Emerson HD1405 User Manual

Page 1
Part No. SP6551 Printed in Canada
CAUTION: READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLATION.
SAVE THIS OWNER’S MANUAL FOR FUTURE REFERENCE.
Model No.
HD14050
HD1405 Evaporative Console Humidifier Owner’s Manual
SP6551 manual - 71238 7/12/05 1:56 PM Page 1
Page 2
Safety Signal Words
DANGER: means if the safety information is
not followed someone will be seriously injured or killed. WARNING: means if the safety information is not followed someone could be seriously injured or killed. CAUTION: means if the safety information is not followed someone may be injured.
1. To reduce the risk of fire or shock hazard, plug humidifier directly into a 120V, A.C. electrical outlet. Do not use extension cords.
2. Keep the electric cord out of traffic areas. To reduce the risk of fire hazard, never put the electric cord under rugs, near heat registers, radiators, stoves or heaters.
3. Always unplug the humidifier before mov­ing it, removing the fan assembly section, before cleaning, or whenever the humidifi­er is not in service.
4. Keep the humidifier clean.
5. Do not put foreign objects inside the humidifier.
6. Never use your humidifier while any part is missing or damaged in any manner.
7. To reduce the risk of electrical hazard or damage to humidifier, do not tilt, jolt or tip humidifier over while unit is running.
8. To reduce the risk of damage to humidifi­er, unplug humidifier when water bottles are empty or when the humidifier is not in use.
9. To reduce the risk of accidental electrical shock, do not touch the cord or controls with wet hands.
10. Note the warning label shown below.
WARNING: To reduce the risk of fire, electric shock, or injury always unplug before filling, servicing or cleaning.
GENERAL SAFETY INSTRUCTIONS
2
Limited Warranty
All products covered by this Owner’s Manual are warranted against defects in workmanship and materials for one year from the date of sale except for motors, which are warranted for two years. This warranty does not apply to damage from accident, misuse or alteration nor where the connected voltage is more than 5% above the nameplate voltage, nor to the equipment improperly installed or wired or maintained in violation of this Owner’s Manual. No other written or oral warranty applies. No employee, agent, dealer or other person is authorized to give any warranties on behalf of Emerson. The customer shall be responsible for all costs incurred in the removal or reinstallation and shipping of the product for repairs. Within the limitations of this warranty, inoperative units should be returned, with a copy of the sales receipt, freight prepaid to a local repair service center and we will repair or replace, at our option, at no charge to you with return freight paid by Emerson. It is agreed that such repair or replacement is the exclusive remedy available from Emerson and that Emerson Is Not Responsible For Damages Of Any Kind, Including Incidental And Consequential Damage. Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above exclusion or limitation may not apply to you. The warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province.
Sales receipt required as proof of purchase for warranty claims.
SP6551 manual - 71238 7/12/05 1:56 PM Page 2
Page 3
3
Know Your Humidifier
Controls
Humidity Light
Fill Light
Bottles
Fan Assembly
Filters:
Replacement
No. HDC-12
or HDC12C
Control Panel Cover & Pivoting Lid
Removed for Clarity
Filter Housing
Description HD1405
Gallon Output/24 hrs.* 14 Litre Output / 24 hrs.* 53 Capacity of Bottles (U.S. Gallons) 2-3/8 Gallons Each Capacity of Bottles (Litres) 9 Litres Each Sq. Ft. Coverage* 2,900 Fan Speeds 3 Number of Filters 4 Pack (HDC-12) or (HDC12C) Fill Light Indicator Yes Desired Humidity Indicator Yes Auto Humidistat Yes Auto Shut Off Yes Manual Dryout Yes (See Page 7) Controls Rotary CUL Listed Yes Volts 120 A.C. Hertz 60 Amps 2.88 Watts 165
* Based on an area with average insulation and an 8 foot ceiling
ANSI/AHAM HU-1-1997, SEC. 8.1
SP6551 manual - 71238 7/12/05 1:56 PM Page 3
Page 4
Humidifier Operations
Your new Emerson humidifier is designed to satisfy home humidity requirements through the principle of evaporation of water into the air.
