connection has been made.
4. When connecting the cables between the battery string ends to the optional circuit breaker always
connect the circuit breaker end of the cable first.
Battery Installation
2.4.4Battery Room Design
Whatever the type of mounting system selected, the following conditions should be noted:
• Cell Layout—1
Whichever battery mounting system is used, the batteries should be arranged to prevent the pos-
sibility of simultaneous contact with two exposed live parts having a potential greater an 150V.
Where this is not possible, insulated terminal shields must be installed and insulated cables must
be used for connections.
• Service Platform—2
The service platform (or duckboard) must be slip-proof, insulated from the floor and at least one
metre (39 in.) wide.
• Connections—3
All connections must be as short as possible.
• Battery Protection Fuses/Circuit Breaker—4
The battery circuit breaker is generally installed at the front of the battery room. See 2.5 - Bat-tery Control for details on connecting the circuit breaker box available for the Liebert NX.
Figure 23 Battery room design
4
1
3
2
38
2.5Battery Control
The battery circuit breaker is controlled by the battery circuit breaker controller board, which is
located within the battery cabinet or adjacent to the battery circuit breaker when the batteries are
rack-mounted. This board controls the circuit breaker's undervolt release coil and also provides a path
for the circuit breaker auxiliary contacts to signal the circuit breaker status back to the UPS control
logic. Refer to Figure 25. All connections between the controller board and the UPS unit are made
via auxiliary terminal Block X3 BCB of the Monitor Board, which is located at the rear of the door in
the UPS Cabinet (refer to 1.8.3 - External Circuit-Breaker Interface).
Battery temperature sensor cables are connected between UPS auxiliary terminal block X3 BCB, the
Battery Circuit Breaker controller board and the battery as shown in Figures 25 and 26.
Battery Installation
Cables connected to X3 BCB must contain a protective earth wire or a shield, be segregated from
power circuits, double insulated and of a typical 0.5 to 1mm
between 25 and 50 meters respectively. The shield should be connected to the protective earth of the
battery cabinet or battery breaker, not at the UPS
CAUTION
!
UPS containing an internal automatic battery contactor do not require BCB board, nor
undervoltage control of the BCB.
In this case, direct wiring to the NX Monitor Board is required:
• the auxiliary NO contact of the battery circuit breaker is wired directly to the NX monitor
board terminal X3 BCB: 2-3.
• “On-Line” X3 BCB terminals 4-3 of the NX monitor board are linked.
• Any temperature sensor is wired directly to the NX monitor board terminal X7:
2(+12V),3(signal),4(GND).
For details, refer to 1.7 - Control Cables and Communication
The above applies to:
• 30 to 40kVA models with internal battery
• - any model with the Battery Start option
• The commissioning engineer must program the UPS accordingly (e.g., enable or disable battery temperature compensation, enable internal battery contactor).
2
cross-section area for maximum runs
39
2.6Battery Circuit Breaker Box
The box contains a battery isolating circuit breaker and the circuit breaker controller board as also
mounted in the battery cabinet.
A range of battery circuit breaker boxes is available for use in installations where the battery is not
installed in the battery cabinet, in which case the appropriate battery box is fitted as close as possible
to the battery and connected to the UPS equipment as illustrated in Figure 25.
The battery circuit breaker box, used with the circuit breaker controller board, is required to protect
the battery from deep discharging and overcurrents. It also provides electrical isolation between the
UPS and the battery, permitting technical service personnel to reduce the risks involved in maintenance work to a minimum. Inside the box are connection bars for power cables arriving from the UPS
and from the battery.
NOTE
The control cables from the UPS unit to the controller board must be made using a 5-core
shielded cable located in a separate conduit to that containing the battery power cables.
The control signal cable is connected to the circuit breaker controller board through the terminal
board.
The cable shield must be earthed to prevent induced noise affecting the control operation, and a separate safety earth must be connected between the UPS unit and circuit breaker box.
The configurations in Table 9 are available, depending on the UPS power rating.
Table 9UPS-circuit breaker configurations
Dimensions
UPS
30 to 40 kVA
60 to 80 kVA200A 4p
100 to 120 kVA25 (55)400A 4p
140 to 160kVA825x530x195
200kVA32 (71)500A 4p
Listed weights do not include packaging.
HxWxD, mm (in)
558x378x180
(22x14.9x7)
(32.4x21x7.7)
Weight
kg (lb)Circuit Breaker
21.5 (47.4)
30 (66)400A 4p
125A 4p
Battery Installation
The BCB box contains a battery isolating circuit breaker and a circuit breaker controller board and
offers the following features:
• Short-circuit and End Of Discharge protection—The circuit-breaker (or internal UPS battery contactor when fitted) automatically opens when the EOD voltage is reached
• UPS Emergency Stop compatibility—The circuit-breaker (or internal UPS battery contactor when
fitted) opens when the emergency stop button is pressed on the UPS front panel.
NOTE
30 to 40kVA UPS models fitted with internal battery and any UPS models fitted with a Battery
Start kit contain an internal UPS battery contactor for automatic connection and
disconnection of the batteries and the battery circuit breaker undervoltage coil is not used.
Refer to 2.5 - Battery Control for details
40
Figure 24 Battery circuit breaker box—30-120kVA and 140-200kVA
6
Battery Installation
9
9
4
2
1
6
3
7
140-200kVA
Circuit Breaker Box
30-120kVA
Circuit Breaker Box
8
10
5
Table 10Battery circuit breaker box legend
Key #
1Battery connections, positive and negative
2Connectionsfrom UPS, positive and negative
3Battery circuit breaker controller board
4Battery circuit breaker
5Plate for cabling holes (User to size and cut holes for the cables to be used)
6Wall mounting holes
7Earth bar
8Insulating cover
9Top plate
10Hinged door
Component
Standard cable entry is from bottom side. The baseplate can be rotated to permit top cable entry.
