Please allow us to congratulate you on choosing a Liebert manufactured Uninterruptible Power System.
If this is your first Liebert UPS, we cordially welcome you to a lifetime relationship of after-sales support
designed to keep your Liebert UPS and your systems permanently at their peak performance.
If you already own and use a Liebert UPS, then we are doubly honoured by your decision to continue this
valued relationship.
Our philosophy is reflected in our mission statement “Keeping Business in Business,” and with this we strive
to contribute to the growth & success of your business.
Please give us your valued feedback to help us realise our mission.
200kVA module for Europe and Middle East, 400V/230V output
OptionsModel IdentificationNote
Narrow battery cabinetNXA0BCNSpecify: UPS kVA rating,
Wide battery cabinetNXA0BCW
Battery Circuit Breaker Box NXA0BCBSpecify UPS kVA rating
Battery Start KitNXA0UFXBB—
Battery Ground Fault detection kitNXA0UFXBGF—
Battery temperature probe (for external battery) NXA0UFXBTS—
Maintenance bypass cabinet (separate bypass input) NXA0MBXSpecify total system kVA
Transformer cabinet NXA0TCXSpecify UPS kVA & I/O Voltage
Fan Redundancy kit NXA0UFXRFSpecify UPS kVA rating
Seismic Anchor kit NXA0UFXSAN—
Bypass current sharing inductanceNXA0UFXBK—
Dual bus control cable 05-10-15 metr esNXA0UFXDSpecify length in metres
Parallel control cable kit 05-10-15 metresNXA0UFXPSpecify length in metres
Relay Card (On Bat, Bat Low, On Byp, Sum, UPS Fail)
Relay Card 4 (4 sets On Bat, bat Low)
Webbrowser/TCPIP/SNMP Card
Jbus/Modbus Card
RAM - Remote Alarm MonitorNXA0CFXRAM Requires RELAYCARD-INT
Modem cardNXA0CFXMOD—
Large Battery Cabinet NXA0NBCL—
Maintenance bypass cabinet (separate bypass input)NXA0NMBX—
Transformer cabinetNXA0NTCX—
Air Filter (One Filter)NXA0UFXARF—
Dual Bus Extension Kit 50-150 Meters NXXXXMLBSKIT(XXX: 050 or 150)- 'Specify Length in metres.
Individual Battery MonitoringBDS 40 or BDS 256Specify number of blocks. Consult Emerson
RELAYCARD-INT
MULTIPORT 4
OCWEB-LB
OC485CARD
3, 4 or 5-shelves
fuse or circuit breaker protection
Intellislot plug-in cards—3 slots available.
Used for extension in length or dual bus
arrangement between Nx and non-Nx
sources'
Network Power representatives for complete
configuration
ix
x
SAFETY PRECAUTIONS
This manual contains information concerning the installation and operation of this Emerson Network
Power Liebert NX Uninterruptible Power System (UPS).
This manual should be read before commencing installation.
The UPS must be commissioned and serviced by an engineer approved by the manufacturer (or
agent).
Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of warranty.
The Liebert NX has been designed for Commercial/Industrial use only, and is not recommended for
use in life support applications.
This is a low emission CLASS A Uninterruptible Power System (UPS) product. In a residential environment, this product may nevertheless cause radio interference, in which case, the user may be
required to take additional measures.
Conformity and Standards
This equipment complies with CE directives 73/23 & 93/68 (LV Safety) and 89/336 (EMC), with Australia and New Zealand EMC Framework (C-Tick) and with the following product standards for Uninterruptible Power System (UPS).
• EN / IEC / AS 62040-1-1—General and safety requirements for use in operator access area
• EN / IEC / AS 62040-2—EMC requirements; Class A compliant
• EN / IEC / AS 62040-3—Performance requirements and test methods
For more details, see 10.0 - Technical Specifications
Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.
WARNING
!
