Emerson NX 10-30kVA User Manual

Page 1
Liebert NX™ UPS
User Manual–10-30kVA, 208V, 60Hz
AC Power For Business-Critical Continuity™
Page 2
Page 3
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1 External Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Internal Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2.1 Storing for Delayed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.1 Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 UPS Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.1 Positioning the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.2 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.3 Special Considerations for 1+N Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Considerations in Moving the NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.6 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.6.1 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.6.2 Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.6.3 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.6.4 Optional Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.0 ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1 Power Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.1 Cable Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.2 UPS Input Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.3 Cabling Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.4 Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1.5 Safety Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1.6 Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1.7 Cabling Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2 Control Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.1 Monitor Board Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3.1 Input Dry Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3.2 Maintenance Bypass Cabinet Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3.3 BCB Box Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3.4 Output Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3.5 EPO Input—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.0 BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3 UPS Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
i
Page 4
3.4 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.4.1 Matching Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.4.2 Connecting the Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.4.3 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.4.4 Connecting the Battery Cabinet to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.5 Non-Standard Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.0 MAINTENANCE BYPASS CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.1 Bypass Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Normal (UPS) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3 Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.4 Maintenance Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.5 Locating the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.6 Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.6.1 Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.6.2 Power Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.6.3 Input/Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.7 Bolting Cabinets Together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.0 OPTION INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
5.1 Load Bus Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.1.1 Performance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.1.2 DBS Cable and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.2 Configuring Parallel System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2.2 Features of Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2.3 Operating Principles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2.4 Operation Modes Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3 Installing Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3.1 Conditions for Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3.2 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3.3 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3.4 Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3.5 Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.3.6 Parallel Control Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.3.7 Emergency Power Off (EPO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.4 Battery Circuit Breaker Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.5 Battery Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6 Remote Alarm Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.7 Analog Input Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.8 Power Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.9 Intellislot
5.10 OC Web Card—SNMP/HTTP Network Interface Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.10.1 Configuring Baud Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.11 Relay Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.12 MultiPort 4 Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
ii
Page 5
6.0 INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
7.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
7.1 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.2 Bypass Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.3 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.0 OPERATOR CONTROL AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
8.1 Operator Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.1.1 Display Panel Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.2 Mimic Display Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.3 Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.4 Alarm Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.5 LCD Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.6 Navigation Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8.7 UPS System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8.8 LCD Menus and Data Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
8.9 Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.10 Current Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.11 UPS Status Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
8.12 Types of LCD Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
8.12.1 Opening Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
8.12.2 Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
8.12.3 UPS Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
8.12.4 Screen Saver Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
8.13 Pop-Up Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.13.1 From Bypass to Inverter Mode With Power Interruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.13.2 From Inverter to Bypass Mode With Interruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.13.3 System Self-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.13.4 Battery Capacity Test Confirmation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.13.5 Battery Self-Test Aborted, Condition Not Met . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.13.6 Battery Refresh Charge Aborted, Condition Not Met . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
9.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
9.1 NX Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.1.1 Power Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.2 UPS Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.2.1 Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.2.2 Verify Switching Between Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.3 Switching the UPS from Normal to Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.4 Powering Down the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.5 Powering Down the UPS and Maintaining Power to Load . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.6 Emergency Shutdown With EPO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.7 Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.8 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions . . . . . . . . . . 79
iii
Page 6
9.9 Battery Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.9.1 Battery Undervoltage Pre-Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.9.2 Battery End-of-Discharge (EOD) Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.9.3 Battery Fuse-Blow Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.10 Isolating and Integrating One Module in a Multi-Module System . . . . . . . . . . . . . . . . . . . . 80
9.11 Inserting One Module into a Multi-Module System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
9.12 Shutting Down a Multi-Module System Without System Bypass Switch . . . . . . . . . . . . . . 82
9.13 Shutting Down a Multi-Module System With System Bypass Switch . . . . . . . . . . . . . . . . . 82
9.14 Commissioning a Parallel System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
9.15 Maintenance Bypass Cabinet Operating Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
9.15.1 Start Up and Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
9.15.2 Shutting Down the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
9.15.3 Transferring System from UPS to Maintenance Bypass Operation . . . . . . . . . . . . . . . . . . . . 83
9.15.4 Transfer the System from Maintenance Bypass to UPS Operation . . . . . . . . . . . . . . . . . . . . 83
9.15.5 Transfer the System from UPS Operation to Maintenance Bypass . . . . . . . . . . . . . . . . . . . . 83
9.16 Parallel System Start Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.17 Replacing Dust Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
10.0 UPS SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
10.1 Conformity and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
10.2 UPS Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
10.3 UPS Mechanical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
10.4 UPS Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
10.4.1 Battery Manufacturers and Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
10.4.2 Input Rectifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
10.4.3 DC Intermediate Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
10.4.4 Inverter Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
10.4.5 Bypass Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
11.0 SPECIFICATIONS AND TECHNICAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
11.1 Lug Size and Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
11.2 Cable Lengths: Floor to Connection Point Inside UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
APPENDIX A-UPS STATUS MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
FIGURES
Figure 1 Cabinet arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 2 Single module block diagram—dual input configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 3 Input busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 4 Battery fuses and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5 Ground and neutral busbar connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 6 Monitor board U2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 7 Auxiliary terminal block detail (Monitoring Board) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 8 Input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 9 Jumper connection for BCB interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 10 Output dry contacts and EPO wiring for firmware before M170 . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 11 EPO wiring for firmware M200 or later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 12 Battery cabinet—details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
iv
Page 7
Figure 13 Narrow battery cabinet, 27 in. (690mm) - rear view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 14 Wide battery cabinet, 57 in. (1488mm) - front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 15 Internal cable wiring from battery cabinet to Liebert NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 16 Battery tray and supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 17 Single UPS with external Maintenance Bypass Cabinet—typical configuration . . . . . . . . . . . . . 25
Figure 18 Maintenance Bypass Cabinet—access plate removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 19 Maintenance Bypass Cabinet wiring access panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 20 Maintenance bypass control wire location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 21 Load Bus Synchronization cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 22 1+N system block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 23 Connecting '1+N' system parallel control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 24 Auxiliary dry contact cables for output breaker in multi-module system . . . . . . . . . . . . . . . . . . . 35
Figure 25 Dry contacts, multiple UPS modules with distribution panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 26 Connecting EPO push button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 27 Battery circuit breaker box connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 28 OC Web card display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 29 MultiPort 4 card pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 30 Dimensional view- front and left side views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 31 Dimensions continued—top and bottom views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 32 Main components—typical unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 33 Cable connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 34 Location of internal batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 35 Battery connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 36 Battery cabinet interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 37 Maintenance Bypass interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 38 NX 1+1 parallel cabinet interconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 39 Lineup detail—SlimLine distribution cabinet to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 40 Lineup detail—1+N Type A connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Figure 41 Lineup detail—1+N Type B1 connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 42 Lineup detail—1+N Type C connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Figure 43 Suggested placement—single NX with auxiliary cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 44 Suggested placement, multiple NX units with auxiliary cabinets. . . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 45 Single module block diagram (dual input configuration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 46 Overview of control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 47 Detailed view of control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 48 Mimic display indicators location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Figure 49 Location of control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Figure 50 Alarm buzzer location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Figure 51 Sections of the LCD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Figure 52 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Figure 53 Current status and history log records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Figure 54 Opening display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Figure 55 Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Figure 56 Help screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Figure 57 Screen saver window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 71
Figure 58 Power switches - 10kVA NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Figure 59 Typical configuration for single UPS with external maintenance bypass cabinet . . . . . . . . . . . . 78
Figure 60 Single UPS with external Maintenance Bypass Cabinet—typical configuration . . . . . . . . . . . . . 84
Figure 61 Dust filter replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
v
Page 8
TABLES
Table 1 Input dry contacts at X3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 2 Maintenance bypass cabinet interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 3 BCB box interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 4 Output dry contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 5 EPO input contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 6 EPO input contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 7 Available battery circuit breaker boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 8 NX communication options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 9 Relay Card pin configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 10 Relay card jumper configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 11 Liebert -supplied interconnect wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 12 Liebert-supplied interconnect wiring for Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . 50
Table 13 Liebert-supplied interconnect wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 14 Liebert-supplied interconnect wiring—SlimLine distribution cabinet to NX . . . . . . . . . . . . . . . . 52
Table 15 Interconnect wiring—1+N Type A connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 16 Interconnect wiring—1+N Type B1 connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 17 Interconnect wiring—1+N Type C connection to NX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 18 Mimic display status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 19 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Table 20 Icons for navigation keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Table 21 Description of items in UPS system window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Table 22 Descriptions of UPS menus and data window items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 23 UPS operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Table 24 Rotary switch configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Table 25 Environmental characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Table 26 Mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Table 27 UPS terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Table 28 Approved batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Table 29 Rectifier input power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Table 30 DC intermediate circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Table 31 Inverter output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Table 32 Bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Table 33 Torque specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Table 34 Battery torque rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Table 35 Maintenance bypass cabinet electrical data (single input). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Table 36 Maintenance bypass cabinet electrical data (dual input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Table 37 Multi-module bypass cabinet electrical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Table 38 Maintenance bypass cabinet lug sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 39 Battery cabinet physical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Table 40 Maintenance Bypass Cabinet weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Table 41 Maintenance bypass cabinet dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Table 42 Multi-module paralleling cabinet dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Table 43 Distance to connection points on the NX UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Table 44 UPS status messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
. . . . . 94
vi
Page 9

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation of your Liebert NX™ UPS and batteries.
Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.
WARNING
!
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight ranges from 850 to 1400 lb. (386 to 635kg).
Determine unit weight and locate center of gravity symbols before handling the UPS. Test lift and balance the cabinet before transporting. Never tilt equipment more than 15 degrees from vertical.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times.
Follow all battery safety precautions when installing, charging or servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 288VDC and is potentially lethal.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages.
Check for voltage with both AC and DC voltmeters prior to making contact.
WARNING
!
As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these voltages is minimized as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.
WARNING
!
High ground leakage current: Ground connection is essential before connecting the input supply.
This equipment must be grounded in accordance with local electrical codes.
Maximum load must not exceed that shown on the UPS rating label.
1
Page 10
CAUTION
!
This equipment is fitted with RFI suppression filters. Ground leakage current exceeds 3.5 mA and is less than 1000 mA. Transient and steady-state ground leakage currents, which may occur when starting the
equipment, should be taken into account when selecting instantaneous residual current circuit breakers (RCCBs) or residual current devices (RCDs).
RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses.
Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.
WARNING
!
Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris.
Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the battery. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Maintenance Manual, before as well as during performance of all maintenance procedures. Observe all battery safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur.
CAUTION
!
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.

Battery Cabinet Precautions

The following warning applies to all battery cabinets supplied with UPS systems. Additional warn­ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation.
WARNING
!
Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet (after initial installation).
• Battery cabinets contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT before moving battery cabinets (after initial installation).
2
Page 11

GLOSSARY OF SYMBOLS

Risk of electrical shock
!
R
i
-
PbH2SO4
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
3
Page 12

1.0 INSTALLATION

Liebert’s NX™ Uninterruptible Power Supply system provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The NX UPS supplies power that is free of the disturbances and variations in voltage and frequency com­mon to utility power, which is subject to brownouts, blackouts, surges and sags.
The NX utilizes the latest in high-frequency, double-conversion pulse width modulation (PWM) tech­nology and fully digital controls to enhance its reliability and increase the ease of use.
This section describes the NX’s environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site is unique, this section presents a guide to general procedures and practices that should be observed by the installing engineer, rather than step-by-step installation instructions.
WARNING
!
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
WARNING
!
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this section.
WARNING
!
Special care should be taken when working with the batteries associated with this equipment. When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves. If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.
Installation
NOTE
The NX UPS can be used in TN utility system.

1.1 External Inspections

1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Liebert Global Services at 1-800-LIEBERT to inform them of the damage claim and the condition of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Liebert representative immediately.

1.2 Internal Inspections

1. Remove any packaging material, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper and to Liebert immediately.
2. Check the nameplate inside the cabinet door to verify that the model number and rating correspond to the ones specified. Record the model number and serial number in the front of this installation manual. This information is necessary should service be required.
3. Check for loose connections or unsecured components in the cabinet.
4. Check for shipping damage to internal components.
4
Page 13

1.2.1 Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the NX from excessive moisture (see 10.2 - UPS Environmental).
CAUTION
!
If the UPS must remain disconnected from power for more than six (6) months, the battery must be recharged before use. To charge the batteries, the unit must be connected to utility power and started up—the charger operates only while the NX is operating.
CAUTION
!
When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS unit, the battery—not the UPS—dictates the designed maximum ambient temperature.

1.3 Preliminary Checks

1.3.1 Identification

The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS.

1.4 UPS Location

Installation

1.4.1 Positioning the UPS

Choose a location for the UPS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the UPS
• Air circulation sufficient to expel heat produced by UPS
• Protection against moisture and excessive humidity
• Protection against dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency

1.4.2 Environmental Considerations

Before installing the NX, verify that the UPS room satisfies the environmental conditions stipulated in 10.2 - UPS Environmental, paying particular attention to the ambient temperature and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating tempera­ture within the range of 74-80°F, (23-27°C).
The NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 24 in. (610mm).
See Table 26 for details on heat dissipation.
Battery Location
Temperature is a major factor in determining battery life and capacity. Battery manufacturers recom­mend an operating temperature of 77°F (25°C). Ambient temperatures warmer than this reduce bat­tery life; temperatures below this reduces battery capacity. In a typical installation, battery temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed where there are no main heat sources or air inlets to prevent portions of batteries from being either much warmer or much cooler than other parts of the batteries.
5
Page 14

1.4.3 Special Considerations for 1+N Systems

1. Consider the grounding configuration of your system before finalizing module placement. For optimal ground performance, the NX modules should be close together.
2. For optimal load-sharing performance, the UPS output cables should be approximately the same length, plus or minus 20 percent.
3. Position modules in such a way as to minimize the length of power cables and control wiring between UPS modules and the paralleling cabinet.

1.5 Considerations in Moving the NX

Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any handling equipment. See Table 26 for weights of various units.
To move the UPS and optional battery cabinets:
• The NX may be rolled on its casters when moving the unit a short distance. For longer distances, move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration.
The optional battery cabinets should be moved with a forklift or similar equipment.
WARNING
!
Ensure that any equipment that will be used to move the NX has sufficient lifting capacity. The NX weight ranges from 850 to 1400 lb. (386 to 635kg). See Table 26 for details. The UPS presents a tipping hazard. Do not tilt the NX further than 15 degrees from vertical.
The UPS is fitted with casters—take care to prevent movement when unbolting the equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are available when taking the NX off its shipping pallet. Do not tilt the unit more than 15 degrees from center.
Installation
WARNING
!
The casters are strong enough for movement across even surfaces only. Casters may fail if they are subjected to shock loading, such as being dropped or rolled over holes in the floor or obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging the equipment.
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a minimum. For further information, see Battery Cabinet Precautions on page 2.

Final Position

When the equipment has been finally positioned, ensure that the adjustable stops are set so that the UPS will remain stationary and stable (see 6.0 - Installation Drawings).

1.6 Mechanical Considerations

The NX is constructed with a steel frame and removable panels. Top and side panels are secured to the chassis by screws. The doors may be opened for access to power connections bars, auxiliary termi­nals blocks and power switches.
The UPS comes with an operator control panel, which provides basic operational status and alarm information. The cabinet houses both the power components and the internal batteries. Cooling is provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the UPS from moving once it has been moved to its final position.
6
Page 15

1.6.1 Clearances

There are no ventilation grilles on the sides or rear of the UPS. The sides must be accessible during installation. After installation, the unit may be placed with the rear against a wall and optional cabi­nets on either side.
To enable routine tightening of power terminations within the UPS, make sure there is sufficient clearance in front of the NX to permit free passage of personnel with the door fully opened.
Leave a minimum of 2 ft. (610mm) between the top of the UPS and the ceiling to permit adequate air circulation above the unit. Liebert recommends against using air conditioning or other systems that blow air onto the top of the unit.

1.6.2 Floor Installation

The diagrams in 6.0 - Installation Drawings show the location of holes in the base plate for bolting the equipment to the floor. An optional anchoring kit is available. For information, see your local Lie­bert representative.
If the equipment is to be placed on a raised floor, it should be mounted on a pedestal that will support the equipment point loading. Refer to the bottom view in Figure 30 to design this pedestal.