41
Figure 25 Battery circuit breaker box connection
+
N
-
Temp
Sensor
TMP-2
Battery Installation
NC
12V
OUT
GND
W3
UPS
UHW241U2
J10
Battery
X7
OL
GND
FB
DRV
W2
BCB
+
UV
220VDC
-
Auxiliary
Contactor
+12V
BAT-T
GND
W3
UPS +
UPS -
Battery
+
Black
Red
Battery
-
Black
Red
X100
OUT-P
OUT-N
AUX1
AUX2
UHW241C2
X101
X108X102
+12V
BAT-T
GND2
USE
GND1
AUX
DRV
NOTES
1. Cable W3 supplied with temperature sensor (5m) and with BCB Box (30m)
2. Cable W2 supplied with BCB Box (30m)
3. X102 labels are 1(DRV), 2(AUX), 3(GND1), 4(USE) - refer to Table 11 for full X102 label
descriptions
4. X101 - HAZARDOUS VOLTAGE - do not connect to battery bus before authorised by the
commissioning engineer
5. X103-X106 are for connecting temperature sensors from multiple battery cabinets.
X103
X104
X105
X106
42
Battery Installation
Table 11Battery control label description (X102)
BCBB
X-102
Ref Label
1 DRV
2 IN (AUX)FB (IN)
4 USE
3 GND1GNDGND1GND1 to GND on U2 board
5 (1) +12V
6 (3) 0VGND2GND2GND2 to GND on U2 board
7 (2) OutOUT
1. Cables connected to X3 BCB must be segregated from power circuits, double insulated and of a typical 0.5 to 1mm2 cross
section area for maximum runs between 25 and 50 meters respectively.
2. Battery temperature sensing cables must be less than 10 m long.
3. 30 and 40kVA UPS models fitted with internal battery and any UPS models fitted with Battery Start kit contain an internal UPS
battery contactor for automatic connection and disconnection of the batteries and the battery circuit breaker undervoltage coil is
not used. Refer to 2.5 - Battery Control for details.
BCB-X3
on U2 Monitor
board
X7
on U2 Monitor
board
Monitor Bd
Reference
LabelDescriptionSignal status
DRV
OL =
On Line
P12
Battery circuit breaker tripping
control signal from UPS
Bat CB auxiliary status contact
(Open contact = CB open)
Bat CB Board status signal
(GND = OV from BCB Bd)
+12V Power supply from
Monitor Bd to Temp Monitoring
Probe & Buffer
Buffered Bat temp Probe signal
from BCB Bd to Monitor Bd
Normal: H level voltage, BCB can close
Abnormal: L level voltage, BCB trips
Normal: OV when BCB is closed.
Abnormal: open when BCB is open
Normal: 0V, the BCB Board is in use.
Abnormal:. open, the BCB Board is not
in use.
Power available: 3W.
CAUTION
!
Leave terminals open if the corresponding facility is not used. The commissioning engineer
must program the UPS accordingly (e.g., disable battery temperature compensation, enable
internal battery contactor)
2.6.1Battery Temperature Sensor—Optional
The optional external battery temperature sensor kit, supplied separately from the battery circuit
breaker, contains one probe and one temperature transport board as illustrated in Figure 26. It is
connected to the UPS Monitor Board (either directly or in case of multiple sensors, through the battery circuit breaker board - see Figures 26 and 27).
Figure 26 Single temperature sensor and monitor board—U2
Temperature
Sensor
+
IN
-
NC
12V
OUT
GND
TMP-2
Name: W2 L = 30m
X7
Monitor
Board
– U2
-12V
BAT-T
GND
UPS
Cable W2 is packed with the temperature sensor.
43
Figure 27 Multiple temperature sensors, battery circuit br eaker box and UPS module
Type: W3 L = 5mType: W3 L = 30m
Temperature
Sensor
Battery Installation
+
IN
TMP-2
Temperature
+
IN
-
Temperature
+
IN
-
Temperature
Sensor
TMP-2
Sensor
TMP-2
Sensor
NC
12V
OUT
GND
NC
12V
OUT
GND
NC
12V
OUT
GND
X103
X104
X105
BCB Control
Board – C2
+12V
OUT
GND
X108
X7
Monitor
Board
– U2
-12V
BAT-T
GND
UPS
X106
BCB Box
IN
+
TMP-2
NC
12V
OUT
GND
Cable W3 (L=5m) is packed with the temperature sensor.
Cable W3 (L=30m) is packed with the BCB box.
NOTE:
1. Each probe consists one OT6-4 terminal and one precision temperature sensor that is
sealed in the OT6-4's terminal. The whole probe is supplied as one cable.
2. The type of temperature transport board illustrated in Figure 27 is TMP-2.
3. The signal cables in the Figure 27 must be shielded and double insulated.
4. The temperature monitoring cable must be less than 10m while the signal transmission
distance of the transport board must be less than 100m.
44
3.0UPS MULTI-MODULE INSTALLATION
3.1General
The installation of a multi-module UPS configuration must follow the installation procedure for a single UPS module with the additional requirements detailed in this chapter.
In addition to the local EPO push button on the front panel of the UPS module (that stops operation of
that module), the UPS supports also a remote emergency stop to permit simultaneous multi-module
shutdown.
NOTES
1. The remote emergency power off switch must be voltage-free and Normally Open or
Normally Closed.
2. The open voltage supplied is 12VDC, < 20mA
3. This external emergency stop may be supplied with a second set of contacts that can be used
to trip incoming mains or bypass supply circuit breakers supplied by others and fitted with
remote trip units.
4. Normally Closed EPO - X2: 1&2, these terminals are supplied factory-linked on the monitor
board.
Figure 28 Emergency power off connections
UPS Multi-Module Installation
EPO
EPO
X2:3
X2:4
UPS1
X2:1
X2:2
UPS1
X2:3
X2:4
Monitor Board
X2:1
X2:2
Moni tor Board
UPS2
Moni tor Board
UPS2
Moni tor Board
45
UPS Multi-Module Installation
3.2Paralleled UPS Modules
The basic installation procedure of a parallel system comprising two or more UPS modules is the
same as that of single module system. The following sections only introduce the installation procedures specific to the parallel system.
3.2.1Cabinet Installation
Place the UPS modules side by side and interconnect as shown in Figure 29. The distribution panel
(external bypass cabinet) is optional but recommended for ease of maintenance and system testing.
