Resistive Load 24 V AC/DC, 1 A
Inductive Load 24 V AC/DC, 0.5 A
Contact is closed:
During alarm condition
Contact is open:
During normal operation and supply power OFF
Valves: EX4-8 (EX4-7-FLR)
CV4-7
Mounting
For standard DIN rail
Operating condition
Digital input status
Compressor starts/run
External contact to be closed (Start)
Compressor stops
External contact to be open (Stop)
EXD-SH1/2 Controller with ModBus communication
General information:
EXD-SH1/2 are stand-alone superheat and or temperature controllers. EXD-SH1 is
intended for operation of one bipolar electrical control valve whereas EXD-SH2 is
designed for operation of two independent bipolar electrical control valves.
A table of the available application possibilities is listed below:
capability for electrical control valves
• Disposal: Electrical and electronic waste must NOT be disposed of with other
commercial waste. Instead, it is the user responsibility to pass it to a
designated collection point for the safe recycling of Waste Electrical and
Electronic Equipment (WEEE directive 2012/19/EU). For further
information, contact your local environmental recycling center.
Temperature setting in normal sense
Notes:
It is possible to use only circuit 1 from EXD-SH2. In this case, the circuit 2 must
be disabled (C2 parameter) and the sensors and the valve for the second circuit
are not needed.
ModBus communication is described in a Technical Bulletin and it is not
covered by this document.
Technical data:
Valve opening %
1tbd
100%
(Controller function as temperature controller)
Temperature sensors
ECN-Z… (temperature range down to -
operating/surrounding
between EXD-SH and
0…+55°C
50 cm
AWG 18 wire size (≥ 1mm
2
)
Temperature
0%
1tAL 1tst 1tAH
Temperature setting in reverse sense
(Controller function as temperature controller)
Valve opening %
Stepper motor output
1tbd
100%
Marking
,
Warning:
EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not
comply with ATEX requirements. Installation only in non-explosive
environment. For flammable refrigerants only use valves and accessories
approved for it!
Dimensions (mm):
Temperature
0%
1tAL 1tst/ 1tAH
Electrical connection and wiring:
• Refer to the electrical wiring diagram for electrical connections.
• Note: Keep controller and sensor wiring well separated from supply power
cables. Minimum recommended distance 30 mm.
• When connecting the wires of the EXV-M… (electrical plug of valves)
consider the color coding as follows:
EXV-M…: WH: White; BK: Black; BN: Brown; BL: Blue
• The digital input DI1 (EXD-SH1/SH2) and DI2 (EXD-SH2) are the interfaces
Safety instructions:
• Read operating instructions thoroughly. Failure to comply can result in device
failure, system damage or personal injury.
• It is intended for use by persons having the appropriate knowledge and skill.
between EXD-SH1/2 and upper level system controller if the Modbus
communication has not been used. The external digital inputs must be free of
potential (dry contact) and shall be operated in function system’s
compressor/demand.
• Before installation or service disconnect all voltages from system and device.
• Do not operate system before all cable connections are completed.
• Do not apply voltage to the controller before completion of wiring.
• Entire electrical connections have to comply with local regulations.
• Inputs are not isolated, potential free contacts needed to be used.
Note: Connecting any EXD-SH1/2 inputs to the supply voltage will permanently
damage the EXD-SH1/2
• Use a class II category transformer for 24VAC power supply. Do not ground
the 24VAC lines. We recommend using individual transformers for EXDSH1/2 controller and for third party controllers to avoid possible interference
or grounding problems in the power supply.
• If EXD-PM is connected, it is mandatory to have individual transformer for
EXD-SH… and EXD-PM.
