Emerson NetSure 802, NetSure 802 DC Application Guide

Page 1
NetSure™ 802 Series
DC Power System
Description
The modular NetSure™ 802 power system is made up of an assort­ment of bays that can be configured to meet any large -48 Volt power requirement from 1000 A to 16,000 A. The basic power unit is a nominal 200 A rectifier capable of up to 220 amps each at cur­rent limit. The system accommodates up to 10 rectifiers per bay, and the bays can be configured for distributed or centralized appli­cations. There are also bays configured to retrofit 200 amp and 400 amp ferro rectifiers with minimum AC infrastructure cost.
Requester Contact Information:
Name:*
Title:*
Company:*
Email/Phone:*
* These are required fields. Please complete before submitting the form.
Table of Contents
Step 1. Select System Frame(s), Main Bay or Supplemental Bay ........2
Step 2. Optional - Select Distribution Frame .....................................2
Step 3. Select Input Voltage Source (AC Input Source) ......................2
Step 4. Select Rectifier Model ...........................................................3
Step 5. Optional - Select AC Service Cabinet (PDSC) .........................3
Step 6. Optional - Select Transient Voltage Surge Suppression .........3
Step 7. Select Controller Accessory Cards .........................................4
Step 8. Select LMS1000 Monitoring Options .....................................4
Step 8a. Select LMS1000 Card/Software Options ................................5
Step 9. Select DC Distribution Device Types......................................6
Step 9a. Choose TPL Style Fuses ..........................................................6
Step 9b. Choose GJ/218 Style Breakers ................................................7
Step 9c. Choose Bullet-Type Circuit Breakers and Adapter Kit.............8
Step 9d. Choose TLS/TPS Fuses with Bullet-Type Fuse Holders ..........10
Step 10. Optional - Select Small Distribution for Distribution Bay ..... 11
Step 11. Optional - Select Internal Return Bar (as needed) ................12
Step 12. Optional - Select External Termination Bus Assembly .........13
Step 13. Optional - Select External Return Bar Option ......................14
Step 14. Order Accessories (as needed) ............................................. 15
Note: Click on the step above to jump to that page. To return to the
Table of Contents, click on the main title of any page.
For additional information or questions visit or call:
For additional information or questions visit or call:
400 A Ferro Retrofit Power Bay200 A Ferro Retrofit Power BayNetSure™ 802 Power Bay Power Bay with Distribution Bay
1004ORA-NS802 / 0913
1
Page 2
NetSure™ 802 Series
DC Power System
Step 1. Select System Frame(s), Main Bay or Supplemental Bay
Select one, quantity of one per system.
List Number
List 1 58214000001
List 2 58214000002
List 3* 58214000003
List 4* 58214000004
List 5* 58214000005
* Must be used with external main battery termination bars.
Emerson Part Number
Description
Main power/distribution frame, equip for individual AC feed per rectifier
Main power/distribution frame, equip for bulk AC feed per frame
Main power bay frame, 5 discrete AC inputs per bay (5 feed) for 400 A ferro retrofit application
Main power bay frame, 2 discrete AC inputs per bay (2 feed)
Main power bay frame, individual AC inputs per rectifier (10 feed) for 200 A Ferro retrofit applications or direct feed from existing AC PDSC
Select quantity as needed per system.
List Number
List 11 58214000011
List 12 58214000012
List 13* 58214000013
List 14* 58214000014
List 15* 58214000015
* Must be used with external main battery termination bars.
Emerson Part Number
Description
Secondary power/distribution frame, equip for individual AC feed per rectifier
Secondary power/distribution frame, equip for bulk AC feed per frame
Secondary power bay frame, 5 discrete AC inputs per bay (5 feed) for 400 A ferro retrofit application
Secondary power bay frame, 2 discrete AC inputs per bay (2 feed)
Secondary power bay frame, individual AC inputs per rectifier (10 feed) for 200 A Ferro retrofit applications or direct feed from exist­ing AC PDSC
Step 2. Optional - Select Distribution Frame
Select quantity as needed if applicable.
