Page 1
EXD-SH1/2 are stand-alone universal superheat and or temperature
Superheat or temperature control
Superheat or temperature control
Other functions: Limitation of evaporating pressure (MOP), Low pressure
Monitoring of sensors and detection of sensor
Optional upload/download key (accessory) for transmission of parameter
in type screw terminals included with
Controller for single refrigeration circuit
Controller for two independent refrigeration circuits
Molex terminal with 3 m wires
Temperature sensor with 3 m cable
Temperature sensor with 6 m cable
Ultralow Temperature sensor with 6 m cable
Pressure transmitters: PT5N (7/16-20UNF connection)
Sensing pressure range -0.8…7 bar
Sensing pressure range 0…18 bar
Sensing pressure range 0…30 bar
Sensing pressure range 0…50 bar
Sensing pressure range 0…150 bar (1/4- 18 NPT)
Pressure transmitters: PT5N (Brazing connection)
Sensing pressure range -0.8…7 bar
Sensing pressure range -0.8…10 bar
Sensing pressure range 0…18 bar
Sensing pressure range 0…30 bar
Sensing pressure range 0…50 bar
EXD-SH1/2 Controller for electrical control valves with ModBus Communication
Capability
controllers for air conditioning units or refrigeration systems.
Features
• EXD-SH1: Control of one valve
• EXD-SH2: Control of two valves in two independent circuits
• Main function
•
switch, freeze protection and manual positioning of valve(s)
• Self-adapting superheat control function in conjunction wit
EX4-8 (EX4-7-FLR) and CV4-7 series
• For multiple refrigerants, including ultralow temperature refrigerant R23
• Modbus (RTU) communication
• Integrated keyboard with two lines display
•
(ECN…/TP1…/PT5N…(FLR)) /stepper motor wiring failures
•
settings among controllers with the same setting
• Low/high superheat alarm as well as other function alarms
• Electrical connection via plug-
controller and Micro Molex EXD-M03 (must be ordered separately)
• DIN rail mounting housing
EXD-SH2
Selection table
Type
Note: Pressure range 18 bar for system with R410A, 30 bar for R410A economizer, 50/150 bar for CO
Description
- 807855
2
www.climate.emerson.com/en-gb
Page 2
M12 Plug and cable for pressure transmitters PT5N(FLR)
Uninterruptible Power supply
Backup battery with two outputs for two controllers
Electrical Terminal Kit for ECP-024
Super cap for only EXD-SH1
(two pieces of EXD-PM required for one EXD-SH2)
Temperature control in normal sense
Temperature control in reverse sense
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Accessories
Type Description
- 807854
Description of functions
Controllers are featured with a main function as superheat controller or temperature controller. The main function is selectable.
Superheat control of evaporators or economizers
This function requires the connection of temperature sensor(s) as well as pressure transmitters(s). The other functions are:
• MOP control: enables the limitation of saturated temperature of suction line (outlet of evaporator/economizer)
• Low pressure behaves similar to low pressure switch including alarm conditions
• Freeze protection is based on saturated temperature from converting measuring suction pressure. It provides alarm condition
below certain adjusted temperature.
Temperature controller
The function is to maintain desired temperature by modulating refrigerant mass flow. If controller is operated as temperature controller,
the connection of pressure transmitter is not required.
In order to fulfill varieties of the applications, the refrigerant mass flow variation can be set according temperature increase or decrease.
