Emerson NetSure 801 R48-5800e, NetSure 801 DC Data Sheet

eSure™ Rectifier
R48-5800e
DC Power for Business-Critical Continuity
-48 V DC, 5800 W
Features and Benefits
Optimized depth-reduced footprint
allows installation in short-depth racks and cabinets
DSP (Digital Signaling Processor)-
means fewer components, optimized operation and active load sharing for increased reliability
Compliant with global standards-
delivers quality, performance and reliability no matter what the application or location demands
High efciency, near 96.2%-reduces
power consumption for lower operating costs
Hot pluggable-facilitates future
extensions
Wide input voltage range-operates in
the most demanding environments where input voltage changes
Wide temperature operating range
(-40°C / -40 °F to +65°C / 149°F) -meets the harshest climatic environment requirements
Description
The eSure™ R48-5800e rectier converts 260 to 530Vac 3-phase AC supply voltages into stable nominal-48V DC voltage adjustable to the needs of the application. The R48-5800e is a constant power rectier designed with the latest patented switch­mode technology using DSP (Digital Signaling Processor) functionality for efcient operation.
For a higher load capacity, rectiers can be connected in parallel and intelligent control can be added with the help of a separate controller.
R48-5800e
eSure™ Rectifier
84
86
88
90
92
94
96
98
0 10 20 30 40 50 60 70 80 90 100
Load (% of rated load)
Efficiency Curve(480V )
Efficiency
(%)
84
86
88
90
92
94
96
98
0 10 20 30 40 50 60 70 80 90 100
Load (% of rated load)
Efficiency Curve(380V )
Efficiency
(%)
R48-5800e
Technical Specifications, R48-5800e
AC Input
Input Voltage, Nominal 380/480 V Input Voltage, Permitted Variation 260 to 530 Vac Line Frequency 45 to 65 Hz Max Input Current 13 A Power Factor 0.99 THD (Total Harmonic Distortion) <5% from 50 to 100% of rated load
DC Output
Output Voltage, Adjustment Range -42 to -58 V DC Output Power 5800W@Vout >48VDC Output Power, Derated for Input Voltage See Diagram Output Current 120A Output Current limit set Point 0 to 120 A Efciency 96.2% peak Psophometric noise (system) <2 mV typical; <32 dBrnc typical Temperature Derating See diagram
Control and Monitoring
Rectier Alarm and Signaling Alarm and status reported via CAN bus to system Controller Visual Indications Green LED = Normal operation; Yellow LED = Alarm;
Red LED = Failure; Flashing red LED = Fan failure
Environmental
Temperature Range, Operating -40 to +65°C, -40 to +149°F Temperature Range, Storage -40 to +70°C, -40 to +158°F Relative Humidity 0 to 95%
Altitude 2000 m, 6560 ft at full power EMC ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B Safety IEC 60950, EN 60950, UL 60950, Telcordia GR-63-CORE
Mechanics
Dimensions (H×W×D) 85.5×245×380mm / 3.37×9.65×14.96 inches Weight 6.5 kg / 14 lbs
Other parts
Controller Units See separate ACU/ACU+ and SCU/SCU+ datasheets
Ordering information
Description Product name Rectier 48V,5800W R48-5800e
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
www.emersonnetworkpower.com www.emersonnetworkpower.com/energysystems www.DCpowerefciency.com
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Business-Critical Continuity, Emerson Network Power
and the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.
Emerson Network Power reserves the right to alter without notice the specication, design or conditions of supply of any product or service.
©2012 Emerson Electric Co.
2012.6