Emerson Nform And Interface Products User Manual

OpenComms™Nform And Interface Products
Adaptive Solutions For IT
Site Monitoring & Services for Business-Critical Continuity
Maximizing Your Investment Through Adaptive Monitoring
support equipment for computer systems has never
been easier…or more cost-efficient.
What You Don’t Know Can Hurt You
A small problem in a computer or communications facility can quickly escalate into a disaster. Knowing what is happening with power and cooling equipment can keep that protective "envelope" at peak operating efficiency, vital to system reliability.
Only Liebert can offer full-scale monitoring and control of these critical support systems by providing the ability to gather operating information from each piece of equipment and pull it together in one central location.
Finding A Better Way To Monitor The Evolving Critical Space
Monitoring the critical space is essential. The problem is, the critical space has evolved and can take on many shapes and sizes, from the traditional centralized data center, to the cutting-edge distributed topologies of telecom, wireless and retail operations. Liebert's mission is to protect the
critical space, whether consolidated in the data center or distributed throughout the network — and monitoring is an essential component of any high-availability solution.
Just as one model of UPS or air conditioner cannot fulfill the requirements of every application, Liebert offers a suite of monitoring products to meet the varying requirements of the vast spectrum of critical space applications. From leak detection to discrete monitoring, unattended orderly computer shutdown to enterprise­wide monitoring, Liebert offers hardware and software solutions that fit.
This full-scale monitoring capability allows for consolidation of all components of critical space infrastructure into an organized, logical, high-availability system. And because different people need to know different information about your support equipment, Liebert will provide the tools to determine what specific data should go where.
2
(a) Up to $50,000 per hour (b) Over $50,000 per hour 4% (c) Unkown 23% (d) $1,000 per hour 42% (e) $10,000 per hour 26%
Source: Infonetics, Cio Magazine/June 15, 2000
Cost of Downtime
How much does and hour of downtime cost your business?
(a) 5%
(b) 4%
(c) 23%
(d) 42%
(e) 26%
`
`
3
Getting Critical Information Into The Right Hands
Business runs on information.
That information, however, must be
managed and protected. Liebert
offers the tools to keep the people
on the front line — such as IT,
network, data center and facility
managers — informed as to the
status of their critical systems. By
utilizing a network infrastructure
approach to monitoring, Liebert
has the solutions that align a
customer's needs for real-time
knowledge and system flexibility
with critical system uptime and
capital allocation constraints.
This type of system can provide
the information you need to
manage your critical equipment,
giving you a variety of ways to
receive and manage this
data — through computers at
your site or even on the web via
standard browser software.
From the traditional centralized
data center to constantly evolving
distributed network topologies,
Liebert has the solutions that
provide just the right amount of
control, monitoring, and protection
for your critical space requirements.
The Importance Of Support System Monitoring
The reliability of your computing and communications systems is a direct result of the reliability of the power and environmental systems that help maintain their proper operation. That's why Liebert is so firmly committed to providing monitoring capability in our products. No one knows more about what it takes to collect and deliver the vital information you need to manage your critical support systems.
To protect your critical business systems, it is important that
we first understand how you and your customers utilize these
resources. Knowing how your network is used allows us to
design system protection that addresses your real world needs.
To maintain the high level of availability that users expect, your
monitoring system must be able to keep you up-to-date on
any changes in the condition of your network infrastructure.
Understanding The Needs Of Your Business
Proper power protection and environmental control is essential for your network components:
Printer servers
Database servers
File servers
E-mail server s
Web ser vers
Router s
Hubs
Your Network Has Many Points That Must Be Protected
Your customers have expectations of the level of system availability you can provide.
DC Power Systems
An overvoltage condition in an essential DC power system causes an alarm to sound. Problem is, no one is there to hear it.
Water Leaks
Your data cabling is lying in a growing puddle of water under the raised floor because of a plumbing leak. It is just a matter of time before that affects your operation. Who knows how long it will take to track down the cause of the problem.
Power Distribution
Several circuits are on the verge of overload. If one of these breakers trips, servers will crash.
Power Conditioning Units
A grounding problem in your power conditioning system causes small voltage disturbances. You may not even realize there is corrupt data or damage to other systems until bigger problems occur months later.
UPS Systems
Yesterday the UPS failed its automatic battery self test. Today the UPS failed to carry the load during a momentary power interruption, halting a critical process. The problem isn’t the UPS or the weak battery. The real problem is that you didn’t know that the UPS failed a self-diagnostic test.