(A: Mass flow increases if temperature rises)
Valve opening %
100%
Temperature
0%
Examples of applications:
• Temperature control by throttling suction mass flow (normal sense, A)
• Temperature control by modulating hot gas into inlet or outlet of evaporators (reverse sense, B)
• Discharge temperature control by injecting liquid (normal sense, A)
• Head pressure control by means of temperature control (normal sense, A)
Valve opening %
100%
Temperature
0%
(B: Mass flow decreases if temperature rises)
2
EXD-SH12_TB_EN_0720_R08.docx
Page 3
Electronic expansion valve circuit 1 (EXV1)
WH-white BK-black BL-blue BN-brown
*) Parameter 2uP with No. 8 = only
Electronic expansion valve circuit 2 (EXV2)
WH-white BK-black BL-blue BN-brown
Temperature sensor circuit 1
Alarm relay circuit 1 (C, NO) – Suitable for
24 VAC/DC
PT5N… circuit 1 & circuit 2
(white wire: 4…20 mA signal)
Alarm relay circuit 2 (C, NO) – Suitable for
24 VAC/DC
+ 12 VDC Voltage input for PT5N…
(brown wire)
Digital input circuit1 (DI1) – Dry contact,
potential free
Alternative ratiometric third Party Pressure
Transmitter:
Digital input circuit 2 (DI2) – Dry contact,
potential free
Pressure transmitter circuit 1 & circuit 2
(0.5…4.5 V signal)
Fuse EXD-SH1 (1A), EXD-SH2 (2A)
UPS for u p
to two
control l e r s
Two su p e r c a p s
for one EXD
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Wiring
Wiring options: UPS (ECP-024) /Supercap (EXD-PM)
Circuit 2 (EXD-SH2)
1 & 7 Supply voltage 24 VAC/DC
3 & 8 Temperature sensor circuit 2 25 & 26
14-17
19-22
- S H1
- S H2
EXV-M… Electrical plug: wire colors
EXV-M… Electrical plug: wire colors
Pressure sensor circuit 1 is used
4 & 5
9
4 & 5
10 GND Ground
Note: No hard failure detection if ground wire of transmitter to be interrupted.
EXD-SH12_TB_EN_0720_R08.docx
27 & 28
29 & 30
31 & 30
35 & 36 Battery/Super capacitor connection terminal
Not used (Terminals on EXD-SH12)
3
Page 4
Suitable for removable screw
Included in controller delivery
Analogue input(s): NTC Temperature sensor
Analogue input: PT1000 Temperature sensor
TP1-N… (-45…+150°C operating range)
ECN-Z60 (-80…-40°C sensing range)
Dry contact, potential free
Digital output(s): Alarm relay(s)
Contact is open: During normal operation and supply power OFF
RS485 RTU Modbus, two wires
Valves: EX4-8 (EX4-7-FLR), CV4-7
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Available configuration options
R22, R134a, R507, R404A, R407C, R410A, R124,
Refrigerants
Main function Superheat or and temperature control Superheat control
Pressure transmitters PT5N… or 3 rd party ratio metric PT5N….
Note:
EXD-SH1/2 IS NOT ATEX APPROVED!
Technical Data: EXD-SH1/2
R744, R407A, R407F, R23, R32, R1234ze,
R448A, R449A, R450A, R513A, R290, R1270,
R454C
Selectable Valves
R744 (CO
)
2
Power consumption
Terminals 1 to 12 Suitable for 12 poles molex plug Relative humidity
Terminals 13 to 36
Marking
Input, Output EXD-SH1/2
Analogue input(s): 4…20 mA pressure transmitters
Analogue input(s): 0.5…4.5 V pressure transmitters
Contact is closed: During alarm condition
EXD-SH1: Max. 25 VA
EXD-SH2: Max. 50 VA
version: wire size 0.14…1.5 mm2
,
Description Specification
(12 poles molex plug with
Third party ratio metric pressure transmitters
Resistive Load 24 VAC/DC, max. 1 A
Inductive Load 24 V AC, max. 0.5 A
storage
-25…+60°C
Type: EXD-M03
(to be ordered separately)
4
EXD-SH12_TB_EN_0720_R08.docx
Page 5
Suitable for removable screw version:
