This manual contains important instructions that should be followed during installation of your
Liebert NX™ UPS and batteries.
Read this manual thoroughly, paying special attention to the sections that apply to your installation,
before working with the UPS. Retain this manual for use by installing personnel.
WARNING
!
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel. The UPS module weight ranges from 850 to 1400 lb. (386 to 635kg).
Determine unit weight and locate center of gravity symbols
before handling the UPS. Test lift and balance the cabinet
before transporting. Never tilt equipment more than 15 degrees from vertical.
Battery manufacturers supply details of the necessary precautions to be observed when
working on, or in the vicinity of, a large bank of battery cells. These precautions should be
followed implicitly at all times.
Follow all battery safety precautions when installing, charging or servicing batteries. In
addition to the hazard of electric shock, gas produced by batteries can be explosive and
sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 288VDC
and is potentially lethal.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages.
Check for voltage with both AC and DC voltmeters prior to making contact.
WARNING
!
As with other types of high power equipment, dangerous voltages are present within the UPS
and battery enclosure. The risk of contact with these voltages is minimized as the live
component parts are housed behind a hinged, lockable door. Further internal safety screens
make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner,
following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be
carried out only by trained personnel.
WARNING
!
High ground leakage current: Ground connection is essential before connecting the input
supply.
This equipment must be grounded in accordance with local electrical codes.
Maximum load must not exceed that shown on the UPS rating label.
1
Page 10
CAUTION
!
This equipment is fitted with RFI suppression filters.
Ground leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state ground leakage currents, which may occur when starting the
equipment, should be taken into account when selecting instantaneous residual current
circuit breakers (RCCBs) or residual current devices (RCDs).
RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to
transient current pulses.
Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.
WARNING
!
Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the UPS system should be kept free of puddles of water, excess
moisture and debris.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system and the battery. Observe all safety precautions in this
manual before handling or installing the UPS system. Observe all precautions in the
Operation and Maintenance Manual, before as well as during performance of all maintenance
procedures. Observe all battery safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only
test equipment designed for troubleshooting should be used. This is particularly true for
oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making
contact or using tools. Even when the power is turned Off, dangerously high electric charges
may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power
and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system.
When performing maintenance with any part of the equipment under power, service
personnel and test equipment should be standing on rubber mats. The service personnel
should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should
be standing by to assist and summon help in case an accident should occur.
CAUTION
!
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J
of the FCC rules. These limits provide reasonable protection against harmful interference in a
commercial environment. This unit generates, uses and radiates radio frequency energy and,
if not installed and used in accordance with this instruction manual, may cause harmful
interference to radio communications. This unit is not designed for use in a residential area.
Operation of this unit in a residential area may cause harmful interference that the user must
correct at his own expense.
Battery Cabinet Precautions
The following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation.
WARNING
!
Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
(after initial installation).
• Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT before moving battery cabinets (after initial installation).
2
Page 11
GLOSSARYOF SYMBOLS
Risk of electrical shock
!
R
i
-
PbH2SO4
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
+
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
3
Page 12
1.0INSTALLATION
Liebert’s NX™ Uninterruptible Power Supply system provides continuous, high-quality AC power to
your business-critical equipment, such as telecommunications and data processing equipment. The
NX UPS supplies power that is free of the disturbances and variations in voltage and frequency common to utility power, which is subject to brownouts, blackouts, surges and sags.
The NX utilizes the latest in high-frequency, double-conversion pulse width modulation (PWM) technology and fully digital controls to enhance its reliability and increase the ease of use.
This section describes the NX’s environmental requirements and mechanical considerations that
must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site is unique, this section presents a guide to general procedures and practices that
should be observed by the installing engineer, rather than step-by-step installation instructions.
WARNING
!
Do not apply electrical power to the UPS equipment before the arrival of the commissioning
engineer.
WARNING
!
The UPS equipment should be installed by a qualified engineer in accordance with the
information contained in this section.
WARNING
!
Special care should be taken when working with the batteries associated with this equipment.
When connected together, the nominal battery voltage is 288VDC and is potentially lethal.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Remove rings, watches and all metal objects.
• Only use tools with insulated handles.
• Wear rubber gloves.
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in
a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with skin, the affected area should be washed immediately
with large amounts of water.
Installation
NOTE
The NX UPS can be used in TN utility system.
1.1External Inspections
1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for
any signs of damage or mishandling. Do not attempt to install the system if damage is apparent.
If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact
Liebert Global Services at 1-800-LIEBERT to inform them of the damage claim and the condition
of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the
carrier and your local Liebert representative immediately.
1.2Internal Inspections
1. Remove any packaging material, then visually examine the UPS and battery equipment for
transit damage, both internally and externally. Report any such damage to the shipper and to
Liebert immediately.
2. Check the nameplate inside the cabinet door to verify that the model number and rating
correspond to the ones specified. Record the model number and serial number in the front of this
installation manual. This information is necessary should service be required.
3. Check for loose connections or unsecured components in the cabinet.
4. Check for shipping damage to internal components.
4
Page 13
1.2.1Storing for Delayed Installation
If the equipment will not be installed immediately, it must be stored indoors where the humidity is no
higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect
the NX from excessive moisture (see 10.2 - UPS Environmental).
CAUTION
!
If the UPS must remain disconnected from power for more than six (6) months, the battery
must be recharged before use. To charge the batteries, the unit must be connected to utility
power and started up—the charger operates only while the NX is operating.
CAUTION
!
When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS unit, the
battery—not the UPS—dictates the designed maximum ambient temperature.
1.3Preliminary Checks
1.3.1Identification
The equipment supplied has an identification tag on the back of the main door listing the type and
size of the UPS.
1.4UPS Location
Installation
1.4.1Positioning the UPS
Choose a location for the UPS that offers:
• Easy connection to inputs, outputs and auxiliary equipment
• Enough space to service the UPS
• Air circulation sufficient to expel heat produced by UPS
• Protection against moisture and excessive humidity
• Protection against dust and other particulate matter
• Compliance with fire prevention regulations and practices
• Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency
1.4.2Environmental Considerations
Before installing the NX, verify that the UPS room satisfies the environmental conditions stipulated
in 10.2 - UPS Environmental, paying particular attention to the ambient temperature and air
exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to
keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS and battery system performance and service life, maintain the operating temperature within the range of 74-80°F, (23-27°C).
The NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit and is
exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the
ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a
minimum of 24 in. (610mm).
See Table 26 for details on heat dissipation.
Battery Location
Temperature is a major factor in determining battery life and capacity. Battery manufacturers recommend an operating temperature of 77°F (25°C). Ambient temperatures warmer than this reduce battery life; temperatures below this reduces battery capacity. In a typical installation, battery
temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed
where there are no main heat sources or air inlets to prevent portions of batteries from being either
much warmer or much cooler than other parts of the batteries.
5
Page 14
1.4.3Special Considerations for 1+N Systems
1. Consider the grounding configuration of your system before finalizing module placement. For
optimal ground performance, the NX modules should be close together.
2. For optimal load-sharing performance, the UPS output cables should be approximately the same
length, plus or minus 20 percent.
3. Position modules in such a way as to minimize the length of power cables and control wiring
between UPS modules and the paralleling cabinet.
1.5Considerations in Moving the NX
Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any
handling equipment. See Table 26 for weights of various units.
To move the UPS and optional battery cabinets:
• The NX may be rolled on its casters when moving the unit a short distance. For longer distances,
move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration.
The optional battery cabinets should be moved with a forklift or similar equipment.
WARNING
!
Ensure that any equipment that will be used to move the NX has sufficient lifting capacity.
The NX weight ranges from 850 to 1400 lb. (386 to 635kg). See Table 26 for details. The UPS
presents a tipping hazard. Do not tilt the NX further than 15 degrees from vertical.
The UPS is fitted with casters—take care to prevent movement when unbolting the
equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are
available when taking the NX off its shipping pallet. Do not tilt the unit more than 15 degrees
from center.
Installation
WARNING
!
The casters are strong enough for movement across even surfaces only. Casters may fail if
they are subjected to shock loading, such as being dropped or rolled over holes in the floor or
obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging
the equipment.
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a
minimum. For further information, see Battery Cabinet Precautions on page 2.
Final Position
When the equipment has been finally positioned, ensure that the adjustable stops are set so that the
UPS will remain stationary and stable (see 6.0 - Installation Drawings).
1.6Mechanical Considerations
The NX is constructed with a steel frame and removable panels. Top and side panels are secured to
the chassis by screws. The doors may be opened for access to power connections bars, auxiliary terminals blocks and power switches.
The UPS comes with an operator control panel, which provides basic operational status and alarm
information. The cabinet houses both the power components and the internal batteries. Cooling is
provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the
UPS from moving once it has been moved to its final position.
6
Page 15
1.6.1Clearances
There are no ventilation grilles on the sides or rear of the UPS. The sides must be accessible during
installation. After installation, the unit may be placed with the rear against a wall and optional cabinets on either side.
To enable routine tightening of power terminations within the UPS, make sure there is sufficient
clearance in front of the NX to permit free passage of personnel with the door fully opened.
Leave a minimum of 2 ft. (610mm) between the top of the UPS and the ceiling to permit adequate air
circulation above the unit. Liebert recommends against using air conditioning or other systems that
blow air onto the top of the unit.
1.6.2Floor Installation
The diagrams in 6.0 - Installation Drawings show the location of holes in the base plate for bolting
the equipment to the floor. An optional anchoring kit is available. For information, see your local Liebert representative.
If the equipment is to be placed on a raised floor, it should be mounted on a pedestal that will support
the equipment point loading. Refer to the bottom view in Figure 30 to design this pedestal.
1.6.3Cable Entry
Cables can enter the NX from the top or bottom. Cable entry is made possible by removing a metal
plate attached to the UPS.
These plates are designed to allow the personnel to punch holes for fitting and securing the conduit.
Once the conduit holes are punched, these plates should be reattached to the UPS.
Installation
Connecting cables to the NX may require that the UPS be accessible from the left side to allow personnel to complete the connections and make necessary adjustments. After installation is complete,
the NX may be serviced from the front.
NOTE
When installing the UPS, the customer must provide a disconnect with overcurrent protection
at the output of the UPS.
10-30kVA UPS
The 10-30kVA NX consists of a single cabinet housing the UPS components and the internal battery
string.
Optional battery cabinets are available to provide extended run time. Each cabinet houses additional
strings of batteries that operate in parallel with the NX’s internal batteries. The cabinets are
designed to be bolted to the right side of the UPS (see Figure 1). Refer to 3.4 - External Battery Cabinet Installation for details.
Optional maintenance bypass/transformer cabinets (MBC-T) are available. These cabinets house the
components necessary to:
• Provide an external wrap-around maintenance bypass switch for servicing the UPS
• Provide voltage transformation for site or application requirements
• Provide a means for neutral isolation and allow installations for site without a neutral conductor
MBC-T cabinets are designed to be bolted to the left side of the UPS (see Figure 1). Refer to 4.5 -
Locating the Cabinet, for further details.
System Composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system
design requirements—e.g., UPS cabinet and External Bypass cabinet. In general, all cabinets used
will be the same height and are designed to be positioned side-by-side to form an aesthetically appealing equipment suite.
7
Page 16
1.6.4Optional Cabinets
If your NX installation includes a Maintenance Bypass Cabinet, the NX must be positioned to allow
the Maintenance Bypass Cabinet to be bolted to left side of the NX (see Figure 1). Cables from the
Maintenance Bypass Cabinet must be brought through the bottom side of the NX for connection.
The Maintenance Bypass Cabinet must be cabled and bolted to the NX before the UPS and bypass
cabinet are moved into their final position. Connect the input wiring to the Maintenance Bypass Cabinet ONLY after the units are connected and positioned.
Battery cabinets may be bolted to either side of the NX, unless used in configurations that include a
Maintenance Bypass Cabinet. If used with a Maintenance Bypass Cabinet, battery cabinets must be
installed on the right side of the UPS; see Figure 1 below.
Figure 1Cabinet arrangement
Installation
ALL UNITS VIEWED FROM ABOVE
Liebert
Maintenance
Bypass
Cabinet
NX connected only to MBC
(MBC must be on left side of the NX)
NX
(Battery Cabinets may be on either side of the NX)
Maintenance
Bypass
Cabinet
NX connected to Maintenance Bypass Cabinet and Battery Cabinets
(MBC must be on left side of the NX)
(Battery Cabinets must be on the right side of the NX in this
Liebert
NX
Battery
Cabinet
NX connected to Battery Cabinets
Liebert
NX
configuration)
Battery
Cabinet
Battery
Cabinet
Battery
Cabinet
8
Page 17
2.0ELECTRICAL CONNECTIONS
The UPS requires both power and control cabling once it has been mechanically installed. All control
cables must run separate from power cables in metal conduits or metal ducts that are electrically
bonded to the metalwork of the cabinets to which they are connected.
WARNING
!
Before connecting input power to the NX, ensure that you are aware of the location and
operation of the overcurrent protection devices that connect the UPS input/bypass supply to
the power distribution panel.
De-energize and lockout or tagout all incoming high- and low-voltage power circuits before
installing cables or making any electrical connections.
2.1Power Cabling
2.1.1Cable Rating
The main factors affecting the choice and size of cable are voltage, current (also taking into account
overcurrent), room temperature and conditions of installation of the cable.
The power cables of the system must be sized with respect to the following description:
• UPS input cables - The UPS input cables must be sized for the maximum input current, including the maximum battery recharge current, given in Table 27, with respect to the unit rating and
the input AC voltage.
• UPS bypass and output cables - The bypass and output cables must be sized for the nominal
output current, given in Table 27, with respect to the unit rating and the output AC voltage.
• Battery cables - Each UPS unit has its own internal batteries factory-wired. If connecting an
external battery cabinet, the battery cables must be sized for the battery discharge current at the
end-of-discharge voltage, as given in Table 27, with respect to the unit rating.
Electrical Connections
NOTE
Table 27 gives nominal currents for determining the size of UPS power cables. Other
important factors to consider include cable route length and coordination with protective
devices.
The power cables can be sized to suit the UPS unit rating according to Table 27.
Lug Size and Torque Requirements
Refer to Table 33 for lug size and torque requirements.
9
Page 18
2.1.2UPS Input Configuration
Figure 2 illustrates the NX in a split bypass (dual-input) configuration. In this configuration the
Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main
input. Both sources must be protected externally with properly sized protective devices. By default,
the unit ships with internal links installed between the Bypass input and Main input (single-input
configuration). To wire the unit as a dual input UPS, remove the links and wire the bypass to the
input bus bars, then wire the Main input directly to CB1 (see Figure 3).
The following are guidelines only and are superseded by local regulations and codes of practice where
applicable. Use wiring rated at 75°C or greater.
1. Take special care when determining the size of the neutral cable, as current circulating on the
neutral cable may be greater than nominal current in the case of non-linear loads. Refer to the
values in 10.4 - UPS Electrical Characteristics.
2. The ground conductor should be sized according to such factors as the fault rating, cable lengths
and type of protection. The ground cable connecting the UPS to the main ground system must
follow the most direct route possible. Control wiring and power wiring must be run in separate
conduit. Output and input cables must be run in separate conduit.
3. Consider using paralleled smaller cables for heavy currents—this can ease installation.
4. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current
ratings in Table 27. For terminal connection sizing, see Table 27.