1.6.3 Cable Entry

Cables can enter the NX from the top or bottom. Cable entry is made possible by removing a metal plate attached to the UPS.
These plates are designed to allow the personnel to punch holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS.
Installation
Connecting cables to the NX may require that the UPS be accessible from the left side to allow per­sonnel to complete the connections and make necessary adjustments. After installation is complete, the NX may be serviced from the front.
NOTE
When installing the UPS, the customer must provide a disconnect with overcurrent protection at the output of the UPS.
10-30kVA UPS
The 10-30kVA NX consists of a single cabinet housing the UPS components and the internal battery string.
Optional battery cabinets are available to provide extended run time. Each cabinet houses additional strings of batteries that operate in parallel with the NX’s internal batteries. The cabinets are designed to be bolted to the right side of the UPS (see Figure 1). Refer to 3.4 - External Battery Cabinet Installation for details.
Optional maintenance bypass/transformer cabinets (MBC-T) are available. These cabinets house the components necessary to:
• Provide an external wrap-around maintenance bypass switch for servicing the UPS
• Provide voltage transformation for site or application requirements
• Provide a means for neutral isolation and allow installations for site without a neutral conductor
MBC-T cabinets are designed to be bolted to the left side of the UPS (see Figure 1). Refer to 4.5 -
Locating the Cabinet, for further details.
System Composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements—e.g., UPS cabinet and External Bypass cabinet. In general, all cabinets used will be the same height and are designed to be positioned side-by-side to form an aesthetically appeal­ing equipment suite.
7
Page 16

1.6.4 Optional Cabinets

If your NX installation includes a Maintenance Bypass Cabinet, the NX must be positioned to allow the Maintenance Bypass Cabinet to be bolted to left side of the NX (see Figure 1). Cables from the Maintenance Bypass Cabinet must be brought through the bottom side of the NX for connection.
The Maintenance Bypass Cabinet must be cabled and bolted to the NX before the UPS and bypass cabinet are moved into their final position. Connect the input wiring to the Maintenance Bypass Cab­inet ONLY after the units are connected and positioned.
Battery cabinets may be bolted to either side of the NX, unless used in configurations that include a Maintenance Bypass Cabinet. If used with a Maintenance Bypass Cabinet, battery cabinets must be installed on the right side of the UPS; see Figure 1 below.
Figure 1 Cabinet arrangement
Installation
ALL UNITS VIEWED FROM ABOVE
Liebert
Maintenance
Bypass Cabinet
NX connected only to MBC
(MBC must be on left side of the NX)
NX
(Battery Cabinets may be on either side of the NX)
Maintenance
Bypass Cabinet
NX connected to Maintenance Bypass Cabinet and Battery Cabinets
(MBC must be on left side of the NX)
(Battery Cabinets must be on the right side of the NX in this
Liebert
NX
Battery
Cabinet
NX connected to Battery Cabinets
Liebert
NX
configuration)
Battery
Cabinet
Battery
Cabinet
Battery
Cabinet
8
Page 17

2.0 ELECTRICAL CONNECTIONS

The UPS requires both power and control cabling once it has been mechanically installed. All control cables must run separate from power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected.
WARNING
!
Before connecting input power to the NX, ensure that you are aware of the location and operation of the overcurrent protection devices that connect the UPS input/bypass supply to the power distribution panel.
De-energize and lockout or tagout all incoming high- and low-voltage power circuits before installing cables or making any electrical connections.

2.1 Power Cabling

2.1.1 Cable Rating

The main factors affecting the choice and size of cable are voltage, current (also taking into account overcurrent), room temperature and conditions of installation of the cable.
The power cables of the system must be sized with respect to the following description:
UPS input cables - The UPS input cables must be sized for the maximum input current, includ­ing the maximum battery recharge current, given in Table 27, with respect to the unit rating and the input AC voltage.
UPS bypass and output cables - The bypass and output cables must be sized for the nominal output current, given in Table 27, with respect to the unit rating and the output AC voltage.
Battery cables - Each UPS unit has its own internal batteries factory-wired. If connecting an external battery cabinet, the battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in Table 27, with respect to the unit rating.
Electrical Connections
NOTE
Table 27 gives nominal currents for determining the size of UPS power cables. Other important factors to consider include cable route length and coordination with protective devices.
The power cables can be sized to suit the UPS unit rating according to Table 27.
Lug Size and Torque Requirements
Refer to Table 33 for lug size and torque requirements.
9
Page 18

2.1.2 UPS Input Configuration

Figure 2 illustrates the NX in a split bypass (dual-input) configuration. In this configuration the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main input. Both sources must be protected externally with properly sized protective devices. By default, the unit ships with internal links installed between the Bypass input and Main input (single-input configuration). To wire the unit as a dual input UPS, remove the links and wire the bypass to the input bus bars, then wire the Main input directly to CB1 (see Figure 3).
Figure 2 Single module block diagram—dual input configuration
Electrical Connections

2.1.3 Cabling Guidelines

The following are guidelines only and are superseded by local regulations and codes of practice where applicable. Use wiring rated at 75°C or greater.
1. Take special care when determining the size of the neutral cable, as current circulating on the neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the values in 10.4 - UPS Electrical Characteristics.
2. The ground conductor should be sized according to such factors as the fault rating, cable lengths and type of protection. The ground cable connecting the UPS to the main ground system must follow the most direct route possible. Control wiring and power wiring must be run in separate conduit. Output and input cables must be run in separate conduit.
3. Consider using paralleled smaller cables for heavy currents—this can ease installation.
4. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current ratings in Table 27. For terminal connection sizing, see Table 27.
5. In most installations, especially parallel multi-module systems, the load equipment is connected to a distribution network of individually protected busbars fed by the UPS output, rather than connected directly to the UPS itself. When this is the case, the UPS output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.
NOTE
If more load is added to the distribution panel, the unit’s cabling must be resized.
6. When laying power cables, do not form coils; this will help avoid increasing formation of electromagnetic interference.
NOTE
Left-side access may be required when making power connections. Cable connections should be made before a cabinet is attached to the left side of the NX or before the UPS is placed where another obstruction, such as a wall, is against the NX’s the left side.
10
Page 19

2.1.4 Cable Connections

The rectifier input, bypass and output are easily accessible from the left side of the unit for installa­tion. All require lug type terminations. They are connected to busbars on the left side of the NX and below the switch, as shown in Figure 3. These busbars are accessible when the left side panel is removed. Busbars to connect external batteries are accessible from the front of the UPS.
NOTE
External battery connection access requires removal of a protective panel on the lower front of the UPS to the left of the bottom two battery shelves.
Figure 3 Input busbars
Electrical Connections
Remove these links for dual input configuration and wire UPS Main input directly to CB1
Output Busbars (Phases are indicated by letters below the bars)
CB
OUTPUT BYPASS
The internal batteries are connected with Anderson connectors inside the battery compartment. The batteries are connected to fuses to protect the NX and connected equipment (see Figure 4).
Figure 4 Battery fuses and connections
Rectifier Input Busbars (Phases are indicated by letters below the bars)
ACBA
Internal battery input
connections
150A 500V AC/DC
B
Bussmann
MADE IN USA
11
150A 500V AC/DC
B
Bussmann
MADE IN USA
Battery fuses (fuses are behind access plate on front of UPS; see Note on page 11)
Page 20

2.1.5 Safety Ground

The safety ground busbar is located below the neutral input and output busbars as shown in Figure 5 below. The safety ground cable must be connected to the ground busbar and bonded to each cabinet in the system.
All cabinets and cable conduit should be grounded in accordance with local regulations.
WARNING
!
Failure to follow proper grounding procedures can result in electric shock hazard to personnel or the risk of fire, should a ground fault occur.
NOTE
Proper grounding significantly reduces problems in systems caused by electromagnetic interference.
NOTE
The ground and neutral busbars are easily accessible when the left protective cover plate is removed. Cable connections should be made before a cabinet is attached to the left side of the NX or before the UPS is placed where another obstruction, such as a wall, is against the NX’s the left side.
Figure 5 Ground and neutral busbar connections
Electrical Connections
Output neutral busbar
Ground
busbar

2.1.6 Protective Devices

For safety, it is necessary to install circuit breakers in the input AC supply and external battery bat­tery cabinets, external to the UPS system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation engineers with knowledge of operating prac­tices, regulatory standards and the equipment to be installed.
UPS Rectifier and Bypass Input Supply
Protection from excessive overcurrents and short circuits in power supply input External overcurrent protection for the AC output circuit is to be provided. See 10.4 - UPS Elec-
trical Characteristics and Table 29 for overload capacity. High-speed fuses and SCRs are used for internal battery circuit overcurrent protection. When an
external battery supply is used, overcurrent protection for the battery circuit is to be provided by the customer.
• Dual Input
When wiring the UPS with dual inputs, the Rectifier input and the Bypass input must be pro­tected separately. Size the breakers according to the input currents shown in Table 27.
OUTPUT
NEUTRAL
INPUT
NEUTRAL
Input neutral busbar
System Output
When using an external distribution panel for load distribution, the output neutral and input neutral must be separated at the input to the UPS.
12
Page 21

2.1.7 Cabling Procedure

CAUTION
!
The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulties, contact your local Liebert representative or Liebert Global Services.
NOTE
Hydraulic pressure pliers, combinative tools and piston ring pliers should be used to connect AC wiring.
Once the equipment has been positioned and secured for operation, and the battery and ground col­lars have been connected (see 2.1.4 - Cable Connections), connect the power cables as described below. (Study the reference drawing in 6.0 - Installation Drawings.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections.
2. Remove the left side panel to gain easier access to the connections busbars.
3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar located on the bottom of the equipment below the power connections. All cabinets in the UPS system must be connected to the user’s ground connection.
NOTE
The grounding and neutral bonding arrangement must comply with the National Electrical Code and all applicable local codes.
Electrical Connections
4. Identify and make power connections with incoming cables according to Steps 5 through 11.
Common Input Connections
5. For common bypass and rectifier inputs, connect the AC input supply cables between the power distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to 44 lb-in. (5 N-m) using the M6 bolt provided.
6. The input neutral cable must be connected to the input neutral busbar (N). See Figure 5.
Dual Input Connections
7. For bypass connect the AC input supply cables between the power distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to 44 lb-in. (5 N-m) using the M6 bolt provided.
8. For Rectifier Input connect AC input supply cables between the power distribution panel and the UPS input circuit breaker (A-B-C terminals)
9. The bypass and rectifier input neutral cables must be connected to the input neutral busbar (N). See Figure 5.
NOTE
Both the rectifier and bypass feeds MUST come from the same utility source, except if the UPS system includes either a configuration F or P external maintenance bypass cabinet.
Output System Connections—Ensure Correct Phase Rotation
10. Connect the system output cables between the UPS output busbars (A-B-C N terminals) and the critical load and tighten the connections to 44 lb-in. (5 N-m) (M6 bolt).
WARNING
!
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, then ensure that the system output cables are safely isolated.
13
Page 22
Internal UPS Battery Connections
The UPS internal batteries will be connected at the factory, EXCEPT the Anderson connections between the shelves and to the fuses.
WARNING
!
The DC bus is live when this internal battery connection is made. This connection is to be performed ONLY by Liebert Global Services at startup.
Observe the battery cable polarity. Be sure that the battery connector is made with the cor­rect polarity.
11. Refit all protective covers removed for cable installation

2.2 Control Cables

2.2.1 Monitor Board Features

Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker, battery temperature sensor), communicate with a personal computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO). The monitor board, arranged for this purpose, is located on the rear of the operator access door. The main features are:
• Input and Output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
• Intellislot™ interface
• Modem interface
• Temperature detect interface
Figure 6 shows the relationship and connection between the monitoring (U2) board and other boards in the UPS.
Figure 6 Monitor board U2
Electrical Connections
M5
Auxiliary Power
U1
DSP Control
U2
Monitor Board
X1
User Interface
Board
K1
Key & LED Board
M3
Parallel Logic
Board
14
Page 23
Figure 7 Auxiliary terminal block detail (Monitoring Board)
J8
J3
LCD
J1
J22
Electrical Connections
X7
J2
J13 J21 J25 J28 J4 J26 J30 J10
BFP INV ACF EPO Dry in MBC BCB
X1
X2

2.3 Dry Contacts

The UPS provides input dry contacts and output dry contacts.

2.3.1 Input Dry Contacts

There are several input dry contacts at the X3 slot.
X3
Intellislot 2
Intellislot 1
Intellislot 3
J23
J12
J9
J15
J16
J17
X4
X6
PWR MODEM SNMP CARD
X5
X4
J24
NOTE: The black square () on each slot indicates Pin 1.
Figure 8 Input dry contacts
Table 1 Input dry contacts at X3
Position Name Description
J4.1 ENV
J4.2 BtG Battery Ground Fault Detection (N.C.)
J4.3 GEN
J4.4 +12V +12V Power
1 - Must be configured by configuration software before becoming active. 2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off.
3
1,2
NOTE: The black square () on each slot indicates Pin 1.
Battery Room Alarm (N.C.)
Generator Join Detection (N.O.)
15
Page 24

2.3.2 Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.
Table 2 Maintenance bypass cabinet interface
Position Name Description
J26.1 T_IT
J26.2 AUX_I Reserved
J26.3 +12V +12V Power
J26.4 GND Power Ground
J30.1 FUSE Reserved
J30.2 F_FAN Fan Fail Alarm (N.C.)
J30.3 T_OT
J30.4 AUX_O Reserved
1 - Must be configured by software before becoming active
1
Input transformer over temperature (N.C.)
1
Output Transformer Overtemperature (N.C.)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 82 and 197 feet (25-60m), respectively.

2.3.3 BCB Box Interface

Electrical Connections
J10 is the BCB box interface.
Table 3 BCB box interface
Position Name Description
J10.1 DRV BCB Driver Signal - Reserved
J10.2 FB BCB Contact State
J10.3 GND Power Ground
J10.4 OL
BCB On-Line - Input - This pin will become active when BCB interface is connected. (N.O.)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 82 and 197 feet (25-60m), respectively.
NOTE
If BCB interface is connected, a jumper needs to added between Pin 3 and Pin 4.
Figure 9 Jumper connection for BCB interface
UPS Monitoring Board
J10
OL
OL
FB
DRV
GND
Aux – N.O.
Aux – N.O.
Battery Circuit Breaker
16
Page 25

2.3.4 Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 10 and Table 4).
Figure 10 Output dry contacts and EPO wiring for firmware before M170
Electrical Connections
+12V
J13
BFP_S
BFP_C
BFP_O
Table 4 Output dry contact relays
Position Name Description
J13.2 BFP_O Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J13.3 BFP_S Bypass feedback protection relay center
J13.4 BFP_C Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.
J21.2 INV_O Inverter mode relay. Normally open. Closed when UPS is in inverter mode.
J21.3 INV_S Inverter mode relay center
J21.4 INV_C Inverter mode relay. Normally closed. Open when UPS is in inverter mode.
J25.2 ACF_O Main input fault relay. Normally open. Closed when main input is in fault.
J25.3 ACF_S Main input fault relay center
J25.4 ACF_C Main input fault relay. Normally closed. Open when main input is in fault.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 82 and 197 feet (25-60m), respectively.
2.3.5 EPO Input—Optional
J21 J25 J28
EPO-H
INV_S
INV_C
INV_O
ACF_C
ACF_S
ACF_O
X2X1
EPO-L
Firmware Before M200
The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 10, is the remote EPO input interface. It is active when shorted from EPO-L to EPO-H.
If an external Emergency Stop facility is required, it is connected terminals EPO-L to EPO-H of the auxiliary terminal block (X2). It also is connected to the Normally Open remote stop switch between these two terminals using shielded cable (see Figure 10 and Table 5). If this function is not used, terminals EPO-L to EPO-H must be opened.
Table 5 EPO input contact relays
Position Name Description
J28.2 EPO_L Emergency Power Off Low
J28.4 EPO_H Emergency Power Off High
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply.
To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
17
Page 26
Firmware M200 or Later
The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 11, is the remote EPO input interface. The EPO has a NO/NC contact point becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1.
If an external Emergency Stop facility is required, it is connected terminals X2: 1&2 or X2: 3 and 4 of the auxiliary terminal block (X2). It also is connected to the Normally Open or Normally Closed remote stop switch between these two terminals using shielded cable (see Figure 11 and Table 6). If this function is not used, terminals X2: 3 and 4 must be opened and X2: 1 and 2 must be closed.
Figure 11 EPO wiring for firmware M200 or later
Electrical Connections
J2 8
EPO - NO
EPO - NC
Table 6 EPO input contact relays
Position Name Description
J28.1 EPO_NC EPO Activated when opened to J28.2
J28.2 EPO_NC EPO Activated when opened to J28.1
J28.3 EPO_NO EPO Activated when shorted to J28.4
J28.4 EPO_NO EPO Activated when shorted to J28.3
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally Closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor board and must remain installed if using NO contacts.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 82 and 197 feet (25-60m), respectively.
X2
18
Page 27

3.0 BATTERY INSTALLATION

3.1 Introduction

Liebert recommends that the batteries in external cabinets match the internal batteries in the NX in manufacturer and type.
If using multiple sets of batteries connected in parallel to provide the required battery backup run times, fit each set with an isolating device to permit working on one of the battery sets while leaving the others in service and providing backup protection.
When replacing batteries, replace with the same manufacturer and type, or equivalent. See your Lie­bert representative for a list approve batteries.
NOTE
The NX, as shipped, has 24 12-volt batteries installed internally in each unit.

3.2 Safety

Special care should be taken when working with the batteries associated with the NX system equip­ment. When all batteries are connected together, the battery terminal voltage may exceed 324V and is POTENTIALLY LETHAL.
Battery Installation
WARNING
!
The NX's internal batteries are connected and energized even if the UPS is turned Off. To minimize the risk of injury, a qualified service person should disconnect internal batteries before any maintenance is performed on the unit.
The center of the battery is connected to the neutral of the UPS and is grounded. A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.

3.3 UPS Batteries

The NX's internal batteries are fully charged before the unit is shipped. During storage and transpor­tation, some charge is lost. All batteries should be recharged before use. The battery charger works only when the NX is connected to input power and turned On.
NOTE
Full safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturer's manuals, available on the manufacturer's Web site.
The battery safety information contained in this section relates to key considerations that must be taken into account during the installation design process and might affect the design outcome, depending on your installation.
19
Page 28

3.4 External Battery Cabinet Installation

3.4.1 Matching Battery Cabinets

Two sizes of optional battery cabinets are available. Refer to Figures 13 and 14. The same model bat­tery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on the cabinet model, the number of cabinets and the load on the UPS.
Handling—The battery cabinet has casters to facilitate movement over short distances. The bottoms of the battery cabinets are reinforced to permit movement by forklift over longer distances.
Inspection—Remove all panels and visually inspect the batteries, bus connections, and cabinet for any damage. Exercise caution; voltage is present within the battery cabinet even before installation. If there are signs of damage, do not proceed. Call Liebert Global Services at 1-800-542-2378.
Storage—The batteries can be stored for up to six months without appreciable deterioration. If plan­ning to store a battery cabinet for longer than six months or at temperatures higher than 77°F (25°C), contact Liebert Global Services for recommended precautions.
The following notes, in conjunction with the diagrams (Figure 13 through 12), illustrate the broad principles to be followed when fitting and connecting the majority of battery cabinet installations.
CAUTION
!
Any battery system should be installed by qualified personnel.
When installing an external battery cabinet that is NOT a Liebert NX battery cabinet, the customer must provide overcurrent protection. See Table 27 for sizing of protection devices.
Battery Installation
NOTE
When using an external battery supply that is not provided with the UPS, please make reference to the battery manufacturer’s installation manual for battery installation and maintenance instructions, available on the manufacturer’s Web site. When replacing batteries, Liebert recommends that the batteries in external cabinets be the same type used internally in the NX. See Table 28 for a list of batteries that are approved for use with this product.