wire size 0.14…1.5 mm2
Output: to
driver/controller
Suitable for one EXD-SH1
Two EXD-PM for one EXD-SH2
Lead acid gel rechargeable battery
Number of backup
batteries
Screw terminals
for wire size 0.5…2.5 mm2
Number of outputs to
drivers
70
35
35
117,5
Ø4,3
110
1
2
5
,
5
4
5
59,5
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Optional EXD-PM Supercap
Max. output current
Terminals
- 1.2 A
- 350 mA during charging
Storage
Relative humidity
between EXD-PM and
50 cm
AWG18 wire size
Marking
Optional Uninterruptible Power Supply ECP-024
2, each 12 VDC, 0.8 Ah Mounting DIN rail mounted
Output voltage, UB 18 VDC Connection
2 Relative humidity
Battery recharge time approximately 2 hours Accessories: Terminals
Storage
-20…+65°C
Marking
-20…+70°C
20…85%
non-condensing
,
Dimensions (mm)
EXD-SH1/2 or EXD-PM ECP-024
EXD-SH12_TB_EN_0720_R08.docx
5
Page 6
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Communication
The use of communication is not necessary/mandatory; however, the communication is available for connection to upper level of system
controller (third party controller) in order to perform data and commands transfer as well as data logging. EXD-SH1/2 act as slave and
third party controller is master. In case of several EXD-SH1/2 connections to master, each driver needs to be addressed for proper
communication.
Bus topology
ModBus protocol details
Mode: RTU
Modbus slave address range: 1 to 127 (parameter Adr )
Baud rate: 9600 bps, 19200 bps (default, parameter Br )
Start bit: 1
Data bits: 8
Parity: even (default), no parity (parameter Par )
Stop bits: 1
Master response timeout: 500ms
Transmission Details
ModBus register address ranges
Read-only data: Starting address: 0x0100 (256)
Writable data: Starting address: 0x0200 (512)
Configuration data: Starting address: 0x0300 (768)
6
EXD-SH12_TB_EN_0720_R08.docx
Page 7
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Read Data transmission
Available through Modbus Function code 03 (0x03) Read Holding Registers
Request
Response
*N = Quantity of Input Registers
Error
01 = Function code not supported
02 = Starting Address or register count out of range
03 = Register count out of range
Write Data transmission (single register)
Available through Modbus Function code 06 (0x06) Write Holding Register
Request
Response
Error
01 = Function code not supported
02 = Starting Address out of range
Write Data transmission (multiple registers)
Available through Modbus Function code 16 (0x10) Write Holding Registers
Request
N = register count.
Response
Error
01 = Function code not supported
02 = Register Address invalid
03 = Register Value out of range
EXD-SH12_TB_EN_0720_R08.docx
7
Page 8
2 = reverse temperature control
0x0000: No demand
0x0001: Demand
P1 suction pressure circuit 1
T1 suction temperature circuit 1
0 = No failure
1 = Failure
0 = No failure
1 = Failure
0x0001 = N/A 0x0002 = Low pressure
0x0040 = Min. Temp (Temp. control)
0x0001 = Temp sensor 1 0x0002 = Temp sensor 2 (SH2)
0x0100 = Config inconsistency 2 0x0200 = Power Failure
Superheat set point circuit 1
P2 suction pressure circuit 2
T2 suction temperature circuit 2
0 = No failure
1 = Failure
Temp 2 sensor failure circuit 2
0 = No failure
1 = Failure
Functional alarm circuit 2
0x0001 = N/A 0x0002 = Low pressure
Application state circuit 2
Superheat setpoint circuit 2
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Read-only variables
Modbus
address
dec. / hex.