High Leakage Current
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA for 30-80kVA, less than
2000mA for 100-120kVA. models and less than 2500mA for 140-200kVA models.
Transient and steady-state earth leakage currents, which may occur when starting the
equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional
pulses (class A) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with the local electrical code of practice.
WARNING
!
Back-Feed Protection Notice
This UPS is fitted with a voltage-free contact closure signal for use with an external
automatic disconnect device (supplied by others) to protect against back-feeding voltage into
the bypass input. If this signal is not used by the installer, a label must be added at the
external bypass input disconnect device to warn service personnel that the circuit is
connected to a UPS.
The text to use is the following or equivalent:
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS
CIRCUIT.
1
User-Serviceable Parts
All equipment maintenance and servicing procedures involving internal access requires the use of a
tool and should be carried out only by trained personnel. There are no user-serviceable parts behind
covers requiring a tool for removal.
This UPS is fully compliant with safety regulations for equipment located in an operator accessible
area. Hazardous voltage is present within the UPS and battery enclosure but out of reach of non-service personnel. Contact with hazardous voltage is minimized by housing live parts behind safety panels that require a tool for their removal. No risk exists to any personnel when operating the
equipment in the normal manner, following the recommended operating procedures.
Battery Voltage Exceeds 400VDC
All physical battery maintenance and servicing requires the use of a tool or a key and should be carried out only by trained personnel.
WARNING
!
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the battery terminal voltage will exceed 400VDC and is potentially
lethal.
Battery manufacturers supply details of the necessary precautions to be observed when working on,
or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all
times.
Attention should be paid to the recommendations concerning local environmental conditions and the
provision of protective clothing, first aid and fire-fighting facilities.
2
1.0SINGLE MODULE UPS INSTALLATION
1.1Introduction
This following section describes the requirements that must be taken into account when planning the
positioning and cabling of the Liebert NX uninterruptible power supply and related equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing
engineer. The particular conditions of each site will determine the applicability of such procedures.
WARNING
!
Professional Installation Required
Do not apply electrical power to the UPS equipment before being authorised to do so by the
commissioning engineer.
The UPS equipment shall be installed by a qualified electrical tradesperson in accordance
with the information contained in this manual. All equipment not referred to this manual is
shipped with details of its own mechanical and electrical installation.
NOTE
Three-phase, 4-wire input supply required.
The standard Liebert NX UPS is suitable for connection to 3-phase, 4-wire (+ Earth) TN, TT
and IT AC power distribution systems (IEC60364-3). Optional 3-wire to 4-wire conversion
transformers are available. If it is used in IT AC power distribution systems, a 4-pole circuit
breaker must be used on the input and refer to the relative IT Systems’ standard
Single Module UPS Installation
WARNING
!
Battery Hazards
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the battery terminal voltage will exceed 400VDC and is hazardous.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Remove rings, watches and all other metal objects.
Use only tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed
immediately with water.
1.2Preliminary Checks
Before installing the UPS, please carry out the following preliminary checks:
1. Visually examine the UPS and battery equipment for transit damage, both internally and
externally. Report any damage to the shipper immediately.
2. Verify that the correct equipment is being installed. The equipment supplied has an identification
tag on the back of the main door reporting: the type, size and main calibration parameters of the
UPS.
3
1.3Location
1.3.1UPS Room
The UPS and its internal battery is intended for indoor installation and should be located in an environment with clean air and with adequate ventilation to keep the ambient temperature within the
specified operating range (see Table 33).
All models in the Liebert NX UPS range are air-cooled with the aid of internal fans. Cold air enters
through ventilation grilles at the front of the cabinet for NXa 30-120kVA and through ventilation
grilles located at the front and bottom of the cabinet for NXa 140-200kVA. Hot air is released through
grilles at the top. Do not cover the ventilation openings.
If necessary to avoid room temperature build-up, install a system of room extractor fans. Optional air
filters are available if the UPS is to operate in a dusty environment.
