Emerson FTA1100 User Manual

Installation and Operation Instructions
Installation and Operation Instructions
Mark II
XG
Diesel Engine Fire Pump Controllers
FTA1100
FTA1100
Mark II
XG
Diesel Engine Fire Pump Controllers
ECN 225126
Table of Contents
INTRODUCTION ...........................................................................................................................1
MOUNTING CONTROLLER ............................................................................................................1
Wall Mount ................................................................................................................... 1 - 2
Floor/Base Plate Mount ......................................................................................................2
MAKING ELECTRICAL CONNECTIONS ...................................................................................... 2 - 4
MAKING SYSTEM PRESSURE CONNECTIONS .................................................................................4
PROGRAMMING THE MARK IIXG ...................................................................................................4
User Interface and Display .................................................................................................5
User Menu Structure..........................................................................................................6
Programming Notes ..........................................................................................................7
MAIN MENU - SETTINGS System Setup Display
Brightness ..................................................................................................................8
Contrast .....................................................................................................................8
Invert .........................................................................................................................8
Keyboard ...................................................................................................................8
Language and Units
Language ...................................................................................................................8
Pressure Units ............................................................................................................8
Passwords
Level 1 ........................................................................................................................8
Level 2 ........................................................................................................................8
Date & Time
Time ..........................................................................................................................8
Date ...........................................................................................................................8
Date Format ...............................................................................................................8
Daylight Saving ..........................................................................................................9
Timers
On Delay ....................................................................................................................9
Minimum Run / Off Delay ...........................................................................................9
Pressure
Pressure Units ............................................................................................................9
Start ...........................................................................................................................9
Stop ...........................................................................................................................9
Automatic Shutdown Disabled ...................................................................................9
i
Pressure (continued)
Overpressure Alarm .................................................................................................10
Recording - Delta .....................................................................................................10
Sensor ......................................................................................................................10
Calibration ...............................................................................................................10
Engine & Cranking
Control .....................................................................................................................10
Overspeed (Engine Terminal #1) ..............................................................................10
Alarm Limits
Overpressure Alarm Enabled ....................................................................................10
Volts DC ...................................................................................................................10
Volts DC Min. ...........................................................................................................10
Volts DC Max. ...........................................................................................................11
Volts AC Min. ............................................................................................................11
Volts AC Max. ...........................................................................................................11
Coil Check ................................................................................................................11
Feature Settings
AC Power Loss Start ..................................................................................................11
Interlock Alarm ........................................................................................................11
Low Pressure Audible ...............................................................................................11
Low Suction .............................................................................................................11
Main Switch Mis-Set .................................................................................................11
Manual Test ..............................................................................................................12
Pump Run Alarm ......................................................................................................12
Remote Start ............................................................................................................12
User Input ................................................................................................................12
Weekly Test Setup .............................................................................................. 12-13
Low Pump Room Temp ............................................................................................13
Low Reservoir ...........................................................................................................13
Relief Valve Open .....................................................................................................13
High Fuel Level .........................................................................................................13
High Reservoir ..........................................................................................................14
Option Settings ...............................................................................................................14
MAIN MENU - EVENT LOG ...........................................................................................................14
MAIN MENU - DATA HISTORY ......................................................................................................14
MAIN MENU - USB
Save to USB .....................................................................................................................14
Remove Drive ..................................................................................................................15
MAIN MENU - FACTORY Confi guration - Model
Serial Number ..........................................................................................................15
Model ......................................................................................................................15
Battery Type .............................................................................................................15
Battery Voltage ........................................................................................................15
ii
MAIN MENU - FACTORY (continued) Confi guration - Model
Pressure Sensor ........................................................................................................15
Autostart NC ............................................................................................................15
User Input Number ...................................................................................................15
Low Suction .............................................................................................................15
Screen Saver .............................................................................................................15
Confi guration - Options ...................................................................................................15
Confi guration - ADC Calibration ......................................................................................15
Diagnostics
Raw Input: Analog ....................................................................................................16
Raw Input: Discrete ..................................................................................................16
Raw Input: Keys ........................................................................................................16
Raw Output: Discrete ...............................................................................................16
Mark II
XG Starts ........................................................................................................16
Lamp Test ................................................................................................................16
Audible Test .............................................................................................................16
USB Test ...................................................................................................................16
Flags ........................................................................................................................16
Tools
Clear Data History ....................................................................................................16
Clear Event Log .........................................................................................................16
Reset to Defaults ......................................................................................................16
Firmware Update .....................................................................................................16
MAIN MENU - ABOUT .................................................................................................................16
BATTERY CHARGER INFORMATION .............................................................................................17
iii
WARNING
RISK OF ELECTRICAL SHOCK
Personal injury could occur.
Ensure all power is disconnected before
installing or servicing this equipment.
These instructions are intended to assist in the understanding of the installation and operation of the FTA1100. Read through these instructions thoroughly prior to connecting the controller. If there are any questions unanswered in these instructions, please contact the local Firetrol representative or factory service department.