Qty. Notes
(1) Main frame type required per system. Maximum of 10 rectifiers/bay.
Must select AC service cabinet option in Step 5.
(1) Main frame type required per system. Maximum of 10 rectifiers/bay.
(1) Main frame type required per system. Maximum of 10 rectifiers/bay.
(1) Main frame type required per system. Maximum of 10 rectifiers/bay.
Qty. Notes
Order as required. Maximum of 10 rectifiers/bay. System can support up to (9) secondary frames as needed.
Must select AC service cabinet option in Step 5. Order as required. Maximum of 10 rectifiers/bay. System can support up to (9) secondary frames as needed.
Order as required. Maximum of 10 rectifiers/bay. System can support up to (9) secondary frames as needed.
Order as required. Maximum of 10 rectifiers/bay. System can support up to (9) secondary frames as needed.
Order as required. Maximum of 10 rectifiers/bay. System can support up to (9) secondary frames as needed.
List Number
List 16* 58214000016 Distribution frame, no rectification
* Must be used with external main battery termination bars.
Emerson Part Number
Description
Qty. Notes
Order as required. System can support up to (5) distribution frames as needed.
Step 3. Select Input Voltage Source (AC Input Source)
Select one, quantity of one.
List Number
List 0A 5821400000A 480 VAC, 3 phase input (4-wire circuit) List 0B 5821400000B 208 VAC, 3 phase input (4-wire circuit)
For additional information or questions visit or call:
2 004ORA-NS802 / 0913
Emerson Part Number
Description
Qty.
Rack
Space
Page 3
NetSure™ 802 Series
DC Power System
Step 4. Select Rectifier Model
List Number
n/a 486534003*
n/a 486532603*
n/a 486532602* 200 amp rectifier R4811600 (480 VAC)
* 200 A is nominal rating. These units are capable of current limiting up to 220 A each.
Emerson Part Number
Description
High efficiency 200 amp eSure R4812000Le (208 VAC), 3 phase input
High efficiency 200 amp eSure R4812000e (480 VAC), 3 phase input
rectifier
rectifier
Qty.
Step 5. Optional - Select AC Service Cabinet (PDSC)
Must be selected if List 2 or List 12 was selected in Step 1.
List Number
List 30 58214000030
List 31 58214000031
List 32 58214000032
Emerson Part Number
Description
480 VAC input bolt-on PDSC (22 kAIC rated breakers)
480 VAC input bolt-on PDSC (65 kAIC rated breakers)
208 VAC input bolt-on PDSC (65 kAIC rated breakers)
Qty. Notes
Rack
Space
Select the quantity of cabinets needed by to total number of List 2 and List 12's needed in total.
Select the quantity of cabinets needed by to total number of List 2 and List 12's needed in total.
Select the quantity of cabinets needed by to total number of List 2 and List 12's needed in total.
Pictorial
Step 6. Optional - Select Transient Voltage Surge Suppression
Must be selected if Lists 2, 4, 12 or 14 were selected in Step 1.
List Number
List 35 58214000035
List 36 58214000036
List 37 58214000037
List 38 58214000038
For additional information or questions visit or call:
004ORA-NS802 / 0913
Emerson Part Number
Description
480 VAC input surge suppression for use in the PDSC cabinet
208 VAC input surge suppression for use in the PDSC cabinet
480 VAC input surge suppression for use in the power bays (List 4 and 14)
208 VAC input surge suppression for use in the power bays (List 4 and 14)
Qty. Notes
For use with List 30 or 31 AC service cabinets only. (1) required for each AC service cabinet.
For use with List 32 AC service cabinets only. (1) required for each AC service cabinet.
For use with List 4 and 14 when equipped for 480 VAC input.
For use with List 4 and 14 when equipped for 208 VAC input.