The UPS heat dissipation detailed in Table 34 can be used as a guide for air conditioning sizing,
depending on the selected mode of operation:
• Normal Mode (VFI SS 111 Double Conversion UPS)
• ECO Mode (VFD SS 311 Stand By UPS)
If in doubt use Normal Mode figures.
NOTE
The UPS is suitable for mounting on concrete or other non-combustible surface only.
Single Module UPS Installation
1.3.2External Battery Room
Batteries should be mounted in an environment where the temperature is consistent and even over
the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical
battery manufacturer performance data are quoted for an operating temperature between 20 and
25°C (68 and 77°F). Operating above this range will reduce the battery life while operation below this
range will reduce the battery capacity. In a normal installation the battery temperature is maintained between 15°C and 25°C (59 and 77°F). Keep batteries away from main heat sources or main air
inlets etc.
Where the batteries are located externally to the main UPS cabinet, a battery protection device
(e.g., fuses or circuit breakers) must be mounted as close as possible to the batteries themselves, and
connected using the most direct route possible.
1.3.3Storage
Should the equipment not be installed immediately, it must be stored in a room for protection against
excessive humidity and or heat sources (see Table 33).
CAUTION
!
An unused battery must be recharged periodically per battery manufacturer
recommendation. Temporarily connecting the UPS to a suitable AC supply mains and
activating it for the time required for recharging the batteries can achieve this.
4
1.4Positioning
The cabinet is mounted on four casters for ease of positioning and for moving short distances. Jacking
feet are provided to prevent the UPS from moving once it has been wheeled to its final position.
For optimal design life, the place chosen must offer:
•Easy connection
• Enough space to easily work on the UPS
• Sufficient air exchange of enough to dispel heat produced by UPS
• Protection against atmospheric agents
• Protection against excessive humidity and very high heat sources
• Protection against dust
• Compliance with the current fire prevention requirements
• Operating environment temperature between 20°C and 25°C (68 and 77°F). The batteries are at
maximum efficiency in this temperature range (see Table 33).
The UPS cabinet is constructed around a steel chassis with removable panels. The top and side panels
are secured to the chassis by screws.
Access to the power terminals, auxiliary terminals blocks and power switches is from the front. Operational status and alarm information is provided through the front door operator control panel. Models 40kVA and below house both the power components and an internal battery. Cooling air enters in
the front of the NXa 30-120kVA and the front and bottom of NXa 140-200kVA; it is exhausted out the
top of each.
1.4.1System Cabinets
A UPS may comprise a number of cabinets, depending on design requirements (e.g., UPS cabinet, external battery cabinet, external bypass cabinet). In general, all the Liebert cabinets used in a particular
installation are of the same height and designed to be positioned side-by-side to form a matching array.
Refer to 5.0 - Installation Drawings for assistance on positioning the cabinets described below.
Single Module UPS Installation
1.4.230 to 40kVA UPS
The UPS consist of a single cabinet, which uses typically forty (40) 12V battery blocks, fitted internally and connected in series to provide a nominal battery voltage.
the batteries fitted.
An extended battery option is available. This comprises a separate cabinet containing additional batteries that can be connected to the UPS to increase its battery run time. Battery cabinets and batteries are usually shipped separately.
1.4.360-200kVA UPS
The 60 to 200kVA consist of a single cabinet without any internal battery. Usually, with 60 to 200kVA
UPS installations, the batteries are contained in a purpose-built battery cabinet, which sits alongside
the main UPS equipment. Batteries are accessible in the external cabinet from the front, making it
unnecessary to allow for side access.
1.4.4Moving the Cabinets
WARNING
!
Ensure that the UPS weight is within the designated surface weight loading of any handling equipment. See Table 35.
UPS and optional cabinets (battery cabinets, top cable entry cabinets, etc.) can be handled by means
of a forklift or similar equipment.
The UPS cabinet also can be moved short distances by its casters.