INTRODUCTION
Firetrol® FTA1100 combined automatic and manual diesel engine fi re pump controllers are intended for starting and monitoring fi re pump diesel engines. They are available for use with 12 or 24 volt negative ground systems using lead acid or Nickel-Cadmium batteries. FTA1100 fi re pump controllers are listed by Underwriters Laboratories Inc., in accordance with UL218, Standard for Fire Pump Control- lers, CSA, Standard for Industrial Control Equipment (cUL), and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code.
MOUNTING CONTROLLER— Note—Consult the appropriate job plans to determine controller mounting location. Controller must
be mounted within view of the engine. Tools and Materials (all mounting):
1. Assortment of common hand tools of the type used to service electromechanical equipment.
2. Hole (conduit) punch.
3. Drill for drilling wall/fl oor anchor holes.
4. Hand level.
5. Tape measure.
6. Four (4) anchors with bolts and washer—if wall mount. Six (6) anchors, bolts and washers—if fl oor/
base mount.
Wall Mount— Procedure—
1. Locate bottom mounting brackets and hardware.
2. Inspect for damage.
3. Gently lay the controller on its back, using protection so the paint is not damaged. It is best to lay
the controller in a location that is out of the way from actual mounting location.
4. Attach each bracket to the bottom of the enclosure using the supplied hardware . Tighten nuts
securely.
WARNING
RISK OF PERSONAL INJURY
Controller cannot stand upright with the bottom
mounting brackets attached. Leave laying on its
back until the wall anchors are ready for controller
Note—Refer to the controller dimension drawing for necessary mounting dimensions.
The controller is wall mounted by using four (4) wall anchors, 2 anchors for the top ears and 2 anchors for the bottom mounting brackets. The ears and brackets are dimensionally on the same center-line for ease in mounting.
installation.
1
5. Using either the dimension print or by measuring the distance between the center lines of the 2
lower bracket slots, transcribe this dimension onto the wall. Note: The bottom edge of the en-
closure should be a minimum of 12” (305 mm.) from the fl oor in case fl ooding of the pump room
occurs.
6. Drill and put 2 anchors into the wall for the 2 lower bracket slot mounts.
7. Mark on the wall, the location of the holes in the upper mounting ears.
8. Drill and put 2 anchors into wall for the upper mounts.
9. Install bolts and washers in 2 lower anchors, leaving a gap between the washer and wall.
10. Lift the controller and place the bottom mounting slots down onto the 2 lower anchor bolts. Do
not tighten bolts.
11. Align holes in upper mounting ears and install 2 bolts and washers in anchors.
12. Shim anchors as necessary to ensure rear of enclosure is vertically level and enclosure is not
stressed. Tighten all 4 anchor bolts.
13. Check to be sure enclosure door opens and closes freely and that enclosure is level.
Floor/Base Plate Mount— Procedure– MOUNTING LEGS (OPTIONAL - IF ORDERED) Procedure—
1. Unpack legs and mounting hardware.
2. Inspect legs for damage.
3. Gently lay the controller on its back, using protection so the paint is not damaged. It is best to lay
the controller in a location that is out of the way from actual mounting location.
4. Attach each leg to the bottom of the enclosure using the provided hardware . Tighten nuts se-
curely.
5. After legs are securely attached, stand the controller up on its legs for mounting. Each leg has 3
holes on the bottom for anchoring to the fl oor or base plate.
WARNING
RISK OF PERSONAL INJURY
Controller is not free standing! Controller must be
secured to floor or wall surface before opening
Note—Consult the appropriate job plans to determine controller mounting location. Refer to the controller dimension print for necessary mounting dimensions.
The controller is fl oor/base plate mounted by using the 3 pre-drilled holes in each leg. The holes are dimensionally on the same center line for ease in mounting.
6. Using either the dimension print or by measuring distance between the center lines of the holes
on one leg, transcribe these dimensions onto the fl oor/base plate.
7. Drill 3 holes in fl oor/base plate for anchoring the leg.
8. Mark location of holes for opposite leg and drill 3 more holes.
9. Secure controller to fl oor/base plate with bolts and washers and tighten.
10. Check to be sure enclosure door opens freely and that enclosure is level.
MAKING ELECTRICAL CONNECTIONS Important Precautions—
Prior to making any fi eld connections:
1. Open door of enclosure and inspect internal components and wiring for any signs of frayed or
loose wires or other visible damage.
door or operating.
2
2. Verify that the controller information is what is required on the project:
• Firetrol catalog number
• Engine voltage and polarity of grounding
• Incoming line voltage and frequency
• Maximum system pressure
3. Project electrical contractor must supply all necessary wiring for fi eld connections in accordance
with the National Electrical Code, local electrical code and any other authority having jurisdic-
tion.
4. Refer to the appropriate fi eld connection drawing for wiring information.
Procedure—
All engine connections, remote alarm functions and AC wiring must be brought into the enclo­sure at the bottom. (See dimension drawing for exact location). A gland plate is supplied for ease of installation.