Environmental HVAC Systems
High head pressure, compressor short cycling, dirty filters, pump or fan failure — these are just a few of the problems that can cause mission-critical air conditioning systems and other HVAC equipment to go down and temperatures to go up. One more problem? Not knowing that these troubles are developing in the first place.
Surge Protection
Thank goodness you installed that surge protector. It has protected your site through many thunderstorms. Unfortunately it self-destructed protecting you from that last surge and you don’t know that it needs to be replaced.
Static Transfer Switches
A transfer switch fails to transfer when your primary power feed goes down in the middle of the night. You won’t know about it, though, until tomorrow morning when there are no sales reports, no e-mails and certainly no one conducting normal business.
Intrusion Alarm
The entrance of unauthorized personnel into a remote shelter is a big problem. The real problem is that the person who needs to know this is happening is unaware and possibly isn’t in the same building – or even the same state.
Generator Operation
The good news is your emergency generator came on-line during a power failure last night and kept things running for several hours. The bad news is that the fuel tank is now almost empty - and no one realizes it, leaving you unprotected for the next outage.
4
When Systems Are Critical… Monitoring Is Not An Option
UNDETECTED
UNNOTICED
UNRECORDED
UNREPORTED
UNSEEN
If you don't know what is happening inside your critical facilities, the result is unavailability
U P S t a t i o n
G X T
+
AC IN P U T B A T T E RY
U P S O N B Y P ASS
U P S t a t i o n
G X T
+
A C IN
P U T B AT T E R Y
UP S ON B Y P A S
S
20
U P S t a t io n G X T
+
A C I N P U T B A T T E RY U P S O N B
Y PA S S
U P S t a ti o n G X T
+
A C I N P U T B A T T E RY U P S O N B
Y PA S S
Liebert Offers A Full Range Of Monitoring And Control Solutions
A
C
P
o
w
e
r
S
y
s
t
e
m
s
P
r
e
c
i
s
i
o
n
C
o
o
l
i
n
g
D
C
P
o
w
e
r
S
y
s
t
e
m
s
5
What Do You Need To Monitor?
No matter which Liebert products you
have...we have a way for you to monitor
performance. Liebert offers a full range
of monitoring and control solutions to
complement your Liebert UPS, power
conditioning, power distribution or
environmental control systems. Find
your Liebert products on this chart to
see which specific monitoring methods
are available. Once you know your
monitoring options, you can then select
the system that best fits your
specific needs based on the type and
depth of information required by
your organization.
OpenComms Network
Products Nform Interface
Single-Phase UPS
Liebert PowerSure PSI OCWeb Liebert UPStation GXT OCWeb Liebert UPStation GXT 6 &10 kVA OCWeb Liebert UpStation GXT 2U OCWeb Liebert UPstation S Voya ger Liebert Nfinity OCWeb Liebert NX OCWeb-LB
Three-Phase UPS
Small 3-Phase
Liebert UPStation S3 Voya ger Liebert Series 300 OCWeb-LB Hiross HiNet OCWEB-300
Large 3-Phase
Liebert NPower OC-NIC Liebert NPower 1+1 OC-NIC Series 600 Single Module System (SMS) OCWEB-300 Hiross Hipulse Multi Module (MM) OC-NIC Hiross Hipulse Single Module (SM) OC-NIC Hiross Hipulse System cabinet (SC) OC-NIC Hiross Series 7200 Multi Module (MM) OC-NIC Hiross Series 7200 Single Module (SM) OC-NIC Hiross Series 7200 System Cabinet (SC) OC-NIC
Power Conditioning & Distribution
Liebert FDC OC-NIC Precision Power Center (post-1990) OC-NIC Top Entry Precision Power Center (post-1990) OC-NIC DataWave (post-1999) OC-NIC
Transfer Switches
Static Transfer Switch OC-NIC Static Transfer Switch 2 OC-NIC
Precision Cooling
Liebert DS OCWeb-LBDS Deluxe System/3 OC-NIC Challenger 3000 OC-NIC Industrial Cooling Series (ICS) OC-NIC Himod LNA OC-NIC Mini-Mate2 OC-NIC Mini-Mate2 8-Ton OC-NIC DataMate OC-NIC Atlas C10 OC-NIC Hiross Microface OC-NIC
Monitoring Panels
Remote Power Monitor Panel (PMP) (post-1990) OC-NIC OpenComms EM Built-In SiteNet Integrator Built-In
DC Power - Emerson Energy Systems
NterpriseIP OCWEB
Candeo Product Line
Candeo IP Built-In Candeo SP 24 Built-In Candeo SP 48 Built-In Candeo Access Built-In
EES DC Product Line
Actura Built-In
Monitoring And Control Through Your Existing Network
Extending The Communication Capabilities Of Your Liebert Equipment
For enhanced remote communications and control of Liebert UPS and air conditioning units, the OpenComms Web and OpenComms NIC cards will deliver SNMP and web-management communications capabilities. Each Liebert system equipped with an OpenComms NIC or Web card takes full advantage
The OpenComms Web Card provides SNMP and web­based management to your UPS.
