Emerson Liebert ICOM-DO User Manual

Page 1
Infrastructure Management & Monitoring For Business-Critical Continuity™
Liebert® iCOM-DO
User Manual
Page 2
Page 3
TABLE OF CONTENTS
1.0 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.1 Retrofit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.1.1 System Wiring—All Liebert iCOM Controllers . . . . . . . . . . . . 2
3.0 CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.1 DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2 Diagnostic LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3 Piezoelectric Horn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.0 OUTPUTS - STATUS AND ALARMS. . . . . . . . . . . . . . . . . 5
FIGURES
Figure 1 Typical system configuration . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 ELV wiring for Liebert iCOM-DO . . . . . . . . . . . . . . . . . . . 3
TABLES
Figure 3 Typical system configuration . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 4 ELV wiring for Liebert iCOM-DO . . . . . . . . . . . . . . . . . . . 3
Page 4
ii
Page 5
1.0 INTRODUCTION
Dry-Contact Discrete Outputs to:
BMS Interface
Alarm Panel
Autodialer , etc.
2-Wire Connection Per Alarm
Liebert Precision Cooling Unit
Liebert iCOM-DO Interface Card
The Liebert iCOM Discrete Output interface card provides dis­crete outputs for Liebert Precision Cooling units equipped with a Liebert iCOM control. Operating status is monitored and critical alarms are communicated via contact closure. Any alarm monitor, I/O panel, autodialer or monitoring system can be used to monitor your Liebert unit.
The Liebert iCOM-DO card is available as a factory-installed option or in a kit for field-retrofit to Liebert Precision Cooling units equipped with the Liebert iCOM control.
Figure 1 Typical system configuration
Introduction
Table 1 Specifications
Electrical Requirements
Voltage 24VAC or 24VDC, ±20% 50/60 Hz, Single Phase
Power 10W maximum
Environmental Conditions, °C (F)
Operating
Temp.
Storage Temp. -20 to 70 (-4 to 158)
Humidity: 10% to 95% RH (non-condensing)
Dimensions, mm (inches)
Card Only 178 x 102 x 38 (7.0 x 4.0 x 1.5)
Shipping 248 x 178 x 64 (9.75 x 7.0 x 2.5)
Weight, kg (lb)
Net 0.1 (0.2)
Shipping 0.6 (1.3)
Compatibility
Discrete Outputs
Precision Cooling units with Liebert iCOM control and software version # PA1.04.022 STD or newer
16 Form-C Contact Closures (SPDT Relays, energize to alarm) Rating: 1A @ 30VDC; 0.46A @ 65 VDC; 0.46 A @ 150VAC 16-24 AWG (1.5mm
5 to 55 (41 to 131)
2
- 0.25mm2)wiring
1
Page 6
2.0 INSTALLATION
As a retrofit kit, the Liebert iCOM-DO is secured to a metal mounting plate. The mounting plate is then attached to a flat metal surface in the extra low voltage (ELV) section of the Lie­bert unit.
If the Liebert iCOM-DO was ordered as a factory-installed option, proceed to 3.0 - Configuration.
2.1 Retrofit Installation
Position the Liebert iCOM-DO in the low voltage/control cav­ity of the Liebert Precision Cooling unit. Use three #8 x 3/8" sheet metal screws to attach the mounting plate to the Liebert Precision Cooling unit.
2.1.1 System Wiring—All Liebert iCOM Controllers
Two wiring harnesses are included with the retrofit kit, one for the power connection and one for CAN communication. Refer to Figure 2 for details on routing the wiring.
Installation
Power Connection
The harness supplied with the Liebert iCOM-DO interface card (P/N 159084G1) is equipped with three connectors, one at either end of the harness and one in the middle. The harness taps power from the 24VAC input to the control board of the Liebert Precision Cooling unit.
To connect this power to the Liebert iCOM-DO:
1. Locate the connector containing the two red wires plugged into P43 on the control board and unplug it. Reconnect it to the connector in the middle of the supplied harness.
2. Plug one end of this harness into P43 on the control board and the other end into TB100 of the Liebert iCOM-DO.
NOTICE
Risk of improper wiring. Can cause equipment damage. Do not tap power from the auxiliary 24VAC Terminals
T5/G5 on the Liebert iCOM. Powering from this source might damage the controller and interface card.
Communication Connection
The second wiring harness provided (P/N 197975G1) has a connector fitted at either end and is the communications con­nection between the unit microprocessor and the Liebert iCOM-DO.