1 and 7 Supply voltage 24 VAC/DC
2 and 8 Temperature sensor circuit 123 and 24 RS485 (+/-terminal)
3 and 8 Temperature sensor circuit 2 25 and 26
4 and 5
9 + 12VDC Voltage input for PT5N… (brown wire) 29 and 30
Warning: Read the note in the last page for limitation of
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Operating instructions
Selected main function
Superheat control
Compressor
ON
Compressor
OFF
Controlled
(°C/F)
Lower display
shows
Valve opening
(%)
Suction pressure
(bar/psig)
Valve opening
(%)
Value on upper display
Code on lower display
Superheat (K/F)
SH
Valve opening (%)
OPEn
Suction temperature (°C/°F)
tASP
Suction pressure (bar/psig)
PEuA
Saturation temperature (°C/°F)
tEuA
Software version: (0A)
SH1 or SH2
Repeating display of values
Displayed Value
Code
Factory Reset
-Fdt
Clear Alarms (only manual reset)
ALrr
Parameter description and
Factory
setting
Field
setting
Manual mode operation; circuit 1
0 1 0
0 = disabled 1 = Enabled
1HP
Valve opening (%)
0
100 0
Manual mode operation; circuit 2
0 1 0
0 = disabled 1 = Enabled
2HP
Valve opening (%)
0
100 0
Next parameter/
Manual Instant values
Lower
Data Display
Circuit 1 is ON
Circuit 2 is ON
ON: alarm
Upper
Observing operating
circuit1
Corresponding
Observing operating
circuit2
Blinking:
Parameters
Blinking:
Next parameter/
Activating/deactivating
EXD-SH1/2 Controller with ModBus communication
Preparation for Start- up:
• Vacuum the entire refrigeration circuit.
• Note: EX/CV valves are delivered partially open position. Do not charge
system with refrigerant before closure of valve.
• Apply supply voltage 24V to EXD-SH1/2 while the digital input (DI1/DI2) is open.
The valve will be driven to close position.
• After closure of valve, start to charge the system with refrigerant.
Setup of parameters:
(need to be checked/modified before system start-up)
• Make sure that digital input (DI1/DI2) is open. Turn on the 24V power supply to
EXD-SH1/2.
• Parameters Password (H5), type of function (1Fct), refrigerant type (1u0/2u0),
pressure sensor type (1uP/2uP) and valve scaling (1uF/2uF) need to be set
according system requirement and only when digital input DI1/DI2 is open. This
feature is for added safety to prevent accidental damage of compressors and other
system components.
• Once the main parameters have been selected and saved, the EXD-SH1/2 is ready
for startup. All other parameters can be modified at any time during operation or
in system standby, if it is necessary.
Display/keypad unit: (LEDs and button functions)
parameters of
valve of circuit
1 and or 2 is in
regulation
Valve is opening
valve is closing
instant values display mode
display mode active
Display description:
Upper display
shows
Superheat (K/F) Superheat (K/F)
Note: when Superheat value is blinking, the controller is in MOP function.
Instant value display mode:
• The controller displays the values of one circuit at a time, to change from one
circuit to the other, press button (Function only for EXD-SH2).
• By pressing the key, the instant value display mode can be
activated/deactivated, which allows the user to check the measured/calculated
values in real time in a sequence shown as below table:
capability for electrical control valves
parameters of
OFF: no alarm
Display
Display
Change 1/2
setting/saving
value (higher)
value (lower)
Temperature
control
temperature
Parameter configuration mode:
The configuration of parameters is protected by a numerical password. The default
password is “12”. To enter the parameter configuration:
• Press both the and buttons for more than 5 seconds.
• A flashing “0” is displayed in upper and “PAS” at lower.
• Press until “12” is displayed; (password).
• Press to confirm password.
• Press or to show the code of the parameter (see table of parameter codes)
that has to be accessed/changed.
• Press to choose and adjust parameter value.
• Press or to increase or decrease the value.
• Press to temporarily confirm the new value. The selected value blinks a few
times and the display shows the next available parameter code.
• Repeat the procedure for other parameters if needed.
To exit and save the new settings:
• When all parameters where changed press to save all the new values and exit
the parameters modification procedure.
To exit and not save the new settings:
• Press and to cancel the parameter modification and delete any changes
made.
• Another way to exit without saving the changes made at the parameters is to not
press any button for at least 120 seconds (TIME OUT).
• Note: While in parameter modification mode, the controller will display the
parameter code on the lower display and the parameter value on the upper
display.
Special manual functions: (Rest, clear)
• Press both the and buttons for more than 5 seconds.
• A flashing “0” is displayed.
• Press until “12” is displayed; (if default password has been changed, it must
select the new password)
• Press to confirm password
• Select the special function as explained at the parameter configuration mode
The special functions are:
• The default value for each variable is 0, when it set to 1 it will trigger the
corresponding function.
• The factory reset of the controller (-Fdt) is possible when digital input DI1/DI2 is
open.