3.4.2 Connecting the Batteries

If the NX battery cabinets are installed on a raised floor, the battery power cables and circuit breaker control cables may be routed to the UPS cabinet via the floor of the cabinet (bottom entry).
If the NX battery cabinets are installed adjacent to one another on a solid floor, these cables may be passed between the cabinets through lifting slots in the lower sides of the cabinets.
Intertray connections must be made before the battery cabinet may be used.
Figure 12 Battery cabinet—details
Removable retainer
Tray handle
20
Insulated post for cabling
Page 29
Figure 13 Narrow battery cabinet, 27 in. (690mm) - rear view
Top cable entry
Battery trays
Battery Installation
BCB plate and BCB
Figure 14 Wide battery cabinet, 57 in. (1488mm) - front view
Top cable entry
Battery tray support
Battery tray
Batteries
BCB plate and BCB
Service shelf
21
Page 30

3.4.3 Installation Considerations

Position—Liebert battery cabinets come in versions specific to either the left or right side of the UPS. Control wires and power cables are cut to different lengths for the different versions. If the sys­tem includes a matching maintenance bypass cabinet (MBC), the MBC should be mounted to the left of the UPS (nearest the busbars) and the battery cabinet(s) should be installed to the right of the UPS. Otherwise, left-side placement of the battery cabinet is preferable.
The battery cabinet(s) are designed to be located conveniently next to each UPS module, and are also available in stand-alone configurations with painted side panels. The front access design eliminates side and rear service clearance requirements. Refer to Table 39 for battery cabinet dimensions and weights.
Bolt-On Cabinets—Matching battery cabinets are designed to bolt onto the side of the UPS module cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in the front and two places in the rear.
Service Clearance—Allow front access to the battery cabinet at all times for maintenance and ser­vicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of clearance at the front of the cabinet when operating. Side and rear panels do not require service clear­ance.
Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet, eliminat­ing the need for external conduit runs. Route cables before moving cabinets into final position for bolt­ing together. No top or bottom entry cables are required, except for remotely located cabinets which require conduits. Refer to Figure 15.
Software—To allow the UPS to accurately display the battery run time, the number of battery cabi­nets must be noted when performing initial startup and setup using the configuration software. This is to be performed by the Liebert Global Services customer engineer when commissioning the unit.
Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet.
Battery Support Tray—Be sure to connect the battery tray support to the front of the cabinet before sliding a battery tray out for connection or service. Without the support, the battery tray may fall out of the cabinet. See Figure 16 for details.
Battery Installation
22
Page 31
Figure 15 Internal cable wiring from battery cabinet to Liebert NX
Power cables from output power switch
Battery Installation
Power cables from batteries
BATTERY CABINET
Power cables (black) enter channel down side of NX to power input connections
LEFT SIDE INTERIOR OF UPS
Power cables exit battery cabinet, enter Liebert NX
Power cables run across top of Liebert NX
RIGHT SIDE INTERIOR OF UPS
RIGHT SIDE CABLE ENTRY SHOWN; CUTOUTS ON LEFT SIDE PERMIT CONNECTION FROM THAT SIDE.
Figure 16 Battery tray and supports
Slot in support secured by screw-in connector at corner of battery tray ...
... and notched end of support slips into slot at top corner of battery compartment
Battery tray supports attach to interior surface of NX front door (note notched ends of supports)
23
Page 32

3.4.4 Connecting the Battery Cabinet to the UPS

After the battery cabinet equipment has been positioned and secured for operation and the batteries have been connected, connect the power cables as described below. (See Figure 36.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections.
2. Remove the UPS left side panel to gain access to the equipment ground busbar.
3. Remove the external battery terminal block plate on the lower left side of the UPS behind the front door.
4. Remove the battery cabinet front panel to gain access to the connection bars.
5. Connect the safety ground and any necessary bonding ground cables to the copper ground busbar. (example: UPS located on the bottom of the equipment below the power connections).
All cabinets in the UPS system must be connected to the user's ground connection.
NOTE
The grounding and neutral bonding arrangement must be in accordance with the National Electrical Code and all applicable local codes.
6. Connect the system battery cables from the UPS battery terminals (+ N -) to battery cabinet BCB (+ N -) as shown in Figure 36. Be sure that the battery connections are made with the right polarity, and tighten the connections to 44 lb-in. (5 N-m) (M6 Bolt). Do not close the battery circuit breaker before the equipment has been commissioned.
7. Connect supplied auxiliary control cable to pins J10.2 and J10.3 on the U2 monitoring board (see
2.3 - Dry Contacts). Add a jumper wire between J10.3 and J10.4.
Battery Installation

3.5 Non-Standard Batteries

When batteries other than a matching battery cabinet are used, a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Contact your local Liebert sales representative about this option.
Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions.
Verify that the battery area has adequate ventilation and battery operating temperature complies with the manufacturer's specifications and with all applicable national and local codes.
If you have any questions concerning batteries, battery racks or accessories, contact Liebert Global Services at 1-800-543-2378.
24
Page 33
Maintenance Bypass Cabinet

4.0 MAINTENANCE BYPASS CABINET

The Maintenance Bypass Cabinet is designed to operate in UPS mode, bypass mode and maintenance mode. The mode is selected using the Bypass Switch.
Figure 17 Single UPS with external Maintenance Bypass Cabinet—typical configuration

4.1 Bypass Switch

The Bypass Switch allows easy and rapid transfer of connected loads between the UPS and Bypass source.

4.2 Normal (UPS) Mode

While the Maintenance Bypass Cabinet rotary switch is in the NORMAL position, the UPS is supply­ing the connected load with continuous, high-quality AC power. In this mode of operation, the load is protected by the UPS.
25
Page 34

4.3 Bypass Mode

When the Maintenance Bypass Cabinet is in the Bypass mode, it provides an alternate path for power to the connected equipment. Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the UPS inverter to the bypass source. In this mode, power will still be supplied to the UPS; however, the load is NOT protected by the UPS.

4.4 Maintenance Mode

When the maintenance bypass cabinet is in the Maintenance mode, it provides an alternate path for power to the connected equipment. Should the UPS need to be taken out of service for limited mainte­nance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT pro­tected by the UPS.

4.5 Locating the Cabinet

This Maintenance Bypass Cabinet may be mounted to the left of the UPS or installed as a stand-alone unit. In either case, ensure that the unit is in a well-ventilated area and that there is clearance for access to the switches and cable connections as required by national and local codes.

4.6 Cable Installation

4.6.1 Wiring Preparation

Maintenance Bypass Cabinet
Be sure that the unit is not connected to any AC utility power source or UPS before installing any wir­ing to this unit. This Maintenance Bypass Cabinet should be installed by a qualified / certified electri­cian.
WARNING
!
Please read this section thoroughly before attempting to install wiring to this unit.
Removing the Cover Plates
Plates cover the input and output terminals on the front of the Maintenance Bypass Cabinet (see Figure 18). Remove these and keep the screws and plates for reinstallation.
Figure 18 Maintenance Bypass Cabinet—access plate removed
Extract screws from corners to remove the access plate
26
Page 35

4.6.2 Power Cable Installation

Refer to Tables 35, 36 and 38 when selecting cables.
NOTE
Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices because these will carry the earth leakage currents of both the UPS equipment and the load.

4.6.3 Input/Output Wiring

Follow the steps below to connect the input wiring:
NOTE
Input wiring must be installed using conduit if cabinet is not mounted to the immediate left of the UPS.
1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch the appropriate size hole for the size conduit being used. Pull the three/four input wires through it, allowing some slack for installation. For cabinets that are located to the immediate left of the UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that the edge guarding is installed and intact.See Figure 19.
Figure 19 Maintenance Bypass Cabinet wiring access panel
Maintenance Bypass Cabinet
Wiring access is on lower right side of Maintenance Bypass Cabinet
Access panel removed; wiring connects NX and MBC
Edge Guard
2. Secure the conduit to the access plate of the Maintenance Bypass Cabinet.
3. Input power cables connect to the system input circuit breaker. Refer to Figure 37 -
Maintenance Bypass interconnection
4. Connect the ground (earth) wire to the earth busbar and tighten it to 44 lb-in. (5 N-m) (M6 bolt).
5. Locate UPS input and output cables and access panel to UPS on lower right side. See Figure 19.
NOTE
If the maintenance bypass cabinet is not to be bolted to the UPS, use either top or bottom access plate.
6. Connect the system ground cable between the Maintenance Bypass Cabinet and UPS and tighten the connections to 44 lb-in. (5 N-m) (M6 bolt).
27
Page 36
7. Connect the system input cables between the Maintenance Bypass Cabinet 'UPS Input' Busbars (A-B-C N terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to 44 lb-in. (5 N-m) (M6 bolt).
8. Connect the system outnput cables between the Maintenance Bypass Cabinet 'UPS Output' Busbars (A-B-C N terminals) and UPS output busbars (A-B-C N terminals) and tighten the connections to 44 lb-in. (5 N-m) (M6 bolt).
9. Connect supplied control wire to X3 on the Parallel (M3) board (see Figure 20).
WARNING
!
The control wire must be installed to ensure proper operation of the system and fully protect the load when switching between bypass cabinet and UPS.
Figure 20 Maintenance bypass control wire location
Maintenance Bypass Cabinet
:X T M AIN T
485-
485+
Terminal
P2 X2
2
Block Location
P1 X2
1
X3
DBS
NOTE
For startup procedure, see the UPS operations and maintenance manual, SL-25210.
28
Page 37

4.7 Bolting Cabinets Together

NOTE
UPS wiring must be completed before the cabinets are bolted together.
1. Line up cabinets so that mounting holes are aligned.
Maintenance Bypass Cabinet
Place cabinets so mounting holes are aligned. A bolt from the adjacent cabinet may be screwed into the threaded top hole, or a bolt may be inserted through the lower hole and screwed into the threaded hole in the adjacent cabinet.
2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the UPS side or from the MBS side, whichever is more convenient.
29
Page 38

5.0 OPTION INSTALLATIONS

5.1 Load Bus Synchronization

The Load Bus Synchronizer (LBS) keeps the output of two independent UPS systems or parallel UPS systems in synchronization even when the systems are operating in different modes and even when either or both systems are operating on batteries. When the LBS is used, one UPS system is desig­nated as master, the other as slave.
The LBS option is typically used with dual-corded equipment or with either the Liebert SmartSwitch or Static Transfer Switch (STS) for single-corded equipment.

5.1.1 Performance Requirements

The DBS operates under the following conditions:
• Both master and slave are on inverter (either system may be on inverter through the rectifier or on inverter through the batteries)
• Master on inverter, and slave on bypass
• Master on bypass, and slave on inverter
• Master and slave on bypass IF the bypass source is the same for both systems

5.1.2 DBS Cable and Settings

For NX-to-NX dual bus configuration, only one optional LBS cable is required, the built-in LBS will operate normally without extra LBS control box or interface box. The LBS port is X4 on the parallel board (M3). The parallel board is on the interior of the NX, above and left of the power electronics; see Figure 32.
Option Installations
An optional, 9-pin LBS cable is used to connect two UPS systems through each system’s DB9 port on its parallel board. For two parallel systems, the LBS cable can be mounted between any two units belonging to different parallel systems. For information about the LBS kit or to order the optional equipment, see your local Liebert representative.
The LBS cable is connected as illustrated in Figure 21.
Figure 21 Load Bus Synchronization cable connection
LBS Cable
Parallel Board
X3
X4
X2-1 X2-2
X1-1 X1-2
Parallel Board
X4
X2-1 X2-2
X1-1 X1-2
The parallel board is on the interior of the NX, above and left of the power electronics; see Figure 32
UPS Module or
System #1
UPS Module or
System #2
The LBS function is activated with configuration software; when the LBS takes effect, the graphic LCD will display “LBS active.”
30
Page 39

5.2 Configuring Parallel System Operation

5.2.1 General

The NX uses intelligent and reliable decentralized technology to achieve parallel operation of two or more modules of the same rating.
The 1+N system is used to:
• Increase the reliability of the system to ensure adequate power supply to the critical load con­nected.
• Increase serviceability and allow the execution of maintenance operations and reparations with­out affecting the ordinary operating conditions of the system (depending on the redundancy level).
Option Installations
31
Page 40

5.2.2 Features of Parallel System

• The hardware and firmware for parallel UPS module operation is standard in the NX, and the configuration can be set up by changing the settings in configuration software.
• It is easy to install the parallel cables in a ring, providing high reliability and redundancy. And the intelligent paralleling logic provides the user with maximum flexibility. For example, shut­ting down or starting up the UPS modules in the parallel system can be done in any sequence. If an overload transfer occurs, the whole system can recover automatically from bypass mode after the overload is cleared.
• The total load of the parallel system can be queried from each module’s liquid crystal display screen.
Figure 22 1+N system block diagram
Option Installations
CB1
208V 60Hz 4W
CB3 CB4
CB5 CB6
4W
UPS1 208V 60Hz
4W
UPS2 208V 60Hz
CB2
208V 60Hz 3 or 4W
CB7 CB8
NOTES:
1. Install in accordance with national and local electrical codes.
2. The equipment ground connection must be connected to the system ground wire.
3. UPS AC input and AC output cables must be run in separate conduits.
4. Control wiring and power wiring must be run in separate conduits.
5. See Electrical Data Specification Sheet U3818101 for individual configurations.
4W
UPS3 208V 60Hz
32
Page 41

5.2.3 Operating Principles

Redundancy Paralleling
The 1+N parallel redundant system can noticeably improve system reliability. In normal condition, none of the UPS modules work at full load. That means that even if the load is increased, the system will not transfer to bypass. And when a UPS module shuts down due to any failure, the remaining UPS modules can still power and protect the load. When redundancy is lost due to module failure or load increase, the parallel system will trigger an alarm.

5.2.4 Operation Modes Summary

The parallel system also has operation modes such as normal, battery, bypass and maintenance bypass. All UPS modules in the 1+N parallel system operate in coordination.
Normal Mode Operation The load is powered by the inverters of all the UPS modules in the system. If the frequency of
bypass is within the synchronous range, the inverter will be synchronized with the bypass. Other­wise, the system will operate at nominal frequency.
Battery Mode Operation The batteries of all UPS modules power the load through their inverters. The system operates at
nominal frequency.
Bypass Mode Operation The condition to transfer to bypass mode is essentially the same as that of single-module system.
The bypass of all the UPS modules powers the load.
Maintenance Bypass Mode Operation The sequence to transfer to maintenance bypass mode is the same as for transferring a single-
module system. The maintenance bypass switches should be switched on as synchronously as pos­sible. Thus the system can be repaired without interrupting the power supply to critical load.
Option Installations

5.3 Installing Parallel System

The basic installation procedure of parallel system is the same as that of single-module system. The following sections introduce only the installation procedures specific to the parallel system.

5.3.1 Conditions for Parallel System

• Each UPS module should have the same rating, the same firmware and hardware version.
• Each UPS module must have the same bypass source.
• The outputs of all UPS modules are connected altogether.
• The main inputs can be from different sources, but the phase rotation sequence of main inputs, bypass inputs and outputs must be correct and the same.
• The parallel logic cable and load sharing cable must be connected in a ring correctly (see Figure 23).

5.3.2 Cabinet Installation

Parallel system composed of two or more UPS modules using parallel cabinet
The UPS modules that will form the 1+N system should be placed side-by-side. Each battery cabinet is placed next to its corresponding UPS module.
The parallel cabinet should be placed in the middle of the system.

5.3.3 Preliminary Checks

Each UPS module should have the same rating, the same firmware and the same hardware version. Refer to the instructions in 5.3.1 - Conditions for Parallel System.

5.3.4 Protective Devices

For each UPS, refer to Table 27. For each system, refer to Table 37.
33
Page 42

5.3.5 Power Cables

Wiring of power cables is similar to that of single-module system (See 2.1 - Power Cabling). The bypass sources of all modules should be the same, and the outputs should be connected altogether cor­rectly.
Power cables will be supplied by customer. Power cables to the UPS’s of the 1+N paralleling cabinet must be routed through either the top or bottom entry access of the UPS.
For systems using a parallel cabinet, see Figures 38 and 40 through 42 for power cable terminations.
NOTE
The length and specifications of power cables including the bypass input cables and UPS output cables should be the same, thus the load can be shared evenly in bypass mode.

