Emerson GDESIGN 10003000 A User Manual

Page 1
Operator’s
Non–Automatic Transfer Switches
Manual
DANGER is used in this manual to warn of a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
Series 386
Refer to the outline and wiring drawings provided with the ASCO Series 386 N–ATS for all installation details.
Rating Label
Each non–automatic transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
Identification Label
The identification label on the Transfer Switch includes data for each specific ASCO Series 386. Use the switch only within the limits shown on identification label.
An experienced licensed electrician must install the Non–Automatic Transfer Switch (N–ATS).
TABLE OF CONTENTS
section-page
INSTALLATION 1-1........................
Mounting and Line Connections 1-1.........
Functional Test 1-2, 1-3.....................
SEQUENCE OF OPERATION 2-1...........
TESTING & SERVICE 3-1..................
Preventive Maintenance 3-1................
Transfer Test 3-1..........................
Trouble-Shooting 3-2......................
ADJUSTMENTS 4-1.......................
Sensor Adjustments 4-1...................
How to Change a Setting 4-1...............
OPTIONAL FEATURES 5-1.................
Motor Load Transfer 5-1...................
Load Disconnect 5-1......................
INDEX back of manual.....................
G–design 1000–1200 A sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
381333–086 D
Page 2
Page 3
SECTION 1 INSTALLATION
ASCO 386 Non–Automatic Transfer Switches (N–ATSs) are factory wired and tested. Field installation simply requires mounting and connection of service cables, and auxiliary control circuit s (if required).
Remove the Shipping Skid (large N–ATSs)
For large N–ATSs, open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the wood skid.
Supporting Foundation
The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the switch for all mounting details including door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Mounting
Refer to the Outline and Mounting Diagram provided with the N–ATS; it shows all mounting details and instructions.
NOTICE
Protect the non–automatic transfer switch from construction grit and metal chips to prevent malfunction or shortened life of the N–ATS.
Mount the ASCO 386 vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the switch.
Auxiliary Cable Boxes for 1000 and 1200 A
For G–design 1000 and 1200 ampere sizes, auxiliary cable boxes are required for all (normal, emergency, & load) bottom or top entry. Be sure to install auxiliary cable boxes if both service and load cables are entering through the top or bottom of enclosure. Consult ASCO Power Technologies.
Be sure that the insulator piece is behind the 260 and 400 ampere transfer switches.
insulator backing piece
Figure 1-1. Insulator for E–design 260 and 400 ampere
Controller Ground
The controller is mounted on the cabinet door. The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs). An add-on DIN rail is provided for some optional accessories and is mounted below the controller on the door.
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used betwee n the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provi ded with this Non–Automatic Tra ns f e r Swi tc h.
Read all instructions on the Wiring Diagram and labels affixed to the non–automatic transfer swi tch. Note the control features that are provi ded and review their operation before proceeding.
Insulator Backing Piece for 260 and 400 A
E–design transfer switches rated 260 and 400 ampere are mounted on an insulator backing piece (installed behind the transfer switch). If the transfer switch is removed from the cabinet and then reinstalled, this insulator piece must be placed behind the transfer switch. See Figure 1-1.
1 --- 1
Page 4
INSTALLATION (continued)
Line Connections
A Wiring Diagram is furnished with the ASCO 386 (separate from this manual). Refer to this drawing. All wiring must be made in accordance with the National Electrical Code and local codes.
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine generator starting control in the OFF position. Make sure engine generator is not in operation.
Testing Power Conductors
Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before should be tested to verify that they are not defective or have been damaged during installation.
they are connected, they
Connecting Power Conductors
After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with the switch. Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the switch. B e careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Bus Connections
If bus connection is used, use SAE grade 5 hardware to connect bus to appropriate terminal p lates on the transfer switch. Wipe off bus surfaces before they are joined. If bus is very dirty, gently clean surfaces with a non–flammable solvent. Avoid touching cleaned surfaces.
Do not breathe cleaning solvent vapors.
UseSAEgrade5hardwareandtightentheboltedjointsto thetorquespecifiedinTableA.
NOTICE
The reliability of the connection depends on how clean and how tight the joint is.
Table A. Tightening torque values for bolted joints.
Bolt Diameter
(Grade 5 hardware)
in inches
5/16 12
3/8 20 1/2 50 5/8 95 3/4 155
Continue to 1–ManualOperationTest on next page.