Manual Valve operation (service /maintenance):
• Press for more than 5 seconds
Select, modify and save the variables like explained at the parameter configuration
mode
Code
choices Min Max
1Ho
2Ho
Note: During manual operation, functional alarms such as low superheat are
disabled. It is recommended to monitor the system operation when the
controller is operated manually. Manual operation is intended for service or
temporary operation of valve at a specific condition. After achieving the
required operation, set the parameter 1Ho and 2Ho at 0 so the controller
automatically operates the valve(s) according to its setpoint(s).
*) Warning -Flammable refrigerants:
EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not
1uH
comply with ATEX requirements. Installation only in non-explosive
environment. For flammable refrigerants only use valves and accessories
approved for it!
For serial production of systems/units, upload/download key allows the transmission
of configured parameters among range of identical systems.
Uploading procedure (storing configured parameters in key):
• Insert the key while the first (reference) controller is ON and press button; the
“uPL” message appears followed by “End” message for 5 seconds.
• Note: If the “Err” message is displayed for failed programming, repeat the
Error/Alarm handling:
Alarm
code
Description
capability for electrical control valves
Related
parameter
Alarm
relay
Valve
What to do?
above procedure.
Downloading procedure (configured parameters from key to other controllers):
• Turn off power to new controller.
• Insert a loaded Key (with stored data from reference controller) into new controller
and turn on the power supply.
• The stored parameters of the key will be downloaded automatically into the new
controller memory; The “doL” message appears followed by a “End” message for
5 seconds.
• The new controller with new loaded parameters setting will start to operate after
“End” message disappears.
• Remove the key.
• Note: If the “Err” message is displayed for failed programming, repeat the
above procedure.
alarm after
1E1/2E1
1Π /2Π
Err
ACEr
PFA
Freeze protection circuit 1/2
Low pressure circuit 1/2
Modbus Timed Out - - -
Power failure alarm - Triggered Fully close
- Triggered Fully close Check wiring connection and measure the resistance of sensor. No
- Triggered
- - - Repeat again the procedure for uploading/downloading. No
- Check wiring connection and measure the resistance of winding. No
Check wiring connection and operation of valve.
Check wiring connection, operation of valve, size of valve and load.
Check the system for cause of low pressure such as refrigerant loss.
active only when the pressure sensor type is configured to be Modbus type
ACF1 or ACF2: Alarm code (circuit1/2) for “not permitted configuration/
selection” Alarm will be displayed for the following cases:
• If two circuits of the EXD-SH2 are connected to two different type of pressure
transducers i.e. 4-20 mA and 0-5 V. It is mandatory that two circuits always are
connected to the same type of pressure transmitter technology.
• Temperature control function is possible only with EX4-8 series valves. If other
valves are used, then the ACF alarm will be displayed.
• Ratiometric pressure transmitters cannot be selected in conjunction with R744.
Notes:
Service / Troubleshooting:
No
No
• When several alarms are present, the alarms will be shown one after the other
on the lower display.
• Pressure sensor error for third party ratiometric pressure transmitters is
based on detection of interruption of two wires (5 V and signal 0.5 - 4.5 V). If
only third wire (ground) is open/ interrupted, no error can be detected and
controller will receive a false signal between 50% and 100% higher. This false
signal leads to improper operation of EXD-SH1/2 controller and can lead to
system/compressor damage. EMERSON is not responsible in such cases.
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
sensors
synchronization
2- Make sure the sensor cables are not installed along with other high voltage
week for 10 seconds if compressor never stops.
Betriebsanleitung
Regler
Regelkreis 1
Regelkreis 2
EXD-SH1
Überhitzungs- oder Temperaturregelung
EXD-SH2
Überhitzungs- oder Temperaturregelung
Überhitzungsregelung
Versorgungsspannung
24VAC/DC +10%/-10% 50/60 Hz,
Leistungsaufnahme
EXD-SH1: 25 VA EXD-SH2: 50 VA
Abnehmbare Schraubklemmen für Kabelquerschnitte
von 0,14 bis 1,5 mm2
Schutzklasse
IP00
ECN-N… / TP1…
Tieftemperatur)
Zulässige
Betrieb
Maximale Kabellänge
EXD-PM
Drucktransmitter
PT5N, PT5N-FLR oder ratiometrische Sensoren
Resistive Load 24 V AC/DC, 1 A
Inductive Load 24 V AC/DC, 0,5 A
Kontakt geschlossen:
Während Alarm
Während Normalbetrieb und AUS
Versorgungsspannung
Schrittmotorausgang
Ventile: EX4-8 (EX4-7-FLR), CV4-7
Montage
Standard Schienenmontage
Betriebszustand
Status Digitaleingang
Verdichter startet/läuft
Externe Schaltkontakte schließen (Start)
Kompressor stoppt
Externe Schaltkontakte öffnen (Stopp)
EXD-SH1/2 Regler mit ModBus
Beschreibung:
EXD-SH1/2 eigenständige Überhitzungs- und Temperaturregler. Der EXD-SH1 ist
für ein bipolares elektrisches Regelventil aus den Serien EX/CV, der EXD-SH2 für
zwei getrennt arbeitende Ventile.