5.3.6 Parallel Control Cables

Parallel System Control Cables
Make the connections listed below on the parallel logic board (M3) inside the NX. (See Figure 32 for the location of the parallel logic board):
Shielded and double-insulated control cables available in lengths of up to 100 feet (30m) must be interconnected in a ring configuration between UPS modules as shown below. The ring configuration ensures high reliability of the control (refer to Figure 23).
See Figure 25 for dry contacts control cable wiring diagram.
Option Installations
Figure 23 Connecting '1+N' system parallel control cables
P5
X4
P4 P1
UPS
Parallel Board
X3
X2-2 X2-1
P2
X1-1 X1-2
P3
1 2 3 4
Parallel Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4 P1
P3
Parallel Board
X3
X2-2 X2-1
P2
X1-1 X1-2
P3
Auxiliary Dry Contact Cables
The external output breaker of each UPS must have Normally Open auxiliary contacts. These con­tacts must be wired to connector X3 on the Parallel Logic Board (M3). See Figure 24.
P5
X4
P4 P1
Parallel Board
X3
P5
X4
X2-2 X2-1
P2
X1-1 X1-2
P4 P1
P3
Interconnecting
Cables
34
Page 43
Figure 24 Auxiliary dry contact cables for output breaker in multi-module system
Option Installations
X3
DBS
:X T M AIN T
485-
485+
P2 X2
2
P1 X2
1
CAUTION
!
The auxiliary control wire must be installed to ensure proper operation of the system.
NOTE
For startup procedure, see the UPS operations and maintenance manual, SL-25210.
Figure 25 Dry contacts, multiple UPS modules with distribution panel
Input Distribution
UPS 1
M3 Board
X3
Ext. Maint. Ext. Out
QUPS
To Load
UPS 2
M3 Board
X3
Ext. Maint. Ext. Out
UPS N
M3 Board
X3
Ext. Maint. Ext. Out
Q1Ext Q2Ext QnExt
QByp
35
Page 44

5.3.7 Emergency Power Off (EPO)

The external emergency stop facility is identical to that described for the single-unit installation— that an individual emergency stop button is provided for each unit.
Figure 26 Connecting EPO push button
Option Installations
UPS2
Normally
Open EPO
Normally
Closed EPO
X2:3
X2:4
X2:1 X2:2
Monitor Board
UPS1
Monitor Board
UPS1
X2:3 X2:4
X2:1 X2:2
Monitor Board
UPS2
Monitor Board

5.4 Battery Circuit Breaker Box

The box contains the same battery isolating circuit breaker as mounted in the battery cabinet.
Two battery circuit breaker boxes are available for use in installations where the battery is not installed in the battery cabinet, in which case the appropriate battery box is fitted as close as possible to the battery and connected to the UPS equipment as illustrated in Figure 27.
The battery circuit breaker box, is required to protect the battery from overcurrents. It also provides electrical isolation between the UPS and the battery, permitting technical service personnel to reduce the risks involved in maintenance work to a minimum.
A separate safety earth must be connected between the UPS unit and circuit breaker box.
Two boxes are available depending on the UPS power rating.

Table 7 Available battery circuit breaker boxes

Dimensions (in)
UPS
10-15 kVA 32.25x20.25x8.3 70A
20-30 kVA 32.25x20.25x8.3 125A
The circuit breaker has the following features:
• Short-circuit protection.
• Protection against battery cabinet and ups connection errors (polarity reversal +/-).
H-W-D Circuit Breaker
36
Page 45

Figure 27 Battery circuit breaker box connections

Option Installations
3.9"
(98mm)
(3) 1/2" (12.7mm) dia. knockouts for control wiring conduit entry
2.5"
(63.5mm)
TB1
32.3"
(819.2mm)
10.8"
(274mm)
5.4"
(137mm)
Top View
(508mm)
(381mm)
Front View
20.0"
15.0"
4.0"
(101.2mm)
31.5"
(800.1mm)
8.3"
(211.7mm)
1 2 3 4 5 6
TB1
COM Black
N.O. Red
N.C. Blue
From Customer’s Battery System (field-supplied and field-installed)
Connect to UPS Module
(field-installed)
(-)
(+)
J10.2
J10.3
(GND)
Midpoint
Midpoint
(-) (+ )
Circuit Breaker
(-) ( +)
(-)
(+)
72 Cells
(+)
(-)
(-)
(+)
72 Cells
CB Load Side
CB Line Side
.31" dia.
(Typ. 4 places)
(7.9mm)
.38"
(9.5mm)
(3) 1/2" (12.7mm) dia. knockouts
Bottom View
for power wiring conduit entry (refer to top dimension)
NOTES:
1. NEMA 1 enclosure provided which is suitable for wall mounting only. Approximate weight is 60 lb.
2. Hardware for connecting cables to the breaker supplied.
3. Circuit breaker, Cutler-Hammer FD4125ED13D15A02 for 20/30 kVA; FD4070ED13D15A02 for 10/15 kVA
4. Color: IBM off-white.
5. Mount enclosure and pull all cables into enclosure before installing dry contacts.
6. Low voltage wiring needs to enter from the top of the enclosure, in separate conduit from power cables.
7. Line side power connections to lugs: (1) # 6AWG per connection for 10 to 15 kVA. (1) # 2AWG per connection for 20-30 kVA to lugs:. load side power connections to busbars; see detail.
8. Power cables must be sized to limit voltage drop from battery system to UPS to be a maximum 4 VDC.
.62"
(15.8mm)
NOTE
1. The signal cables in this figure must be shielded and double-insulated.
2. Connect the Pes (Protection Earth) of the UPS cabinet and BCB box to the same point.
.5"
(12.7mm)
1"
(25.4mm)
(11.8mm)
.47"
(11.8mm)
Midpoint Busbar Detail
DPN U3813078 Rev. N
1.93"
(49mm)
.46"
37
Page 46

5.5 Battery Start

With this option, the NX UPS can be started with power supplied only by the batteries (at charged condition). This type of start, in the absence of utility power, allows independent utilization of battery power and provides for higher availability in some circumstances.
CAUTION
!
Before attempting to start the UPS without utility power present, ensure that the batteries are fully charged—over 2.1V per cell—and will supply adequate run time to the load.

5.6 Remote Alarm Monitor

Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel which is driven by voltfree alarm status contacts (from an optional relay alarm board).

5.7 Analog Input Interface

At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is 2 percent. “ENV-T” is used for environment temperature detecting.

5.8 Power Output

The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to 12V. The maximum current is 500mA.
Option Installations

5.9 Intellislot™ Communication

The NX has three Intellislot ports to allow field-installation of optional communication cards. Intellis­lot cards communicate via Liebert’s proprietary ESP2 protocol to cards that translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide dry contact signals for external signaling of operating status.
The Intellislot communication ports may be installed or removed while the NX is operating..
38
Page 47
5.10 OC Web Card—SNMP/HTTP Network Interface Card
This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status information and all measured parameters for display via a Web browser.

Table 8 NX communication options

On the UPS
Physical
description
of port
Top
Intellislot
Middle
Intellislot
Bottom
Intellislot
Top
DB9 port
Bottom
DB9 port
Labeled
ID Name
of Port
Intellislot 1
(On Monitor Board)
Intellislot 2
(On Monitor Board)
Intellislot 3
(On Monitor Board)
RS232-1 Comm 1
RS232-2 Comm 2
LCD screen,
under Settings,
controlled by:
Comm 1
Comm 2
Comm 3
Monitoring
Devices
supported
Multiport 4 any
Relaycard-int any
OCWEB-LB
Modbus/Jbus 2400
Multiport 4 any
Relaycard-int any
OCWEB-LB
Modbus/Jbus 2400
Multiport 4 any
Relaycard-int any
OCWEB-LB 2400
Modbus/Jbus 2400
Multilink Serial
Service Software (Reserved)
Option Installations
Baud
rate Comments
2400
2400
9600
9600
Not simultaneous with Multilink in RS232-1
Not simultaneous with Multilink in RS232-2
Not simultaneous with Web card in top intellislot.
Not simultaneous with Web card in middle intellislot.
39
Page 48

5.10.1 Configuring Baud Rates

The default baud rate for Intellislots is 9600. To communicate with the OCWEB-LB, Modbus/Jbus, or the MultiLink cards, the baud rate must be set to 2400.
To change the baud rate (refer to Table 8):
1. Use the Navigation keys directly below the LCD to highlight the Settings Screen.
2. Press F1 to move the highlight into the Data & Settings area of the LCD.
3. Use the Navigation keys to scroll down to highlight the current baud rate across from the appropriate Comm Channel.
NOTE
The Comm channel settings are not immediately visible because of window-size constraints. Scroll down to view them on the screen.
4. Press the Enter (F4) key to select the Comm Channel to change.
5. Navigate to underline the desired baud rate (2400).
6. Press the Enter (F4) key to lock in the new baud rate.
Option Installations
40
Page 49
Figure 28 OC Web card display
Option Installations
41
Page 50

5.11 Relay Card

The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig- nals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A. and supported in any of the three Intellislot bays on the NX.

Table 9 Relay Card pin configuration

Pin Function Operation
1 UPS Fault Closed if no UPS failure
2-3 Not Used
4 UPS Fault Closed if UPS fails
5 Summary Alarm** Closed if SUMMARY ALARM** occurs
6 Summary Alarm** Closed if no alarm conditions are present
7 Any Mode Shutdown return Not supported – use External EPO terminal
8 Not Used
9 Common - Low Battery
10 Low Battery Closed if battery is OK
11 Low Battery Closed if LOW BATTERY point occurs.
12-13 Not Used
14 UPS Any Mode Shutdown Not supported – use External EPO terminal
15 On UPS Closed if ON UPS (inverter) power
16 On Battery Closed if ON BATTERY power (Utility failure)
17
18 On Battery Closed if not ON Battery power (Utility OK)
19±23 Not Used
24 On Bypass Closed if ON BYPASS
25 Not Used
**A Summary Alarm occurs when any of the following conditions exist:
1. Utility power is out of the acceptable range (voltage and/or frequency).
2. UPS is in BYPASS MODE (load not on Inverter power).
3. UPS Battery is LOW.
4. UPS fault has occurred.
Option Installations
Common - UPS Fault, Summary Alarm, On UPS, On Battery, On Bypass

Table 10 Relay card jumper configuration

Number Connection Description
JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together. ANY JP02 Pin 7 to Pin 17 REMOVE - (Interconencts all relay COMMONS and the (not
supported) MODE SHUTDOWN Return
42
Page 51

5.12 MultiPort 4 Card

The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical applicaton is to allow a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure-low battery) of a singleUPS.
This card is supported in any of the three Intellislot bays on the NX.

Figure 29 MultiPort 4 card pin assignment

Option Installations
UPS
CPU
CPU
CPU
CPU
Assignment
Pin
1 Low Battery
2Not Used
3Not Used
4Not Used
5Not Used
6Not Used
7 Low Battery Common
8 Utility Fail Common
9 Utility Fail
Description
43
Page 52

6.0 INSTALLATION DRAWINGS

The diagrams in this section illustrate the key mechanical and electrical characteristics of the NX UPS System cabinets.

Figure 30 Dimensional view- front and left side views

Installation Drawings
600
Monitoring Panel
1600
Air intake area. Do not block air filter.
90
FRONT VIEW LEFT SIDE VIEW
825
10mm dia. threaded mounting holes
Leveler
Detail “A” Rear of unit shown without side panel
Adjustable Stops (see Note 11)
1. All dimensions are in millimeters.
2. A minimum of 24 inches clearance above the unit is required for air exhaust.
3. Installation and service access required. Left-side access recommended for maximum ease of installation.
4. Keep cabinet within 15 degrees of vertical while handling.
5. Top and bottom cable entry available through removal access plates. Remove punch to suit conduit size and replace.
6. Unit bottom is structurally adequate for forklift handling.
7. Open door to replace air filter, washable type, size 354x314.
8. Threaded mounting holes used for seismic anchoring or floor stand. Note: If a floor stand is used, the weight of the unit must be supported under all casters.
9. Each mounting location is supported by two 10 GA. (.135”) galvanized steel. The threaded 12mm insert is approximately 3/4” deep. Mounting bolts must be threaded into unit.
10. Includes side panel. Refer to Detail A for dimension to frame with side panel removed. Side panels are removed between adjacent units that are bolted together.
11. Adjustable stops are not designed to carry the full weight of the cabinet. Finger-tighten stop against the floor, then tighten with a wrench less than two turns for friction against the floor.
44
Page 53
Figure 31 Dimensions continued—top and bottom views
A
Rear stabiliz­ing foot
Air Exhaust
Power Cable Entry Area
Top and Bottom
Installation Drawings
10mm dia. threaded mounting holes 4 (typ). See Notes 8 and 9 above.
Air
TOP VIEW BOTTOM VIEW
Figure 32 Main components—typical unit
Monitor Board (U2)
IntelliSlot Communication Ports
Input Breaker
Rotary System Switch
Input Breaker
ccess Plate
Parallel Board (M3)
Power Electronics
Battery Trays
Internal and External Battery Terminal Block Access Plate
Front View
(with door open)
DPN U3812048 Rev. 1
45
Page 54

Figure 33 Cable connections

Installation Drawings
AC output cable connections
Bypass AC input cable connections
Input Neutral Bus (side view)
Input/Output Neutral
Earth
Battery connections (+ N -)
4.1 to battery
4.2 to external battery cabinet
NOTES
Output Neutral Bus (side view)
Power Earth (side view)
1. All dimensions are millimeters.
2. Top and bottom cable entry available through removable access plates. Remove, punch to accommodate conduit size and replace.
3. Control wiring and power wiring must be run in separate conduit. Output and input cables must be run in separate conduit.
4. Aluminum and copper-clad aluminum cables are not recommended,
5. All wiring is to be in accordance with national and local electrical codes.
46
Page 55

Figure 34 Location of internal batteries

Installation Drawings
417mm
Battery
186mm
687mm
47
Page 56

Figure 35 Battery connections

TOP LAYER MIDDLE LAYER
W501 3pcs
Installation Drawings
DYNASTY BATTERY
+
W500 18pcs
+
+
+
W510 to W511 W502 to W503 W503 to W502 W504 to W505
W511 to W510
-
+
-
+
-
+
-
+
W507 to W506
-
W506 to W507
-
-
-
W509 to W508
+
+
+
+
BOTTOM LAYER
+
-
+
-
+
-
+
-
+
-
+
-
-
-
-
-
+
+
-
+
-
+
-
-
-N+
CON4
+
W505 to W504 W508 to W509
48
-
+
-
Page 57

Figure 36 Battery cabinet interconnection

Refer to Table 11 for key to interconnection
Positive (+)
Midpoint (N)
Negative (-)
Breaker
Connection
Detail
Detail
Positive (+)
Negative (-)
Midpoint (N)
Breaker
Detail
Installation Drawings
A
A
B
B
OR
A
UPS Module
Front View
with doors removed
27" Battery Cabinet
Front View
without doors and
protective plates
59" Battery Cabinet
Front View
without doors and
protective plates
NOTES:
1. All Liebert-supplied cable must be repositioned prior to and while the cabinets are being placed in their final installed location.
2. All interconnection hardware supplied by Liebert
3. All interconnection cables supplied by Liebert when bolted together.
4. Interconnection cables field-supplied when battery cabinets are stand-alone.
5. Refer to the individual drawing of each piece of equipment for additional details.
B

Table 11 Liebert -supplied interconnect wiring

Run From To Conductors
A UPS battery terminal block External 27" or 59" battery cabinet Positive, midpoint, negative
B Battery cabinet terminal block UPS monitor board Battery breaker aux contacts
49
Page 58

Figure 37 Maintenance Bypass interconnection

Refer to Table 12 for key to interconnection
Installation Drawings
Maintenance Bypass/Transformer Cabinet
front view without front door and panel
NOTES
left-side view without side panel
UPS Module
1. All Liebert-supplied cable must be repositioned prior to and while the cabinets are being placed in their final installed location.
2. All interconnection hardware supplied by Liebert.
3. AC connections must be made to the UPS module before attaching maintenance bypass/transformer cabinet to UPS module.
4. Utility AC source neutral not required for maintenance bypass/transformer cabinet types D, E, M, N.
5. All cabling will be field-supplied when maintenance bypass/transformer cabinet is configured as stand­alone cabinet.
6. Maintenance bypass/transformer cabinets must attach to the left side only.
7. Refer to the individual drawing of each piece of equipment for additional details.

