Figure 1. Fisher LCP100 Local Control Panel, with
FIELDVUE DVC6200 SIS Digital Valve Controller
and Bettis
X0247
™
Actuator
Introduction
Scope of Manual
This instruction manual includes installation and maintenance information for the Fisher LCP100 local control panel
(figure 1). This device is used with Fisher FIELDVUE™ instruments in Safety Instrumented Systems (SIS). Refer to the
DVC6200 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions instruction manual
(D103557X012
instruction manual (D103230X012
Unless otherwise noted, the information in this instruction manual applies to both DVC6200 SIS and DVC6000 SIS
digital valve controllers. For simplicity, the DVC6200 SIS model name will be used throughout.
www.Fisher.com
) or the DVC6000 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions
) for additional information.
LCP100 Local Control Panel
August 2017
Do not install, operate, or maintain an LCP100 local control panel without being fully trained and qualified in valve,
actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is
important to carefully read, understand, and follow all of the contents of this manual, includingall safety cautions and
warnings. If you have any questions about these instructions, contact your Emerson sales office
Partner.
Instruction Manual
D103272X012
or Local Business
Description
The LCP100 local control panel is used with the HARTr communicating DVC6200 SIS digital valve controller. This panel
is used to manually open and close a safety shutdown valve. The LCP100 also provides a manual reset feature as well as
a button for initiating a partial stroke test.
Specifications
Typical specifications for the LCP100 local control panel are shown in table 1.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
Radiated EM fieldIEC 61000‐4‐3
Burst (fast transients)IEC 61000‐4‐4
SurgeIEC 61000‐4‐5
Conducted RFIEC 61000‐4‐6150 kHz to 80 MHz at 3 Vrms with 1 kHz AM at 80%A
$4 kV contact
$8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
$1 kV, I/O lines
$2 kV, DC power lines
$1 kV, I/O lines
$2 kV, DC power lines)
Figure 2. Fisher LCP100 Local Control Panel Dimensions
Instruction Manual
D103272X012
Performance
Criteria
A
A
A
A
(1)
E1077‐1
129
(5.1)
94
(3.7)
110
(4.3)
194
(7.6)
257
(10.1)
mm
(INCH)
4
Instruction Manual
D103272X012
LCP100 Local Control Panel
August 2017
Installation
WARNING
Electrostatic charge hazard. Do not rub or clean the LCP100 with solvents if a flammable vapor is present. To do so could
result in an explosion.
Note
Direct all wiring to the left side inside the LPC100 compartment, away from the buttons.
Hazardous Area Classifications and Special Instructions for “Safe Use” and
Installation in Hazardous Locations
Refer to the following instruction manual supplements for approval information.
D CSA (C/US) Hazardous Area Approvals - LCP100 Local Control Panel (D104236X012
D ATEX Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104237X012
D IECEx Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104238X012
All documents are available from your Emerson sales office, Local Business Partner, or Fisher.com
Emerson sales office or Local Business Partner for all other approval/certification information.
)
)
)
. Contact your
Mounting
Refer to figure 2 for dimensional information. The LCP100 local control panel has four (4) mounting holes for on‐site
mounting of the device. The LCP100 must be installed so that the wiring connections are on the bottom to prevent
accumulation of moisture inside the box.
Electrical Connections
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous location, ingress protection,
and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion.
Refer to the appropriate wiring diagram, as defined in table 3, based on your protection method and installation
requirements. Also refer to figure 4 for LCP100 switch setting, terminal connections, and label details and information,
as well as DVC6200 SIS terminal box details.
