Emerson CF901VNB00, CF901ORB00, CF901GES00, CF901BS00, CF901CK00 User Manual

Part No. F40BP74460000 Form No. BP7446
U.L. Model No.: CF901
READ AND SAVE THESE INSTRUCTIONS
Ceiling Fan Owner's Manual
CF901BS00 CF901CK00 CF901GES00
PRIMA
Net Weight: 20.3 Lbs.
CF901ORB00 CF901VNB00
WARNING: To avoid fire, shock, and serious personal injury, follow these instructions.
Safety Instructions
1. Read your owner’s manual carefully and keep it for future reference.
2. Before servicing or cleaning unit, switch power off at service panel and lock service panel disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a warning device, such as a tag, to the service panel.
3. Be careful of the fan and blades when cleaning, painting, or working near the fan. Always turn off the power to the ceiling fan before servicing.
4. Do not put anything into the fan blades while they are turning.
5. Do not operate reversing switch until fan blades have come to a complete stop.
Additional Safety Instructions for Installation
1. To avoid possible shock, be sure electricity is turned off at the fuse box before wiring, and do not operate fan without blades.
2. All wiring must be in accordance with the National Electrical Codes “ANSI/NFPA 70-2008” and Local Electrical Codes. Use the National Electrical Code if Local Codes do not exist. The ceiling fan must be grounded as a precaution against possible electrical shock. Electrical installation should be made or approved by a licensed electrician.
3. The outlet box and joist must be securely mounted and capable of reliably supporting at least 50 pounds. Use only U.L. outlet boxes listed as “Acceptable for Fan Support of 22.7 kg. (50 lbs) or less”, and use the mounting screws provided with the outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
4. The downrod furnished with the fan provides the minimum recommended floor to fan blade clearance for an 8 foot ceiling.
5. The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental contact with the fan blades.
6. Follow the recommended instructions for the proper method of wiring your ceiling fan. If you do not know enough about electrical wiring, have your fan installed by a licensed electrician.
NOTE: All set screws must be checked and re-tightened where necessary before installation.
NOTE: This fan is suitable for use with solid-state speed controls.
WARNING: To reduce the risk of fire or electric shock, this fan should only be used with fan speed
control, Model No. SW46/U.L. Model No. UC9020 manufactured by Rhine Electric Co., Ltd.
WARNING: To avoid fire, shock or injury, do not use an Emerson or any other brand of control not specifically approved for this fan.
WARNING: This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
WARNING: To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
WARNING: To reduce the risk of electrical shock, this fan must be installed with an isolating wall control/switch.
WARNING
2
!
DATE CODE:
The date code of this fan may be found on the box, stamped in ink on a white label.
You should record this data above and keep it in a safe place for future use.
U.L. Model No.: CF901
Unpacking Instructions
1. Check to see that you have received the following
parts:
NOTE: If you are uncertain of part description, refer to exploded view illustration.
a. Fan motor assembly b. One switch housing assembly c. Five fan blades d. One ceiling cover e. Five blade flanges f. One hanger ball/downrod assembly g. One hanger bracket h. One coupling cover i. One 4-speed fan speed control j. One loose parts bag containing:
1. Sixteen #10-24 x 7mm washer head blade screws
2. One 1/4-20 x 14 captive screw with lockwasher
3. One #8-32 x 8mm pan head screw
4. Three wire connectors
5. Two threaded studs
6. Two knurled knobs
7. Two lockwashers
This Manual Is Designed to Make it as Easy as Possible for You to Assemble,
Install, Operate and Maintain Your Ceiling Fan
Tools Needed for Assembly
One Phillips head screwdriver One stepladder One 1/4” blade screwdriver One wire stripper
MATERIALS
Wiring outlet box and box connectors must be of type required by the local code. The minimum wire would be a 3-conductor (2-wire with ground) of the following size:
3
Installed Wire Length Wire Size A.W.G.
Up to 50 ft. 14
50-100 ft. 12
Before assembly your ceiling fan, refer to section on proper method of wiring your fan (page 10). If you feel you do not have enough wiring knowledge or experience, have your fan installed by a licensed electrician.