Figure 29 Typical 1+N system block diagram with common input supply, with separate batteries and
optional output / bypass distribution panel
Supplied
by Ot he r s
Input M a i ns
Supply L1, L2, L3, N
UPS1
Charger
Input M ai ns
Supply L1, L2, L3, N
Q1
Q1
UPS2
Rectifier
Rectifier
Charger
Inverter
Inverter
Q2
Q3
Q5
Q5
L1 , L2, L3 , NL1, L2, L3, N
Q1EXTQ2EXT
Q2
Q3
QUPS
QBYP
Dist ribution Cabinet
To Load
NOTE
Internal maintenance bypass switch Q3 must be removed when the load exceeds the capacity of
one UPS module.
46
Figure 30 Dry contact s, multiple UPS modules with distribution panel
Input Distribution
UPS Multi-Module Installation
UPS 1
M3 Board
X3
Ext. Maint. Ext. Out
QUPS
UPS 2
M3 Board
X3
Ext. Maint. Ext. Out
Q1ExtQ2ExtQnExt
UPS N
M3 Board
X3
Ext. Maint. Ext. Out
QByp
To Load
3.2.2External Protective Devices
Refer to the instructions in 1.0 - Single Module UPS Installation.
3.2.3Power Cables
The wiring of power cables is similar to that of single module system. The Bypass and the Main input
sources must be referenced to the same neutral potential and input earth leakage monitoring devices,
if installed, must be located upstream of the common neutral sinking point. Refer to the instructions
in 1.0 - Single Module UPS Installation.
NOTE
The length and specification of power cables including the bypass input cables and UPS output
cables should be the same. This facilitates load sharing when operating in bypass mode.
47
3.2.4Control Cables
Intermodule Control
Shielded and double insulated control cables available in lengths of up to 30 meters must be interconnected in a ring configuration between UPS modules as shown below. The parallel control board is
mounted on the top, behind protective cover of each UPS module (refer to Figure 44). The ring configuration ensures high reliability of the control (refer to Figure 31).
Figure 31 Connection of 1+N system parallel control cables
UPS Multi-Module Installation
123456
Paralle l Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4P1
P3
Parallel Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4P1
P3
3.3Hot-Standby UPS Modules
3.3.1Cabinet Installation
Place the UPS modules side by side and interconnect as shown below.
The hot standby mode comprises two series-connected UPS modules of the same rating. One module
is designated as the hot standby master (downstream), and the other module is designated as the hot
standby slave (upstream). Their roles are determined by power connection and configuration software. In normal operation, both slave and master operate in normal mode and the output from one
upstream (slave) UPS feeds the bypass input to the other (downstream, master) UPS. The output of
the downstream (master) UPS is connected to the critical load and is always synchronised to the output of the upstream (slave) UPS. If the inverter of the UPS connected to the load fails, the inverter of
the upstream (slave) UPS supplies the load through the downstream (master) UPS bypass circuit.
The system can be programmed to cycle the downstream (master) UPS between normal mode and
bypass mode so that both UPS units are equally exercised.
Paralle l Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4P1
P3
UPS
Parallel Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4P1
P3
Parallel Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4P1
P3
Paralle l Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4P1
P3
NOTE
If it is a hot-standby system, the master must be turned on first.
3.3.2External Protective Devices
Refer to the instructions in 1.0 - Single Module UPS Installation.
48
UPS Multi-Module Installation
3.3.3Power Cables
The wiring of power cables is similar to that of single module system except that the output of the
upstream UPS is fed into the bypass input of the downstream UPS, and the load is fed by the downstream UPS through its inverter or bypass. The bypass and the main input sources must be referenced to the same neutral potential and input earth leakage monitoring devices, if installed, must be
located upstream of the common neutral sinking point. Refer to the instructions in 1.0 - Single Mod-ule UPS Installation.
No control wires other than those specified for the single module configuration are required.
Figure 32 Hot standby configuration
Input Distribution
UpstreamDownstream
Mains L1,
L2, L3, N
Bypass L1,
L2, L3, N
Mains L1,
L2, L3, N
Bypass L1,
L2, L3, N
UPS1
Charger
Q1
Rectifier
Inverter
Q2
Q5
UPS1 O ut put
Q3
Q1
UPS2
Rectifier
Charger
Inverter
Q2
Q3
Q5
L1, L2, L3, NL1, L2, L3, N
49
UPS Multi-Module Installation
3.4Dual Bus System
3.4.1Cabinet Installation
The Dual Bus System consists of two independent UPS configurations each consisting of one or more
UPS modules. Dual Bus Systems are high availability configurations suitable for loads with multiple
input terminals. For single input loads an optional Static Transfer Switch may be added and the standard Load Bus Synchroniser activated. Depending on the configuration, follow the appropriate installation instructions for each system.
Place the UPS modules side by side and interconnect as shown below.
The objective of the Dual-bus Synchronizer (DBS) is to keep the output of two independent UPS systems (or parallel systems) in synchronization. One system is designated as the master; the other is
designated as the slave. The operating modes covered comprise master and or slave operating
inverter or bypass mode.
Figure 33 Typical dual bus system configuration with static transfer switch and Load Bus Synch
Bypass Supply
Bypass Supply
Input
Rectifier
UPS1
CHARGER
Q5
UPS1
CHARGER
Input
Rectifier
Q1
Q5
RECTIFER
INVERTER
Q2
Q3
INTERMODULE
CONTROL CABLE
3.4.2External Protective Devices
Q1
RECTIFER
INVERTER
UPS1
CHARGER
Input
Rectifier
Q1
Q5
RECTIFER
INVERTER
Q2
Q3
Input
Rectifier
Q1
UPS1
RECTIFER
CHARGER
Q2
Q3
LBS
Q5
INVERTER
Q2
Q3
INTERMODULE
CONTROL CABLE
STS
Load
Refer to the instructions supplied in 1.0 - Single Module UPS Installation.
3.4.3Power Cables
The wiring of power cables is similar to that of single module system. The Bypass and the Main input
sources must be referenced to the same neutral potential and input earth leakage monitoring devices,
if installed, must be located upstream of the common neutral sinking point. Refer to the instructions
in 1.0 - Single Module UPS Installation
50
3.4.4Control Wires
For Liebert NX to NX dual bus configuration, interconnect the optional DBS cable between any DBS
ports of two parallel systems as illustrated in Figure 34.