5
LCP100 Local Control Panel
August 2017
Table 3. Wiring Configurations with DVC6200 SIS Digital Valve Controller
LCP100 Protection MethodLCP100 Power Source
Ex e mb [ib] IIC
Ex tb IIIC
Ex ic IIC
Ex tb IIIC
Ex ia IIB
Ex tb IIIC
LOOP
24 VDCDVC6200 SIS then LCP100
LOOP
24 VDCDVC6200 SIS then LCP100
LOOP
Wiring Order from
Logic Solver
DVC6200 SIS then LCP100
LCP100 then DVC6200 SIS
DVC6200 SIS then LCP100
LCP100 then DVC6200 SIS
DVC6200 SIS then LCP100
LCP100 then DVC6200 SIS
Instruction Manual
DVC6200 SIS Mode
(Current or Voltage)
Point-to-Point5
Multi-Drop6
Point-to-Point7
Multi-Drop8
Point-to-Point9
Multi-Drop10
Point-to-Point11
Multi-Drop12
Point-to-Point13
Multi-Drop14
Point-to-Point15
Multi-Drop16
Point-to-Point17
Multi-Drop18
Point-to-Point19
Multi-Drop20
D103272X012
Refer to figure
Note
For intrinsically safe applications, the LCP100 forms an intrinsically safe explosion protection system when used with intrinsically
safe associated apparatus (a barrier) or with any other intrinsically safe devices.
The following requirements must be met: Uo ≤ Ui , Io ≤ Ii, Po ≤ Pi , Co ≥ Ci + Cc, Lo ≥ Li + Lc.
When installing the cover, tighten the screws evenly in a criss‐cross pattern such as the one indicated in figure 3, to a
torque of 2.82 N•m (25 lbf•in), to help ensure the cover is properly installed.
Figure 3. Proper Cover Installation
3
1
2
NOTE: TIGHTEN THE SCREWS IN A CRISS‐CROSS PATTERN
TO HELP ENSURE PROPER COVER INSTALLATION.
6
4
Instruction Manual
D103272X012
Figure 4. Interior Details of Fisher LCP100 and FIELDVUE DVC6200 SIS
POWER SELECTOR
SWITCH (FACTORY
DEFAULT IS 24VDC)
LABEL IDENTIFIES
POWER SELECTOR
SWITCH SETTING:
LEFT = 24VDC
RIGHT = LOOP
TERMINAL CONNECTIONS:
USED WHEN 24VDC POWER
SWITCH IS SELECTED
LABEL IDENTIFIES TERMINALS USED WHEN POWER
SELECTOR SWITCH IS SET TO 24VDC. NOTE THAT
MIDDLE TERMINAL IS NOT USED WITH THIS SETTING
TERMINAL CONNECTIONS: USED FOR BOTH 24VDC
AND LOOP POWER SWITCH SELECTION. REFER TO
WIRING DIAGRAMS IN THE FOLLOWING FIGURES
FOR CORRECT WIRING CONNECTIONS
LABEL IDENTIFIES TERMINALS USED WHEN
POWER SELECTOR SWITCH IS SET TO LOOP
LCP100 Local Control Panel
August 2017
GE26881-Sheet 2
ELECTRICAL ENTRY
3/4 NPT OR M20
LCP100 INTERIOR
AUX +
AUX -
SAFETY
GROUND
EARTH GROUND
DVC6200 SIS
TERMINAL BOX INTERIOR
TALK TALK +
LOOP LOOP +
7
LCP100 Local Control Panel
August 2017
Figure 5. Ex e mb [ib] IIC or Ex tb IIIC Wiring Diagram 1
Instruction Manual
D103272X012
LCP100
Protection Method
Ex e mb [ib] IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPDVC6200 SIS then LCP100Point-to-Point
2
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100 WHEN
POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 FOR FLAMEPROOF/EXPLOSION-PROOF APPROVED DIGITAL VALVE CONTROLLERS,
INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN
THE FLAMEPROOF/EXPLOSION-PROOF INTEGRITY OF THE DEVICE.
GE26881-Sheet 3
8
2
Instruction Manual
D103272X012
Figure 6. Ex e mb [ib] IIC or Ex tb IIIC Wiring Diagram 2
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex e mb [ib] IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPDVC6200 SIS then LCP100Multi-Drop
2
FLD
LC340 LINE
CONDITIONER
SYS
LOGIC SOLVER
OUTPUT
24VDC
(USER SUPPLIED)
1
NOTES:
1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 FOR FLAMEPROOF/EXPLOSION-PROOF APPROVED DIGITAL VALVE
CONTROLLERS, INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS
REQUIRED TO MAINTAIN THE FLAMEPROOF/EXPLOSION-PROOF INTEGRITY OF THE
DEVICE.
