EMERSON EXD-SH2, EXD-M03 Technical Bulletin

Page 1
Technical Bulletin
EXD-SH1/2 are stand-alone universal superheat and or temperature
Circuit 1
Circuit 2
EXD-SH1
Superheat or temperature control
EXD-SH2
Superheat or temperature control
Superheat Control
Other functions: Limitation of evaporating pressure (MOP), Low pressure
h EMERSON
Monitoring of sensors and detection of sensor
Optional upload/download key (accessory) for transmission of parameter
in type screw terminals included with
EXD-M03
Part No.
Multipack (pcs)
Single pack
Controllers
EXD-SH1
Controller for single refrigeration circuit
EXD-SH2
Controller for two independent refrigeration circuits
-
807856
EXD-M03
Molex terminal with 3 m wires
-
807865
Temperature sensors
TP1-NP3
Temperature sensor with 3 m cable
804489M (20)
804489
TP1-NP6
Temperature sensor with 6 m cable
804490M (20)
804490
ECN-Z60
Ultralow Temperature sensor with 6 m cable
-
807826
Pressure transmitters: PT5N (7/16-20UNF connection)
PT5N-07M
Sensing pressure range -0.8…7 bar
805350M (25)
805350
PT5N-18M
Sensing pressure range 0…18 bar
805351M (25)
805351
PT5N-30M
Sensing pressure range 0…30 bar
805352M (25)
805352
PT5N-50M
Sensing pressure range 0…50 bar
805353M (25)
805353
PT5N-150D
Sensing pressure range 0…150 bar (1/4- 18 NPT)
805379M (25)
805379
Pressure transmitters: PT5N (Brazing connection)
PT5N-07T / PT5N-07P-FLR
Sensing pressure range -0.8…7 bar
805380M / 805390M (25)
805380 / 805390
PT5N-010P-FLR
Sensing pressure range -0.8…10 bar
805391M (25)
805391
PT5N-18T
Sensing pressure range 0…18 bar
805381M (25)
805381
PT5N-30T / PT5N-30P-FLR
Sensing pressure range 0…30 bar
805382M / 805389M (25)
805382 / 805389
PT5N-50T
Sensing pressure range 0…50 bar
805383M (25)
805383
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
controllers for air conditioning units or refrigeration systems.
Features
EXD-SH1: Control of one valve
EXD-SH2: Control of two valves in two independent circuits
Main function
switch, freeze protection and manual positioning of valve(s)
Self-adapting superheat control function in conjunction wit EX4-8 (EX4-7-FLR) and CV4-7 series
For multiple refrigerants, including ultralow temperature refrigerant R23
Modbus (RTU) communication
Integrated keyboard with two lines display
(ECN…/TP1…/PT5N…(FLR)) /stepper motor wiring failures
settings among controllers with the same setting
Low/high superheat alarm as well as other function alarms
Electrical connection via plug-
controller and Micro Molex EXD-M03 (must be ordered separately)
DIN rail mounting housing
EXD-SH2
Selection table
Type
Note: Pressure range 18 bar for system with R410A, 30 bar for R410A economizer, 50/150 bar for CO
Description
- 807855
2
Page 2
Part No.
Multipack (20 pieces)
Single pack
M12 Plug and cable for pressure transmitters PT5N(FLR)
PT4-M15
1.5 m
804803M
804803
PT4-M30
3.0 m
804804M
804804
PT4-M60
6.0 m
804805M
804805
PT4-M60 FLR
6.0 m - 804806
Uninterruptible Power supply
ECP-024
Backup battery with two outputs for two controllers
-
804558
K09-P00
Electrical Terminal Kit for ECP-024
-
804560
EXD-PM
Super cap for only EXD-SH1 (two pieces of EXD-PM required for one EXD-SH2)
Temperature control in normal sense
1tAL 1tst 1tAH
Temperature control in reverse sense
1tAL 1tst/ 1tAH
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Accessories
Type Description
- 807854
Description of functions
Controllers are featured with a main function as superheat controller or temperature controller. The main function is selectable.
Superheat control of evaporators or economizers
This function requires the connection of temperature sensor(s) as well as pressure transmitters(s). The other functions are:
MOP control: enables the limitation of saturated temperature of suction line (outlet of evaporator/economizer)
Low pressure behaves similar to low pressure switch including alarm conditions
Freeze protection is based on saturated temperature from converting measuring suction pressure. It provides alarm condition
below certain adjusted temperature.
Temperature controller
The function is to maintain desired temperature by modulating refrigerant mass flow. If controller is operated as temperature controller, the connection of pressure transmitter is not required. In order to fulfill varieties of the applications, the refrigerant mass flow variation can be set according temperature increase or decrease.