5. In most installations, especially parallel multi-module systems, the load equipment is connected
to a distribution network of individually protected busbars fed by the UPS output, rather than
connected directly to the UPS itself. When this is the case, the UPS output cables can be rated to
suit the individual distribution network demands rather than being fully load-rated.
NOTE
If more load is added to the distribution panel, the unit’s cabling must be resized.
6. When laying power cables, do not form coils; this will help avoid increasing formation of
electromagnetic interference.
NOTE
Left-side access may be required when making power connections. Cable connections should be
made before a cabinet is attached to the left side of the NX or before the UPS is placed where
another obstruction, such as a wall, is against the NX’s the left side.
10
Page 19
2.1.4Cable Connections
The rectifier input, bypass and output are easily accessible from the left side of the unit for installation. All require lug type terminations. They are connected to busbars on the left side of the NX and
below the switch, as shown in Figure 3. These busbars are accessible when the left side panel is
removed. Busbars to connect external batteries are accessible from the front of the UPS.
NOTE
External battery connection access requires removal of a protective panel on the lower front of
the UPS to the left of the bottom two battery shelves.
Figure 3Input busbars
Electrical Connections
Remove these links
for dual input
configuration and
wire UPS Main input
directly to CB1
Output Busbars
(Phases are
indicated by
letters below the
bars)
CB
OUTPUTBYPASS
The internal batteries are connected with Anderson connectors inside the battery compartment. The
batteries are connected to fuses to protect the NX and connected equipment (see Figure 4).
Figure 4Battery fuses and connections
Rectifier Input
Busbars
(Phases are
indicated by
letters below the
bars)
ACBA
Internal battery input
connections
150A 500V AC/DC
B
Bussmann
MADE IN USA
11
150A 500V AC/DC
B
Bussmann
MADE IN USA
Battery fuses
(fuses are behind
access plate on
front of UPS; see
Note on page 11)
Page 20
2.1.5Safety Ground
The safety ground busbar is located below the neutral input and output busbars as shown in
Figure 5 below. The safety ground cable must be connected to the ground busbar and bonded to each
cabinet in the system.
All cabinets and cable conduit should be grounded in accordance with local regulations.
WARNING
!
Failure to follow proper grounding procedures can result in electric shock hazard to personnel
or the risk of fire, should a ground fault occur.
NOTE
Proper grounding significantly reduces problems in systems caused by electromagnetic
interference.
NOTE
The ground and neutral busbars are easily accessible when the left protective cover plate is
removed. Cable connections should be made before a cabinet is attached to the left side of the
NX or before the UPS is placed where another obstruction, such as a wall, is against the NX’s
the left side.
Figure 5Ground and neutral busbar connections
Electrical Connections
Output neutral
busbar
Ground
busbar
2.1.6Protective Devices
For safety, it is necessary to install circuit breakers in the input AC supply and external battery battery cabinets, external to the UPS system. Given that every installation has its own characteristics,
this section provides guidelines for qualified installation engineers with knowledge of operating practices, regulatory standards and the equipment to be installed.
UPS Rectifier and Bypass Input Supply
• Protection from excessive overcurrents and short circuits in power supply input
External overcurrent protection for the AC output circuit is to be provided. See 10.4 - UPS Elec-
trical Characteristics and Table 29 for overload capacity.
High-speed fuses and SCRs are used for internal battery circuit overcurrent protection. When an
external battery supply is used, overcurrent protection for the battery circuit is to be provided by
the customer.
• Dual Input
When wiring the UPS with dual inputs, the Rectifier input and the Bypass input must be protected separately. Size the breakers according to the input currents shown in Table 27.
OUTPUT
NEUTRAL
INPUT
NEUTRAL
Input neutral
busbar
System Output
When using an external distribution panel for load distribution, the output neutral and input neutral
must be separated at the input to the UPS.
12
Page 21
2.1.7Cabling Procedure
CAUTION
!
The operations described in this section must be performed by authorized electricians or
qualified technical personnel. If you have any difficulties, contact your local Liebert
representative or Liebert Global Services.
NOTE
Hydraulic pressure pliers, combinative tools and piston ring pliers should be used to connect
AC wiring.
Once the equipment has been positioned and secured for operation, and the battery and ground collars have been connected (see 2.1.4 - Cable Connections), connect the power cables as described
below. (Study the reference drawing in 6.0 - Installation Drawings.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
tagged out before installing cables or making any electrical connections.
2. Remove the left side panel to gain easier access to the connections busbars.
3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar
located on the bottom of the equipment below the power connections. All cabinets in the UPS
system must be connected to the user’s ground connection.
NOTE
The grounding and neutral bonding arrangement must comply with the National Electrical
Code and all applicable local codes.
Electrical Connections
4. Identify and make power connections with incoming cables according to Steps 5 through 11.
Common Input Connections
5. For common bypass and rectifier inputs, connect the AC input supply cables between the power
distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to
44 lb-in. (5 N-m) using the M6 bolt provided.
6. The input neutral cable must be connected to the input neutral busbar (N). See Figure 5.
Dual Input Connections
7. For bypass connect the AC input supply cables between the power distribution panel and the UPS
input busbars (A-B-C terminals) and tighten the connections to 44 lb-in. (5 N-m) using the M6
bolt provided.
8. For Rectifier Input connect AC input supply cables between the power distribution panel and the
UPS input circuit breaker (A-B-C terminals)
9. The bypass and rectifier input neutral cables must be connected to the input neutral busbar (N).
See Figure 5.
NOTE
Both the rectifier and bypass feeds MUST come from the same utility source, except if the UPS
system includes either a configuration F or P external maintenance bypass cabinet.
Output System Connections—Ensure Correct Phase Rotation
10. Connect the system output cables between the UPS output busbars (A-B-C N terminals) and the
critical load and tighten the connections to 44 lb-in. (5 N-m) (M6 bolt).
WARNING
!
If the load equipment will not be ready to accept power on the arrival of the commissioning
engineer, then ensure that the system output cables are safely isolated.
13
Page 22
Internal UPS Battery Connections
The UPS internal batteries will be connected at the factory, EXCEPT the Anderson connections
between the shelves and to the fuses.
WARNING
!
The DC bus is live when this internal battery connection is made. This connection is to be
performed ONLY by Liebert Global Services at startup.
Observe the battery cable polarity. Be sure that the battery connector is made with the correct polarity.
11. Refit all protective covers removed for cable installation
2.2Control Cables
2.2.1Monitor Board Features
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker, battery temperature sensor), communicate with a personal
computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).
The monitor board, arranged for this purpose, is located on the rear of the operator access door. The
main features are:
• Input and Output dry contacts signal (one pair of contacts of relay)
• Emergency Power Off control (EPO)
• Environmental parameter input interface
• User communication (for data setting and user background monitor)
• Intellislot™ interface
• Modem interface
• Temperature detect interface
Figure 6 shows the relationship and connection between the monitoring (U2) board and other boards
in the UPS.
The UPS provides input dry contacts and output dry contacts.
2.3.1Input Dry Contacts
There are several input dry contacts at the X3 slot.
X3
Intellislot 2
Intellislot 1
Intellislot 3
J23
J12
J9
J15
J16
J17
X4
X6
PWR
MODEM
SNMP CARD
X5
X4
J24
NOTE: The black square ()
on each slot indicates Pin 1.
Figure 8Input dry contacts
Table 1Input dry contacts at X3
PositionNameDescription
J4.1ENV
J4.2BtGBattery Ground Fault Detection (N.C.)
J4.3GEN
J4.4+12V+12V Power
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.
3
1,2
NOTE: The black square () on each slot indicates Pin 1.
Battery Room Alarm (N.C.)
Generator Join Detection (N.O.)
15
Page 24
2.3.2Maintenance Bypass Cabinet Interface
J26 and J30 are the MBC interface.
Table 2Maintenance bypass cabinet interface
PositionNameDescription
J26.1T_IT
J26.2AUX_IReserved
J26.3+12V+12V Power
J26.4GNDPower Ground
J30.1FUSEReserved
J30.2F_FANFan Fail Alarm (N.C.)
J30.3T_OT
J30.4AUX_OReserved
1 - Must be configured by software before becoming active
1
Input transformer over temperature (N.C.)
1
Output Transformer Overtemperature (N.C.)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 82 and 197 feet (25-60m), respectively.
2.3.3BCB Box Interface
Electrical Connections
J10 is the BCB box interface.
Table 3BCB box interface
PositionNameDescription
J10.1DRVBCB Driver Signal - Reserved
J10.2FBBCB Contact State
J10.3GNDPower Ground
J10.4OL
BCB On-Line - Input - This pin will become active when
BCB interface is connected. (N.O.)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 82 and 197 feet (25-60m), respectively.
NOTE
If BCB interface is connected, a jumper needs to added between Pin 3 and Pin 4.
Figure 9Jumper connection for BCB interface
UPS Monitoring Board
J10
OL
OL
FB
DRV
GND
Aux – N.O.
Aux – N.O.
Battery Circuit Breaker
16
Page 25
2.3.4Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 10 and Table 4).
Figure 10 Output dry contacts and EPO wiring for firmware before M170
Electrical Connections
+12V
J13
BFP_S
BFP_C
BFP_O
Table 4Output dry contact relays
PositionNameDescription
J13.2BFP_OBypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J13.3BFP_SBypass feedback protection relay center
J13.4BFP_CBypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.
J21.2INV_OInverter mode relay. Normally open. Closed when UPS is in inverter mode.
J21.3INV_SInverter mode relay center
J21.4INV_CInverter mode relay. Normally closed. Open when UPS is in inverter mode.
J25.2ACF_OMain input fault relay. Normally open. Closed when main input is in fault.
J25.3ACF_SMain input fault relay center
J25.4ACF_CMain input fault relay. Normally closed. Open when main input is in fault.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 82 and 197 feet (25-60m), respectively.
2.3.5EPO Input—Optional
J21J25J28
EPO-H
INV_S
INV_C
INV_O
ACF_C
ACF_S
ACF_O
X2X1
EPO-L
Firmware Before M200
The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel
or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 10, is the remote EPO input interface. It is active when shorted from
EPO-L to EPO-H.
If an external Emergency Stop facility is required, it is connected terminals EPO-L to EPO-H of the
auxiliary terminal block (X2). It also is connected to the Normally Open remote stop switch between
these two terminals using shielded cable (see Figure 10 and Table 5). If this function is not used,
terminals EPO-L to EPO-H must be opened.
Table 5EPO input contact relays
PositionNameDescription
J28.2EPO_LEmergency Power Off Low
J28.4EPO_HEmergency Power Off High
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static
bypass. It does not internally disconnect the input power supply.
To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote
EPO is activated.
17
Page 26
Firmware M200 or Later
The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by
a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 11, is the remote EPO input interface. The EPO has a NO/NC contact
point becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1.
If an external Emergency Stop facility is required, it is connected terminals X2: 1&2 or X2: 3 and 4 of
the auxiliary terminal block (X2). It also is connected to the Normally Open or Normally Closed
remote stop switch between these two terminals using shielded cable (see Figure 11 and Table 6). If
this function is not used, terminals X2: 3 and 4 must be opened and X2: 1 and 2 must be closed.
Figure 11 EPO wiring for firmware M200 or later
Electrical Connections
J2 8
EPO - NO
EPO - NC
Table 6EPO input contact relays
PositionNameDescription
J28.1EPO_NCEPO Activated when opened to J28.2
J28.2EPO_NCEPO Activated when opened to J28.1
J28.3EPO_NOEPO Activated when shorted to J28.4
J28.4EPO_NOEPO Activated when shorted to J28.3
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static
bypass. It does not internally disconnect the input power supply. To disconnect ALL power to
the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally Closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor
board and must remain installed if using NO contacts.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 82 and 197 feet (25-60m), respectively.
X2
18
Page 27
3.0BATTERY INSTALLATION
3.1Introduction
Liebert recommends that the batteries in external cabinets match the internal batteries in the NX in
manufacturer and type.
If using multiple sets of batteries connected in parallel to provide the required battery backup run
times, fit each set with an isolating device to permit working on one of the battery sets while leaving
the others in service and providing backup protection.
When replacing batteries, replace with the same manufacturer and type, or equivalent. See your Liebert representative for a list approve batteries.
NOTE
The NX, as shipped, has 24 12-volt batteries installed internally in each unit.
3.2Safety
Special care should be taken when working with the batteries associated with the NX system equipment. When all batteries are connected together, the battery terminal voltage may exceed 324V and is
POTENTIALLY LETHAL.
Battery Installation
WARNING
!
The NX's internal batteries are connected and energized even if the UPS is turned Off. To
minimize the risk of injury, a qualified service person should disconnect internal batteries
before any maintenance is performed on the unit.
The center of the battery is connected to the neutral of the UPS and is grounded.
A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
3.3UPS Batteries
The NX's internal batteries are fully charged before the unit is shipped. During storage and transportation, some charge is lost. All batteries should be recharged before use. The battery charger works
only when the NX is connected to input power and turned On.
NOTE
Full safety instructions concerning the use and maintenance of UPS batteries are provided in
the appropriate battery manufacturer's manuals, available on the manufacturer's Web site.
The battery safety information contained in this section relates to key considerations that must
be taken into account during the installation design process and might affect the design
outcome, depending on your installation.
19
Page 28
3.4External Battery Cabinet Installation
3.4.1Matching Battery Cabinets
Two sizes of optional battery cabinets are available. Refer to Figures 13 and 14. The same model battery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Battery
run time depends on the cabinet model, the number of cabinets and the load on the UPS.
Handling—The battery cabinet has casters to facilitate movement over short distances. The bottoms
of the battery cabinets are reinforced to permit movement by forklift over longer distances.
Inspection—Remove all panels and visually inspect the batteries, bus connections, and cabinet for
any damage. Exercise caution; voltage is present within the battery cabinet even before installation.
If there are signs of damage, do not proceed. Call Liebert Global Services at 1-800-542-2378.
Storage—The batteries can be stored for up to six months without appreciable deterioration. If planning to store a battery cabinet for longer than six months or at temperatures higher than 77°F (25°C),
contact Liebert Global Services for recommended precautions.
The following notes, in conjunction with the diagrams (Figure 13 through 12), illustrate the broad
principles to be followed when fitting and connecting the majority of battery cabinet installations.
CAUTION
!
Any battery system should be installed by qualified personnel.
When installing an external battery cabinet that is NOT a Liebert NX battery cabinet, the customer
must provide overcurrent protection. See Table 27 for sizing of protection devices.
Battery Installation
NOTE
When using an external battery supply that is not provided with the UPS, please make
reference to the battery manufacturer’s installation manual for battery installation and
maintenance instructions, available on the manufacturer’s Web site. When replacing batteries,
Liebert recommends that the batteries in external cabinets be the same type used internally in
the NX. See Table 28 for a list of batteries that are approved for use with this product.
3.4.2Connecting the Batteries
If the NX battery cabinets are installed on a raised floor, the battery power cables and circuit breaker
control cables may be routed to the UPS cabinet via the floor of the cabinet (bottom entry).
If the NX battery cabinets are installed adjacent to one another on a solid floor, these cables may be
passed between the cabinets through lifting slots in the lower sides of the cabinets.
Intertray connections must be made before the battery cabinet may be used.