After water is added to the bottles and posi­tioned in the humidifier, the filters begin to soak up the water and become totally saturat­ed in approximately 30 minutes. Air is drawn in from the rear of the humidifier and through the filters by means of two circulation fans. As air passes through the filters, moisture is absorbed into the air and then released through the top of the humidifier. This moist air is released in the form of vapor. No water droplets will enter the home. All evaporation into the air takes place in the humidifier, which means that the residue left by evaporating water is not passed into the home, but remains in the filter.
CAUTION: Use only liquid EPA Registered Bacteriostat available from your local retail store. Under no circum­stances should you use water treatment products for Roto belt or Ultrasonic humidifiers.
inside your humidifier and follow the instruc­tions of this owner’s manual for proper usage. The packaging material is located under the fan assembly. Remove the pack­aging material and discard.
Humidified Air is
Then Released
Through the Top
Dry Air Enters Through the Rear
CAUTION: Keep your humidifier clean. While humidifiers do not cause colds, some studies suggest that dirty humidi­fiers can cause cold-like symptoms in some people. To avoid this, clean your humidifier weekly with cleaners specifi­cally recommended for evaporative humidifiers.
Unpacking & Assembly
Your new Emerson humidifier is completely assembled for you to use. Remove the bag pack containing two plastic caster pads from top of humidifier and retain for future use if required. See Step 1 on page 5 for instruc­tions. Remove the packaging material from
Electrical Hook-Up
Locate nearest 120V A.C. wall socket in the location desired, preferably on inside wall. With the humidifier in the desired location, route the electrical cord safely so no one will trip or upset the humidifier. Plug in the electrical cord.
WARNING: To reduce the risk of fire or shock hazard, humidifier should be plugged into a 120V A.C. outlet. Do not use extension cords.
To reduce the risk of electrical shock, this humidifier has a polarized plug (one blade is wider than the other). This plug will fit in a polarized outlet only one way.
If the plug does not fit fully in the outlet, reverse plug. If it still does not fit, contact a qualified electrician to install the proper outlet. Do not change the plug in any way.
4
SP6551 manual - 71238 7/12/05 1:56 PM Page 4
Page 5
5
WARNING: For your own safety, do not use humidifier if any parts are damaged or missing.
Step 1
Place humidifier on a flat level surface in area of house where humidity is needed most, or one which would likely result in moist air being circulated throughout the house such as near a cold air return. Placing the unit level is very important if the humidifier is located on carpeting.
NOTE: This console humidifier contains water bottles. The weight of the bottles in the front of the cabinet may sink the front casters deeper in the carpet. This will keep the water level forward in the cabi­net. The water level float (located at the rear of the cabinet) may not sense the water and the fill light will be on and the unit will not energize. If this happens, the unit will need to be leveled in order for the humidifier to be energized.
To level the humidifier on carpeted surfaces place the included caster pads under the front two casters of the humidifier only. Moist air (humidity) produced will disperse into the whole house, but area closest to unit will have the highest humidity. If the unit is positioned close to a window, condensation may form on the window pane. If this is not appropriate the unit should be repositioned in another location.
Location Instructions
Water Fill
WARNING: To reduce the risk of shock, always unplug humidifier before filling, cleaning, or servicing.
WARNING: To reduce the risk of fire or shock hazard, do not pour or spill water into control or motor area. Close the control cover. If controls get wet, let them dry completely and have unit checked by authorized service person­nel before plugging in.
This humidifier is designed to be used with the two water bottles that are located under the pivoting lid.
NOTE: Due to release of cool, moist air from humidifier, it is best to direct air away from home thermostat and hot air registers. It is best to position humidifier next to an inside wall. Hot air registers and cold air from out­side walls can affect the efficiencies of the controls. Unit should not be placed where warm air from a hot air register blows directly on unit.