The OpenComms NIC Card transforms Liebert units into manageable nodes within your Network, NMS and BMS systems.
Liebert DS Card provides SNMP and web-based management for Liebert DS.
6
On-line Demo Sites:
http://gxtwebdemo.liebert.com http://npowerwebdemo.liebert.com http://nfinitywebdemo.liebert.com http://deluxeamwebdemo.liebert.com http://nxwebdemo.liebert.com
Network Based
Scalable and Adaptable
Graphical User Interface
Information Whenever Needed
Interface with Liebert Power and Cooling Systems
Multiple Web Browser Support
No Third-Party Application Required
OpenComms Interface Advantages
of your Ethernet network, allowing remote monitoring from your computer desktop, network operations center or wherever network access is permitted.
The OpenComms cards support 10 and 100 MBit Ethernet network transmission speeds, which will be auto-detected upon connection to the network. Plus, these cards support in-the-field firmware updates, which increases the value of your investment.
OPENCOMMS INTERFACE PRODUCTS
7
Liebert OpenComms™ EM
For event greater flexibility, the Liebert OpenComms EM is designed to monitor temperature, humidity and contact closures inside critical environments, including racks and small computer rooms.
For applications that require the management of power within the Network rack, the OpenComms EM PDU option manages up to (2) two Liebert MP Advanced Power Strips.
This compact device provides network connectivity through Web access and/or E-Mail Notifications of events for stand-alone applications.
The SNMP interface provides access to parameteric data and notifications of alarm events to Liebert OpenComms Nform Critical Management Software and/or a Network Management System.
On-line Demo Sites:
http://mpwebdemo.liebert.com http://emwebdemo.liebert.com
Managed Power Strips Provide Distribution, Control, And Monitoring To Rack Applications
Monitor Temperature and Humidity in the Rack
E-mail Notifications directly from OpenComms EM
Trending of Environmental and Power data points
Communicate and Monitor MP Advanced Power Strips Via MP-S Access Ser ver
OpenComms EM Advantages
Interface With Most Critical Support Equipment
Liebert OpenComms Nform will monitor any Liebert SNMP device that supports a network interface, such as the OpenComms Web card and the OpenComms NIC (network interface card). This will allow connection to a full range of Liebert power and mission-critical cooling systems and equipment from other manufacturers, including DC power systems and other third party SNMP-based products.
Connectivity to Liebert OpenComms Nform can also be achieved with the Liebert OpenComms EM network-enabled monitoring device. The unit provides SNMP traps for use with Liebert OpenComms Nform.
The software can also be connected to the Liebert MP-S Access Server which is used to communicate with and monitor Liebert MP Advanced Power Strips.
Liebert OpenComms™ EM
OPENCOMMS EM/MP ADVANCED POWER STRIPS
Liebert Shutdown Control: Maximum Data Protection
MultiLink automated shutdown software allows you to actively protect data on servers supported by the Liebert UPS equipment
you are monitoring with OpenComms Nform, using the same OpenComms Web and OpenComms NIC cards.
MultiLink®Shutdown Software
Because today’s critical business applications are often distributed over several computers, there is a need for shutdown software capable of protecting information on multiple machines. The shutdown notifications from OpenComms Nform to MultiLink
1.5 clients perform the critical task of protecting your computers from costly damage and data loss as a result of power failure and environmental alarm conditions – on anything from a single workstation to a network of workstations and servers.
Stay In Control
During an extended utility failure, MultiLink warns computer users of impending power loss and automatically shuts down computer operating systems in a smooth and orderly manner if the UPS battery capacity runs low.