(TVSS)
3
Page 4
NetSure™ 802 Series
DC Power System
LMS 1000 – Lorain® Monitoring Unit
1
2 3
MCA Circuit Card, (Primary Bay)
1
List 1, 2, 3, 4, 5
Router Circuit Card (Secondary Bay)
List 11, 12, 13, 14, 15
Optional LMS Main CPU Circuit
2
Card, List 50 or Optional LMS Expansion CPU Circuit Card, List 63
Available MCA Input/Output (I/O)
3
Circuit Cards:
– MCA Customer Alarm Relay Card
(6 Form-C Contacts), List 70
– MCA Analog Input/Output and
Binary Input Circuit Card, List 71
Step 7. Select Controller Accessory Cards
Select one, quantity of one, if desired.
List Number
List 70 58214000070 MCA alarm relay card
List 71 58214000071 MCA analog and binary I/O card
Emerson Part Number
Description
Qty. Notes
Provide (6) Form-C alarm user defined output relays. (Each primary frame is factory equipped with [2]).
Provide (4) binary inputs plus (1) analog input and (1) analog output signal .
Step 8. Select LMS1000 Monitoring Options
Select List 50 for all main bays (lists 1-5). Select list 63 for supplemental bays if required.
List Number
List 50 58214000050 LMS1000 main CPU card Order 1 list 50 for each main bay ordered (lists 1, 2, 3, 4 or 5).
List 63 58214000063 LMS1000 CPU expansion card
Note: Refer to SAG586505000 for additional LMS options.
Emerson Part Number
Description
Qty. Notes
Requires the main CPU card. This option mounts into the LMS chassis slot for all supplemental bays to enable all LMS cards in expansion bays.
For additional information or questions visit or call:
4 004ORA-NS802 / 0913
Page 5
NetSure™ 802 Series
DC Power System
Step 8a. Select LMS1000 Card/Software Options
Select at least 1 analog card for battery monitoring (58650500020) and 1 binary card for battery disconnect status (58650500031).
Order additional cards as necessary.
List Number
LMS 1000 Cards – Select quantity as needed
n/a 58650500020 Four (4) channel analog input card
n/a 58650500021 Eight (8) channel temperature input card
n/a 58650500022 Eight (8) channel analog input card
n/a 58650500023
n/a 58650500030 Four (4) channel binary input card n/a 58650500031 Eight (8) channel binary input card n/a 58650500040 Four (4) channel Form-C relay output card n/a 58650500070 Modem circuit card
Software Options – Select as many below as required
n/a 58650500078 LMS dual MCA interface software option
n/a 58650500079 Gateway port software option
n/a 58650500086 TL1/X.25 software option n/a 58650500087 Power metering software option n/a 58650500090 TL1 (over Ethernet) software option
Accessories – Select as many below as required
n/a 586505000BA Current limit resistor kit, 3/8" ring lug
n/a 586505000BB Current limit resistor kit, splice
n/a 586505000BC Current limit resistor kit, 5/16" ring lug
n/a 586505000BE In-line fuse kit, 3/8" ring lug
n/a 586505000BF In-line fuse kit, 5/16" ring lug
n/a 535135
n/a 586505000ST
n/a 586505000SU
Emerson Part Number
Description
Twelve (12) channel analog input card - bat­tery cell voltage
In-line fuse kit, 1/4" ring lug, 3/8" ring lug, 5/16" ring lug, or butt splice
Temperature sensor, mounts to a 5/16" or M8 battery post
Temperature sensor, mounts to a 1/4" or M6 battery post
Qty. Notes
Select the required amount and type of current limit resistor kits (List BA, BB, or BC) or in-line fuse kits (List BE, BF, or 535135)
Select the required amount and type of temperature sensors (List ST or SU)
Select the required amount and type of current limit resistor kits (List BA, BB, or BC)
Select the required amount and type of in-line fuse kits (List BE, BF, or 535135)
Select the required amount and type of current limit resistor kits (List BA, BB, or BC) or in-line fuse kits (List BE, BF, or 535135).