Description Unit Remarks
Circuit 1
257 / 0x101 Main function, circuit 1
259 / 0x103 Digital input circuit 1
264 / 0x108 Pressure 1 sensor failure circuit 1
265 / 0x109 Temp 1 sensor failure circuit 1
266 / 0x10A Functional Alarm set circuit 1
267 / 0x10B Hardware alarm set
268 / 0x10C Application state circuit 1
1 = temperature control
0x0004 = High superheat 0x0008 = Low superheat
0x0010 = Freeze 0x0020 = Max. Temp (Tem p. control)
0x0004 = Pressure sensor 0 x0008 = Pressure sensor 2 (SH2)
0x0010 = Stepper 1 0x0020 = Stepper 2 (SH2)
0x0040 = Modbus timeout (3 sec.) 0x0080 = Config inconsistency 1
1 = Waiting startup (valve ref pending) 6 = Manual mode
2 = Startup 7 = Power fail
3 = Control 8 = MOP
272 / 0x110 Digital input circuit 2
277 / 0x115 Pressure 2 sensor failure circuit 2
Circuit 2
0x0004 = High superheat 0x0008 = Low superheat
1 = Waiting startup (valve ref pending) 6 = Manual mode
2 = Startup 7 = Power fail
3 = Control 8 = MOP
8
EXD-SH12_TB_EN_0720_R08.docx
Page 9
1 = Resets alarms (only the alarms which are set as manual reset)
Manual valve opening Circuit 1
only active while manual mode is ”on”
Alternative to digital input, circuit 1 via
Modbus
Demand circuit 1
0
1 = enabled
Pressure circuit 1 via Modbus
Pressure if 1uP selection is Modbus Range: -0.1 to 150 barg
Minimum update rate: 1s Alarm timeout: 3 sec.
To set the relay 1 manually, only active when manual mode circuit1 is
”
Manual valve opening Circuit 2
only active while manual mode 2 = on
Alternative to digital input, circuit 2 via
Modbus
Demand circuit 2
0
1 = enabled
Pressure if 2uP selection is Modbus Range: -0.1 to 150 barg
Minimum update rate: 1s Alarm timeout: 3 sec.
To set the relay 2 manually, only active when manual mode circuit 2 is
“
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Writable variables
Modbus
address
dec. / hex.
Display
code
Units Remarks
515 / 0x203 1Ho
517 / 0x205
518 / 0x206
519 / 0x207
520 / 0x208 2Ho
522 / 0x20A
523 / 0x20B
524 / 0x20C
Note: References to control circuit 2 of EXD-SH2 are invisible in configuration/write list if disabled.
circuit 2 via Modbus 1/100 barg
1/100 barg
Circuit 2
= disabled
on”
= off
= disabled
on”
= off
EXD-SH12_TB_EN_0720_R08.docx
9
Page 10
0 = 9600 baud
1 = 19200 baud
0 = parity even
1 = no parity
0 = circuit 2 disabled
1 = circuit 2 enabled Only EXD-SH2
0 = °C, K, barg 1 = °F, psig
Changes only allowed if circuit 1 is in “OFF” state
2 = Temperature control Reverse sense
Changes only allowed if circuit 1 is in “OFF” state
Changes only allowed if circuit 1 is in “OFF” state
Changes only allowed if circuit 1 is in “OFF” state
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
Basically 2 variants are possible to set the parameters:
1. Configuration parameters in flash memory - Max. 1000 overwrite cycle limitation!
2. Configuration parameters in RAM memory - unlimited overwrite cycles possible
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation
Modbus
address
dec. / hex.
770 / 0x302 br Modbus baudrate 0 0 - 1
771 / 0x303 PAr Modbus parity 0 0 - 1
773 / 0x305 -C2 Circuit 2 Enabled
Display
Note: In case of power failure, the stored data from the RAM memory will be lost and controller switches to the
configuration data. (Factory setting)
code
Description Unit
2
1 0 - 1
Default
value
Range Remarks
774 / 0x306 -uC Units conversion 0 0 - 1
Note: 2) References to control circuit 2 if EXD-SH2 are invisible in configuration/write list if disabled
Modbus
address
dec. / hex.