Table 12 Liebert-supplied interconnect wiring for Maintenance Bypass Cabinet

Run From To Conductors
A Utility AC source Maintenance Ph A, B, C bypass/ transformer cabinet
B Utility AC source Maintenance Neutral bypass/ transformer cabinet
C Maintenance UPS module AC input Neutral - UPS Input
D Maintenance UPS module AC input Ph A, B, C - UPS Input
E UPS module AC output Maintenance Ph A, B, C - UPS Output
F UPS module AC output Maintenance Neutral - UPS Output
G Maintenance Load AC connection Neutral bypass cabinet
H Maintenance Load AC connection Ph A, B, C bypass cabinet
I Utility AC source All ground connections Ground
J Monitoring terminal block UPS Parallel Logic Board (M3) Bypass contacts
50
Page 59

Figure 38 NX 1+1 parallel cabinet interconnections

1+1 Parallel Cabinet
(Front View Without Front Door and Panel)
Installation Drawings
E1,E2
F1,F2
UPS Module Left Side View
(Without Side Panel)
C
K1,K2
D1,D2
I
D1
D2
F1, F2
G
Type A 00
J
D1
D2
H
B
I
F1,F2
G
Type BR0
J
K1
H
K2
I
A
D1
D2
G
F1,F2
Type DR1 & CR1
J
A
H
B
I
E1,E2
NOTES:
1. All Liebert-supplied cable will need to be repositioned prior to and while setting the cabinets in their installed location.
2. All interconnection cable and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules.
4. Utility AC source neutral not required for maintenance bypass/transformer cabinet type CR1.
5. Paralleling cabinets must between both UPS modules.
6. Refer to the individual drawing of each piece of equipment for additional details

Table 13 Liebert-supplied interconnect wiring

Run From To Conductors Cabinet Type
A Utility AC Source Paralleling Cabinet PH A, B, C - Bypass BR0, CR1, DR1
B Utility AC Source Paralleling Cabinet Neutral - Bypass BR0, CR1, DR1
C Utility AC Source UPS Module AC Input PH A,B,C - UPS A00, BR0
D1 UPS #1 Module AC Output Paralleling Cabinet PH A, B, C - UPS A00, BR0, CR1, DR1
D2 UPS #2 Module AC Output Paralleling Cabinet PH A, B, C - UPS A00, BR0, CR1, DR1
E Utility AC Source UPS #1 Module AC Input Neutral - UPS Input A00, BR0, CR1, DR1
E2 Utility AC Source UPS #1 Module AC Input Neutral - UPS Input A00, BR0, CR1, DR1
F1 Paralleling Cabinet UPS #1 Module AC Output Neutral - UPS Output A00, BR0, CR1, DR1
F2 Paralleling Cabinet UPS #1 Module AC Output Neutral - UPS Output A00, BR0, CR1, DR1
G Paralleling Cabinet Load AC Connection Neutral - Load A00, BR0, CR1, DR1
H Paralleling Cabinet Load AC Connection PH A, B, C - Load A00, BR0, CR1, DR1
I Utility AC Source All Ground Connections Ground A00, BR0, CR1, DR1
J Monitoring Terminal Block UPS Parallel Logic Board (M3) Auxiliary Contacts A00, BR0, CR1, DR1
K1 UPS #1 Module AC Input Paralleling Cabinet PH A, B, C - UPS CR1, DR1
K2 UPS #1 Module AC INPUT Paralleling Cabinet PH A, B, C - UPS CR1, DR1
51
Page 60
Figure 39 Lineup detail—SlimLine distribution cabinet to NX
Installation Drawings
E
H
G
H A C
B
D
D
G
E
H
NOTES:
1. All Liebert-supplied cable will need to be repositioned prior to and while setting the cabinets in their installed location.
2. All interconnection cables and hardware supplied by Liebert.
3. AC connections must be made to the UPS module before attaching.
4. See Figure 43 for placement of distribution cabinet.
5. Refer to the individual drawing of each piece of equipment for additional details.
Table 14 Liebert-supplied interconnect wiring—SlimLine distribution cabinet to NX
Run From To Conductors
A Distribution Cabinet Load AC Connection Isolated Ground
B Distribution Cabinet Load AC Connection
C Distribution Cabinet Load AC Connection
D Distribution Cabinet Load AC Connection PH A,B,C
E UPS Module AC Output Distribution Cabinet PH A, B, C
G UPS Module AC Output Distribution Cabinet Neutral
H UPS Module AC Output All Ground Connections Ground
Neutral Distribution Cabinet
Ground Distribution Cabinet
52
Page 61
Installation Drawings
e
I
Figure 40 Lineup detail—1+N Type A connection to NX
1 + N Parallel Cabinet
(front view without front door and panel)
1. All Liebert-supplied cable must be repositioned prior to and while setting the cabinets in their installed location.
2. All interconnection cables and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules
4. The interconnecting output cables between the paralleling cabinet and the UPSes must be the same siz and the same length.
5. The location of the system output neutral busbar (connection K) and the ground busbar (connections H, and J) are shown for a left-access style. For right-access version, these busbars are at opposite locations
6. Refer to the individual drawing of each piece of equipment for additional details.
Table 15 Interconnect wiring—1+N Type A connection to NX
RUN FROM TO CONDUCTORS
A1-A4 Utility AC Source UPS #1-UPS #4 Module AC Input Ph A, B, C - UPS Input
B1-B4 Utility AC Source UPS #1-UPS #4 Module AC Input Neutral - UPS Input
C1-C4 UPS #1-UPS #4 Module AC Output Paralleling Cabinet Ph A, B, C- UPS Output
D1-D4 UPS #1-UPS #4 Module AC Output Paralleling Cabinet Neutral - UPS Output
E1-E4 Paralleling Cabinet UPS #1-UPS #4 Module AC Ground Ground-UPS
F Paralleling Cabinet Load AC Connection Ph A, B, C - Load
G Paralleling Cabinet Load AC Connection Ground-Load
H Paralleling Cabinet Load AC Connection Neutral-Load
I1-I4
Paralleling Cabinet
UPS #1-UPS #4 Module
Parallel Logic Board (M3)
Output Breaker Aux Contact
53
Page 62
Figure 41 Lineup detail—1+N Type B1 connection to NX
Installation Drawings
1 + N Cabinet Side View
(without side panel or door)
(front view without front door and panel)
1 + N Parallel Cabinet
1 + N Cabinet Interior View
(neutral and ground busbar location)
1. All Liebert-supplied cable must be repositioned prior to and while setting the cabinets in their installed location.
2. All interconnection cables and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules.
4. The interconnecting input cables between the paralleling cabinet and the UPSes must be the same size and the same length.
5. The interconnecting output cables between the paralleling cabinet and the UPSes must be the same size and the same length.
6. The location of the system output neutral busbar (connection K) and the ground busbar (connections H, I and J) are shown for a left-access style. For right-access version, these busbars are at opposite locations.
7. Refer to the individual drawing of each piece of equipment for
UPS Module Left Side View
(without side panel)
additional details.
Table 16 Interconnect wiring—1+N Type B1 connection to NX
Run From To Conductors
A Utility AC Source Paralleling Cabinet Ph A, B, C - System Input
B Utility AC Source Paralleling Cabinet Ground - System Input
C Utility AC Source Paralleling Cabinet Neutral -system Input
D1-D4 Paralleling Cabinet UPS #1-UPS #4 Module AC Input Ph A, B, C - UPS Input
E1-E4 Paralleling Cabinet UPS #1-UPS #4 Module AC Input Neutral - UPS Input
F1-F4 UPS #1-UPS #4 Module AC Output Paralleling Cabinet Ph A, B, C - UPS Output
G1-G4 UPS #1-UPS #4 Module AC Output Paralleling Cabinet Neutral - UPS Output
H1-H4 Paralleling Cabinet UPS #1-UPS #4 Module AC Ground Ground-UPS
I Paralleling Cabinet Load AC Connection Ph A, B, C - Load
J Paralleling Cabinet Load AC Connection Ground-load
K Paralleling Cabinet Load AC Connection Neutral-Load
L1-L4
M1-M4
Paralleling Cabinet
Paralleling Cabinet
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
Output Breaker Aux Contact
Rotary Switch Aux Contact
54
Page 63
Figure 42 Lineup detail—1+N Type C connection to NX
Installation Drawings
1 + N Cabinet Side View
(without side panel or door)
(front view without front door and panel)
1 + N Parallel Cabinet
1. All Liebert-supplied cable must be repositioned prior to and while setting the cabinets in their installed location.
2. All interconnection cables and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules.
4. Utility AC source neutral not required for maintenance bypass/ transformer cabinet Type C.
5. The interconnecting input cables between the paralleling cabinet and the UPSes must be the same size and the same length.
6. The interconnecting output cables between the paralleling cabinet and the UPSes must be the same size and the same length.
7. The location of the system output neutral busbar (connection K) and the ground busbar (connections H, I and J) are shown for a left-access style. For right-access version, these busbars are at opposite locations.
UPS Module Left Side View
(without side panel)
8. Refer to the individual drawing of each piece of equipment for additional details.
Table 17 Interconnect wiring—1+N Type C connection to NX
Run From To Conductors
A Utility AC Source Paralleling Cabinet Ph A, B, C-system Input
B Utility AC Source Paralleling Cabinet Ground - System Input
C1-C4 Paralleling Cabinet UPS #1-UPS #4 Module AC Input Ph A ,B, C - UPS Input
D1-d4 Paralleling Cabinet UPS #1-UPS #4 Module AC Input Neutral - UPS Input
E1-E4 UPS #1-UPS #4 Module AC Output Paralleling Cabinet Ph A, B, C - UPS Output
G1-G4 UPS #1-UPS #4 Module AC Output Paralleling Cabinet Neutral - UPS Output
H1-H4 Paralleling Cabinet UPS #1-UPS #4 Module AC Ground Ground - UPS
I Paralleling Cabinet Load AC Connection Ph A ,B, C - Load
J Paralleling Cabinet Load AC Connection Ground - Load
K Paralleling Cabinet Load AC Connection Neutral - Load
L1-l4
M1-M4
Paralleling Cabinet
Paralleling Cabinet
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
1 + N Cabinet Interior View
(neutral and ground busbar location)
Output Breaker Aux Contact
Rotary Switch Aux Contact
55
Page 64
Figure 43 Suggested placement—single NX with auxiliary cabinets
Installation Drawings
Maintenance
Transformer
Maintenance
Bypass /
Transformer
Cabinet
Slimline Distribution
Bypass /
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Battery
Cabinet
Battery
Battery
Cabinet
Cabinet
Liebert
Battery
Battery Cabinet
Cabinet
Front of Units Front of UnitsFront of Units
Liebert
NX
UPS
Slimline Distribution
NX
UPS
Battery
Battery Cabinet
Cabinet
Front of UnitsFront of Units Front of Units
Liebert
NX
UPS
Liebert
NX
UPS
Slimline Distribution
Battery
Battery Cabinet
Cabinet
Maintenance
Bypass /
Transformer
Cabinet
Slimline Distribution
Liebert
NX
UPS
Maintenance
Transformer
Battery
Battery Cabinet
Cabinet
Front of Units
Bypass /
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Front of UnitsFront of Units Front of Units
Liebert
NX
UPS
Slimline Distribution
Slimline Distribution
56
Page 65

Figure 44 Suggested placement, multiple NX units with auxiliary cabinets

Installation Drawings
Battery
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Battery
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Front of Units
Liebert
NX
UPS
Front of Units
Battery Cabinet
Multi-Module
Paralleling
Cabinet
Liebert
NX
UPS
Multi-Module
Paralleling
Cabinet
57
Page 66

7.0 OPERATION

7.1 General Description

The standard NX consists of the UPS and internal batteries in a compact, single cabinet.
As shown in Figure 45, the AC utility source is input at CB1 and the rectifier converts the AC utility into DC power. The inverter converts that DC power from the utility—or DC power from the batter­ies—into AC power for the load. The batteries power the load through the inverter in the event of a power failure. The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in service to the maintenance bypass.

Figure 45 Single module block diagram (dual input configuration)

Operation

7.2 Bypass Supplies

The circuit block labeled “Static Switch” and “Contactor” in Figure 45 contains an electronically con­trolled switching circuit that enables the critical load to be connected to either the inverter output or to a bypass power source via the static bypass line. During normal system operation the load is con­nected to the inverter and the inverter contactor is closed; but in the event of a UPS overload or inverter failure, the load is automatically transferred to the static bypass line.
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply, provided that the bypass remains within an acceptable frequency window.
A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine maintenance.
NOTE
When the UPS is operating in bypass mode or on maintenance bypass, the connected equipment is not protected from power failures or surges and sags.

7.3 Operating Modes

The UPS is designed to operate as an on-line, double-conversion, reverse-transfer system in the fol­lowing modes:
58
Page 67
Operation

Normal Mode

Operating in normal mode, the NX’s rectifier derives power from a utility AC source and supplies reg­ulated DC power to the inverter, which regenerates precise AC power to supply the connected equip­ment. The rectifier also uses the utility source power to charge the batteries.

Battery Mode

When utility AC power fails, the NX protects the critical load by instantaneously channeling battery power to the inverter which continues supporting the critical load without interruption. When utility power returns and is within acceptable limits, the NX automatically shifts back to Normal mode, with the rectifier powering the critical load.

Bypass Mode

When the NX is in bypass mode, the load is directly supported by utility power and is without battery backup protection.
The NX’s static transfer switch will shift the load from the inverter to bypass mode without an inter­ruption in AC power if the inverter is synchronous with the bypass and any of the following occurs:
• inverter fails
• inverter overload capacity is exceeded
• inverter is manually turned off by user
NOTE
If the inverter is asynchronous with the bypass, the static switch will transfer the load from the inverter to the bypass WITH interruption in AC power to the critical load. This interruption will be less than 15ms (in 50Hz), or less than 13.33ms (in 60Hz). This interruption time may be altered by modifying the Output transfer interrupt time setting.

Maintenance Mode

For maintenance or repair, the NX may be operated in maintenance mode. To place the NX in mainte­nance mode, the load must be transferred to bypass and the inverter must be turned off. When those conditions are met, the rotary switch may be turned to MAINT and the UPS may be shut down, per­mitting disconnecting the batteries for maintenance.
CAUTION
!
The internal maintenance bypass must not be used when the UPS system is in 1+N parallel.
WARNING
!
The UPS input and output must be protected with external overcurrent protection devices. In maintenance mode, the input and output busbars remain energized.

Parallel Redundancy Mode (System Expansion)

For higher capacity, higher reliability or both, the outputs of up to four UPS modules can be pro­grammed for directly paralleling while a built-in parallel controller in each UPS ensures automatic load sharing.

Frequency Converter Mode

The Liebert NX can be programmed into frequency converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 40Hz to 70Hz. In this mode, the static bypass operation is disabled and the battery becomes optional, depending on any requirement to operate in battery mode (stored energy mode).
59
Page 68

8.0 OPERATOR CONTROL AND DISPLAY PANEL

8.1 Operator Control Panel

The control panel and LCD on the front of the Liebert NX lets the operator:
• turn the UPS on or off
• transfer into the various operating modes
• silence alarms
• check the status of the UPS and its batteries, including all measured parameters, events and alarms
The main areas of the control panel are shown below in Figure 46 and detailed in Figure 47.
Mimic Display - view the status of the NX in single-line diagram format—indicators show status by changing color when ON, flashing or OFF
Liquid Crystal Display (LCD) and Navigation keys - view status and operational data from the NX in tabular format
Control buttons - turn the NX on or off, silence alarms

Figure 46 Overview of control panel

Operator Control and Display Panel
Mimic display
Liquid Crystal Display (LCD)
Navigation keys

8.1.1 Display Panel Layout

Figure 47 shows the control panel in greater detail, identifying individual items that are described in the rest of this section.
Figure 47 Detailed view of control panel
2
1
5
3
4
7
6
Liebert NX 30KVA-3X3
Main
Vphase V
Iphase A Freq. Hz Vline V
P. F.
Input Breaker Cl osed 01-12 12:28:16 Manual Turn On 01-12 12:30:06 UPS in Normal Mode 01-22 12:30:16
Main
F2 F4 HELPF1 F3
Output
B(BC)
120
20.5
50.1 208
0.99
A(AB)
120
20.5
50.1 208
0.99
2006-01-22 12:30: 36
Bypass
C(CA)
120
20.5
50.1 208
0.99
Liebert N X
30KVA-3X3
Vphase V Iphase A Freq. Hz Vline V P. F.
Input Breaker Closed 01-12 12:28:16 Manual Turn O n 01-12 12:30:06 UPS in Normal Mode 01 -22 12:30:16
2006-01-22 12:30:36
Unit #1 Normal
Bypass
A(AB) 120
20.5
50.1 208
0.99
F2 F4 HELPF1 F3
Unit #1 Normal
Output
C(CA)
B(BC)
120
120
20.5
20.5
50.1
50.1 208
208
0.99
0.99
?
8
INVERTER ON INVERTER OFF
?
FAULT CLE AR S ILENCE ON/OFF
EPO
INVERTER ON INVERTER OFF
FAULT CL EAR S ILENCE ON/OFF
9
EPO
10
12
Control buttons
11
13
14
15 16 17 18 19
Mimic indicators Control buttons Navigation keys
1. Rectifier indicator 8. Button cover 15. F1
2. Battery indicator 9. EPO button 16. F2
3. Bypass indicator 10. INVERTER ON button 17. F3
4. Inverter indicator 11. INVERTER OFF button 18. F4
5. Load indicator 12. FAULT CLEAR button 19. Help
6. Status indicator 13. SILENCE ON/OFF button
-------------------------------------
7. Buzzer
------------------------------------------ ---------
14. LCD
60
Page 69

8.2 Mimic Display Indicators

The Mimic display on the front panel consists of six indicators arranged in a single-line diagram depicting the various paths of UPS power, as shown in Figure 48.

Figure 48 Mimic display indicators location

Operator Control and Display Panel
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Status indicator
2
1
5
6
4
3
Main
F2 F4 HELPF1 F3
A(AB)
120
20.5
50.1 208
0.99
2006-01-22 12:30:36
Unit #1 Normal
Bypass
Output
C(CA)
B(BC)
120
120
20.5
20.5
50.1
50.1 208
208
0.99
0.99
EPO
INVERTER ON INVERTER OFF
?
FAULT CLEAR SIL ENCE ON/OFF
Liebert NX
30KVA-3X3
Vphase V
Iphase A Freq. Hz Vline V
P. F.
Input Breaker Closed 01-12 12: 28:16 Manual Turn On 01-12 12:30:06 UPS in Normal Mode 01 -22 12:30:16
The current operational status of the Liebert NX is indicated by the color of the indicators—green, amber or red—and whether they are ON (solid), flashing or OFF. Table 18 provides a guide to inter­preting the various states of the indicators.

Table 18 Mimic display status indicators

Indicator
(see
Figure 48) Green Flashing Green / Amber Red Off
1. Rectifier
2. Battery
3. Bypass
4. Inverter
5. Load
6. Status
Load on rectifier Flashing Green: Utility normal,
but rectifier not operating
Battery powering the load
Load on Bypass power
Inverter powering the load normally
UPS output on
No alarms—UPS working normally
Flashing Green: Battery pre­warning (low battery)
Flashing Green: Inverter on standby
Amber: UPS has a general alarm
* Battery or battery converter abnormal events include these event messages (see Table 44 in Appendix A): No Battery, Battery Replaced,
Battery Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.
Rectifier fault Rectifier is normal, but utility is
abnormal
Battery or battery converter abnormal*
Battery and converter are normal, and battery is not discharging
Bypass out of
Bypass Normal
normal range
Inverter fault Inverter normal, but off
UPS output
UPS no output power
overloaded
UPS has a serious alarm
61
Page 70

8.3 Control Buttons

The Control Buttons on the front panel may be used to shut down the UPS completely, turn the inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 49. The function of each button is described in Table 19.
NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.