(A: Mass flow increases if temperature rises)
Valve opening %
100%
Temperature 0%
Examples of applications:
Temperature control by throttling suction mass flow (normal sense, A)
Temperature control by modulating hot gas into inlet or outlet of evaporators (reverse sense, B)
Discharge temperature control by injecting liquid (normal sense, A)
Head pressure control by means of temperature control (normal sense, A)
Valve opening %
100%
Temperature 0%
(B: Mass flow decreases if temperature rises)
2
EXD-SH12_TB_EN_0720_R08.docx
Page 3
Circuit 1 (EXD-SH1/SH2)
Electronic expansion valve circuit 1 (EXV1)
WH-white BK-black BL-blue BN-brown
*) Parameter 2uP with No. 8 = only
Download/upload key
Electronic expansion valve circuit 2 (EXV2)
WH-white BK-black BL-blue BN-brown
2 & 8
Temperature sensor circuit 1
23 & 24
RS485 (+/-terminal)
Alarm relay circuit 1 (C, NO) – Suitable for 24 VAC/DC
PT5N… circuit 1 & circuit 2 (white wire: 4…20 mA signal)
Alarm relay circuit 2 (C, NO) – Suitable for 24 VAC/DC
+ 12 VDC Voltage input for PT5N… (brown wire)
Digital input circuit1 (DI1) – Dry contact, potential free
Alternative ratiometric third Party Pressure Transmitter:
Digital input circuit 2 (DI2) – Dry contact, potential free
Pressure transmitter circuit 1 & circuit 2 (0.5…4.5 V signal)
11
+ 5 VDC voltage input
Fuse EXD-SH1 (1A), EXD-SH2 (2A)
6,12,13, 18,32-34
T
UPS for up to two controllers
One supercap for one EXD
See parameter 2uP *
P
Two supercaps for one EXD
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Wiring
Wiring options: UPS (ECP-024) /Supercap (EXD-PM)
Circuit 2 (EXD-SH2)
1 & 7 Supply voltage 24 VAC/DC
3 & 8 Temperature sensor circuit 2 25 & 26
14-17
19-22
-SH1
-SH2
EXV-M… Electrical plug: wire colors
EXV-M… Electrical plug: wire colors
Pressure sensor circuit 1 is used
4 & 5
9
4 & 5
10 GND Ground
Note: No hard failure detection if ground wire of transmitter to be interrupted.
EXD-SH12_TB_EN_0720_R08.docx
27 & 28
29 & 30
31 & 30
35 & 36 Battery/Super capacitor connection terminal
Not used (Terminals on EXD-SH12)
3
Page 4
EX
CV
Supply voltage
24 VAC/DC ±10%, 50/60 Hz
Mounting
DIN rail mounted
Temperatures
operating/ surrounding
0…+55°C
20…85% non-condensing
Suitable for removable screw
Included in controller delivery
Accessory
3 m cable)
Protection class
IP 00
Housing
Self-extinguishing ABS
Compliance
EMC, RoHS,
Weight
320 g
Analogue input(s): NTC Temperature sensor Analogue input: PT1000 Temperature sensor
TP1-N… (-45…+150°C operating range) ECN-Z60 (-80…-40°C sensing range)
PT5N…
(total error: ≤ 1%)
Digital input(s)
Dry contact, potential free
Digital output(s): Alarm relay(s)
Contact is open: During normal operation and supply power OFF
Communication
RS485 RTU Modbus, two wires
Stepper motor output
Valves: EX4-8 (EX4-7-FLR), CV4-7
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Available configuration options
R22, R134a, R507, R404A, R407C, R410A, R124,
Refrigerants
Main function Superheat or and temperature control Superheat control
Pressure transmitters PT5N… or 3rd party ratio metric PT5N….
Note:
EXD-SH1/2 IS NOT ATEX APPROVED!
Technical Data: EXD-SH1/2
R744, R407A, R407F, R23, R32, R1234ze, R448A, R449A, R450A, R513A, R290, R1270, R454C
Selectable Valves
R744 (CO
)
2
Power consumption
Terminals 1 to 12 Suitable for 12 poles molex plug Relative humidity
Terminals 13 to 36
Marking
Input, Output EXD-SH1/2
Analogue input(s): 4…20 mA pressure transmitters Analogue input(s): 0.5…4.5 V pressure transmitters
Contact is closed: During alarm condition
EXD-SH1: Max. 25 VA EXD-SH2: Max. 50 VA
version: wire size 0.14…1.5 mm2
,
Description Specification
(12 poles molex plug with
Third party ratio metric pressure transmitters
Resistive Load 24 VAC/DC, max. 1 A Inductive Load 24 V AC, max. 0.5 A
storage
-25…+60°C
Type: EXD-M03 (to be ordered separately)
4
EXD-SH12_TB_EN_0720_R08.docx
Page 5
Supply voltage