Figure 14 Wide battery cabinet, 57 in. (1488mm) - front view
Top cable entry
Battery tray
support
Battery tray
Batteries
BCB plate and
BCB
Service
shelf
21
Page 30
3.4.3Installation Considerations
Position—Liebert battery cabinets come in versions specific to either the left or right side of the
UPS. Control wires and power cables are cut to different lengths for the different versions. If the system includes a matching maintenance bypass cabinet (MBC), the MBC should be mounted to the left
of the UPS (nearest the busbars) and the battery cabinet(s) should be installed to the right of the
UPS. Otherwise, left-side placement of the battery cabinet is preferable.
The battery cabinet(s) are designed to be located conveniently next to each UPS module, and are also
available in stand-alone configurations with painted side panels. The front access design eliminates
side and rear service clearance requirements. Refer to Table 39 for battery cabinet dimensions and
weights.
Bolt-On Cabinets—Matching battery cabinets are designed to bolt onto the side of the UPS module
cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in the front
and two places in the rear.
Service Clearance—Allow front access to the battery cabinet at all times for maintenance and servicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of
clearance at the front of the cabinet when operating. Side and rear panels do not require service clearance.
Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet, eliminating the need for external conduit runs. Route cables before moving cabinets into final position for bolting together. No top or bottom entry cables are required, except for remotely located cabinets which
require conduits. Refer to Figure 15.
Software—To allow the UPS to accurately display the battery run time, the number of battery cabinets must be noted when performing initial startup and setup using the configuration software. This
is to be performed by the Liebert Global Services customer engineer when commissioning the unit.
Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the
cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small
amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery
cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet.
Battery Support Tray—Be sure to connect the battery tray support to the front of the cabinet
before sliding a battery tray out for connection or service. Without the support, the battery tray may
fall out of the cabinet. See Figure 16 for details.
Battery Installation
22
Page 31
Figure 15 Internal cable wiring from battery cabinet to Liebert NX
Power cables from output power switch
Battery Installation
Power cables
from batteries
BATTERY
CABINET
Power cables
(black) enter
channel down side
of NX to power
input connections
LEFT SIDE
INTERIOR
OF UPS
Power cables exit battery
cabinet, enter Liebert NX
Power cables run
across top
of Liebert NX
RIGHT SIDE
INTERIOR
OF UPS
RIGHT SIDE CABLE
ENTRY SHOWN;
CUTOUTS ON LEFT
SIDE PERMIT
CONNECTION
FROM THAT SIDE.
Figure 16 Battery tray and supports
Slot in support secured by
screw-in connector at
corner of battery tray ...
... and notched end of support
slips into slot at top corner
of battery compartment
Battery tray supports attach
to interior surface of NX
front door (note notched
ends of supports)
23
Page 32
3.4.4Connecting the Battery Cabinet to the UPS
After the battery cabinet equipment has been positioned and secured for operation and the batteries
have been connected, connect the power cables as described below. (See Figure 36.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or
tagged out before installing cables or making any electrical connections.
2. Remove the UPS left side panel to gain access to the equipment ground busbar.
3. Remove the external battery terminal block plate on the lower left side of the UPS behind the
front door.
4. Remove the battery cabinet front panel to gain access to the connection bars.
5. Connect the safety ground and any necessary bonding ground cables to the copper ground busbar.
(example: UPS located on the bottom of the equipment below the power connections).
All cabinets in the UPS system must be connected to the user's ground connection.
NOTE
The grounding and neutral bonding arrangement must be in accordance with the National
Electrical Code and all applicable local codes.
6. Connect the system battery cables from the UPS battery terminals (+ N -) to battery cabinet BCB
(+ N -) as shown in Figure 36. Be sure that the battery connections are made with the right
polarity, and tighten the connections to 44 lb-in. (5 N-m) (M6 Bolt). Do not close the battery circuit
breaker before the equipment has been commissioned.
7. Connect supplied auxiliary control cable to pins J10.2 and J10.3 on the U2 monitoring board (see
2.3 - Dry Contacts). Add a jumper wire between J10.3 and J10.4.
Battery Installation
3.5Non-Standard Batteries
When batteries other than a matching battery cabinet are used, a remote battery disconnect switch
with overcurrent protection is required per the National Electrical Code. Contact your local Liebert
sales representative about this option.
Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions.
Verify that the battery area has adequate ventilation and battery operating temperature complies
with the manufacturer's specifications and with all applicable national and local codes.
If you have any questions concerning batteries, battery racks or accessories, contact Liebert Global
Services at 1-800-543-2378.
24
Page 33
Maintenance Bypass Cabinet
4.0MAINTENANCE BYPASS CABINET
The Maintenance Bypass Cabinet is designed to operate in UPS mode, bypass mode and maintenance
mode. The mode is selected using the Bypass Switch.
Figure 17 Single UPS with external Maintenance Bypass Cabinet—typical configuration
4.1Bypass Switch
The Bypass Switch allows easy and rapid transfer of connected loads between the UPS and Bypass
source.
4.2Normal (UPS) Mode
While the Maintenance Bypass Cabinet rotary switch is in the NORMAL position, the UPS is supplying the connected load with continuous, high-quality AC power. In this mode of operation, the load is
protected by the UPS.
25
Page 34
4.3Bypass Mode
When the Maintenance Bypass Cabinet is in the Bypass mode, it provides an alternate path for power
to the connected equipment. Should the UPS need to be taken out of service for limited maintenance
or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the
UPS inverter to the bypass source. In this mode, power will still be supplied to the UPS; however, the
load is NOT protected by the UPS.
4.4Maintenance Mode
When the maintenance bypass cabinet is in the Maintenance mode, it provides an alternate path for
power to the connected equipment. Should the UPS need to be taken out of service for limited maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT protected by the UPS.
4.5Locating the Cabinet
This Maintenance Bypass Cabinet may be mounted to the left of the UPS or installed as a stand-alone
unit. In either case, ensure that the unit is in a well-ventilated area and that there is clearance for
access to the switches and cable connections as required by national and local codes.
4.6Cable Installation
4.6.1Wiring Preparation
Maintenance Bypass Cabinet
Be sure that the unit is not connected to any AC utility power source or UPS before installing any wiring to this unit. This Maintenance Bypass Cabinet should be installed by a qualified / certified electrician.
WARNING
!
Please read this section thoroughly before attempting to install wiring to this unit.
Removing the Cover Plates
Plates cover the input and output terminals on the front of the Maintenance Bypass Cabinet (see
Figure 18). Remove these and keep the screws and plates for reinstallation.
Extract screws
from corners to
remove the
access plate
26
Page 35
4.6.2Power Cable Installation
Refer to Tables 35, 36 and 38 when selecting cables.
NOTE
Transient and steady state earth leakage currents may occur when starting the equipment.
This should be taken into account when selecting ground current detection devices because
these will carry the earth leakage currents of both the UPS equipment and the load.
4.6.3Input/Output Wiring
Follow the steps below to connect the input wiring:
NOTE
Input wiring must be installed using conduit if cabinet is not mounted to the immediate left of
the UPS.
1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch
the appropriate size hole for the size conduit being used. Pull the three/four input wires through
it, allowing some slack for installation. For cabinets that are located to the immediate left of the
UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that
the edge guarding is installed and intact.See Figure 19.
Wiring access is on
lower right side of
Maintenance
Bypass Cabinet
Access panel removed;
wiring connects NX and MBC
Edge Guard
2. Secure the conduit to the access plate of the Maintenance Bypass Cabinet.
3. Input power cables connect to the system input circuit breaker. Refer to Figure 37 -
Maintenance Bypass interconnection
4. Connect the ground (earth) wire to the earth busbar and tighten it to 44 lb-in. (5 N-m) (M6 bolt).
5. Locate UPS input and output cables and access panel to UPS on lower right side. See Figure 19.
NOTE
If the maintenance bypass cabinet is not to be bolted to the UPS, use either top or
bottom access plate.
6. Connect the system ground cable between the Maintenance Bypass Cabinet and UPS and tighten
the connections to 44 lb-in. (5 N-m) (M6 bolt).
27
Page 36
7. Connect the system input cables between the Maintenance Bypass Cabinet 'UPS Input' Busbars
(A-B-C N terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to
44 lb-in. (5 N-m) (M6 bolt).
8. Connect the system outnput cables between the Maintenance Bypass Cabinet 'UPS Output'
Busbars (A-B-C N terminals) and UPS output busbars (A-B-C N terminals) and tighten the
connections to 44 lb-in. (5 N-m) (M6 bolt).
9. Connect supplied control wire to X3 on the Parallel (M3) board (see Figure 20).
WARNING
!
The control wire must be installed to ensure proper operation of the system and fully protect
the load when switching between bypass cabinet and UPS.
Figure 20 Maintenance bypass control wire location
Maintenance Bypass Cabinet
:X T M AIN T
485-
485+
Terminal
P2X2
2
Block
Location
P1X2
1
X3
DBS
NOTE
For startup procedure, see the UPS operations and maintenance manual, SL-25210.
28
Page 37
4.7Bolting Cabinets Together
NOTE
UPS wiring must be completed before the cabinets are bolted together.
1. Line up cabinets so that mounting holes are aligned.
Maintenance Bypass Cabinet
Place cabinets so mounting holes are
aligned.
A bolt from the adjacent cabinet may be
screwed into the threaded top hole, or a
bolt may be inserted through the lower
hole and screwed into the threaded hole
in the adjacent cabinet.
2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the
UPS side or from the MBS side, whichever is more convenient.
29
Page 38
5.0OPTION INSTALLATIONS
5.1Load Bus Synchronization
The Load Bus Synchronizer (LBS) keeps the output of two independent UPS systems or parallel UPS
systems in synchronization even when the systems are operating in different modes and even when
either or both systems are operating on batteries. When the LBS is used, one UPS system is designated as master, the other as slave.
The LBS option is typically used with dual-corded equipment or with either the Liebert SmartSwitch
or Static Transfer Switch (STS) for single-corded equipment.
5.1.1Performance Requirements
The DBS operates under the following conditions:
• Both master and slave are on inverter
(either system may be on inverter through the rectifier or on inverter through the batteries)
• Master on inverter, and slave on bypass
• Master on bypass, and slave on inverter
• Master and slave on bypass IF the bypass source is the same for both systems
5.1.2DBS Cable and Settings
For NX-to-NX dual bus configuration, only one optional LBS cable is required, the built-in LBS will
operate normally without extra LBS control box or interface box. The LBS port is X4 on the parallel
board (M3). The parallel board is on the interior of the NX, above and left of the power electronics; see
Figure 32.
Option Installations
An optional, 9-pin LBS cable is used to connect two UPS systems through each system’s DB9 port on
its parallel board. For two parallel systems, the LBS cable can be mounted between any two units
belonging to different parallel systems. For information about the LBS kit or to order the optional
equipment, see your local Liebert representative.
The LBS cable is connected as illustrated in Figure 21.
Figure 21 Load Bus Synchronization cable connection
LBS Cable
Parallel Board
X3
X4
X2-1 X2-2
X1-1 X1-2
Parallel Board
X4
X2-1 X2-2
X1-1 X1-2
The parallel board is on the
interior of the NX, above and
left of the power electronics;
see Figure 32
UPS Module or
System #1
UPS Module or
System #2
The LBS function is activated with configuration software; when the LBS takes effect, the graphic
LCD will display “LBS active.”
30
Page 39
5.2Configuring Parallel System Operation
5.2.1General
The NX uses intelligent and reliable decentralized technology to achieve parallel operation of two or
more modules of the same rating.
The 1+N system is used to:
• Increase the reliability of the system to ensure adequate power supply to the critical load connected.
• Increase serviceability and allow the execution of maintenance operations and reparations without affecting the ordinary operating conditions of the system (depending on the redundancy level).
Option Installations
31
Page 40
5.2.2Features of Parallel System
• The hardware and firmware for parallel UPS module operation is standard in the NX, and the
configuration can be set up by changing the settings in configuration software.
• It is easy to install the parallel cables in a ring, providing high reliability and redundancy. And
the intelligent paralleling logic provides the user with maximum flexibility. For example, shutting down or starting up the UPS modules in the parallel system can be done in any sequence. If
an overload transfer occurs, the whole system can recover automatically from bypass mode after
the overload is cleared.
• The total load of the parallel system can be queried from each module’s liquid crystal display
screen.
Figure 22 1+N system block diagram
Option Installations
CB1
208V 60Hz
4W
CB3 CB4
CB5CB6
4W
UPS1
208V 60Hz
4W
UPS2
208V 60Hz
CB2
208V 60Hz
3 or 4W
CB7CB8
NOTES:
1. Install in accordance with national and local electrical codes.
2. The equipment ground connection must be connected to the system ground wire.
3. UPS AC input and AC output cables must be run in separate conduits.
4. Control wiring and power wiring must be run in separate conduits.
5. See Electrical Data Specification Sheet U3818101 for individual configurations.
4W
UPS3
208V 60Hz
32
Page 41
5.2.3Operating Principles
Redundancy Paralleling
The 1+N parallel redundant system can noticeably improve system reliability. In normal condition,
none of the UPS modules work at full load. That means that even if the load is increased, the system
will not transfer to bypass. And when a UPS module shuts down due to any failure, the remaining
UPS modules can still power and protect the load. When redundancy is lost due to module failure or
load increase, the parallel system will trigger an alarm.
5.2.4Operation Modes Summary
The parallel system also has operation modes such as normal, battery, bypass and maintenance
bypass. All UPS modules in the 1+N parallel system operate in coordination.
• Normal Mode Operation
The load is powered by the inverters of all the UPS modules in the system. If the frequency of
bypass is within the synchronous range, the inverter will be synchronized with the bypass. Otherwise, the system will operate at nominal frequency.
• Battery Mode Operation
The batteries of all UPS modules power the load through their inverters. The system operates at
nominal frequency.
• Bypass Mode Operation
The condition to transfer to bypass mode is essentially the same as that of single-module system.
The bypass of all the UPS modules powers the load.
• Maintenance Bypass Mode Operation
The sequence to transfer to maintenance bypass mode is the same as for transferring a single-
module system. The maintenance bypass switches should be switched on as synchronously as possible. Thus the system can be repaired without interrupting the power supply to critical load.
Option Installations
5.3Installing Parallel System
The basic installation procedure of parallel system is the same as that of single-module system. The
following sections introduce only the installation procedures specific to the parallel system.
5.3.1Conditions for Parallel System
• Each UPS module should have the same rating, the same firmware and hardware version.
• Each UPS module must have the same bypass source.
• The outputs of all UPS modules are connected altogether.
• The main inputs can be from different sources, but the phase rotation sequence of main inputs,
bypass inputs and outputs must be correct and the same.
• The parallel logic cable and load sharing cable must be connected in a ring correctly (see
Figure 23).
5.3.2Cabinet Installation
Parallel system composed of two or more UPS modules using parallel cabinet
The UPS modules that will form the 1+N system should be placed side-by-side. Each battery cabinet
is placed next to its corresponding UPS module.
The parallel cabinet should be placed in the middle of the system.
5.3.3Preliminary Checks
Each UPS module should have the same rating, the same firmware and the same hardware version.
Refer to the instructions in 5.3.1 - Conditions for Parallel System.
5.3.4Protective Devices
For each UPS, refer to Table 27. For each system, refer to Table 37.
33
Page 42
5.3.5Power Cables
Wiring of power cables is similar to that of single-module system (See 2.1 - Power Cabling). The
bypass sources of all modules should be the same, and the outputs should be connected altogether correctly.