Proceed as follows:
1. Use a hole (conduit) punch, not a torch nor a drill, and punch a hole in the gland plate for the size
conduit being used.
2. Install necessary conduit.
Warning—Use only gland plate for conduit entrance. Controller warranty is VOID if any other
location is used.
Note—All fi eld wiring connections are connected to terminal blocks located in the controller.
Terminals for interconnection to the corresponding numbered terminals on the engine terminal
block are located between the circuit breakers (CB1, AC power and CB2-CB3, battery connections).
Not all engines require all terminals to be connected. Reference engine wiring diagram and Field
Connection Diagram for appropriate information. Other terminals are for connecting remote
alarm functions and optional features are located on the controller relay board(s). AC line connections are made to terminals L1 and L2 (1CB). A ground lug, marked “G” is provided
for grounding. This AC circuit should come from a source having a circuit breaker sized in accor-
dance with the National Electrical Code and other local codes.
3. Pull all wires necessary for engine connections, remote alarm functions, AC power and all other
optional features. Allow enough excess wire inside enclosure to make up connections to the ter-
minal block. Be sure to consult the appropriate fi eld connection diagram. Make sure AC Circuit
Breaker (CB1) and Battery Circuit Breakers (CB2, CB3) are turned “Off”.
Warning—Do not use controller wire way for routing external wiring. Wire Sizes—
• Use #14 AWG wire minimum for all electrical connections except for battery charger connec-
tions. (Battery chargers connected to terminals 6, 8, and 11.)
• On terminals 6, 8, and 11, use the following information to determine wire sizes:
Linear feet (in conduit run) from controller to terminal
Maximum
Wire Size
block on engine
2
0’ to 25’ (0 to 7.62 m.)
25’ to 50’ (7.62 m. to 15.24 m.)
#10 AWG (6 mm #8 AWG (10 mm2)
)
4. Make all fi eld connections to remote alarm functions and any other optional features.
5. Verify AC line voltage and frequency with the controller data plate on the enclosure door prior to
energizing AC power.
3
6. Connect AC power to “L1” and “L2” (CB1) —120 Volt, 60 Hz or as called for on controller data
plate.
7. Connect remote normally open START push-button wires to terminals “13” and “14” (if used).
8. If deluge valve is used, remove jumper from terminals “16” and “17”. Connect wires from normally
closed contact on deluge valve to terminals “16” and “17”.
9. Connect remote normally open shutdown interlock wires to terminals “15” and “16” (if used). A
factory installed jumper will be installed on these terminals. If installing a interlock, this jumper
may be removed, otherwise leave jumper in place until the set up of the Mark II
XG is complete.
10. Check to see that all connections are both correctly wired (in accordance with fi eld connection
diagram) and tight.
11. Close enclosure door.
MAKING SYSTEM PRESSURE CONNECTIONS
The FTA1100 controller requires one (1) “System Pressure” connection from the system piping to the enclosure. The connection fi tting, 1/2” FNPT, is provided on the bottom, external side of the enclosure for this purpose.
The “Test Drain” connection, located to the left of the “System Pressure” connection, should be piped to a vented drain or to waste. The “Test Drain” is used only briefl y during the weekly test cycle. Note—Test drain line must be free fl owing. Do not use any valves or plugs on this line.
Refer to NFPA 20 for correct fi eld piping procedure of sensing line between the pumping system and the controller.
PROGRAMMING THE MARK IIXG
1. Energize (Turn “ON”) circuit breakers 1CB (AC Power), 2CB & 3CB (Battery Connections). Follow
the programming instructions included in this manual to set pressure, timers, etc...
2. When all programming is complete and the unit is ready to put into service, remove interlock
jumper wire from terminals 15 & 16. This jumper is factory installed to prevent starting of the
engine during installation and setup.