GE26881-Sheet 4
2
9
LCP100 Local Control Panel
August 2017
Figure 7. Ex e mb [ib] IIC or Ex tb IIIC Wiring Diagram 3
Instruction Manual
D103272X012
LCP100
Protection Method
Ex e mb [ib] IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPLCP100 then DVC6200 SISPoint-to-Point
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1
2
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100 WHEN
POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 FOR FLAMEPROOF/EXPLOSION-PROOF APPROVED DIGITAL VALVE CONTROLLERS,
INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN
THE FLAMEPROOF/EXPLOSION-PROOF INTEGRITY OF THE DEVICE
GE26881-Sheet 5
10
Instruction Manual
D103272X012
Figure 8. Ex e mb [ib] IIC or Ex tb IIIC Wiring Diagram 4
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex e mb [ib] IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPLCP100 then DVC6200 SISMulti-Drop
SYS
FLD
LC340 LINE
CONDITIONER
LOGIC SOLVER
OUTPUT
24VDC
(USER SUPPLIED)
1
2
NOTES:
1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 FOR FLAMEPROOF/EXPLOSION-PROOF APPROVED DIGITAL VALVE CONTROLLERS,
INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN
THE FLAMEPROOF/EXPLOSION-PROOF INTEGRITY OF THE DEVICE.
GE26881-Sheet 6
11
LCP100 Local Control Panel
August 2017
Figure 9. Ex e mb [ib] IIC or Ex tb IIIC Wiring Diagram 5
Instruction Manual
D103272X012
LCP100
Protection Method
Ex e mb [ib] IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
24VDCDVC6200 SIS then LCP100Point-to-Point
2
LOGIC SOLVER
OUTPUT
4 - 20 mA
(USER SUPPLIED)
1
NOTES:
1 WHEN 24VDC POWER IS AVAILABLE FOR THE LCP100, IT IS NOT NECESSARY TO
CONNECT THE LOOP + OF THE DIGITAL VALVE CONTROLLER TO THE LOOP + OF THE
LCP100. DOING SO WILL CAUSE THE LCP100 TO UNNECESSARILY CONSUME 4 mA AT
THE EXPENSE OF THE DIGITAL VALVE CONTROLLER
2 FOR FLAMEPROOF/EXPLOSION-PROOF APPROVED DIGITAL VALVE CONTROLLERS,
INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN
THE FLAMEPROOF/EXPLOSION-PROOF INTEGRITY OF THE DEVICE.
GE26881-Sheet 7
12
24 VDC
SOURCE
2
(USER SUPPLIED)
Instruction Manual
D103272X012
Figure 10. Ex e mb [ib] IIC or Ex tb IIIC Wiring Diagram 6
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex e mb [ib] IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
24VDCDVC6200 SIS then LCP100Multi-Drop
2
FLD
LC340 LINE
CONDITIONER
SYS
LOGIC SOLVER
OUTPUT
24VDC
(USER SUPPLIED)
1
NOTES:
1 WHEN 24VDC POWER IS AVAILABLE FOR THE LCP100, IT IS NOT NECESSARY TO
CONNECT THE LOOP + OF THE DIGITAL VALVE CONTROLLER TO THE LOOP + OF THE
LCP100. DOING SO WILL CAUSE THE LCP100 TO UNNECESSARILY CONSUME 4 mA AT
THE EXPENSE OF THE DIGITAL VALVE CONTROLLER
2 FOR FLAMEPROOF/EXPLOSION-PROOF APPROVED DIGITAL VALVE CONTROLLERS,
INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN
THE FLAMEPROOF/EXPLOSION-PROOF INTEGRITY OF THE DEVICE.