Ensure that any equipment used to move the UPS cabinet has sufficient lifting capacity.
The UPS is fitted with casters. Take care to prevent the NX from moving when unbolting the
unit from its shipping pallet. Ensure that adequate personnel and lifting aids are available
when removing the shipping pallet.
The UPS may be shipped without
NOTE
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a
minimum.
5
1.4.5Clearances
The Liebert NX has no ventilation grilles at either side of the UPS. To enable routine tightening of
power terminations within the UPS, in addition to meeting any local regulations, Liebert recommends providing adequate clearance in the front of the equipment for unimpeded passage of personnel with the doors fully opened. It is important to leave 800mm (31.5") clearance above the UPS to
permit adequate circulation of air coming out of the unit.
1.4.6Access
The component layout of the UPS supports front and top access while servicing, diagnosing and
repairing the UPS, thus reducing the space requirement for side and rear access.
1.4.7Final Positioning
The UPS cabinets are fitted with casters on the base to allow ease of movement and positioning.
WARNING
!
Casters are strong enough for movement across even surfaces only. Caster failure could occur
if they are subjected to shock loading.
When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS
will remain stationary and stable.
1.4.8Floor Anchoring
Single Module UPS Installation
Diagrams in 5.0 - Installation Drawings show the location of the holes in the base plate through
which the equipment may be bolted to the floor. If the equipment is to be installed on a raised floor it
should be mounted on a pedestal suitably designed to accept the equipment point loading.
1.4.9Cable Entry
Cables can enter the Liebert NX UPS and battery cabinet from below. Cable entry is made possible by
removing a blanking piece fitted at the bottom of equipment to reveal the cable entry hole.
Top Cable Entry—Optional
Optionally a top cable entry extension may be used. The cabinet extends the overall width of the UPS
and permits connection of all incoming AC/DC power cables from above.
The top cable entry option is fitted on the side of the UPS cabinet and is supplied without side panels;
the side cover from the UPS being used.
The cabinet with cables coming in from the top for the 30-40 kVA UPS must be positioned on the left
side; the cabinet for the 60 to 200 kVA UPS can be positioned on either side.
This facilitates cable entry through the top metal panel after the appropriate cable entry holes have
been cut.
NOTE
The top cable entry also includes the power connection cables between the cabinet and the UPS.
1.5External Protective Devices
Circuit breakers or other protective devices must be installed in the AC supply, external to the UPS.
This chapter provides guidelines for qualified installers who must have knowledge of local wiring
practices pertaining to the equipment to be installed.
6
1.5.1Rectifier and Bypass Input
Overcurrent protection must be installed at the distribution panel of the incoming main supply. The
protection must discriminate with the power cables current capacity and with the overload capacity of
the system (see Table 38). As a guideline, a thermomagnetic circuit breaker, with an IEC 60947-2
trip curve C (normal) for 125% of the current listed in Table 1 is suitable.
Split-Bypass—If a split-bypass is used, install separate protective devices for the rectifier and for
the bypass in the incoming mains distribution panel.
NOTE
Rectifier and bypass input sources must be referenced to the same neutral potential.
NOTE
Earth Leakage (RCD)
Any residual current detector (RCD) installed upstream of the UPS input supply must be:
For IT power systems, four-pole protective devices must be used, external to the UPS, both
upstream of the input distribution panel and downstream (toward the load).
• sensitive to DC unidirectional pulses (Class A)
• insensitive to transient current pulses, and
• must have an average sensitivity, adjustable between 0.3 and 1A.
Single Module UPS Installation
Figure 1Residual current circuit breakers (RCCB) symbols
To avoid false alarms, earth leakage monitoring devices when used in systems with split-bypass input
or when used in paralleled UPS configurations, must be located upstream of the common neutral
sinking point. Alternatively, the device must monitor the combined four-wire rectifier and splitbypass input currents.