OpenComms Nform 1.2
Server with Viewer
Ethernet
Liebert NX
Nform Client
(Viewer Only)
MultiLink 1.5
Client
MultiLink 1.5
Client
MultiLink 1.5
Client
UPS Load
8
Automated and Orderly Shutdown on Environmental, UPS and Power conditions
Scalable
Network Based
Suitable for Single Workstation or Network of Servers
Wide Operating System Capabilities
http://Multilink.liebert.com
MultiLink Advantages
MULTILINK SHUTDOWN SOFTWARE
9
On-line Demo Sites:
http://Nform.liebert.com
Liebert OpenComms Nform is a network
communications system that will
enable you to leverage the distributed
monitoring capabilities of your network
connected equipment.
When Systems Are Critical… Monitoring Is Not An Option
OpenComms Nform software solution combines full-scale monitoring with cost-effective deployment through the use of the existing network infrastructure — so the cost of dedicated, out­of-band communications cabling is eliminated. It is both scalable and adaptable so it can grow as your systems expand and needs change.
The software can be configured to monitor your network for alarm notifications from Liebert power protection and precision cooling equipment. These alarms, or SNMP traps, can be received by the software and processed to trigger event actions such as e-mail alerts or local notifications.
For ease of use, the OpenComms Nform graphical user interface enables you to view device status conditions through either a native SNMP interface or an HTML web browser interface. The Alarm Log will manage all alarms that are received by OpenComms Nform.
OpenComms Nform will monitor any Liebert SNMP devices that support a network interface, such as the OpenComms Web card and the OpenComms NIC. The customizable navigation tree provides the flexibility to design an OpenComms Nform user interface around your network layout. Authenticated alarm management and event notification ensures that alarms are detected and acted upon, which allows problems to be quickly resolved.
One Company, Providing You a Complete High­Availability Solution
Connecting to equipment in the distributed critical space is only part of the monitoring challenge. Liebert OpenComms Nform leverages the network connectivity capabilities of your Liebert equipment to provide a centralized monitoring view of your distributed equipment. Utilizing the SNMP and Web technologies built into each of the OpenComms communication cards, OpenComms Nform will centrally manage alarm notifications to provide you with an easy interface to access critical status information.
OpenComms Nform effectively eliminates the need for expensive third-party monitoring applications. The Liebert "turn-key" approach to communications and monitoring minimizes your installation and maintenance costs, consolidates your view of the critical space status, and maximizes your uptime through automated notifications of alarm conditions.
OpenComms Nform centralizes the management of your distributed Liebert network equipment.
Alarm Management Features
Connection to Other Manufacturers Equipment
Turn Key Approach to Communications and Monitoring
MultiLink Integration for Shutdown of systems
Management of UPS, Power, Environmental and Monitoring Products that support SNMP
Centralized Management of critical systems
Web Integration
OpenComms Nform Advantages
OPENCOMMS NFORM SOLUTIONS
Small
Mission-Critical
Air
Network
Management
System
Large
Mission-Critical
Nform Server
Rackmount
Air
Ethernet
UPS
UPS
Three-Phase UPSSingle-Phase
Nform Client (Viewer Only)
NterpriseIP Battery
Monitoring
10
Comprehensive Monitoring: The OpenComms Nform Advantage
Device Surveillance
The status of managed equipment propagates up through the customized navigation view.
Status at a Glance
Real-time device view of operation and current alarms.
Web Integration
The web interface from managed devices is integrated directly within the software.
Navigational Graphics
Incorporate graphic floor-plans or maps that allow for quick equipment location and hyper-links to managed equipment that support a web interface.
SNMP Direct
Devices that do not support an embedded web interface can be managed directly through their native SNMP interfaces.
SNMP Configuration
View only the configurable SNMP data. One button download allows for quick configuration changes.
11
License Management
As your business expands, you can adapt your critical systems monitoring to these changes by adding license kits.
Device Management
Deploying new equipment has never been this easy. Up to 44 base templates are included for Liebert Products.
Local Visual and Audio Alerts
Application to Foreground
Play Sound Wave
Load Local Viewer
Flash Application in Taskbar
Stay in Control
The software has the flexibility to execute a set of actions when conditions are present and a completely different set of actions when alarms return to normal.
Send Alerts and Notify Personnel
Notifications can be assigned to each specific managed device alarm or condition.
Event Management and Processing
The Event History log will manage all alarms that are received, notifying the user of new or active alarms, enabling the user to acknowledge new alarms, and delete acknowledged alarms.
Execute External Programs
Some network infrastructure can span long distances dependent on bridges and routers. The Run External program can execute ping commands to devices on the edge of your network, including routers and switches that represent a network path to resources within your critical business operation.