Step 2
The humidifier should be positioned with the back (cord exit side), at least 2 inches away from the wall. Air needs to enter through lou­vers in the back of the cabinet in order for the humidifier to operate at peak efficiency.
Water Bottles
Cabinet
Front of Humidifier
Fan Assembly
NOTE: If positioning on carpet, place
caster pads under front casters only
to level (if necessary).
Front of Cabinet
Front Caster
Caster Pad
Carpet Surface
At Least 2" From Wall
Pivoting Lid Removed for Clarity
SP6551 manual - 71238 7/12/05 1:56 PM Page 5
Page 6
Water Fill (continued)
Open the pivoting lid of the humidifier. Remove the water bottles, by lifting them straight up and out of the cabinet.
Notice the water bottles are designed as right and left hand units. Position them in the cor­rect location so the humidifier can function properly. The water bottles should rest in the front of the cabinet. Each Side Fill Cap must be facing the rear of the unit
Each water bottle is designed with a Side Fill Cap that is easily removable. Remove the Side Fill Cap on the side of the water bottle by twisting counterclockwise. Each bottle will hold 2-3/8 gallons (9 litres) of water.
Place the opening of the water bottle under a water faucet (the bottle should fit under a four-inch clearance faucet). Fill with cold water. If necessary, add recommended amount of EPA registered liquid bacteriostat. Do not add solid debris as this could make the valve leak. Install the Side Fill Cap by twisting clockwise. Hand tighten only.
Check for possible leaks by performing the following:
1. Grasp bottle handle and hold the bottle upright over a sink.
2. Press up on valve cap plunger for about one second to let out a little water.
3. Release the plunger.
4.Listen for air bubbles. Look for leaks around Side Fill Cap.
5. If you hear air bubbles or see leaks, retighten Side Fill Cap and repeat steps 1-4.
NOTE: Repeat for other bottle. If either fill cap leaks, water may overflow and leak out of the rear vents of the cabinet.
Wipe off excess water from the bottle. Position the water bottle back into the unit. Grasp the water bottle handle, and lower into the cabinet until the bottle sits on pads at bot­tom of cabinet. The Side Fill Cap must be facing the rear of the cabinet. When posi­tioned properly, the plunger will open and water will flow into the cabinet. The water level will automatically remain at approxi­mately 1/2" until the bottles are empty. The unit is now ready for operation.
Rear of
Humidifier
Valve
Cap Plunger
Pivoting Lid Removed
for Clarity
Side Fill Cap” Should Always
Face Rear
Turn Counterclockwise
to Remove Cap
6
SP6551 manual - 71238 7/12/05 1:56 PM Page 6
Page 7
7
Operating Humidifier Controls
The operating controls of your Emerson evaporative humidifier are located on the top center of the humidifier. The controls are found under the smoked cover, located between the air circulating fans. Lift the con­trol cover by placing your finger in the round cutout and lifting. The cover will stay open. Now you can clearly see the control area. Familiarize yourself with the controls and ref­erence the diagram of the control area for the correct naming used within this manual.
To Operate the Controls
Humidity Control:
Adjust the amount of humidity depending on your needs. The humidifier will turn on and off as required to maintain level of humidity selected. A medium setting (half way between and is recommended, but there are times when a low or high amount of humidity may be preferred. For constant operation of humidifier, turning the control all the way clockwise allows for the maximum amount of humidity to be evaporated into the air continuously.
IMPORTANT: Water damage may result if condensation starts to form on windows or walls. Humidity Control setting should be lowered until condensation no longer forms.
Green Humidity Light
When the selected humidity level is met, the fans will shut off and the green “Desired Humidity” light will illuminate. When more humidity is called for, the fans will turn on and the light will go out.
Air Flow Control
The unit is adjusted from OFF “ ” to high “ ” with a three speed rotary control.