Do not install or use fan if any part is damaged or missing. Call Toll-Free:
1-800-654-3545
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
WARNING
!
WARNING
!
WARNING
!
8. One clevis pin
9. One hairpin clip
10. One balancing kit
NOTE: Place the parts from the loose parts bags in a small container to keep them from being lost. If any parts are missing, contact your local retailer or catalog outlet for replacement before proceeding.
2. Remove the fan assembly from the protective
plastic bag. Place the fan assembly into the upper foam pad with the bottom of the motor facing up.
The upper foam pad serves as a holder for the fan during the first stages of assembly.
U.L. Model No.: CF901
j. LOOSE PARTS BAG
a. FAN MOTOR ASSEMBLY
f. HANGER BALL/ DOWNROD ASSEMBLY
e. BLADE FLANGES
h. COUPLING COVER
i. WALL
i. FAN SPEED
d. CEILING COVER
CONTROL
CONTROL
g. HANGER BRACKET
b. SWITCH HOUSING ASSEMBLY
4
3
2
1
0
c. FAN BLADES
Electrical Requirements
How to Put Your Ceiling Fan Together
4
Figure 2
Figure 1
If your fan is to replace an existing ceiling light fixture, turn electricity off at the main fuse box at this time and remove the existing light fixture.
Your new ceiling fan will require a grounded electrical supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and capable of withstanding a load of at least 50 pounds.
To avoid fire or shock, follow all wiring instructions carefully. Any electrical work not described in these instructions should be done or approved by a licensed electrician.
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
WARNING
!
WARNING
!
To reduce the risk of fire, electrical shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
WARNING
!
It is critical that the clevis pin in the motor coupling is properly installed and the setscrews securely tightened. Failure to verify that the pin and setscrews are properly installed could result in the fan falling.
WARNING
!
U.L. Model No.: CF901
1. Remove the hanger ball by loosening the setscrew
in the hanger ball until the ball falls freely down the downrod (Figure 1). Remove the pin from the downrod, then remove the hanger ball. Retain the pin and hanger ball for reinstallation in step 4.
2. Separate, untwist and unkink the three 80” motor
leads. Route the motor lead wires through the downrod. Remove the upper setscrew from the motor coupling. Align the clevis pin holes in the downrod with the holes in the motor coupling. Install the clevis pin and secure with the hairpin clip (Figure 2). The clevis pin must go through the holes in the motor coupling and the holes in the downrod. Be sure to push the straight leg of the hairpin clip through the hole near the end of the clevis pin until the curved portion of the hairpin clip snaps around the clevis pin. The hairpin clip must be properly installed to prevent the clevis pin from working loose. Pull on the downrod to make sure the clevis pin is properly installed. Reinstall the upper setscrew in the motor coupling. Check that the lower setscrew is tightened securely (Figure 2).
NOTE: The setscrews must be properly installed as described above, or fan wobble could result.
PIN
SETSCREW
DOWNROD
CLEVIS PIN
SETSCREW
SETSCREW
CLEVIS PIN
CLEVIS PIN
UPPER SETSCREW
HANGER BALL
DOWNROD
MOTOR COUPLING
HAIRPIN CLIP
HAIRPIN CLIP
MOTOR COUPLING
How to Put Your Ceiling Fan Together (continued)
3. Make sure the grommet is properly installed in the
coupling cover, then slide the coupling cover on the downrod until it rests on the motor housing. Place the ceiling cover over the downrod. Be sure that the ceiling cover and the coupling cover are both oriented correctly (Figure 3).
4. Reinstall the hanger ball (Figure 3) on the downrod
as follows. Route the three 80” motor leads through the hanger ball. Position the pin through the two holes in the downrod and align the hanger ball so the pin is captured in the groove in the top of the hanger ball. Pull the hanger ball up tight against the pin and securely tighten the setscrew in the hanger ball. A loose setscrew could create fan wobble.
5
Figure 4
DOWNROD
Figure 3
U.L. Model No.: CF901
It is critical that the pin in the hanger ball is properly installed and the setscrew securely tightened. Failure to verify that the pin and setscrew are properly installed could result in the fan falling.
WARNING
!