Shutdown Clients
For high-priority event alarms, email notifications can be sent to data center managers, notifying them that servers will be shut down soon due to loss of power or high temperature conditions.
SMTP Email
For high-priority event alarms, email notifications can be sent to data center managers, notifying them that servers will be shut down soon due to loss of power.
12
Alarm-Event Exporting to Disk
To maintain extended history of events, the file-write can be used for logging and database collection.
Condition-Based System Recording
This action notification can be used to get a snapshot of your system as an alarm-event occurs. Often IT managers have to answer why systems are unavailable during a crisis. The recording of the "state-of the-system" as an alarm occurred can prove useful for trouble-shooting and determining the root-cause of failures within the system.
Information you need, every time you need it.
Alarm Management — Getting The Right Information To The Right People
OpenComms Nform puts critical systems information at the fingertips of support personnel - wherever they are - increasing responsiveness to alarm-event conditions, thus allowing IT organizations to maximize their system availabilty.
Automated Action Control Response
Nform gives you the ability to control equipment on received alarm-events. For example, when a high temperature alarm is received, an SNMP Set can automatically turn on another unit for cooling. SNMP Set Request can be used to reboot or turn on/off Liebert MP Advanced Power Strips or even close relay contacts for external notifications.
With installed leak detection products, a water-detected summary alarm was transmitted to OpenComms Nform by the OpenComms EM. The facility engineer was notified and corrected the faulty plumbing.
Voltage disturbances were reflected in the trend graphing of the OpenComms EM with Managed Power. After further analysis, facility engineer discovered and corrected the grounding problem.
OpenComms Nform received a failed battery test and forwarded the conditions to the Liebert Global Services Response Center, dispatching the service technician for a battery replacement site visit.
High temperature alarm was reported through the OpenComms Web Interface to the OpenComms Nform system. With advance notification, the standby unit was remotely activated, maintaining the desired operating temperature setpoint within the data center.
Since OpenComms Nform was monitoring the TVSS summary alarm, maintenance was notified to incorporate testing of the surge suppression device due to its recent heavy usage.
Before the primary power source failed, facility engineer received a “secondary source not available” alert via his SMTP supported cell phone. The heads-up was given and the problem was resolved before the system went critical.
Security personnel were alerted when the OpenComms EM reported a door ajar alarm to the OpenComms Nform system.
Recent runtime on the generator has consumed most of the fuel. Since the low fuel summary alarm was being monitored by the OpenComms EM, an event was triggered in OpenComms Nform, sending a request for refueling to the local fuel supplier.
Telecommunications engineer was dispatched through OpenComms Nform notifications, allowing the engineer to quickly replace the faulty rectifier before the critical overvoltage threshold was reached.
IT recently installed Liebert MP Advanced Power Strips inside their rows of rack enclosures. Now, with the control of each receptacle, overloading of circuits is prevented. OpenComms Nform users can easily control access to which outlet circuits are enabled or disabled.
13
Managing The Adaptive Enterprise
CORRECTED
REPORTED
RECORDED
NOTIFIED
DETECTED
Technology at work
U P S t a t i o n
G X T
+
AC IN
P U T B A T T E RY
U P S O N B Y P ASS
U P S t a t i o n
G X T
+
A C IN
P U T B AT T E R Y
UP S ON B Y P A S
S
20
U P S t a t io n G X T
+
A C I N P U T B A T T E RY U P S O N B
Y PA S S
U P S t a ti o n G X T
+
A C I N P U T B A T T E RY U P S O N B
Y PA S S
SOFTWARE OPTIONS
OpenComms Nform Software OpenComms Nform Software OpenComms Nform Software
System Features
**Download Edition Professional Edition Enterprise Edition
Local Client Viewer 1 1 1
Remote Concurrent Client Viewer No No 5
Supported Operating Systems Windows NT 4.0 w/SP6 or higher, Windows NT 4.0 w/SP6 or higher, Windows NT 4.0 w/SP6 or higher,
Windows 2000, Windows XP, Windows 2000, Windows XP, Windows 2000, Windows XP,
Windows 2003 Server Windows 2003 Server Windows 2003 Server
Real-Time Monitoring and Control
Device Status Polling Yes Yes Yes
Default Devices Supported 1 30 500
Web Card Integration Yes Yes Yes
Open Architecture Standard RFC1628 UPS Device Standard RFC1628 UPS Device Standard RFC1628 UPS (Monitoring of non-proprietary SNMP devices) Template Included Template Included Device Template Included
Device Supported All Liebert UPS, Environmental, All Liebert UPS, Environmental, All UPS Liebert, Environmental,
