Section 1: Adding XTE3000 Actuators into Existing Network
1.1 Update Firmware in Slot 1 Coprocessor Module ............................................1
1.2 Congure Controlinc Network Master to Communicate with
XTE3000 Actuators ....................................................................................... 1
Section 2: Replacing Actuators with XTE3000 in Existing Network
2.1 Update Firmware in Slot 1 Coprocessor Module ............................................6
2.2 Congure Controlinc Network Master to Communicate with
XTE3000 Actuators ....................................................................................... 6
Table of Contents
July 2020
Table of Contents
i
July 2020
Installation Instructions
VCIOM-15629-EN Rev. 0
This page intentionally left blank
Installation Instructions
VCIOM-15629-EN Rev. 0
!
Failure to follow instructions for proper installation may result in errant information being displayed.
WARNING
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
Section 1: Adding XTE3000 Actuators
into Existing Network
(Number of actuators increases)
1.1 Update Firmware in Slot 1 Coprocessor Module
Obtain rmware le "M250_502.abm" and "Controlinc Network Master Firmware
Download Procedure" from Emerson website, link: www.Emerson.com/Controlinc.
Use the procedure to download M250_502.abm rmware to Slot 1
Coprocessor module.
1.2 Congure Controlinc Network Master to Communicate with XTE3000 Actuators
1. Update number of actuators in the loop.
On Touch Panel go to Main Menu, Figure 1.
Figure 1
Adding XTE3000 Actuators into Existing Network 1
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
Select System Setup, Figure 2.
Figure 2
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 3
Enter security code default 999, Figure 3.
Adding XTE3000 Actuators into Existing Network2
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 4
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
Change number of actuators on the network, Figure 4.
Change number of devices on the network
Click Write and wait for 5 seconds, then Read to verify it is written.
2. Edit Scanlist
On the Main Menu, refer to Figure 1 above.
Select the Scanlist, Figure 5.
Figure 5
Scanlist
Adding XTE3000 Actuators into Existing Network 3
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
Enter security code default 999, refer to Figure 3 above.
Edit the Scanlist, Figure 6.
Figure 6
Installation Instructions
VCIOM-15629-EN Rev. 0
Edit Scanlist
Click Write and wait for 5 seconds then Read to verify it is written.
3. Enter Device Type
In order for Controlinc to recognize XTE3000 actuators, set Device Type 7.
On the Main Menu, refer to Figure 1 above.
Select Device Type, Figure 7.
Figure 7
Click Device Type
Adding XTE3000 Actuators into Existing Network4
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 8
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
Enter security code, default 999, refer to Figure 3 above.
Enter Device Type 7 for XTE3000 actuators, Figure 8.
Only change the address that needs to be changed
Click Write and wait for 5 seconds then Read to verify it is written.
Cycle Network Master power.
Adding XTE3000 Actuators into Existing Network 5
Section 2: Replacing Actuators with XTE3000 in Existing Network
July 2020
Installation Instructions
VCIOM-15629-EN Rev. 0
Section 2: Replacing Actuators with
XTE3000 in Existing Network
(Number of actuators stays the same)
2.1 Update Firmware in Slot 1 Coprocessor Module
Obtain rmware le "M250_502.abm" and "Controlinc Network Master Firmware
Download Procedure" from Emerson website, link: www.Emerson.com/Controlinc.
Use the procedure to download M250_502.abm rmware to Slot 1
Coprocessor module.
2.2 Congure Controlinc Network Master to Communicate with XTE3000 Actuators
1. No change to the number of actuators in the loop.
2. No change to the Scanlist.
3. Edit Device Type.
In order for Controlinc to recognize XTE3000 actuators, change Device Type to 7.
On Touch Panel go to Main Menu, Figure 9.
Figure 9
6
Replacing Actuators with XTE3000 in Existing Network
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 10
Section 2: Replacing Actuators with XTE3000 in Existing Network
July 2020
Select Device Type, Figure 10.
Click Device Type
Figure 11
Enter security code, default 999.
Enter Device Type 7 for all XTE3000 actuator, Figure 11.
Only change the address that needs to be changed
Click Write and wait for 5 seconds then Read to verify it is written.
Cycle Network Master power.
Replacing Actuators with XTE3000 in Existing Network
7
World Area Conguration Centers (WACC) offer sales support, service,
inventory and commissioning to our global customers.
Choose the WACC or sales ofce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065
USA
T +1 281 477 4100
Av. Hollingsworth
325 Iporanga Sorocaba
SP 18087-105
Brazil
T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road #01-02 Singapore 629361
T +65 6777 8211
No. 1 Lai Yuan Road Wuqing Development Area
Tianjin 301700 P. R. China T +86 22 8212 3300
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone Dubai
T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia
T +966 3 340 8650
24 Angus Crescent
Longmeadow Business Estate East
P.O. Box 6908 Greenstone
1616 Modderfontein Extension 5
South Africa T +27 11 451 3700
EUROPE
Holland Fasor 6
Székesfehérvár 8000
Hungary T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
www.emerson.com
VCIOM-15629-EN ©2020 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...