Select the required amount and type of temperature sensors (List ST or SU).
Provides (25) shunt inputs. Maximum quantity of one per bay. For use with GJ/218 breakers with shunts or TPH or TPL-B fuse panels with shunts. Mounts internal to power system.
Provides (25) shunt inputs. Maximum quantity of one per bay. For use with GJ/218 breakers with shunts or TPH or TPL-B fuse panels with shunts. Mounts internal to power system.
Provides (8) temperature inputs. Maximum quantity of eight per system. Mounts external to power system.
Provides temperature monitoring and alarming for battery or ambient. Battery-assigned probes provide temperature compen­sation and battery thermal runaway management. Comprised of
0.3 m length sensor and 10 m length extension.
Provides temperature monitoring and alarming for battery or ambient. Battery-assigned probes provide temperature compen­sation and battery thermal runaway management. Comprised of
0.3 m length sensor and 10 m length extension.
Provides temperature monitoring and alarming for battery or ambient. Battery-assigned probes provide temperature compen­sation and battery thermal runaway management. Comprised of
0.3 m length sensor and 10 m length extension.
Provides temperature monitoring and alarming for battery or ambient. Battery-assigned probes provide temperature compen­sation and battery thermal runaway management. Comprised of
0.3 m length sensor and 10 m length extension.
Provides temperature monitoring and alarming for battery or ambient. Battery-assigned probes provide temperature compen­sation and battery thermal runaway management. Comprised of
0.3 m length sensor and 10 m length extension.
For additional information or questions visit or call:
004ORA-NS802 / 0913
5
Page 6
NetSure™ 802 Series
DC Power System
Step 9. Select DC Distribution Device Types
Select quantity and type as needed.
Step 9a. Choose TPL Style Fuses
List Number
n/a 248251500 Fuse, TPL-C, 70 A 2 Uses (1) 514403 fuseholder n/a 248252000 Fuse, TPL-C, 80 A 2 Uses (1) 514403 fuseholder n/a 248252600 Fuse, TPL-B, 100 A 2 Uses (1) 514403 fuseholder n/a 248253300 Fuse, TPL-B, 150 A 2 Uses (1) 514403 fuseholder n/a 248254000 Fuse, TPL-B, 200 A 2 Uses (1) 514403 fuseholder n/a 248254500 Fuse, TPL-B, 225 A 2 Uses (1) 514403 fuseholder n/a 248255000 Fuse, TPL-B, 250 A 2 Uses (1) 514403 fuseholder n/a 248255700 Fuse, TPL-C, 300 A 2 Uses (1) 514403 fuseholder n/a 248257000 Fuse, TPL-C, 400 A 2 Uses (1) 514403 fuseholder n/a 248258000 Fuse, TPL-C, 500 A 2 Uses (1) 514403 fuseholder n/a 248259000 Fuse, TPL-C, 600 A 2 Uses (1) 514403 fuseholder n/a 102901 Fuse, TPL-C, 800 A 3 Uses (1) 514404 fuseholder
For each fuse needed, order (1) 248610301 GMT alarm fuse (18/100 A) and (1) 248898700 GMT fuse safety cover.
n/a 248610301 GMT alarm fuse, 18/100 A n/a 248898700 GMT fuse safety cover
For each fuse needed, order (1) of the listed fuseholders; for all fuses 600 A or less, the 514403 is the recommended device.
n/a 514403 TPL fuse holder, 600 A max
n/a 514404 TPL fuse holder, 800 A max
Emerson Part Number
Description
Qty.