2
Page 7
To put it in the system:
Connect 24VAC power from P45 on the fuse board to P43 on the unit control board
Connect CAN Bus to P66 or P67 on the back of Liebert iCOM control
Route CAN Bus communications from P999 on the Liebert iCOM-DO board to P66 or P67 on the back of the Liebert iCOM control
Route 24VAC power from P43 on the cooling unit control board to TB100 on the Liebert iCOM-DO board
Liebert iCOM-DO board
Liebert Precision Cooling unit control board
Fuse Board
Liebert
iCOM
control
1. Connect the RJ-type connector to the Liebert iCOM control board at either the P66 or P67 connection if unit is equipped with a small display. If unit is equipped with a large display, connect the RJ-type connector to the CAN connector on the back of the large display.
2. Connect the MTA-style connector of the wire harness to TB102 of the Liebert iCOM-DO interface card.
Figure 2 ELV wiring for Liebert iCOM-DO
Installation
3
Page 8
3.0 CONFIGURATION
Configuration
The Liebert iCOM-DO can function with either Liebert SiteLink
®
or Liebert IntelliSlot® monitoring cards. The Lie­bert iCOM-DO outputs can be configured only from the large Liebert iCOM display. The small Liebert iCOM display cannot be used to configure the Liebert iCOM-DO outputs. Refer to the Liebert iCOM manual, SL-18835, for details. The docu­ment is available at Liebert’s Web site: www.liebert.com
3.1 DIP Switch Settings
The Liebert iCOM currently supports one connected Liebert iCOM-DO. The Liebert iCOM-DO is configured at the factory with all switches in the OFF position (default is OFF). No DIP switch changes are necessary.
The Liebert iCom control uses the default address and will automatically detect the Liebert iCOM-DO when it is con­nected. Refer to the Liebert iCOM manual for details.
3.2 Diagnostic LEDs
LEDs are provided on the interface card to provide informa­tion for diagnostic purposes. The following table summarizes their indications:
Table 2 Diagnostic LED indications
LED Identifier Description
DS1 CAN Receive Active
DS2 CAN Transmit Active
DS3 +12V Isolated Power On
DS4 24VAC or 24VDC Power Supply On
DS5 +5V Logic Power On
3.3 Piezoelectric Horn
The jumper, P5, located adjacent to the piezoelectric buzzer, is used to enable or disable operation of the audible alarm. The card ships with the buzzer disabled. With the jumper connect­ing the two pins of P5, the audible alarm is enabled. The buzzer will be activated whenever there is an alarm for TB1-TB15.
NOTE
The buzzer should be enabled only for use during troubleshooting.
4
Page 9
Outputs - Status and Alarms
4.0 OUTPUTS - STATUS AND ALARMS
A three-position screw terminal block is provided for each Form-C contact closure output. The wiring connection is uni­form for all 16 outputs:
Position 1: Common Position 2: Normally Closed Position 3: Normally Open
Position 1 is the left-most connection, and is marked by a tri­angular symbol on the circuit board. The outputs are not supervised (except as noted below); thus, the N.O. contact would be closed only upon an active/alarm condition.
Refer to Table 3 for the standard mapping of status and alarms. The output terminal block (TB) for each alarm output is configurable. For details, refer to the Liebert iCOM manual, SL-18835, available at Liebert’s Web site: www.liebert.com
NOTE
The top of the screw terminals cannot be used to obtain contact when using a meter to verify the status of a contact closure. The meter must contact the terminal block in the openings where the wires are inserted.
Table 3 Standard mapping of status and alarms
Terminal Block Description Liebert iCOM
TB1 Cooling Status
TB2 Heating Status
TB3 Humidifying Status
TB4 Dehumidifying Status
TB5 High Temperature
TB6 High Humidity
TB7 Low Temperature
TB8 Low Humidity
TB9a High Head Pressure C1
TB9b High Head Pressure C2
TB10 Loss of Airflow
TB11 Change Filters
TB12 Water Detected/ Customer Alarm 1
TB13 Customer Alarm 2
TB14 GLYCOOL Status
TB15 Unit On
5
Page 10
Outputs - Status and Alarms
6
Page 11
Page 12
Ensuring The High Availability Of Mission-Critical Data And Applications.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is the registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
The global leader in enabling Business-Critical Continuity™.
AC Power Systems
Connectivity
DC Power Systems
Racks & Integrated Cabinets
Embedded Computing
Embedded Power
Power Switching & Control
Precision Cooling
Outside Plant
EmersonNetworkPower.com
Services
Surge Protection
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877 Liebert.monitoring@emerson.com Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877 upstech@emersonnetworkpower.com Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378 powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778 Outside the United States 614-888-0246
Emerson Network Power.
Infrastructure Management & Monitoring
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
©2010 Emerson Electric Co.
SL-28096_REV1_07-10
Loading...