Figure 34 Connections of a typical dual bus system utilising Load Bus Synch
UPS Multi-Module Installation
Para llel Board
X3
P5
X2-2X2-1
P2
X1-1X1-2
P3
8
Parallel System IParallel System II
X4
P4P1
UPS
Para llel Board
X3
P5
X4
X2-2X2-1
P2
X1-1X1-2
P4P1
P3
A
DBS Cable
Parallel Board
X3
P5
X2-2X2-1
P2
X1-1X1-2
P3
8
UPS
X4
P4P1
Parallel Board
X3
P5
X4
X2-2X2-1
P2
X1-1X1-2
P4P1
P3
B
NOTE
Example shown with ring control cables (“8”) for DSB applied to two 1+1 paralleled systems.
3.4.5Extended Dual Bus Synchronization Option (DBS Interface Box)
For Liebert NX to non- NX (whether another Liebert UPS range or not) dual bus configuration, one
DBS interface box shall be mounted on the non- Liebert NX UPS and one on the Liebert NX UPS. In
this situation, the other UPS system is always treated as a master and the following conditions are
covered:
• Master and slave are both on inverter
• Master on bypass, slave on inverter
NOTE
Extended DBS interface box is also used for extending DBS cable length up to 150 metres for
DBS configuration between two groups of NX UPS systems.
51
4.0EXTERNAL OPTIONAL CABINETS
4.1External Maintenance Bypass Cabinets
The bypass cabinet enables maintenance operations and repairs to be performed in full isolation
while also allowing the disabling of each UPS without affecting the ordinary operation of the system
(depending on the redundancy level).
The optional maintenance bypass cabinet must be used in all configurations where one internal maintenance bypass switch is insufficient to supply the full system load.
Each kVA rating has maintenance bypass cabinets sufficient to supply the full system load up to six
units in parallel power operation.
4.2Interlock with UPS Module
Interlock the External Maintenance Bypass Switch with the operation of the UPS module(s) prevents
backfeed of the External Bypass AC power into the Inverter if an incorrect switching sequence is
used. A volt-free auxiliary status contact from external bypass switch QF3 is connected to UPS terminal X3 (MBC interface) of the parallel control board (M3).
Figure 35 External maintenance bypass cabinet with separate bypass input
400V, 50Hz
4W
4P
External Optional Cabinets
400V, 50Hz
3 or 4W
4P
S
Supplied
by Other s
400V, 50Hz
4W
Q1
UPS1
Q1
UPS2
Q1
CB
CB
X3
X1
X3
X1
Q2
Q2
Q2
Q3
Q3
Q3
Q5
Q5
Q5
4P
4P
4P
UPS3
CB
X3
X1
52
External Optional Cabinets
EXT-Maint X3-1&2 on UPS Parallel Board M3 (leave open if no external bypass switch is used). Provides external maintenance bypass interlock protection for the UPS. Short circuit means external
bypass closed.
EXT-Out (X3-3&4) on UPS Parallel Board (leave shorted if no external output switch is used). Provides external output interlock protection for paralleled UPS modules. Short circuit means external
output switch closed.
4.3Isolation Tr ansformer Option
Isolation transformers are required in cases requiring galvanic isolation between the input supply
mains and the UPS.
These options are housed in cabinets and they are available for every range of UPS.
These optional cabinets provide the Top Cable entry function.
NOTE
Terminals and cabling for the battery connection is not a part of the MBP or TC cabinet.
Hazardous mains and / or battery voltage present behind covers.
No user-serviceable parts are located behind covers that require a tool for their removal. Only
qualified service personnel are authorised to remove such covers.
6.1Introduction
The Liebert NXa Uninterruptible Power System is connected between the Mains AC input source and
the critical load to provide uninterruptible power to the latter. The power from the UPS is free from
voltage and frequency variations and from disturbances experienced at the Mains AC input supply.
This is achieved through high frequency double conversion power pulse width modulation (PWM)
associated with full digital signal processing control (DSP).
As shown in Figure 63, the AC input mains source is supplied at Q1 and converted into a DC source.
This DC source feeds a DC/DC Bidirectional Battery Converter (that ensures the battery to remain
charged at all times) and at the same time feeds the Inverter that converts the DC source into a clean
and input independent AC source. The battery powers the load through the bidirectional battery converter and through the inverter in case of an AC input mains power failure. In case of Inverter
unavailability or excessive overload, the load may also be powered from an external AC Bypass source
through input isolator Q2 and the static bypass. Besides this, if maintenance or repair of the UPS is
necessary, the UPS can support the load through the internal and manually controlled maintenance
bypass isolator Q3. With the exception of the maintenance bypass isolator, all the isolators shown are
closed during normal UPS operation.
Operation
Figure 63 Single unit block diagram with split-bypass input
Bypass
Mains
Supply
Input
Mains
Supply
N
Input
Isolator
Q1
Mai nten ance Byp ass I so lator Q 3
Bypass Isolator Q2
DC Bus
Rectifier
Input
Static
Switch
Inverter
CB
Battery
Converter
Battery
Circuit
Breaker
Static Switch
1
UPS Modul e
Bypass Side
Output
Isolator
Q5
UPS
Output
75
2
Battery
6.1.1Split-Bypass Input
Figure 63 illustrates the Liebert NX UPS in what is known as the split-bypass configuration
wherein a separate power switch to a dedicated bypass power source that also feeds the maintenance
bypass line connects the static bypass line. Where a separate power source is not available, the bypass
and rectifier input supply connections are linked.
6.1.2Static Transfer Switch
The circuit blocks labeled Static Switch in Figure 63 contain electronically controlled switching circuits that enable the critical load to be connected to either the inverter output or to a bypass power
source via the static bypass line. During normal system operation the load is connected to the
inverter; but in the event of a UPS overload or inverter failure, the load is automatically transferred
to the static bypass line.
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the
static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass
supply must be fully synchronized during normal operating conditions. This is achieved through the
inverter control electronics, which make the inverter frequency track that of the static bypass supply,
provided that the bypass remains within an acceptable frequency window.
A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the
critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine
maintenance.
NOTE
When the UPS is operating in bypass mode or on maintenance bypass, the connected
equipment is not protected from power failures or surges and sags.