5. The fan comes with blue, black and white leads
that are 80” long. Before installing fan, measure up approximately 6 to 9-inches above top of hanger ball/downrod assembly. Cut off excess leads and strip back insulation 1/2-inch from end of leads.
6. Carefully turn the partially assembled ceiling fan
over and set it on the shipping styrofoam for blade installation.
7. Remove the shipping spacers and the spacer
attachment screws from the motor before installation of blade assemblies. Discard the spacers and spacer screws (Figure 4).
8. Mount blade flanges to fan blades using three
#10-24 x 7mm washer head blade screws (Figure 5).
NOTE: Take care not to scratch fan housing when installing blades.
NOTE: Remove and discard the four shipping spacers and screws from the motor hub.
9. Loosely attach one blade assembly to the motor
hub using the two 1/4-20 x 14 captive screws with lockwashers. Make sure the screws are NOT tightened. (Figure 6.) Repeat this procedure for other four blade assemblies.
10. The blade flanges have an interlocking feature
that must be fully engaged before tightening the screw. Make sure all the flanges are properly engaged and then tighten the flange screws. If one of the flanges does not seat properly on the motor hub, loosen the adjacent flange screws, re-engage and reseat the flanges, then tighten the screws again.
Figure 5
Figure 6
PIN
HANGER BALL
CEILING COVER
SETSCREW
COUPLING COVER
SWITCH HOUSING MOUNTING PLATE SCREW (4)
#10-24 x 7mm WASHER HEAD BLADE SCREW (3)
FAN BLADE
BLADE FLANGE
CAPTIVE SCREW
LOCKWASHER
SWITCH HOUSING MOUNTING PLATE HOLE
BLADE FLANGE ASSEMBLY
SHIPPING SPACERS AND SCREWS
11. Engage the connector of the switch housing
assembly with the motor connector (Figure 7). The two connectors are keyed and color-coded and must be mated correctly (color-to-color) before they can be engaged. Make sure the connector latch closes properly.
12. Remove the four switch housing mounting
screws (Figure 7) from the switch housing plate. Position the switch housing assembly on the switch housing plate and align the holes in the switch housing assembly with the holes in the plate. Secure the switch housing assembly by installing the four screws (Figure 8).
6
13. You have now completed the assembly of your
new ceiling fan. You can now proceed with hanging and wiring your fan.
How to Put Your Ceiling Fan Together (continued)
To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
WARNING
!
U.L. Model No.: CF901
Figure 7
Figure 8
SWITCH HOUSING ASSEMBLY
SWITCH HOUSING MOUNTING SCREW (4)
MOUNTING SCREWS (4)
MOTOR CONNECTOR
SWITCH HOUSING CONNECTOR
7
How to Hang Your Ceiling Fan
The fan must be hung with at least 7' of clearance from floor to blades (Figure 9).
Figure 9
WARNING
!
The outlet box and joist must be securely mounted and capable of supporting at least 50 lbs. Use only a U.L. outlet box listed as “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”.
WARNING
!
To reduce the risk of fire, electrical shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
WARNING
!
U.L. Model No.: CF901
NOTE: CEILING COVER OMITTED FOR CLARITY.
Figure 11
To avoid possible fire or shock, do not pinch wires between the hanger ball/downrod assembly and hanger bracket.
WARNING
!
Hanger bracket must seat firmly against outlet box. If the outlet box is recessed, remove wall board until bracket contacts box. If bracket and/or outlet box are not securely attached, the fan could wobble or fall.
Failure to seat tab in groove could cause damage to electrical wires and possible shock or fire hazard.
2. Carefully lift the fan and seat the hanger
ball/downrod assembly on the hanger bracket that was just attached to the outlet box (Figure 11). Be sure the groove in the ball is lined up with tab on the hanger bracket (Figure 10).
WARNING
!
WARNING
!
1.Securely attach the hanger bracket to the outlet box
using the two screws supplied with the outlet box. (Figure 10.)
TWO SCREWS SUPPLIED WITH OUTLET BOX
HANGER BRACKET
TAB
OUTLET BOX
Figure 2
Figure 10
NOTE: CEILING COVER, SUPPLY WIRES AND FAN WIRES OMITTED FOR CLARITY.