24 VAC/DC ±10%, 50/60 Hz
Protection class
IP 20
Output voltage
12 VDC
Mounting
DIN rail mounted
Temperatures
operating/ surrounding
-10…+60°C
Power consumption
12 VA
Housing
Self-extinguishing ABS
Suitable for removable screw version: wire size 0.14…1.5 mm2
Output: to driver/controller
Suitable for one EXD-SH1 Two EXD-PM for one EXD-SH2
Charging time
60 seconds
Weight
125 g
Max. cable length
EXD-SH1/2
Backup battery type
Lead acid gel rechargeable battery
Protection class
IP 20
Number of backup batteries
Supply voltage
24 VAC ±10%, 50-60 Hz
Housing
Aluminum
Screw terminals for wire size 0.5…2.5 mm2
Number of outputs to drivers
< 90% non-condensing
K09-U00 Part No: 804559
Temperatures
operating/ surrounding
-10…+60°C
Weight
1200 g
,
70
35
35
117,5
Ø4,3
110
1
2
5
,
5
4
5
59,5
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Optional EXD-PM Supercap
Max. output current
Terminals
- 1.2 A
- 350 mA during charging
Storage
Relative humidity
between EXD-PM and
50 cm AWG18 wire size
Marking
Optional Uninterruptible Power Supply ECP-024
2, each 12 VDC, 0.8 Ah Mounting DIN rail mounted
Output voltage, UB 18 VDC Connection
2 Relative humidity
Battery recharge time approximately 2 hours Accessories: Terminals
Storage
-20…+65°C Marking
-20…+70°C
20…85% non-condensing
,
Dimensions (mm)
EXD-SH1/2 or EXD-PM ECP-024
EXD-SH12_TB_EN_0720_R08.docx
5
Page 6
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Communication
The use of communication is not necessary/mandatory; however, the communication is available for connection to upper level of system controller (third party controller) in order to perform data and commands transfer as well as data logging. EXD-SH1/2 act as slave and third party controller is master. In case of several EXD-SH1/2 connections to master, each driver needs to be addressed for proper communication.
Bus topology
ModBus protocol details
Mode: RTU Modbus slave address range: 1 to 127 (parameter Adr) Baud rate: 9600 bps, 19200 bps (default, parameter Br) Start bit: 1 Data bits: 8 Parity: even (default), no parity (parameter Par) Stop bits: 1 Master response timeout: 500ms
Transmission Details ModBus register address ranges
Read-only data: Starting address: 0x0100 (256) Writable data: Starting address: 0x0200 (512) Configuration data: Starting address: 0x0300 (768)
6
EXD-SH12_TB_EN_0720_R08.docx
Page 7
Function code
1 Byte
0x03
Starting Address
2 Bytes
0x0000 to 0xFFFF
Register count
2 Bytes
1 to 125 (0x7D)
Function code
1 Byte
0x03
Byte count
1 Byte
2 x N*
Holding Registers
N* x 2 Bytes
Error code
1 Byte
0x83
Exception code
1 Byte
01 or 02 or 03
Function code
1 Byte
0x06
Starting Address
2 Bytes
0x0000 to 0xFFFF
Value
2 Bytes
0x0000 to 0xFFFF
Function code
1 Byte
0x06
Starting Address
2 Bytes
0x0000 to 0xFFFF
Value
2 Bytes
0x0000 to 0xFFFF
Error code
1 Byte
0x86
Exception code
1 Byte
01 or 02 or 03
Function code
1 Byte
0x10
Start Address
2 Bytes
0x0000 to 0xFFFF
Register count
2 Bytes
0x0001 to 0x0078
Byte count
1 Byte
2 x N
Registers values
2 x N Bytes
Value
Function code
1 Byte
0x10
Starting Address
2 Bytes
0x0000 to 0xFFFF
Register count
2 Bytes
0x0001 to 0x0078
Error code
1 Byte
0x90
Exception code
1 Byte
01 or 02 or 03
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability

Read Data transmission

Available through Modbus Function code 03 (0x03) Read Holding Registers
Request
Response
*N = Quantity of Input Registers
Error
01 = Function code not supported 02 = Starting Address or register count out of range 03 = Register count out of range
Write Data transmission (single register)
Available through Modbus Function code 06 (0x06) Write Holding Register
Request
Response
Error
01 = Function code not supported 02 = Starting Address out of range
Write Data transmission (multiple registers)
Available through Modbus Function code 16 (0x10) Write Holding Registers
Request
N = register count.