Power cables will be supplied by customer. Power cables to the UPS’s of the 1+N paralleling cabinet
must be routed through either the top or bottom entry access of the UPS.
For systems using a parallel cabinet, see Figures 38 and 40 through 42 for power cable terminations.
NOTE
The length and specifications of power cables including the bypass input cables and UPS
output cables should be the same, thus the load can be shared evenly in bypass mode.
5.3.6Parallel Control Cables
Parallel System Control Cables
Make the connections listed below on the parallel logic board (M3) inside the NX. (See Figure 32 for
the location of the parallel logic board):
Shielded and double-insulated control cables available in lengths of up to 100 feet (30m) must be
interconnected in a ring configuration between UPS modules as shown below. The ring configuration
ensures high reliability of the control (refer to Figure 23).
See Figure 25 for dry contacts control cable wiring diagram.
Option Installations
Figure 23 Connecting '1+N' system parallel control cables
P5
X4
P4P1
UPS
Parallel Board
X3
X2-2 X2-1
P2
X1-1 X1-2
P3
1234
Parallel Board
X3
P5
X4
X2-2 X2-1
P2
X1-1X1-2
P4P1
P3
Parallel Board
X3
X2-2 X2-1
P2
X1-1X1-2
P3
Auxiliary Dry Contact Cables
The external output breaker of each UPS must have Normally Open auxiliary contacts. These contacts must be wired to connector X3 on the Parallel Logic Board (M3). See Figure 24.
P5
X4
P4P1
Parallel Board
X3
P5
X4
X2-2 X2-1
P2
X1-1X1-2
P4P1
P3
Interconnecting
Cables
34
Page 43
Figure 24 Auxiliary dry contact cables for output breaker in multi-module system
Option Installations
X3
DBS
:X T M AIN T
485-
485+
P2X2
2
P1X2
1
CAUTION
!
The auxiliary control wire must be installed to ensure proper operation of the system.
NOTE
For startup procedure, see the UPS operations and maintenance manual, SL-25210.
Figure 25 Dry contacts, multiple UPS modules with distribution panel
Input Distribution
UPS 1
M3 Board
X3
Ext. Maint. Ext. Out
QUPS
To Load
UPS 2
M3 Board
X3
Ext. Maint. Ext. Out
UPS N
M3 Board
X3
Ext. Maint. Ext. Out
Q1ExtQ2ExtQnExt
QByp
35
Page 44
5.3.7Emergency Power Off (EPO)
The external emergency stop facility is identical to that described for the single-unit installation—
that an individual emergency stop button is provided for each unit.
Figure 26 Connecting EPO push button
Option Installations
UPS2
Normally
Open EPO
Normally
Closed EPO
X2:3
X2:4
X2:1
X2:2
Monitor Board
UPS1
Monitor Board
UPS1
X2:3
X2:4
X2:1
X2:2
Monitor Board
UPS2
Monitor Board
5.4Battery Circuit Breaker Box
The box contains the same battery isolating circuit breaker as mounted in the battery cabinet.
Two battery circuit breaker boxes are available for use in installations where the battery is not
installed in the battery cabinet, in which case the appropriate battery box is fitted as close as possible
to the battery and connected to the UPS equipment as illustrated in Figure 27.
The battery circuit breaker box, is required to protect the battery from overcurrents. It also provides
electrical isolation between the UPS and the battery, permitting technical service personnel to reduce
the risks involved in maintenance work to a minimum.
A separate safety earth must be connected between the UPS unit and circuit breaker box.
Two boxes are available depending on the UPS power rating.
Table 7Available battery circuit breaker boxes
Dimensions (in)
UPS
10-15 kVA32.25x20.25x8.370A
20-30 kVA32.25x20.25x8.3125A
The circuit breaker has the following features:
• Short-circuit protection.
• Protection against battery cabinet and ups connection errors (polarity reversal +/-).
H-W-DCircuit Breaker
36
Page 45
Figure 27 Battery circuit breaker box connections
Option Installations
3.9"
(98mm)
(3) 1/2" (12.7mm)
dia. knockouts
for control wiring
conduit entry
2.5"
(63.5mm)
TB1
32.3"
(819.2mm)
10.8"
(274mm)
5.4"
(137mm)
Top View
(508mm)
(381mm)
Front View
20.0"
15.0"
4.0"
(101.2mm)
31.5"
(800.1mm)
8.3"
(211.7mm)
1
2
3
4
5
6
TB1
COM Black
N.O. Red
N.C. Blue
From Customer’s Battery System
(field-supplied and field-installed)
Connect to UPS Module
(field-installed)
(-)
(+)
J10.2
J10.3
(GND)
Midpoint
Midpoint
(-)(+ )
Circuit Breaker
(-) ( +)
(-)
(+)
72 Cells
(+)
(-)
(-)
(+)
72 Cells
CB
Load
Side
CB
Line
Side
.31" dia.
(Typ. 4 places)
(7.9mm)
.38"
(9.5mm)
(3) 1/2" (12.7mm)
dia. knockouts
Bottom View
for power wiring
conduit entry
(refer to top dimension)
NOTES:
1. NEMA 1 enclosure provided which is suitable for
wall mounting only. Approximate weight is 60 lb.
2. Hardware for connecting cables to the breaker supplied.
3. Circuit breaker, Cutler-Hammer FD4125ED13D15A02 for 20/30 kVA;
FD4070ED13D15A02 for 10/15 kVA
4. Color: IBM off-white.
5. Mount enclosure and pull all cables into enclosure before installing dry contacts.
6. Low voltage wiring needs to enter from the top of the enclosure, in separate conduit from power cables.
7. Line side power connections to lugs: (1) # 6AWG per connection for 10 to 15 kVA.
(1) # 2AWG per connection for 20-30 kVA to lugs:. load side power connections to busbars; see detail.
8. Power cables must be sized to limit voltage drop from battery system to UPS to be a maximum 4 VDC.
.62"
(15.8mm)
NOTE
1. The signal cables in this figure must be shielded and double-insulated.
2. Connect the Pes (Protection Earth) of the UPS cabinet and BCB box to the same point.
.5"
(12.7mm)
1"
(25.4mm)
(11.8mm)
.47"
(11.8mm)
Midpoint Busbar Detail
DPN U3813078 Rev. N
1.93"
(49mm)
.46"
37
Page 46
5.5Battery Start
With this option, the NX UPS can be started with power supplied only by the batteries (at charged
condition). This type of start, in the absence of utility power, allows independent utilization of battery
power and provides for higher availability in some circumstances.
CAUTION
!
Before attempting to start the UPS without utility power present, ensure that the batteries
are fully charged—over 2.1V per cell—and will supply adequate run time to the load.
5.6Remote Alarm Monitor
Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel which is
driven by voltfree alarm status contacts (from an optional relay alarm board).
5.7Analog Input Interface
At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is
2 percent. “ENV-T” is used for environment temperature detecting.
5.8Power Output
The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to
12V. The maximum current is 500mA.
Option Installations
5.9Intellislot™ Communication
The NX has three Intellislot ports to allow field-installation of optional communication cards. Intellislot cards communicate via Liebert’s proprietary ESP2 protocol to cards that translate the information
into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide dry contact signals for
external signaling of operating status.
The Intellislot communication ports may be installed or removed while the NX is operating..
38
Page 47
5.10OC Web Card—SNMP/HTTP Network Interface Card
This network interface card provides all real-time data and status information as SNMPv1 traps for
connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status
information and all measured parameters for display via a Web browser.
Table 8NX communication options
On the UPS
Physical
description
of port
Top
Intellislot
Middle
Intellislot
Bottom
Intellislot
Top
DB9 port
Bottom
DB9 port
Labeled
ID Name
of Port
Intellislot 1
(On Monitor Board)
Intellislot 2
(On Monitor Board)
Intellislot 3
(On Monitor Board)
RS232-1Comm 1
RS232-2Comm 2
LCD screen,
under Settings,
controlled by:
Comm 1
Comm 2
Comm 3
Monitoring
Devices
supported
Multiport 4any
Relaycard-intany
OCWEB-LB
Modbus/Jbus2400
Multiport 4any
Relaycard-intany
OCWEB-LB
Modbus/Jbus2400
Multiport 4any
Relaycard-intany
OCWEB-LB2400
Modbus/Jbus2400
Multilink Serial
Service Software
(Reserved)
Option Installations
Baud
rateComments
2400
2400
9600
9600
Not simultaneous with
Multilink in RS232-1
Not simultaneous with
Multilink in RS232-2
Not simultaneous with Web
card in top intellislot.
Not simultaneous with Web
card in middle intellislot.
39
Page 48
5.10.1 Configuring Baud Rates
The default baud rate for Intellislots is 9600. To communicate with the OCWEB-LB, Modbus/Jbus, or
the MultiLink cards, the baud rate must be set to 2400.
To change the baud rate (refer to Table 8):
1. Use the Navigation keys directly below the LCD to highlight the Settings Screen.
2. Press F1 to move the highlight into the Data & Settings area of the LCD.
3. Use the Navigation keys to scroll down to highlight the current baud rate across from the
appropriate Comm Channel.
NOTE
The Comm channel settings are not immediately visible because of window-size constraints.
Scroll down to view them on the screen.
4. Press the Enter (F4) key to select the Comm Channel to change.
5. Navigate to underline the desired baud rate (2400).
6. Press the Enter (F4) key to lock in the new baud rate.
Option Installations
40
Page 49
Figure 28 OC Web card display
Option Installations
41
Page 50
5.11Relay Card
The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig-
nals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other
relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A. and supported in any of the three Intellislot bays on the
NX.
Table 9Relay Card pin configuration
PinFunctionOperation
1UPS FaultClosed if no UPS failure
2-3Not Used
4UPS FaultClosed if UPS fails
5Summary Alarm**Closed if SUMMARY ALARM** occurs
6Summary Alarm**Closed if no alarm conditions are present
7Any Mode Shutdown returnNot supported – use External EPO terminal
8Not Used
9Common - Low Battery
10Low BatteryClosed if battery is OK
11Low BatteryClosed if LOW BATTERY point occurs.
12-13Not Used
14UPS Any Mode ShutdownNot supported – use External EPO terminal
15On UPSClosed if ON UPS (inverter) power
16On BatteryClosed if ON BATTERY power (Utility failure)
17
18On BatteryClosed if not ON Battery power (Utility OK)
19±23Not Used
24On BypassClosed if ON BYPASS
25Not Used
**A Summary Alarm occurs when any of the following conditions exist:
1. Utility power is out of the acceptable range (voltage and/or frequency).
2. UPS is in BYPASS MODE (load not on Inverter power).
3. UPS Battery is LOW.
4. UPS fault has occurred.
Option Installations
Common - UPS Fault,
Summary Alarm, On UPS, On
Battery, On Bypass
Table 10 Relay card jumper configuration
NumberConnectionDescription
JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together.
ANY JP02 Pin 7 to Pin 17 REMOVE - (Interconencts all relay COMMONS and the (not
supported) MODE SHUTDOWN Return
42
Page 51
5.12MultiPort 4 Card
The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of
alarm conditions UPS operation On Battery and battery low condition. A typical applicaton is to allow
a maximum of four computer systems to simultaneously monitor the status (e.g., utility power
failure-low battery) of a singleUPS.
This card is supported in any of the three Intellislot bays on the NX.
Figure 29 MultiPort 4 card pin assignment
Option Installations
UPS
CPU
CPU
CPU
CPU
Assignment
Pin
1Low Battery
2Not Used
3Not Used
4Not Used
5Not Used
6Not Used
7Low Battery Common
8Utility Fail Common
9Utility Fail
Description
43
Page 52
6.0INSTALLATION DRAWINGS
The diagrams in this section illustrate the key mechanical and electrical characteristics of the NX
UPS System cabinets.
Figure 30 Dimensional view- front and left side views
Installation Drawings
600
Monitoring
Panel
1600
Air intake area.
Do not block
air filter.
90
FRONT VIEWLEFT SIDE VIEW
825
10mm dia. threaded
mounting holes
Leveler
Detail “A” Rear of unit
shown without side panel
Adjustable Stops
(see Note 11)
1. All dimensions are in millimeters.
2. A minimum of 24 inches clearance above the unit is required for air exhaust.
3. Installation and service access required. Left-side access recommended for maximum ease of
installation.
4. Keep cabinet within 15 degrees of vertical while handling.
5. Top and bottom cable entry available through removal access plates. Remove punch to suit conduit size
and replace.
6. Unit bottom is structurally adequate for forklift handling.
7. Open door to replace air filter, washable type, size 354x314.
8. Threaded mounting holes used for seismic anchoring or floor stand. Note: If a floor stand is used, the
weight of the unit must be supported under all casters.
9. Each mounting location is supported by two 10 GA. (.135”) galvanized steel. The threaded 12mm insert
is approximately 3/4” deep. Mounting bolts must be threaded into unit.
10. Includes side panel. Refer to Detail A for dimension to frame with side panel removed. Side panels are
removed between adjacent units that are bolted together.
11. Adjustable stops are not designed to carry the full weight of the cabinet. Finger-tighten stop against the
floor, then tighten with a wrench less than two turns for friction against the floor.
44
Page 53
Figure 31 Dimensions continued—top and bottom views
A
Rear stabilizing foot
Air Exhaust
Power Cable
Entry Area
Top and
Bottom
Installation Drawings
10mm dia. threaded
mounting holes 4 (typ).
See Notes 8 and 9 above.
Air
TOP VIEWBOTTOM VIEW
Figure 32 Main components—typical unit
Monitor
Board
(U2)
IntelliSlot
Communication
Ports
Input
Breaker
Rotary
System
Switch
Input Breaker
ccess Plate
Parallel Board (M3)
Power
Electronics
Battery
Trays
Internal and
External Battery
Terminal Block
Access Plate
Front View
(with door open)
DPN U3812048
Rev. 1
45
Page 54
Figure 33 Cable connections
Installation Drawings
AC output cable
connections
Bypass AC input cable
connections
Input Neutral Bus
(side view)
Input/Output
Neutral
Earth
Battery connections (+ N -)
4.1 to battery
4.2 to external battery cabinet
NOTES
Output Neutral Bus
(side view)
Power Earth
(side view)
1. All dimensions are millimeters.
2. Top and bottom cable entry available through removable access plates. Remove, punch to
accommodate conduit size and replace.
3. Control wiring and power wiring must be run in separate conduit. Output and input cables must be
run in separate conduit.
4. Aluminum and copper-clad aluminum cables are not recommended,
5. All wiring is to be in accordance with national and local electrical codes.
46
Page 55
Figure 34 Location of internal batteries
Installation Drawings
417mm
Battery
186mm
687mm
47
Page 56
Figure 35 Battery connections
TOP LAYERMIDDLE LAYER
W501 3pcs
Installation Drawings
DYNASTY BATTERY
+
W500 18pcs
+
+
+
W510 to W511W502 to W503 W503 to W502W504 to W505
W511 to W510
-
+
-
+
-
+
-
+
W507 to W506
-
W506 to W507
-
-
-
W509 to W508
+
+
+
+
BOTTOM LAYER
+
-
+
-
+
-
+
-
+
-
+
-
-
-
-
-
+
+
-
+
-
+
-
-
-N+
CON4
+
W505 to W504W508 to W509
48
-
+
-
Page 57
Figure 36 Battery cabinet interconnection
Refer to Table 11 for key to interconnection
Positive (+)
Midpoint (N)
Negative (-)
Breaker
Connection
Detail
Detail
Positive (+)
Negative (-)
Midpoint (N)
Breaker
Detail
Installation Drawings
A
A
B
B
OR
A
UPS Module
Front View
with doors removed
27" Battery Cabinet
Front View
without doors and
protective plates
59" Battery Cabinet
Front View
without doors and
protective plates
NOTES:
1. All Liebert-supplied cable must be repositioned prior to and while the cabinets are being placed in
their final installed location.
