M250 Controlinc Network Master
Bettis XTE3000 Integration Procedure
Installation Instructions
VCIOM-15629-EN Rev. 0
July 2020
Notes
July 2020
Installation Instructions
VCIOM-15629-EN Rev. 0
This page intentionally left blank
Installation Instructions
VCIOM-15629-EN Rev. 0
Table of Contents
Section 1: Adding XTE3000 Actuators into Existing Network
1.1 Update Firmware in Slot 1 Coprocessor Module ............................................1
1.2 Congure Controlinc Network Master to Communicate with
XTE3000 Actuators ....................................................................................... 1
Section 2: Replacing Actuators with XTE3000 in Existing Network
2.1 Update Firmware in Slot 1 Coprocessor Module ............................................6
2.2 Congure Controlinc Network Master to Communicate with
XTE3000 Actuators ....................................................................................... 6
Table of Contents
July 2020
Table of Contents
i
Notes
July 2020
Installation Instructions
VCIOM-15629-EN Rev. 0
This page intentionally left blank
Installation Instructions
VCIOM-15629-EN Rev. 0
!
Failure to follow instructions for proper installation may result in errant information
being displayed.
WARNING
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
Section 1: Adding XTE3000 Actuators
into Existing Network
(Number of actuators increases)
1.1 Update Firmware in Slot 1 Coprocessor Module
• Obtain rmware le "M250_502.abm" and "Controlinc Network Master Firmware
Download Procedure" from Emerson website, link: www.Emerson.com/Controlinc.
• Use the procedure to download M250_502.abm rmware to Slot 1
Coprocessor module.
1.2 Congure Controlinc Network Master to
Communicate with XTE3000 Actuators
1. Update number of actuators in the loop.
— On Touch Panel go to Main Menu, Figure 1.
Figure 1
Adding XTE3000 Actuators into Existing Network 1
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
— Select System Setup, Figure 2.
Figure 2
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 3
— Enter security code default 999, Figure 3.
Adding XTE3000 Actuators into Existing Network2
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 4
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
— Change number of actuators on the network, Figure 4.
Change number
of devices on the
network
— Click Write and wait for 5 seconds, then Read to verify it is written.
2. Edit Scanlist
— On the Main Menu, refer to Figure 1 above.
— Select the Scanlist, Figure 5.
Figure 5
Scanlist
Adding XTE3000 Actuators into Existing Network 3
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
— Enter security code default 999, refer to Figure 3 above.
— Edit the Scanlist, Figure 6.
Figure 6
Installation Instructions
VCIOM-15629-EN Rev. 0
Edit Scanlist
— Click Write and wait for 5 seconds then Read to verify it is written.
3. Enter Device Type
In order for Controlinc to recognize XTE3000 actuators, set Device Type 7.
— On the Main Menu, refer to Figure 1 above.
— Select Device Type, Figure 7.
Figure 7
Click Device
Type
Adding XTE3000 Actuators into Existing Network4
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 8
Section 1: Adding XTE3000 Actuators into Existing Network
July 2020
— Enter security code, default 999, refer to Figure 3 above.
— Enter Device Type 7 for XTE3000 actuators, Figure 8.
Only change
the address
that needs to
be changed
— Click Write and wait for 5 seconds then Read to verify it is written.
— Cycle Network Master power.
Adding XTE3000 Actuators into Existing Network 5
Section 2: Replacing Actuators with XTE3000 in Existing Network
July 2020
Installation Instructions
VCIOM-15629-EN Rev. 0
Section 2: Replacing Actuators with
XTE3000 in Existing Network
(Number of actuators stays the same)
2.1 Update Firmware in Slot 1 Coprocessor Module
• Obtain rmware le "M250_502.abm" and "Controlinc Network Master Firmware
Download Procedure" from Emerson website, link: www.Emerson.com/Controlinc.
• Use the procedure to download M250_502.abm rmware to Slot 1
Coprocessor module.
2.2 Congure Controlinc Network Master to
Communicate with XTE3000 Actuators
1. No change to the number of actuators in the loop.
2. No change to the Scanlist.
3. Edit Device Type.
In order for Controlinc to recognize XTE3000 actuators, change Device Type to 7.
— On Touch Panel go to Main Menu, Figure 9.
Figure 9
6
Replacing Actuators with XTE3000 in Existing Network
Installation Instructions
VCIOM-15629-EN Rev. 0
Figure 10
Section 2: Replacing Actuators with XTE3000 in Existing Network
July 2020
— Select Device Type, Figure 10.
Click Device
Type
Figure 11
— Enter security code, default 999.
— Enter Device Type 7 for all XTE3000 actuator, Figure 11.
Only change
the address
that needs to
be changed
— Click Write and wait for 5 seconds then Read to verify it is written.
— Cycle Network Master power.
Replacing Actuators with XTE3000 in Existing Network
7
World Area Conguration Centers (WACC) offer sales support, service,
inventory and commissioning to our global customers.
Choose the WACC or sales ofce nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway
Houston TX 77065
USA
T +1 281 477 4100
Av. Hollingsworth
325 Iporanga Sorocaba
SP 18087-105
Brazil
T +55 15 3413 8888
ASIA PACIFIC
No. 9 Gul Road
#01-02 Singapore 629361
T +65 6777 8211
No. 1 Lai Yuan Road
Wuqing Development Area
Tianjin 301700
P. R. China
T +86 22 8212 3300
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at
info.actuationtechnologies@emerson.com
MIDDLE EAST & AFRICA
P. O. Box 17033
Jebel Ali Free Zone
Dubai
T +971 4 811 8100
P. O. Box 10305
Jubail 31961
Saudi Arabia
T +966 3 340 8650
24 Angus Crescent
Longmeadow Business Estate East
P.O. Box 6908 Greenstone
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
www.emerson.com
VCIOM-15629-EN ©2020 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
All other marks are property of their respective owners.
The contents of this publication are presented for information purposes
only, and while effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding
the products or services described herein or their use or applicability.
All sales are governed by our terms and conditions, which are available
on request. We reserve the right to modify or improve the designs or
specifications of our products at any time without notice.