The higher the air flow speed, the more water is evaporated and released into the air. Low speed “ ” is the quietest and is provided for conditions that may not require as high an evaporation rate.
Fill Light
When the unit has a small amount of water left in it, the amber fill light will come on and the unit will automatically shut off.
NOTE: This humidifier is designed so the right bottle as viewed from front empties first. For maximum run time between fills, let both bottles empty completely before refilling.
Manual Dryout
At the end of the humidification season or if you do not plan to run the humidifier for one week or more, you can override the auto­matic shutoff function to completely dry the humidifier cabinet out.
To do this, simply slide the float retainer locat­ed at the back of the humidifier cabinet to the top position of the slot it is located in. This will hold the float in an upward position and the fans will run until you turn the power off.
NOTE: Be sure to position float retainer to the normal operating mode (lowest position in slot) for normal operation.
Below is a diagram of the slot the float retain­er is located in at the back of the cabinet.
TOP POSITION IS FOR MANUAL DRYOUT
BOTTOM POSITION IS FOR NORMAL
OPERATION MODE FLOAT RETAINER SLOT
SP6551 manual - 71238 7/12/05 1:56 PM Page 7
Back of Cabinet
Page 8
Using Your Humidifier
Step 1
Be sure unit is full of water and plugged in.
Step 2
Set air flow control to desired setting.
Step 3
Set Humidity Control to medium position (half way between and )
NOTE: Humidifier should operate with humid­ity control on the recommended medium set­ting. If it does not, the humidity is at a rela­tively high level. To test the unit under this condition, turn Humidity Control all the way clockwise and unit should begin to operate. After the unit has been tested, set Humidity Control to about medium or desired level.
Allow 24 to 48 hours for humidifier to adjust.
If humidity level in home is sufficient, the humidifier will only operate with Humidity Control turned all the way clockwise.
IMPORTANT: Water damage may result if condensation starts to form on windows or walls. Humidity Control setting should be lowered until condensation no longer forms.
1. Position the humidifier at least 2 inches from any wall and away from any heat reg­isters.
2. Do not restrict airflow from entering or exit­ing the humidifier.
3. Use liquid EPA Registered Bacteriostat to retard bacteria growth that may cause odors and may be harmful to your health.
4. Regular cleaning as instructed in “Cleaning Your Humidifier” section of this manual is recommended.
5. Replace the evaporative wicking filters at least once per humidification season or more depending on water conditions in your area.
Operating Tips for Best Performance
Relative Humidity
8
Step 4
If humidifier stops running and the amber Fill Light is not illuminated, the green desired humidity light will illuminate. This means the humidity level is at the normal requirements for that setting or it is adjusting to the home conditions. The table below shows recom­mended indoor humidity levels. The figure below shows approximate relative humidity percentages which correspond to the various settings of the Humidity Control.
-10° F 2° F
10° F
20° F*
-24° C
-18° C
-12° C
-6° C*
20% 25% 30% 35%
When Outdoor Recommended Indoor
Temperature is: Relative Humidity is:
* and above
SP6551 manual - 71238 7/12/05 1:56 PM Page 8
y
t
i
d
i
m
u
H
.
l
e
R
MIN
m
u
H
i
d
.
l
i
e
R
t
MAX
y
R
e
l
.
H
u
m
i
d
i
t
y
Page 9
9
Replacement and Care of Filters
WARNING: To reduce the risk of shock or injury from moving parts, always unplug humidifier before removing or replacing any parts.
CAUTION: To help retard bacteria growth and keep maximum efficiency, the filters should be replaced at least once a season, or more often under hard water conditions. Use Emerson HDC-12 (or HDC12C in Canada) rec­ommended replacement filter.
All filters may be rinsed in clear water only. Take care not to damage paper.
To replace the evaporative wicking filters in your Emerson humidifier, follow the instruc­tions below.