2. All interconnection hardware supplied by Liebert
3. All interconnection cables supplied by Liebert when bolted together.
4. Interconnection cables field-supplied when battery cabinets are stand-alone.
5. Refer to the individual drawing of each piece of equipment for additional details.
K1UPS #1 Module AC InputParalleling CabinetPH A, B, C - UPSCR1, DR1
K2UPS #1 Module AC INPUTParalleling CabinetPH A, B, C - UPSCR1, DR1
51
Page 60
Figure 39 Lineup detail—SlimLine distribution cabinet to NX
Installation Drawings
E
H
G
H
A
C
B
D
D
G
E
H
NOTES:
1. All Liebert-supplied cable will need to be repositioned prior to and while setting the cabinets in their
installed location.
2. All interconnection cables and hardware supplied by Liebert.
3. AC connections must be made to the UPS module before attaching.
4. See Figure 43 for placement of distribution cabinet.
5. Refer to the individual drawing of each piece of equipment for additional details.
Table 14Liebert-supplied interconnect wiring—SlimLine distribution cabinet to NX
RunFromToConductors
ADistribution CabinetLoad AC ConnectionIsolated Ground
BDistribution Cabinet Load AC Connection
CDistribution Cabinet Load AC Connection
DDistribution Cabinet Load AC ConnectionPH A,B,C
EUPS Module AC OutputDistribution Cabinet PH A, B, C
GUPS Module AC OutputDistribution CabinetNeutral
HUPS Module AC OutputAll Ground ConnectionsGround
Neutral
Distribution Cabinet
Ground
Distribution Cabinet
52
Page 61
Installation Drawings
e
I
Figure 40 Lineup detail—1+N Type A connection to NX
1 + N Parallel Cabinet
(front view without front door and panel)
1. All Liebert-supplied cable must be repositioned prior to and while setting the cabinets in their installed
location.
2. All interconnection cables and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching paralleling cabinet to UPS modules
4. The interconnecting output cables between the paralleling cabinet and the UPSes must be the same siz
and the same length.
5. The location of the system output neutral busbar (connection K) and the ground busbar (connections H,
and J) are shown for a left-access style. For right-access version, these busbars are at opposite locations
6. Refer to the individual drawing of each piece of equipment for additional details.
Table 15Interconnect wiring—1+N Type A connection to NX
RUN FROMTOCONDUCTORS
A1-A4Utility AC SourceUPS #1-UPS #4 Module AC InputPh A, B, C - UPS Input
B1-B4Utility AC SourceUPS #1-UPS #4 Module AC InputNeutral - UPS Input
C1-C4 UPS #1-UPS #4 Module AC OutputParalleling CabinetPh A, B, C- UPS Output
E1-E4Paralleling CabinetUPS #1-UPS #4 Module AC GroundGround-UPS
FParalleling CabinetLoad AC ConnectionPh A, B, C - Load
GParalleling CabinetLoad AC ConnectionGround-Load
HParalleling CabinetLoad AC ConnectionNeutral-Load
I1-I4
Paralleling Cabinet
UPS #1-UPS #4 Module
Parallel Logic Board (M3)
Output Breaker Aux Contact
53
Page 62
Figure 41 Lineup detail—1+N Type B1 connection to NX
Installation Drawings
1 + N Cabinet Side View
(without side panel or door)
(front view without front door and panel)
1 + N Parallel Cabinet
1 + N Cabinet Interior View
(neutral and ground busbar location)
1. All Liebert-supplied cable must be repositioned prior to and while
setting the cabinets in their installed location.
2. All interconnection cables and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching
paralleling cabinet to UPS modules.
4. The interconnecting input cables between the paralleling cabinet and
the UPSes must be the same size and the same length.
5. The interconnecting output cables between the paralleling cabinet and
the UPSes must be the same size and the same length.
6. The location of the system output neutral busbar (connection K) and
the ground busbar (connections H, I and J) are shown for a left-access
style. For right-access version, these busbars are at opposite locations.
7. Refer to the individual drawing of each piece of equipment for
UPS Module Left Side View
(without side panel)
additional details.
Table 16Interconnect wiring—1+N Type B1 connection to NX
RunFromToConductors
AUtility AC SourceParalleling CabinetPh A, B, C - System Input
BUtility AC SourceParalleling CabinetGround - System Input
CUtility AC SourceParalleling CabinetNeutral -system Input
D1-D4Paralleling CabinetUPS #1-UPS #4 Module AC InputPh A, B, C - UPS Input
E1-E4Paralleling CabinetUPS #1-UPS #4 Module AC InputNeutral - UPS Input
F1-F4UPS #1-UPS #4 Module AC OutputParalleling CabinetPh A, B, C - UPS Output
H1-H4Paralleling CabinetUPS #1-UPS #4 Module AC GroundGround-UPS
IParalleling CabinetLoad AC ConnectionPh A, B, C - Load
JParalleling CabinetLoad AC ConnectionGround-load
KParalleling CabinetLoad AC ConnectionNeutral-Load
L1-L4
M1-M4
Paralleling Cabinet
Paralleling Cabinet
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
Output Breaker Aux Contact
Rotary Switch Aux Contact
54
Page 63
Figure 42 Lineup detail—1+N Type C connection to NX
Installation Drawings
1 + N Cabinet Side View
(without side panel or door)
(front view without front door and panel)
1 + N Parallel Cabinet
1. All Liebert-supplied cable must be repositioned prior to and while
setting the cabinets in their installed location.
2. All interconnection cables and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching
paralleling cabinet to UPS modules.
4. Utility AC source neutral not required for maintenance bypass/
transformer cabinet Type C.
5. The interconnecting input cables between the paralleling cabinet and
the UPSes must be the same size and the same length.
6. The interconnecting output cables between the paralleling cabinet
and the UPSes must be the same size and the same length.
7. The location of the system output neutral busbar (connection K) and
the ground busbar (connections H, I and J) are shown for a left-access
style. For right-access version, these busbars are at opposite locations.
UPS Module Left Side View
(without side panel)
8. Refer to the individual drawing of each piece of equipment for
additional details.
Table 17Interconnect wiring—1+N Type C connection to NX
Run FromToConductors
AUtility AC SourceParalleling CabinetPh A, B, C-system Input
BUtility AC SourceParalleling CabinetGround - System Input
C1-C4Paralleling CabinetUPS #1-UPS #4 Module AC InputPh A ,B, C - UPS Input
D1-d4Paralleling CabinetUPS #1-UPS #4 Module AC InputNeutral - UPS Input
E1-E4 UPS #1-UPS #4 Module AC OutputParalleling CabinetPh A, B, C - UPS Output
H1-H4Paralleling CabinetUPS #1-UPS #4 Module AC GroundGround - UPS
IParalleling CabinetLoad AC ConnectionPh A ,B, C - Load
JParalleling CabinetLoad AC ConnectionGround - Load
KParalleling CabinetLoad AC ConnectionNeutral - Load
L1-l4
M1-M4
Paralleling Cabinet
Paralleling Cabinet
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
UPS #1-UPS #4 Module
UPS Parallel Logic Board (M3)
1 + N Cabinet Interior View
(neutral and ground busbar location)
Output Breaker Aux Contact
Rotary Switch Aux Contact
55
Page 64
Figure 43 Suggested placement—single NX with auxiliary cabinets
Installation Drawings
Maintenance
Transformer
Maintenance
Bypass /
Transformer
Cabinet
Slimline Distribution
Bypass /
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Battery
Cabinet
Battery
Battery
Cabinet
Cabinet
Liebert
Battery
Battery
Cabinet
Cabinet
Front of UnitsFront of UnitsFront of Units
Liebert
NX
UPS
Slimline Distribution
NX
UPS
Battery
Battery
Cabinet
Cabinet
Front of UnitsFront of UnitsFront of Units
Liebert
NX
UPS
Liebert
NX
UPS
Slimline Distribution
Battery
Battery
Cabinet
Cabinet
Maintenance
Bypass /
Transformer
Cabinet
Slimline Distribution
Liebert
NX
UPS
Maintenance
Transformer
Battery
Battery
Cabinet
Cabinet
Front of Units
Bypass /
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Front of UnitsFront of UnitsFront of Units
Liebert
NX
UPS
Slimline Distribution
Slimline Distribution
56
Page 65
Figure 44 Suggested placement, multiple NX units with auxiliary cabinets
Installation Drawings
Battery
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Battery
Cabinet
Liebert
NX
UPS
Liebert
NX
UPS
Front of Units
Liebert
NX
UPS
Front of Units
Battery
Cabinet
Multi-Module
Paralleling
Cabinet
Liebert
NX
UPS
Multi-Module
Paralleling
Cabinet
57
Page 66
7.0OPERATION
7.1General Description
The standard NX consists of the UPS and internal batteries in a compact, single cabinet.
As shown in Figure 45, the AC utility source is input at CB1 and the rectifier converts the AC utility
into DC power. The inverter converts that DC power from the utility—or DC power from the batteries—into AC power for the load. The batteries power the load through the inverter in the event of a
power failure. The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in
service to the maintenance bypass.
Figure 45 Single module block diagram (dual input configuration)
Operation
7.2Bypass Supplies
The circuit block labeled “Static Switch” and “Contactor” in Figure 45 contains an electronically controlled switching circuit that enables the critical load to be connected to either the inverter output or
to a bypass power source via the static bypass line. During normal system operation the load is connected to the inverter and the inverter contactor is closed; but in the event of a UPS overload or
inverter failure, the load is automatically transferred to the static bypass line.
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the
static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass
supply must be fully synchronized during normal operating conditions. This is achieved through the
inverter control electronics, which make the inverter frequency track that of the static bypass supply,
provided that the bypass remains within an acceptable frequency window.
A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the
critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine
maintenance.
NOTE
When the UPS is operating in bypass mode or on maintenance bypass, the connected
equipment is not protected from power failures or surges and sags.
7.3Operating Modes
The UPS is designed to operate as an on-line, double-conversion, reverse-transfer system in the following modes:
58
Page 67
Operation
Normal Mode
Operating in normal mode, the NX’s rectifier derives power from a utility AC source and supplies regulated DC power to the inverter, which regenerates precise AC power to supply the connected equipment. The rectifier also uses the utility source power to charge the batteries.
Battery Mode
When utility AC power fails, the NX protects the critical load by instantaneously channeling battery
power to the inverter which continues supporting the critical load without interruption. When utility
power returns and is within acceptable limits, the NX automatically shifts back to Normal mode, with
the rectifier powering the critical load.
Bypass Mode
When the NX is in bypass mode, the load is directly supported by utility power and is without battery
backup protection.
The NX’s static transfer switch will shift the load from the inverter to bypass mode without an interruption in AC power if the inverter is synchronous with the bypass and any of the following occurs:
• inverter fails
• inverter overload capacity is exceeded
• inverter is manually turned off by user
NOTE
If the inverter is asynchronous with the bypass, the static switch will transfer the load from the
inverter to the bypass WITH interruption in AC power to the critical load. This interruption
will be less than 15ms (in 50Hz), or less than 13.33ms (in 60Hz). This interruption time may be
altered by modifying the Output transfer interrupt time setting.
Maintenance Mode
For maintenance or repair, the NX may be operated in maintenance mode. To place the NX in maintenance mode, the load must be transferred to bypass and the inverter must be turned off. When those
conditions are met, the rotary switch may be turned to MAINT and the UPS may be shut down, permitting disconnecting the batteries for maintenance.
CAUTION
!
The internal maintenance bypass must not be used when the UPS system is in 1+N parallel.
WARNING
!
The UPS input and output must be protected with external overcurrent protection devices. In
maintenance mode, the input and output busbars remain energized.
Parallel Redundancy Mode (System Expansion)
For higher capacity, higher reliability or both, the outputs of up to four UPS modules can be programmed for directly paralleling while a built-in parallel controller in each UPS ensures automatic
load sharing.
Frequency Converter Mode
The Liebert NX can be programmed into frequency converter mode for either 50Hz or 60Hz stable
output frequency. The input frequency may vary from 40Hz to 70Hz. In this mode, the static bypass
operation is disabled and the battery becomes optional, depending on any requirement to operate in
battery mode (stored energy mode).
59
Page 68
8.0OPERATOR CONTROLAND DISPLAY PANEL
8.1Operator Control Panel
The control panel and LCD on the front of the Liebert NX lets the operator:
• turn the UPS on or off
• transfer into the various operating modes
• silence alarms
• check the status of the UPS and its batteries, including all measured parameters, events and
alarms
The main areas of the control panel are shown below in Figure 46 and detailed in Figure 47.
• Mimic Display - view the status of the NX in single-line diagram format—indicators show status
by changing color when ON, flashing or OFF
• Liquid Crystal Display (LCD) and Navigation keys - view status and operational data from
the NX in tabular format
• Control buttons - turn the NX on or off, silence alarms
Figure 46 Overview of control panel
Operator Control and Display Panel
Mimic display
Liquid Crystal
Display (LCD)
Navigation keys
8.1.1Display Panel Layout
Figure 47 shows the control panel in greater detail, identifying individual items that are described in
the rest of this section.
Figure 47 Detailed view of control panel
2
1
5
3
4
7
6
Liebert NX
30KVA-3X3
Main
Vphase V
Iphase A
Freq. Hz
Vline V
P. F.
Input Breaker Cl osed 01-12 12:28:16
Manual Turn On 01-12 12:30:06
UPS in Normal Mode 01-22 12:30:16
Main
F2F4HELPF1F3
Output
B(BC)
120
20.5
50.1
208
0.99
A(AB)
120
20.5
50.1
208
0.99
2006-01-2212:30: 36
Bypass
C(CA)
120
20.5
50.1
208
0.99
Liebert N X
30KVA-3X3
Vphase V
Iphase A
Freq. Hz
Vline V
P. F.
Input Breaker Closed 01-12 12:28:16
Manual Turn O n 01-12 12:30:06
UPS in Normal Mode 01 -22 12:30:16
2006-01-2212:30:36
Unit #1Normal
Bypass
A(AB)
120
20.5
50.1
208
0.99
F2F4HELPF1F3
Unit #1Normal
Output
C(CA)
B(BC)
120
120
20.5
20.5
50.1
50.1
208
208
0.99
0.99
?
8
INVERTER ON INVERTER OFF
?
FAULT CLE AR S ILENCE ON/OFF
EPO
INVERTER ON INVERTER OFF
FAULT CL EAR S ILENCE ON/OFF
9
EPO
10
12
Control
buttons
11
13
14
1516 171819
Mimic indicatorsControl buttonsNavigation keys
1. Rectifier indicator8. Button cover15. F1
2. Battery indicator9. EPO button16. F2
3. Bypass indicator10. INVERTER ON button17. F3
4. Inverter indicator11. INVERTER OFF button18. F4
The Mimic display on the front panel consists of six indicators arranged in a single-line diagram
depicting the various paths of UPS power, as shown in Figure 48.