Poles Used Notes
Pictorial
For additional information or questions visit or call:
6 004ORA-NS802 / 0913
Page 7
NetSure™ 802 Series
DC Power System
Step 9b. Choose GJ/218 Style Breakers
List Number
Electrical Trip Alarm (White Handle) GJ/218 Style Breakers with Internal Shunt
n/a 513766 100 A circuit breaker, E-trip 1 520891 Not required n/a 513768 125 A circuit breaker, E-trip 1 520891 Not required n/a 513770 150 A circuit breaker, E-trip 1 520891 Not required n/a 513772 175 A circuit breaker, E-trip 1 520891 Not required n/a 513774 200 A circuit breaker, E-trip 1 520891 Not required n/a 513776 225 A circuit breaker, E-trip 1 520891 Not required n/a 513778 250 A circuit breaker, E-trip 1 520891 Not required n/a 513780 300 A circuit breaker, E-trip 2 520892 529132 n/a 513782 350 A circuit breaker, E-trip 2 520892 529132 n/a 513784 400 A circuit breaker, E-trip 2 520892 529132 n/a 513786 450 A circuit breaker, E-trip 3 520893 529131 n/a 513788 500 A circuit breaker, E-trip 3 520893 529131 n/a 513790 600 A circuit breaker, E-trip 3 520893 529131 n/a 513792 800 A circuit breaker, E-trip 4 520894 534420
Electrical/Mechanical Trip Alarm (Black Handle) GJ/218 Style Breakers with Internal Shunt
n/a 513767 100 A circuit breaker, E/M-trip 1 520891 Not required n/a 513769 125 A circuit breaker, E/M-trip 1 520891 Not required n/a 513771 150 A circuit breaker, E/M-trip 1 520891 Not required n/a 513773 175 A circuit breaker, E/M-trip 1 520891 Not required n/a 513775 200 A circuit breaker, E/M-trip 1 520891 Not required n/a 513777 225 A circuit breaker, E/M-trip 1 520891 Not required n/a 513779 250 A circuit breaker, E/M-trip 1 520891 Not required n/a 513781 300 A circuit breaker, E/M-trip 2 520892 529132 n/a 513783 350 A circuit breaker, E/M-trip 2 520892 529132 n/a 513785 400 A circuit breaker, E/M-trip 2 520892 529132 n/a 513787 450 A circuit breaker, E/M-trip 3 520893 529131 n/a 513789 500 A circuit breaker, E/M-trip 3 520893 529131 n/a 513791 600 A circuit breaker, E/M-trip 3 520893 529131 n/a 513793 800 A circuit breaker, E/M-trip 4 520894 534420
Emerson Part Number Description
Qty.
Poles Used
Power/Dist. Bay
Lug Adapter
Distribution Only
Bay Lug Adapter
Pictorial
For additional information or questions visit or call:
004ORA-NS802 / 0913
7
Page 8
NetSure™ 802 Series
DC Power System
Step 9c. Choose Bullet-Type Circuit Breakers and Adapter Kit
List Number
Toggle Handle Electrical Trip Alarm (White Handle) Bullet Breakers
n/a 102272 CB, 1 A, bullet, toggle handle, E-trip Occupies one position n/a 102273 CB, 3 A, bullet, toggle handle, E-trip Occupies one position n/a 102274 CB, 5 A, bullet, toggle handle, E-trip Occupies one position n/a 102275 CB, 10 A, bullet, toggle handle, E-trip Occupies one position n/a 102276 CB, 15 A, bullet, toggle handle, E-trip Occupies one position n/a 102277 CB, 20 A, bullet, toggle handle, E-trip Occupies one position n/a 102278 CB, 25 A, bullet, toggle handle, E-trip Occupies one position n/a 102279 CB, 30 A, bullet, toggle handle, E-trip Occupies one position n/a 102280 CB, 35 A, bullet, toggle handle, E-trip Occupies one position n/a 102281 CB, 40 A, bullet, toggle handle, E-trip Occupies one position n/a 121998 CB, 45 A, bullet, toggle handle, E-trip Occupies one position n/a 102282 CB, 50 A, bullet, toggle handle, E-trip Occupies one position n/a 102283 CB, 60 A, bullet, toggle handle, E-trip Occupies one position n/a 102284 CB, 70 A, bullet, toggle handle, E-trip Occupies one position n/a 102285 CB, 75 A, bullet, toggle handle, E-trip Occupies one position n/a 121996 CB, 80 A, bullet, toggle handle, E-trip Occupies one position n/a 102286 CB, 100 A, bullet, toggle handle, E-trip Occupies one position n/a 516991 CB, 125 A, bullet, toggle handle, E-trip Occupies two positions n/a 516993 CB, 150 A, bullet, toggle handle, E-trip Occupies (2) positions, space required n/a 144883 CB, 175 A, bullet, toggle handle, E-trip Occupies (2) positions, space required n/a 121831 CB, 200 A, bullet, toggle handle, E-trip Occupies (2) positions, space required n/a 144885 CB, 225 A, bullet, toggle handle, E-trip Occupies (3) positions, space required n/a 121835 CB, 250 A, bullet, toggle handle, E-trip Occupies (3) positions, space required
n/a 513747
Emerson Part Number Description
Circuit breaker/fuseholder mounting assembly
Qty. Notes
Order (1) 513747 assembly for every six circuit breaker/fuseholder combi­nations required. Each assembly occupies (3) larger "pole" positions in the distribution section. For use with
lists 1, 2, 11 & 12 only.