The residual earth current introduced by the RFI suppression filter inside the UPS is greater than
3.5mA, 1000mA for 30-80kVA, 2000mA for 100-120kVA models and less than 2500mA for
140-200kVA models. Liebert recommends verifying the selectivity with all other differential devices
both upstream of the input distribution board and downstream (toward the load).
1.5.2External Battery
The UPS and its associated batteries are protected against overcurrents through a DC compatible disconnect device.
1.5.3UPS Output
Any external distribution board used for load distribution shall be fitted with protective devices that
discriminate with those used at the bypass input to the UPS and with the UPS overload characteristics (see Table 38).
7
1.6Power Cables
The cable design must comply with the voltages and currents provided in this section, follow local wiring practices and take into consideration the environmental conditions (temperature and physical
support media).
For cable entry terminal, refer to Figures 43, 48, 52 and 56.
WARNING
!
Table 1Maximum steady state AC and DC currents
RATING
Before starting the UPS, ensure that you are aware of the location and operation of the
external isolators that connect the ups input/bypass supply to the mains distribution panel.
Check that these supplies are electrically isolated and post any necessary warning signs to
prevent their inadvertent operation.
UPS 30/40 kVAUPS 60-80 kVAUPS 100-120 kVAUPS 140-200 kVA
1320(52)1500 (59)
M8: 13 (2.9)
M10: 26 (5.8)
WARNING
!
Failure to follow adequate earthing procedures may result in electromagnetic interference or
in hazards involving electric shock and fire.
8
1.6.1Cable Termination
NOTE
Once the equipment has been finally positioned and secured, connect the power cables as described in
the following procedure.
Refer to the appropriate cable connection drawing in 5.0 - Installation Drawings.
1. Verify that the UPS equipment is isolated from its external power source and all the UPS power
2. Open the door to the UPS cabinet and remove one of the two protective cover to gain access to the
3. Connect the safety earth and any necessary bonding earth cables to the copper earth busbar
The operations described in this section must be performed by authorised electricians or
qualified technical personnel. If you have any difficulties, do not hesitate to contact our
Customer Service and Support Department. See the back page of this manual for contact
information.
isolators are open. Check that these supplies are electrically isolated and post any necessary
warning signs to prevent their inadvertent operation.
desired connection bars.
• the lower protective cover houses the 60-200kVA connection bars
• the left protective cover houses the 30-40kVA connection bars
The protective cover on the UPS cabinet of 60 to 200kVA models must be removed after the
handles on the power isolators have been removed.
located on the floor of the equipment below the power connections. All cabinets in the UPS must
be connected to the user’s ground connection.
Single Module UPS Installation
NOTE
The earthing and neutral bonding arrangement must be in accordance with local and national
codes of practice.
Identify and make power connections for incoming cables according to one of the two procedures
below, depending on the type of installation.
Common Input Connections
4. For common bypass and rectifier inputs, connect the AC input supply cables between the mains
distribution panel and the UPS input (U1-V1-W1-N terminals) and tighten the connections to
5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm for M10 bolts. Ensure correct phase rotation.
Split-Bypass Connections
5. If a split-bypass configuration is used, connect the AC input supply cables to the rectifier input
busbars (U1-V1-W1-N terminals) and the AC bypass supply cables to the bypass input
(U3-V3-W3-N terminals) and tighten the connections to 5Nm for M6 bolts, to 13Nm for M8 bolts
or to 26Nm (M10 bolt). Ensure correct phase rotation.
NOTE
For split-bypass operation, ensure that the linking busbars between bypass and rectifier input
are removed.
The AC input and the AC bypass supplies must be referenced to the same neutral point.
Frequency Converter Mode
If a frequency converter configuration is used, connect the AC input supply cables to the rectifier
input busbars (U1-V1-W1-N terminals). Torque to 5Nm for M6 bolts, to 13Nm for M8 bolts or to
26Nm (M10 bolt). Ensure correct phase rotation. There will not be any AC bypass supply cables to the
bypass input (U3-V3-W3-N terminals) and tighten the connections.