Folgende Anwendungen sind möglich:
Hinweis:
Es ist möglich nur den Kreislauf 1 vom EXD-SH2 zu verwenden. In diesem Falle
muss der Kreislauf 2 über den Parameter C2 abgeschaltet werden; Ventil und
Sensoren brauchen nicht angeschlossen werden.
Die ModBus Kommunikation ist im Technical Bulletin beschrieben und nicht
Teil dieses Dokuments.
Technische Daten:
Steckerverbindung
Temperaturfühler
Umgebungstemperatur bei
zwischen EXD-SH und
(Temperaturbereich bis -45°C)
ECN-Z… (Temperaturbereich bis -80°C,
0…+55°C
50 cm
AWG 18 adrig, Querschnitt (≥ 1 mm
Belastbarkeit Alarm-Relais
Kontakt offen:
Kennzeichnung
Warnung:
EXD-SH1/2 (EXD-PM, ECP-024) hat eine potentielle Zündquelle und
entspricht nicht den ATEX Bestimmungen. Installation nur in nicht
explosionsgefährdeter Umgebung. Für brennbare Kältemittel nur Ventile und
Zubehörteile, die dafür zugelassen sind verwenden!
Abmessungen (mm):
Sicherheitshinweise:
• Lesen Sie die Betriebsanleitung gründlich. Nichtbeachtung kann zum
Versagen oder zur Zerstörung des Gerätes und zu Verletzungen führen.
• Der Einbau darf nur von Fachkräften vorgenommen werden.
• Der Kältekreislauf darf nur in drucklosem Zustand geöffnet werden.
• Die Anlage erst in Betrieb nehmen, wenn alle Kabelverbindungen vollständig
sind.
• • Die Anlage darf erst dann in Betrieb genommen werden, wenn alle
Verbindungen hergestellt sind.
Kommunikation für elektrische Regelventile
2
)
,
• Für den gesamten elektrischen Anschluss sind die länderspezifischen
Vorschriften einzuhalten.
• Digitaleingänge sind spannungsbehaftet; nur potentialfreie Schaltkontakte
verwenden.
• Entsorgung: Elektro- und Elektronik-Altgeräte dürfen nicht mit anderen
Gewerbemüll entsorgt werden. Stattdessen ist es in der Verantwortung Benutzer
es zu einem Sammelpunkt für die sichere Entsorgung von Elektro- und ElektronikAltgeräte (WEEE-Richtlinie 2012/19/EU) zu übergeben. Für weitere
Informationen kontaktieren Sie bitte Ihren örtlichen Recyclinghof.
• Den elektrischen Anschluss gemäß Verdrahtungsschema durchführen!
• Hinweis: Signalleitungen und Leitungen mit Netzspannung in getrennten
Kabelschächten verlegen, Mindestabstand 30mm.
• Bei Anschluss von EXV-M… (Ventilstecker) muss die Farbe der Adern wie
folgt berücksichtigt werden:
EXV-M…: WH: Weiß; BK: Schwarz; BN: Braun; BL: Blau
• Die Digitaleingänge DI1 (EXD-SH1/SH2) und DI2 (EXD-SH2) sind die
Schnittstellen zwischen EXD-SH1/2 und dem übergeordnetem Systemregler,
wenn keine Modbus Kommunikation eingesetzt wird. Die externen Schaltkontakte
müssen potentialfrei sein (dry contact) und entsprechend der Systemanforderung
angesteuert werden.
Hinweis: Das Aufschalten von externer Spannung auf die Digitaleingänge führt
zur dauerhaften Beschädigung des EXD-SH1/2.
• Für die 24V Stromversorgung sind ausschließlich Transformatoren der
Klasse II zu verwenden. Die 24V Leitungen dürfen nicht geerdet werden. Wir
empfehlen die Verwendung jeweils separater EMERSON Transformatoren
für EXD-SH1/2 Regler und die Regler anderer Hersteller, weil unter
Umständen über die Erdleitungen Kurzschlüsse entstehen können.
