Emerson Liebert IntelliSlot Relay Card User Manual

INTELLISLOT
MONITORING
USER MANUAL
Interface Card for
Relay Contacts
CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . 1
NSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . 2
3.0 P
IN CONFIGURATION. . . . . . . . . . . . . . . . . . . . 4
4.0 J
UMPER SETUP . . . . . . . . . . . . . . . . . . . . . . . 5
5.0 C
ONTACTING TECHNICAL SUPPORT . . . . . . . . . 6
TABLES
Table 1 Relay contact card pin configuration. . . . . 4
Table 2 Jumper connections . . . . . . . . . . . . . . . . . . 5
i
ii
Introduction

1.0 INTRODUCTION

The Liebert Intellislot™ Interface for Relay Contacts card provides contact closures for remote monitoring of alarm conditions in your Liebert UPS. Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the easy-to-install card integrates with other relay contact monitoring systems.
This advanced power-management device is specially designed to function only in the Liebert Intellislot port of the following supported UPS units:
•Nfinity™
•Liebert NX™
•PowerSure PSI™
In addition, the RS-232 port on the UPS remains active with the card installed, allowing more sophisticated monitoring with Liebert MultiLink™ software.
On supported units, the inverter shut-off command can be controlled from the computer directly connected to the UPS (via the factory-installed DB9 connector) and will conserve battery power after the workstation shutdown is completed.
The Intellislot Interface for Relay Contacts card is rated for 24 VAC/DC at 1A.

Inspecting Shipment on Receipt

Upon accepting shipment, please inspect the product for any damaged or missing parts. If damage is observed, call Liebert at 1-800-222-5877 and select the Warranty Support option from the menu. If components are missing, contact your sales representative for replacement.
Items included with the shipment are:
• Intellislot Interface for Relay Contacts card protected by an anti-static bag
• Hardwire Adapter board
• User manual
• UPStation GXT™
• UPStation GXT2™
1
Installation

2.0 INSTALLATION

Parts and Tools Required

• Intellislot Interface for Relay Contacts card and required cable assembly
• #2 (medium) Phillips or small flat-head screwdriver

Instructions

1. Turning off the UPS prior to installation is suggested, although not required.
2. Locate the Intellislot port on the UPS. The Intellislot port is on the rear of some
units (GXT, Nfinity and PowerSure PSI); on the Liebert NX, the port is inside the front door. Refer to your UPS user man­ual for port location and orientation.
3. Remove the two retaining screws from the Intellislot port cover plate on the UPS.
NOTE: Save the screws for re-assembly (described in Step 5).
4. The card and slot are keyed to insert in one position only. Initially, the card should slide in freely as you carefully align screw holes. As you feel it click into place, press firmly to ensure solid seating in the slot.
CARD AND SLOT ORIENTATION
INTELLISLOT PORT ON A UPS
Remove screws
CorrectIncorrect
5. Using the screwdriver, secure the card to the UPS chassis with the two retaining screws. Make sure the screws are snug, not tight, to avoid damage to the device.
2
Installation
6. Select either interface Option 1 or 2 below (also see Step 7 and 3.0 - Pin Configuration).
Option 1: Hardwire (terminal block pins) - Use these
guidelines for terminal block specifications:
Acceptable
Wire Size
30-16 AWG
Wire Strip
Length
0.24-0.28 in. (6-7mm)
Recommended
Tightening Torque Screw
1.73 lb-in
(2 kgf-cm)
M2
Option 2: DB25 pins
a. Disconnect the Hardwire
Remove screws
Adapter board by removing the two mounting screws, as shown at right.
b. Pull the Hardwire Adapter
board away from the Relay Card.
Hardwire Adapter board
7. Configure the terminal block or DB25 pins, depending on
which interface option you chose in Step 6 (see figure below and Table 1 in 3.0 - Pin Configuration).
TERMINAL BLOCK PINS (Option 1)
Hardwire Adapter board
Pin numbering
14
DB25 PINS (Option 2)
Intellislot card
Pin numbering
13
25
1
11
1
24
See Table 1 for configuration of terminal block & DB25 pins.
3
14
Pin Configuration