Response
Error
01 = Function code not supported 02 = Register Address invalid 03 = Register Value out of range
EXD-SH12_TB_EN_0720_R08.docx
7
Page 8
256 / 0x100
Software version
0 = superheat control
2 = reverse temperature control
258 / 0x102
Valve opening circuit 1
1/100%
0x0000: No demand 0x0001: Demand
260 / 0x104
Digital output circuit 1
0x0001: alarm relay
261 / 0x105
P1 suction pressure circuit 1
1/100 barg
262 / 0x106
T1 suction temperature circuit 1
1/100°C
263 / 0x107
Sat. Temp circuit 1
1/100°C
0 = No failure 1 = Failure
0 = No failure 1 = Failure
0x0001 = N/A 0x0002 = Low pressure
0x0040 = Min. Temp (Temp. control)
0x0001 = Temp sensor 1 0x0002 = Temp sensor 2 (SH2)
0x0100 = Config inconsistency 2 0x0200 = Power Failure
0 = OFF 5 = Alarm
4 = Closing
269 / 0x10D
Superheat set point circuit 1
1/100 K
270 / 0x10E
Superheat circuit 1
1/100 K
271 / 0x10F
Valve opening circuit 2
1/100%
0 = no demand 1 = demand
273 / 0x111
Digital output circuit 2
0x0001: alarm relay
274 / 0x112
P2 suction pressure circuit 2
1/100 bar
275 / 0x113
T2 suction temperature circuit 2
1/100°C
276 / 0x114
Sat. Temp circuit 2
1/100°C
0 = No failure 1 = Failure
278 / 0x116
Temp 2 sensor failure circuit 2
0 = No failure 1 = Failure
279 / 0x117
Functional alarm circuit 2
0x0001 = N/A 0x0002 = Low pressure
0x0010 = Freeze
280 / 0x118
Application state circuit 2
0 = OFF 5 = Alarm
4 = Closing
281 / 0x119
Superheat setpoint circuit 2
1/100 K
282 / 0x11A
Superheat circuit 2
1/100 K
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Read-only variables
Modbus address
dec. / hex.
Description Unit Remarks
Circuit 1
257 / 0x101 Main function, circuit 1
259 / 0x103 Digital input circuit 1
264 / 0x108 Pressure 1 sensor failure circuit 1
265 / 0x109 Temp 1 sensor failure circuit 1
266 / 0x10A Functional Alarm set circuit 1
267 / 0x10B Hardware alarm set
268 / 0x10C Application state circuit 1
1 = temperature control
0x0004 = High superheat 0x0008 = Low superheat 0x0010 = Freeze 0x0020 = Max. Temp (Tem p. control)
0x0004 = Pressure sensor 0x0008 = Pressure sensor 2 (SH2) 0x0010 = Stepper 1 0x0020 = Stepper 2 (SH2) 0x0040 = Modbus timeout (3 sec.) 0x0080 = Config inconsistency 1
1 = Waiting startup (valve ref pending) 6 = Manual mode 2 = Startup 7 = Power fail 3 = Control 8 = MOP
272 / 0x110 Digital input circuit 2
277 / 0x115 Pressure 2 sensor failure circuit 2
Circuit 2
0x0004 = High superheat 0x0008 = Low superheat
1 = Waiting startup (valve ref pending) 6 = Manual mode 2 = Startup 7 = Power fail 3 = Control 8 = MOP
8
EXD-SH12_TB_EN_0720_R08.docx
Page 9
Description
512 / 0x200
Factory default
1 = do a factory default
513 / 0x201
Future use
514 / 0x202
Alarm reset
1 = Resets alarms (only the alarms which are set as manual reset)
Manual mode Circuit 1
0 = off 1 = on
516 / 0x204
1HP
Manual valve opening Circuit 1
%
only active while manual mode is ”on”
Alternative to digital input, circuit 1 via Modbus
Demand circuit 1
0 1 = enabled
Pressure circuit 1 via Modbus
Pressure if 1uP selection is Modbus Range: -0.1 to 150 barg Minimum update rate: 1s Alarm timeout: 3 sec.
Digital output circuit 1
To set the relay 1 manually, only active when manual mode circuit1 is ”
0 1 = on
Manual mode
0 = off 1 = on
521 /0x209
2HP
Manual valve opening Circuit 2
%
only active while manual mode 2 = on
Alternative to digital input, circuit 2 via Modbus
Demand circuit 2
0 1 = enabled
Pressure
Pressure if 2uP selection is Modbus Range: -0.1 to 150 barg Minimum update rate: 1s Alarm timeout: 3 sec.
Digital output circuit 2
To set the relay 2 manually, only active when manual mode circuit 2 is “
0 1 = on
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Writable variables
Modbus address
dec. / hex.
Display
code
Units Remarks
515 / 0x203 1Ho
517 / 0x205
518 / 0x206
519 / 0x207
520 / 0x208 2Ho
522 / 0x20A
523 / 0x20B
524 / 0x20C
Note: References to control circuit 2 of EXD-SH2 are invisible in configuration/write list if disabled.
circuit 2 via Modbus 1/100 barg
1/100 barg
Circuit 2
= disabled
on”
= off
= disabled
on”
= off
EXD-SH12_TB_EN_0720_R08.docx
9
Page 10
768 /0x300
H5
Password
12
1 - 1999
769 /0x301
Adr
Modbus address
1 1 - 127
0 = 9600 baud 1 = 19200 baud
0 = parity even 1 = no parity
0 = circuit 2 disabled 1 = circuit 2 enabled Only EXD-SH2
0 = °C, K, barg 1 = °F, psig
based.