1. Unplug humidifier, and proceed to clean. Before removing the filters, we recom­mend moving the humidifier to an area where floor coverings are not susceptible to water damage, i.e. kitchen or bath areas.
2. Open the pivoting lid and remove water bottles and set aside. Grasp the fan assembly front center and rear center. Lift off and set aside on a clean flat surface. The filter assemblies are now accessible.
3. Lift filter housings out of cabinet and place where you may work on them comfortably. With a soft, absorbent cloth, remove any remaining water or loose mineral deposits not trapped in the filter from the humidifier cabinet.
4. To open filter housing for easy access to filters
a. Deflect the two spring tabs on top of fil-
ter housing. Lift top cover off of the fil­ter housing and set aside.
b. Remove the two filters and dispose of
properly. Clean internal parts of humidi­fier per the “Cleaning Your Humidifier“ section of your owner’s manual.
Spring
Tabs
Pivoting
Lid
Fan
Assembly
Filter
Housing
SP6551 manual - 71238 7/12/05 1:56 PM Page 9
Page 10
10
Replacement and Care of Filters (continued)
c. Install new filters in the filter housing
track with the glue beads of the wicking pad to the inside of the filter housing.
d. Return the top cover of the filter hous-
ing by installing the cover over the fixed tabs on the rear of the lower filter hous­ing and pivoting the cover down over the top of the filters. Snap the cover over the two spring tabs.
e. Replace the filter housing in the cabi-
net. Note: There is a front and back ori­entation. To position the filter housings correctly:
• Be sure that spring tabs of filter hous­ings are towards front of cabinet.
• Align the lower portion of the filter assembly over the six ribs, located at the bottom rear of the humidifier cabi­net.
f. Position fan assembly onto the cabinet.
Make sure the fan venturi (lowest cylin­der section below the fan) is placed inside the filter housing.
g. Replace water bottles.
h. Close the pivoting lid on the fan
assembly.
i. The unit is ready for use or to be stored
away for the next season.
Spring Tabs
Fixed Tabs
Filter Housing
Front of
Humidifier
Rear of
Humidifier
Top Cover
Flat Portion of Filter Housing
Towards Back of Cabinet
Spring Tabs Towards Front of Cabinet
Step 4.e.
Spring Tabs Towards Front of Cabinet
SP6551 manual - 71238 7/12/05 1:56 PM Page 10
Page 11
11
Cleaning Your Humidifier
CAUTION: To reduce the risk of injury, fire or damage to humidifier, use only cleaners specifically recommended for humidifiers. Never use flammable, com­bustible or poisonous materials to clean your humidifier. To reduce the risk of scalds and damage to humidifier, never put hot water in humidifier.
CAUTION: Local water purity may vary from area to area and under certain conditions water impurities and air­borne bacteria may promote the growth of microorganisms in the reservoir of a humidifier.
To retard bacteria growth that may cause odors and be harmful to your health, use only Emerson replacement filters. We also recommend using an EPA registered liquid bacteriostat, and cleaners specifically recommended for evaporative humidifiers available at your local retail store.
NOTE: If it is necessary to use an approved
bacteriostat, follow the directions correctly. The bottles of this unit will hold 2-3/8 gallons or 9 litres of water each.
Step 1
To make cleaning easier, the humidifier cabi­net should be empty and completely dried out. To accomplish this, use the following method:
a. Allow the humidifier to run until the auto-
matic shutoff turns the humidifier “OFF”.
b. Unplug humidifier
WARNING: If humidifier is not un­plugged, fan could start after housing is removed.
