Emerson NetSure 802, NetSure 802 DC Data Sheet

Page 1
NetSure™ 802 Series
DC Power System
Key Features
n NEBS Level 3 certified
n Single frame design provides power
conversion, distribution, control and monitoring in a small footprint
n Patented, laminated internal
bus work improves DC cable routing options
n Modular distribution design includes
built-in automatic monitoring for all distribution devices
n Integrated internal DC bus, in
combination bays, eliminates eliminates costly overhead busses and eases plant expansion
n Integrated LMS1000 design
features a distributed I/O architecture, an internet port and web page to simplify monitoring of internal/external equipment
n Controller backplane accepts plug-
in alarm cards and LMS I/O cards
n Optional integrated AC Power
Distribution Service Cabinet (PDSC) for protected bulk AC service feeds with 22 or 65 kAIC breakers
The expanded NetSure
802 Series introduces separate, stand-alone power and distribution bays complementing the system’s compact combination bays and integrating easily with existing AC infrastructure.
Combination Power
and Distribution Bay
Description
The expanded NetSure™ 802 Series offers solutions to meet the needs of any central office, Mobile Telephone Switching Office (MTSO) or data center deployment. NetSure 802 combination bays still provide reliable, efficient power and distribution in a compact footprint, while new stand-alone power and distribution bays can be used together or in combination with other systems to deliver maximum flexibility. NetSure bays can be paired with high-efficiency rectifiers and can replace 200 and 400 amp ferro rectifiers—with a single breaker for each rectifier—without disrupting the existing AC infrastructure. All models are backward compatible with existing systems.
Power Bay with
Distribution Bay
Back of Power Bay
802 power
n TCP/IP, SNMP, Ethernet,
standard modem optional
n Supports distributed and
bulk plant architectures
1004D-NS802 / 0413
Page 2
NetSure™ 802 Series
NetSure
802 Combination BayNetSure™ 802 Power Bay 200A Ferro Retrofit
Power Bay
400A Ferro Retrofit
Power Bay
Centralized Architecture: Stand-Alone Power and Distribution Bays
The NetSure™ 802 system’s new, individual power bays and distribution bays can be paired with high-efficiency eSure ers and configured to meet any application requirement, including ferro retrofits. Power bays are available with individual AC feeds or may be bulk fed using an existing power distribution service cabinet (PDSC) by simply rerouting existing cabling and using existing breakers—with a separate breaker for each rectifier. That means shutting down a breaker to service or replace a rectifier impacts only that rectifi­er. Web pages in the LMS1000 monitoring system have been upgraded to offer new features. There are three power bays to choose from, and the bays can be mixed and matched to suit specific applications. Those three options are:
n Bulk Feed (Main Bay = 58214000004,
Sup Bay = 58214000014)
n 400A Ferro Retrofit (Main Bay =
58214000003, Sup Bay = 58214000013)
n 200A Ferro Retrofit (Main Bay =
58214000005, Sup Bay = 58214000015)
rectifi-
Distributed Architecture: Combination Bays
The proven NetSure™ 802 combination bays provide power and distribution in the same bay, retaining the internal busses originally introduced in this product line. These bays also may be configured with new high-efficiency eSure are available with individual AC feeds (480V or 208V options) or may be bulk fed using Emerson’s side-by-side PDSC. The web interface for the LMS1000 monitoring system has been upgraded for ease of use.
rectifiers and
Ferro Retrofits
Emerson Network Power’s NetSure™ 802 power bays are set up to allow reuse of existing AC infrastructure for 200 and 400 amp ferro rectifiers—the most popular fer­ros still in service. These bays, with each rectifier assigned to its own breaker, are useful for deployments with existing PDSCs or when the preference is to have the AC circuit breakers remote from the system. Ferro retrofit applications also allow reuse of existing main battery termi­nation bars.
Distribution Options
Distribution Element Combination Bay Distribution Bay
TPS/TLS Fuses or Bullet Circuit Breakers 48 24
100-250A Circuit Breakers 24 48 300-400A Circuit Breakers 12 24 70-600A TPL Fuses 12 24 450-600A Circuit Breakers 8 16 800A TPL Fuses 8 16 800A Circuit Breakers 4* 8*
* For each 800 Amp circuit breaker deployed there is space on the bus for one two-pole or two single-pole circuit breakers.
2 004D-NS802 / 0413
Page 3
NetSure™ 802 Series
Bulk Feed Bay Power Bay eSure
Power Bays for New Construction
For new applications, the NetSure™ 802 bulk feed bay keeps AC infrastructure costs to a minimum. Configured with NetSure will provide power plants up to 16,000 amps—and can be factory-configured up to 26,000 amps.
802 distribution bays, this
R48-12000Le (486534003)
High-Efficiency Rectifier
Rectifier Options
There are three rectifier options for the NetSure to all NetSure original Lorain These are:
n Standard (92.6%) 480V AC,
n eSure
n eSure
802, each backward compatible
802 bays as well as the
®
Power Systems (LPS).