4
Mark IIXG User Interface and Display
1
2
Ready
1
11.7
2
11.5
09-28-2009 14:37:06
DIESEL
Esc
Esc
4
132 psi
0.8A 120~
0.7A 118~
5
3
Enter
Enter
Silence
Silence
SYSTEM STATUS
AC POWER AVAILABLE ALARM MAIN SWITCH IN AUTO MAIN SWITCH IN MANUAL
SYSTEM PRESSURE LOW ENGINE RUNNING
ENGINE FAIL TO START ENGINE TEMPERATURE HIGH ENGINE OIL PRESSURE LOW ENGINE OVERSPEED ENGINE ALTERNATE ECM
ENGINE FUEL INJECTOR MALFUNCTION
FUEL LEVEL LOW AUTOMA TIC SHUTDOWN DISABLED
CHARGER MALFUNCTION BATTERY #1 TROUBLE BATTERY #2 TROUBLE
6
Informational Display
1
Control Status and System Pressure Battery 1 & 2 Status - DC Volts, Charging Amps, AC Volts (charger) Active Alarms - Primary Status Notifi cation Date-Time or Active Timer Secondary Status Notifi cation
ESC Button
2
Used to go backwards through menu screens
Enter Button
3
Used to go forwards through menu screens and save user defi ned settings
Directional Arrows
4
Used to go up and down in menu screens and change user defi ned values
Silence Alarm Button
5
Used to silence audible alarm
System Status LED’s
6
Provide visual indication of important system information
5
Mark IIXG User Menu Structure
Main Menu
Settings
System Setup Date & Time
Display
Language/Units
Passwords
Time Date
Daylight Saving
Calls to Start • Starts • Pump Total Run Time • Last Pump Run Time • Controller
Timers
On Delay Time Min. Run Time
Pressure
Units Start
Stop Auto Shtdwn Overpressure
Recording
Sensor
Calibration
Engine & Cranking
Control # Attempts Crank Time
Rest Time
Overspeed Term 1
Alarm Limits
Overpressure
Sys DC Volt Set
DC Volt Min DC Volt Max AC Volt Min AC Volt Max
Coil Check
Event Log
Event History
Data History
Power On Time • Last Pump Start • Min. Pressure • Max. Pressure • Last High Temp. • Last Low Oil • Last Low Fuel • Last Charger Fail • Last Battery Trouble • Last Overspeed • Batt. 1 Volts (min, now, max) • Batt. 2 Volts (min, now, max)•
Batt. 1 Amps (min, now, max) • Batt. 2 Amps (min, now, max)
USB
Feat. Settings
AC Failure Start Interlock Alarm
Low Press Aud
Low Suction
Main Sw Mis-Set
Manual Test
Pump Run Alarm
Remote Start
User Input
Weekly Test
Low PR Temp
Low Reservoir
Relief Valve Open
High Fuel Level High Reservoir
Opt. Settings
(As ordered
with controller)
Status
Save to USB
Remove USB Drive
Factory
Confi guration
Diagnostics
Tools
About
Model #
S/N
SW P/N
SW Build Ver.
Boot Code Ver.
6
Programming Notes
The Firetrol Mark IIXG is multi-level password protected. User programmable functions are protected by a Level 1 password.
LEVEL 1 PASSWORD
2 - 1 - 1 - 2
Indicates the level of password required to modify a setting.
1
Note: Many menu settings feature an “enable/disable” option. These options are indicated by a
9 for enabled or a “x” for disabled. In many cases this can also be interpreted as 9 for yes
or a “x” for no.
WARNING
RISK OF PROPERY LOSS,
Incorrect or inappropriate controller settings could render the
fire protection system inoperable. Only qualified and knowl-
edgeable personnel should operate this equipment.
DEATH OR INJURY
7
Mark IIXG User Menu Settings
Note: Many menu settings feature an “enable/disable” option. These options are indicated by a "9” for enabled or a “x” for disabled.
Indicates the level of password required to modify setting.
1
System Setup - Display
SETTINGS
Use and arrows to set desired display brightness. Press to confi rm.
SETTINGS
Use and arrows to set desired display contrast. Press to confi rm.
SETTINGS
Use or arrows to enable/disable inverted display (bright background with dark letters). Press to confi rm.
SETTINGS
Use or arrows to set the amount of time of keyboard inactivity before the display returns to the main screen. Press to confi rm.
SYSTEM SETUP
SYSTEM SETUP
SYSTEM SETUP
SYSTEM SETUP
DISPLAY
DISPLAY
DISPLAY
DISPLAY
BRIGHTNESS
CONTRAST
INVERT
KEYBOARD
1
1
1
1
System Setup - Language & Units
SETTINGS
Use and arrows to select preferred display language. Press to confi rm.
SETTINGS
Use and arrows to select preferred pressure unit display (psi, bar, kPa). Press to confi rm.
SYSTEM SETUP
SYSTEM SETUP
LANGUAGE & UNITS
LANGUAGE & UNITS
LANGUAGE
PRESSURE
1
1
System Setup - Passwords
SETTINGS
Use arrows to set preferred password for level 1 access. Press to confi rm.
SETTINGS
Use arrows to set preferred password for level 2 access. Press to confi rm.
NOTE: A higher level can change a lower level password (level 2 can change level 1). If passwords are changed from factory default and forgotten, charges my be incurred to reset the passwords.
SYSTEM SETUP
SYSTEM SETUP
PASSWORDS LEVEL 1
PASSWORDS
LEVEL 2
1
2
Settings - Date & Time
SETTINGS
Use arrows to set current local time (24 hr format). Press to confi rm.
SETTINGS
Use arrows to set current date (YYYY-MM-DD). The day of week will automatically update as required. Press to confi rm.
SETTINGS
Use arrows to set current date format (YYYY-MM-DD, DD-MM-YYYY, MM-DD-YYYY). Press to confi rm.
DATE & TIME
DATE & TIME
DATE & TIME
TIME
DATE
DATE FORMAT
1
1
1
8
SETTINGS
Use arrows to enable or disable automatic Daylight Saving time adjustments. Press to confi rm.