Operation
6.1.3Battery Circuit Breaker
Any external battery is connected to UPS through a circuit breaker fitted inside the battery cabinet –
or located adjacent to the batteries where a battery cabinet is not used. This circuit breaker is closed
manually, but it contains an undervoltage release coil, which enables it to be tripped from the UPS
control electronics following certain detected faults. It also has a magnetic trip facility for overload
protection. The undervoltage release coil control is replaced by a battery contactor located inside the
UPS fitted with either internal batteries or with battery start option or both
6.1.4Battery Temperature Compensation
For 30-40kVA UPS with internal batteries, a standard temperature probe is installed to measure the
internal battery temperature to optimize battery management. The measured temperature can be
displayed from the UPS front panel.
For UPS with external batteries, an optional battery temperature interface equally optimises the
external battery management by connecting up to four external temperature sensors from the battery
cabinet(s) to a control unit inside the UPS.
For details, refer to Figure 27.)
6.1.5Redundant Control Power Supply Board
The UPS is equipped with two identical and fully redundant control power supply boards. Each of
them takes inputs from the AC and DC sources. When one of the sources or even if one of the control
power boards fails, the UPS system can still operate normally. This feature further enhances the reliability of the system.
6.1.6Socket Outlet
One single-phase Shuko-type universal outlet of 3A current handling capability provides nominal
UPS output voltage of up to 3A current capacity for the ease of testing, commissioning & servicing of
the UPS.
76
6.2Multi Module UPS—1+N
Multi-module UPS are formed by several “single unit” UPS modules to constitute “1+N”system where
groups of one or more, up to six, single units operate together for the purpose of providing additional
power or reliability or both. The load is equally shared between any paralleled UPS.
Figure 64 1+N multi-module UPS with external maintenance bypass switch
SUPPLIED BY OTHERS
INPUT MAINS SUPPLY
L1, L2, L3, N
BYPASS MAINS SUPPLY
L1, L2, L3, N
INPUT MAINS SUPPLY
L1, L2, L3, N
BYPASS MAINS SUPPLY
L1, L2, L3, N
INPUT MAINS SUPPLY
L1, L2, L3, N
Operation
Qin UPS3 Qin UPS2 Qin UPS1
Qin Ext Byp
L1, L2, L3, N
Q1
Q5
RECTIFER
INVERTER
Qout
BYP
Q2
Q3
UPS1
CHARGER
L1, L2, L3, N
Q1
RECTIFER
INVERTER
Q5
Qout UPS1
Qout all UPS
Q1
UPS2
RECTIFER
CHARGER
Q2
Q3
L1, L2, L3, N
INVERTER
Q2
Q3
Q5
Qout UPS2
UPS3
CHARGER
UPS3 OUTPUT UPS2 OUTPUT UPS1 OUTPUT
L1, L2, L3, N
Qout UPS3
Distribution Cabinet
Further, single unit or 1+N groups may be configured as “distributed redundant” systems with independent outputs that nevertheless are synchronised through a Load Bus Synchroniser (LBS) so that
critical loads can be seamlessly transferred from one system to another. See 6.3 - Modes of Opera-tion for more information.
6.2.1Features of NX Multi-Module UPS Configurations
1. The hardware and firmware of single module UPS units is completely compatible with the
requirements of a multi-module system. Multi-module configuration is achieved merely through
settings in configuration software and control cables.
2. Parallel control cables are connected in a ring, providing both performance and redundancy.
Dual-bus control cables are connected between any two UPS modules of each bus. The intelligent
paralleling logic provides the user with maximum flexibility. For example, shutting down or
starting up UPS modules in a parallel system can be done in any sequence. Transfers between
Normal and Bypass modes of operation are synchronised and self –recovering e.g. following
overloads and their clearance.
3. The total load of the multi-module system can be queried from each module’s LCD.
77
6.2.2Requirements for Paralleling of UPS Modules
A group of paralleled modules behave as if it were one large UPS with the advantage of presenting
higher reliability. In order to assure that all modules are equally utilised and to comply with relevant
wiring rules, the following requirements apply:
1. All UPS modules must be of the same rating and must be connected to the same bypass source.
2. The bypass and the main input sources must be referenced to the same neutral potential.
3. Any RCD, Residual Current monitoring device, if installed, must be of an appropriate setting and
located upstream of the common neutral bonding point. Alternatively, the device must monitor
the combined 4-wire rectifier and split-bypass input currents of the system. Refer to the High Leakage CurrentWarning on page 1.
4. The outputs of all UPS modules must be connected to a common output bus.
NOTE
Optional isolation transformers are available for applications where sources do not share the
same neutral reference or where the neutral is not available.
5. Passive bypass current equalising chokes are available as an option in systems comprising more
than three parallel redundant UPS modules (or two or more parallel capacity UPS modules).
6.3Modes of Operation
The NX UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these
modes:
•Normal Mode
• Battery Mode (Stored Energy Mode)
• Auto-Restart Mode
• Bypass Mode
• Maintenance Mode (Manual Bypass)
• ECO Mode
• Parallel Redundancy Mode
• Hot-Standby Mode
• Frequency Converter Mode
Operation
6.3.1Normal Mode
The UPS inverter continuously supplies the critical AC load. The rectifier/charger derives power from
the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or
BOOST charging its associated backup battery.
6.3.2Battery Mode (Stored Energy Mode)
Upon failure of the AC mains input power; the inverter, which obtains power from the battery, supplies the critical AC load. There is no interruption in power to the critical load upon failure or restoration of the AC mains input power after which the “Normal Mode” operation will continue without the
necessity of user intervention.
6.3.3Auto-Restart Mode
The battery may become exhausted following an extended AC mains failure. The inverter shuts down
when the battery reaches the End Of Discharge voltage (EOD). The UPS may be programmed to
“Auto Recovery after EOD” after a delay time. This mode and any delay time are programmed by the
commissioning engineer.
78
6.3.4Bypass Mode
If the inverter overload capacity is exceeded, or if the inverter becomes unavailable for any reason,
the static transfer switch will perform a transfer of the load from the inverter to the bypass source,
with no interruption in power to the critical AC load. Should the inverter be asynchronous with the
bypass, the static switch will perform a transfer of the load from the inverter to the bypass with interruption in power to critical AC load. This is to avoid paralleling of unsynchronised AC sources. This
interruption is programmable but typically set to be less than 3/4 of an electrical cycle, e.g., less than
15ms (50Hz) or less than 12.5ms (60Hz).