Recommended
Tightening Torque
in foot pounds
Do not run cables behi nd the switch. Cables can be bundled on the right side of the switch. Maintain proper electrical clearance between the live metal parts and grounded metal: ½ inch minimum for 260-400 amperes, 1 inch minimum over 400 amperes.
1 --- 2
Page 5
INSTALLATION (continued)
Functional Test
The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation.
NOTICE
Do these checks in the order presented to avoid damaging the non–automatic transfer switch.
1 – Manual Operation Test
A detachable maintenance handle is provided on the transfer switch for maintenance purpose s only.Manual operation of the switch should be checked before it is energized (operated electrically).
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
1. Selecttheappropriateswitchamperagesize/design and follow the directions for installing the handle:
260 and 400 amp. E–design SeeFigure1-2. Insert the manual handle into the hole in the shaft, left side of the operator.
1000 – 3000 ampere. G–design SeeFigure1-3. Install the hub onto the center operator shaft and insert the manual firmly into the hole in the side of the hub (spring fully compressed).
handle
Figure 1-2. Maintenance handle for E–design 260 and
400 ampere
2. Movethehandleasshowntomanuallyoperatethe Transfer Switch. The switch should operate smoothly without binding. If it does not, check for shipping damage or construction debris.
3. Return the transfer switch to the N (normal) position. Remove manual operator handle (if detachable) and store it on the transfer switch in the place provided.
NOTICE
Verify that the maintenance handle has been removed before proceeding!
Now continue to 2–VoltageCheckson next page.
Emergency contacts
window
indicators
OPEN or CLOSED
Normal contacts
contact position
indicators (left side)
Figure 1-3. Maintenance handle on 1000 – 3000 ampere G design transfer switches.
Grasp handle firmly with both hands
Insert handle into hole (spring fully compressed)
counterclockwise DOWN closes the Emergency source contacts (upper) and opens the Normal source contacts (lower)
1 --- 3
Turn counterclockwise to Emergency.
Turn clock w ise to Normal.
Slide hub onto shaft
clockwise DOWN closes the Normal source contacts (lower) and opens the Emergency source contacts (upper)
Page 6
INSTALLATION (continued)
Functional Test (continued)
2–VoltageChecks
First check nameplate on the transfer switch for rated voltage. It should be the same as the normal and emergency line voltages.
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
1. Close the normal source circuit breaker. The Load Connected To Normal lamp should come on.
2. Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the Transfer Switch normal source terminals.
3. Close the emergency source circuit breaker. (Start the generator, if necessary.)
4. Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the Transfer Switch emergency source terminals.
If necessary, adjust the voltage regulator on the generator according to the manufacturer’s recommenda­tions. The ASCO 386 will respond only to the rated voltage specified on the Transfer Switch nameplate.
5. Check phase rotation; it must be the same as the normal source.
6. Shut down engine-driven generator, if applicable.
7. Close the cabinet door and tighten the screws.
3 – Electrical Operation
This procedure will check the electrical operation of the Non-Automatic Transfer Switch. See Figure 1–4.
Close the transfer switch enclosure door and tighten the screws before you test electrical operation.
Transfer Test
Both normal and emergency sources must be available and above 90% of nominal voltage specified on nameplate.
1. Turn the door-mounted Tr an sfe r Co n tr ol switch clockwise to Tr ans fer To E mer g en c y.
2. The transfer switch will operate to the Emergency position. The Load Connected To Emergency light should come on and the Load Connected To Normal light should go off.
3. Turn the door-mounted Tr an sfe r Co n tr ol switch counterclockwise to Transfer To Normal.
4. The transfer switch will operate back to the Normal position. The Load Connected to Normal light should come on and the Load Connected To Emergency light should go off.
This completes the Functional Test of the ASCO 386 non-automatic transfer switch.
Figure 1–4. Operating Controls.
1 --- 4
Page 7
SECTION 2
SEQUENCE OF OPERATION
Controller Code 1
Refer to Section 5, Optional Accessories for additional control functions.
Refer to Wiring Diagram furnish e d with the ASCO 386. Note Control Features furnished on this switch, and review operation.
Trans fer
Control
Trans fer
To
Normal
Trans fer
To
Emergency
Transfer To Emergency
The sequence for load transfer to the emergency source begins when you turn the door-mounted
Transfer Control switch clockwise to the Tr a n sfer To Emergency position.