• Wenn EXD-PM angeschlossen ist, ist es notwendig, dass der EXD-SH-Regler
Kreislauf 2 (EXD-SH2)
Kopierschlüssel
Versorgungsspannung 24 VAC/DC
1 & 7
Temperaturfühler Kreislauf 2
3 & 8
4 & 5
9
Drittanbietern:
Warnung: Beachten sie die Einschränkungen betreffend der
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
14-17
19-22
25 & 26
27 & 28
29 & 30
31 & 30
35 & 36
EXV-M… elektr. Stecker: Adernfarben
EXV-M… elektr. Stecker: Adernfarben
Digitaleingang Kreislauf 2 (DI2) –
Kontakte
Batterie/ Power Modul Anschluss
Sicherung EXD-SH1 (1A), EXD-SH2 (2A)
Nicht verwendet (Terminals on EXD-SH12)
und die EXD-PM-Kondensatoren eigene Transformatoren haben.
Drucksensor von Kreislauf 1 genutzt
Betriebsanleitung
Gewählte Hauptfunktion
Überhitzungsregelung
Verdichter
AN
Verdichter
AUS
Oberes
Anzeigefeld
Überhitzung
(K/F)
Überhitzung
(K/F)
Isttemperatur
(°C/F)
Unteres
Anzeigefeld
Ventilöffnung
(%)
Saugdruck
(bar/psig)
Ventilöffnung
(%)
Wert im oberen Anzeigefeld
Code im unteren Anzeigefeld
Überhitzung (K/F)
SH
Ventilöffnung (%)
OPEn
Saugtemperatur (°C/°F)
tASP
Saugdruck (bar/psig)
PEuA
Sättigungstemperatur (°C/°F)
tEuA
Softwareversion: (0A)
SH1 oder SH2
Die Werte können wiederholt angezeigt werden
Anzeige
Code
Zurück zur Werkseinstellung
-Fdt
Alarme löschen (nur manuell)
ALrr
Parameter und Optionen
Werk-
einstell-
ung
Individ-
Einstell.
Handbetrieb Kreislauf 1
0 1 0 0 = inaktiv 1 = aktiv
1HP
Ventilöffnung (%)
0
100
0
Handbetrieb Kreislauf 2
0 1 0 0 = inaktiv 1 = aktiv
2HP
Ventilöffnung (%)
0
100
0
Nächster
(Abwärts)
Istwertanzeigemodus ist
unteres
Anzeige n-
Kreislauf 1 ist AN
Kreislauf 2 ist AN
AN: Alarm
oberes
Anzeige Parameter
Regelbetrieb
Anzeige Parameter
Blinkt:
Parameter
Blinkt:
Nächster
(Aufwärts)
Aktivierung/Deaktivierung
EXD-SH1/2 Regler mit ModBus
Vorbereitungen für die Inbetriebnahme:
• Gesamten Kältekreislauf evakuieren.
• Hinweis: Die Elektrischen Regelventile EX/CV werden halb geöffnet
ausgeliefert. Den Kältekreislauf nur bei geschlossenem Ventil mit Kältemittel
füllen.
• Die 24V Versorgungsspannung des EXD-SH1/2 einschalten, während die
Digitaleingänge (DI1/DI2) offen sind. Das Ventil wird schließen.
• Bei geschlossenem Ventil System mit Kältemittel füllen.
Parametereinstellung:
(müssen vor dem Starten geprüft und bei Bedarf angepasst werden)
• Stellen sie sicher, dass die Digitaleingänge (DI1/DI2) offen sind. Schalten sie die
24V Spannungsversorgung des EXD-SH1/2 ein.
• Wenn die Digitaleingänge DI1/DI2 offen sind, müssen die Parameter Passwort
(H5), Funktion (1Fct), Kältemittel (1u0/2u0), Drucksensortyp (1uP/2uP) und
Regelbereich (1uF/2uF) entsprechend den Systemanforderungen eingestellt
werden. Dies ist eine Sicherheitsmaßnahme um zu verhindern, dass versehentlich
am Verdichter und an anderen Komponenten Schäden entstehen.
• Sobald die wichtigsten Parameter eingestellt und gespeichert sind, ist der Regler
EXD-SH1/2 fertig für die Inbetriebnahme. Alle anderen Parameter könne auch
während des Betriebes oder im Stand-By Modus verändert werden.