6.3.5Maintenance Mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS
becomes unavailable e.g. during a maintenance procedure. This manual bypass switch is fitted in all
UPS modules and rated for full load of one module.
6.3.6ECO Mode (Single UPS Only)
If ECO mode is selected, the double-conversion UPS operation is inhibited at most times for the purpose of saving energy. In this mode of operation, not unlike UPS of line-interactive or stand-by technology, the bypass is the preferred source and only when the voltage and / or frequency of the bypass
supply are beyond pre-defined and adjustable limits the critical AC load is transferred to the inverter.
This transfer takes place with an interruption of less than 3/4 of an electrical cycle, e.g., less than
15ms (50Hz) or less than 12.5ms (60Hz).
6.3.7Parallel Redundancy Mode (System Expansion)
Operation
For higher capacity or higher reliability or both, the outputs of up to six UPS modules can programmed for directly paralleling while a built-in parallel controller in each UPS ensures automatic
load sharing.
6.3.8Hot-Standby Mode
This is an alternative 1+1 redundancy application that ensures higher availability or better usage
control or both. Two UPS are connected in Hot Stand By mode as follows: UPS 1connects to the critical load, and UPS 2 connects to the bypass of UPS 1. The remaining AC inputs are connected to the
incoming AC mains supply. UPS 1 synchronises to the output of the UPS 2 ensuring uninterrupted
load transfer from UPS 1 to UPS 2 or vice versa. This ensures that any specified load is supplied by a
UPS while still providing a bypass path to cater for overloads. Further, the system can also be programmed to reverse UPS1 between Normal and Bypass Modes so that each UPS is equally utilised.
This interval is programmable from 1 to 4,320 hours (180 days).
6.3.9Frequency Converter Mode
The NX UPS can be programmed into frequency converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 40Hz to 70Hz. In this mode the static bypass operation is disabled, and the battery becomes optional depending on any requirement to operate in
battery mode (stored energy mode).
6.3.10 Source Share Mode (Co-Generation)
NXa modules have the capability of fully supporting their critical load while limiting the amount of
power taken from the incoming AC mains supply. Any balance of power required is supplied by the
UPS battery. This feature is useful e.g. in applications where peak-hour tariffs apply or where a generator smaller than needed feeds the UPS during mains outages. The Source Share Mode is user-activated and the ratio of the main AC input power is programmable from 20% to 100% of the rated UPS
power.
79
Operation
6.4Battery Management—Set During Commissioning
6.4.1Normal Function
• Constant charging current—Current can be set up to limit charging power.
• Constant boost voltage (if applicable)—Voltage of boost charging can be set as required by the
type of battery.
For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not
exceed 2.4V / cell.
• Float Charge—Voltage of float charging can be set as required by the type of battery.
For VRLA, float charge voltage should be between 2.2V to 2.3V.
• Float Charge Temperature Compensation (optional)—A coefficient of temperature compensation can be as required by the type of battery.
• End of discharge protection (EOD)—If the battery voltage is lower than the EOD, the battery
converter will shut down and the battery is isolated to avoid further battery discharge. EOD is
adjustable from 1.6V to 1.75V per cell (VRLA) or 0.9 to 1.1 V per cell (NiCd).
• Battery Low Warning Time—Adjustable between 3 and 60 minutes. The default is 5 minutes.
6.4.2Advanced Functions (Software Settings Performed by the Commissioning Engineer)
Battery Self-Test and Self-Service
At periodic intervals 20% of the rated capacity of the battery will be discharged automatically at a
rate equal to 15% (kW) of the rated UPS (kVA) capacity. During discharge the rectifier provides the
balance necessary to feed the load. The minimum amount of load must exceed 20% of the nominal rating of the UPS module. If the load is less than 20%, auto-discharge cannot be executed. The periodic
interval can be set from 30 to 360 days. The periodic testing can also be inhibited.
• Conditions—Battery at float charge for at least 5 hours, load 20~100% of rated UPS capacity
• Trigger—Manually through the command of Battery Maintenance Test in LCD panel or automatically
• Battery Self-Test Interval—30-360 days (default setting is 60 days)
6.5Battery Protection (settings by commissioning engineer)
Battery Undervoltage Pre-warning
The battery undervoltage pre-warning occurs before the end of discharge. After this pre-warning, the
battery should have the capacity for 3 remaining minutes discharging with full load. The time is user
configured from 3 to 60 minutes.
Battery End of Discharging (EOD) Protection
If the battery voltage is lower than the EOD, the battery converter will be shut down. EOD is adjustable from 1.6V to 1.75V per VRLA cell (or 1.0 to 1.1 V per NiCd cell).
Battery Contactor Fault Warning
If the battery contactor monitor status is different from the drive signal, this warning will occur.
Battery Disconnect Devices
For 30- 40kVA models with internal batteries and for any model fitted with a Battery Start kit, the
UPS contains an internal contactor for automatic connection and disconnection of the batteries. The
relevant features are:
• Low battery safety cutoff
• Connect/disconnect status displayed via LCD
• Overcurrent protection
• Maximum discharging time protection (1 to 72 hours)
For models above 40kVA and not fitted with an internal contactor:
The features above (except automatic connect) are performed by connecting the external battery to
the UPS through an external battery circuit breaker, which is manually closed and electronically
tripped via the UPS control circuits.
80
7.0OPERATING PROCEDURES
WARNING
!
Hazardous mains and / or battery voltage present behind covers.
No user-serviceable parts are located behind covers that require a tool for their removal. Only
qualified service personnel are authorised to remove such covers.
7.1Introduction
Following installation and commissioning by an authorised service engineer, the UPS will operate in
one of the modes described in 6.3 - Modes of Operation. This chapter describes the various procedures available for the operator to intervene with the UPS mode of operation including starting up,
transferring load to bypass and shutting down.
NOTE
All the user controls and indicators mentioned in these procedures are identified in 8.0 Operator Control Panel and Display.
All power switches mounted inside the cabinet and accessible after opening the key-locked front
door are shown in Figure 63 and described in 7.0 - Operating Procedures.