3.0 PIN CONFIGURATION

Table 1 Relay contact card pin configuration

Terminal
Block
DB25
Pin
Pin Function Operation
1 1 UPS Fault Closed if no UPS failure* —2 Not Used —3 Not Used
4 4 UPS Fault Closed if UPS fails*
5 5 Summary Alarm**
6 6 Summary Alarm**
77
—8 Not Used
9 9 Common - Low Battery 10 10 Low Battery Closed if battery is OK
11 11 Low Battery
12 Not Used — 13 Not Used
14 14
15 15 On UPS Closed if ON UPS (inverter) power*
16 16 On Battery
17 17
18 18 On Battery
19 Not Used — 20 Not Used — 21 Not Used — 22 Not Used — 23 Not Used 24 24 On Bypass Closed if ON BYPASS* — 25 Not Used
* Feature not available on PSI products
** A Summary Alarm occurs when any of the following conditions exists:
• Utility power is out of the accepta ble range (voltage and/or frequency).
• UPS is in BYPASS MODE (load not on Inverter power).
• UPS battery is LOW (<2 minutes of battery power remaining).
• UPS fault has occurred.
Signal Ground (for UPS
Any Mode Shutdown)
UPS Any Mode
Shutdown (short to pin 7)
Common - UPS Fault,
Summary Alarm, On UPS,
On Battery, On Bypass
Closed if SUMMARY ALARM**
Closed if no alarm conditions
are present*
Closed if LOW BATTERY
point occurs.
Turn UPS output OFF
when connected to pin 7*
Closed if ON BATTERY power
(Utility failure)
Closed if not ON Battery power
(Utility OK)
4
occurs*
Jumper Setup

4.0 JUMPER SETUP

Refer to Table 2 and the figure below for jumper setup.

Table 2 Jumper connections

# Connection Description
JP01
JP02
Pin 9
to
Pin 17
Pin 7
to
Pin 17
Allows all relay COMMONS to be tied together.
Allows all relay COMMONS and the ANY MODE SHUTDOWN GROUND to be tied together.
NOTE: This jumper should be removed if there is any external voltage source that may intentionally or inadvertently be connected to the DB25 pins.
Jumper JP01
Jumper JP02
5
Contacting Technical Support

5.0 CONTACTING TECHNICAL SUPPORT

Liebert has a team of specially trained technicians waiting to quickly assist you with any installation or troubleshooting problems.
Refer to the back of this manual for the Technical Support phone number.
To successfully diagnose your individual problem, our technicians may require the following installation site and system information. Please have it available when you call.
INSTALLATION SITE
Company Name:
Street Address:
City:
State / Principality:
ZIP / Postal Code:
Country:
INSTALLATION SITE CONTACT
Name of Contact:
Phone Number:
Fax Number:
E-Mail Address:
Fax Number:
6
INTELLISLOT
The Company Behind the Products
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
• Environmental systems—close-control air conditioning from 1 to 60 tons
• Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
• Integrated systems that provide both environmental and power protection in a single, flexible package
• Monitoring and control—from systems of any size or location, on-site or remo te
• Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2005 Liebert Corporation All rights reserved throughout the world. Specifications subject to change withou t notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23210 (2/05) Rev. 1
MONITORING
USER MANUAL
Technical Support/Service
monitoring@liebert.com
Outside the US: 614-841-6755
Outside the US: 614-841-6755
powertech@liebert.com
Environmental Systems
Outside the United States
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Fax: +39 049 5841 257
23F, Allied Kajima Bldg.
Web Site
www.liebert.com
Monitoring
800-222-5877
Single-Phase UPS
800-222-5877
upstech@liebert.com
Three-Phase UPS
800-543-2378
800-543-2778
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
+39 049 9719 111
138 Gloucester Road
Fax: +852 2 831 0114
Italy
Asia
Wanchai
Hong Kong
+852 2 572 2201
Loading...