GE26881-Sheet 8
24 VDC
SOURCE
2
(USER SUPPLIED)
13
LCP100 Local Control Panel
August 2017
Figure 11. Ex ic IIC or Ex tb IIIC Wiring Diagram 1
Instruction Manual
D103272X012
LCP100
Protection Method
Ex ic IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPDVC6200 SIS then LCP100Point-to-Point
LOOP
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
INTRINSICALLY
SAFE
BARRIER
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100 WHEN
POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 9
14
2
) FOR
Instruction Manual
D103272X012
Figure 12. Ex ic IIC or Ex tb IIIC Wiring Diagram 2
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex ic IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPDVC6200 SIS then LCP100Multi-Drop
LOOP
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
INTRINSICALLY
SAFE
BARRIER
SYS
FLD
LC340 LINE
CONDITIONER
LOGIC SOLVER
OUTPUT
24 VDC
(USER SUPPLIED)
1
NOTES:
1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 10
2
) FOR
15
LCP100 Local Control Panel
August 2017
Figure 13. Ex ic IIC or Ex tb IIIC Wiring Diagram 3
Instruction Manual
D103272X012
LCP100
Protection Method
Ex ic IIC
Ex tb IIIC
LOOP
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
2
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPLCP100 then DVC6200 SISPoint-to-Point
INTRINSICALLY
SAFE
BARRIER
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100
WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
FOR SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 11
16
)
Instruction Manual
D103272X012
Figure 14. Ex ic IIC or Ex tb IIIC Wiring Diagram 4
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex ic IIC
Ex tb IIIC
LOOP
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
2
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPLCP100 then DVC6200 SISMulti-Drop
INTRINSICALLY
SAFE
BARRIER
FLD
LC340 LINE
CONDITIONER
SYS
LOGIC SOLVER
OUTPUT
24 VDC
(USER SUPPLIED)
1
NOTES:
1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 12
) FOR
17
LCP100 Local Control Panel
August 2017
Figure 15. Ex ic IIC or Ex tb IIIC Wiring Diagram 5
Instruction Manual
D103272X012
LCP100
Protection Method
Ex ic IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
24VDCDVC6200 SIS then LCP100Point-to-Point
LOOP
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
AUX +
24 VDC
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
2
INTRINSICALLY
SAFE
BARRIER
LOGIC SOLVER
OUTPUT
4 - 20 mA
(USER SUPPLIED)
1
AUX -
NOTES:
1 WHEN 24 VDC POWER IS AVAILABLE FOR THE LCP100, IT IS NOT NECESSARY TO
CONNECT THE LOOP + OF THE DIGITAL VALVE CONTROLLER TO THE LOOP + OF THE
LCP100. DOING SO WILL CAUSE THE LCP100 TO UNNECESSESARILY CONSUME 4 mA AT
THE EXPENSE OF THE DIGITAL VALVE CONTROLLER.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 13
) FOR
INTRINSICALLY
SAFE
BARRIER
24 VDC
SOURCE
(USER SUPPLIED)
18
Instruction Manual
D103272X012
Figure 16. Ex ic IIC or Ex tb IIIC Wiring Diagram 6
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex ic IIC
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
24VDCDVC6200 SIS then LCP100Multi-Drop
LOOP
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
AUX +
24 VDC
TERMINALS:
Ui = 27 VDC
Ii = N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
AUX -
2
INTRINSICALLY
SAFE
BARRIER
FLD
LC340 LINE
CONDITIONER
SYS
LOGIC SOLVER
OUTPUT
24 VDC
(USER SUPPLIED)
1
NOTES:
1 WHEN 24 VDC POWER IS AVAILABLE FOR THE LCP100, IT IS NOT NECESSARY
TO CONNECT THE LOOP + OF THE DIGITAL VALVE CONTROLLER TO THE LOOP +
OF THE LCP100. DOING SO WILL CAUSE THE LCP100 TO UNNECESSESARILY
CONSUME 4 mA AT THE EXPENSE OF THE DIGITAL VALVE CONTROLLER.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 14
) FOR
INTRINSICALLY
SAFE
BARRIER
24 VDC
SOURCE
(USER SUPPLIED)
19