When the T ran sfer Control switch is operated to Transfer T o Emergency, the voltage and frequency sensor begins monitoring the emergency source. The sensor will accept the emergency source only when both pickup points. If the emergency source is available immediately, the sensor may accept it as soon as the Tr ans fer Cont rol switch is operated.
When the emergency source is accepted by the sensor, relay ER picks up to transfer the load to the emergency source.
ER relay energizes, the TS coil is energized, the transfer switch operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transfer switch is now supplying the load from the emergency source.
voltage and frequency reach preset
Trans fer
Control
Trans fer
To
Normal
Trans fer
To
Emergency
Retransfer to Normal
The sequence for load retransfer to the normal source begins when you turn the door-mounted Transfer Control switch counterclockwise to the T ransfer To Normal position.
When the Transfer Control switch is operated to T ransfer To Normal, the voltage sensor begins monitoring the normal source.
The SE relay energizes when the sensor accepts the normal source voltage.
SE relay energizes. The TS coil is energized, the transfer switch operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transfer switch is now supplying the load from the normal source again.
The SE relay de–energizes when the Tra n sfe r Control switch is released.
ThetransferswitchwillremainintheNormal position until the Transfer Control switch is operated to the Transfer To Emergency position.
ThetransferswitchwillremainintheEmergency position until the Transfer Control switc h is operated to the Transfer To Normal position.
Note
Activation of standard control features shown in Section 5 will alter the sequence of operation and introduce additional time delays during transfer operations.
2 --- 1
Page 8
SECTION 3
TESTING & SERVICE
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure high reliability and long life for the switch. An annual preventive maintenance program is recommended.
ASCO Services, Inc. (ASI) is ASCO Power Technologies’s national service organization. ASI can be contacted at 1-800-800-2726 for infor­mation on preventive maintenance agreements.
TESTING
Operate the switch at least once a month by following this four-step Electrical Operation Test.
Transfer Switch Test
A. Turn the door-mounted Tra ns f er C on t ro l switch
clockwise to Transfer to Emergency.
B. The transfer switch will operate to the Emergency
position. The Load Connected To Emergency light should come on and the Load Connected to Normal light should go off.
C. Turn the door-mounted Tr a n s fe r Con t ro l switch
counterclockwise to Transfer to Normal.
D. The transfer switch will operate to the Normal
position. The Load Connected to Normal light should come on and the Load Connected to Emergen- cy light should go off.
REPLACEMENT PARTS
Replacement parts are available in kit form. When ordering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch nameplate. Contact your local ASCO Power Technolo­gies sales office or ASI. In the United States call 1–800–800–ASCO (2726).
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps:
Disconnecting the Plugs
1. Observe the position of the transfer switch.
a. If the transfer switch is in the Normal position,
place standby engine starting control in the off position. Then open the emergency source circuit breaker.
b. If the transfer switch is in the Emergency posi-
tion, ope n the normal source circuit breaker. Place the engine starting control in the test or run position.
2. Separate the quick disconnect plugs by squeezing the latches. Do not pull on the harness wires.
Checklist for Yearly Inspection
Hazardous voltage capable of causing shock, burns, or death is used in this switch. Deenergize both Normal & Emergency power sources before performing inspections!
S Clean the switch enclosure. Brush and vacuum
away any excessive dust accumulation. Remove anymoisturewithacleancloth.
S Check the Switch Contacts
switch barriers and check the condition of the contacts. Replace the contacts if they become pitted or worn excessively. Reinstall barriers carefully.
S Maintain transfer switch lubrication.Ifswitchis
subjected to severe dust or abnormal operating conditions, renew factory lubrication on all move­ments and linkages. Relubricate solenoid operator if TS coil is replaced. F or 260–400 A order lubri- cation 625550–001 (Castrol EndurexR 4000 lubri- cant). For 1000–3000 A order lubricant kit 75–100.
S Check all cable connections and retighten them.
.Removetransfer
Reconnecting the Plugs
1. Observe the position of the t ransfer switch.
a. If the transfer switch is in the Normal position,
be sure that the standby engine starting control is still in the off position. The emergency source circuit brea ker still should be open.
b. If transfer switch is in the Emergency position,
normal source circuit breaker still should be open.
2. The harness plugs and sockets are keyed. Carefully align t he plugs with the sockets and press straight in until both latches click.
