Emerson NetSure 801 R48-5800L, NetSure 801 DC Data Sheet

R48-5800L
DC Power for Business-Critical Continuity
-48VDC, 5800W
Features and Benefits
Optimized depth – reduced footprint
allows installation in short-depth racks and cabinets
DSP (Digital Signaling Processor) –
means fewer components, optimized operation and active load sharing for increased reliability
Compliant with global standards
– delivers quality, performance and reliability no matter what the application or location demands
High efciency, up to 92% – reduces
power consumption for loweroperating costs
Hot pluggable – facilitates future
extensions
Wide input voltage range – operates
in the most demanding environments where input voltage changes
Wide temperature operating range
(-40°C / -40°F to +65°C / 149°F) – meets the harshest climatic environment requirements
Description
The R48-5800L rectier converts 145V to 264 V 3-phase AC supply voltages into stable nominal -48 V DC voltage adjustable to the needs of the application. The R48-5800L is a constant power rectier designed with the latest patented switch-mode technology using DSP (Digital Signaling Processor) functionality for efcient operation. For a higher load capacity, rectiers can be connected in parallel and intelligent control can be added with the help of a separate controller.
R48-5800L
R48-5800L
Technical Specifications, R48-5800L
AC Input
Input Voltage, Nominal 208 V AC Input Voltage, Permitted Variation 145 to 264 V AC Line Frequency 45 to 65 Hz Max Input Current 18 A Power Factor 0.99 THD (Total Harmonic Distortion) <5% from 50 to 100% of rated load
DC Output
Output Voltage, Adjustment Range -42 to -58 V DC Output Power 5800W@Vout >48VDC Output Power, Derated for Input Voltage See Diagram Output Current 120A Output current limit set point 0 to 120 A Efciency 92% Psophometric Noise (System) <1mV at 0 to 100% of rated load; <32 dBrnc at 0 to 100% of rated load Temperature Derating See Diagram
Control and Monitoring
Rectier Alarm and Signaling Alarm and status reported via CAN bus to system controller Visual Indications Green LED: Normal Operation
Yellow LED: Alarm Red LED: HVSD Indicating Lamp Blinking Red LED: Fan Fault
Output power vs. Temperature at Uin > 166 VAC
120 100
80
60
40
20
0
% of output power
-40 -20 0 20 40 60 80 100
Temperature (°C)
Output power vs. input voltage at Tamb < 45°C
120 100
80
60
40
20
0
% of output power
130 150 170 190 210 230 250 270
Input voltage (VAC)
Environmental
Temperature Range, Operating -40 to +65°C, -40 to +149°F Temperature Range, Storage -40 to +70°C, -40 to +158°F Relative Humidity 0 to 95%
Altitude 2000 m, 6560 ft at full power EMC EN 300 386 Class B; Telcordia GR-1089-CORE Class B;
FCC CFR 47 Part 15 Class B
Safety UL 60950; IEC 60950; CSA-C22.2 NO. 60950; Telcordia GR-63-CORE
Mechanics
Dimensions (H×W×D)
85.5×245×380 mm (3.37×9.65×14.96 inches)
Weight <10 kg (22lbs)
Other parts
Controller Units See separate ACU / ACU+ and SCU / SCU+ datasheets
Ordering information
Product Name R48-5800L
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
www.emersonnetworkpower.com www.emersonnetworkpower.com/energysystems www.DCpowerefciency.com
Emerson Network Power reserves the right to alter without notice the specication, design or conditions of supply of any product or service.
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Business-Critical Continuity, Emerson Network Power
and the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.
©2010 Emerson Electric Co.
Loading...