200 amp rectifier
high-efficiency (95.7%)
208V AC, 200 amp rectifier
high-efficiency (96.1%)
480V AC, 200 amp rectifier
NetSure
802 Power Bay Replaces
Five 400 amp Ferro Rectifiers
Smaller Footprint, Higher Efficiency
Either NetSure™ 802 configuration—stand­alone bays or combination bays—reduces the footprint from ferro rectifiers sig­nificantly. Emerson’s high density power bays are just 24 inches wide, 30 inches deep and 84 inches tall. A single NetSure 802 (58214000003) power bay replaces five 400 amp ferro rectifiers in the floor space of two legacy ferros, occupying a 60% smaller footprint. That space savings, coupled with the reduced energy con­sumption achieved with high-efficiency rectifiers and reduced cooling costs, pro­vide tremendous operating cost savings over time.
004D-NS802 / 0413
3
Page 4
NetSure™ 802 Series
System Features
Nominal System Voltage 408-528V AC (480 nominal) or 176-264V AC (208 nominal) Monitoring MCA controller with optional LMS1000 monitor
Output Capacity
Per System 16,000A Power Bay (POB) 2000A (nominal), 2200A (full current limit) Combination Bay Power 2000A (nominal), 2200A (full current limit)
Distribution Bay (DOB) 6000A
Physical Characteristics
Dimensions (H x W x D), Weight Power Bay with Rectifiers: 84" x 24" x 30", 995 lbs.
Environmental
Operating Temperature 0°C to +40°C (+32°F to +104°F) Storage Temperature -40°C to +85°C (-40°F to +149°F) Safety Compliance UL Listed (UL1801), CSA 22.2 (No. 225), c UL, NEBS Level 3
Distribution 2400A
Combination Power and Distribution Bay List 1 and List 11 93.5" x 24" x 30", 830 lbs. List 2 and List 12 84" x 24" x 30", 830 lbs. AC Distribution Bay (PDSC): 84" x 10" x 30", 190 lbs. Distribution Bay (DOB): 84" x 30" x 30", 850 lbs.
OverviewTechnical Specifications
1 2
3 4
5
6 7
Ordering Information
Part Number Description
Main Bay Sup Bay Power & Distribution Bays
58214000001 58214000011 Distributed Architecture, Combination Power and Distribution Bay.
58214000002 58214000012 Distributed Architecture, Combination Power and Distribution Bay.
58214000003 58214000013 400A Ferro Retrofit Power Bay
58214000004 58214000014 Bulk Feed Power Bay for New Centralized Applications
58214000005 58214000015 200A Ferro Retrofit Power Bay
58214000016 Distribution Bay
Rectifiers
486534003 High efficiency 200 amp eSure 486532603 High efficiency 200 amp eSure 486532602 200 amp rectifier R4811600 (480VAC)
EmersonNetworkPower.com/EnergySystems (North America) EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2013.
Business-Critical Continuity™, Emerson Network Power™, the Emer son Net work Power l ogo, Emer son® and Consi der it Solv ed are ser vice mark s and
tradem arks of Eme rson Elec tric Co. En ergyMas ter Netw ork Power En ergy Syste ms North A merica. A ny other pro duct, br and, or compa ny names or lo gos are the pr opert y of the resp ective o wner.
Individual AC feeds for each rectifier located above the bay for easy access. Has internal bus, does not require overhead Main Battery Term Bars (MBTB) but may be used with them.
Bulk feed, requires a list 30, 31 or 32 PDSC. Has internal bus, does not require overhead Main Battery Term Bars (MBTB) but may be used with them.
Accommodates existing AC infrastructure for 400A Ferros (100A @208 or 50A @480). Requires overhead MBTB.
Requires 2 AC feeds (250A @208 or 100A @480). Requires overhead MBTB.
Accommodates existing AC infrastructure for 200A Ferros (60A @208 or 25A @480). Requires overhead MBTB.
Used for distribution when power bays are deployed or for additional distribution when combination bays are used. Requires overhead MBTB.
rectifier R4812000Le (208V AC)
rectifier R4812000e (480V AC)
, eSure™, NetPerform™, NetReach™, NetSpan™, NetSu re™ and NetXtend™ are trad emarks of E merson
8
PDSC (with individual AC breakers)
1
Distribution
2
TPL Fuse Holders
3
Bullet Breaker/Fuse Holder
4
GJ Breakers
5
LMS1000 Monitoring System
6
I/O Cards
7
eSure™ Rectifiers
8
(486534003 or 486532603)
While ev ery prec aution has b een taken to e nsure accur acy and completeness herein, Emerson Electric Co. assumes no responsibility, and disc laims all liab ility, for da mages resul ting from u se of this information or for any errors or omissions. Specifications subject to change without notice.
4 004D-NS802 / 0413
Loading...