Power Distribution, and Power Distribution, and Power Distribution, and Monitoring products that Monitoring products that Monitoring products that support a SNMP interface support a SNMP interface support a SNMP interface
Notifications and Alerts
Propagate Application to foreground Yes Yes Yes
Load Local Viewer Yes Yes Yes
Play Sound Wave Yes Yes Yes
Play Default Beep Yes Yes Yes
Flash Application when Minimized Yes Yes Yes
Standard Actions
E-mail Notification Yes Yes Yes
Run External Program Capability Yes Yes Yes
File Write Yes Yes Yes
Shutdown Network License*
Shutdown ML Clients No No Unlimited Included
Advance Notifications*
SNMP Set Request(s) No No Yes
SNMP Get Request(s) Report No No Yes
* Note: These add-on packages can be added to the system with Licensing
**Software available at no charge at Nform.liebert.com
SOFTWARE OPTIONS
OpenComms Nform Additional Licenses
PART NUMBERS OpenComms Nform Additional Managed Device Licenses
NFORM-30N Managed Device License kits allows the user to incrementally add support for monitoring additional numbers of NFORM-100N network devices. Node Licenses are additive and manageable through License Key Administrator NFORM-500N
OpenComms Nform Managed Device Licenses
NFORM-1CUSER Concurrent Client License allows the user to incrementally add support for additional numbers of connected clients. NFORM-5CUSER Concurrent Client Licenses are additive and manageable through License Key Administrator NFORM-10CUSER
OpenComms Nform Advance Notification License
NFORM-ANOTIFY Advance Notification License allows the user to add support for SNMP SET/GET Requests Actions
MultiLink®Network Shutdown License, Unrestricted
MLLKU MultiLink Network Shutdown License allows you to efficiently shutdown workstations and servers
running MultiLink throughout the network via Event-Alarm conditions from OpenComms Nform
Liebert OpenComms Nform Software Options
14
Professional Services The Ultimate In Customer Service
Applications Engineering Services
This service provides, at no charge, to all Liebert customers ultimate product support with direct access to factory-trained Monitoring Engineers. Our engineers receive in-depth instruction and hands­on experience in providing support for monitoring software and hardware.
Instant Phone Assistance - 24 X 7 X 365
1.800.222.5877
614.841.6755 (Outside U.S.)
Email an Engineer - M-F 8:00a.m. - 5:00p.m.
monitoring@liebert.com
OpenComms Nform Support Web Portal
Registering at the Nform Support Web site gives you access to all the latest updates and notifications of special offerings and new releases. By registering your license keys, this support site puts you in control of your investment. As a registered user you can submit feedback on the OpenComms Nform Products and gain access to valuable resources within Liebert.
Software Integration Services (SIS)
The further your resources are stretched, the less time you have to quickly deploy your monitoring products. Sotware Integration Services is designed to help the customer implement and verify the Liebert software and hardware in a timely efficient manner. A Monitoring Engineer will assist with the deployment of your monitoring solution on-site.
Installation and Start-up
Configuration and Verification
On-Site Training and Education
On-Line Support Overview and Web Site Registration
Remote Monitoring Service: When You Need To Know — But Can’t Do It Yourself
The key to providing proper service for critical support systems is being aware of that equipment's operating status at any given time. That’s why Liebert is so firmly committed to providing monitoring capability in our products. Our Remote Monitoring Service, provided by Liebert Global Services, is designed to maximize the capabilities of your Liebert equipment by maximizing the effectiveness of your monitoring systems.
15
Standard Services Optional Services
AC Power Systems Connectivity DC Power Systems
Embedded Power Inbound Power Integrated Cabinet Solutions
Outside Plant Precision Cooling
Site Monitoring and Services
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2005 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
® Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-28090 (R11/05) Printed in USA
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2005 Emerson Electric Co.
EmersonNetworkPower.com
Emerson Network Power.
The global leader in enabling business-critical continuity.
Ensuring The High Availability Of Mission-Critical Data And Applications.
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 Phone (Outside U.S.) 614 841 6022 FAX
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 Gloucester Rd, Wanchai Hong Kong 852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone 614 841 6755 (outside U.S.)
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies — including Liebert power and cooling technologies — that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility, and reduced capital equipment and operating costs.