DATE & TIME
DAYLIGHT SAVING
1
(+/-)
(DST +) “Begin” - Hour
(DST +) “Begin” - Day Use arrows to set the day of the month that Daylight Saving time begins.
(DST +) “Begin” - Month Use arrows to set the month of the year that Daylight Saving time begins.
(Example: Hour=2:00, Day=2nd Sun, Month=Mar means Daylight Saving time would begin at 2:00a.m. on the 2nd Sunday in March)
(DST -) “End” - Hour Use arrows to set the hour of day that Daylight Saving time ends. Press to
(DST -) “End” - Day
(DST -) “End” - Month
(Example: Hour=2:00, Day=1st Sun, Month=Nov means Daylight Saving time would end at 2:00a.m. on the 1st Sunday in November)
Use arrows to set number of minutes to adjust for at the beginning or end of Daylight Saving time. Press to confi rm.
Use arrows to set the hour of day that Daylight Saving time begins. Press to confi rm.
Press to confi rm.
Press to confi rm.
confi rm.
Use arrows to set the day of the month that Daylight Saving time ends. Press to confi rm.
Use arrows to set the month of the year that Daylight Saving time ends. Press to confi rm.
Settings - Timers
SETTINGS
Use arrows to set preferred on delay time. Press to confi rm.
TIMERS
ON DELAY
1
Note: On Delay (also known as sequential start) time, delays the starting of the motor when an automatic call to start is received.
SETTINGS
Use arrows to set timer mode to Minimum Run or Off Delay. Press key and use keys to set desired time. Press to confi rm.
Note: Minimum Run time will begin when motor starts, Off Delay time will begin when system pressure has been restored to Stop pressure setting.
TIMERS
MIN RUN/OFF DELAY
1
Settings - Pressure
SETTINGS
Use arrows to set preferred pressure unit system (psi, bar, kPa). Press to confi rm.
SETTINGS
Use arrows to set desired pump start pressure. Press to confi rm.
SETTINGS
Use arrows to set desired pump stop pressure. Press to confi rm. Note: Pump stop pressure must be set below the pump “churn” pressure (including minimum suction pressure), oth-
erwise the pump will run continuously once started.
SETTINGS
Use arrows to enable or disable the automatic shutdown disabled feature. Press to confi rm. Note: Enabling this feature makes the controller “manual stop only”.
PRESSURE
PRESSURE
PRESSURE
PRESSURE
UNITS
START
STOP
AUTOMATIC SHUTDOWN DISABLED
1
1
1
1
9
SETTINGS
Use arrows to enable or disable the overpressure alarm feature. Press to confi rm.
Limit
Use arrows to set the pressure limit for the overpressure alarm. Press to confi rm.
PRESSURE
OVERPRESSURE ALARM
1
SETTINGS
Use arrows to set pressure delta recording limit. Press to confi rm. Note: Pressure will be recorded whenever pressure changes by more than set limit.
HOURLY
Note: Pressure will be recorded every hour, on the hour.
SETTINGS
The maximum operating pressure of the sensor (transducer) is displayed. Value cannot be changed from this location.
SETTINGS
NOTE: Before proceeding, place jumper wire between fi eld terminals #15 & 16 to prevent starting of the engine. A calibrated pressure gauge will be required to correctly adjust the settings.
Remove/relieve system pressure from the controller sensing line. If gauge shows 0 psi, no adjustments are required; otherwise set zero calibration to same value as displayed on pressure gauge. (Example: With system pressure removed the gauge reads 3 psi, set zero calibration value to 3).
Use arrows to set zero calibration value. Press to confi rm.
Using calibrated gauge, restore pressure to controller sensing line. Adjust span setting to match the value shown on the gauge.
SET TO SPAN
NOTE: Remove interlock jumper wire from terminal #15 & 16 when calibration is complete.
RESET TO DEFAULT
NOTE: Calibration setting will reset to factory defaults and reset function will automatically return to disabled.
PRESSURE
Use arrows to enable or disable hourly pressure recording. Press to confi rm.
PRESSURE
PRESSURE
Use arrows to set span calibration value. Press to confi rm.
Use arrows to enable reset. Press to confi rm.
SENSOR
RECORDING - DELTA
CALIBRATION - SET TO ZERO
1
2
Settings - Engine & Cranking
SETTINGS
Current value is shown (Mechanical or Electronic). This setting determines the type of Engine being used. Use arrows to select engine type. Press to confi rm.
Also shown on this screen are the cranking cycle values (# Crank Attempts, Duration of a Crank Cycle, Duration of a Rest Cycle). This is informational only and cannot be changed.
SETTINGS
This setting determines if the Fuel Valve Relay (Terminal #1) remains energized during an overspeed condition. This output is required on some engines. Use arrows to enable or disable this setting. Press to confi rm.
ENGINE & CRANKING
ENGINE & CRANKING
CONTROL
OVERSPEED (Engine Terminal #1)
3
1
Settings - Alarm Limits
SETTINGS
Use arrows to enable or disable this setting. Press to confi rm.