Figure 49 Location of control buttons

Liebert NX 30KVA-3X3
Vphas e V
Iphase A Freq. Hz Vline V
P. F.
Input Breaker Closed 01-12 12: 28:16 Manual Turn On 01-12 12:30:06 UPS in Normal Mode 01-22 12 :30:16

Table 19 Control buttons

Button
(see Figure 49) Function
EPO Completely shuts down the UPS, including the static switch.
INVERTER ON Press this button to start the inverter and transfer from static bypass to inverter.
INVERTER OFF Press this button to shut down the inverter during operation. The load will be transferred
FAULT CLEAR After the UPS shuts down due to a fault and the alarm condition has been resolved, press
SILENCE ON/OFF Press this button once to silence the alarm buzzer when an alarm is active. Any new fault
2006-01-22 12:30:36
Unit #1 Normal
Main
Bypass
A(AB)
120
20.5
50.1 208
0.99
F2 F4 HELPF1 F3
CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button completely shuts down the unit and the critical load.
NOTE: If the inverter is not ready, this will not activate the UPS.
to static bypass.
this button to clear the fault and restart the UPS.
will sound the buzzer again. If the alarm buzzer is not beeping, press this button to test the alarm sound.
B(BC)
120
20.5
50.1 208
0.99
Output
C(CA)
120
20.5
50.1 208
0.99
INVERTER ON INVERTER OFF
?
FAULT CLEAR SILENCE ON/OFF
EPO
Operator Control and Display Panel
8 9
10
11
12
13
Control buttons
8. Button cover
9. EPO button
10. INVERTER ON button
11. INVERTER OFF button
12. FAULT CLEAR button
13. SILENCE ON/OFF button

8.4 Alarm Buzzer

The alarm buzzer produces three types of sounds:
Single beep - when any Control button is pressed
Single beep repeating every two seconds - the system has a general alarm
Continuous - the system has a serious fault
If the alarm buzzer makes no sound, the system may be operating properly or the alarm may have been silenced manually.

Figure 50 Alarm buzzer location

Alarm
Buzzer
Main
A(AB)
120
20.5
50.1 208
0.99
2006-01-22 12:30:36
Unit #1 Normal
Bypass
Output
B(BC)
120
20.5
50.1 208
0.99
Liebert NX
30KVA-3X3
Vphas e V
Iphase A Freq. Hz
Vline V
P. F.
Input Breaker Closed 01-12 12: 28:16 Manual Turn On 01-12 12:30:06 UPS in Normal Mode 01-22 12 :30:16
62
C(CA)
120
20.5
50.1 208
0.99
INVERTER ON INVERTER OFF
?
EPO
Page 71

8.5 LCD Overview

The LCD on the front panel has five main sections, as shown in Figure 51. Press the F1 key below the LCD to scroll through these sections.
UPS system information - view UPS name and model, date and time, overall status (see Table 21).
LCD Menu - choose a category of data items to appear below the menus (see Table 22).
Data and settings - view data items for the selected menu (see Table 22).
Current status messages - check the most recent UPS event and alarm messages (see Table 44 in Appendix A).
Navigation key icons - look at the icon above each navigation key to determine how the key operates when pressed (see 8.6 - Navigation Keys).
The LCD displays alarm information in real time. After appearing in the current status section of the LCD, status messages are stored in the history log—512 records can be stored and retrieved.

Figure 51 Sections of the LCD

Operator Control and Display Panel
LCD menu
Data & settings
Current status messages
2006-01-22 12:30:36Liebert NX
Single Normal30kVA-3X3
BypassMains Out put
L1-N/L2 L2-N/L3 L3-N/L1 L-N voltage (V) 119.8 119.4 119.4 L-N current (A) 0.3 0.5 0.6 Frequ ency ( Hz) 59.97 59.97 5 9.97 L-L voltage (A) 207.1 206.8 207.1
Power factor 0.00 0.00 0.00
Fault reset 01-22 10:32
Manual turn on 01-22 10:32 Normal mode 01-22 11:05
F2 F4 HELPF1 F3
UPS system information
?
Navigation key icons
63
Page 72

8.6 Navigation Keys

The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view the current status and other information about the NX.
Navigation key icons on the LCD appear above each key to indicate its operation (see Table 20). The keys are “soft keys” that can change functions according to the icon.
•Use F1 either to move to a different portion of the LCD (shift icon) or to escape to a previous view (ESC icon).
•Use F2 and F3 as cursor keys to move left and right or up and down, depending on the icons dis- played above the keys.
•Use F4 as an Enter key to confirm a choice.
•Use HELP to access help information on the LCD.

Table 20 Icons for navigation keys

Key F1 F2 F3 F4 HELP
Operator Control and Display Panel
Functions Available
Shift Left Right
ESC
Exit Up Down

8.7 UPS System Information

The UPS system information displayed at the top of the LCD is detailed in Table 21.

Table 21 Description of items in UPS system window

No. Item Type Explanation
1 Liebert NX UPS name 2 2002-10-12 Current date 3 12:30:36 Current time
030kVA-3x3 030 means UPS model is 30kVA;
4
Unit #1 #1 of 6 Paralleled changed to “Unit #1”
5
Single UPS is configured as a single-unit system running in Normal mode Normal UPS in normal operation, inverter powering load, no warnings
6
Warning UPS has a general alarm Fault UPS has a serious fault
3x3 means 3 by 3 system (three phase input and output)
?
Enter Help
64
Page 73

8.8 LCD Menus and Data Items

The LCD menus provide access to the following categories of information and settings for the UPS. Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The menu choices are listed below and described in detail in Table 22.
Mains - view utility power input data: voltage, current, frequency and power factor
TX Input - view input transformer voltages
Bypass - view bypass data: voltage and frequency
Output - view output data: voltage, current, frequency and power factor
Load - view load data: load percent, output current, output power and crest factor (CF)
System - view system data
Battery - view battery characteristics—voltage, current, temperature, remaining time and capac­ity—and messages when the battery is boost/float charging or disconnected
Records - access the history log—displays all records in the log (newest records added at end)
Language - select a language for LCD text (choices appear in the native language)
Settings - configure UPS settings: adjust the display contrast, choose a format for date display, set the date and time, set up the UPS for modem communications (baud rate, address, mode and phone numbers to dial for alarm notifications) and change the password
Command - start or stop a battery maintenance test, battery capacity test or system test
Version - view firmware versions for the inverter, rectifier and software display board and the model information for the UPS
Figure 52 shows a menu tree of the options available from the LCD menus.

Figure 52 Menu tree

Operator Control and Display Panel
Mains (input)
L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor
Load
Sout (kVA) Pout (kW) Qout (kVAR) Loadlevel % Crest factor
Language
(Choices for display)
TX Input *
L-N voltage (V) L-L voltage (V)
System
Sout (kVA) Pout (kW) Qout (kVAR) Single unit, no parallel data
Settings
Display contrast Date format set Date & time Comm1 baud rate Comm2 baud rate Comm3 baud rate Communication address Communication mode Callback times Phone No.1 Phone No.2 Phone No.3 Command password
Bypass
L-N voltage (V) Frequency (Hz) L-L voltage (V)
Battery
Battery voltage (V) Battery current (A) Battery temperature (°C) Remain Time Min. Battery capacity (%) Battery boost charging Battery float charging Battery disconnected
Command
Battery maintenance test Battery capacity test System test Stop testing Freshening Charge Stop Freshening Charge Modem Auto-answer enable
Output
L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor
* When configured, input transformer voltages are
displayed on the front LCD. When not activated, the values are hidden.
** When configured, output transformer voltages
are displayed on the front LCD. When not activated, the values are hidden.
TX Output **
L-N voltage (V) L-L voltage (V)
Records
(history log)
Version
UPS version UPS model
65
Page 74

8.9 Language Selection

The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a differ­ent language:
• From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the screen.
• Press F2 and F3 (left and right arrows) as needed to select the Language menu.
• Press F1 (shift) to move the cursor to the data and settings area of the LCD.
•Use F2 and F3 (up and down) to select the required language.
• Press the F4 (enter) key to accept the language selection.
• Return to the main menu by repeatedly pressing F1 (ESC) as needed; all text on the LCD will now be displayed in the selected language.

8.10 Current Date and Time

To change the system date and time:
• From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the screen.
• Press F2 and F3 (left and right arrows) as needed to select the Settings menu.
• Press F1 (shift) to move the cursor to the data and settings area of the LCD.
•Use F2 and F3 (up and down) to select the Date & Time option, then press F4 (enter).
• Position the cursor on the row in which the date and time are displayed, then press F4 (enter).
•Using the F2 and F3 (up and down) keys, enter the current time and date information.
• Press F4 (enter) to save the settings, then press F1 (ESC) to return to the main menu.
Operator Control and Display Panel
2006-01-22 12:30:36Liebert NX
Single Normal30kVA-3X3
RecordsBattery Language
POLSKI ESPAÑOL
Fault reset 01-22 10:32 Manual turn on 01-22 10:32 Normal mode 01-22 11:05
Display contrast
Date format set M/D/Y
D/M/Y M/D/Y Y/M/D
Date & time
01-22-2004 12:30:36
Fault reset 01-22 10:32 Manual turn on 01-22 10:32 Normal mode 01-22 11:05
ENGLISH FRANCAIS NEDERLANDS
РУСС КИ Й
F2 F4 HELPF1 F3
2006-01-22 12:30:36Liebert NX
Sing le Normal30kVA-3X3
LanguageRecords Settings
F2 F4 HELPF1 F3
DEUTSCH ITALIANO SVENSKA PORTUGUÊS
?
?
66
Page 75
Operator Control and Display Panel

Table 22 Descriptions of UPS menus and data window items

Menu Type Item Type Explanation
L-N voltage (V) Phase voltage
Mains (input)
TX Input
Bypass
Output
TX Output
Load
System
Battery
Records (history log) Displays all records in the history log Language (choices for text displayed) User may select any of 12 languages for LCD text.
L-N current (A) Phase current
Frequency (Hz) Input frequency
L-L voltage (v Line-line voltage
Power factor Power factor
L-N voltage (V) Phase voltage
L-L voltage (V) Line-line voltage
L-N voltage (V) Phase voltage
Frequency (Hz) Bypass frequency
L-L voltage (A) Line-line voltage
L-N voltage (V) Phase voltage
L-N current (A) Phase current
Frequency (Hz) Output frequency
L-L voltage (V) Line-line voltage
Power factor Power factor
L-N voltage (V) Phase voltage
L-L voltage (V) Line-line voltage
Sout (kVA) Sout: Apparent power
Pout (kW) Pout: Active power
Qout (kVAR) Qout: Reactive power
Loadlevel % The percent of the UPS rating load
Crest factor Output current Crest Factor
Sout (kVA) Sout: Apparent power
Pout (kW) Pout: Active power
Qout (kVAR) Qout: Reactive power
Single unit, no parallel data When configured as a single unit, UPS has only native load, no system load.
Battery voltage (V) Battery bus voltage
Battery current (A) Battery bus current
Battery temperature (°C) Internal battery temperature °C
Remain Time Min. Battery run time remaining
Battery boost charging Battery is boost charging
Battery float charging Battery is float charging
Battery disconnected Battery is not connected
67
Page 76
Table 22 Descriptions of UPS menus and data window items (continued)
Menu Type Item Type Explanation
Display contrast Adjust the LCD display contrast
Date format set Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D
Date & time Set the date and time
Comm1 baud rate Communication baud rate setting for Intellislot 1
Comm2 baud rate Communication baud rate setting for Intellislot 2
Comm3 baud rate Communication baud rate setting for Intellislot 3
Communication address This setting is applicable to RS485 communication mode
Settings
Command (start/stop battery & system tests)
Version
Communication mode Communication Mode Setting
Callback times When Intellislot 1 Communication mode is Modem, this parameter sets the
number of times a number is redialed to send an alarm notification.
Phone No.1 When Intellislot 1 Communication mode is Modem, this is the first phone
Phone No.2 When Intellislot 1 Communication mode is Modem, this is the second phone
Phone No.3 When Intellislot 1 Communication mode is Modem, this is the third phone
Command password User can modify the command password.
Battery maintenance test This test performs a partial discharge of the battery to obtain a rough estimate
Battery capacity test This test performs a full discharge of the battery to obtain a precise measure of
System test This is a self-test of the UPS. When the user activates this function, a pop-up
Stop testing Manually stops a battery maintenance test, battery capacity test or system
Freshening Charge Allows a temporary Equalize charge for the batteries. This charge is
Stop Freshening Charge Manually stops a Freshening Charge
Modem Auto-answer enable
UPS version Provides UPS firmware version numbers for the inverter, rectifier and software
UPS model Provides UPS model information—for example, 208V-60Hz.
number to be dialed (to send an alarm notification).
number to be dialed (to send an alarm notification).
number to be dialed (to send an alarm notification).
of the battery capacity. Load must be between 20% and 80%.
the battery capacity. Load must be between 20% and 80%.
window appears about 5 seconds later to show the results.
test.
configurable for 1 to 36 hours.
Manually enable the modem’s auto-answer function.
display board.
Operator Control and Display Panel
68
Page 77

8.11 UPS Status Messages

The NX displays status changes as they occur in the current status window of the LCD, then stores that data in the history log, as shown in Figure 53.
Current Status Window: The status messages are displayed chronologically and include the date and time of the events. Three status messages are visible in the window at a time. To see other messages, use the navigation keys to scroll up or down the list. A status message remains in the current status area of the LCD until the status changes, when it is moved to the history log.
History Log: When a record moves to the history log, the time the status changed is recorded. The history log can hold up to 512 records. History log records may be viewed by accessing the Records menu.

Figure 53 Current status and history log records

Operator Control and Display Panel
2006-01-22 12:30:36Liebert NX
Single Normal30kVA-3X3
Records
History log (records menu)
Current status messages
BatterySystem
Bypass abnormal
Inverter asynchronous
Mains freq. abnormal
Fault reset 01-22 10:32
Manual turn on 01-22 10:32 Normal mode 01-22 11:05
01-22-2004 09:57: 13 01-22-2004 10:02: 16
01-22-2004 09:57: 13 01-22-2004 10:02: 21
01-22-2004 09:57: 14 01-22-2004 10:02: 14
?
F2 F4 HELPF1 F3
See Table 44 in Appendix A for a complete list of status messages, along with a description and any recommended actions.
69
Page 78

8.12 Types of LCD Screens

This section provides a quick guide to the main types of LCD screens.

8.12.1 Opening Display

As the UPS begins powering up, the opening display appears, as shown in Figure 54.
Figure 54 Opening display
Operator Control and Display Panel

8.12.2 Default Screen

After the UPS has powered up and completed a self-test, the output screen appears, as shown in Figure 55. This window is the default screen.
Figure 55 Default screen
F2 F4F1 F3
2006-01-22 12:30:36Liebert NX
Single Normal30kVA-3X3
BypassMains Outpu t
L-N voltage (V) 119.8 119.4 119.4 L-N current (A) 0.3 0.5 0.6 Frequ ency ( Hz) 59.97 59.97 59.97 L-L voltage (A) 207.1 206.8 207.1 Power factor 0.00 0.00 0.00
Fault reset 01-22 10:32
Manual turn on 01-22 10:32 Normal mode 01-22 11:05
L1-N/L2 L2-N/L3 L3-N/L1
F2 F4 HELPF1 F3
HELP
?
70
Page 79

8.12.3 UPS Help Screen

Press the HELP key below the LCD to display the Help window shown in Figure 56. (Press the HELP key again to exit the Help window.)
Figure 56 Help screen
Help information
Select the current record window
Select the previous menu item
Q3
Q2
Q1
Press help key back to main menu
F2 F4 HELPF1 F3
Operator Control and Display Panel
Q5

8.12.4 Screen Saver Window

If there has been no interaction with the NX’s LCD for 2 minutes, the screen saver window appears. It remains on the LCD for 2 minutes, then the screen will go dark. The LCD will become active again when any key is pressed.
Figure 57 Screen saver window
Liebert NX 30kVA-3X3
2006-01-22 12:30:36
Single Normal
Press any key back to main menu
F2 F4F1 F3
HELP
71
Page 80

8.13 Pop-Up Windows

Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This section describes the pop-up windows.

8.13.1 From Bypass to Inverter Mode With Power Interruption

If the bypass voltage or frequency exceeds the synchronized range and utility voltage or frequency is normal, the inverter cannot be in syn­chronization with the bypass, and the output can only transfer to inverter after an interruption of about 15ms when the user presses the INVERTER ON button. Before transferring, the system will let the user confirm whether the interruption can be accepted, as shown at right. If the bypass voltage returns to normal before the user makes confirmation, the UPS will transfer to inverter mode auto­matically. At the same time, the prompt window will close.

8.13.2 From Inverter to Bypass Mode With Interruption

If the bypass voltage or frequency exceeds the synchronized range and the UPS is in inverter mode, the system must let the user to confirm and accept the power interruption danger before pressing the INVERTER OFF button to shut down the output of the inverter. The user can also cancel the shutdown operation, as shown at right. If the bypass voltage returns to normal before the user makes the confirma­tion, the UPS will transfer to bypass operation mode automatically, and at the same time the prompt window will disappear soon.
Operator Control and Display Panel
Transfer with Interrupt,
please confirm or cancel
This operation leads to
output shutdown, Confirm or cancel

8.13.3 System Self-Test

When a system self-test is completed, a pop-up window reports the results of the test, as shown at right.
• Press the F4 (Enter) key and the pop-up window closes.