Figure 48 Mimic display indicators location
Operator Control and Display Panel
Mimic indicators
1. Rectifier indicator
2. Battery indicator
3. Bypass indicator
4. Inverter indicator
5. Load indicator
6. Status indicator
2
1
5
6
4
3
Main
F2F4HELPF1F3
A(AB)
120
20.5
50.1
208
0.99
2006-01-2212:30:36
Unit #1Normal
Bypass
Output
C(CA)
B(BC)
120
120
20.5
20.5
50.1
50.1
208
208
0.99
0.99
EPO
INVERTER ON INVERTER OFF
?
FAULT CLEAR SIL ENCE ON/OFF
Liebert NX
30KVA-3X3
Vphase V
Iphase A
Freq. Hz
Vline V
P. F.
Input Breaker Closed 01-12 12: 28:16
Manual Turn On 01-12 12:30:06
UPS in Normal Mode 01 -22 12:30:16
The current operational status of the Liebert NX is indicated by the color of the indicators—green,
amber or red—and whether they are ON (solid), flashing or OFF. Table 18 provides a guide to interpreting the various states of the indicators.
Table 18Mimic display status indicators
Indicator
(see
Figure 48)GreenFlashing Green / AmberRedOff
1. Rectifier
2. Battery
3. Bypass
4. Inverter
5. Load
6. Status
Load on rectifierFlashing Green: Utility normal,
but rectifier not operating
Battery powering
the load
Load on Bypass
power
Inverter powering
the load normally
UPS output on
No alarms—UPS
working normally
Flashing Green: Battery prewarning (low battery)
—
Flashing Green: Inverter on
standby
—
Amber: UPS has a general
alarm
* Battery or battery converter abnormal events include these event messages (see Table 44 in Appendix A): No Battery, Battery Replaced,
Rectifier faultRectifier is normal, but utility is
abnormal
Battery or battery
converter abnormal*
Battery and converter are
normal, and battery is not
discharging
Bypass out of
Bypass Normal
normal range
Inverter faultInverter normal, but off
UPS output
UPS no output power
overloaded
UPS has a serious
alarm
—
61
Page 70
8.3Control Buttons
The Control Buttons on the front panel may be used to shut down the UPS completely, turn the
inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 49. The
function of each button is described in Table 19.
NOTE
To activate a button properly, press and hold until you hear a short beep—about two seconds.
Figure 49 Location of control buttons
Liebert NX
30KVA-3X3
Vphas e V
Iphase A
Freq. Hz
Vline V
P. F.
Input Breaker Closed 01-12 12: 28:16
Manual Turn On 01-12 12:30:06
UPS in Normal Mode 01-22 12 :30:16
Table 19Control buttons
Button
(see Figure 49)Function
EPOCompletely shuts down the UPS, including the static switch.
INVERTER ONPress this button to start the inverter and transfer from static bypass to inverter.
INVERTER OFFPress this button to shut down the inverter during operation. The load will be transferred
FAULT CLEARAfter the UPS shuts down due to a fault and the alarm condition has been resolved, press
SILENCE ON/OFFPress this button once to silence the alarm buzzer when an alarm is active. Any new fault
2006-01-2212:30:36
Unit #1Normal
Main
Bypass
A(AB)
120
20.5
50.1
208
0.99
F2F4HELPF1F3
CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This
button completely shuts down the unit and the critical load.
NOTE: If the inverter is not ready, this will not activate the UPS.
to static bypass.
this button to clear the fault and restart the UPS.
will sound the buzzer again.
If the alarm buzzer is not beeping, press this button to test the alarm sound.
B(BC)
120
20.5
50.1
208
0.99
Output
C(CA)
120
20.5
50.1
208
0.99
INVERTER ON INVERTER OFF
?
FAULT CLEAR SILENCE ON/OFF
EPO
Operator Control and Display Panel
8
9
10
11
12
13
Control buttons
8. Button cover
9. EPO button
10. INVERTER ON button
11. INVERTER OFF button
12. FAULT CLEAR button
13. SILENCE ON/OFF button
8.4Alarm Buzzer
The alarm buzzer produces three types of sounds:
• Single beep - when any Control button is pressed
• Single beep repeating every two seconds - the system has a general alarm
• Continuous - the system has a serious fault
If the alarm buzzer makes no sound, the system may be operating properly or the alarm may have
been silenced manually.
Figure 50 Alarm buzzer location
Alarm
Buzzer
Main
A(AB)
120
20.5
50.1
208
0.99
2006-01-2212:30:36
Unit #1Normal
Bypass
Output
B(BC)
120
20.5
50.1
208
0.99
Liebert NX
30KVA-3X3
Vphas e V
Iphase A
Freq. Hz
Vline V
P. F.
Input Breaker Closed 01-12 12: 28:16
Manual Turn On 01-12 12:30:06
UPS in Normal Mode 01-22 12 :30:16
62
C(CA)
120
20.5
50.1
208
0.99
INVERTER ON INVERTER OFF
?
EPO
Page 71
8.5LCD Overview
The LCD on the front panel has five main sections, as shown in Figure 51. Press the F1 key below
the LCD to scroll through these sections.
• UPS system information - view UPS name and model, date and time, overall status (see Table 21).
• LCD Menu - choose a category of data items to appear below the menus (see Table 22).
• Data and settings - view data items for the selected menu (see Table 22).
• Current statusmessages - check the most recent UPS event and alarm messages (see Table 44
in Appendix A).
• Navigation key icons - look at the icon above each navigation key to determine how the key
operates when pressed (see 8.6 - Navigation Keys).
The LCD displays alarm information in real time. After appearing in the current status section of the
LCD, status messages are stored in the history log—512 records can be stored and retrieved.
Figure 51 Sections of the LCD
Operator Control and Display Panel
LCD menu
Data & settings
Current status
messages
2006-01-2212:30:36Liebert NX
SingleNormal30kVA-3X3
BypassMainsOut put
L1-N/L2L2-N/L3L3-N/L1
L-N voltage (V)119.8119.4119.4
L-N current (A) 0.3 0.5 0.6
Frequ ency ( Hz)59.9759.975 9.97
L-L voltage (A)207.1206.8207.1
Power factor0.000.000.00
Fault reset01-2210:32
Manual turn on01-2210:32
Normal mode01-2211:05
F2F4HELPF1F3
UPS system
information
?
Navigation
key icons
63
Page 72
8.6Navigation Keys
The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view
the current status and other information about the NX.
Navigation key icons on the LCD appear above each key to indicate its operation (see Table 20). The
keys are “soft keys” that can change functions according to the icon.
•Use F1 either to move to a different portion of the LCD (shift icon) or to escape to a previous view
(ESC icon).
•Use F2 and F3 as cursor keys to move left and right or up and down, depending on the icons dis-
played above the keys.
•Use F4 as an Enter key to confirm a choice.
•Use HELP to access help information on the LCD.
Table 20Icons for navigation keys
KeyF1F2F3F4HELP
Operator Control and Display Panel
Functions
Available
ShiftLeftRight
ESC
ExitUpDown
8.7UPS System Information
The UPS system information displayed at the top of the LCD is detailed in Table 21.
Table 21Description of items in UPS system window
No.Item TypeExplanation
1Liebert NXUPS name
22002-10-12Current date
312:30:36Current time
030kVA-3x3030 means UPS model is 30kVA;
4
Unit #1#1 of 6 Paralleled changed to “Unit #1”
5
SingleUPS is configured as a single-unit system running in Normal mode
NormalUPS in normal operation, inverter powering load, no warnings
6
WarningUPS has a general alarm
FaultUPS has a serious fault
3x3 means 3 by 3 system (three phase input and output)
?
EnterHelp
64
Page 73
8.8LCD Menus and Data Items
The LCD menus provide access to the following categories of information and settings for the UPS.
Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The
menu choices are listed below and described in detail in Table 22.
• Mains - view utility power input data: voltage, current, frequency and power factor
• TX Input - view input transformer voltages
• Bypass - view bypass data: voltage and frequency
• Output - view output data: voltage, current, frequency and power factor
• Load - view load data: load percent, output current, output power and crest factor (CF)
• System - view system data
• Battery - view battery characteristics—voltage, current, temperature, remaining time and capacity—and messages when the battery is boost/float charging or disconnected
• Records - access the history log—displays all records in the log (newest records added at end)
• Language - select a language for LCD text (choices appear in the native language)
• Settings - configure UPS settings: adjust the display contrast, choose a format for date display,
set the date and time, set up the UPS for modem communications (baud rate, address, mode and
phone numbers to dial for alarm notifications) and change the password
• Command - start or stop a battery maintenance test, battery capacity test or system test
• Version - view firmware versions for the inverter, rectifier and software display board and the
model information for the UPS
Figure 52 shows a menu tree of the options available from the LCD menus.
Figure 52 Menu tree
Operator Control and Display Panel
Mains (input)
L-N voltage (V)
L-N current (A)
Frequency (Hz)
L-L voltage (V)
Power factor
Load
Sout (kVA)
Pout (kW)
Qout (kVAR)
Loadlevel %
Crest factor
Language
(Choices for
display)
TX Input *
L-N voltage (V)
L-L voltage (V)
System
Sout (kVA)
Pout (kW)
Qout (kVAR)
Single unit, no
parallel data
Settings
Display contrast
Date format set
Date & time
Comm1 baud rate
Comm2 baud rate
Comm3 baud rate
Communication address
Communication mode
Callback times
Phone No.1
Phone No.2
Phone No.3
Command password
Bypass
L-N voltage (V)
Frequency (Hz)
L-L voltage (V)
Battery
Battery voltage (V)
Battery current (A)
Battery temperature (°C)
Remain Time Min.
Battery capacity (%)
Battery boost charging
Battery float charging
Battery disconnected
Command
Battery maintenance test
Battery capacity test
System test
Stop testing
Freshening Charge
Stop Freshening Charge
Modem Auto-answer enable
Output
L-N voltage (V)
L-N current (A)
Frequency (Hz)
L-L voltage (V)
Power factor
* When configured, input transformer voltages are
displayed on the front LCD. When not activated,
the values are hidden.
** When configured, output transformer voltages
are displayed on the front LCD. When not
activated, the values are hidden.
TX Output **
L-N voltage (V)
L-L voltage (V)
Records
(history log)
Version
UPS version
UPS model
65
Page 74
8.9Language Selection
The LCD menus and data display are available in
12 languages (Chinese, Dutch, English, French,
German, Italian, Japanese, Polish, Portuguese,
Russian, Spanish and Swedish). To select a different language:
• From the main menu, press the F1 (shift) key
to move the cursor to the menu at the top of
the screen.
• Press F2 and F3 (left and right arrows) as
needed to select the Language menu.
• Press F1 (shift) to move the cursor to the data
and settings area of the LCD.
•Use F2 and F3 (up and down) to select the
required language.
• Press the F4 (enter) key to accept the language
selection.
• Return to the main menu by repeatedly pressing F1 (ESC) as needed; all text on the LCD will now
be displayed in the selected language.
8.10Current Date and Time
To change the system date and time:
• From the main menu, press the F1 (shift) key
to move the cursor to the menu at the top of
the screen.
• Press F2 and F3 (left and right arrows) as
needed to select the Settings menu.
• Press F1 (shift) to move the cursor to the data
and settings area of the LCD.
•Use F2 and F3 (up and down) to select the Date & Time option, then press F4 (enter).
• Position the cursor on the row in which the
date and time are displayed, then press
F4 (enter).
•Using the F2 and F3 (up and down) keys,
enter the current time and date information.
• Press F4 (enter) to save the settings, then
press F1 (ESC) to return to the main menu.
Operator Control and Display Panel
2006-01-2212:30:36Liebert NX
SingleNormal30kVA-3X3
RecordsBatteryLanguage
POLSKI
ESPAÑOL
Fault reset01-2210:32
Manual turn on01-2210:32
Normal mode01-2211:05
Display contrast
Date format setM/D/Y
D/M/YM/D/YY/M/D
Date & time
01-22-200412:30:36
Fault reset01-2210:32
Manual turn on01-2210:32
Normal mode01-2211:05
ENGLISH
FRANCAIS
NEDERLANDS
РУСС КИ Й
F2F4HELPF1F3
2006-01-2212:30:36Liebert NX
Sing leNormal30kVA-3X3
LanguageRecordsSettings
F2F4HELPF1F3
DEUTSCH
ITALIANO
SVENSKA
PORTUGUÊS
?
?
66
Page 75
Operator Control and Display Panel
Table 22Descriptions of UPS menus and data window items
Menu TypeItem TypeExplanation
L-N voltage (V)Phase voltage
Mains
(input)
TX Input
Bypass
Output
TX Output
Load
System
Battery
Records(history log)Displays all records in the history log
Language(choices for text displayed)User may select any of 12 languages for LCD text.
L-N current (A)Phase current
Frequency (Hz)Input frequency
L-L voltage (vLine-line voltage
Power factorPower factor
L-N voltage (V)Phase voltage
L-L voltage (V)Line-line voltage
L-N voltage (V)Phase voltage
Frequency (Hz)Bypass frequency
L-L voltage (A)Line-line voltage
L-N voltage (V)Phase voltage
L-N current (A)Phase current
Frequency (Hz)Output frequency
L-L voltage (V)Line-line voltage
Power factorPower factor
L-N voltage (V)Phase voltage
L-L voltage (V)Line-line voltage
Sout (kVA)Sout: Apparent power
Pout (kW)Pout: Active power
Qout (kVAR)Qout: Reactive power
Loadlevel %The percent of the UPS rating load
Crest factorOutput current Crest Factor
Sout (kVA)Sout: Apparent power
Pout (kW)Pout: Active power
Qout (kVAR)Qout: Reactive power
Single unit, no parallel dataWhen configured as a single unit, UPS has only native load, no system load.
Battery voltage (V)Battery bus voltage
Battery current (A)Battery bus current
Battery temperature (°C)Internal battery temperature °C
Remain Time Min.Battery run time remaining
Battery boost chargingBattery is boost charging
Battery float chargingBattery is float charging
Battery disconnectedBattery is not connected
67
Page 76
Table 22Descriptions of UPS menus and data window items (continued)
Menu TypeItem TypeExplanation
Display contrastAdjust the LCD display contrast
Date format setChoose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D
Date & timeSet the date and time
Comm1 baud rateCommunication baud rate setting for Intellislot 1
Comm2 baud rateCommunication baud rate setting for Intellislot 2
Comm3 baud rateCommunication baud rate setting for Intellislot 3
Communication addressThis setting is applicable to RS485 communication mode
Settings
Command
(start/stop
battery &
system
tests)
Version
Communication modeCommunication Mode Setting
Callback timesWhen Intellislot 1 Communication mode is Modem, this parameter sets the
number of times a number is redialed to send an alarm notification.
Phone No.1When Intellislot 1 Communication mode is Modem, this is the first phone
Phone No.2When Intellislot 1 Communication mode is Modem, this is the second phone
Phone No.3When Intellislot 1 Communication mode is Modem, this is the third phone
Command passwordUser can modify the command password.