3. Restore the opposite source as follows:
a. If the transfer switch is in the Normal position,
place the standby engine starting control in the automatic position. Then close the emergency source circuit breaker.
b. If the transfer switch is in the Emergency
position, close the normal source circuit breaker.
3 --- 1
Page 9
TESTING & SERVICE
PROBLEM
(continued)
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the Controller is disconnected.
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
TROUBLE-SHOOTING
Note the ControlFeaturesthat are activated or furnished on the switch and review their operation. Refer to Section 5, Optional Features.
Table 3-1. Trouble-Shooting Checks.
1OPERATION 2VOLTAGE
T ransfer switch does not transfer the load to the emergency source.
T ransfer switch does not transfer the load to the normal source.
Tur n Transfer Control switch clockwise to Transfer to Emergency position.
Tur n Transfer Control switch counterclock­wise to Transfer to Normal position.
1. Open normal and emergency source circuit breakers.
2. Use manual handle to manually operate transfer switch to the opposite source. Remove the handle. See Section 1, Manual Operation.
3. If the transfer switch is in the Emergency position manually start the engine generator and then close the emergency source circuit breaker.
Proceed with care! The ASCO 386 is energized.
CHECK IN NUMERICAL SEQUENCE
Generator ouput circuit breaker must be closed. Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals EA and EC (or EL1 and EL2 for 2 pole switches). * Generator frequency must be at least 57 Hz. *
* These are factory settings.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals NB and NC, NC and NA, and NA and NB (or NL1 and NL2 for 2 pole switches).
Trouble-Shooting Motor Load Transfer (Optional Feature 27) (refer to page 5-1)
3. Turn the TRANSFER TO EMERGENCY control switch clockwise. The load should transfer to
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch powe r terminals; shock, burns, or death could result !
1. Connect a voltmeter (set for twice system phase-to-phase voltage) between Transfer Switch terminals NA and EA.
2. Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0 and about twice system voltage.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASI. In t he United States, call 1–800–800–2726. Furnish the Serial No., B ill of Material (BOM ) No., & Catalog No. from transfer switch nameplate .
emergency source when meter needle is near 0 volts. If t ransfer does not occur, the Motor Load Transfer accessory is not operating.
4. Turn the TRANSFER TO NORMAL control switch counterclockwise. The load should retransfer back to the normal source when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor L oad Transfer accessory is not operating.
5. Disconnect the voltmeter.
3 --- 2
Page 10
SECTION 4 ADJUSTMENTS
F
Sensor Adjustments
Voltage and frequency sensor pickup and dropout points are factory set as specified on the Wiring Diagram. The frequency setting can be set for 50 or 60 Hz.. To change this setting, follow the procedure below. Use Table 4-1 for the setting and corresponding DIP switch actuator.
Table 4-1. Frequency Settings. ( Shaded DIP switch i s standard factory setting).
DESCRIPTION LABEL
requency 60/50Hz 60Hz
cover
hook on left side
FACTORY
SETTING
thumb latch
ADJUSTMENT
NOTICE
Do not change any other factory settings. Any change in these settings may affect the normal operation of the ASCO 386. This change could allow the load circuits to remain connected to a low voltage source.
RANGE
60 Hz Actuator 4 off
50 Hz Actuator 4 on
S1 DIP SWITCH
4
4
Figure 4-1. Controller cover latch.
How to Change a Setting
NOTICE
Do not make any setting changes while the controller is energized.
1. Deenergize all power, then open the enclosure door.
2. Disconnect both harness plugs from controller by squeezing the latches. Do not pull on the wires.
3. Remove cover from the controller by releasing latch on right side with your thumb. See Figure 4-1.
4. Locate the appropriate adjustment DIP switch for the setting that you want to change. Refer to Table 4-1 above and Figure 4-2 and Figure 4-3.
5. Use a ball-point pen (or similar pointed tool) to slide the switch actuators left or right so they match the illustrationnext to the setting (left = off, right = on). Recheck the setting. See Figure 4-3.
6. Install the cover o n the controller by hooking it on the left side and latching the right side.
harness
plugs
S1 DIP
switch
Figure 4-2. Location of DIP switch.
DIP
switch
S1
actuator
(8 on each DIP switch)
S2 DIP
switch
(load disconnect feature)
seepage5---1
onoff
7. Reconnect both harness plugs to the controller by aligning and pressing straight in until lat ches click.
8. Close the enclosure door, then restore both sources.
Figure 4-3. Setting DIP switch actuator.