Pictorial
For additional information or questions visit or call:
8 004ORA-NS802 / 0913
Page 9
NetSure™ 802 Series
DC Power System
Step 9c. Choose Bullet-Type Circuit Breakers and Adapter Kit (continued)
List Number
Toggle Handle Electrical/Mechanical Trip Alarm (Black Handle) Bullet Breakers
n/a 101596 CB, 1 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101597 CB, 3 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101598 CB, 5 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101599 CB, 10 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101600 CB, 15 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101601 CB, 20 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101602 CB, 25 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101603 CB, 30 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101604 CB, 35 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101605 CB, 40 A, bullet, toggle handle, E/M-trip Occupies one position n/a 121997 CB, 45 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101606 CB, 50 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101607 CB, 60 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101608 CB, 70 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101609 CB, 75 A, bullet, toggle handle, E/M-trip Occupies one position n/a 121995 CB, 80 A, bullet, toggle handle, E/M-trip Occupies one position n/a 101610 CB, 100 A, bullet, toggle handle, E/M-trip Occupies one position n/a 516838 CB, 125 A, bullet, toggle handle, E/M-trip Occupies two positions n/a 516839 CB, 150 A, bullet, toggle handle, E/M-trip Occupies (2) positions, space required n/a 144884 CB, 175 A, bullet, toggle handle, E/M-trip Occupies (2) positions, space required n/a 121832 CB, 200 A, bullet, toggle handle, E/M-trip Occupies (2) positions, space required n/a 144886 CB, 225 A, bullet, toggle handle, E/M-trip Occupies (3) positions, space required n/a 121836 CB, 250 A, bullet, toggle handle, E/M-trip Occupies (3) positions, space required
n/a 513747
Emerson Part Number Description
Circuit breaker/fuseholder mounting assembly
Qty. Notes
Order (1) 513747 assembly for every six circuit breaker/fuseholder combi­nations required. Each assembly occupies (3) larger "pole" positions in the distribution section. For use with
lists 1, 2, 11 & 12 only.