7.2Startup in Normal Mode
Operating Procedures
This procedure must be followed when turning on the UPS from a fully powered down condition - i.e.,
where the load is not being initially supplied at all or where supplied by the maintenance bypass
switch. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed.
81
Operating Procedures
In multi-module systems—perform each step of the procedure in every UPS module before proceed-
ing to the next step.
WARNING
!
Mains Voltage will be applied to UPS output terminals.
This procedure results in mains voltage being applied to the UPS output terminals.
• Isolate and attach warning labels to any downstream load connections, as applicable.
• No operator serviceable parts are located behind covers that require a tool for removal.
• Only qualified service personnel are authorised to remove such covers.
1. Open the UPS door to gain access to the main power switches.
2. Close Bypass input power switch Q2 and UPS output power switch Q5.
Close also any external output isolation switches, where used.
The LCD becomes active and after initialization, the UPS output is powered from the bypass,
with the bypass and load indicators turned on.
The UPS Mimic LED's will indicate (refer to Figure 67):
# LED
LED FunctionStatus
3Bypass indicatorGreen
5Output indicatorGreen
2Battery indicatorRed
6Alarm indicatorAmber / red
3. Close the Rectifier AC Input Power Switch Q1.
The Rectifier indicator flashes on the UPS mimic panel during the startup of rectifier and
becomes steady green once the rectifier reaches normal operation state after about 30s.
4. Close external battery circuit breaker (where an external battery is used). This breaker is located
inside the battery cabinet (if used) or is otherwise adjacent to the battery racks
5. Following battery availability being detected by the UPS, the red battery indicator extinguishes
moments after when the battery charger starts operation.
6. Open (or confirm open) the internal Manual Bypass Power Switch Q3.
Open also any external Maintenance Bypass Switch, where used.
7. Press INVERTER ON button for two seconds.
The inverter will start up and the inverter indicator flashes while it synchronises to the bypass
voltage frequency.
After the inverter is ready, the UPS transfers from bypass to inverter, the bypass indicator turns
off, and the inverter indicator becomes steady green.
8. Check that no “Warning” message is displayed in the top right corner of the LCD Monitor and the
status of the indicators are:
Applies only to a single module UPS and when programmed by the commissioning engineer to perform ECO mode control of the power delivered to the load.
Follow 7.2 - Startup in Normal Mode and observe at the end of the procedure that the mimic panel
bypass indicator remains green (indicating that the load is supplied by the bypass mains).
The UPS is now operating in ECOMODE.
7.4Battery Test Mode Procedures
The Battery test mode procedures transfer the UPS into shared source mode wherein approximately
15% of the rated load power is supplied by the battery and the balance by the AC input mains. There
are two Battery tests to select from:
Maintenance test—verifies battery integrity and leads to a 20-percent battery discharge.
Battery Capacity test—verifies the battery’s precise capacity and leads to a full battery discharge
(until “Battery Low” alarm).
The battery test procedures are password-controlled and menu-driven. The test is immediately terminated in the event of a battery or a mains failure and the total load power is supported from the
remaining source without interruptions.
The tests can be carried out from the UPS control panel by the operator when the following conditions
are satisfied:
Operating Procedures
• The load must be between 20% and 100% of rated UPS capacity
• The battery must have been float charging for 5 hours or more.
7.4.1Test Procedure
1. Select “Commands” window on the UPS control panel.
Use the right or left arrow keys to navigate to the “Commands” window.
2. Select desired Test.
Use “page” (F1) and up / down arrow keys (F2, F3) to highlight the desired test. Press “enter” (F4).
When prompted, enter each password digit with up arrow (F2) and use right arrow (F3) to access
next field. Press “enter” (F4) when all digits have been entered.
3. Wait until the test completes.
This tests updates the battery information used to calculate the expected back-up time (displayed
during AC input failure) and the battery capacity percentage when compared to a new battery
(displayed in normal mode).
4. Stop test.
If required, the test may be stopped before completion by selecting “Stop Test” in the “Commands”
window.
For more details on how to operate the UPS control panel refer to 8.0 - Operator Control Panel and Display.
83
7.5UPS Self-Test
The UPS test procedure checks the control functions of the UPS, the mimic flow chart LEDs and the
audible alarm. This self-test is password controlled and menu driven. It can be carried out from the
UPS front panel by the operator and takes 5 seconds.
7.5.1UPS Self-Test Procedure
1. Select “Commands” window on the UPS front panel.
Use the right or left arrow keys to navigate to the “Commands” window
2. Select desired Test.
Use “page” (F1) and up / down arrow keys (F2, F3) to highlight the desired test. Press “enter” (F4).
When prompted, enter each password digit with up arrow (F2) and use right arrow (F3) to access
next field. Press “enter” (F4) when all digits have been entered.
3. Wait until the test completes.
After 5 seconds, a popup window will appear to showing the result of this diagnosis: Rectifier,
Inverter, Monitor OK or Fault
4. Stop test.
If required, the test may be stopped before completion by selecting “Stop Test” in the “Commands”
window.
For more details on operating the UPS front panel, see 8.0 - Operator Control Panel and Display.
7.6Maintenance Bypass Procedure and UPS Shutdown
The following procedure transfers the load supply from being protected by the UPS into being connected
directly to the AC input bypass supply though a maintenance bypass switch. This switch is either:
• internal (Q3- located behind the front door) for “Single module” or “1+1 redundant multi-module”
UPS applications.
• external (located in the bypass cabinet) for “1+1 capacity” and “1+N redundant” multi-module
UPS applications – refer to Figure 64.
Operating Procedures
In multi-module systems—perform each step of the procedure in every UPS module before proceeding to the next step.
CAUTION
!
Risk of Load Interruption
Except in emergency situations, so as not to risk a short interruption in powering the load,
before initiating this bypass procedure, confirm that no WARNING status is displayed in the
top right corner of the UPS Monitor.
If a WARNING status is displayed, the operator will be prompted to confirm (“enter”) or
cancel (“ESC”) any action that can lead to load interruption.
1. Press INVERTER OFF direct access key on the UPS front panel.
The UPS inverter will shut down and the load is supplied through the Static Bypass supply.The
UPS Mimic indicator Inverter ON (4) will extinguish, the Status LED (6) turns on.
2. In “Single module” or “1+1 redundant” multi-module UPS—Close the internal maintenance
bypass power switch Q3 and any external maintenance bypass switch, if used.