LCP100 Local Control Panel
August 2017
Figure 17. Ex ia IIB or Ex tb IIIC Wiring Diagram 1
Instruction Manual
D103272X012
LCP100
Protection Method
Ex ia IIB
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPDVC6200 SIS then LCP100Point-to-Point
AUX
TERMINALS:
Ui = 30 VDC
Ii = 452 mA
Pi = 1.4 W
Ci = 0 mF
Li = 0 mH
LOOP
TERMINALS:
Ui = 30 VDC
Ii = 226 mA
Pi = 1.4 W
Ci = 0.22 mF
Li = 16.0 mH
2
INTRINSICALLY
SAFE
BARRIER
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100
WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
FOR SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 15
20
)
Instruction Manual
D103272X012
Figure 18. Ex ia IIB or Ex tb IIIC Wiring Diagram 2
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex ia IIB
Ex tb IIIC
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPDVC6200 SIS then LCP100Multi-Drop
AUX
TERMINALS:
Ui = 30 VDC
Ii = 452 mA
Pi = 1.4 W
Ci = 0 mF
Li = 0 mH
LOOP
TERMINALS:
Ui = 30 VDC
Ii = 226 mA
Pi = 1.4 W
Ci = 0.22 mF
Li = 16.0 mH
2
INTRINSICALLY
SAFE
BARRIER
FLD
LC340 LINE
CONDITIONER
SYS
LOGIC SOLVER
OUTPUT
24 VDC
(USER SUPPLIED)
1
NOTES:
1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 16
) FOR
21
LCP100 Local Control Panel
August 2017
Figure 19. Ex ia IIB or Ex tb IIIC Wiring Diagram 3
Instruction Manual
D103272X012
LCP100
Protection Method
Ex ia IIB
Ex tb IIIC
LOOP
TERMINALS:
Ui = 30 VDC
Ii = 226 mA
Pi = 1.4 W
Ci = 0.22 mF
Li = 16.0 mH
2
AUX
TERMINALS:
Ui = 30 VDC
Ii = 452 mA
Pi = 1.4 W
Ci = 0 mF
Li = 0 mH
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPLCP100 then DVC6200 SISPoint-to-Point
INTRINSICALLY
SAFE
BARRIER
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100
WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
FOR SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 17
22
)
Instruction Manual
D103272X012
Figure 20. Ex ia IIB or Ex tb IIIC Wiring Diagram 4
LCP100 Local Control Panel
August 2017
LCP100
Protection Method
Ex ia IIB
Ex tb IIIC
LOOP
TERMINALS:
Ui = 30 VDC
Ii = 226 mA
Pi = 1.4 W
Ci = 0.22 mF
Li = 16.0 mH
2
AUX
TERMINALS:
Ui = 30 VDC
Ii = 452 mA
Pi = 1.4 W
Ci = 0 mF
Li = 0 mH
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
LOOPLCP100 then DVC6200 SISMulti-Drop
INTRINSICALLY
SAFE
BARRIER
FLD
LC340 LINE
CONDITIONER
SYS
(USER SUPPLIED)
1
LOGIC SOLVER
OUTPUT
24 VDC
NOTES:
1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 18
) FOR
23
LCP100 Local Control Panel
August 2017
Instruction Manual
D103272X012
Pre‐Setup Testing
Before connecting the LCP100 to the process, conduct the following tests on the LCP100 connected to the
DVC6200 SIS.
Successful Partial Stroke Test
1. Press the Valve Test (bottom) pushbutton for more than 3 seconds (but less than 10 seconds).
2. Observe that the green light starts flashing when the valve starts moving.
3. Observe that the valve moves no more than the configured partial stroke test travel limit.
4. Observe that the valve returns to the normal operating position and the green light comes on solid.
Manually Aborted Partial Stroke Test
1. Press the Valve Test (bottom) pushbutton for more than 3 seconds (but less than 10 seconds).
2. Observe that the green light starts flashing when the valve starts moving.
3. Before the valve reaches the travel limit of the configured partial stroke test, press the Valve Test pushbutton, or
the pushbutton next to the green light.
4. Observe that the valve immediately returns to the normal operating position and the green light comes on solid.
Emergency Demand through the Logic Solver
1. Reduce the current to the DVC6200 SIS to 4 mA (for de‐energize to trip operation).
Note
For a loop powered installation, a minimum current of 8 mA is required at the trip state / “Safety Demand” for proper functioning
of the pushbuttons and lights.