AT LEAST
7'
CEILING
FLOOR
OUTLET BOX
HANGER BRACKET
HANGER BALL/ DOWNROD ASSEMBLY
8
U.L. Model No.: CF901
How to Wire Your Ceiling Fan
If you feel that you do not have enough electrical wiring knowledge or experience, have your fan installed by a licensed electrician.
1. Connect the green grounding lead from the hanger
ball and the green grounding lead from the hanger bracket to the grounding conductor of supply (this may be a bare wire or wire with green colored insulation). Securely connect wires with wire connectors supplied.
NOTE: If you are using an Emerson Light Fixture with your fan, see Light Fixture Owner’s Manual for wiring.
2. Securely connect the fan motor white wire to the
supply white (neutral) wire using wire connector supplied (Figure 12). Securely connect the fan motor black wire to the supply black (hot) wire using wire connector supplied (Figure 12).
3. If a downlight is not being installed, cap the blue
wire using a supplied wire connector. If a downlight is being installed, a separate hot supply must be available or an optional Emerson accessory control must be used. Follow the installation instruction of the accessory control, if used.
4. If accessory uplight (AL100) is not being installed,
cap the yellow wire using a supplied wire connector. If the AL100 is being installed, a separate hot supply must be available or an optional Emerson accessory control must be used. Follow the installation instruction of both the AL100 and the accessory control, if used.
5. After connections have been made, turn leads
upward and carefully push leads into the outlet box, with the white and green leads on one side of the outlet box and the black, blue and yellow leads on the other side of the outlet box.
To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring.
NOTE: If you are not sure if the outlet box is grounded, contact a licensed electrician for advice, as it must be grounded for safe operation.
Check to see that all connections are tight, including ground, and that no bare wire is visible at the wire connectors, except for the ground wire. Do not operate fan until blades are in place. Noise and fan damage could result.
Figure 12
WARNING
!
WARNING
!
6. Screw the two threaded studs (supplied) into the
tapped holes in the hanger bracket.
7. Lift the ceiling cover up to the threaded studs and
turn until studs protrude through the holes in the ceiling cover (Figure 13).
8. Secure the ceiling cover in place by sliding
lockwashers over the threaded studs and installing the two knurled knobs (supplied). (Figure 13).
To avoid possible fire or shock, make sure that the electrical wires are completely inside the outlet box and not pinched between the ceiling cover and the ceiling.
Figure 13
WARNING
!
Tighten the knurled knobs securely until the ceiling cover fits snugly against the ceiling and the hole in the ceiling cover is clear of the downrod. Your fan is now wired to be turned on and off from the fan switch.
GROUND WIRE
LISTED WIRE CONNECTOR (3)
GREEN WIRE (GROUND) FROM HANGER BRACKET
GREEN WIRE (GROUND) FROM HANGER BALL
THREADED STUDS (2)
KNURLED KNOBS (2)
BLACK FAN WIRE
BLUE FAN WIRE
WHITE SUPPLY (NEUTRAL)
WHITE FAN WIRE
BLACK SUPPLY (HOT)
NOTE: CEILING COVER OMITTED FOR CLARITY.
YELLOW FAN WIRE
CEILING COVER
LOCKWASHERS (2)
Wall Control Installation
9
U.L. Model No.: CF901
The fan speed control is designed to operate only one ceiling fan, and not an accessory light kit. This wall control is rated for 1.2 amps at 120 volts. To avoid erratic speeds and possible damage to your ceiling fan, use this control only with the fan pull chain switch set to its high speed setting.
NOTE: The “0” position is OFF. The four fan speeds are selected by sliding the bar to the other four speed positions (“1”, “2”, “3” and “4”).
1. Before disconnecting power, ensure that the fan is
set at the highest speed.
NOTE: Electric connections should be in accordance with the National Electrical Codes and all Local Codes. Before starting, disconnect power to the circuit at the fuse box or circuit breaker panel.
2. Remove the faceplate and screws from the existing
wall switch. Pull switch out from wall outlet box.
3. Disconnect wire from existing fan wall switch
(Figure 14).
4. Slide the fan control in the OFF position (0).
5. Connect one BLACK wire from the fan speed
control to the fan/motor lead with a wire connector (provided). (Figure 15.)