Pictorial
For additional information or questions visit or call:
004ORA-NS802 / 0913
9
Page 10
NetSure™ 802 Series
DC Power System
Step 9d. Choose TLS/TPS Fuses with Bullet-Type Fuse Holders
List Number
n/a 117201 Fuse holder, TLS/TPS, bullet type Order one fuse holder per fuse
n/a 248230900 Fuse, TLS/TPS, 3 amps Occupies one position n/a 248231000 Fuse, TLS/TPS, 5 amps Occupies one position n/a 248231200 Fuse, TLS/TPS, 6 amps Occupies one position n/a 248231500 Fuse, TLS/TPS, 10 amps Occupies one position n/a 248231800 Fuse, TLS/TPS, 15 amps Occupies one position n/a 248232100 Fuse, TLS/TPS, 20 amps Occupies one position n/a 248232400 Fuse, TLS/TPS, 25 amps Occupies one position n/a 248232700 Fuse, TLS/TPS, 30 amps Occupies one position n/a 248233300 Fuse, TLS/TPS, 40 amps Occupies one position n/a 248233900 Fuse, TLS/TPS, 50 amps Occupies one position n/a 248234200 Fuse, TLS/TPS, 60 amps Occupies one position n/a 248234500 Fuse, TLS/TPS, 70 amps Occupies one position n/a 118413 Fuse, TLS/TPS, 80 amps Occupies one position n/a 118414 Fuse, TLS/TPS, 90 amps Occupies one position n/a 118415 Fuse, TLS/TPS, 100 amps Occupies one position n/a 139052 Fuse, TLS/TPS, 125 amps Occupies one position
Emerson Part Number Description
Qty. Notes
Pictorial
Order (1) 513747 assembly for every
n/a 513747
Circuit breaker/fuseholder mounting assembly
six circuit breaker/fuseholder combi­nations required. Each assembly occupies (3) larger "pole" positions in the distribution section.
For additional information or questions visit or call:
10 004ORA-NS802 / 0913
Page 11
NetSure™ 802 Series
DC Power System
Step 10. Optional - Select Small Distribution for Distribution Bay
Order smaller circuit breakers and fuses from Step 8c and 8d above.
List Number
List 0C 5821400000C
n/a 509128 Fuse module, ten (10) GMT fuse positions
n/a 248610301 Fuse, GMT, 18/100 amp n/a 248610200 Fuse, GMT, 1/4 amp n/a 248610300 Fuse, GMT, 1/2 amp n/a 248610500 Fuse, GMT, 3/4 amp n/a 248610700 Fuse, GMT, 1-1/3 amps n/a 248610800 Fuse, GMT, 2 amps n/a 248610900 Fuse, GMT, 3 amps n/a 248611000 Fuse, GMT, 5 amps n/a 248611300 Fuse, GMT, 7-1/2 amps n/a 248611200 Fuse, GMT, 10 amps n/a 248611500 Fuse, GMT, 15 amps n/a 102774 Replacement safety cover n/a 248872600 Replacement dummy fuse
Emerson Part Number Description
Bullet nose fuse/circuit breaker panel for use in 58214000016 distribution bay
Qty.
(List 16)
Pictorial
For additional information or questions visit or call:
004ORA-NS802 / 0913
11
Page 12
NetSure™ 802 Series
DC Power System
Step 11. Optional - Select Internal Return Bar (as needed)
Select one, quantity of one, if desired. Note restrictions.
List Number
n/a 554862 2000 A ground bar kit, internal
n/a 555214 2000 A ground bar kit, internal
Emerson Part Number Description
Qty. Notes
Internal ground bar kit recommended for use with >100 A distribution devices. Mounts only in List 1, 2, 11, or 12 power/ distribution frames.
Internal ground bar kit recommended for use with >200 A distribution devices. Mounts only in List 1, 2, 11, or 12 power/ distribution frames.
Pictorial
For additional information or questions visit or call:
12 004ORA-NS802 / 0913
Page 13
NetSure™ 802 Series
DC Power System
Step 12. Optional - Select External Termination Bus Assembly
Select one, quantity of one, if desired. Note restrictions.
List Number
n/a 554873
n/a 528482 Busbar shield kit
n/a 554874
Emerson Part Number Description
External top-mount hori­zontal battery input bus assembly
External top-mount verti­cal batter input bus assembly
Qty. Notes
Provides for external battery input
landings for use with List 1, 2, 3, 4, 5, 11, 12, 13, 14, and 15. Lug sizes should be 3/8" x 1.000" centers. Rated for 2000 A each.
Lexan kit provides protection on -48 V bus. For use with 554873 kit.
Order (1) per bay as required. Must be mounted on top of 554873 bus assembly. Includes Lexan shields.