NOTE
For frequency converter operation, ensure that the linking busbars between bypass and rectifier
input are removed.
9
Single Module UPS Installation
Output System Connections
6. Connect the system output cables between the UPS output (U2-V2-W2-N terminals) and the
critical load and tighten the connections to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm for
M10 bolts. Ensure correct phase rotation.
External UPS Battery Connection (60kVA Models and Above, Option for 30-40kVA Models)
Connect the battery cables between the UPS terminals (+\-) and its associated battery circuit
breaker. Observe the battery cable polarity.
NOTE
When connecting the cables between the battery extremities to the circuit breaker always
connect the circuit breaker end of the cable first.
WARNING
!
If the load equipment will not be ready to accept power on the arrival of the commissioning
engineer, ensure that the system output cables are safely isolated at their ends.
Internal UPS Battery Connection (30/40kVA only)
7. The battery consists of a series string connection of 5 x 8 (or 10) x 12V 6-cell battery blocks.
a. Ensure that the eight (or 10) battery blocks in each tier (tray) are interconnected.
b. Connect the positive and negative cables to the UPS terminals.
c.Plug in the cables between the tiers.
d. Ensure correct polarity battery string series connections (i.e., intertier and
interblock connections are from positive to negative terminals.
WARNING
!
Hazardous Battery Terminal Voltage 480VDC
Ensure correct polarity of string end connections to the UPS terminals, i.e., positive to
positive and negative to negative, but leave these UPS terminal cables disconnected until
connection is authorised by the commissioning engineer.
Ensure correct polarity of string end connections to the battery circuit breaker and from the
battery circuit breaker to the UPS terminals, i.e., positive to positive and negative to negative,
but disconnect one or more battery cell links in each tier.
Do not reconnect these links and do not close the battery circuit breaker before authorised by
the commissioning engineer.
8. Refit all protective covers removed for cable installation.
10
1.7Control Cables and Communication
1.7.1Monitor Board Features
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker, battery temperature sensor), communicate with a personal
computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).
The monitor board, arranged for this purpose, is located on the rear of the operator access door. The
main features are:
• Input and Output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
The black square ( )
on each s lot indi cates P in 1.
X4
J24
X6
PWR
Modem
SNMP Card
X4
X5
11
1.8Dry Contacts
The UPS provides input dry contacts and output dry contacts.
1.8.1Input Dry Contacts
There are several input dry contacts at the X3 slot.
X3 Ancillary Control and Alarms
X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts
The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, pushin terminal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS
when connection between the relevant terminal and the +12V terminal is altered. Cables connected to
X3 IN DRY must be segregated from power circuits (for screening purposes), double insulated and of a
typical 0.5 to 1mm
respectively.
Figure 3Input dry contacts
12V
2
cross-section area for maximum runs between 25 and 50 meters (82-164 ft),
Single Module UPS Installation
12V12V
12V
X3
J4J26J30J10
12V
BtG
GEN
ENV
12V
GND
T_IT
AUX_I
T_OT
AUX_O
FUSE
F_FAN
OL
GND
Table 3Input dry contacts at X3
Position
J4.1ENV
J4.2BtGBattery Ground Fault Detection (NC)
J4.3GEN
J4.4+12V+12V Power
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
Name
Description
3
Battery Room Alarm (NC)
1,2
On Generator (NO)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.
- Must be configured by software before becoming active
Name
Description
1
Input transformer overtemperature (NC)
1
Output Transformer Overtemperature (NC)
Single Module UPS Installation
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.
1.8.3External Circuit-Breaker Interface
J10 is the interface to any external battery circuit breaker (BCB).
Table 5
Position
J10.1DRVBCB Driver Signal - Output (N.O.)
J10.2FBBCB Contact State - Input (N.O.)