6. Connect the other BLACK wire from the fan speed
control to the 120VAC hot wire with a wire connector (provided).
NOTE: Use wire connectors (supplied) to secure electrical connections.
7. Attach the fan speed control to the wall outlet box
with two 6-32 x 3/4” screws (provided).
8. Position the faceplate (provided) onto the speed
control. Using the two 6-32 x 1/4” screws, screw the faceplate and speed control to the wall outlet box (Figure 16).
9. Restore power at the main fuse box or circuit
breaker panel.
Figure 14
Figure 16
Figure 15
TO
NEUTRAL
TO FAN LIGHT
4
3
2
1
0
FAN SPEED CONTROL
FACEPLATE
TO FAN MOTOR LOAD
MOTOR LOAD
1.2 AMP MAXIMUM
BLACK
BLACK
OUTLET BOX
4
3
2
1
0
SWITCH
STANDARD ON-OFF WALL LIGHT SWITCH
TO 120VAC
SOURCE HOT
WALL OUTLET BOX
TO 120-VOLT LIGHT SUPPLY HOT
6-32 x 3/4" SCREW (2)
FACEPLATE
6-32 x 1/4" SCREW (2)
10
Accessories
Operation of Reverse Switch
All fans are shipped from the factory with the reversing switch positioned to circulate air downward. If airflow is desired in the opposite direction, turn your fan off and wait for the blades to stop turning, then slide the reversing switch to the opposite position, and turn fan on again. The fan blades will turn in the opposite direction and reverse the airflow (Figure 17).
• Warm weather - (Counterclockwise) A downward air flow creates a cooling effect. This allows you to set your air conditioner on a higher setting without affecting your comfort. The switch is in the left position.
• Cool weather - (Clockwise) An upward air flow moves warm air off the ceiling. This allows you to set your heating unit on a lower setting without affecting your comfort. The switch is in the right position.
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
The use of any other control not specifically approved for this fan could result in fire, shock and personal injury.
1. Ceiling Fan Light Kits (see store or catalog).
2. Ceiling Fan/Light Controls (see store or catalog).
3. Downrod Extension Kits (see store or catalog).
4. Ceiling Fan Blades (see store or catalog).
WARNING
!
WARNING
!
Energy Efficient Use of Ceiling Fans
Ceiling fan performance and energy savings rely heavily on the proper installation and use of the ceiling fan. Here are a few tips to ensure quality and product performance.
Choosing the Appropriate Mounting Location.
Ceiling fans should be installed, or mounted, in the middle of the room and at least 7 feet above the floor and 18 inches from the walls. If ceiling height allows, install the fan 8 - 9 feet above the floor for optimal airflow. Consult your Emerson Retailer for optional mounting accessories.
Using the Ceiling Fan Year Round. In the summer, use the ceiling fan in the counter-clockwise direction. The airflow produced by the ceiling fan creates a wind-chill effect, making you "feel" cooler. Select a fan speed that provides a comfortable breeze, lower speeds consume less energy. In the winter, reverse the motor and operate the ceiling fan at low speed in the clockwise direction. This produces a gentle updraft, which forces warm air near the ceiling down into the occupied space. Remember to adjust your thermostat when using your ceiling fan - additional energy and dollar savings could be realized with this simple step!
Turn Off When Not in the Room. Ceiling fans cool people, not rooms. If the room is unoccupied, turn off the ceiling fan to save energy.
Figure 17
SLIDE REVERSE SWITCH RIGHT OR LEFT TO CHANGE BLADE DIRECTION
REVERSE SWITCH
11
Trouble Shooting
WARNING: For your own safety, turn off power at fuse box or circuit breaker before trouble shooting your fan.
TROUBLE PROBABLE CAUSE SUGGESTED REMEDY
1. Fan will not start. 1. Fuse or circuit breaker blown. 1. Check main and branch circuit fuses or circuit
breakers.
2. Loose power line connections to the fan, 2. Check line wire connections in the switch housing or loose switch wire connections in the to fan and speed switch. switch housing.
WARNING: Make sure main power is turned OFF.
3. Reversing switch in neutral position. 3. Make sure reversing switch position is all the
way to one side.