2. Observe that the valve moves to its fail safe state.
3. Observe that the red light comes on solid and the yellow light stays off.
4. Press the pushbutton next to the green light and observe that the valve does not move.
5. Increase the current to the DVC6200 SIS to 20 mA (for de‐energize to trip) and observe that the valve remains in its
fail safe state.
6. Observe that the red light stays on solid and the yellow light comes on solid (ready to reset).
7. Press the pushbutton next to the green light.
8. Observe that the red light goes off, the valve moves to its normal operating position, and then the green light
comes on solid.
Emergency Demand through Local Control Panel
1. Press the pushbutton next to the red light.
2. Observe that the valve moves to it fail safe position.
3. Observe that the red light comes on solid and the yellow light comes on solid (ready to reset).
4. Press the pushbutton next to the green light.
5. Observe that the red light goes off, the valve moves to its normal operating position, and then the green light
comes on solid.
24
Instruction Manual
D103272X012
LCP100 Local Control Panel
August 2017
Setup
In order for the LCP100 to operate properly, it must be connected to a DVC6200 SIS with firmware revision 3 or later,
or a DVC6000 SIS device with firmware revision 7 or later. Once the physical connections are made, use the following
checklist to configure the LCP100. Refer to the DVC6200 SIS instruction manual (D103557X012
instruction manual (D103230X012
D Using a 475 Field Communicator select Configure > Guided Setup > Device Setup. Follow the prompts on the Field
Communicator:
Enter Supply Pressure and Unit
Enter Actuator Make, Model, and Size
Enter Partial Stroke test Starting Point, Relay Type and Zero Power Condition [select the “instrument connected to
local control panel (LCP100)” option]
D Follow the prompts to complete Device Setup. The following parameters will be automatically set under Travel
Alerts:
d Hi Hi / Lo Lo Enable - Yes
d Lo Lo Point (%) - 1
d Hi Hi Point (%) - 99
d Deadband (%) - 0.5
d DVC Power Up - Manual Reset
) if additional setup information is needed.
) or the DVC6000 SIS
D Continue to set up the digital valve controller according the normal set up procedure.
D Remember to place the instrument back in service before disconnecting.
Note
An alternative method to configure the LCP100 is through Manual Setup. Using the Field Communicator, select Configure >
Manual Setup > Instrument > Terminal Box > Edit Auxiliary Terminal Action > SIS Local Control Panel. When this setting is downloaded
to the device, an information screen will pop up advising that some additional parameters will be configured. Select Yes.
Principle of Operation
The lights indicate the state of the valve as described in table 4.
25
LCP100 Local Control Panel
August 2017
Instruction Manual
D103272X012
Table 4. Fisher LCP100 Light and Button Operation
WHAT THE LCP100 LIGHTS SHOW...POSSIBLE CONDITIONS...
SolidThe valve is in its normal operating state.- - -TripRun PST
The valve is in the process of running a partial stroke
test (PST).
Fast Blink (1/2 second)
Slow Blink (1 second)A partial stroke test has failed.
Solid
Fast Blink (1/2 second)
SolidThe valve may be reset to the normal operating state.
NOTES
1. If the green, red, and yellow lights are blinking in sequence, then the DVC6200 SIS is out of service. In point-to-point mode, the DVC6200 SIS will not respond to a trip from the logic solver.
2. Depending on the emergency shutdown valve configuration, the top button could be labeled “Valve Open” and the middle button could be labeled “Valve Close”; or vice versa. The bottom
button will aways be labeled “Valve Test”.
3. Acknowledgment of a PST failure means that the LCP100 will return the blinking green light to solid green. The PST alert will still be visible via HART communication with the DVC6200 SIS.
4. If the red and green lights are both solid the valve is throttling in mid‐travel.
5. The information contained in this table applies to firmware 9 and later.
The valve is not at its normal operating position because
the actuator pressure is low or the valve is stuck.