J10.3GNDPower Ground
J10.4OL
External circuit-breaker interface
Name
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
Description
BCB On-Line - Input - This pin will become active when
BCB interface is connected. (N.O.)
2
2
13
1.8.4Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 4 and Table 6)
Single Module UPS Installation
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.
Figure 4Output dry contacts and EPO wiring for firmware before M162
J13
BFP_C
BFP_S
BFP_O
J21J25J25
INV_S
INV_C
INV_O
ACF_C
ACF_S
ACF_O
Table 6Output dry contact relays for firmware before M162
PositionName
J13.2BFP_OBypass feedback protection relay; normally ope n. Closed when bypass SCR is shorted.
J13.3BFP_SBypass feedback protection relay center
J13.4BFP_CBypass feedback protection relay; normally closed. Open when bypass SCR is shorted.
J21.2INV_OInverter mode relay; normally open. Closed when UPS is in inverter mode.
J21.3INV_SInve rter mode relay center
J21.4INV_CInverter mode relay; normally closed. Open when UPS is in inverter mode.
J25.2ACF_OMain input fault relay; normally open. Closed when main input is in fault.
J25.3ACF_SMain input fault relay center
J25.4ACF_CMain input fault relay; normally closed. Open when main input is in fault.
Description
2
+12V
X2X1
EPO-LEPO-H
Figure 5EPO wiring for firmware M200 or later
J28
EPO-NOEPO-NC
1.8.5Emergency Power Off Input
The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel
or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 4, is the remote EPO input interface. The EPO has an NO/NC contact
point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1
If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the
auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop
X2
14
Single Module UPS Installation
switch between these two terminals using shielded cable (see Figure 4 and Table 7). If this function
is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed.
Table 7EPO input contact relays
PositionName
J28.1EPO_NC EPO Activated when opened to J28.2
J28.2EPO_NCEPO Activated when opened to J28.1
J28.3EPO_NOEPO Activated when sh orted to J28.4
J28.4EPO_NOEPO Activated when sh orted to J28.3
Description
NOTE
The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass.
It does not internally disconnect the input power supply. To disconnect ALL power to the UPS,
open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor
board and must remain installed if using NC contacts.
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 0.5-1.5mm
2
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
X5: Auxiliary DC Power Output
Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maximum current is 500mA.
X6: Analog Input Interface
Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%.
• X6 pin 1: Not used
• X6 pin 2: +12V
• X6 pin 3: ENV-T – environment temperature detection
• X6 pin 4: GND
X7: External Battery Temperature Detector Interface
Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see
Figure 26).
Pin reference:
• X7 pin 1: Not used
• X7 pin 2: +12V (Power supply for Temperature Monitoring Probe)
• X7 pin 3: BAT-T (Battery Temperature signal)
• X7 pin 4: GND
15
Serial Ports RS232-1 and RS232-2
RS232-1 provides serial data and is intended for direct use with Liebert MultiLink monitoring and
server shutdown software.
RS232-2 provides serial data and is intended for use by authorized commissioning and service personnel.
These serial ports are shared with the optional Web browser, SNMP, ModBus and relay cards. Refer
to Table 31 regarding compatibility of simultaneous use.
Intellislot Web Browser, SNMP, ModBus and Relay Cards Interface
There are three interface slots available for optional Web browser, SNMP, ModBus and Relay cards
as illustrated in 9.0 - Options—For Assembly Inside the UPS Cabinet.
1.8.6External Bypass Switch Interlock
EXT-Maint X3-1&2 on UPS Parallel Board M3 (leave open if no external bypass switch is used)
Provides external maintenance bypass interlock protection for the UPS. Short circuit means external
bypass closed.
EXT-Out (X3-3&4) on UPS Parallel Board (leave shorted if no external output switch is used). Provides external output interlock protection for paralleled UPS modules. Short circuit means external
output switch closed.