Anzeige/Tastatur (LEDs and Testenfunktionen)
Kreislauf 1 aktiv
Ventil 1 bzw 2
Ventil geöffnet
Ventil schließt
Parameter/Istwert
Istwertanzeigemodus
manuell aktiviert
Anzeige Beschreibung:
Hinweis: Wenn der Überhitzungswert blinkt ist der Regler im MOP Betrieb.
Istwertanzeigenmodus:
• Es werden jeweils die Istwerte von einem Kreis angezeigt.
• Um von einem Kreis zum anderen zu wechseln kann die Taste betätigt
werden. (Funktion nur bei EXD-SH2).
• Durch Drücken der Taste kann die Istwertanzeige aktiviert/deaktiviert
werden. Damit können folgende gemessene oder berechnete Istwerte entsprechend
der unteren Tabelle abgerufen werden.
Kommunikation für elektrische Regelventile
Kreislauf 2 aktiv
AUS: kein Alarm
Anzeigefeld
Anzeigefeld
wechsel
Kreislauf 1
bzw. 2
Einstellung/
Speicherung
Parameter/Istwert
Temperatur-
regelung
Parametereinstellungsmodus:
Der Parametereinstellungsmodus ist durch ein numerisches Passwort geschützt.
Die Werkseinstellung ist “12”.
Zum starten des Parametereinstellungsmodus:
• Beide Tasten, und für mehr als 5 Sekunden gedrückt halten.
• Im oberen Anzeigefeld wird eine blinkende “0” und im unteren Anzeigefeld “PAS”
angezeigt
• gedrückt halten bis “12” (das Passwort) angezeigt wird.
• Mit das Passwort bestätigen.
• Mit oder können die Parameter der Liste nacheinander angezeigt werden.
• Mit kann der Parameter der eingestellt bzw. verändert werden soll ausgewählt
werden.
• Mit oder können die Werte vergrößert oder verkleinert werden.
• Durch drücken von wird der Wert zwischengespeichert. Der Wert blinkt für
kurze Zeit dann wechselt die Anzeige zum nächsten Parameter.
• Diese Abfolge kann für alle einzustellenden Parameter wiederholt werden.
Um die neuen Werte dauerhaft zu speichern und den Einstellmodus zu
verlassen:
• Taste drücken
Den Einstellmodus verlassen OHNE die neuen Einstellungen dauerhaft zu
speichern:
• Beide Tasten und drücken: die vorherigen Änderungen werden gelöscht
und der Parametereinstellmodus wird geschlossen.
• Eine andere Möglichkeit zum Beenden ohne Speicherung ist mehr als 120
Sekunden ohne eine Tasteneingabe zu warten (TIME OUT).
• Hinweis: Im Parametereinstellungsmodus wird im unteren Anzeigefeld der
Parameter und im oberen Anzeigefeld der Wert angezeigt.
Spezielle Funktionen (Reset, clear) und Handbetrieb
• Beide Tasten und für mehr als 5 Sekunden gedrückt halten.
• Eine blinkende “0” wird angezeigt.
• drücken bis “12” angezeigt wird; (falls ein individuelles, numerisches
Passwort eingestellt ist muss dieses eingegeben werden.)
• Mit wird das Passwort bestätigt
Folgende Spezielle Funktionen können ausgewählt werden:
• Die Voreinstellung ist 0, mit 1wird die jeweilige Funktion aktiviert
• Zurück zur Werkseinstellung (-Fdt) kann nur aktiviert werden, wenn die
Digitaleingänge DI1/DI2 offen sind.
Handbetrieb Ventile (Service /Wartung):
• länger als 5 Sekunden gedrückt halten
Die Auswahl, Änderung und Speicherung der Parameter ist wie beim obigen
Parametereinstellungsmodus.
Code
Min Max
uelle
1Ho
2Ho
Hinweis: Während des Handbetriebes sind Funktionsalarme, wie “Zu niedrige
Überhitzung” unterdrückt. Deshalb muss die Anlage in diesem Falle sorgfältig
mit anderen Mitteln überwacht werden. Der Handbetrieb ist nur für Test und
Servicezwecke vorgesehen. Danach sind für den Automatik Betrieb die
Parameter 1Ho und 2Ho auf “ 0” zu setzen so dass der Regler entsprechend den
Sollwerteinstellungen arbeiten kann.