8.13.4 Battery Capacity Test Confirmation

When a battery capacity test is started from the Command menu, the battery will be discharged to low-battery warning level. The NX asks for confirmation before the test is started, as shown at right.
• To confirm the choice and begin the battery capacity test, press the F4 (Enter) key and the pop-up window disappears.
• To cancel the test, press the F1 (ESC) key. The pop-up window disappears.
NOTE
For a battery capacity test to function properly, the load must be between 20% and 100%.

8.13.5 Battery Self-Test Aborted, Condition Not Met

When a battery capacity test is started from the Command menu and the battery self-test condition is inadequate, the NX will not perform a battery test. User should check whether the battery state is boost charging and whether the load level is greater than 20 percent.
• Press the F4 (Enter) key and the pop-up window closes.
System Self-Test finished,
Everything is OK
Battery will be depleted,
Confirm or cancel
Battery Self-Test aborted,
Conditions not met

8.13.6 Battery Refresh Charge Aborted, Condition Not Met

When a battery refreshening charge is started from the Command menu and battery refreshening condition fails to meet requirements, the NX will not perform a battery refreshening charge. User should check if boost charging condition is not enough, such as (No battery, charger failed, etc.).
• Press the F4 (Enter) key and the pop-up window closes.
72
Battery Refresh Charge
aborted,
Conditions not met
Page 81

9.0 OPERATING INSTRUCTIONS

9.1 NX Operating Modes

The NX can operate in any of four modes, as shown in Table 23. This section provides instructions on switching between modes, resetting the UPS, switching the inverter On and Off and performing other operations.

Table 23 UPS operating modes

Operating Mode
Normal Operation
On Maintenance Bypass
On Test
On Static Bypass
Rotary Switch Position Description
NORMAL The UPS is powering the load.
MAINT The UPS is shut down but the load is connected to utility power via the
TEST No load power is supplied by the UPS. The load is connected to utility power
BYPASS or NORMAL
Operating Instructions
Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode.
via the Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode.
The load power is supplied through the static bypass line. This may be considered as a temporary mode during load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.
NOTE
1. The user controls and indicators mentioned in these procedures are identified in 8.0 ­Operator Control and Display Panel.
2. The audible alarm may sound at various points during these procedures. It can be canceled at any time by pressing the SILENCE ON/OFF push button.
NOTE
This unit refers to some modes and conditions that are set or adjusted using proprietary service software. To take advantage of all the available features for the NX, the unit must be commissioned by a Liebert factory-trained service engineer.
73
Page 82

9.1.1 Power Switches

The UPS can be isolated by means of power switches, mounted inside the cabinet and accessible after opening the front door.
The location of the UPS power switches is shown in Figure 58.
Figure 58 Power switches - 10kVA NX
CB1 - Utility Connection Inside the door, left side
Operating Instructions
SW1 - Rotary Switch Inside the door, near the center (above the batteries)
The UPS unit power switches are CB1 and SW1.
CB1 - Input Isolator. Connects the utility supply to the UPS input.
SW1 - Rotary switch. Has four positions—NORMAL, BYPASS, TEST and MAINT—that corre­spond to different positions of the SW1-A/B/C/D.
The positions of the rotary switch (SW1) are:
SW1-A - Output Isolator. Connects the output of the UPS to the load.
SW1-B - Neutral Isolator. Connects neutral to the UPS.
SW1-C - Bypass Isolator. Connects the UPS with the bypass supply.
SW1-D - Maintenance Bypass Isolator. Permits supply of the load directly by the bypass line for maintenance of the UPS unit.
The functions of the rotary switch are shown in Table 24.
Table 24 Rotary switch configuration
Rotary switch
position
NORMAL ✔✔
BYPASS ✔✔
TEST ✔✔ ✔
MAINT
OUTPUT
(SW1-A)
BYPASS
(SW1-C)
MAINT
(SW1-D)
NEUTRAL
(SW1-B)
NOTE
Do NOT turn the rotary switch too fast. Allow the rotary switch to stay in each position at least three seconds before turning it to the next position.
74
Page 83

9.2 UPS Start Up

The NX must be fully installed and commissioned before start up, and external power isolators must be closed. Once those general conditions are met, the UPS may be started.

9.2.1 Start-Up Procedure

To start the UPS from a fully powered-down condition:
1. Open the UPS door to gain access to the main power switches.
WARNING
!
During this procedure the output terminals will become live.
If any load equipment is connected to the UPS output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, then ensure that it is safely isolated from the UPS output terminals.
CAUTION
!
Do not operate the rotary switch too fast. Always wait at least three seconds when rotating the switch from one position to another.
2. Turn the rotary switch to TEST.
3. Close CB1. The bypass contactor (M2) closes automatically and the LCD begins to show start-up screens. The Rectifier indicator flashes green while the rectifier is starting up. It stops flashing and
becomes solid green about 30 seconds after the rectifier enters the normal operation state. After initialization, the bypass static switch closes.
Because output switch SW1-A is still open, the UPS channels power through Maintenance Bypass Supply line (SW1-D). The bypass indicator extinguishes, pro­vided that the bypass is normal.
The opening display is shown in the figure at right. The UPS Mimic display indicators will be:
Operating Instructions
Indicator State
Rectifier indicator Off
Battery indicator Off
Bypass indicator Off
Inverter indicator Off
Load indicator Off
Status indicator Off
WARNING
!
Do NOT turn the rotary switch until the rectifier indicator stops flashing green.
4. Turn the rotary switch to BYPASS. The maintenance switch SW1-D opens and output switch SW1-A
closes. The UPS powers from static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The design of the rotary switch ensures uninterrupted output.
F2 F4F1 F3 HELP
Indicator State
Rectifier indicator Green
Battery indicator Off
Bypass indicator Green
Inverter indicator Off
Load indicator Green
Status indicator Amber
75
Page 84
5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds. The inverter will start and the inverter indicator will flash green. After the inverter is ready, the
UPS transfers from bypass to inverter, the bypass indicator turns off and the inverter and load indicators turn on.
The UPS is operating normally. The UPS Mimic display indicators will:
Indicator State
Rectifier indicator Green
Battery indicator Off
Bypass indicator Off
Inverter indicator Green
Output indicator Green
Status indicator Green

9.2.2 Verify Switching Between Operation Modes

Switch from Normal Mode to Battery Mode
• Open CB1 to enter battery mode. This breaks the utility connection to the NX. To return to normal mode, close CB1 after a few seconds. The rectifier will restart automatically
after 10 seconds and resume feeding power to the inverter.
Switch from Normal Mode to Bypass Mode
• Press INVERTER OFF button to switch to bypass mode.
Operating Instructions
NOTE
In bypass mode, the load is being powered by the utility and is not receiving conditioned power through the inverter.
Switch from Bypass Mode to Normal Mode
• Turn the rotary switch to NORMAL.
• In bypass mode, press the INVERTER ON button. When the inverter is ready, the UPS will switch to normal mode.
76
Page 85

9.3 Switching the UPS from Normal to Maintenance Bypass

Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass line of the UPS.
CAUTION
!
Before performing this operation, read the messages on the LCD to be sure that bypass supply is regular and the inverter is synchronous with it. If those conditions are not present, there is a risk of a short interruption in powering the load.
This procedure assumes that UPS is operating normally.
1. Press the INVERTER OFF button on the right side of the operator control panel for longer than 2 seconds.
The Inverter indicator will turn off and the status indicator (6) will turn amber and an audible alarm will sound. The load will transfer to static bypass and the inverter will shut off.
NOTE
Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message displayed until the appropriate condition is rectified.
2. Open the UPS door to gain access to the main power switches, SW1 and CB1.
3. Turn the rotary switch to BYPASS position. The UPS Bypass Static Switch still supply power to load.
4. Turn the rotary switch to TEST. The load is now on maintenance bypass.
5. Turn the rotary switch to MAINT.
6. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven internal power supplies decay. The unit will power down, but the load will continue to be supplied by the manual Maintenance bypass.
Operating Instructions
WARNING
!
Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to remove the internal protective barriers.
WARNING
!
Even with the UPS in maintenance bypass and “Off,” portions of the unit are still energized. Service is to be performed by qualified personnel only.
CAUTION
!
The load equipment is not protected from normal supply aberrations when operating in the maintenance bypass mode.

9.4 Powering Down the UPS

To power down the UPS completely, follow the procedures in 9.3 - Switching the UPS from Nor­mal to Maintenance Bypass.
To completely isolate the UPS from the AC supplies, the main external power input isolator (both iso­lators, where separate supplies are provided for rectifier and bypass) should be opened (see
Figure 59).
WARNING
!
To prevent injury to personnel, lockout or tagout the service supplies.
77
Page 86

9.5 Powering Down the UPS and Maintaining Power to Load

NOTE
An external Maintenance Bypass Cabinet must be installed before attempting to perform the following procedure.
If the UPS needs to be shut down completely while maintaining power to the load, follow these steps:
1. Perform Steps 1 through 5 in 9.3 - Switching the UPS from Normal to Maintenance Bypass.
2. Close the external maintenance bypass rotary switch to Maint postion. On the primary input distribution panel, which is often located distant from the UPS area, a label
should be posted advising service personnel that the UPS circuit is under maintenance.
WARNING
!
Wait 5 minutes for the internal DC busbar capacitors to discharge.
The UPS is now completely powered down.
NOTE
The Maintenance Bypass Power switch may be operated at any time while the UPS is powered down to connect the load to the maintenance bypass supply if required.
Operating Instructions
The procedure can be performed only after the installation has been completed (which includes the maintenance bypass cabinet), after the system has been placed in operation by authorized personnel. See the reference drawing of Figure 59 for more information.

Figure 59 Typical configuration for single UPS with external maintenance bypass cabinet

78
Page 87

9.6 Emergency Shutdown With EPO

This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS’s controls will remain active; however, the output will be turned off. To remove all power from the UPS, the external feeder breaker should be opened.

9.7 Auto Restart

When the main and bypass sources fail, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.
The UPS will automatically restart and enable output power:
• after utility power is restored
• if “Auto Recovery after EOD Enabling” is enabled
• after the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes) During the auto recovery delay, the NX will be charging its batteries to provide a safety margin
for equipment shutdown if input power fails again.
If the “Auto Recovery after EOD Enabling” feature is disabled, the user must restart the system man­ually.
Operating Instructions

9.8 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions

Once all appropriate measures have been taken to correct the problem indicated by the alarm mes­sage appearing on the operator control panel display, carry out this procedure to restore the UPS to regular operation following an EPO action or for the following reasons: Inverter Overtemperature, Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.
When the user confirms that the fault is cleared:
1. Press the FAULT CLEAR button to let the system exit the emergency off state.
NOTE:
A UPS manufactured before March 2006 may first require a full power down, i.e., manual opening of the input breakers, for the "Fault Clear" to take effect.
NOTE
The rectifier will start again, the battery contactor will close and the bypass will begin to power the load. The Rectifier indicator (1) flashes while the rectifier is starting up. When the rectifier enters the normal operation state (about 30 seconds), the rectifier indicator turns green.
2. Press the INVERTER ON button (10) on the right side of the operator control panel for longer than 2 seconds.
NOTE
The rectifier will be turned on automatically when the overtemperature fault disappears at 5 minutes after the disappearance of overtemperature signals.
After the EPO button is pressed, if the input utility is removed, theUPS will shut down completely. When input utility is returned, if the rotary switch (SW1) is in either Bypass or in Normal position, the UPS will start up on Bypass. There will be power at the output terminals of the UPS.
WARNING
!
If the rotary switch is in the Maint. position and input utility is present, there will be power at the output terminals of the UPS.
79
Page 88

9.9 Battery Protection

9.9.1 Battery Undervoltage Pre-Warning

Before the end of discharge, the NX displays a battery undervoltage pre-warning. After this pre-warn­ing, the battery has the capacity for 5 minutes discharging with full load (default time). The NX can be user-configured to display this warning from 3 to 60 minutes before end-of-discharge.

9.9.2 Battery End-of-Discharge (EOD) Protection

If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut down.

9.9.3 Battery Fuse-Blow Warning

Battery current protection is provided by the battery fuses FU7 and FU8. If a battery fuse blows, the NX displays the battery fuse-blow warning and the battery converter will be shut down.
NOTE
All equipment servicing procedures must be carried out only by trained personnel.

9.10 Isolating and Integrating One Module in a Multi-Module System

1. Turn Off inverter
2. Open External Output CB1 The UPS enters Isolation Status automatically, parallel signaling and communication becomes
masked, and output becomes inhabited.
3. Power Off unit for maintenance.
4. Power On unit with External Output CB1 open.
5. Unit enters Test Mode by configuration software setting.
6. Diagonosis or testing.
7. The UPS exits Test Mode by configuration software setting. Output becomes inhibited because of Isolation Status.
8. Return all switches to the Normal position, including External Output Circuit Breaker 1.
9. Close External Output Circuit Breaker 1. The UPS exits Isolation Status automatically, parallel signaling and communication recovers,
output becomes enabled but interlocking works now.
10. Turn On inverter and join the parallel system.
Operating Instructions
WARNING
!
Hazardous Battery Voltage
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
The UPS battery and connecting terminals remains energized at hazardous voltage levels at all times. The battery is located behind protective covers that require a tool for their removal: inside the UPS cabinet, inside a free-standing battery cabinet or on open racks inside a dedicated battery room that may be locked.
80
Page 89

9.11 Inserting One Module into a Multi-Module System

This procedure outlines how to integrate a UPS module that has been previously isolated from other modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the sys­tem has been commissioned by authorized personnel and the external power isolators are closed.
WARNING
!
Mains voltage will be applied to UPS output terminals.
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
1. Open the UPS door to gain access to the main power switches.
2. Rotate the switch to Test position. The LCD becomes active.
3. Close Input breaker CB1 The Rectifier indicator flashes on the UPS mimic panel during the startup of the rectifier and
becomes steady green once the rectifier reaches normal operation state after about 30s.
4. Close external battery circuit breaker QF1 (where an external battery is used). This breaker is inside the battery cabinet (if used) or is otherwise adjacent to the battery racks.
5. After the UPS detects the batteries, the red battery indicator extinguishes when the battery charger starts operation.
6. Rotate switch to Bypass position
7. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds. The inverter will start up and the inverter indicator flashes while it synchronizes to the load volt-
age and frequency. After the inverter is ready, the UPS connects to the load, the inverter indicator becomes steady green and the output indicator turns green.
8. Check that no “Warning” message is displayed in the top right corner of the LCD Monitor and that the indicators have the status shown below.
Operating Instructions
# LED LED Function Status
1 Rectifier indicator Green
2 Battery indicator Off
3 Bypass indicator Off
4 Inverter indicator Green
5 Output indicator Green
6 Alarm indicator Off
The UPS is now operating in NORMAL mode.
81
Page 90
Operating Instructions

9.12 Shutting Down a Multi-Module System Without System Bypass Switch

NOTE
Before beginning this procedure, shut down the connected load to prevent the possibility of damage. This procedure will shut off power to the load.
1. Open the UPS door to gain access to the main power switches, SW1 and CB1of a UPS in the system.
2. Turn the rotary switch to BYPASS position. Rotating any UPS Rotary Switch (SW1) to the Bypass position will force all UPS modules to Static Bypass
3. Repeat Steps 1 and 2 for the rest of the units in the system.
NOTE
If this operation will be performed on multiple units, the procedures should be performed on each unit with as little delay as possible.
4. Turn the rotary switch of each unit in the system to TEST. The load is now on maintenance bypass.
5. Turn the rotary switch of each unit in the system to MAINT.
NOTE
The following step will shut off power to the connected load.
6. Open system output breaker. The load will now be disconnected.
7. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility-driven internal power supplies decay.
8. To isolate a module: a. For systems that have UPS input breakers in paralleling cabinet, open the UPS input breaker
for the unit you want to isolate.
b. For systems that do not have UPS input breakers in paralleling cabinet, the utility source to
the UPS will need to be opened.

9.13 Shutting Down a Multi-Module System With System Bypass Switch

1. In the Bypass Cabinet, rotate the system bypass switch to the Bypass position. This will force the UPS's in the system to Static Bypass.
2. Open the UPS door to gain access to the main power switches, SW1 and CB1of a UPS in the system.
3. Turn the UPS SW1 to BYPASS position for each module in the system
4. Repeat Steps 2 and 3 for the rest of the units in the system.
5. Turn the rotary switch of each unit in the system to TEST.
6. Turn the rotary switch of each unit in the system to MAINT.
7. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven internal power supplies decay.
8. To isolate the UPS(s) from the bypass cabinet, open the module input and output isolation breaker(s).
82
Page 91

9.14 Commissioning a Parallel System

CAUTION
!
The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficult, do not hesitate to contact Liebert Global Service at 1-800-LIEBERT.
Check the input and output wiring of each UPS module. Ensure that the phase rotation sequence of the main inputs and the bypass inputs and outputs of each UPS module are the same. Ensure the parallel cables are connected firmly.
It is assumed that the installation is complete, the system has been commissioned by authorized per­sonnel and the external power isolators are closed. Before start up, disconnect the load.

9.15 Maintenance Bypass Cabinet Operating Procedures

9.15.1 Start Up and Initialization

Follow these steps to start the UPS while connected to the Maintenance Bypass.
1. Set Maintenance Bypass switch to the Normal position on Maintenance Bypass Cabinet.
2. Close the system input circuit breaker.
3. Start the UPS as instructed in 9.2 - UPS Start Up.
4. Close system output circuit breaker.