Battery maintenance testThis test performs a partial discharge of the battery to obtain a rough estimate
Battery capacity testThis test performs a full discharge of the battery to obtain a precise measure of
System test This is a self-test of the UPS. When the user activates this function, a pop-up
Stop testingManually stops a battery maintenance test, battery capacity test or system
Freshening ChargeAllows a temporary Equalize charge for the batteries. This charge is
Stop Freshening ChargeManually stops a Freshening Charge
Modem Auto-answer
enable
UPS versionProvides UPS firmware version numbers for the inverter, rectifier and software
UPS modelProvides UPS model information—for example, 208V-60Hz.
number to be dialed (to send an alarm notification).
number to be dialed (to send an alarm notification).
number to be dialed (to send an alarm notification).
of the battery capacity. Load must be between 20% and 80%.
the battery capacity. Load must be between 20% and 80%.
window appears about 5 seconds later to show the results.
test.
configurable for 1 to 36 hours.
Manually enable the modem’s auto-answer function.
display board.
Operator Control and Display Panel
68
Page 77
8.11UPS Status Messages
The NX displays status changes as they occur in the current status window of the LCD, then
stores that data in the history log, as shown in Figure 53.
• Current Status Window: The status messages are displayed chronologically and include the
date and time of the events. Three status messages are visible in the window at a time. To see
other messages, use the navigation keys to scroll up or down the list. A status message remains in
the current status area of the LCD until the status changes, when it is moved to the history log.
• History Log: When a record moves to the history log, the time the status changed is recorded.
The history log can hold up to 512 records. History log records may be viewed by accessing the
Records menu.
Figure 53 Current status and history log records
Operator Control and Display Panel
2006-01-2212:30:36Liebert NX
SingleNormal30kVA-3X3
Records
History log
(records menu)
Current status
messages
BatterySystem
Bypass abnormal
Inverter asynchronous
Mains freq. abnormal
Fault reset01-2210:32
Manual turn on01-2210:32
Normal mode01-2211:05
01-22-200409:57: 13
01-22-200410:02: 16
01-22-200409:57: 13
01-22-200410:02: 21
01-22-200409:57: 14
01-22-200410:02: 14
?
F2F4HELPF1F3
See Table 44 in Appendix A for a complete list of status messages, along with a description and any
recommended actions.
69
Page 78
8.12Types of LCD Screens
This section provides a quick guide to the main types of LCD screens.
8.12.1 Opening Display
As the UPS begins powering up, the opening display appears, as shown in Figure 54.
Figure 54 Opening display
Operator Control and Display Panel
8.12.2 Default Screen
After the UPS has powered up and completed a self-test, the output screen appears, as shown in
Figure 55. This window is the default screen.
Figure 55 Default screen
F2F4F1F3
2006-01-2212:30:36Liebert NX
SingleNormal30kVA-3X3
BypassMainsOutpu t
L-N voltage (V)119.8119.4119.4
L-N current (A) 0.3 0.5 0.6
Frequ ency ( Hz)59.9759.9759.97
L-L voltage (A)207.1206.8207.1
Power factor0.000.000.00
Fault reset01-2210:32
Manual turn on01-2210:32
Normal mode01-2211:05
L1-N/L2L2-N/L3L3-N/L1
F2F4HELPF1F3
HELP
?
70
Page 79
8.12.3 UPS Help Screen
Press the HELP key below the LCD to display the Help window shown in Figure 56. (Press the
HELP key again to exit the Help window.)
Figure 56 Help screen
Help information
Select the current record window
Select the previous menu item
Q3
Q2
Q1
Press help key back to main menu
F2F4HELPF1F3
Operator Control and Display Panel
Q5
8.12.4 Screen Saver Window
If there has been no interaction with the NX’s LCD for 2 minutes, the screen saver window appears. It
remains on the LCD for 2 minutes, then the screen will go dark. The LCD will become active again
when any key is pressed.
Figure 57 Screen saver window
Liebert NX
30kVA-3X3
2006-01-2212:30:36
SingleNormal
Press any key back to main menu
F2F4F1F3
HELP
71
Page 80
8.13Pop-Up Windows
Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This
section describes the pop-up windows.
8.13.1 From Bypass to Inverter Mode With Power Interruption
If the bypass voltage or frequency exceeds the synchronized range and
utility voltage or frequency is normal, the inverter cannot be in synchronization with the bypass, and the output can only transfer to
inverter after an interruption of about 15ms when the user presses the
INVERTER ON button. Before transferring, the system will let the
user confirm whether the interruption can be accepted, as shown at right. If the bypass voltage
returns to normal before the user makes confirmation, the UPS will transfer to inverter mode automatically. At the same time, the prompt window will close.
8.13.2 From Inverter to Bypass Mode With Interruption
If the bypass voltage or frequency exceeds the synchronized range and
the UPS is in inverter mode, the system must let the user to confirm
and accept the power interruption danger before pressing the
INVERTER OFF button to shut down the output of the inverter. The
user can also cancel the shutdown operation, as shown at right. If the
bypass voltage returns to normal before the user makes the confirmation, the UPS will transfer to bypass operation mode automatically, and at the same time the prompt
window will disappear soon.
Operator Control and Display Panel
Transfer with Interrupt,
please confirm or cancel
This operation leads to
output shutdown,
Confirm or cancel
8.13.3 System Self-Test
When a system self-test is completed, a pop-up window reports the
results of the test, as shown at right.
• Press the F4 (Enter) key and the pop-up window closes.
8.13.4 Battery Capacity Test Confirmation
When a battery capacity test is started from the Command menu, the
battery will be discharged to low-battery warning level. The NX asks
for confirmation before the test is started, as shown at right.
• To confirm the choice and begin the battery capacity test, press the
F4 (Enter) key and the pop-up window disappears.
• To cancel the test, press the F1 (ESC) key. The pop-up window disappears.
NOTE
For a battery capacity test to function properly, the load must be between 20% and 100%.
8.13.5 Battery Self-Test Aborted, Condition Not Met
When a battery capacity test is started from the Command menu and
the battery self-test condition is inadequate, the NX will not perform a
battery test. User should check whether the battery state is boost
charging and whether the load level is greater than 20 percent.
• Press the F4 (Enter) key and the pop-up window closes.
System Self-Test finished,
Everything is OK
Battery will be depleted,
Confirm or cancel
Battery Self-Test aborted,
Conditions not met
8.13.6 Battery Refresh Charge Aborted, Condition Not Met
When a battery refreshening charge is started from the Command
menu and battery refreshening condition fails to meet requirements,
the NX will not perform a battery refreshening charge. User should
check if boost charging condition is not enough, such as (No battery,
charger failed, etc.).
• Press the F4 (Enter) key and the pop-up window closes.
72
Battery Refresh Charge
aborted,
Conditions not met
Page 81
9.0OPERATING INSTRUCTIONS
9.1NX Operating Modes
The NX can operate in any of four modes, as shown in Table 23. This section provides instructions on
switching between modes, resetting the UPS, switching the inverter On and Off and performing other
operations.
Table 23UPS operating modes
Operating
Mode
Normal
Operation
On Maintenance
Bypass
On Test
On Static
Bypass
Rotary Switch
PositionDescription
NORMALThe UPS is powering the load.
MAINTThe UPS is shut down but the load is connected to utility power via the
TESTNo load power is supplied by the UPS. The load is connected to utility power
BYPASS
or
NORMAL
Operating Instructions
Maintenance Bypass Supply line.
NOTE: The load is not protected against disturbances in AC input power in this
mode.
via the Maintenance Bypass Supply line.
NOTE: The load is not protected against disturbances in AC input power in this
mode.
The load power is supplied through the static bypass line. This may be
considered as a temporary mode during load transfers between inverter and
maintenance bypass or supply under abnormal operating conditions.
NOTE
1. The user controls and indicators mentioned in these procedures are identified in 8.0 Operator Control and Display Panel.
2. The audible alarm may sound at various points during these procedures. It can be canceled
at any time by pressing the SILENCE ON/OFF push button.
NOTE
This unit refers to some modes and conditions that are set or adjusted using proprietary service
software. To take advantage of all the available features for the NX, the unit must be
commissioned by a Liebert factory-trained service engineer.
73
Page 82
9.1.1Power Switches
The UPS can be isolated by means of power switches, mounted inside the cabinet and accessible after
opening the front door.
The location of the UPS power switches is shown in Figure 58.
Figure 58 Power switches - 10kVA NX
CB1 - Utility
Connection
Inside the door,
left side
Operating Instructions
SW1 - Rotary Switch
Inside the door, near
the center (above the
batteries)
The UPS unit power switches are CB1 and SW1.
• CB1 - Input Isolator. Connects the utility supply to the UPS input.
• SW1 - Rotary switch. Has four positions—NORMAL, BYPASS, TEST and MAINT—that correspond to different positions of the SW1-A/B/C/D.
The positions of the rotary switch (SW1) are:
• SW1-A - Output Isolator. Connects the output of the UPS to the load.
• SW1-B - Neutral Isolator. Connects neutral to the UPS.
• SW1-C - Bypass Isolator. Connects the UPS with the bypass supply.
• SW1-D - Maintenance Bypass Isolator. Permits supply of the load directly by the bypass
line for maintenance of the UPS unit.
The functions of the rotary switch are shown in Table 24.
Table 24Rotary switch configuration
Rotary
switch
position
NORMAL✔✔✔
BYPASS✔✔✔
TEST✔✔ ✔
MAINT✔
OUTPUT
(SW1-A)
BYPASS
(SW1-C)
MAINT
(SW1-D)
NEUTRAL
(SW1-B)
NOTE
Do NOT turn the rotary switch too fast. Allow the rotary switch to stay in each position at least
three seconds before turning it to the next position.
74
Page 83
9.2UPS Start Up
The NX must be fully installed and commissioned before start up, and external power isolators must
be closed. Once those general conditions are met, the UPS may be started.
9.2.1Start-Up Procedure
To start the UPS from a fully powered-down condition:
1. Open the UPS door to gain access to the main power switches.
WARNING
!
During this procedure the output terminals will become live.
If any load equipment is connected to the UPS output terminals, please check with the load
user and ascertain whether it is safe to apply power to the load. If the load is not ready to
receive power, then ensure that it is safely isolated from the UPS output terminals.
CAUTION
!
Do not operate the rotary switch too fast. Always wait at least three seconds when rotating
the switch from one position to another.
2. Turn the rotary switch to TEST.
3. Close CB1.
The bypass contactor (M2) closes automatically and the LCD begins to show start-up screens.
The Rectifier indicator flashes green while the rectifier is starting up. It stops flashing and
becomes solid green about 30 seconds after the rectifier enters the normal operation state.
After initialization, the bypass static switch closes.
Because output switch SW1-A is still open, the UPS
channels power through Maintenance Bypass Supply
line (SW1-D). The bypass indicator extinguishes, provided that the bypass is normal.
The opening display is shown in the figure at right.
The UPS Mimic display indicators will be:
Operating Instructions
IndicatorState
Rectifier indicatorOff
Battery indicatorOff
Bypass indicatorOff
Inverter indicatorOff
Load indicatorOff
Status indicatorOff
WARNING
!
Do NOT turn the rotary switch until the rectifier indicator stops flashing green.
4. Turn the rotary switch to BYPASS.
The maintenance switch SW1-D opens and output switch SW1-A
closes. The UPS powers from static bypass instead of from
maintenance bypass. The bypass and load indicators turn on.
The design of the rotary switch ensures uninterrupted output.
F2F4F1F3HELP
IndicatorState
Rectifier indicatorGreen
Battery indicatorOff
Bypass indicatorGreen
Inverter indicatorOff
Load indicatorGreen
Status indicatorAmber
75
Page 84
5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds.
The inverter will start and the inverter indicator will flash green. After the inverter is ready, the
UPS transfers from bypass to inverter, the bypass indicator turns off and the inverter and load
indicators turn on.
The UPS is operating normally. The UPS Mimic display indicators will:
IndicatorState
Rectifier indicatorGreen
Battery indicatorOff
Bypass indicatorOff
Inverter indicatorGreen
Output indicatorGreen
Status indicatorGreen
9.2.2Verify Switching Between Operation Modes
Switch from Normal Mode to Battery Mode
• Open CB1 to enter battery mode. This breaks the utility connection to the NX.
To return to normal mode, close CB1 after a few seconds. The rectifier will restart automatically
after 10 seconds and resume feeding power to the inverter.
Switch from Normal Mode to Bypass Mode
• Press INVERTER OFF button to switch to bypass mode.
Operating Instructions
NOTE
In bypass mode, the load is being powered by the utility and is not receiving conditioned power
through the inverter.
Switch from Bypass Mode to Normal Mode
• Turn the rotary switch to NORMAL.
• In bypass mode, press the INVERTER ON button. When the inverter is ready, the UPS will
switch to normal mode.
76
Page 85
9.3Switching the UPS from Normal to Maintenance Bypass
Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass
line of the UPS.
CAUTION
!
Before performing this operation, read the messages on the LCD to be sure that bypass supply
is regular and the inverter is synchronous with it. If those conditions are not present, there is
a risk of a short interruption in powering the load.
This procedure assumes that UPS is operating normally.
1. Press the INVERTER OFF button on the right side of the operator control panel for longer than
2 seconds.
The Inverter indicator will turn off and the status indicator (6) will turn amber and an audible
alarm will sound. The load will transfer to static bypass and the inverter will shut off.
NOTE
Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message
displayed until the appropriate condition is rectified.
2. Open the UPS door to gain access to the main power switches, SW1 and CB1.
3. Turn the rotary switch to BYPASS position. The UPS Bypass Static Switch still supply power to
load.
4. Turn the rotary switch to TEST. The load is now on maintenance bypass.
5. Turn the rotary switch to MAINT.
6. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven
internal power supplies decay. The unit will power down, but the load will continue to be supplied
by the manual Maintenance bypass.
Operating Instructions
WARNING
!
Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting
to remove the internal protective barriers.
WARNING
!
Even with the UPS in maintenance bypass and “Off,” portions of the unit are still energized.
Service is to be performed by qualified personnel only.
CAUTION
!
The load equipment is not protected from normal supply aberrations when operating in the
maintenance bypass mode.
9.4Powering Down the UPS
To power down the UPS completely, follow the procedures in 9.3 - Switching the UPS from Normal to Maintenance Bypass.
To completely isolate the UPS from the AC supplies, the main external power input isolator (both isolators, where separate supplies are provided for rectifier and bypass) should be opened (see
Figure 59).
WARNING
!
To prevent injury to personnel, lockout or tagout the service supplies.
77
Page 86
9.5Powering Down the UPS and Maintaining Power to Load
NOTE
An external Maintenance Bypass Cabinet must be installed before attempting to perform the
following procedure.
If the UPS needs to be shut down completely while maintaining power to the load, follow these steps:
1. Perform Steps 1 through 5 in 9.3 - Switching the UPS from Normal to Maintenance Bypass.
2. Close the external maintenance bypass rotary switch to Maint postion.
On the primary input distribution panel, which is often located distant from the UPS area, a label
should be posted advising service personnel that the UPS circuit is under maintenance.
WARNING
!
Wait 5 minutes for the internal DC busbar capacitors to discharge.
The UPS is now completely powered down.
NOTE
The Maintenance Bypass Power switch may be operated at any time while the UPS is powered
down to connect the load to the maintenance bypass supply if required.
Operating Instructions
The procedure can be performed only after the installation has been completed (which includes the
maintenance bypass cabinet), after the system has been placed in operation by authorized personnel.
See the reference drawing of Figure 59 for more information.
Figure 59 Typical configuration for single UPS with external maintenance bypass cabinet
78
Page 87
9.6Emergency Shutdown With EPO
This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The
system will turn off the rectifier, inverter and stop powering the load immediately (including the
inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS’s controls will remain active; however, the output will be
turned off. To remove all power from the UPS, the external feeder breaker should be opened.
