NetSure™ 802 Series
DC Power System
Key Features
n NEBS Level 3 certified
n Single frame design provides power
conversion, distribution, control
and monitoring in a small footprint
n Patented, laminated internal
bus work improves DC
cable routing options
n Modular distribution design includes
built-in automatic monitoring
for all distribution devices
n Integrated internal DC bus, in
combination bays, eliminates
eliminates costly overhead busses
and eases plant expansion
n Integrated LMS1000 design
features a distributed I/O
architecture, an internet port and
web page to simplify monitoring
of internal/external equipment
n Controller backplane accepts plug-
in alarm cards and LMS I/O cards
n Optional integrated AC Power
Distribution Service Cabinet (PDSC)
for protected bulk AC service feeds
with 22 or 65 kAIC breakers
™
The expanded NetSure
802 Series introduces separate,
stand-alone power and distribution bays complementing
the system’s compact combination bays and integrating
easily with existing AC infrastructure.
Combination Power
and Distribution Bay
Description
The expanded NetSure™ 802 Series offers solutions to meet the needs of any central
office, Mobile Telephone Switching Office (MTSO) or data center deployment. NetSure
802 combination bays still provide reliable, efficient power and distribution in a compact
footprint, while new stand-alone power and distribution bays can be used together or in
combination with other systems to deliver maximum flexibility. NetSure
bays can be paired with high-efficiency rectifiers and can replace 200 and 400 amp ferro
rectifiers—with a single breaker for each rectifier—without disrupting the existing AC
infrastructure. All models are backward compatible with existing systems.
Power Bay with
Distribution Bay
Back of Power Bay
™
802 power
™
n TCP/IP, SNMP, Ethernet,
standard modem optional
n Supports distributed and
bulk plant architectures
1004D-NS802 / 0413

NetSure™ 802 Series
NetSure
™
802 Combination BayNetSure™ 802 Power Bay 200A Ferro Retrofit
Power Bay
400A Ferro Retrofit
Power Bay
Centralized Architecture:
Stand-Alone Power and
Distribution Bays
The NetSure™ 802 system’s new, individual
power bays and distribution bays can be
paired with high-efficiency eSure
ers and configured to meet any application
requirement, including ferro retrofits.
Power bays are available with individual AC
feeds or may be bulk fed using an existing
power distribution service cabinet (PDSC)
by simply rerouting existing cabling and
using existing breakers—with a separate
breaker for each rectifier. That means
shutting down a breaker to service or
replace a rectifier impacts only that rectifier. Web pages in the LMS1000 monitoring
system have been upgraded to offer new
features. There are three power bays to
choose from, and the bays can be mixed
and matched to suit specific applications.
Those three options are:
n Bulk Feed (Main Bay = 58214000004,
Sup Bay = 58214000014)
n 400A Ferro Retrofit (Main Bay =
58214000003, Sup Bay = 58214000013)
n 200A Ferro Retrofit (Main Bay =
58214000005, Sup Bay = 58214000015)
™
rectifi-
Distributed Architecture:
Combination Bays
The proven NetSure™ 802 combination
bays provide power and distribution in the
same bay, retaining the internal busses
originally introduced in this product line.
These bays also may be configured with
new high-efficiency eSure
are available with individual AC feeds
(480V or 208V options) or may be bulk fed
using Emerson’s side-by-side PDSC. The
web interface for the LMS1000 monitoring
system has been upgraded for ease of use.
™
rectifiers and
Ferro Retrofits
Emerson Network Power’s NetSure™ 802
power bays are set up to allow reuse of
existing AC infrastructure for 200 and 400
amp ferro rectifiers—the most popular ferros still in service. These bays, with each
rectifier assigned to its own breaker, are
useful for deployments with existing
PDSCs or when the preference is to have
the AC circuit breakers remote from the
system. Ferro retrofit applications also
allow reuse of existing main battery termination bars.
Distribution Options
Distribution Element Combination Bay Distribution Bay
TPS/TLS Fuses or Bullet Circuit Breakers 48 24
100-250A Circuit Breakers 24 48
300-400A Circuit Breakers 12 24
70-600A TPL Fuses 12 24
450-600A Circuit Breakers 8 16
800A TPL Fuses 8 16
800A Circuit Breakers 4* 8*
* For each 800 Amp circuit breaker deployed there is space on the bus for one two-pole or two single-pole circuit breakers.
2 004D-NS802 / 0413