9.15.2 Shutting Down the UPS

Operating Instructions
Use the following procedure to power down the system.
1. Turn the NX off by following the procedures in 9.4 - Powering Down the UPS
2. Open system output circuit breaker.
3. Open system input circuit breaker.

9.15.3 Transferring System from UPS to Maintenance Bypass Operation

1. Turn the bypass switch (SW) to the bypass position on the Maintenance Bypass Cabinet. The UPS will switch to bypass mode.
The connected equipment is now powered from the bypass source and is NOT protected.
2. To isolate the UPS from the system, rotate the bypass switch to the maintenance position.

9.15.4 Transfer the System from Maintenance Bypass to UPS Operation

1. Turn the bypass switch (SW) to the Normal position on the Maintenance Bypass Cabinet. The UPS will go to bypass mode.
2. Press the “Inverter On” button on the UPS and allow the UPS to go to normal mode.
3. The connected equipment is now powered and protected by the UPS.

9.15.5 Transfer the System from UPS Operation to Maintenance Bypass

If the UPS needs to be shut down completely while maintaining power to the load, follow these steps:
1. Perform Steps 1 through 5 in 9.3 - Switching the UPS from Normal to Maintenance Bypass.
2. Rotate Maintenance Bypass Switch to Maintenance position.
3. Post a label on the primary input distribution panel, which often is installed outside the UPS area, advising personnel that the UPS circuit is under maintenance.
The UPS is now completely powered down.
WARNING
!
Wait 5 minutes for the internal DC busbar capacitors to discharge.
NOTE
The Maintenance Bypass power switch may be operated at any time while the UPS is powered down to connect the load to the maintenance bypass supply.
83
Page 92
Operating Instructions
The procedure can be performed only after the installation has been completed (which includes the maintenance bypass cabinet), after the system has been placed in operation by authorized personnel and after the external power switches have been closed. See Figure 60 for more information.
Figure 60 Single UPS with external Maintenance Bypass Cabinet—typical configuration
Input Supply
ABC
N
Sys in CB1
Qin UPS
Input Mains Supply A B C
UPS1
Charger
Fuse
Battery
Bat Byp
CB1
Static
Switch
SW1-A
N
Rectifier
Inverter
SW1-C
SW1-D
Rotary
Switch
SW
Y
N
A B C
Ext
Byp
Y
Qout UPS
Sys Out CB2
N
To Load
84
Page 93

9.16 Parallel System Start Up

1. Start each UPS normally as described in 9.2 - UPS Start Up
2. Turn on the inverter of each UPS module one at a time.
3. Apply the load after the last UPS module transfers to inverter. The total load can be determined through the LCD of either UPS.
4. Verify the load rate of each UPS module. If the load rates are roughly the same, then the parallel system may be assumed to be operating normally.
NOTE
If one module cannot transfer to inverter mode long after its inverter is on, its output connection may not be good or its output phase rotation may not be coincident with other modules. At this time, the LCD for the UPS module will display “inverter asynchronous” and the inverter indicator will flash continuously. If either UPS module makes abnormal noise after it transfers to inverter, its parallel cables may be incorrectly connected.

9.17 Replacing Dust Filters

1. Open the UPS door.
2. The dust filters are behind the door. For each filter, there is a bracket on either side holding the dust filter in place, as shown in Figure 61.
3. Remove one bracket and loosen the other. The second bracket need not be removed.
4. Remove the old filter and replace with the new filter
5. Reinstall the bracket that was removed and tighten the other bracket.
Operating Instructions

Figure 61 Dust filter replacement

Bracket
Sems screw
Bracket
85
Page 94

10.0 UPS SPECIFICATIONS

These specifications describe requirements for the Liebert NX UPS.

10.1 Conformity and Standards

The UPS has been designed to conform to the following standards:
• IEEC1000-4-5
•ASME
• CSA 22.2, No. 107.1
• FCC Part 15, Class A
• ISO 9001
• National Electrical Code (NFPA-70)
• NEMA PE-1
•OSHA
• UL Standard 1778
The UPS system has UL and c-UL approval.

10.2 UPS Environmental

The UPS is designed to operate under the following environmental conditions without damage or deg­radation in electrical operating characteristics:

Table 25 Environmental characteristics

Rated Power 10-30kVA
Operating Temperature, UPS 32°F to 104°F (0°C to 40°C)
Optimal Operating Temperature, Battery 68°F to 86°F (20°C to 30°C)
Relative Humidity 0 to 95%, non-condensing
Acoustical Noise, dBA at 39 in. (1m) 54
Altitude of Operation 1000m per IEC 62040/3
Storage-Transport Temperature, UPS -4°F to 158°F (-20°C to 70°C)
Storage-Transport Temperature, Battery -4°F to 86°F (-20°C to 30°C)
UPS Specifications

10.3 UPS Mechanical Characteristics

Table 26 Mechanical characteristics

Parameter 10kVA 15kVA 20kVA 30kVA
Width, in. (mm) 24 (600)
Depth, in. (mm) 32.5 (825)
Height, in. (mm) 63 (1600)
Weight Without Inner Batteries, lb. (kg) 450 (205) 450 (205) 550 (250) 550 (250)
UPS12-100 weight 954 (433) 954 (433) 1054 (478) 1054 (478)
UPS12-140 weight 1098 (498) 1098 (498) 1198 (543) 1198 (543)
Heat Dissipation, BTU/H (kWH) 2800 (0.82) 4200 (1.23) 5500 (1.61) 8300 (2.43)
3
Airflow, CFM (m
Cable Entry Bottom or top
Color PMS 877
Protection Grade (with open/closed front doors) IP 20
/h) 384 (652) 558 (948) 522 (886) 834 (1417)
86
Page 95
UPS Specifications

10.4 UPS Electrical Characteristics

Table 27 UPS terminal

Input (for single-input unit)
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Lug T&B
One Hole
REDDY
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP Device Rating Bolt Size
10 28 35 42 45 6M (1/4") 54105 62204
15 42 53 63 70 6M (1/4") 54106 62204
20 56 70 84 90 6M (1/4") 54107 62204
30 83 104 125 125 6M (1/4") 54152 62205
Rectifier input (for dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP Device Rating Bolt Size
10 25 31 37 40 6M (1/4") 54130 62204
15 37 47 57 60 6M (1/4") 54106 62204
20 50 63 76 80 6M (1/4") 54107 62204
30 75 94 113 125 6M (1/4") 54152 62205
Bypass input (for dual input units)
Maximum Recommended Lug
Lug T&B
One Hole
54000
Unit
Rating
Nominal
Input
Current OCP Current
OCP
Device
Rating Bolt Size
10 28 35 35 6M (1/4”) 54105 62204
15 42 53 60 6M (1/4”) 54106 62204
20 56 70 70 6M (1/4”) 54107 62204
30 83 104 110 6M (1/4”) 54152 62205
Output
OCP
Unit
Rating Nominal Output Current
OCP
Current
Device Rating Bolt Size
10 28 35 35 6M (1/4") 54130 62204
15 42 53 60 6M (1/4") 54106 62204
20 56 70 70 6M (1/4") 54106 62204
30 84 105 110 6M (1/4") 54108 62205
Battery
OCP
Unit
Rating Battery Current
OCP
Current
Device Rating Bolt Size
10/15 55 55 70 6M (1/4") 54106 62204
20/30 110 110 125 8M (5/16") 54153 62212
1. Nominal (Nom) current is based on full rated output load.
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions.
3. UPS input and bypass cables must be run in separate conduit from output cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215.
6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 2005.
7. Wiring requirements:
a. AC Input: 3-phase, 4-wire, plus ground output. b. AC Output: 3-phase, 3- or 4-wire, plus ground
8. All wiring is to be in accordance with national and local electric codes.
87
Page 96

10.4.1 Battery Manufacturers and Models

Either of two manufacturers’ batteries will be installed in the NX 10-30 kVA 208V as shipped. Below are the battery makers and the models they supply.
Table 28 Approved batteries
Battery Manufacturer Models Supplied Enersys Yuasa NPX-80FR NPX-100FR NPX-150FR
C&D Dynasty UPS12-100MR UPS12-140MR -

10.4.2 Input Rectifier

Table 29 Rectifier input power
Rated Power 10kVA 15kVA 20kVA 30kVA
Rated Voltage, VAC 120/208
Supply 3-phase, 4-wire plus ground
Input Voltage Tolerance, VAC (without derating) 166-239
Frequency, Hz 50 / 60
Input Frequency Tolerance % ±10
Power Factor
Harmonic Current Less than 4% at full rated UPS output load
1
Input Current,
Output Current, Nominal, A 28 42 56 83
Notes:
1. Overload capacity of input current: 100% Imax <I<125% Imax:
Nominal, A 28 42 56 83
0.99 at full load
0.95 at 50% load
125% Imax <I<150% Imax:
I>150%:
UPS Specifications
10 min. 1 min. Limits input current immediately

10.4.3 DC Intermediate Circuit

Table 30 DC intermediate circuit
Rated Power 10kVA 15kVA 20kVA 30kVA
Recommended number of lead-acid batteries
Recommended float charge voltage 2.27VDC*
Recommended boost charge voltage 2.3VDC*
Recommended end of discharge voltage 1.65-1.8 VDC
Maximum recharge battery current, A 7.5 7.5 15 15
Maximum boost charge duration, min.* 1440
Boost-float threshold current, A* 0.1 C default
Temperature voltage compensation, mV/°C* 3
Ripple voltage superimposed % ≤ 1
* Set by configuration software and based on usage of VLRA batteries.
Number of batteries is 24 jars (12V per jar), or 144 cells (2V per cell) for VRLA. The unit is shipped with a nominal voltage of 288VDC.
88
Page 97
UPS Specifications

10.4.4 Inverter Output

Table 31 Inverter output
Rated Power 10kVA 15kVA 20kVA 30kVA
Rated voltage, VAC 120/208
Supply 3-phase, 4-wire plus ground
Frequency, Hz 50 / 60
Rated Power, kW 8 12 16 24
Three -phase transient overload, min. load
Voltage Regulation % ±1.0% three-phase RMS average for a balanced three-phase load
±2.0% three-phase RMS average for a 100% unbalanced load
Frequency Regulation % Nominal frequency regulation is ±0.05% in single-module mode,
and+/- 0.25% in parallel mode.
Maximum rate of change of frequency, Hz/sec
Current rating of neutral cable, A 1.5 x input current
For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s
10 minutes - 105-125% load
1 minute - 126-150% load

10.4.5 Bypass Input

Table 32 Bypass input
Rated Power 10kVA 15kVA 20kVA 30kVA
Rated voltage, VAC 120/208
Supply Three-phase, 4-wire plus ground
Rated Current, A
208VAC 28425683
Bypass voltage tolerance %
Frequency, Hz 50 / 60
Input frequency tolerance % ± 10 or ± 20%; default ±10%
Current rating of neutral cable, A 1.5 x input current
Bypass overload capacity (all ratings)
Upper limit: +10%, +15% or +20%
Lower limit: -10%, -20%, -30% or -40%
Time
Long-term operation:
10 minutes:
100milliseconds:
Upper limit default: +15% Lower limit default: -20%
Load
<135% load 135% - 170% load 1000% full UPS rated output current
89
Page 98

11.0 SPECIFICATIONS AND TECHNICAL DATA

11.1 Lug Size and Torque Requirements

Use commercially available solderless lugs for the wire size required for your application. Refer to Table 33. Connect wire to the lug using tools and procedures specified by the lug manufacturer.

Table 33 Torque specifications

Nut and Bolt CombinationS
Grade 2 Standard
Bolt Shaft Size
1/4 53 6.0 46 5.2
5/16 107 12 60 6.8
3/8 192 22 95 11 1/2 428 22 256 29
Circuit Breakers With Compression Lugs (For Power Wiring)
Wire Size or Range Lb-in N-m
#6 - #4 100 11 #3 - #1 125 14
1/0 - 2/0 150 17
3/0 - 200 MCM 200 23 250 - 400 MCM 250 28 500 - 700 MCM 300 34
Lb-in N-m Lb-in N-m
Specifications and Technical Data
Electrical Connections
with Belleville Washers
Circuit Breakers With Compression Lugs (For Power Wiring)
Current Rating Lb-in N-m
400 - 1200 Amps 300.00 34.00
Terminal Block Compression Lugs (For Control Wiring)
AWG Wire Size or Range Lb-in N-m
#22 -#14 3.5 to 5.3 0.4 to 0.6
NOTE: Use the values in this table unless the equipment is labeled with a different torque value.

Table 34 Battery torque rating

Initial Torque
Battery
UPS12-100MR 40 (4.5) 32 (3.48)
UPS12-140MR 40 (4.5) 32 (3.48)
UPS12-200MR 40 (4.5) 32 (3.48)
UPS12-270MR 40 (4.5) 32 (3.48)
UPS12-310MR 65 (7.4) 52 (5.88)
UPS12-370MR 65 (7.4) 52 (5.88)
UPS12-475MR 110 (12.4) 110 (12.4)
in-lb (N-m)
Annual Torque
in-lb (N-m)
90
Page 99
Specifications and Technical Data

Table 35 Maintenance bypass cabinet electrical data (single input)

Maintenance
Bypass
kVA Type
30 A, J 208 104 125 208 83 125
30 B, K 480 47 60 208 83 125
30 B, K 600 37 50 208 83 125
30 B, K 220 101 125 208 83 125
30 C, L 480 48 60 480 36 50
30 C, L 600 38 50 600 29 40
30 C, L 220 105 125 220 79 100
30 D, M 480 47 60 208 83 125
30 D, M 600 38 50 208 83 125
30 D, M 208 108 150 208 83 125
30 D, M 220 103 125 208 83 125
30 D, M 240 93 125 208 83 125
30 E, N 480 48 60 480 36 50
30 E, N 600 39 50 600 29 40
30 E, N 220 106 125 220 79 100
20 A, J 208 69 90 208 56 70
20 B, K 480 31 40 208 56 70
20 B, K 600 25 30 208 56 70
20 B, K 220 68 90 208 56 70
20 C, L 480 32 40 480 24 30
20 C, L 600 26 40 600 19 30
20 C, L 220 70 90 220 52 70
20 D, M 480 31 40 208 56 70
20 D, M 600 25 40 208 56 70
20 D, M 208 72 90 208 56 70
20 D, M 220 68 90 208 56 70
20 D, M 240 62 80 208 56 70
20 E, N 480 32 40 480 24 30
20 E, N 600 26 40 600 19 30
20 E, N 220 70 90 220 52 70
15 A, J 208 52 70 208 42 60
15 B, K 480 23 30 208 42 60
15 B, K 600 19 30 208 42 60
15 B, K 220 51 70 208 42 60
15 C, L 480 24 30 480 18 30
15 C, L 600 19 30 600 14 20
15 C, L 220 52 70 220 39 50
15 D, M 480 23 30 208 42 60
15 D, M 600 19 30 208 42 60
15 D, M 208 54 70 208 42 60
15 D, M 220 51 70 208 42 60
15 D, M 240 47 60 208 42 60
15 E, N 480 24 30 480 18 30
15 E, N 600 19 30 600 14 20
15 E, N 220 53 70 220 39 50
I/P Voltage
(VAC)
Bypass Cabinet
Max Input
Current
Cabinet
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
OCP CB Size (A)
Output
91
Page 100
Specifications and Technical Data
Table 35 Maintenance bypass cabinet electrical data (single input) (continued)
Maintenance
Bypass
kVA Type
10 A, J 208 35 50 208 28 40
10 B, K 480 16 20 208 28 40
10 B, K 600 12 15 208 28 40
10 B, K 220 34 50 208 28 40
10 C, L 480 16 20 480 12 15
10 C, L 600 13 20 600 10 15
10 C, L 220 35 50 220 26 40
10 D, M 480 16 20 208 28 40
10 D, M 600 13 15 208 28 40
10 D, M 208 36 50 208 28 40
10 D, M 220 34 50 208 28 40
10 D, M 240 32 40 208 28 40
10 E, N 480 16 20 480 12 15
10 E, N 600 13 20 600 10 15
10 E, N 220 35 50 220 26 40
I/P Voltage
(VAC)
Bypass Cabinet
Max Input
Current
Cabinet
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
OCP CB Size (A)
Output

Table 36 Maintenance bypass cabinet electrical data (dual input)

System
I/P Voltage
kVA Type
30 F, P 480 42 50 47 50 208 83 125
30 F, P 600 33 40 37 40 208 83 125
30 F, P 208 95 125 107 125 208 83 125
30 F, P 220 90 125 101 125 208 83 125
30 F, P 240 83 100 93 100 208 83 125
20 F, P 480 28 40 31 40 208 55 70
20 F, P 600 22 30 25 30 208 56 70
20 F, P 208 64 80 71.5 80 208 56 70
20 F, P 220 61 80 68 70 208 56 70
20 F, P 240 56 70 62 70 208 56 70
15 F, P 480 21 30 24 30 208 42 60
15 F, P 600 17 30 19 20 208 42 60
15 F, P 208 49 60 54 60 208 42 60
15 F, P 220 46 60 51 60 208 42 60
15 F, P 240 42 60 47 50 208 42 60
10 F, P 480 14 20 16 20 208 28 40
10 F, P 600 12 15 13 15 208 28 40
10 F, P 208 33 40 36 40 208 28 40
10 F, P 220 31 40 34 40 208 28 40
10 F, P 240 29 40 32 40 208 28 40
(VAC)
Rectifier
Max Input
Current
Rectifier
Input OCP
CB Size (A)
Bypass
Max Input
Current
Bypass
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output OCP
CB Size (A)
92
Loading...