Step 2
To Remove Parts
a. Open the pivoting lid and remove water
bottles and set aside. Grasp the fan assembly front center and rear center. Lift
off and set aside on a clean flat surface. The filter housings are now accessible.
b. Before removing the internal parts of the
humidifier cabinet, we recommend moving the humidifier to an area where floor cov­erings are not susceptible to water dam­age, i.e., kitchen or bath area. Lift the filter housing assemblies out of the cabinet and set to the side.
c. Remove the water level float from the
humidifier cabinet by pinching the float retainer at the back of the cabinet to release it. The cabinet should be empty before cleaning. The cabinet consists of the lower areas of the humidifier where the filters are during normal operation time.
d. Empty cabinet of any remaining water.
e. Proceed to “Bi-Weekly Maintenance” or
“End of Season Maintenance” then contin­ue as described below.
f. Remove old filters and dispose of properly
as described on page 9 and 10.
Step 3
Install new filters (use Emerson Replacement Filters) into the location where the old filters were positioned. Install water level float at back of cabinet. Ensure that you slide the float retainer down to the lowest position in slot at back of cabinet. (See dia­gram of slot below). Install the filter housings with the new filters into the correct location. Position the fan assembly on top of the cabi­net and return the humidifier to the desired location for use.
Refill humidifier bottles with fresh cool water. Plug the unit into a 120 volt A.C. power outlet and set the controls per the “Operating Humidifier Controls” section of this manual.
BOTTOM POSITION IS FOR NORMAL OPERATION MODE
FLOAT RETAINER SLOT
SP6551 manual - 71238 7/12/05 1:56 PM Page 11
Back of Cabinet
Page 12
12
Bi-Weekly Maintenance
Removing Scale
1. Fill the humidifier cabinet with one 8 oz. cup of undiluted white vinegar. Let solu­tion stay 20 minutes.
2. Clean all interior surfaces with soft brush. Dampen a soft cloth with undiluted white vinegar and wipe out the humidifier cabi­net to remove scale.
3. Rinse thoroughly with clean warm water to remove scale and cleaning solution before disinfecting the humidifier cabinet.
4. Dust the fan assembly and outside sur­faces with a soft cloth only.
Disinfecting Humidifier Cabinet and Bottles
1. Fill humidifier cabinet with 1 teaspoon chlorine bleach in 1 gallon of water. Let solution stay 20 minutes, swishing every few minutes. Wet all surfaces normally exposed to water.
2. Empty humidifier cabinet after 20 min­utes. Rinse with water until bleach smell is gone. Allow unit to dry out completely.
3. Water bottles should be cleaned in same manner.
End of Season Maintenance
1. Follow bi-weekly maintenance instructions at end of humidification season.
2. Remove and throw away filters.
3. Let humidifier dry completely before stor­ing. Do not store with water inside cabi­net.
4. Store in cool, dry location.
5. Install new filters into a clean humidifier before next season begins.
6. “Bi-Weekly Maintenance” is also recom­mended if you do not plan to run the humidifier for one week or more.
Cleaning Your Humidifier (continued)
SP6551 manual - 71238 7/12/05 1:56 PM Page 12
Page 13
13
Troubleshooting
CAUTION: Use only approved EPA Registered liquid bacteriostat available from your local retail store. Use of other water treatment products may damage the filter elements. Under no circumstances should you use water treatment products designed for Rotobelt or Ultrasonic humidifiers.
PROBABLE CAUSE
• No power.
• Speed control in off position.
• Selected humidity level has been established.
• Float is not free.
• Float retainer positioned in “Manual Dryout” position (top slot at back of cabinet).
• Dirty filters.
• Right bottle contains water.
• Unit is not set up on a level surface. (Float will not sense water at the rear of the cabi­net.)
• Bottle is not seated properly.
• Air is entering water bottles.
• This is normal.
TROUBLE
Unit will not run and no control panel lights are illuminated.
Power source OK and fans still not operating.
Unit will not shut off.
Slow evaporation of water.
Left bottle not emptying and/or Fill indicator turns on before bottles are emp­tying.
Neither bottle is emptying.
Bottles continue to empty.
A small amount of water in cabinet and fill light is on.
REMEDY
• Check 120 volt power source.
• Turn speed control clockwise.
• Raise humidistat setting if desired.