The valve is tripped but is stuck at the normal position.- - -- - -- - -
The valve is tripped due to loss of actuator pressure
(e.g., solenoid valve trip)
The valve is tripped due to a command from the logic
solver or LCP100.
The valve is stuck in the tripped state.- - -- - -- - The valve is at mid-travel after a trip. The valve may be
moving or stuck in this position.
PRESS INDICATED BUTTON TO...
TopMiddleBottom
Stop PSTTripStop PST
Acknowledge
PST Failure
Acknowledge
PST Failure
Acknowledge
PST Failure
- - -- - -- - -
- - -- - -- - -
Reset to
Normal State
TripRun PST
TripRun PST
TripRun PST
- - -- - -
Note
The primary safety function should be implemented by controlling the current (in point‐to‐point mode) or voltage (in multi‐drop
mode) from the logic solver. The red button is not intended to perform the primary safety function for the process.
Maintenance
WARNING
Electrostatic charge hazard. Do not rub or clean the LCP100 with solvents if a flammable vapor is present. To do so could
result in an explosion.
The LCP100 has four major components; the housing, lights, conduit connections, and electronics. If a light is not
working it can be replaced with the appropriate color. The conduit connections do not normally need replacement.
The electronics module can be replaced as an assembly without having to disconnect the conduit connections or
remove the box from its mounting.
Instrument Troubleshooting
If difficulties are experienced with the LCP100 control panel, refer to table 5.
26
Instruction Manual
D103272X012
LCP100 Local Control Panel
August 2017
Table 5. Instrument Troubleshooting
SymptomPossible CauseAction
1. Lights are not lit.1. LCP100 is not properly connected to the digital valve
2. LCP100 is properly connected to
the digital valve controller aux.
terminal, but the lights are not lit.
3. The power switch is set correctly,
but the lights are not lit.
4. The LCP100 and the digital valve
controller are properly connected,
and there is sufficient current but
the lights are not lit.
5. Lights are blinking.5. Valve is not at it's normal stop.5. Check for proper calibration. Re‐run calibration if
6. Proper calibration but lights are
blinking.
controller aux. terminal.
2. Power switch is not set correctly.2. Ensure that the power switch is set correctly. If Loop
3. Loop Power option is selected, but there is not enough
current.
4. The LED may be damaged.4. Replace LED.
6. Hi Hi / Lo Lo alerts settings not correctly set.6. Ensure that the Hi Hi / Lo Lo Alert settings are 99 and
1. Ensure that the LCP100 is connected correctly to the
digital valve controller aux. terminal, as described in the
Installation section of this manual.
Power is used, ensure that the switch position is set to
Loop Power, and NOT 24 VDC, and vice versa.
3. The Loop Power Option requires 8 mA current to
operate. Ensure that there is sufficient current.
necessary.
1% respectively. For large rotary valve, adjust settings to
98 and 2% and observe.
Parts Ordering
When corresponding with your Emerson sales office or Local Business Partner about this equipment, mention the
serial number found on the nameplate of the unit.
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Automation Solutions should
not, under any circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson Automation
Solutions may void your warranty and hazardous area approval, might adversely affect the performance of the instrument,
and could cause personal injury and property damage.
Parts Kits
DescriptionPart Number
LED Assemblies Kit (see figure 22)
Includes LED's (qty. 3); Yellow, Red, and
Green (keys 11*, 12*, and 13*)
and fasteners (qty. 6) (key 8) GE25751X012
Enclosure Labels Kit
Includes labels (qty. 6); OPEN, CLOSED,
VALVE OPEN, VALVE CLOSE,
READY TO RESET, and VALVE TESTGE25750X012
Switch Cover Kit
Includes switch actuator shroud cover (qty. 3)
and Enclosure Labels (qty. 6); OPEN, CLOSED,
VALVE OPEN, VALVE CLOSE, READY TO RESET,
and VALVE TESTGE23730X022
Parts List
Note
Contact your Emerson sales office or Local Business Partner for Part
Ordering information.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, and Bettis are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson
Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a registered trademark of
FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
28
E 2007, 2017 Fisher Controls International LLC. All rights reserved.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.