775 / 0x307
Future use
776 / 0x308
Future use
Changes only allowed if circuit 1 is in “OFF” state
2 = Temperature control Reverse sense
0 = standard control
3 = adjustable fixed PID
Changes only allowed if circuit 1 is in “OFF” state
18 = R1270 19 = R454C
Changes only allowed if circuit 1 is in “OFF” state
8 = Modbus
781 / 0x30D
1Prr
Ratio metric range 1
1/10 bar
30
3 - 60
If ratio metric is used
Changes only allowed if circuit 1 is in “OFF” state
12 = CV7
783 / 0x30F
1uF
Valve scaling 1
%
100
5 - 100
784 / 0x310
1uu
Start opening valve1
%
10
0 - 100
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Basically 2 variants are possible to set the parameters:
1. Configuration parameters in flash memory - Max. 1000 overwrite cycle limitation!
2. Configuration parameters in RAM memory - unlimited overwrite cycles possible
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation
Modbus address
dec. / hex.
770 / 0x302 br Modbus baudrate 0 0 - 1
771 / 0x303 PAr Modbus parity 0 0 - 1
773 / 0x305 -C2 Circuit 2 Enabled
Display
Note: In case of power failure, the stored data from the RAM memory will be lost and controller switches to the configuration data. (Factory setting)
code
Description Unit
2
1 0 - 1
Default
value
Range Remarks
774 / 0x306 -uC Units conversion 0 0 - 1
Note: 2) References to control circuit 2 if EXD-SH2 are invisible in configuration/write list if disabled
Modbus address
dec. / hex.
777 / 0x309 1Fct Function circuit 1 0 0 - 2
778 / 0x30A 1u4 Control mode circuit 1 0 0 - 3
779 / 0x30B 1u0 Refrigerant circuit 1 1 0 - 19
780 / 0x30C 1uP Pressure sensor type 1 1 0 - 8
Display
code
Description Unit
Default
value
Circuit 1
Range Remarks
This parameter only affects the display. Internally (as well as for MODBUS communication) the units are always SI-
0 = superheat control 1 = Temperature control Normal sense
1 = slow control 2 = intermediate control
0 = R22 1 = R134a 2 = R507 3 = R404A 4 = R407C 5 = R410A 6 = R124 7 = R744 8 = R407A 9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A 15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x 3 = PT5N-50x 4 = PT5N-150 5 = PT5N-10P-FLR 6 = Ratio metric(gauge) 7 = Ratio metric(absolute)
782 / 0x30E 1ut Valve type 1 0 0 - 12
10
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A 4 = N/A 5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
EXD-SH12_TB_EN_0720_R08.docx
Page 11
785 / 0x311
1u9
Start opening duration valve 1
s 5 0 - 120
0 = disabled
2 = enabled manual reset
787 / 0x313
1u5
Superheat setpoint circuit 1
1/10 K 6 0.5 - 30
Range = 3 – 30K with 1uL = 1 or 2
0 = disabled 1 = enabled
789 / 0x315
1u3
MOP sat. temp. limit circuit1
1/10°C
see MOP table (page 16)
0 = disabled
2 = enabled manual reset
Low pressure alarm cut-out circuit1
Low pressure alarm delay circuit1
Low pressure alarm cut-in circuit1
0 = disabled
2 = enabled manual reset
795 / 0x31B
1P2
Freeze alarm cut-out circuit1
1/10°C 0 -5 - 5
796 / 0x31C
1P5
Freeze alarm delay circuit1
s
30
5 - 199
High superheat alarm mode circuit 1
0 = disabled 1 = enabled auto-reset
High superheat alarm setpoint circuit 1
High superheat alarm delay circuit 1
800 / 0x320
1tSt
Temperature set point
1/10°C 4 -80 - 50
801 / 0x321
1tbd
Temperature band
1/10 K 2 1 - 10
0 = disabled 1 = enabled
Min. temperature alarm set­point
804 / 0x324
1tdL
Min. temperature alarm delay
min 3 1 - 10
Max. temperature alarm set­point
806 / 0x326
1tdH
Max. temperature alarm delay
min 3 1 - 10
807 / 0x327
Future use
808 / 0x328
Future use
0 = TP1-N… 1 = ECN-Z60
Superheat control circuit1 fixed PID Kp factor
Superheat control circuit1 fixed PID Ti factor
Superheat control circuit1 fixed PID Td factor
Display 1/10K, Kd = Kp*Td
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation (continued)
Modbus address
dec. / hex.