4. Fan Wall Control is OFF. 4. Turn ON Fan Wall Control.
2. Fan sounds noisy. 1. Blades not attached to fan. 1. Attach blades to fan before operating.
2. Loose screws in motor housing. 2. Check to make sure all screws in motor housing
are snug (not over-tight).
3. Screws securing fan blade flanges to 3. Check to make sure the screws which attach motor hub are loose. the fan flanges to the motor hub are tight.
4. Wire connectors inside switch housing 4. Check to make sure wire connectors in switch rattling. housing are not rattling against each other or
against the interior wall of the switch housing.
WARNING: Make sure main power is turned OFF.
5. Screws holding blades to flanges 5. Tighten screws securely. are loose.
6. Motor noise caused by solid-state 6. Some fan motors are sensitive to signals from variable speed control. Solid-State variable speed controls. If Solid-
State Control is used and motor noise results choose an alternative control method.
3. Fan wobbles 1. Setscrew in motor coupling is loose. 1. Tighten both setscrews securely in the motor excessively. coupling.
2. Setscrew in hanger ball/downrod 2. Tighten the setscrew in the hanger ball/ assembly is loose. downrod assembly.
3. Screws securing fan blade flanges to 3. Check to be sure screws which attach the fan motor are loose. blade flanges to the motor are tight.
4. Fan blade flanges not seated properly. 4. Check to be sure the fan blade flanges seat
firmly and uniformly to the surface of the motor. If flanges are seated incorrectly, loosen the flange screws and retighten according to the procedure in the section on "How to Put Your Ceiling Fan Together".
5. Hanger bracket and/or ceiling outlet 5. Tighten the hanger bracket screws to the outlet box is not securely fastened. box, and/or secure outlet box.
6. Fan blades out of balance. 6. Interchanging an adjacent (side-by-side) blade
pair can redistribute the weight and result in smoother operation.
!
!
!
U.L. Model No.: CF901
Maintenance
IMPORTANT CARE INSTRUCTIONS
for your Ceiling Fan
Periodic cleaning of your new ceiling fan is the only maintenance that is needed.
When cleaning, use only a soft brush or lint free cloth to avoid scratching the finish.
Abrasive cleaning agents are not required and should be avoided to prevent damage to finish.
Do not use water when cleaning your ceiling fan. It could damage the motor or the blades and create the possibility of an electrical shock.
WARNING
!
12
U.L. Model No.: CF901
Repair Parts
20
1
13
4
4
3
2
1
0
7
5
11
10 12
2
3
14
15
6
18
19
16
17
9
8
13
Repair Parts Listing
Key Model Numbers No. Description CF901BS00 CF901CK00 CF901GES00 CF901ORB00 CF901VNB00
* Hanger Ball Assembly, 761655-17 761655-23 761655-35 761655-32 761655-89
Consisting of: 1 Hanger Bracket — 2 Hanger Ball — 3 Downrod (4.5”)
* Parts Bag Containing: 764111-1 764111-1 764111 764111 764111 4 Wire Connector (3) — 5 Pin, Clevis (1) — 6 Clip, Hairpin (1) — 7 Screw, Washer Head,
#10-24 x 7mm (16)
8 Screw, Pan Head,
1/4-20 x 14mm and Lockwasher(1)
9 Screw, Pan Head,
#8-32 x 8mm (1)
10 Lockwasher,
External Tooth #8 (2)
11 Threaded Stud,
#8-32 x 1-1/4” (2) — 12 Knurled Knob, #8-32 (2) — 13 Balancing Kit (1)
14 Canopy, Ceiling (1) 761620-BS 761620-CK 761620-GES 761620-ORB 761620-VNB 15 Motor Coupling Cover (1) 764100-BS 764100-CK 764100-GES 764100-ORB 764100-VNB 16 Wiring Harness (1) 764109 764109-1 764109 764109 764109 17 Switch Housing (1) 764110-BS 764110-CK 764110-GES 764110-ORB 764110-VNB 18 Blade Assembly (set of 5) 764107 764107-2 764107 764107-1 764107-1 19 Flange Assembly (set of 5) 764105-BS 764105-CK 764105-GES 764105-ORB 764105-VNB 20 Speed Switch Wall Control 761971-1 761971-1 761971-1 761971-1 761971-1
Owner's Manual BP7446 BP7446 BP7446 BP7446 BP7446
Before discarding packaging material, be certain all
parts have been removed.