4 --- 1
Page 11
SECTION 5 OPTIONAL FEATURES
MOTOR LOAD TRANSFER
Inphase monitoring logic controls transfer and retransfer of motor loads, so that inrush currents do not exceed normal starting currents. It avoids nuisance tripping of circuit breakers and mechanical damage to motor couplings.
The Motor Load Transfer feature is built into the controller. DIP switch S1 (actuator 5) activates this feature: right = ON, left = OFF.
FUNCTION S1 DIP SWITCH
enable Actuator 5 on
disable Actuator 5 off
Shaded DIP switches are standard factory settings.
Note
If the Motor L oad Transfer feature is enabled, it will be activated following
the Load Disconnect Feature Delay Before Transfer delay. Also, the transfer switch may not operate immediately after the transfer control switch is operated, even if both sources are available. This delay is intentional introduced if the two power sources are not inphase. Depending on the frequency difference, it may take a few seconds for the sources to reach synchronism.
5
5
LOAD DISCONNECT FEATURE
Connect external circuits to the terminals indicated on the Wiring Diagram in the back of this manual.
The double throw (Form C) contact is rated for 28 VDCor120VAC(6ampsresistive). Thecontact operates prior to a selectable 0, 3, 10, or 20 second delay before transfer of the Non-Automatic Transfer Switch. The contact resets either immediately following transfer or after the same
delay as set for
pre–signal before transfer.
Time delay between the load disconnect control signal and initiation of transfer is set on the controller with DIP switch S2 (actuators 6, 7, 8) as shown below:
Delay Before Transfer
LD TDBT S2 DIP SWITCH
0 (disable)
3seconds
10 seconds
20 seconds
Actuator 7 on Actuator 8 on
Actuator 7 on Actuator 8 off
Actuator 7 off Actuator 8 on
Actuator 7 off Actuator 8 off
87
87
87
87
Shaded DIP switches are standard factory settings.
Delay After Transfer*
LD TDAT S2 DIP SWITCH
enable Actuator 6 on
disable Actuator 6 off
*Enabling the Delay After Transfer will cause the control signal to reset after the same delay the Delay Before Transfer.
6
6
as set for
5 --- 1
Page 12
INDEX
A
auxiliary circuits, 1–1
B
barriers, 1–2
bus connections, 1–2
C
cable
lugs, 1–1, 1–2 preparation, 1–1, 1–2
catalog number, inside cover
cleaning, 3–1
connections
line, 1–2
controller, 4–1
code, inside cover cover removal, 4–1 disconnecting, 3–1
D
DIP Switches, 4–1, 5–1
E
electrical operation, 1–4
F
frequency, 50 or 60 Hz setting, 4–1
functional test, 1–3, 1–4
H
harness, 1–1
disconnect plugs, 3–1
HELP
800–800–2726 (ASCO) customercare@asco.com
I
identification label, cover
inphase monitor, 5–1
inspection, 3–1
installation, 1–1
L
labels,
rating, cover
lights, 1–4, 3–1
load connected to emergency, 1–4,
3–1
load connected to normal, 1–4, 3–1
load disconnect feature, 5–1
lubrication, 3–1
M
maintenance, preventive, 3–1
manual load transfer, 3–2
warning, 3–2
manual operation, 1–3
illustration of, 1–3 warning, 1–3
motor load transfer feature, 3–2, 5–1
O
operation
electrical, 1–4 manual, 1–3
illustration of, 1–3 warning, 1–3
sequence of, 2–1
optional features, 5–1
load disconnect, 5–1 motor load transfer, 5–1
P
parts, 3–1
problem, 3–2
R
rating label, cover
replacement parts, 3–1
retransfer to normal, 1–4, 2–1, 3–1
S
sequence of operation, 2–1
settings
changing, 4–1 factory, 4–1 frequency, 4–1
T
test, functional, 1–3, 1–4
transfer control, 1–4, 2–1, 3–1
transfer to emergency, 1–4, 2–1, 3–1
transfer to normal, 1–4, 2–1, 3–1
trouble–shooting, 3–2
inphase monitor, 3–2
V
voltage checks, 1–4
Printed in U.S.A.
Copyright --- ASCO Power Technologies, L .P. 2011
Loading...