Display
code
Description Unit
Default
value
Range Remarks
786 / 0x312 1uL
788 / 0x314 1u2 MOP mode circuit 1 1 0 - 1
790 / 0x316 1P9
791 / 0x317 1PA
792 / 0x318 1Pb
793 / 0x319 1Pd
794 / 0x31A 1P4 Freeze alarm mode circuit1 0 0 - 2
797 / 0x31D 1uH
798 / 0x31E 1uA
799 / 0x31F 1ud
Low superheat alarm mode circuit 1
Low pressure alarm mode circuit1
1 0 - 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
0 0 - 1
1/10 K 30 16 - 40
min 3 1-15
1 = enabled auto-reset
1 = enabled auto-reset
1 = enabled auto-reset
802 / 0x322 1tAF Temperature Alarm Enable 0 0 - 1
803 / 0x323 1tAL
805 / 0x325 1tAH
809 / 0x329 1tt- Temperature sensor type 0 0 - 1
852 / 0x354 1P-
853 / 0x355 1i-
854 / 0x356 1d-
1/10°C 0 -50 - 50
1/10°C 15 -50 - 50
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
EXD-SH12_TB_EN_0720_R08.docx
11
Page 12
0 = standard control
3 = adjustable fixed PID
Changes only allowed if circuit 2 is in OFF state
18 = R1270 19 = R454C
Changes only allowed if circuit 2 is in “OFF” state
circuit1
813 / 0x32D
2Prr
Ratio metric range circuit 2
1/10 bar
30
3 - 60
If ratio metric is used
Changes only allowed if circuit 2 is in “OFF” state
12 = CV7
815 / 0x32F
2uF
Valve scaling circuit 2
%
100
5 - 100
816 / 0x330
2uu
Start opening valve circuit 2
%
10
0 - 100
Start opening duration valve circuit 2
0 = disabled
2 = enabled manual reset
819 / 0x333
2u5
Superheat setpoint circuit 2
1/10 K
6
0.5 - 30
Range = 3 – 30K with 1uL = 1 or 2
0 = disabled 1 = enabled
821 / 0x335
2u3
MOP sat. temp. limit circuit 2
1/10°C
see MOP table (page 16)
0 = disabled
2 = enabled manual reset
Low pressure alarm cut-out circuit 2
Low pressure alarm delay circuit 2
Low pressure alarm cut-in circuit 2
0 = disabled
2 = enabled manual reset
827 / 0x33B
2P2
Freeze alarm cut-out circuit 2
1/10°C
0
-5 - 5
828 / 0x33C
2P5
Freeze alarm delay circuit 2
s
30
5 - 199
High superheat alarm mode circuit 2
0 = disabled 1 = enabled auto-reset
High superheat alarm setpoint circuit 2
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation (continued)
Modbus address
dec. / hex.
Display
code
Description Unit
Default
value
Circuit 2
Range Remarks
810 / 0x32A 2u4 Control mode circuit 2 0 0 - 3
811 / 0x32B 2u0 Refrigerant circuit 2 1 0 - 19
812 / 0x32C 2uP Pressure sensor type circuit 2 1 0 - 9
814 / 0x32E 2ut Valve type circuit 2 0 0 - 12
817 / 0x331 2u9
818 / 0x332 2uL
Low superheat alarm mode circuit 2
s 5 0 - 120
1 0 - 2
1 = slow control 2 = intermediate control
0 = R22 1 = R134a 2 = R507 3 = R404A 4 = R407C 5 = R410A 6 = R124 7 = R744 8 = R407A 9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A 15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x 3 = PT5N-50x 4 = PT5N-150 5 = PT5N-10P-FLR 6 = Ratio metric(gauge) 7 = Ratio metric(absolute) 8 = Modbus 9 = Pressure sensor type and refrigerant settings from
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A 4 = N/A 5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
1 = enabled auto-reset
820 / 0x334 2u2 MOP mode circuit 2 1 0 - 1
822 / 0x336 2P9
823 / 0x337 2PA
824 / 0x338 2Pb
825 / 0x339 2Pd
826 / 0x33A 2P4 Freeze alarm mode circuit 2 0 0 - 2
829 / 0x33D 2uH
830 / 0x33E 2uA
Low pressure alarm mode circuit 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
0 0 - 1
1/10 K 30 16 - 40
1 = enabled auto-reset
1 = enabled auto-reset
12
EXD-SH12_TB_EN_0720_R08.docx High superheat alarm delay circuit 2
Page 13
0 = TP1-N… 1 = ECN-Z60
Superheat control circuit 2 fixed PID Kp factor
Superheat control circuit 2 fixed PID Ti factor
Superheat control circuit 2 fixed PID Td factor
Display 1/10K, Kd = Kp*Td
1792 / 0x700
NA
1793 / 0x701
NA
1794 / 0x702
NA
1795 / 0x703
NA
0 = circuit 2 disabled 1 = circuit 2 enabled Only EXD-SH2
0 = °C, K, barg
This parameter only affects the display. Internally (as well
-
based.
1799 / 0x707
Future use
1800 / 0x708
Future use
Changes only allowed if circuit 1 is in “OFF” state
2 = Temperature control Reverse sense
0 = standard control
3 = adjustable fixed PID
Changes only allowed if circuit 1 is in “OFF” state
18 = R1270 19 = R454C
Changes only allowed if circuit 1 is in “OFF” state
8 = Modbus
1805 / 0x70D
1Prr
Ratio metric range 1
1/10 bar
30
3 - 60
If ratio metric is used
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation (continued)
Modbus address
dec. / hex.
Display
code
Description Unit
Default
value
Range Remarks
831 / 0x33F 2ud
832 / 0x340 2tt- Temperature sensor type 0 0 - 1
833 / 0x341 2P-
834 / 0x342 2i-
835 / 0x343 2d-
min 3 1-15
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
2. Configuration parameters in RAM memory - unlimited overwrite cycles
Note: In case of power failure, the stored data from the RAM memory will be lost and switch to the configuration data. (Factory setting)
Modbus address
dec. / hex.