777 / 0x309 1Fct Function circuit 1 0 0 - 2
778 / 0x30A 1u4 Control mode circuit 1 0 0 - 3
779 / 0x30B 1u0 Refrigerant circuit 1 1 0 - 19
780 / 0x30C 1uP Pressure sensor type 1 1 0 - 8
Display
code
Description Unit
Default
value
Circuit 1
Range Remarks
This parameter only affects the display. Internally (as well
as for MODBUS communication) the units are always SI-
0 = superheat control
1 = Temperature control Normal sense
1 = slow control
2 = intermediate control
0 = R22 1 = R134a 2 = R507
3 = R404A 4 = R407C 5 = R410A
6 = R124 7 = R744 8 = R407A
9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A
15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x
2 = PT5N-30x 3 = PT5N-50x
4 = PT5N-150 5 = PT5N-10P-FLR
6 = Ratio metric(gauge) 7 = Ratio metric(absolute)
782 / 0x30E 1ut Valve type 1 0 0 - 12
10
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A
4 = N/A 5 = N/A 6 = N/A 7 = N/A
8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
EXD-SH12_TB_EN_0720_R08.docx
Page 11
Start opening duration valve 1
Superheat setpoint circuit 1
Range = 3 – 30K with 1uL = 1 or 2
MOP sat. temp. limit circuit1
Low pressure alarm cut-out
circuit1
Low pressure alarm delay
circuit1
Low pressure alarm cut-in
circuit1
Freeze alarm cut-out circuit1
Freeze alarm delay circuit1
High superheat alarm mode
circuit 1
0 = disabled
1 = enabled auto-reset
High superheat alarm setpoint
circuit 1
High superheat alarm delay
circuit 1
Min. temperature alarm setpoint
Min. temperature alarm delay
Max. temperature alarm setpoint
Max. temperature alarm delay
Superheat control circuit1
fixed PID Kp factor
Superheat control circuit1
fixed PID Ti factor
Superheat control circuit1
fixed PID Td factor
Display 1/10K,
Kd = Kp*Td
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation (continued)
Modbus
address
dec. / hex.
Display
code
Description Unit
Default
value
Range Remarks
786 / 0x312 1uL
788 / 0x314 1u2 MOP mode circuit 1 1 0 - 1
790 / 0x316 1P9
791 / 0x317 1PA
792 / 0x318 1Pb
793 / 0x319 1Pd
794 / 0x31A 1P4 Freeze alarm mode circuit1 0 0 - 2
797 / 0x31D 1uH
798 / 0x31E 1uA
799 / 0x31F 1ud
Low superheat alarm mode
circuit 1
Low pressure alarm mode
circuit1
1 0 - 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
0 0 - 1
1/10 K 30 16 - 40
min 3 1-15
1 = enabled auto-reset
1 = enabled auto-reset
1 = enabled auto-reset
802 / 0x322 1tAF Temperature Alarm Enable 0 0 - 1
803 / 0x323 1tAL
805 / 0x325 1tAH
809 / 0x329 1tt- Temperature sensor type 0 0 - 1
852 / 0x354 1P-
853 / 0x355 1i-
854 / 0x356 1d-
1/10°C 0 -50 - 50
1/10°C 15 -50 - 50
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
EXD-SH12_TB_EN_0720_R08.docx
11
Page 12
Changes only allowed if circuit 2 is in OFF state
Changes only allowed if circuit 2 is in “OFF” state
Ratio metric range circuit 2
Changes only allowed if circuit 2 is in “OFF” state
Start opening valve circuit 2
Start opening duration valve
circuit 2
Superheat setpoint circuit 2
Range = 3 – 30K with 1uL = 1 or 2
MOP sat. temp. limit circuit 2
Low pressure alarm cut-out
circuit 2
Low pressure alarm delay
circuit 2
Low pressure alarm cut-in
circuit 2
Freeze alarm cut-out circuit 2
Freeze alarm delay circuit 2
High superheat alarm mode
circuit 2
0 = disabled
1 = enabled auto-reset
High superheat alarm setpoint
circuit 2
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation (continued)
Modbus
address
dec. / hex.