LIMIT
Use arrows to set pressure limit at which the alarm is activated. Press to confi rm.
SETTINGS
Indicates controller battery voltage setting. Informational only - setting cannot be changed from this menu.
ALARM LIMITS
ALARM LIMITS
OVERPRESSURE ALARM ENABLED
1
SETTINGS
Use arrows to set minimum voltage point for Battery Trouble alarm. Press to confi rm.
ALARM LIMITS
MIN
1
10
SETTINGS
Use arrows to set maximum voltage point for Battery Trouble alarm. Press to confi rm.
ALARM LIMITS
MAX
1
SETTINGS
Use arrows to set minimum voltage point for AC Voltage Low alarm. Press to confi rm.
ENABLED
Use arrows to enable or disable the AC Voltage Low alarm. Press to confi rm.
SETTINGS
Use arrows to set maximum voltage point for AC Voltage High alarm. Press to confi rm.
ENABLED
Use arrows to enable or disable the AC Voltage High alarm. Press to confi rm.
SETTINGS
Use arrows to set monitoring of the engine starting solenoid coils (1-, -2, 1&2, OFF). Press to confi rm.
ALARM LIMITS
1
ALARM LIMITS
1
ALARM LIMITS
V MIN
V MAX
COIL CHECK
1
1
1
Settings - Feature Settings
SETTINGS
ENABLED
Use arrows to enable or disable the AC Voltage Loss Start feature. Press to confi rm.
DELAY
Use arrows to set the time delay between loss of AC voltage and engine starting (0-60 sec.). Press to confi rm.
1
FEATURE SETTINGS
1
AC POWER LOSS START
SETTINGS
Use arrows enable or disable the alarm for Interlock On. Press to confi rm.
SETTINGS
Use arrows enable or disable the audible alarm for Low System Pressure. Press to confi rm.
SETTINGS
ENABLE
Use arrows to enable or disable the alarm for Low Suction Pressure. Press to confi rm.
AUDIBLE
Use arrows to enable or disable the audible alarm for Low Suction Pressure. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Low Suction Pressure. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for Low Suction Pressure (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to confi rm.
SETTINGS
1
Use arrows to choose how the Main Switch Mis-Set alarm relay operates. “Pick Up” means the relay will ener­gize when the switch is not in auto. “Drop Out” means the relay we de-energize when the switch is not in auto. Press to confi rm.
FEATURE SETTINGS
FEATURE SETTINGS
FEATURE SETTINGS
1
1
1
1
FEATURE SETTINGS
INTERLOCK ALARM
LOW PRESSURE AUD
LOW SUCTION
MAIN SWITCH MIS-SET
1
1
11
SETTINGS
DURATION
Use arrows to set the minimum run time (duration) when manual test push-button is used (10 - 99 min.). Press to confi rm.
FEATURE SETTINGS
1
MANUAL TEST
SETTINGS
AUDIBLE
Use arrows to enable or disable the audible alarm for Pump Run. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Pump Run. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for Pump Run (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to confi rm.
SETTINGS
USE ON DELAY
Use arrows to enable or disable the on delay timer function when remote start is used. Press to confi rm. NOTE: The on delay timer must be set in the TIMER SETTINGS menu.
AUTO SHUTDOWN
Use arrows to enable or disable the automatic shutdown feature when remote start is used. NOTE: If enabled, the minimum run timer set in TIMER SETTINGS will be used. Press to confi rm.
SETTINGS
ENABLE
Use arrows to enable or disable the user defi ned alarm. Press to confi rm.
ON DELAY
Use arrows to select an on delay time before the alarm is acknowledged (0-99 seconds). Press to confi rm.
AUDIBLE
Use arrows to select if the user input activates the audible alarm. Press to confi rm.
COMMON ALARM
Use arrows to select if the user input activates the common alarm output (ALR Relay). Press to confi rm.
PUMP ROOM
Use arrows to select if the user input activates the alarm output (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to confi rm.
1
FEATURE SETTINGS
1
1
1
FEATURE SETTINGS
1
1
FEATURE SETTINGS
1
1
1
1
PUMP RUN ALARM
REMOTE START
USER INPUT
ON MESSAGE TEXT
Use arrows to program the message that is displayed and recorded when the user defi ned alarm is acti- vated. Press to confi rm.
OFF MESSAGE TEXT
Use arrows to program the message that is displayed and recorded when the user defi ned alarm is deacti- vated. Press to confi rm.
SETTINGS
ENABLE
Use arrows to disable or defi ne the frequency of the Weekly Test feature (Disabled, Every Week, Every 2 Weeks,
...........Every 5 Weeks). Press to confi rm.
ON
Use arrows to choose the day of the week that the Weekly Test is performed. Press to confi rm.
1
1
FEATURE SETTINGS
1
1
WEEKLY TEST SETUP
12
AT
Use arrows to choose the time of day that the Weekly Test is performed. Press to confi rm.