1797 / 0x705 -C2
1798 / 0x706 -uC Units conversion 0 0 - 1
Display
code
Description Unit
Circuit 2 Enabled
3
Default
value
1 0 - 1
Range Remarks
1 = °F, psig
as for MODBUS communication) the units are always SI
Note: 3) References to control circuit 2 of EXD-SH2 are invisible in configuration/write list if disabled
Modbus address
dec. / hex.
1801 / 0x709 1Fct Function circuit 1 0 0 - 2
1802 / 0x70A 1u4 Control mode circuit 1 0 0 - 3
1803 / 0x70B 1u0 Refrigerant circuit 1 1 0 - 19
1804 / 0x70C 1uP Pressure sensor type 1 1 0 - 8
Display
code
Description Unit
Default
value
Circuit 1
Range Remarks
0 = superheat control 1 = Temperature control Normal sense
1 = slow control 2 = intermediate control
0 = R22 1 = R134a 2 = R507 3 = R404A 4 = R407C 5 = R410A 6 = R124 7 = R744 8 = R407A 9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A 15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x 3 = PT5N-50x 4 = PT5N-150 5 = PT5N-10P-FLR 6 = Ratio metric(gauge) 7 = Ratio metric(absolute)
EXD-SH12_TB_EN_0720_R08.docx
13
Page 14
Changes only allowed if circuit 1 is in “OFF” state
12 = CV7
1807 / 0x70F
1uF
Valve scaling 1
%
100
5 - 100
1808 / 0x710
1uu
Start opening valve1
%
10
0 - 100
Start opening duration valve 1
0 = disabled
2 = enabled manual reset
1811 / 0x713
1u5
Superheat setpoint circuit 1
1/10 K
6
0.5 - 30
Range = 3 – 30K with 1uL = 1 or 2
0 = disabled 1 = enabled
1813 / 0x715
1u3
MOP sat. temp. limit circuit1
1/10°C
see MOP table (page 16)
0 = disabled
2 = enabled manual reset
Low pressure alarm cut-out circuit1
Low pressure alarm delay circuit1
Low pressure alarm cut-in circuit1
0 = disabled
2 = enabled manual reset
1819 / 0x71B
1P2
Freeze alarm cut-out circuit1
1/10°C 0 -5 - 5
1820 / 0x71C
1P5
Freeze alarm delay circuit1
s
30
5 - 199
High superheat alarm mode circuit 1
0 = disabled 1 = enabled auto-reset
High superheat alarm setpoint circuit 1
High superheat alarm delay circuit 1
1824 / 0x720
1tSt
Temperature set point
1/10°C
4
-80 - 50
1825 / 0x721
1tbd
Temperature band
1/10 K
2
1 - 10
0 = disabled 1 = enabled
Min. temperature alarm set­point
Min. temperature alarm delay
Max. temperature alarm set­point
Max. temperature alarm delay
1831 / 0x727
Future use
1832 / 0x728
Future use
0 = TP1-N… 1 = ECN-Z60
Superheat control circuit1 fixed PID Kp factor
Superheat control circuit1 fixed PID Ti factor
Superheat control circuit1 fixed PID Td factor
Display 1/10K, Kd = Kp*Td
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
2. Configuration parameters in RAM memory - unlimited overwrite cycles possible (continued)
Modbus address
dec. / hex.
1806 / 0x70E 1ut Valve type 1 0 0 - 12
Display
code
Description Unit
Default
value
Range Remarks
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A 4 = N/A 5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
1809 / 0x711 1u9
1810 / 0x712 1uL
1812 / 0x714 1u2 MOP mode circuit 1 1 0 - 1
1814 / 0x716 1P9
1815 / 0x717 1PA
1816 / 0x718 1Pb
1817 / 0x719 1Pd
1818 / 0x71A 1P4 Freeze alarm mode circuit1 0 0 - 2
1821 / 0x71D 1uH
1822 / 0x71E 1uA
1823 / 0x71F 1ud
Low superheat alarm mode circuit 1
Low pressure alarm mode circuit1
s 5 0 - 120
1 0 - 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
0 0 - 1
1/10 K 30 16 - 40
min 3 1-15
1 = enabled auto-reset
1 = enabled auto-reset
1 = enabled auto-reset
1826 / 0x722 1tAF Temperature Alarm Enable 0 0 - 1
1827 / 0x723 1tAL
1828 / 0x724 1tdL
1829 / 0x725 1tAH
1830 / 0x726 1tdH
1833 / 0x729 1tt- Temperature sensor type 0 0 - 1
1876 / 0x754 1P-
1877 / 0x755 1i-
1878 / 0x756 1d-
1/10 °C 0 -50 - 50
min 3 1 - 10
1/10°C 15 -50 - 50
min 3 1 - 10
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
14
EXD-SH12_TB_EN_0720_R08.docx
Page 15
0 = standard control
3 = adjustable fixed PID
Changes only allowed if circuit 2 is in “OFF” state
18 = R1270 19 = R454C
Changes only allowed if circuit 2 is in “OFF” state
circuit1
1837 / 0x72D
2Prr
Ratio metric range circuit 2
1/10 bar
30
3 - 60
If ratio metric is used
Changes only allowed if circuit 2 is in “OFF” state
12 = CV7
1839 / 0x72F
2uF
Valve scaling circuit 2
%
100
5 - 100
1840 / 0x730
2uu
Start opening valve circuit 2
%
10
0 - 100
Start opening duration valve circuit 2
0 = disabled
2 = enabled manual reset
1843 / 0x733
2u5
Superheat setpoint circuit 2
1/10 K
6
0.5 - 30
Range = 3 – 30K with 1uL = 1 or 2
0 = disabled 1 = enabled
1845 / 0x735
2u3
MOP sat. temp. limit circuit 2
1/10°C
see MOP table (page 16)
0 = disabled
2 = enabled manual reset
Low pressure alarm cut-out circuit 2
Low pressure alarm delay circuit 2
Low pressure alarm cut-in circuit 2
0 = disabled
2 = enabled manual reset
Freeze alarm cut-out circuit 2
1852 / 0x73C
2P5
Freeze alarm delay circuit 2
s
30
5 - 199
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
2. Configuration parameters in RAM memory - unlimited overwrite cycles (continued)
Modbus address
dec. / hex.