Display
code
Description Unit
Default
value
Circuit 2
Range Remarks
810 / 0x32A 2u4 Control mode circuit 2 0 0 - 3
811 / 0x32B 2u0 Refrigerant circuit 2 1 0 - 19
812 / 0x32C 2uP Pressure sensor type circuit 2 1 0 - 9
814 / 0x32E 2ut Valve type circuit 2 0 0 - 12
817 / 0x331 2u9
818 / 0x332 2uL
Low superheat alarm mode
circuit 2
s 5 0 - 120
1 0 - 2
1 = slow control
2 = intermediate control
0 = R22 1 = R134a 2 = R507
3 = R404A 4 = R407C 5 = R410A
6 = R124 7 = R744 8 = R407A
9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A
15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x
2 = PT5N-30x 3 = PT5N-50x
4 = PT5N-150 5 = PT5N-10P-FLR
6 = Ratio metric(gauge) 7 = Ratio metric(absolute)
8 = Modbus
9 = Pressure sensor type and refrigerant settings from
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A
4 = N/A 5 = N/A 6 = N/A 7 = N/A
8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
1 = enabled auto-reset
820 / 0x334 2u2 MOP mode circuit 2 1 0 - 1
822 / 0x336 2P9
823 / 0x337 2PA
824 / 0x338 2Pb
825 / 0x339 2Pd
826 / 0x33A 2P4 Freeze alarm mode circuit 2 0 0 - 2
829 / 0x33D 2uH
830 / 0x33E 2uA
Low pressure alarm mode
circuit 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
0 0 - 1
1/10 K 30 16 - 40
1 = enabled auto-reset
1 = enabled auto-reset
12
EXD-SH12_TB_EN_0720_R08.docx
High superheat alarm delay
circuit 2
Page 13
Superheat control circuit 2
fixed PID Kp factor
Superheat control circuit 2
fixed PID Ti factor
Superheat control circuit 2
fixed PID Td factor
Display 1/10K,
Kd = Kp*Td
0 = circuit 2 disabled
1 = circuit 2 enabled Only EXD-SH2
This parameter only affects the display. Internally (as well
Changes only allowed if circuit 1 is in “OFF” state
2 = Temperature control Reverse sense
Changes only allowed if circuit 1 is in “OFF” state
Changes only allowed if circuit 1 is in “OFF” state
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
1. Configuration parameters In Flash memory - Max. 1000 overwrite cycle limitation (continued)
Modbus
address
dec. / hex.
Display
code
Description Unit
Default
value
Range Remarks
831 / 0x33F 2ud
832 / 0x340 2tt - Temperature sensor type 0 0 - 1
833 / 0x341 2P-
834 / 0x342 2i-
835 / 0x343 2d-
min 3 1-15
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
2. Configuration parameters in RAM memory - unlimited overwrite cycles
Note: In case of power failure, the stored data from the RAM memory will be lost and switch to the configuration data. (Factory setting)
Modbus
address
dec. / hex.
1797 / 0x705 -C2
1798 / 0x706 -uC Units conversion 0 0 - 1
Display
code
Description Unit
Circuit 2 Enabled
3
Default
value
1 0 - 1
Range Remarks
1 = °F, psig
as for MODBUS communication) the units are always SI
Note: 3) References to control circuit 2 of EXD-SH2 are invisible in configuration/write list if disabled
Modbus
address
dec. / hex.