Pictorial
For additional information or questions visit or call:
004ORA-NS802 / 0913
13
Page 14
NetSure™ 802 Series
DC Power System
Step 13. Optional - Select External Return Bar Option
Select one, quantity of one, if desired. Note restrictions.
List Number
n/a 514688
n/a 514689
n/a 514690
n/a 514691
n/a 514543
Emerson Part Number Description
External ground return bar, 6000 A
External ground return bar, 10,000 A
External ground return bar, 6000 A
External ground return bar, 10,000 A
Load return lug expansion busbar
Qty. Notes
Must be used with 554873 kits. For use with List 1, 3, 4, 5, 11, 13, 14 and 15 frames.
Must be used with 554873 kits. For use with List 1, 3, 4, 5, 11, 13, 14 and 15 frames.
Must be used with 554873 kits. For use only with List 2 and 12 frames.
Must be used with 554873 kits. For use only with List 2 and 12 frames.
Mounts to any of the available 6000 A or 10,000 A external ground return bar options.
Pictorial
For additional information or questions visit or call:
14 004ORA-NS802 / 0913
Page 15
NetSure™ 802 Series
DC Power System
Step 14. Order Accessories (as needed)
Select quantity and vertical rack spacing as desired and as relay rack space allows.
List Number
n/a 107021 Temperature probe, 25' long n/a 106824 Temperature probe, 100' long List 64 58214000064 Interface kit to LVPS power system e/w DGU List 65 58214000065 Interface kit to LVPS power system e/w LMS1000 n/a 550281 3000 A external main termination bar, no shunt (1) power bay (1) distribution bay n/a 550282 5000 A external main termination bar, no shunt (2) power bays (1) distribution bay n/a 550283 5000 A external main termination bar, no shunt (2) power bays (2) distribution bays n/a 550284 7500 A external main termination bar, no shunt (3) power bays (2) distribution bays n/a 550285 7500 A external main termination bar, no shunt (3) power bays (3) distribution bays n/a 550286 10,000 A external main termination bar, no shunt (4) power bays (2) distribution bays n/a 550287 10,000 A external main termination bar, no shunt (4) power bays (3) distribution bays n/a 550291 3000 A external main termination bar, e/w shunt (1) power bay (1) distribution bay n/a 550292 5000 A external main termination bar, e/w shunt (2) power bays (1) distribution bay n/a 550293 5000 A external main termination bar, e/w shunt (2) power bays (2) distribution bays n/a 550294 7500 A external main termination bar, e/w shunt (3) power bays (2) distribution bays n/a 550295 7500 A external main termination bar, e/w shunt (3) power bays (3) distribution bays n/a 550296 10,000 A external main termination bar, e/w shunt (4) power bays (2) distribution bays n/a 550297 10,000 A external main termination bar, e/w shunt (4) power bays (3) distribution bays
Emerson Part Number
Description
Qty.
Rack
Space Notes
For additional information or questions visit or call:
004ORA-NS802 / 0913
15
Page 16
NetSure™ 802 Series
DC Power System
EmersonNetworkPower.com/EnergySystems (North America) EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2013.
Business-Critical Continuity™, Emerson Network Power™, the Emer son Net work Power l ogo, Emer son® and Consi der it Solv ed are ser vice mark s and
tradem arks of Eme rson Elec tric Co. En ergyMas ter Netw ork Power, Ener gy Systems , North Am erica, In c. Any other p roduct , brand, or co mpany names o r logos are t he proper ty of the r especti ve owner.
16 004ORA-NS802 / 0913
, eSure™, NetPerform™, NetReach™, NetSpan™, NetSu re™ and NetXtend™ are trad emarks of E merson
While ev ery prec aution has b een taken to e nsure accur acy and completeness herein, Emerson Electric Co. assumes no responsibility, and disc laims all liab ility, for da mages resul ting from u se of this information or for any errors or omissions. Specifications subject to change without notice.
Loading...