NetSure™ 802 Series
Bulk Feed Bay Power Bay eSure
Power Bays for
New Construction
For new applications, the NetSure™ 802
bulk feed bay keeps AC infrastructure
costs to a minimum. Configured with
NetSure
will provide power plants up to 16,000
amps—and can be factory-configured
up to 26,000 amps.
™
802 distribution bays, this
™
R48-12000Le (486534003)
High-Efficiency Rectifier
Rectifier Options
There are three rectifier options for the
NetSure
to all NetSure
original Lorain
These are:
n Standard (92.6%) 480V AC,
n eSure
n eSure
™
802, each backward compatible
™
802 bays as well as the
®
Power Systems (LPS).
200 amp rectifier
™
high-efficiency (95.7%)
208V AC, 200 amp rectifier
™
high-efficiency (96.1%)
480V AC, 200 amp rectifier
™
NetSure
802 Power Bay Replaces
Five 400 amp Ferro Rectifiers
Smaller Footprint,
Higher Efficiency
Either NetSure™ 802 configuration—standalone bays or combination bays—reduces
the footprint from ferro rectifiers significantly. Emerson’s high density power
bays are just 24 inches wide, 30 inches
deep and 84 inches tall. A single NetSure
802 (58214000003) power bay replaces
five 400 amp ferro rectifiers in the floor
space of two legacy ferros, occupying a
60% smaller footprint. That space savings,
coupled with the reduced energy consumption achieved with high-efficiency
rectifiers and reduced cooling costs, provide tremendous operating cost savings
over time.
™
004D-NS802 / 0413
3

NetSure™ 802 Series
System Features
Nominal System Voltage 408-528V AC (480 nominal) or 176-264V AC (208 nominal)
Monitoring MCA controller with optional LMS1000 monitor
Output Capacity
Per System 16,000A
Power Bay (POB) 2000A (nominal), 2200A (full current limit)
Combination Bay Power 2000A (nominal), 2200A (full current limit)
Distribution Bay (DOB) 6000A
Physical Characteristics
Dimensions (H x W x D), Weight Power Bay with Rectifiers: 84" x 24" x 30", 995 lbs.
Environmental
Operating Temperature 0°C to +40°C (+32°F to +104°F)
Storage Temperature -40°C to +85°C (-40°F to +149°F)
Safety Compliance UL Listed (UL1801), CSA 22.2 (No. 225), c UL, NEBS Level 3
Distribution 2400A
Combination Power and Distribution Bay
List 1 and List 11 93.5" x 24" x 30", 830 lbs.
List 2 and List 12 84" x 24" x 30", 830 lbs.
AC Distribution Bay (PDSC): 84" x 10" x 30", 190 lbs.
Distribution Bay (DOB): 84" x 30" x 30", 850 lbs.
OverviewTechnical Specifications
1 2
3 4
5
6 7
Ordering Information
Part Number Description
Main Bay Sup Bay Power & Distribution Bays
58214000001 58214000011 Distributed Architecture, Combination Power and Distribution Bay.
58214000002 58214000012 Distributed Architecture, Combination Power and Distribution Bay.
58214000003 58214000013 400A Ferro Retrofit Power Bay
58214000004 58214000014 Bulk Feed Power Bay for New Centralized Applications
58214000005 58214000015 200A Ferro Retrofit Power Bay
58214000016 Distribution Bay
Rectifiers
486534003 High efficiency 200 amp eSure
486532603 High efficiency 200 amp eSure
486532602 200 amp rectifier R4811600 (480VAC)
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2013.
Business-Critical Continuity™, Emerson Network Power™, the Emer son Net work Power l ogo, Emer son® and Consi der it Solv ed are ser vice mark s and
tradem arks of Eme rson Elec tric Co. En ergyMas ter
Netw ork Power En ergy Syste ms North A merica. A ny other pro duct, br and, or compa ny names or lo gos are the pr opert y of the resp ective o wner.
Individual AC feeds for each rectifier located above the bay for easy access.
Has internal bus, does not require overhead Main Battery Term Bars (MBTB)
but may be used with them.
Bulk feed, requires a list 30, 31 or 32 PDSC. Has internal bus, does not require
overhead Main Battery Term Bars (MBTB) but may be used with them.
Accommodates existing AC infrastructure for 400A Ferros (100A @208 or 50A
@480). Requires overhead MBTB.
Requires 2 AC feeds (250A @208 or 100A @480). Requires overhead MBTB.
Accommodates existing AC infrastructure for 200A Ferros (60A @208 or 25A
@480). Requires overhead MBTB.
Used for distribution when power bays are deployed or for additional distribution
when combination bays are used. Requires overhead MBTB.
™
rectifier R4812000Le (208V AC)
™
rectifier R4812000e (480V AC)
™
, eSure™, NetPerform™, NetReach™, NetSpan™, NetSu re™ and NetXtend™ are trad emarks of E merson
8
PDSC (with individual AC breakers)
1
Distribution
2
TPL Fuse Holders
3
Bullet Breaker/Fuse Holder
4
GJ Breakers
5
LMS1000 Monitoring System
6
I/O Cards
7
eSure™ Rectifiers
8
(486534003 or 486532603)
While ev ery prec aution has b een taken to e nsure accur acy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disc laims all liab ility, for da mages resul ting from u se of this
information or for any errors or omissions. Specifications subject to
change without notice.
4 004D-NS802 / 0413