1
FOR
Use arrows to choose the duration (engine run time) of the Weekly Test. Press to confi rm.
NOW IN WEEK
Use arrows to choose current time frame in reference to the Weekly Test schedule. Press to confi rm. (Example: If test is programmed for every 2 weeks on Sunday and today were Friday then - If testing is desired to start this week, then every other week thereafter, we would now be in week 2 of 2 - If testing is desired to start on the fol­lowing Sunday, not the coming Sunday, then we would now be in week 1 of 2).
SETTINGS
AUDIBLE
Use arrows to enable or disable the audible alarm for Low Pump Room Temperature. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Low Pump Room Temperature. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for Low Pump Room Temperature (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to confi rm.
SETTINGS
AUDIBLE
Use arrows to enable or disable the audible alarm for Low Reservoir Level. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Low Reservoir Level. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for Low Reservoir Level (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to confi rm.
1
1
FEATURE SETTINGS
1
1
1
FEATURE SETTINGS
1
1
1
LOW PUMP ROOM TEMP
LOW RESERVOIR
SETTINGS
AUDIBLE
Use arrows to enable or disable the audible alarm for Relief Valve Open. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Relief Valve Open. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for Relief Valve Open (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to confi rm.
SETTINGS
AUDIBLE
Use arrows to enable or disable the audible alarm for High Fuel Level. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for High Fuel Level. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for High Fuel Level (Disabled, PTR (Pump Room Trouble), ETR (En­gine Trouble), Both PTR and ETR). Press to confi rm.
1
FEATURE SETTINGS
1
1
1
FEATURE SETTINGS
1
1
RELIEF VALVE OPEN
HIGH FUEL LEVEL
13
SETTINGS
AUDIBLE
Use arrows to enable or disable the audible alarm for High Reservoir Level. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for High Reservoir Level. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for High Reservoir Level (Disabled, PTR (Pump Room Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to confi rm.
FEATURE SETTINGS
1
1
1
HIGH RESERVOIR
SETTINGS
NOTE: The list of available options and the settings associated with them will vary with each controller. Listed below are the most common user defi ned settings that may appear.
AUDIBLE
Use arrows to enable or disable the audible alarm for selected option. Press to confi rm.
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for selected option. Press to confi rm.
PUMP ROOM
Use arrows to select the alarm output relay for selected option (Disabled, PTR (Pump Room Trouble), ETR (En­gine Trouble), Both PTR and ETR). Press to confi rm.
EVENT LOG
The Event Log is a record of events (pressure recording, alarms, starts, etc...) that are stored in the memory of the Mark IIXG. The last 3000 events are kept in this memory. The events are stored in the order that they occur, with the most recent being “fi rst” (the last event that occurred will be event #1). The following keys are used to browse through the event log:
Move forward through the events one at a time (1 - 2 - 3....etc)
Move backward through the events one at a time (55 - 54 - 53....etc)
Move forward through the events ten at a time (60 - 70 - 80....etc)
Move backward through the events ten at a time (91 - 81 - 71....etc)
Pressing and holding of the arrow keys will allow the scrolling to move faster.
OPTION SETTINGS
1
1
1
DATA HISTORY
The Data History is a record of important data and events that are kept throughout the life of the controller. Use arrows to scroll through the information stored in the Data History log. The available information is:
Numbers of calls to start • Number of actual starts • Pump total run time • Pump last run time • Total controller power on time • Last pump start time/date • Minimum system pressure • Maximum system pressure • Last high temp. alarm time/date • Last low oil pressure time/date • Last low fuel level time/date • Last charger failure time/ date • Last battery trouble time/date • Last engine overspeed time/date • Battery 1 & 2 voltage min/current/max • Battery 1 & 2 amps min/current/max
USB
SAVE TO USB
Use arrows to enable or disable the Save to USB function. Press to confi rm. The following is saved to the USB fl ash drive: Event Log, Data History, Controller Information and all user defi ned
settings (pressure settings, timer settings, alarm settings....etc.). The saved fi le is a text fi le named the same as the
controller serial number (87654321.txt) and can be viewed using most word processing software.
1
14
REMOVE DRIVE
Use arrows to enable or disable the Remove Drive feature. Press to confi rm. Much like a computer, the Remove Drive feature ensures fi le closure prior to removing the USB fl ash drive from the Mark IIXG. Use of this feature helps prevent fi le corruption.
NOTE: The Mark IIXG also features an automatic daily save function. Every day at midnight (0:00) the events for that day are written to a fi le on the USB fl ash drive. This fi le is also a text fi le (.txt) and is named for the month, in the current year folder under Firetrol (x:\Firetrol\2009\Sept.txt).
1
FAC TORY
SERIAL NUMBER
Use arrows to enter the controller serial number. Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed.
MODEL
Use arrows to select required model number. Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed.
BATTERY TYPE
Use arrows to select required battery type. Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed.
BATTERY VOLTAGE
Use arrows to select required battery voltage. Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed.