9.7Auto Restart
When the main and bypass sources fail, the UPS draws power from the battery system to supply the
load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it
will shut down.
The UPS will automatically restart and enable output power:
• after utility power is restored
• if “Auto Recovery after EOD Enabling” is enabled
• after the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes)
During the auto recovery delay, the NX will be charging its batteries to provide a safety margin
for equipment shutdown if input power fails again.
If the “Auto Recovery after EOD Enabling” feature is disabled, the user must restart the system manually.
Operating Instructions
9.8Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions
Once all appropriate measures have been taken to correct the problem indicated by the alarm message appearing on the operator control panel display, carry out this procedure to restore the UPS to
regular operation following an EPO action or for the following reasons: Inverter Overtemperature,
Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.
When the user confirms that the fault is cleared:
1. Press the FAULT CLEAR button to let the system exit the emergency off state.
NOTE:
A UPS manufactured before March 2006 may first require a full power down, i.e., manual
opening of the input breakers, for the "Fault Clear" to take effect.
NOTE
The rectifier will start again, the battery contactor will close and the bypass will begin to power
the load. The Rectifier indicator (1) flashes while the rectifier is starting up. When the rectifier
enters the normal operation state (about 30 seconds), the rectifier indicator turns green.
2. Press the INVERTER ON button (10) on the right side of the operator control panel for longer
than 2 seconds.
NOTE
The rectifier will be turned on automatically when the overtemperature fault disappears at
5 minutes after the disappearance of overtemperature signals.
After the EPO button is pressed, if the input utility is removed, theUPS will shut down completely.
When input utility is returned, if the rotary switch (SW1) is in either Bypass or in Normal position,
the UPS will start up on Bypass. There will be power at the output terminals of the UPS.
WARNING
!
If the rotary switch is in the Maint. position and input utility is present, there will be power at
the output terminals of the UPS.
79
Page 88
9.9Battery Protection
9.9.1Battery Undervoltage Pre-Warning
Before the end of discharge, the NX displays a battery undervoltage pre-warning. After this pre-warning, the battery has the capacity for 5 minutes discharging with full load (default time). The NX can
be user-configured to display this warning from 3 to 60 minutes before end-of-discharge.
9.9.2Battery End-of-Discharge (EOD) Protection
If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut
down.
9.9.3Battery Fuse-Blow Warning
Battery current protection is provided by the battery fuses FU7 and FU8. If a battery fuse blows, the
NX displays the battery fuse-blow warning and the battery converter will be shut down.
NOTE
All equipment servicing procedures must be carried out only by trained personnel.
9.10Isolating and Integrating One Module in a Multi-Module System
1. Turn Off inverter
2. Open External Output CB1
The UPS enters Isolation Status automatically, parallel signaling and communication becomes
masked, and output becomes inhabited.
3. Power Off unit for maintenance.
4. Power On unit with External Output CB1 open.
5. Unit enters Test Mode by configuration software setting.
6. Diagonosis or testing.
7. The UPS exits Test Mode by configuration software setting.
Output becomes inhibited because of Isolation Status.
8. Return all switches to the Normal position, including External Output Circuit Breaker 1.
9. Close External Output Circuit Breaker 1.
The UPS exits Isolation Status automatically, parallel signaling and communication recovers,
output becomes enabled but interlocking works now.
10. Turn On inverter and join the parallel system.
Operating Instructions
WARNING
!
Hazardous Battery Voltage
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
The UPS battery and connecting terminals remains energized at hazardous voltage levels at
all times. The battery is located behind protective covers that require a tool for their removal:
inside the UPS cabinet, inside a free-standing battery cabinet or on open racks inside a
dedicated battery room that may be locked.
80
Page 89
9.11Inserting One Module into a Multi-Module System
This procedure outlines how to integrate a UPS module that has been previously isolated from other
modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed.
WARNING
!
Mains voltage will be applied to UPS output terminals.
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
1. Open the UPS door to gain access to the main power switches.
2. Rotate the switch to Test position. The LCD becomes active.
3. Close Input breaker CB1
The Rectifier indicator flashes on the UPS mimic panel during the startup of the rectifier and
becomes steady green once the rectifier reaches normal operation state after about 30s.
4. Close external battery circuit breaker QF1 (where an external battery is used). This breaker is
inside the battery cabinet (if used) or is otherwise adjacent to the battery racks.
5. After the UPS detects the batteries, the red battery indicator extinguishes when the battery
charger starts operation.
6. Rotate switch to Bypass position
7. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds.
The inverter will start up and the inverter indicator flashes while it synchronizes to the load volt-
age and frequency. After the inverter is ready, the UPS connects to the load, the inverter indicator
becomes steady green and the output indicator turns green.
8. Check that no “Warning” message is displayed in the top right corner of the LCD Monitor and
that the indicators have the status shown below.
Operating Instructions
# LEDLED FunctionStatus
1Rectifier indicatorGreen
2Battery indicatorOff
3Bypass indicatorOff
4Inverter indicatorGreen
5Output indicatorGreen
6Alarm indicatorOff
The UPS is now operating in NORMAL mode.
81
Page 90
Operating Instructions
9.12Shutting Down a Multi-Module System Without System Bypass Switch
NOTE
Before beginning this procedure, shut down the connected load to prevent the possibility of
damage. This procedure will shut off power to the load.
1. Open the UPS door to gain access to the main power switches, SW1 and CB1of a UPS in the
system.
2. Turn the rotary switch to BYPASS position. Rotating any UPS Rotary Switch (SW1) to the
Bypass position will force all UPS modules to Static Bypass
3. Repeat Steps 1 and 2 for the rest of the units in the system.
NOTE
If this operation will be performed on multiple units, the procedures should be performed on
each unit with as little delay as possible.
4. Turn the rotary switch of each unit in the system to TEST. The load is now on maintenance
bypass.
5. Turn the rotary switch of each unit in the system to MAINT.
NOTE
The following step will shut off power to the connected load.
6. Open system output breaker. The load will now be disconnected.
7. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility-driven
internal power supplies decay.
8. To isolate a module:
a. For systems that have UPS input breakers in paralleling cabinet, open the UPS input breaker
for the unit you want to isolate.
b. For systems that do not have UPS input breakers in paralleling cabinet, the utility source to
the UPS will need to be opened.
9.13Shutting Down a Multi-Module System With System Bypass Switch
1. In the Bypass Cabinet, rotate the system bypass switch to the Bypass position. This will force the
UPS's in the system to Static Bypass.
2. Open the UPS door to gain access to the main power switches, SW1 and CB1of a UPS in the
system.
3. Turn the UPS SW1 to BYPASS position for each module in the system
4. Repeat Steps 2 and 3 for the rest of the units in the system.
5. Turn the rotary switch of each unit in the system to TEST.
6. Turn the rotary switch of each unit in the system to MAINT.
7. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven
internal power supplies decay.
8. To isolate the UPS(s) from the bypass cabinet, open the module input and output isolation
breaker(s).
82
Page 91
9.14Commissioning a Parallel System
CAUTION
!
The operations described in this section must be performed by authorized electricians or
qualified technical personnel. If you have any difficult, do not hesitate to contact Liebert
Global Service at 1-800-LIEBERT.
Check the input and output wiring of each UPS module. Ensure that the phase rotation sequence of
the main inputs and the bypass inputs and outputs of each UPS module are the same. Ensure the
parallel cables are connected firmly.
It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed. Before start up, disconnect the load.
Follow these steps to start the UPS while connected to the Maintenance Bypass.
1. Set Maintenance Bypass switch to the Normal position on Maintenance Bypass Cabinet.
2. Close the system input circuit breaker.
3. Start the UPS as instructed in 9.2 - UPS Start Up.
4. Close system output circuit breaker.
9.15.2 Shutting Down the UPS
Operating Instructions
Use the following procedure to power down the system.
1. Turn the NX off by following the procedures in 9.4 - Powering Down the UPS
2. Open system output circuit breaker.
3. Open system input circuit breaker.
9.15.3 Transferring System from UPS to Maintenance Bypass Operation
1. Turn the bypass switch (SW) to the bypass position on the Maintenance Bypass Cabinet. The UPS
will switch to bypass mode.
The connected equipment is now powered from the bypass source and is NOT protected.
2. To isolate the UPS from the system, rotate the bypass switch to the maintenance position.
9.15.4 Transfer the System from Maintenance Bypass to UPS Operation
1. Turn the bypass switch (SW) to the Normal position on the Maintenance Bypass Cabinet. The
UPS will go to bypass mode.
2. Press the “Inverter On” button on the UPS and allow the UPS to go to normal mode.
3. The connected equipment is now powered and protected by the UPS.
9.15.5 Transfer the System from UPS Operation to Maintenance Bypass
If the UPS needs to be shut down completely while maintaining power to the load, follow these steps:
1. Perform Steps 1 through 5 in 9.3 - Switching the UPS from Normal to Maintenance Bypass.
2. Rotate Maintenance Bypass Switch to Maintenance position.
3. Post a label on the primary input distribution panel, which often is installed outside the UPS
area, advising personnel that the UPS circuit is under maintenance.
The UPS is now completely powered down.
WARNING
!
Wait 5 minutes for the internal DC busbar capacitors to discharge.
NOTE
The Maintenance Bypass power switch may be operated at any time while the UPS is powered
down to connect the load to the maintenance bypass supply.
83
Page 92
Operating Instructions
The procedure can be performed only after the installation has been completed (which includes the
maintenance bypass cabinet), after the system has been placed in operation by authorized personnel
and after the external power switches have been closed. See Figure 60 for more information.
Figure 60 Single UPS with external Maintenance Bypass Cabinet—typical configuration
Input Supply
ABC
N
Sys in CB1
Qin UPS
Input Mains
Supply A B C
UPS1
Charger
Fuse
Battery
Bat Byp
CB1
Static
Switch
SW1-A
N
Rectifier
Inverter
SW1-C
SW1-D
Rotary
Switch
SW
Y
N
A B C
Ext
Byp
Y
Qout UPS
Sys Out CB2
N
To Load
84
Page 93
9.16Parallel System Start Up
1. Start each UPS normally as described in 9.2 - UPS Start Up
2. Turn on the inverter of each UPS module one at a time.
3. Apply the load after the last UPS module transfers to inverter. The total load can be determined
through the LCD of either UPS.
4. Verify the load rate of each UPS module. If the load rates are roughly the same, then the parallel
system may be assumed to be operating normally.
NOTE
If one module cannot transfer to inverter mode long after its inverter is on, its output
connection may not be good or its output phase rotation may not be coincident with other
modules. At this time, the LCD for the UPS module will display “inverter asynchronous” and
the inverter indicator will flash continuously. If either UPS module makes abnormal noise
after it transfers to inverter, its parallel cables may be incorrectly connected.
9.17Replacing Dust Filters
1. Open the UPS door.
2. The dust filters are behind the door. For each filter, there is a bracket on either side holding the
dust filter in place, as shown in Figure 61.
3. Remove one bracket and loosen the other. The second bracket need not be removed.
4. Remove the old filter and replace with the new filter
5. Reinstall the bracket that was removed and tighten the other bracket.
Operating Instructions
Figure 61 Dust filter replacement
Bracket
Sems screw
Bracket
85
Page 94
10.0 UPS SPECIFICATIONS
These specifications describe requirements for the Liebert NX UPS.
10.1Conformity and Standards
The UPS has been designed to conform to the following standards:
• IEEC1000-4-5
•ASME
• CSA 22.2, No. 107.1
• FCC Part 15, Class A
• ISO 9001
• National Electrical Code (NFPA-70)
• NEMA PE-1
•OSHA
• UL Standard 1778
The UPS system has UL and c-UL approval.
10.2UPS Environmental
The UPS is designed to operate under the following environmental conditions without damage or degradation in electrical operating characteristics:
Table 25Environmental characteristics
Rated Power10-30kVA
Operating Temperature, UPS32°F to 104°F (0°C to 40°C)
Optimal Operating Temperature, Battery68°F to 86°F (20°C to 30°C)
Relative Humidity0 to 95%, non-condensing
Acoustical Noise, dBA at 39 in. (1m)54
Altitude of Operation≤1000m per IEC 62040/3
Storage-Transport Temperature, UPS-4°F to 158°F (-20°C to 70°C)
Storage-Transport Temperature, Battery-4°F to 86°F (-20°C to 30°C)
UPS Specifications
10.3UPS Mechanical Characteristics
Table 26Mechanical characteristics
Parameter10kVA15kVA20kVA30kVA
Width, in. (mm)24 (600)
Depth, in. (mm)32.5 (825)
Height, in. (mm)63 (1600)
Weight Without Inner Batteries, lb. (kg)450 (205)450 (205)550 (250)550 (250)
Protection Grade (with open/closed front doors)IP 20
/h)384 (652)558 (948)522 (886)834 (1417)
86
Page 95
UPS Specifications
10.4UPS Electrical Characteristics
Table 27UPS terminal
Input (for single-input unit)
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Lug T&B
One Hole
REDDY
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
RatingBolt Size
10283542456M (1/4")5410562204
15425363706M (1/4")5410662204
20567084906M (1/4")5410762204
30831041251256M (1/4")5415262205
Rectifier input (for dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
RatingBolt Size
10253137406M (1/4")5413062204
15374757606M (1/4")5410662204
20506376806M (1/4")5410762204
3075941131256M (1/4")5415262205
Bypass input (for dual input units)
Maximum Recommended Lug
Lug T&B
One Hole
54000
Unit
Rating
Nominal
Input
CurrentOCP Current
OCP
Device
RatingBolt Size
102835356M (1/4”)5410562204
154253606M (1/4”)5410662204
205670706M (1/4”)5410762204
30831041106M (1/4”)5415262205
Output
OCP
Unit
RatingNominal Output Current
OCP
Current
Device
RatingBolt Size
102835356M (1/4")5413062204
154253606M (1/4")5410662204
205670706M (1/4")5410662204
30841051106M (1/4")5410862205
Battery
OCP
Unit
RatingBattery Current
OCP
Current
Device
RatingBolt Size
10/155555706M (1/4")5410662204
20/301101101258M (5/16")5415362212
1. Nominal (Nom) current is based on full rated output load.
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions.
3. UPS input and bypass cables must be run in separate conduit from output cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full
load current (continuous) per NEC 215.
6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to
be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 2005.
7. Wiring requirements:
a. AC Input: 3-phase, 4-wire, plus ground output.
b. AC Output: 3-phase, 3- or 4-wire, plus ground
8. All wiring is to be in accordance with national and local electric codes.
87
Page 96
10.4.1 Battery Manufacturers and Models
Either of two manufacturers’ batteries will be installed in the NX 10-30 kVA 208V as shipped. Below
are the battery makers and the models they supply.
<135% load
135% - 170% load
1000% full UPS rated output current
89
Page 98
11.0SPECIFICATIONSAND TECHNICAL DATA
11.1Lug Size and Torque Requirements
Use commercially available solderless lugs for the wire size required for your application. Refer to
Table 33. Connect wire to the lug using tools and procedures specified by the lug manufacturer.
Table 33Torque specifications
Nut and Bolt CombinationS
Grade 2 Standard
Bolt Shaft Size
1/4536.0465.2
5/1610712606.8
3/8192229511
1/24282225629
Circuit Breakers With Compression Lugs (For Power Wiring)