1801 / 0x709 1Fct Function circuit 1 0 0 - 2
1802 / 0x70A 1u4 Control mode circuit 1 0 0 - 3
1803 / 0x70B 1u0 Refrigerant circuit 1 1 0 - 19
1804 / 0x70C 1uP Pressure sensor type 1 1 0 - 8
Display
code
Description Unit
Default
value
Circuit 1
Range Remarks
0 = superheat control
1 = Temperature control Normal sense
1 = slow control
2 = intermediate control
0 = R22 1 = R134a 2 = R507
3 = R404A 4 = R407C 5 = R410A
6 = R124 7 = R744 8 = R407A
9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A
15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x
2 = PT5N-30x 3 = PT5N-50x
4 = PT5N-150 5 = PT5N-10P-FLR
6 = Ratio metric(gauge) 7 = Ratio metric(absolute)
EXD-SH12_TB_EN_0720_R08.docx
13
Page 14
Changes only allowed if circuit 1 is in “OFF” state
Start opening duration valve
1
Superheat setpoint circuit 1
Range = 3 – 30K with 1uL = 1 or 2
MOP sat. temp. limit circuit1
Low pressure alarm cut-out
circuit1
Low pressure alarm delay
circuit1
Low pressure alarm cut-in
circuit1
Freeze alarm cut-out circuit1
Freeze alarm delay circuit1
High superheat alarm mode
circuit 1
0 = disabled
1 = enabled auto-reset
High superheat alarm
setpoint circuit 1
High superheat alarm delay
circuit 1
Min. temperature alarm setpoint
Min. temperature alarm
delay
Max. temperature alarm setpoint
Max. temperature alarm
delay
Superheat control circuit1
fixed PID Kp factor
Superheat control circuit1
fixed PID Ti factor
Superheat control circuit1
fixed PID Td factor
Display 1/10K,
Kd = Kp*Td
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
2. Configuration parameters in RAM memory - unlimited overwrite cycles possible (continued)
Modbus
address
dec. / hex.
1806 / 0x70E 1ut Valve type 1 0 0 - 12
Display
code
Description Unit
Default
value
Range Remarks
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A
4 = N/A 5 = N/A 6 = N/A 7 = N/A
8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
1809 / 0x711 1u9
1810 / 0x712 1uL
1812 / 0x714 1u2 MOP mode circuit 1 1 0 - 1
1814 / 0x716 1P9
1815 / 0x717 1PA
1816 / 0x718 1Pb
1817 / 0x719 1Pd
1818 / 0x71A 1P4 Freeze alarm mode circuit1 0 0 - 2
1821 / 0x71D 1uH
1822 / 0x71E 1uA
1823 / 0x71F 1ud
Low superheat alarm mode
circuit 1
Low pressure alarm mode
circuit1
s 5 0 - 120
1 0 - 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
0 0 - 1
1/10 K 30 16 - 40
min 3 1-15
1 = enabled auto-reset
1 = enabled auto-reset
1 = enabled auto-reset
1826 / 0x722 1tAF Temperature Alarm Enable 0 0 - 1
1827 / 0x723 1tAL
1828 / 0x724 1tdL
1829 / 0x725 1tAH
1830 / 0x726 1tdH
1833 / 0x729 1tt- Temperature sensor type 0 0 - 1
1876 / 0x754 1P-
1877 / 0x755 1i-
1878 / 0x756 1d-
1/10 °C 0 -50 - 50
min 3 1 - 10
1/10°C 15 -50 - 50
min 3 1 - 10
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
14
EXD-SH12_TB_EN_0720_R08.docx
Page 15
Changes only allowed if circuit 2 is in “OFF” state
Changes only allowed if circuit 2 is in “OFF” state
Ratio metric range circuit 2
Changes only allowed if circuit 2 is in “OFF” state
Start opening valve circuit 2
Start opening duration valve
circuit 2
Superheat setpoint circuit 2
Range = 3 – 30K with 1uL = 1 or 2
MOP sat. temp. limit circuit 2
Low pressure alarm cut-out
circuit 2
Low pressure alarm delay
circuit 2
Low pressure alarm cut-in
circuit 2
Freeze alarm cut-out circuit
2
Freeze alarm delay circuit 2
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
2. Configuration parameters in RAM memory - unlimited overwrite cycles (continued)
Modbus
address
dec. / hex.