PRESSURE SENSOR
Use arrows to select if a pressure sensor (transducer) is used. Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed. If disabled, menu op­tions in SETTINGS/PRESSURE are disabled.
AUTOSTART NC
Use arrows to enable or disable this parameter. Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed.
CONFIGURATION
3
3
3
3
3
3
MODEL
USER INPUT NUMBER
Use arrows to select input used for user defi ned option. Press to confi rm. NOTE: This is a factory set parameter and under normal circumstances would never be changed.
LOW SUCTION
Use arrows to select input used for Low Suction Pressure option. Press to confi rm. NOTE: This value cannot be changed unless a Low Suction option has been selected in the options confi guration.
SCREEN SAVER
Use arrows to enable or disable the screen saver function. Press to confi rm. NOTE: The display screen is designed to automatically dim 5 minutes after returning to the home screen and without any activity. The screen will “wake up” or return to set brightness on a key press or any event that would cause a mes­sage to appear on the screen. This feature is designed to prolong the life of the display. It is not recommended that this function be disabled.
FAC TORY
This is area where ordered options are added by the factory. Any user defi ned parameters for these options would ap- pear in the SETTING/OPTION SETTINGS menu.
FAC TORY
This area displays the values of the Analog to Digital Converter calibrations. This calibration is done by the manufac­turer. Any changes to these settings would have to be made by the factory.
CONFIGURATION
CONFIGURATION
3
3
1
OPTIONS
ADC CALIBRATION
15
3
4
FAC TORY
DIAGNOSTICS
RAW INPUT: ANALOG
Input values are shown. This information is for factory level troubleshooting purposes.
RAW INPUT: DISCRETE
Input values are shown. This information is for factory level troubleshooting purposes.
RAW INPUT: KEYS
Input values are shown. This information is for factory level troubleshooting purposes.
RAW OUTPUT: DISCRETE
Output values are shown. This information is for factory level troubleshooting purposes.
MARK IIXG STARTS
Displays the total number of times the Mark IIXG has been booted.
LAMP TEST
1 Use arrows to enable the lamp test. Press to begin test. All System Status LED’s should illuminate. Use arrows to disable the lamp test. Press to end test. System Status LED’s should turn off and
return to normal indications.
AUDIBLE TEST
1 Use arrows to enable the audible test. Press to begin test. The audible alarm should sound. Use arrows to disable the audible test. Press to end test. The audible alarm will turn off.
USB TEST
1
Use arrows to enable the USB test. Press to begin test. A small test fi le is written to the USB fl ash drive then read back from the drive. If the write/read is successful, the test is passed. After completion of the test the set­ting will automatically return to disabled.
FLAGS
These fl ags are a part of a manufacturer level testing tool.
FAC TORY
CLEAR DATA HISTORY
TOOLS
3 Use arrows to enable this option. Press to confi rm. Data History will be cleared and option will automati- cally revert back to disabled. NOTE: Once cleared, this data cannot be recovered.
CLEAR EVENT LOG
3 Use arrows to enable this option. Press to confi rm. The Event Log will be cleared and option will automati- cally revert back to disabled. NOTE: Once cleared, this data cannot be recovered.
RESET TO DEFAULTS
Use arrows to enable this option. Press to confi rm. The Mark II
3
XG will be reset to “out of the box” default
settings.
NOTE: All user and factory con guration settings will be lost.
FIRMWARE UPDATE
3 This is a tool for installing fi rmware updates. Updates are installed from a USB fl ash drive. On screen instructions will guide the process. Installing fi rmware usually takes just a few minutes, however, the controller is out of service during this time.
ABOUT
Information is shown for: Model Number, Serial Number, Software (Part Number, Build Number, Date), and Boot Code (Part Number and Version Information).
16
BATTERY CHARGER
When installing the battery charger as a replacement part, it is necessary to verify the proper charger settings and adjust as necessary.
1. Incoming AC voltage 115 or 230 volts.
2. Battery voltage - 12 or 24 volts DC.
3. Battery type - Lead Acid / Ni-Cad 9 or 18 Cell / Ni-Cad 10 or 20 Cell.
If battery charger is powered with the incorrect settings, damage to the charger and/or batteries may occur.
The Firetrol® battery charger features a fully automatic 4 step charging cycle. The charging cycles are as indicated: Step 1: Qualification Stage (Flashing yellow and green LEDs) During this stage, the battery charger checks the batteries to insure they can accept a fast charge. It also checks for missing or defective batteries. If the charger detects missing or defective batteries a fault will be given (solid red LED). Step 2: Fast Charge (Solid yellow LED) Charges the batteries until they reach peak voltage. Step 3: Bulk Charge (Solid yellow LED and slow blinking green LED) Charges the batteries at a constant potential of peak voltage until current reaches 500mA. Step 4: Float Charge (Solid green LED) Trickle charges the batteries to maintain peak potential.
• Charger reset push-button (resets charging cycle to beginning)
17
Loading...