• Free float from obstruction
• Slide float retainer down to lowest position in slot at back of cabinet.(See diagram on page 11.)
• Change to fresh filters.
• The humidifier is designed so the
right bottle empties first. Continue to run until fill light comes on.
• Position unit level. (Some carpet
padding may allow unit to sit lower in front than rear with additional weight of water bottles in the front of the cabinet.) Install caster pads under front casters. (See owner’s manual.)
• Check the position of bottles.
Reposition so that bottle cap plunger (stem) is depressed by post in bottom of cabinet.
• Ensure Side Fill Caps and valve
assembly caps are tight.
• Check for leak in water bottles.
• Ensure gasket for each cap is in
place.
• Approximately one inch of water
remains in the cabinet after unit shuts off. Position float retainer in “Manual Dryout” position to completely dry out. See owner’s manual (if applicable).
FOR TECHNICAL HELP
If in the USA call 1-800-654-3545
If in Canada call 1-888-744-4687
SP6551 manual - 71238 7/12/05 1:56 PM Page 13
Page 14
14
Repair Parts
Parts List for MoistAir Humidifier
Model No. HD14050
28
27
26
25
24
23
28
27
21
26
30
24
23
22
21
20
19
18
14
15
13
31
12
11
33
16
17
3
1
32
8
10
7
5
4
6
9
34
2
SP6551 manual - 71238 7/12/05 1:56 PM Page 14
Page 15
15
Repair Parts
Parts List for MoistAir Humidifier
Model No. HD14050
Always order by part number - Not by key number
Key Part No. Description
No.
1 823884 Cover, Dust
2 829844 Lid, Stationary
3 829841-1 Lid, Pivoting
4 828381 Knob
5 830890 Label, Control
6 826400 Cover, Control
7 823912 Switch, Rotary
8 825858 Light, Fill
9 825858-1 Light, Humidity
10 13805-02 Humidistat
11 823728 Switch, Micro
12 826401 Enclosure, Electronics
13 824101-1 Retainer, Float
14 828200 Float, Water Level
15 824690 Side Fill -Cap
16 828192 Bottle, Left
(Includes Key No's 15 & 18)
17 828726 Bottle, Right
(Includes Key No's 15 & 18)
Key Part No. Description
No.
18 509229-1 Cap, Valve Assembly
19 828998 Cabinet
20 823726 Rail, Kick
21 * * Screw, Pan Hd. Ty “AB” #10 x 3/4
22 828515 Caster, Twin Wheel
23 823849 Support, Filter Lower
24 HDC-12 or
Filter, Evaporative (USA)
HDC12C
Filter, Evaporative (Canada)
25 828197 Support, Upper Filter
26 828534 Support, Motor
27 828115-1 Motor
(Includes mounting hardware)
28 822406-1 Fan
30 828197 Support, Upper Filter
31 824120 Cord w/Plug
32 826367 Retainer, Micro Switch
33 * * Screw, Pan Hd. Type AB #6 x 3/8
34 828920 Pad, Caster (Two)
SP6551 Owner’s Manual (not illustrated)
* Standard Hardware Item - May be purchased locally. † Stock Item - Purchase locally or call 1-800-654-3545 from
the USA or 1-866-808-6500 from Canada to order
NOTE: Any attempt to repair the control assembly or motor may create a hazard unless repair is done by a qualified
service technician.
To order parts call: USA 1-800-654-3545 Canada 1-866-808-6500
SP6551 manual - 71238 7/12/05 1:56 PM Page 15
Page 16
© 2004 Emerson Part No. SP6551 Form No. SP6551 Printed in Canada 11/04
FOR TECHNICAL HELP, CALL
(800) 654-3545 FROM USA OR (888) 744-4687 FROM CANADA
(Please have complete model number)
Emerson Tool Company
For more information about MoistAir® humidifiers visit our website at
www.moistair.com
SP6551 manual - 71238 7/12/05 1:56 PM Page 16
Loading...