Display
code
Description Unit
Default
value
Circuit 2
Range Remarks
1834 / 0x72A 2u4 Control mode circuit 2 0 0 - 3
1835 / 0x72B 2u0 Refrigerant circuit 2 1 0 - 19
1836 / 0x72C 2uP
1838 / 0x72E 2ut Valve type circuit 2 0 0 - 12
1841 / 0x731 2u9
1842 / 0x732 2uL
Pressure sensor type circuit 2
Low superheat alarm mode circuit 2
1 0 - 9
s 5 0 - 120
1 0 - 2
1 = slow control 2 = intermediate control
0 = R22 1 = R134a 2 = R507 3 = R404A 4 = R407C 5 = R410A 6 = R124 7 = R744 8 = R407A 9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A 15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x 3 = PT5N-50x 4 = PT5N-150 5 = PT5N-10P-FLR 6 = Ratio metric(gauge) 7 = Ratio metric(absolute) 8 = Modbus 9 = Pressure sensor type and refrigerant settings from
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A 4 = N/A 5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
1 = enabled auto-reset
1844 / 0x734 2u2 MOP mode circuit 2 1 0 - 1
1846 / 0x736 2P9
1847 / 0x737 2PA
1848 / 0x738 2Pb
1849 / 0x739 2Pd
1850 / 0x73A 2P4 Freeze alarm mode circuit 2 0 0 - 2
1851 / 0x73B 2P2
Low pressure alarm mode circuit 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
1/10°C 0 -5 - 5
1 = enabled auto-reset
1 = enabled auto-reset
EXD-SH12_TB_EN_0720_R08.docx
15
Page 16
High superheat alarm mode circuit 2
0 = disabled 1 = enabled auto-reset
High superheat alarm setpoint circuit 2
High superheat alarm delay circuit 2
0 = TP1-N… 1 = ECN-Z60
Superheat control circuit 2 fixed PID Kp factor
Superheat control circuit 2 fixed PID Ti factor
Superheat control circuit 2 fixed PID Td factor
Display 1/10K, Kd = Kp*Td
Min.
Max.
Default
Min.
Max.
Default
Min.
Max.
Default
R22
-70
50
+13
R744
-40
-4
-5
R449A
-57
66
+12
R134a
-57
66
+15
R407A
-66
48
+10
R450A
-57
66
+19
R507
-75
42
+7
R407F
-66
48
+10
R513A
-57
66
+13
R404A
-76
42
+7
R23
-70
-18
-40
R290
-66
48
+15
R407C
-66
48
+15
R32
-52
30
+15
R1270
-66
48
+15
R410A
-52
30
+15
R1234ze
-57
66
+24
R454C
-66
48
+17
R124
-45
91
+50
R448A
-57
66
+12
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
2. Configuration parameters in RAM memory - unlimited overwrite cycles (continued)
Modbus address
dec. / hex.
Display
code
Description Unit
Default
value
Range Remarks
1853 / 0x73D 2uH
1854 / 0x73E 2uA
1855 / 0x73F 2ud
1856 / 0x740 2tt- Temperature sensor type 0 - 1
1857 / 0x741 2P-
1858 / 0x742 2i-
1859 / 0x743 2d-
0 0 - 1
1/10 K 30 16 - 40
min 3 1-15
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
MOP saturation temperature limit table
Refrigerant
°C
Refrigerant
°C
Refrigerant
°C
EXD-SH12_TB_EN_0720_R08.docx
Emerson Climate Technologies GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specications, designs and technical data contained in this document are subject to modi cation by us without prior notice. Illustrations are not binding.
The Emerson Climate Technologies logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co.
Loading...