HOW TO ORDER REPAIR PARTS
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING INFORMATION:
• PART NUMBER • PART DESCRIPTION
• NAME OF ITEM • MODEL NUMBER
For repair parts, phone 1-800-654-3545.
14
U.L. Model No.: CF901
Notes
15
U.L. Model No.: CF901
LIMITED WARRANTY
What The Warranty Covers:
This warranty covers the motor and the other components and accessories of your Emerson ceiling fan against all defects in workmanship and materials. You must be the original purchaser or user of the product to be covered.
What The Period Of Coverage Is:
As it applies to the motor, this warranty will last for the lifetime of your ceiling fan. All other components and accessories are covered by this warranty for one year from the date you purchased your ceiling fan. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, MADE WITH RESPECT TO COMPONENTS AND ACCESSORIES IS ALSO LIMITED TO ONE YEAR.
What Will Emerson Electric Co. Do To Correct Problems:
Emerson Electric Co. will replace a defective Emerson Air Comfort Ceiling Fan motor, blade, component or other accessory at no charge to you. If repair of the motor or blades is not practical or possible within a reasonable time and no replacement can be provided, Emerson will refund the actual purchase price of your fan. We will ship the repaired product or replacement to you at no charge, but you are responsible for all costs or removal, reinstallation and shipping of the product to Emerson Electric Co.
How Can You Get Service:
YOU MUST HAVE PROOF OF YOUR PURCHASE OF THE CEILING FAN TO OBTAIN LIMITED WARRANTY SERVICE. KEEP YOUR RECEIPT OR OTHER PROOF OF PURCHASE. You can return the product to our factory or to your nearest authorized service center.
• To return the product to the factory, obtain a return authorization and service identification tag by writing to Air Comfort Products, Division of Emerson Electric Electric Co., 8100 W. Florissant Ave., St. Louis, MO 63136. Include all model numbers shown on the product with your request.
• To return the product to an authorized service center, call 1-800-654-3545 for the address of the nearest authorized service center.
You will be responsible for all insurance, freight or other transportation charges to our factory or authorized service center. Your Emerson Air Comfort Ceiling Fan should be properly packed to avoid damage in transit since we will not be responsible for any such damage.
What Is Not Covered:
The glass globes and light bulbs of your ceiling fan are not covered by this warranty. This warranty also does not cover any defects, malfunctions or failures caused by:
• Repairs by persons not authorized by Emerson Electric Co.,
• Use of parts or accessories not authorized by Emerson Electric Co.,
• Mishandling, improper installation, modifications or damage to your ceiling fan while in your possession, or
• Unreasonable use, misuse, abuse, including failing to do reasonable and necessary maintenance, and normal wear and tear.
Additionally, this warranty and any implied warranty of merchantability or fitness for a particular purpose are voided when:
• The original purchaser or user ceases to own the product, or
• The fan is moved from its original point of installation.
This warranty is only valid within the 50 states of the United States and the District of Columbia. No other written or oral warranties apply, and no employee, agent, dealer or other person is authorized to give any warranties on behalf of Emerson Electric Co.
REPAIR, REPLACEMENT OR A REFUND ARE THE EXCLUSIVE REMEDIES AVAILABLE UNDER THIS WARRANTY AND EMERSON IS NOT RESPONSIBLE FOR DAMAGES OF ANY KIND, INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGES. Incidental damages include but are not limited to such damages as loss of time and loss of use. Consequential damages include but are not limited to the cost of repairing or replacing other property which was damaged if this product does not work properly.
How State Law Relates To The Warranty:
Some states do not allow the exclusion or limitation of incidental or consequential damages so the above exclusion or limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
U.L. Model No.: CF901
Part No. F40BP74460000 Printed in China 12/11 Form No. BP7446
Air Comfort Products
DIVISION OF EMERSON ELECTRIC CO.
8100 W. Florissant • St. Louis, MO 63136
Loading...