Emerson EXD-SH1, EXD-SH2 Operating instructions

Operating instructions
Controller
Circuit 1: Main function
Circuit 2: Main function
EXD-SH1
Superheat or temperature control
EXD-SH2
Superheat or temperature control
Superheat Control
Power supply
24VAC/DC +10%/-10% 50/60HZ,
Power consumption
EXD-SH1: 25VA EXD-SH2: 50VA
Plug-in connector
Removable screw terminals wire size 0.14...1.5 mm2
Protection class
IP00
ECN-N… / TP1… (temperature range down to -45°C)
80°C ultra low
temperature)
Allowable
temperature
Maximum cable distance
EXD-PM
Pressure sensors
PT5N, PT5N-FLR or ratiometric probes
Output alarm relay current rating
Resistive Load 24 V AC/DC, 1 A Inductive Load 24 V AC/DC, 0.5 A
Contact is closed:
During alarm condition
Contact is open:
During normal operation and supply power OFF
Valves: EX4-8 (EX4-7-FLR) CV4-7
Mounting
For standard DIN rail
Operating condition
Digital input status
Compressor starts/run
External contact to be closed (Start)
Compressor stops
External contact to be open (Stop)
EXD-SH1/2 Controller with ModBus communication
intended for operation of one bipolar electrical control valve whereas EXD-SH2 is designed for operation of two independent bipolar electrical control valves. A table of the available application possibilities is listed below:
capability for electrical control valves
Disposal: Electrical and electronic waste must NOT be disposed of with other commercial waste. Instead, it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment (WEEE directive 2012/19/EU). For further information, contact your local environmental recycling center.
Temperature setting in normal sense
Notes: It is possible to use only circuit 1 from EXD-SH2. In this case, the circuit 2 must be disabled (C2 parameter) and the sensors and the valve for the second circuit are not needed. ModBus communication is described in a Technical Bulletin and it is not covered by this document.
Technical data:
Valve opening %
1tbd
100%
(Controller function as temperature controller)
Temperature sensors
ECN-Z… (temperature range down to -
operating/surrounding
between EXD-SH and
0…+55°C
50 cm AWG 18 wire size (≥ 1mm
2
)
Temperature 0%
1tAL 1tst 1tAH
Temperature setting in reverse sense
(Controller function as temperature controller)
Valve opening %
Stepper motor output
1tbd
100%
Marking
,
Warning: EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not comply with ATEX requirements. Installation only in non-explosive environment. For flammable refrigerants only use valves and accessories approved for it!
Dimensions (mm):
Temperature
0%
1tAL 1tst/ 1tAH
Electrical connection and wiring:
Refer to the electrical wiring diagram for electrical connections.
Note: Keep controller and sensor wiring well separated from supply power
cables. Minimum recommended distance 30 mm.
When connecting the wires of the EXV-M… (electrical plug of valves) consider the color coding as follows: EXV-M…: WH: White; BK: Black; BN: Brown; BL: Blue
• The digital input DI1 (EXD-SH1/SH2) and DI2 (EXD-SH2) are the interfaces
Safety instructions:
Read operating instructions thoroughly. Failure to comply can result in device failure, system damage or personal injury.
It is intended for use by persons having the appropriate knowledge and skill.
between EXD-SH1/2 and upper level system controller if the Modbus communication has not been used. The external digital inputs must be free of potential (dry contact) and shall be operated in function system’s compressor/demand.
Before installation or service disconnect all voltages from system and device.
Do not operate system before all cable connections are completed.
Do not apply voltage to the controller before completion of wiring.
Entire electrical connections have to comply with local regulations.
Inputs are not isolated, potential free contacts needed to be used.
Note: Connecting any EXD-SH1/2 inputs to the supply voltage will permanently damage the EXD-SH1/2
.
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Operating instructions
*) Parameter 2uP with No. 8 = only pressure sensor circuit 1 is used
Circuit 2 (EXD-SH2)
Download/upload key
Electrical control valve circuit 2 (ECV2)
WH-white BK-black BL-blue BN-brown
Alarm relay circuit 1 (C, NO) – Suitable for 24 VAC/DC
PT5N… circuit 1 & circuit 2 (white wire: 4 – 20 mA signal)
Alarm relay circuit 2 (C, NO) – Suitable for 24 VAC/DC
Digital input circuit1 (DI1) – Dry contact, potential free
Alternative ratiometric third Party Pressure Transmitter:
error condition
Pressure transmitter circuit 1 & circuit 2 (0.5 - 4.5 V signal)
6,12,13, 18,32-34
VAC/ VDC
24
UPS for up to controllers
One supercap for one EXD
Two supercaps for one EXD
24 V
24 V
24 V
24 V
24 V
See parameter 2uP
EXD-SH1/2 Controller with ModBus communication
capability for electrical control valves
Wiring options: UPS (ECP-024) /Supercap (EXD-PM)
*
Circuit 1 (EXD-SH1/SH2)
14-17
Electrical control valve circuit 1 (ECV1) EXV-M… Electrical plug: wire colors WH-white BK-black BL-blue BN-brown
two
-SH1
-SH2
Warning:
Use a class II category transformer for 24VAC power supply. Do not ground the 24VAC lines. We recommend using individual transformers for EXD­SH1/2 controller and for third party controllers to avoid possible interference or grounding problems in the power supply.
If EXD-PM is connected, it is mandatory to have individual transformer for EXD-SH… and EXD-PM.
1 and 7 Supply voltage 24 VAC/DC
2 and 8 Temperature sensor circuit 1 23 and 24 RS485 (+/-terminal)
3 and 8 Temperature sensor circuit 2 25 and 26
4 and 5
9 + 12VDC Voltage input for PT5N… (brown wire) 29 and 30
Warning: Read the note in the last page for limitation of
4 and 5
11 + 5 VDC voltage input
10 GND Ground
19-22
27 and 28
31 and 30
35 and36 Battery/Super capacitor connection terminal
EXV-M… Electrical plug: wire colors
Digital input circuit 2 (DI2) – Dry contact, potential free
Fuse: EXD-SH1 (1A), EXD-SH2 (2A)
Not used (Terminals on EXD-SH12)
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Operating instructions
Selected main function
Superheat control
Compressor
ON
Compressor
OFF
Controlled
(°C/F)
Lower display
shows
Valve opening
(%)
Suction pressure
(bar/psig)
Valve opening
(%)
Value on upper display
Code on lower display
Superheat (K/F)
SH
Valve opening (%)
OPEn
Suction temperature (°C/°F)
tASP
Suction pressure (bar/psig)
PEuA
Saturation temperature (°C/°F)
tEuA
Software version: (0A)
SH1 or SH2
Repeating display of values
Displayed Value
Code
Factory Reset
-Fdt
Clear Alarms (only manual reset)
ALrr
Parameter description and
Factory
setting
Field
setting
Manual mode operation; circuit 1
0 1 0
0 = disabled 1 = Enabled
1HP
Valve opening (%)
0
100 0
Manual mode operation; circuit 2
0 1 0
0 = disabled 1 = Enabled
2HP
Valve opening (%)
0
100 0
Next parameter/
Manual Instant values
Lower
Data Display
Circuit 1 is ON
Circuit 2 is ON
ON: alarm
Upper
Observing operating
circuit1
Corresponding
Observing operating
circuit2
Blinking:
Parameters
Blinking:
Next parameter/
Activating/deactivating
EXD-SH1/2 Controller with ModBus communication
Preparation for Start- up:
• Vacuum the entire refrigeration circuit.
Note: EX/CV valves are delivered partially open position. Do not charge
system with refrigerant before closure of valve.
• Apply supply voltage 24V to EXD-SH1/2 while the digital input (DI1/DI2) is open. The valve will be driven to close position.
• After closure of valve, start to charge the system with refrigerant.
Setup of parameters: (need to be checked/modified before system start-up)
• Make sure that digital input (DI1/DI2) is open. Turn on the 24V power supply to EXD-SH1/2.
• Parameters Password (H5), type of function (1Fct), refrigerant type (1u0/2u0), pressure sensor type (1uP/2uP) and valve scaling (1uF/2uF) need to be set according system requirement and only when digital input DI1/DI2 is open. This feature is for added safety to prevent accidental damage of compressors and other system components.
• Once the main parameters have been selected and saved, the EXD-SH1/2 is ready for startup. All other parameters can be modified at any time during operation or in system standby, if it is necessary.
Display/keypad unit: (LEDs and button functions)
parameters of
valve of circuit 1 and or 2 is in regulation
Valve is opening
valve is closing
instant values display mode
display mode active
Display description:
Upper display
shows
Superheat (K/F) Superheat (K/F)
Note: when Superheat value is blinking, the controller is in MOP function.
Instant value display mode:
• The controller displays the values of one circuit at a time, to change from one
circuit to the other, press button (Function only for EXD-SH2).
• By pressing the key, the instant value display mode can be activated/deactivated, which allows the user to check the measured/calculated values in real time in a sequence shown as below table:
capability for electrical control valves
parameters of
OFF: no alarm
Display
Display
Change 1/2
setting/saving
value (higher)
value (lower)
Temperature
control
temperature
Parameter configuration mode:
The configuration of parameters is protected by a numerical password. The default password is “12”. To enter the parameter configuration:
• Press both the and buttons for more than 5 seconds.
• A flashing “0” is displayed in upper and “PAS” at lower.
• Press until “12” is displayed; (password).
• Press to confirm password.
• Press or to show the code of the parameter (see table of parameter codes) that has to be accessed/changed.
• Press to choose and adjust parameter value.
• Press or to increase or decrease the value.
• Press to temporarily confirm the new value. The selected value blinks a few times and the display shows the next available parameter code.
• Repeat the procedure for other parameters if needed.
To exit and save the new settings:
• When all parameters where changed press to save all the new values and exit the parameters modification procedure.
To exit and not save the new settings:
• Press and to cancel the parameter modification and delete any changes made.
• Another way to exit without saving the changes made at the parameters is to not press any button for at least 120 seconds (TIME OUT).
Note: While in parameter modification mode, the controller will display the
parameter code on the lower display and the parameter value on the upper display.
Special manual functions: (Rest, clear)
• Press both the and buttons for more than 5 seconds.
• A flashing “0” is displayed.
• Press until “12” is displayed; (if default password has been changed, it must select the new password)
• Press to confirm password
• Select the special function as explained at the parameter configuration mode
The special functions are:
• The default value for each variable is 0, when it set to 1 it will trigger the corresponding function.
• The factory reset of the controller (-Fdt) is possible when digital input DI1/DI2 is open.
Manual Valve operation (service /maintenance):
• Press for more than 5 seconds
Select, modify and save the variables like explained at the parameter configuration mode
Code
choices Min Max
1Ho
2Ho
Note: During manual operation, functional alarms such as low superheat are disabled. It is recommended to monitor the system operation when the controller is operated manually. Manual operation is intended for service or temporary operation of valve at a specific condition. After achieving the required operation, set the parameter 1Ho and 2Ho at 0 so the controller automatically operates the valve(s) according to its setpoint(s).
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Operating instructions
Factory
setting
H5
Password
1
1999
12
Adr
ModBus address
1
127 1 br
Modbus baudrate
0 1 0
PAr
Modbus parity
0 1 0
Circuit 2 of EXD-SH2 enabled
0 1 1
0 =Disabled 1 = Enabled
Units conversion
0 1 0
0 = °C, K, bar 1 = F, psig
Circuit 1 Parameters
Function 0 2
0
0 = Superheat control 1 = Temperature control normal sense 2 = temperature control reverse sense
Control Mode
0 3 0
0 = standard 1 = slow 2 = intermediate control 3 = adjustable fixed PID
Refrigerant type
0
19
1
0 = R22 1 = R134a 2 = R507 3 = R404A
16 = R513A 17 = R290* 18 = R1270* 19 = R454C*
Pressure sensor type
0 8 1
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x
6 = Ratio metric (gauge) 7 = Ratio metric (absolute) 8 = Modbus
1Prr
Ratio metric range (bar)
3
60
30
Valve type
0
12
0
0 = EX4-6(FLR) 1 = EX7(FLR) 2 = EX8 3 = N/A 4 = N/A
10 = CV4 11 = CV5-6 12 = CV7
1uF
Valve scaling (%)
5
100
100
1uu
Start opening (%)
0
100
10
1u9
Start opening duration (s)
0
120
5
Low superheat alarm
0 2 1
0 = disabled 1 = enabled auto reset 2 = enabled manual reset Alarm at 0.5K (if it maintains 1 min.); Alarm clear immediately at 3K
Superheat set point (K)
0.5
30 6 Range = 3-30 K if parameter 1uL is set to 1 or 2
MOP function
0 1 1
0 = disabled 1 = Enabled
MOP saturation temp (°C)
(1u0). The default value can be changed
(see
table)
Low pressure alarm mode
0 2 0
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
1PA
Low pressure alarm cut-out (bar)
-0.8
17.7 0 1Pb
Low pressure alarm delay (s)
5
199 5 1Pd
Low pressure alarm cut-in (bar)
-0.5
18
0.3
Freeze alarm delay mode
0 2 0
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
1P2
Freeze alarm cut-out (°C)
-5 5 0
1P5
Freeze alarm delay (s)
5
199
30
1P-
Superheat control circuit1 (Kp factor) Display 1/10K
0.1
10
1.0
1i-
Superheat control circuit1 (Ti factor)
1
350
100
1d-
Superheat control circuit1 (Td factor) Display 1/10K
0.1
30
3.0
High superheat alarm mode
0 1 0
0 = disabled 1 = enabled auto-reset;
1uA
High superheat alarm set point (K)
16
40
30
1ud
High superheat alarm delay (min)
1
15 3 1tSt
Temperature control set point (°C)
-80
50 4 1tbd
Temperature band (K)
1
10
2
Temperature alarm mode
0 1 0
0 = disabled 1 = enabled
1tAL
Min. temperature alarm set point (°C)
-50
50 0 1tdL
Min. temperature alarm delay (min)
1
10 3 1tAH
Max. temperature alarm set point (°C)
-50
50
15
1tdH
Max. temperature alarm delay (min)
1
10
3
Temperature sensor type
0 1 0
0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C) 1 = ECN-Z... ( -80…-40°C) for R23
Factory
setting
Circuit 2 Parameters (only EXD-SH2)
Control Mode
0 3 0
0 = standard 1 = slow 2 = intermediate control 3 = adjustable fixed PID
Refrigerant type
0
19
1
0 = R22 1 = R134a 2 = R507 3 = R404A
16 = R513A 17 = R290* 18 = R1270* 19 = R454C*
Pressure sensor type
0 9 1
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x
8 = Modbus 9 = Pressure sensor circuit1 is used (1uP)
2Prr
Ratio metric range (bar)
3
60
30
Valve type
0
12
0
0 = EX4-6(FLR) 1 = EX7(FLR) 2 = EX8 3 = N/A 4 = N/A
10 = CV4 11 = CV5-6 12 = CV7
2uF
Valve scaling (%)
5
100
100
2uu
Start opening (%)
0
100
10
2u9
Start opening duration (s)
0
120
5
Low superheat alarm
0 2 1
0 = disabled 1 = enabled auto reset 2 = enabled manual reset Alarm at 0.5K (if it maintains 1 min.); Alarm clear immediately at 3K
Superheat set point (K)
0.5
30 6 Range = 3-30K if parameter 2uL is set to 1 or 2
MOP function
0 1 1
0 = disabled 1 = Enabled
MOP saturation temp (°C)
(2u0). The default value can be changed
(see
table)
Low pressure alarm mode
0 2 0
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
2PA
Low pressure alarm cut-out (bar)
-0.8
17.7 0 2Pb
Low pressure alarm delay (s)
5
199 5 2Pd
Low pressure alarm cut-in (bar)
-0.5
18
0.3
Freeze alarm delay mode
0 2 0
0 = disabled 1 = enabled auto-reset 2 = enabled manual reset
2P2
Freeze alarm cut-out (°C)
-5 5 0
2P5
Freeze alarm delay (s)
5
199
30
2P-
Superheat control circuit2
0.1
10
1.0
(Kp factor), fixed PID Display 1/10K
2i-
Superheat control circuit2 (Ti factor), fixed PID
1
350
100
2d-
Superheat control circuit2
0.1
30
3.0
(Td factor), fixed PID Display 1/10K
High superheat alarm mode
0 1 0
0 = disabled 1 = enabled auto-reset;
2uA
High superheat alarm set point (K)
16
40
30
2ud
High superheat alarm delay (min)
1
15
3
Temperature sensor type
0 1 0
0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C) 1 = ECN-Z60 ( -80°C…-40°C) for R23
Refrigerant
Default (C°)
Refrigerant
Default (C°)
Refrigerant
Default (C°)
R22
+13
R744
-5
R449A
+12
R134a
+15
R407A
+10
R450A
+19
R507
+7
R407F
+10
R513A
+13
R404A
+7
R23
-40
R290
+15
R407C
+15
R32
+15
R1270
+15
R410A
+15
R1234ze
+24
R454C
+17
R124
+50
R448A
+12
EXD-SH1/2 Controller with ModBus communication
List of parameters in scrolling sequence by pressing button:

Code Parameter description and choices Min Max

-C2
-uC
1Fct
1u4
capability for electrical control valves
Code Parameter description and choices Min Max
2u4
4 = R407C 5 = R410A 6 = R124 7 = R744
2u0
8 = R407A 9 = R407F 10 = R23 11 = R32* 12 = R1234ze* 13 = R448A 14 = R449A 15 = R450A
2uP
3 = PT5N-50x 4 = PT5N-150D 5 = PT5N-10-FLR 6 = Ratio metric (gauge) 7 = Ratio metric (absolute)
4 = R407C 5 = R410A 6 = R124 7 = R744
1u0
8 = R407A 9 = R407F 10 = R23 11 = R32* 12 = R1234ze* 13 = R448A 14 = R449A 15 = R450A
1uP
3 = PT5N-50x 4 = PT5N-150D 5 = PT5N-10P-FLR
1ut
5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A
1uL
1u5
1u2
1u3
Factory setting according to selected refrigerant
1P9
1P4
- -
MOP
2ut
5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A
2uL
2u5
2u2
2u3
Factory setting according to selected refrigerant
2P9
2P4
2uH
- -
MOP
2tt
*) Warning -Flammable refrigerants: EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not
1uH
comply with ATEX requirements. Installation only in non-explosive environment. For flammable refrigerants only use valves and accessories approved for it!
MOP default value table:
1tAF
1tt
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Operating instructions
(1uu + 1u9) / (2uu +2u9)
CV7 6.6 Seconds
Requires clear
resolving alarm
1E0/2E0
Pressure sensor circuit 1/2 error
-
Triggered
Fully close
Check wiring connection and measure the signal.
No
Temperature sensor circuit 1/2 error
Valve Circuit 1/2 electrical connection error
AFE 1/2
1P4/2P4:1
Triggered
Fully close
Check the system for cause of low pressure such as insufficient load on evaporator.
No if it is ON
AFE 1/2
1P4/2P4:2
Triggered
Fully close
Yes if it is blinking
LSH 1/2
Low superheat (<0,5K)
1uL/2uL:1
Triggered
Fully close
No if it is ON
LSH 1/2
1uL/2uL:2
Triggered
Fully close
Yes if it is blinking
tAL1
Min. temperature alarm
1tAL
Triggered
Fully close
No
tAH1
Max. temperature alarm
1tAH
Triggered
Fully close
No
HSH 1/2
High superheat circuit 1/2
1uH/2uH:1
Triggered
Operating
Check the system.
No
LOP 1/2
1P9/2P9 1
Triggered
Operating
No if it is ON
LOP 1/2
1P9/2P9 2
Triggered
Operating
Yes if it is blinking
Failed uploading/downloading
Check Modbus communication. Note: Modbus alarm (ACEr) detection is
and the corresponding circuit is on demand.
When the controller is connected to the battery supply and power supply interrupted, this alarm code will be displayed while the valve is closing.
Symptom
Cause
Action
Operating superheat is several degrees higher or
Incorrect signal from pressure or temperature
1- Check the sensors (see list of parameters)
cables
Operating superheat is too low i.e. compressor wet running
1- Incorrect wiring of ECVs 2- Defective sensors
1- Check the wiring 2- Check the sensor
Valve is not fully closed
1- The digital input is ON 2- Wrong setting of parameter ut.
1- Valve is shut off only when the digital input is turned off. 2- Check the setting of parameter ut.
Instable superheat (hunting)
Evaporator is designed to operate at higher superheat
Increase the superheat set-point.
Valve opens when EXD commands to close and vice versa
Wrong wiring between EXD-SH... and valve
Correct the wiring.
EX8 is not able to open at high differential pressure
Wrong setting of parameter ut
Check the parameter ut. (Larger valve requires higher torque and higher current)
Superheat set-point is shifting after several months
24 V digital input
Stepper motor driven valves require
Do not jumper digital input permanently. Interrupt digital input once every
EXD-SH1/2 Controller with ModBus communication
Control (valve) start- up behavior factory settings
EX4/5/6 ≤ 5.3 Seconds EX7 ≤ 5.6 Seconds EX8 ≤ 5.9 Seconds CV4 5.3 Seconds CV5/6 5.3 Seconds
Upload/download Key: Function
For serial production of systems/units, upload/download key allows the transmission of configured parameters among range of identical systems.
Uploading procedure (storing configured parameters in key):
• Insert the key while the first (reference) controller is ON and press button; the
uPL” message appears followed by “End” message for 5 seconds.
Note: If the “Err” message is displayed for failed programming, repeat the
Error/Alarm handling:
Alarm code
Description
capability for electrical control valves
Related parameter
Alarm relay
Valve

What to do?

above procedure.
Downloading procedure (configured parameters from key to other controllers):
• Turn off power to new controller.
• Insert a loaded Key (with stored data from reference controller) into new controller and turn on the power supply.
• The stored parameters of the key will be downloaded automatically into the new controller memory; The “doL” message appears followed by a “End” message for 5 seconds.
• The new controller with new loaded parameters setting will start to operate after “End” message disappears.
• Remove the key.
Note: If the “Err” message is displayed for failed programming, repeat the
above procedure.
alarm after
1E1/2E1
1Π /2Π
Err
ACEr
PFA
Freeze protection circuit 1/2
Low pressure circuit 1/2
Modbus Timed Out - - -
Power failure alarm - Triggered Fully close
- Triggered Fully close Check wiring connection and measure the resistance of sensor. No
- Triggered
- - - Repeat again the procedure for uploading/downloading. No
- Check wiring connection and measure the resistance of winding. No
Check wiring connection and operation of valve.
Check wiring connection, operation of valve, size of valve and load.
Check the system for cause of low pressure such as refrigerant loss.
active only when the pressure sensor type is configured to be Modbus type
ACF1 or ACF2: Alarm code (circuit1/2) for “not permitted configuration/ selection” Alarm will be displayed for the following cases:
• If two circuits of the EXD-SH2 are connected to two different type of pressure transducers i.e. 4-20 mA and 0-5 V. It is mandatory that two circuits always are connected to the same type of pressure transmitter technology.
• Temperature control function is possible only with EX4-8 series valves. If other valves are used, then the ACF alarm will be displayed.
• Ratiometric pressure transmitters cannot be selected in conjunction with R744.
Notes: Service / Troubleshooting:
No
No
When several alarms are present, the alarms will be shown one after the other
on the lower display.
Pressure sensor error for third party ratiometric pressure transmitters is based on detection of interruption of two wires (5 V and signal 0.5 - 4.5 V). If only third wire (ground) is open/ interrupted, no error can be detected and controller will receive a false signal between 50% and 100% higher. This false signal leads to improper operation of EXD-SH1/2 controller and can lead to system/compressor damage. EMERSON is not responsible in such cases.
lower than set-point
of uninterrupted operation or permanent jumper of
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
sensors
synchronization
2- Make sure the sensor cables are not installed along with other high voltage
week for 10 seconds if compressor never stops.
Betriebsanleitung
Regler
Regelkreis 1
Regelkreis 2
EXD-SH1
Überhitzungs- oder Temperaturregelung
EXD-SH2
Überhitzungs- oder Temperaturregelung
Überhitzungsregelung
Versorgungsspannung
24VAC/DC +10%/-10% 50/60 Hz,
Leistungsaufnahme
EXD-SH1: 25 VA EXD-SH2: 50 VA
Abnehmbare Schraubklemmen für Kabelquerschnitte von 0,14 bis 1,5 mm2
Schutzklasse
IP00
ECN-N… / TP1…
Tieftemperatur)
Zulässige
Betrieb
Maximale Kabellänge
EXD-PM
Drucktransmitter
PT5N, PT5N-FLR oder ratiometrische Sensoren
Resistive Load 24 V AC/DC, 1 A Inductive Load 24 V AC/DC, 0,5 A
Kontakt geschlossen:
Während Alarm
Während Normalbetrieb und AUS Versorgungsspannung
Schrittmotorausgang
Ventile: EX4-8 (EX4-7-FLR), CV4-7
Montage
Standard Schienenmontage
Betriebszustand
Status Digitaleingang
Verdichter startet/läuft
Externe Schaltkontakte schließen (Start)
Kompressor stoppt
Externe Schaltkontakte öffnen (Stopp)
EXD-SH1/2 Regler mit ModBus
Beschreibung: EXD-SH1/2 eigenständige Überhitzungs- und Temperaturregler. Der EXD-SH1 ist
für ein bipolares elektrisches Regelventil aus den Serien EX/CV, der EXD-SH2 für zwei getrennt arbeitende Ventile. Folgende Anwendungen sind möglich:
Hinweis: Es ist möglich nur den Kreislauf 1 vom EXD-SH2 zu verwenden. In diesem Falle muss der Kreislauf 2 über den Parameter C2 abgeschaltet werden; Ventil und Sensoren brauchen nicht angeschlossen werden. Die ModBus Kommunikation ist im Technical Bulletin beschrieben und nicht Teil dieses Dokuments.
Technische Daten:
Steckerverbindung
Temperaturfühler
Umgebungstemperatur bei
zwischen EXD-SH und
(Temperaturbereich bis -45°C) ECN-Z… (Temperaturbereich bis -80°C,
0…+55°C
50 cm AWG 18 adrig, Querschnitt (≥ 1 mm
Belastbarkeit Alarm-Relais
Kontakt offen:
Kennzeichnung
Warnung: EXD-SH1/2 (EXD-PM, ECP-024) hat eine potentielle Zündquelle und entspricht nicht den ATEX Bestimmungen. Installation nur in nicht explosionsgefährdeter Umgebung. Für brennbare Kältemittel nur Ventile und Zubehörteile, die dafür zugelassen sind verwenden!
Abmessungen (mm):
Sicherheitshinweise:
Lesen Sie die Betriebsanleitung gründlich. Nichtbeachtung kann zum
Versagen oder zur Zerstörung des Gerätes und zu Verletzungen führen.
Der Einbau darf nur von Fachkräften vorgenommen werden.
Der Kältekreislauf darf nur in drucklosem Zustand geöffnet werden.
Die Anlage erst in Betrieb nehmen, wenn alle Kabelverbindungen vollständig
sind.
• Die Anlage darf erst dann in Betrieb genommen werden, wenn alle
Verbindungen hergestellt sind.
Kommunikation für elektrische Regelventile
2
)
,
Für den gesamten elektrischen Anschluss sind die länderspezifischen
Vorschriften einzuhalten.
Digitaleingänge sind spannungsbehaftet; nur potentialfreie Schaltkontakte verwenden.
• Entsorgung: Elektro- und Elektronik-Altgeräte dürfen nicht mit anderen Gewerbemüll entsorgt werden. Stattdessen ist es in der Verantwortung Benutzer es zu einem Sammelpunkt für die sichere Entsorgung von Elektro- und Elektronik­Altgeräte (WEEE-Richtlinie 2012/19/EU) zu übergeben. Für weitere Informationen kontaktieren Sie bitte Ihren örtlichen Recyclinghof.
Temperatureinstellungen Direkt- Proportionalbetrieb
(Temperatur-Regelmodus)
Ventilöffnung %
1tbd
100%
Temperatur 0%
1tAL 1tst 1tAH
Temperatureinstellungen Indirekt- Proportionalbetrieb
(Temperatur-Regelmodus)
Ventilöffnung %
1tbd
100%
Temperatur
0%
1tAL 1tst/ 1tAH
Elektrischer Anschluss und Verdrahtung:
Den elektrischen Anschluss gemäß Verdrahtungsschema durchführen!
Hinweis: Signalleitungen und Leitungen mit Netzspannung in getrennten
Kabelschächten verlegen, Mindestabstand 30mm.
Bei Anschluss von EXV-M… (Ventilstecker) muss die Farbe der Adern wie folgt berücksichtigt werden: EXV-M…: WH: Weiß; BK: Schwarz; BN: Braun; BL: Blau
• Die Digitaleingänge DI1 (EXD-SH1/SH2) und DI2 (EXD-SH2) sind die Schnittstellen zwischen EXD-SH1/2 und dem übergeordnetem Systemregler, wenn keine Modbus Kommunikation eingesetzt wird. Die externen Schaltkontakte müssen potentialfrei sein (dry contact) und entsprechend der Systemanforderung angesteuert werden.
Hinweis: Das Aufschalten von externer Spannung auf die Digitaleingänge führt zur dauerhaften Beschädigung des EXD-SH1/2.
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Betriebsanleitung
Kreislauf 1 (EXD-SH1/SH2)
Elektrisches Regelventil Kreislauf 1 (ECV1)
WH-weiß BK-schwarz BL-blau BN-braun
*) Parameter 2uP mit Nr. 8 = nur
Elektrisches Regelventil Kreislauf 2 (ECV2)
WH-weiß BK-schwarz BL-blau BN-braun
2 & 8
Temperaturfühler Kreislauf 1
23 & 24
RS485 (+/-Klemmen)
Alarmrelais Kreislauf 1 (C, NO) – geeignet für 24 VAC/DC
PT5N… Kreislauf 1 & Kreislauf 2 (weiße Ader: 4 – 20 mA Signal)
Alarmrelais Kreislauf 2 (C, NO) – geeignet für 24 VAC/DC
+ 12 VDC Spannungseingang für PT5N… (braune Ader)
Digitaleingang Kreislauf (DI1) – für potentialfreie Kontakte
Alternative ratiometrische Drucktransmitter v.
Fehlerzustände auf der letzten Seite
für potentialfreie
Drucktransmitter Kreislauf 1 & Kreislauf 2 (0,5 - 4,5 V Signal)
11
6,12,13, 18,32-34
Drucktransmitter PT5N-…
EXD-M…
Kabel & Stecker
EXV-M…
Stecker
24 VAC/
B
Temperaturfühler
EXV-M…
Stecker
UPS für bis zu zwei Controller
Ein Supercap für ein EXD
Zwei Supercaps für ein EXD
Siehe Parameter 2uP
EXD-SH1/2 Regler mit ModBus
Kommunikation für elektrische Regelventile
Möglichkeiten Verdrahtung: UPS (ECP-024) /Supercap (EXD-PM)
ECN-N…/ TP1-…/ ECN-Z…
VDC
Kabel &
Kabel &
-SH1
-SH2
Warnung:
Für die 24V Stromversorgung sind ausschließlich Transformatoren der Klasse II zu verwenden. Die 24V Leitungen dürfen nicht geerdet werden. Wir empfehlen die Verwendung jeweils separater EMERSON Transformatoren für EXD-SH1/2 Regler und die Regler anderer Hersteller, weil unter Umständen über die Erdleitungen Kurzschlüsse entstehen können.
Wenn EXD-PM angeschlossen ist, ist es notwendig, dass der EXD-SH-Regler
Kreislauf 2 (EXD-SH2)
Kopierschlüssel
Versorgungsspannung 24 VAC/DC
1 & 7
Temperaturfühler Kreislauf 2
3 & 8
4 & 5
9
Drittanbietern:
Warnung: Beachten sie die Einschränkungen betreffend der
4 & 5
+ 5 VDC Spannungseingang
GND Erdung
10
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
14-17
19-22
25 & 26
27 & 28
29 & 30
31 & 30
35 & 36
EXV-M… elektr. Stecker: Adernfarben
EXV-M… elektr. Stecker: Adernfarben
Digitaleingang Kreislauf 2 (DI2) – Kontakte
Batterie/ Power Modul Anschluss
Sicherung EXD-SH1 (1A), EXD-SH2 (2A)
Nicht verwendet (Terminals on EXD-SH12)
und die EXD-PM-Kondensatoren eigene Transformatoren haben.
Drucksensor von Kreislauf 1 genutzt
Betriebsanleitung
Gewählte Hauptfunktion
Überhitzungsregelung
Verdichter
AN
Verdichter
AUS
Oberes
Anzeigefeld
Überhitzung
(K/F)
Überhitzung
(K/F)
Isttemperatur
(°C/F)
Unteres
Anzeigefeld
Ventilöffnung
(%)
Saugdruck
(bar/psig)
Ventilöffnung
(%)
Wert im oberen Anzeigefeld
Code im unteren Anzeigefeld
Überhitzung (K/F)
SH
Ventilöffnung (%)
OPEn
Saugtemperatur (°C/°F)
tASP
Saugdruck (bar/psig)
PEuA
Sättigungstemperatur (°C/°F)
tEuA
Softwareversion: (0A)
SH1 oder SH2
Die Werte können wiederholt angezeigt werden
Anzeige
Code
Zurück zur Werkseinstellung
-Fdt
Alarme löschen (nur manuell)
ALrr
Parameter und Optionen
Werk-
einstell-
ung
Individ-
Einstell.
Handbetrieb Kreislauf 1
0 1 0 0 = inaktiv 1 = aktiv
1HP
Ventilöffnung (%)
0
100
0
Handbetrieb Kreislauf 2
0 1 0 0 = inaktiv 1 = aktiv
2HP
Ventilöffnung (%)
0
100
0
Nächster
(Abwärts)
Istwertanzeigemodus ist
unteres
Anzeige n-
Kreislauf 1 ist AN
Kreislauf 2 ist AN
AN: Alarm
oberes
Anzeige Parameter
Regelbetrieb
Anzeige Parameter Blinkt:
Parameter
Blinkt:
Nächster
(Aufwärts)
Aktivierung/Deaktivierung
EXD-SH1/2 Regler mit ModBus
Vorbereitungen für die Inbetriebnahme:
• Gesamten Kältekreislauf evakuieren.
Hinweis: Die Elektrischen Regelventile EX/CV werden halb geöffnet
ausgeliefert. Den Kältekreislauf nur bei geschlossenem Ventil mit Kältemittel füllen.
• Die 24V Versorgungsspannung des EXD-SH1/2 einschalten, während die Digitaleingänge (DI1/DI2) offen sind. Das Ventil wird schließen.
• Bei geschlossenem Ventil System mit Kältemittel füllen.
Parametereinstellung: (müssen vor dem Starten geprüft und bei Bedarf angepasst werden)
• Stellen sie sicher, dass die Digitaleingänge (DI1/DI2) offen sind. Schalten sie die 24V Spannungsversorgung des EXD-SH1/2 ein.
• Wenn die Digitaleingänge DI1/DI2 offen sind, müssen die Parameter Passwort (H5), Funktion (1Fct), Kältemittel (1u0/2u0), Drucksensortyp (1uP/2uP) und Regelbereich (1uF/2uF) entsprechend den Systemanforderungen eingestellt werden. Dies ist eine Sicherheitsmaßnahme um zu verhindern, dass versehentlich am Verdichter und an anderen Komponenten Schäden entstehen.
• Sobald die wichtigsten Parameter eingestellt und gespeichert sind, ist der Regler EXD-SH1/2 fertig für die Inbetriebnahme. Alle anderen Parameter könne auch während des Betriebes oder im Stand-By Modus verändert werden.
Anzeige/Tastatur (LEDs and Testenfunktionen)
Kreislauf 1 aktiv
Ventil 1 bzw 2
Ventil geöffnet
Ventil schließt
Parameter/Istwert
Istwertanzeigemodus
manuell aktiviert
Anzeige Beschreibung:
Hinweis: Wenn der Überhitzungswert blinkt ist der Regler im MOP Betrieb.
Istwertanzeigenmodus:
• Es werden jeweils die Istwerte von einem Kreis angezeigt.
• Um von einem Kreis zum anderen zu wechseln kann die Taste betätigt werden. (Funktion nur bei EXD-SH2).
• Durch Drücken der Taste kann die Istwertanzeige aktiviert/deaktiviert werden. Damit können folgende gemessene oder berechnete Istwerte entsprechend der unteren Tabelle abgerufen werden.
Kommunikation für elektrische Regelventile
Kreislauf 2 aktiv
AUS: kein Alarm
Anzeigefeld
Anzeigefeld
wechsel Kreislauf 1 bzw. 2
Einstellung/ Speicherung
Parameter/Istwert
Temperatur-
regelung
Parametereinstellungsmodus:
Der Parametereinstellungsmodus ist durch ein numerisches Passwort geschützt. Die Werkseinstellung ist “12”. Zum starten des Parametereinstellungsmodus:
• Beide Tasten, und für mehr als 5 Sekunden gedrückt halten.
• Im oberen Anzeigefeld wird eine blinkende “0” und im unteren Anzeigefeld “PAS” angezeigt
gedrückt halten bis “12” (das Passwort) angezeigt wird.
• Mit das Passwort bestätigen.
• Mit oder können die Parameter der Liste nacheinander angezeigt werden.
• Mit kann der Parameter der eingestellt bzw. verändert werden soll ausgewählt werden.
• Mit oder können die Werte vergrößert oder verkleinert werden.
• Durch drücken von wird der Wert zwischengespeichert. Der Wert blinkt für kurze Zeit dann wechselt die Anzeige zum nächsten Parameter.
• Diese Abfolge kann für alle einzustellenden Parameter wiederholt werden.
Um die neuen Werte dauerhaft zu speichern und den Einstellmodus zu verlassen:
• Taste drücken
Den Einstellmodus verlassen OHNE die neuen Einstellungen dauerhaft zu speichern:
• Beide Tasten und drücken: die vorherigen Änderungen werden gelöscht und der Parametereinstellmodus wird geschlossen.
• Eine andere Möglichkeit zum Beenden ohne Speicherung ist mehr als 120 Sekunden ohne eine Tasteneingabe zu warten (TIME OUT).
Hinweis: Im Parametereinstellungsmodus wird im unteren Anzeigefeld der
Parameter und im oberen Anzeigefeld der Wert angezeigt.
Spezielle Funktionen (Reset, clear) und Handbetrieb
• Beide Tasten und für mehr als 5 Sekunden gedrückt halten.
• Eine blinkende “0” wird angezeigt.
drücken bis “12” angezeigt wird; (falls ein individuelles, numerisches Passwort eingestellt ist muss dieses eingegeben werden.)
• Mit wird das Passwort bestätigt
Folgende Spezielle Funktionen können ausgewählt werden:
• Die Voreinstellung ist 0, mit 1wird die jeweilige Funktion aktiviert
• Zurück zur Werkseinstellung (-Fdt) kann nur aktiviert werden, wenn die Digitaleingänge DI1/DI2 offen sind.
Handbetrieb Ventile (Service /Wartung):
länger als 5 Sekunden gedrückt halten
Die Auswahl, Änderung und Speicherung der Parameter ist wie beim obigen Parametereinstellungsmodus.
Code
Min Max
uelle
1Ho
2Ho
Hinweis: Während des Handbetriebes sind Funktionsalarme, wie “Zu niedrige Überhitzung” unterdrückt. Deshalb muss die Anlage in diesem Falle sorgfältig mit anderen Mitteln überwacht werden. Der Handbetrieb ist nur für Test und Servicezwecke vorgesehen. Danach sind für den Automatik Betrieb die Parameter 1Ho und 2Ho auf “ 0” zu setzen so dass der Regler entsprechend den Sollwerteinstellungen arbeiten kann.
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Betriebsanleitung
Parameterbeschreibung und
H5
Passwort
1
1999
12
Adr
ModBus Adresse
1
127 1 br
Modbus Baudrate
0 1 0
PAr
Modbus Parität
0 1 0
Regelkreis 2 von EXD-HP2 aktivieren
0 1 1
0 =eingeschaltet 1 = ausgeschaltet
Maßeinheitensystem umstellen
0 1 0
0 = °C, K, bar 1 = F, psig
Kreislauf 1 Parameter
Funktion 0 2
0
0 = Überhitzungsregelung 1 = Temperaturregelung direkt proportional 2 = Temperaturregelung indirekt proportional
Regelungsart Überhitzung
0 2 0
0 = Standard 1 = langsam 2 = Zwischeneinstellung 3 = PID fest einstellbar
Kältemittel
0
19
1
0 = R22 1 = R134a 2 = R507 3 = R404A
12 = R1234ze 16 = R513A 17 = R290* 18 = R1270* 19 = R454C*
Drucksensor
0 8 1
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x 3 = PT5N 6 = Ratiometrisch (Druck relativ) 8 = Modbus
1Prr
Ratiometrischer Bereich (bar)
3
60
30
Ventiltyp 0 12
0
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A 4 = N/A
10 = CV4 11 = CV5-6 12 = CV7
1uF
Ventil-Regelungsbereich (%)
5
100
100
1uu
Start Öffnung (%)
0
100
10
1u9
Dauer Ventilöffnung bei Start (s)
0
120
5
Alarm ein „zu geringe Überhitzung“
0 2 1
0 = aus 1 = ein – autom. Rückstellung 2 = ein Alarm bei 0.5K (bei Dauer > 1 min.); autom. Rückstellung sofort bei 3K
Überhitzungssollwert (K)
0.5
30
6
Bereich = 3-30 K wenn Parameter 1uL auf 1 oder 2
MOP Funktion
0 1 1
0 = aus 1 = ein
MOP Sättigungstemperatur (°C) Werkseinstellung entsprechend dem gewählten Kältemittel (1u0). Einstellung kann geändert werden
Niedrigdruckalarm Regelkreis 1
0 2 0
0 = aus 1 = ein - autom. Reset 2 = ein - Handrückstellung
1PA
Grenzwert für Niederdruckalarm (bar)
-0.8
17.7 0 1Pb
Niedrigdruckalarm Verzögerung (s)
5
199 5 1Pd
Rückstellung Niederdruckalarm (bar)
-0.5
18
0.3
Frostschutzalarm Regelkreis 1
0 2 0
0 = aus 1 = ein - autom. Rückstellung 2 = ein - Handrückstellung
1P2
Grenzwert Frostschutzalarm (°C)
-5 5 0
1P5
Alarmverzögerung Frostschutz (s)
5
199
30
1P-
Überhitzungsregelung Kreislauf 1 (Kp Faktor) Display 1/10K
0.1
10
1.0
1i-
Überhitzungsregelung Kreislauf 1 (Ti Faktor)
1
350
100
1d-
Überhitzungsregelung Kreislauf 1 (Td Faktor) Display 1/10K
0.1
30
3.0
Alarm „zu große Überhitzung“
0 1 0
0 = aus 1 = ein mit Auto Reset
1uA
Grenzwert “Zu große Überhitzung” (K)
16
40
30
1ud
Verzögerung “Zu große Überhitzung” (min)
1
15 3 1tSt
Temperaturregelung Sollwert (°C)
-80
50 4 1tbd
Temperatur-Regelbereich (K)
1
10
2
Temperatur Alarm
0 1 0
0 = aus 1 = ein
1tAL
Alarm unterer Temperaturwert (°C)
-50
50
0
Verzögerung Alarm unterer Temperaturwert (min)
1
10
3
1tAH
Alarm oberer Temperaturwert (°C)
-50
50
15
Verzögerung Alarm Oberer Temperaturwert (min)
1
10
3
Temperatursensor
0 1 0
0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C) 1 = ECN-Z60 ( -80…-40°C) für R23
Parameterbeschreibung und
Kreislauf 2 Parameter (nur EXD-SH2)
Regeloptionen
0 2 0
0 = Standard 1 = langsam 2 = Zwischeneinstellung 3 = PID fest einstellbar
Kältemittel
0
19
1
0 = R22 1 = R134a 2 = R507 3 = R404A
12 = R1234ze 16 = R513A 17 = R290* 18 = R1270* 19 = R454C*
Drucksensor
0 9 1
0 = PT5N-07x 1 = PT5N-18x 2 = PT5N-30x 3 = PT5N 6 = Ratiometrisch (Druck relativ) 8= Modbus 9 = Drucksensor von Kreislauf 1 genutzt (1uP)
2Prr
Ratiometrisch Bereich (bar)
3
60
30
Ventiltyp 0 12
0
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A 4 = N/A
10 = CV4 11 = CV5-6 12 = CV7
2uF
Ventil-Regelungsbereich (%)
5
100
100
2uu
Start Öffnung (%)
0
100
10
2u9
Dauer Ventilöffnung bei Start (s)
0
120
5
Alarm ein „ zu geringe Überhitzung“
0 2 1
0 = aus 1 = ein - autom. Rückstellung 2 = ein Alarm bei 0.5 K (bei Dauer >1 min.); autom. Rückstellung sofort bei 3K
Überhitzungssollwert (K)
0.5
30
6
Bereich = 3-30 K wenn Parameter 2uL auf 1 oder 2
MOP Funktion
0 1 1
0 = aus 1 = ein
MOP Sättigungstemperatur (°C) Werkseinstellung entsprechend dem gewählten Kältemittel (2u0). Einstellung kann geändert werden
Niederdruckalarm Regelkreis 2
0 2 0
0 = aus 1 = ein - autom. Rückstellung 2 = ein - Handrückstellung
2PA
Grenzwert für Niederdruckalarm (bar)
-0.8
17.7 0 2Pb
Niederdruckalarm Verzögerung (s)
5
199 5 2Pd
Rückstellung Niederdruckalarm (bar)
-0.5
18
0.3
2P4
Frostschutzalarm Regelkreis 2
0 2 0
0 = aus 1 = ein - autom. Rückstellung 2 = ein - Handrückstellung
2P2
Grenzwert Frostschutzalarm (°C)
-5 5 0
2P5
Alarmverzug Frostschutz (s)
5
199
30
2P-
Überhitzungsregelung Kreislauf 2
0.1
10
1.0
(Kp Faktor), feste PID Display 1/10K
2i-
Überhitzungsregelung Kreislauf 2 (Ti Faktor), feste PID
1
350
100
2d-
Überhitzungsregelung Kreislauf 2
0.1
30
3.0
(Td Faktor), feste PID Display 1/10K
Alarm “zu große Überhitzung“
0 1 0
0 = aus 1 = ein - autom.-Rückstellung
2uA
Grenzwert “Zu große Überhitzung” (K)
16
40
30
2ud
Verzögerung “Zu große Überhitzung” (min)
1
15
3
Temperatursensor
0 1 0
0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C) 1 = ECN-Z60 ( -80…-40°C) für R23
Kältemittel
Eingestellter Wert (C°)
Refrigerant
Eingestellter Wert (C°))
Refrigerant
Eingestellter Wert (C°)
R22
+13
R744
-5
R449A
+12
R134a
+15
R407A
+10
R450A
+19
R507
+7
R407F
+10
R513A
+13
R404A
+7
R23
-40
R290
+15
R407C
+15
R32
+15
R1270
+15
R410A
+15
R1234ze
+24
R454C
+17
R124
+50
R448A
+12
EXD-SH1/2 Regler mit ModBus
Parametertabelle (hinterlegte Reihenfolge mit Taste):

Code

-C2
-uC
1Fct
1u4
- auswahl Min Max
Kommunikation für elektrische Regelventile
Werk
Code
2u4
4 = R407C 5 = R410A 6 = R124 7 = R744
2u0
8 = R407A 9 = R407F 10 = R23 11 = R32*
2uP
* 13 = R448A 14 = R449A 15 = R450A
-50x 4 = PT5N-150D 5 = PT5N-10P-FLR
-auswahl Min Max Werk
7 = Ratiometrisch (Druck absolute)
4 = R407C 5 = R410A 6 = R124 7 = R744
1u0
8 = R407A 9 = R407F 10 = R23 11 = R32*
1uP
1ut
5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A
1uL
1u5
1u2
1u3
1P9
* 13 = R448A 14 = R449A 15 = R450A
-50x 4 = PT5N-150D 5 = PT5N-10P-FLR
– Handrückstellung
7 = Ratiometrisch (Druck absolute)
- -
(lt. MOP
Tabelle)
2ut
5 = N/A 6 = N/A 7 = N/A 8 = N/A 9 = N/A
2uL
2u5
2u2
2u3
2P9
– Handrückstellung
- -
(lt. MOP
Tabelle)
1P4
2uH
2tt
*) Warnung – Brennbare Kältemittel
EXD-SH1/2 (EXD-PM, ECP-024) hat eine potentielle Zündquelle und entspricht nicht den ATEX Bestimmungen. Installation nur in nicht
1uH
explosionsgefährdeter Umgebung. Für brennbare Kältemittel nur Ventile und Zubehörteile, die dafür zugelassen sind verwenden!
MOP Werkseinstellung:
1tAF
1tdL
1tdH
1tt
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 29.07.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx
Loading...
+ 21 hidden pages