Display
code
Description Unit
Default
value
Circuit 2
Range Remarks
1834 / 0x72A 2u4 Control mode circuit 2 0 0 - 3
1835 / 0x72B 2u0 Refrigerant circuit 2 1 0 - 19
1836 / 0x72C 2uP
1838 / 0x72E 2ut Valve type circuit 2 0 0 - 12
1841 / 0x731 2u9
1842 / 0x732 2uL
Pressure sensor type circuit
2
Low superheat alarm mode
circuit 2
1 0 - 9
s 5 0 - 120
1 0 - 2
1 = slow control
2 = intermediate control
0 = R22 1 = R134a 2 = R507
3 = R404A 4 = R407C 5 = R410A
6 = R124 7 = R744 8 = R407A
9 = R407F 10 = R23 11 = R32
12 = R1234ze 13 = R448A 14 = R449A
15 = R450A 16 = R513A 17 = R290
0 = PT5N-07x 1 = PT5N-18x
2 = PT5N-30x 3 = PT5N-50x
4 = PT5N-150 5 = PT5N-10P-FLR
6 = Ratio metric(gauge) 7 = Ratio metric(absolute)
8 = Modbus
9 = Pressure sensor type and refrigerant settings from
0 = EX4-6 1 = EX7 2 = EX8 3 = N/A
4 = N/A 5 = N/A 6 = N/A 7 = N/A
8 = N/A 9 = N/A 10 = CV4 11 = CV5+6
1 = enabled auto-reset
1844 / 0x734 2u2 MOP mode circuit 2 1 0 - 1
1846 / 0x736 2P9
1847 / 0x737 2PA
1848 / 0x738 2Pb
1849 / 0x739 2Pd
1850 / 0x73A 2P4 Freeze alarm mode circuit 2 0 0 - 2
1851 / 0x73B 2P2
Low pressure alarm mode
circuit 2
0 0 - 2
1/10 bar 0 -0.8 - 17.7
s 5 5 - 199
1/10 bar 0.3 -0.5 - 18
1/10°C 0 -5 - 5
1 = enabled auto-reset
1 = enabled auto-reset
EXD-SH12_TB_EN_0720_R08.docx
15
Page 16
High superheat alarm mode
circuit 2
0 = disabled
1 = enabled auto-reset
High superheat alarm
setpoint circuit 2
High superheat alarm delay
circuit 2
Superheat control circuit 2
fixed PID Kp factor
Superheat control circuit 2
fixed PID Ti factor
Superheat control circuit 2
fixed PID Td factor
Display 1/10K,
Kd = Kp*Td
EXD-SH1/2 Controller for electrical control valves with ModBus Communication Capability
2. Configuration parameters in RAM memory - unlimited overwrite cycles (continued)
Modbus
address
dec. / hex.
Display
code
Description Unit
Default
value
Range Remarks
1853 / 0x73D 2uH
1854 / 0x73E 2uA
1855 / 0x73F 2ud
1856 / 0x740 2tt- Temperature sensor type 0 - 1
1857 / 0x741 2P-
1858 / 0x742 2i-
1859 / 0x743 2d-
0 0 - 1
1/10 K 30 16 - 40
min 3 1-15
1/10 1.0 0.1 - 10 Display 1/10K
s 100 1 - 350 Ki = Kp/Ti
1/10s 3.0 0.1 – 30
MOP saturation temperature limit table
Refrigerant
°C
Refrigerant
°C
Refrigerant
°C
EXD-SH12_TB_EN_0720_R08.docx
Emerson Climate Technologies GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifi cations, designs and technical data contained in
this document are subject to modi fi cation by us without prior notice. Illustrations are not binding.
The Emerson Climate Technologies logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co.