Single Module UPS Installation
NOTE
UPS Parallel Board M3 is located behind protective covers accessible after opening the UPS
front door—removal of this barrier requires the use of a tool and is restricted to service
personnel.
NOTE
Jumper JP1 (located next to X3) needs to be removed for X3:3&4 to work properly.
16
2.0BATTERY INSTALLATION
2.1Introduction
The UPS battery bank consists of battery blocks connected in series to provide a D.C. string voltage as
required by the UPS converter. The 'AUTONOMY TIME' (the time during which the battery can
maintain supply to the load in the event of a mains failure) is limited by the ampere-hour capacity of
the battery blocks and in some cases this results in several strings being connected in parallel.
The NX 30-40kVA has internal batteries, but longer run time is available by using an external battery cabinet.
The battery cabinet will be supplied in one of the following forms:
1. Complete installation, comprising the battery cabinet, batteries and protective device.
2. Battery cabinets and protective device only—batteries supplied by others
3. Battery cabinet only—batteries and circuit breaker supplied by others.
NOTE
30kVA to 40kVA UPS models contain an internal battery compartment that can accommodate
up to 42 blocks 24 Ah/12V batteries.
The battery bank may be disconnected from the UPS for maintenance or service. The circuit breaker
can be switched ON or OFF manually and further battery isolation control is achieved through the
use of either a battery circuit-breaker undervoltage coil or through an automatic contactor inside the
UPS.
Battery Installation
17
2.2Safety
Special care should be taken when working with the batteries associated with the Liebert NX UPS
system. When all the cells are connected together, the battery terminal voltage is potentially hazardous. The battery installation must be segregated from all but appropriately qualified maintenance
personnel by locating the cells in a key-lockable cabinet or in a purpose-designed, dedicated battery
room.
!
Battery Installation
NOTE
Full safety instructions concerning the use and maintenance of UPS batteries are provided in
the appropriate battery manufacturers manuals. The battery safety information contained in
this section relates to key considerations that must be taken into account during the
installation design process and might affect the design outcome depending on localised
conditions.
WARNING
Hazardous battery voltage present behind covers
No user-serviceable parts are located behind covers that require a tool for their removal. Only
qualified service personnel are authorised to remove such covers.
When using internal batteries in 30 and 40kVA units, the batteries are always connected
through power fuses to the UPS and to the segregated terminal bars available for connection
to an external battery.
Isolate any internal battery connections before attempting to access the segregated terminal
bars available for connection to an external battery.
The following general battery safety precautions and warnings should be observed at all
times:
• A battery can present risk of electric shock or burn from high- short-circuit currents.
• The full nominal string voltage, when the battery blocks are interconnected, is 480VDC,
which is hazardous
• Only qualified personnel should install or service batteries.
• Eye protection should be worn to prevent injury from electrical arcs.
• Remove rings, watches, necklaces, bracelets and all other metal objects.
• Use only tools with insulated handles.
• Wear rubber gloves and a rubber apron when handling batteries.
• If a battery leaks electrolyte or is otherwise damaged, it should be placed in a container
resistant to sulfuric acid and disposed of in accordance with local regulations.
• If electrolyte comes into contact with the skin the affected area should be washed immediately with plenty of clean water.
• Batteries must always be disposed of according to local environmental laws.
• When replacing batteries, use the same number and type that were originally fitted.
• Disconnect charging source before connecting or disconnecting battery terminals.
• Determine whether the battery is inadvertently grounded. If it is inadvertently grounded,
remove the source of the ground. Contact with any part of a grounded battery can result in
electrical shock.
2.3Battery Cabinet
2.3.1Introduction
This cabinet can also be used in conjunction additional cabinets, to provide the necessary accommodation required by the larger cells associated with system’s having a long autonomy time.
Where two (or more) cabinets are used they are positioned alongside each other and secured and
bonded together. If the cabinet(s) is located immediately adjacent to the main UPS equipment the two
units are bolted together.
18
Loading...
+ 102 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.