3. In “1+N redundant” or “1+1 capacity” multi-module UPS—Close the external maintenance switch
only.
4. The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply.
5. The display window will show messages reflecting the actions taken (i.e. Maintenance Bypass
closed, etc.).
6. Open output power switch Q5.
This ends the Bypass Procedure. The load is now powered directly from the Maintenance Bypass
supply.
NOTE
The load equipment is NOT protected from AC supply aberrations.
Proceed with the following steps to shutdown the rectifier and battery.
84
Operating Procedures
7. Press the EPO (Emergency Power Off) button at the UPS front panel of this UPS module only.
This will disable further Rectifier, Inverter, Static Switch and Battery operation. This will not
affect the manual maintenance bypass power switch.
NOTE
Do not press any remote EPO button.
8. Open the Rectifier input power switch Q1 and Static bypass input power switch Q2
9. When an external battery is connected, open external battery circuit breaker. This breaker is
located inside the battery cabinet (if used) or is otherwise adjacent to the battery racks
All mimic panel LED indications and messages will extinguish as the mains driven internal
power supplies decay.
The load is now powered from the maintenance bypass supply and the UPS is completely
shut down.
WARNING
!
Hazardous Voltage at UPS terminals
No operator-serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
The input and output AC and DC battery and connecting terminals remains energized at
hazardous voltage levels at all times. The battery is located behind protective covers that
require a tool for their removal. inside the UPS cabinet (30 and 40kVA models), inside a freestanding battery cabinet or on open racks inside a dedicated battery room that may be locked.
Figure 65 Example of configuration for single UPS with external Maintenance Bypass Cabinet
External Maintenance Bypass Cabin et
U3/V3/W3/N3
QF2
U4/V4/W4/N4
Q1
U1/V1/W1/N1
Supplied
by O thers
UPS
QF3
U5/V5/W5/N5
QF4
U6/V6/W6/N6
Q3
Q2
Q5
U2/V2/W2/N2
CB
85
Operating Procedures
7.7Isolation of One Module in a Multi-Module System
7.7.1Multi-Module Systems With External Output CB1
Figure 66 Typical 1+N system block diagram with common input supply, with separate batteries and
optional output / bypass distribution panel
Supplied
by Ot he r s
Input M a i ns
Supply L1, L2, L3, N
UPS1
Charger
Input M ai ns
Supply L1, L2, L3, N
Q1
Q1
UPS2
Rectifier
Rectifier
Charger
Inverter
Inverter
Q2
Q3
Q5
Q5
L1 , L2, L3 , NL1, L2, L3, N
Q1EXTQ2EXT
Q2
Q3
QUPS
QBYP
Dist ribution Cabinet
To Load
1. Turn Off inverter.
2. Open External Output isolator (Q1ext or Q2ext).
The UPS enters Isolation Status automatically, parallel signaling and communication becomes
masked, and output becomes inhibited.
3. Power Off unit for maintenance.
4. Power On unit.
5. Unit enters Test Mode by configuration software setting.
6. Diagonosis or testing.
7. The UPS exits Test Mode by configuration software setting.
Output becomes inhabited because of Isolation Status.
8. Return all switches to the Normal position.
9. Close External Output isolator (Q1ext or Q2ext).
The UPS exits Isolation Status automatically, parallel signaling and communication recovers,
86
output becomes enabled but interlocking works now.
10. Turn On inverter and join the parallel system.
7.7.2Multi-Module System Without External Output Circuit Breaker 1
This procedure is indicated for isolation of one UPS module from other modules of a group of otherwise normally operating paralleled UPS modules. Only the power switches, isolators and circuit
breakers in the module to be isolated will be opened. This procedure does not require the supply of
any bypass power to the critical load.
1. Turn Off the inverter
2. Open Internal Output isolator (Q5) but keep Internal Maintenance Circuit Breaker open.
The UPS enters Isolation Status automatically, parallel signaling and communication become
masked, and internal output becomes inhibited.
3. Power Off unit for maintenance.
4. Power On unit with Internal Output isolator (Q5) open.
5. The UPS enters Test Mode by configuration software setting.
6. Diagonosis or testing.
7. The UPS exits Test Mode by configuration software setting.
Output becomes inhibited because of Isolation Status.
8. Return all switches of Unit 1 to the Normal position, including Internal Output Circuit Breaker 1.
When Internal Output isolator (Q5) is closed, unit will exit Isolation Status automatically, parallel
signaling and communication recovers, output becomes enabled but interlocking works now.
9. Turn On Inverter1 and join the parallel system.
Operating Procedures
WARNING
!
Hazardous Battery Voltage
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
The UPS battery and connecting terminals remains energized at hazardous voltage levels at
all times. The battery is located behind protective covers that require a tool for their removal:
inside the UPS cabinet (30 and 40kVA models), inside a free-standing battery cabinet or on
open racks inside a dedicated battery room that may be locked.
87
7.8Insertion of One Module in a Multi-Module System
This procedure is indicated to reintegrate a UPS module that has been previously isolated from other
modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed.
WARNING
!
Mains voltage will be applied to UPS output terminals.
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
1. Open the UPS door to gain access to the main power switches.
2. Open (or confirm disabled) maintenance bypass power switch Q3
3. Close input bypass power switch Q2 and UPS output power switch Q5.
(Close also any external output isolation switches, where used). The LCD display becomes active.
4. Close the Rectifier AC Input Power Switch Q1.
The Rectifier indicator flashes on the UPS mimic panel during the startup of rectifier and
becomes steady green once the rectifier reaches normal operation state after about 30s.
5. Close external battery circuit breaker QF1 (where an external battery is used). This breaker is
located inside the battery cabinet (if used) or is otherwise adjacent to the battery racks
6. Following battery availability being detected by the UPS, the red battery indicator extinguishes
moments after when the battery charger starts operation.
7. Press INVERTER ON button for two seconds.
The inverter will start up and the inverter indicator flashes while it synchronises to the load volt-
age frequency. After the inverter is ready, the UPS connects to the load, the inverter indicator
becomes steady green and the output indicator turns green.
8. Check that no “Warning” message is displayed in the top right corner of the LCD Monitor and the
status of the indicators as follows: