Emerson GDESIGN 10003000 A User Manual

Operator’s
Non–Automatic Transfer Switches
Manual
DANGER is used in this manual to warn of a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
Series 386
Refer to the outline and wiring drawings provided with the ASCO Series 386 N–ATS for all installation details.
Rating Label
Each non–automatic transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
Identification Label
The identification label on the Transfer Switch includes data for each specific ASCO Series 386. Use the switch only within the limits shown on identification label.
An experienced licensed electrician must install the Non–Automatic Transfer Switch (N–ATS).
TABLE OF CONTENTS
section-page
INSTALLATION 1-1........................
Mounting and Line Connections 1-1.........
Functional Test 1-2, 1-3.....................
SEQUENCE OF OPERATION 2-1...........
TESTING & SERVICE 3-1..................
Preventive Maintenance 3-1................
Transfer Test 3-1..........................
Trouble-Shooting 3-2......................
ADJUSTMENTS 4-1.......................
Sensor Adjustments 4-1...................
How to Change a Setting 4-1...............
OPTIONAL FEATURES 5-1.................
Motor Load Transfer 5-1...................
Load Disconnect 5-1......................
INDEX back of manual.....................
G–design 1000–1200 A sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
381333–086 D
SECTION 1 INSTALLATION
ASCO 386 Non–Automatic Transfer Switches (N–ATSs) are factory wired and tested. Field installation simply requires mounting and connection of service cables, and auxiliary control circuit s (if required).
Remove the Shipping Skid (large N–ATSs)
For large N–ATSs, open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the wood skid.
Supporting Foundation
The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the switch for all mounting details including door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Mounting
Refer to the Outline and Mounting Diagram provided with the N–ATS; it shows all mounting details and instructions.
NOTICE
Protect the non–automatic transfer switch from construction grit and metal chips to prevent malfunction or shortened life of the N–ATS.
Mount the ASCO 386 vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the switch.
Auxiliary Cable Boxes for 1000 and 1200 A
For G–design 1000 and 1200 ampere sizes, auxiliary cable boxes are required for all (normal, emergency, & load) bottom or top entry. Be sure to install auxiliary cable boxes if both service and load cables are entering through the top or bottom of enclosure. Consult ASCO Power Technologies.
Be sure that the insulator piece is behind the 260 and 400 ampere transfer switches.
insulator backing piece
Figure 1-1. Insulator for E–design 260 and 400 ampere
Controller Ground
The controller is mounted on the cabinet door. The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs). An add-on DIN rail is provided for some optional accessories and is mounted below the controller on the door.
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used betwee n the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provi ded with this Non–Automatic Tra ns f e r Swi tc h.
Read all instructions on the Wiring Diagram and labels affixed to the non–automatic transfer swi tch. Note the control features that are provi ded and review their operation before proceeding.
Insulator Backing Piece for 260 and 400 A
E–design transfer switches rated 260 and 400 ampere are mounted on an insulator backing piece (installed behind the transfer switch). If the transfer switch is removed from the cabinet and then reinstalled, this insulator piece must be placed behind the transfer switch. See Figure 1-1.
1 --- 1
INSTALLATION (continued)
Line Connections
A Wiring Diagram is furnished with the ASCO 386 (separate from this manual). Refer to this drawing. All wiring must be made in accordance with the National Electrical Code and local codes.
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine generator starting control in the OFF position. Make sure engine generator is not in operation.
Testing Power Conductors
Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before should be tested to verify that they are not defective or have been damaged during installation.
they are connected, they
Connecting Power Conductors
After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with the switch. Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the switch. B e careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Bus Connections
If bus connection is used, use SAE grade 5 hardware to connect bus to appropriate terminal p lates on the transfer switch. Wipe off bus surfaces before they are joined. If bus is very dirty, gently clean surfaces with a non–flammable solvent. Avoid touching cleaned surfaces.
Do not breathe cleaning solvent vapors.
UseSAEgrade5hardwareandtightentheboltedjointsto thetorquespecifiedinTableA.
NOTICE
The reliability of the connection depends on how clean and how tight the joint is.
Table A. Tightening torque values for bolted joints.
Bolt Diameter
(Grade 5 hardware)
in inches
5/16 12
3/8 20 1/2 50 5/8 95 3/4 155
Continue to 1–ManualOperationTest on next page.
Recommended
Tightening Torque
in foot pounds
Do not run cables behi nd the switch. Cables can be bundled on the right side of the switch. Maintain proper electrical clearance between the live metal parts and grounded metal: ½ inch minimum for 260-400 amperes, 1 inch minimum over 400 amperes.
1 --- 2
Loading...
+ 8 hidden pages