Emerson CF830GES00 User Manual

READ AND SAVE THESE INSTRUCTIONS
Part No. F40BP74050000 Form No. BP7405
U.L. Model No.: CF830
Net Weight: 35.3 Lbs.
Model Number
MONACO
Owner's Manual
CF830GES00
Golden Espresso
2
WARNING
!
WARNING: To avoid fire, shock, and serious personal injury, follow these instructions.
Safety Instructions
1. Read your owner’s manual carefully and keep it for future reference
2. Before attempting installation, servicing or cleaning unit, switch power off at service panel and lock service panel disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a warning device, such as a tag, to the service panel.
3. Be careful of the fan and blades when cleaning, painting, or working near the fan. Always turn off the power to the ceiling fan before servicing.
4. Do not put anything into the fan blades while they are turning.
Additional Safety Instructions for Installation
1. To avoid possible shock, be sure electricity is turned off at the fuse box before wiring, and do not operate fan without blades.
2. All wiring must be in accordance with the National Electrical Code “ANSI/NFPA 70-2008” and Local Electrical Codes. Use the National Electrical Code if Local Codes do not exist. The ceiling fan must be grounded as a precaution against possible electrical shock. Electrical installation should be made or approved by a licensed electrician.
3. The outlet box and joist must be securely mounted and capable of reliably supporting a least 50 pounds. Use only U.L. outlet boxes listed as “Acceptable for Fan Support of 50 lbs. or Less”, and use the mounting screws provided with the outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
4. The longer downrod (10”) furnished with the ceiling fan provides the minimum recommended floor-to-fan blade clearance for a 9-foot ceiling. The 4.5” downrod (supplied) is to be used for shorter ceilings.
5. The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental contact with th fan blades.
6. Follow the recommended instructions for the proper method of wiring your ceiling fan. If you do not know enough about electrical wiring, have your fan installed by a licensed electrician.
NOTE: This fan is suitable for use with solid-state speed controls. WARNING: To reduce the risk of fire or electric shock, this fan should only be used with fan speed control,
Model No. SW90/U.L. No. UC9031, manufactured by Rhine Electric Co., Ltd. WARNING: To avoid fire, shock or injury, do not use an Emerson or any other brand of control not specifically
approved for this fan. WARNING: This product is designed to use only those parts supplied with this product and/or any
accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
WARNING: To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
WARNING: To reduce the risk of electrical shock, this fan must be installed with a general use, isolating wall control/switch.
DATE CODE:
The date code of this fan may be found on
the box, stamped in ink on a white label.
You should record this data above and keep
it in a safe place for future use.
U.L. Model No.: CF830
FOR CANADA, THIS FAN MUST BE SECURED DIRECTLY TO THE BUILDING STRUCTURE/CEILING JOIST.
DO NOT SECURE THIS FAN TO AN OUTLET BOX.
3
This Manual Is Designed to Make it as Easy as Possible for You to
Assemble, Install, Operate and Maintain Your Ceiling Fan
One stepladder One wire stripper One Phillips head screwdriver
MATERIALS
Wiring outlet box and box connectors must be of type required by the local code. The minimum wire would be a 3-conductor (2-wire with ground) of the wire size, to right:
Installed Wire Length Wire Size A.W.G.
Up to 50 ft. 14
50-100 ft. 12
If you feel you do not have enough wiring knowledge or experience, have your fan installed by a licensed electrician.
WARNING
!
Unpacking Instructions
For your convenience, check-off boxes are provided next to each step. As each step is completed, place a check mark in the box. This will insure that all steps have been completed and will be helpful in finding your place should you be interrupted.
Do not install or use fan if any part is damaged or missing. Call Toll-Free:
1-800-654-3545
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
WARNING
!
WARNING
!
1. Open styrofoam unit containing fan. Remove upper
and center sections of styrofoam unit. Remove parts and check to see that you have received the following:
a. One Fan Motor and Housing Assembly b. One Ceiling Cover c. Five Fan Blades d. Five Flange Assemblies e. Five Flange Medallion Assemblies f. One Coupling Cover g. One Hanger Bracket h. One 10” Downrod/Hanger Ball Assembly i. One 4.5” Downrod j. One Decorative Upper Scroll k. One Decorative Lower Scroll l. One Switch Housing Adapter m.One Switch Cup/Finial Nut Assembly n. One Fan/Light Dual Slide Wall Control
(transmitter) o. Four 40 Watt Candelabra Base Bulbs p. One loose parts bag containing:
1. One clevis pin
2. One hairpin clip
3. Five 12 Ga wire nut connectors
4. Two #8-32 x 1-14” threaded studs
5. Two #8-32 knurled knobs
Tools Needed for Assembly
6. Two #8 external tooth lockwashers
7. Eleven 1/4-20 x 12mm oval head CR screws
8. Twenty-one #10-32 x 22mm oval head CR screws
9. Five #8-32 x 10mm pan head CR screws
10. One 2mm hex wrench
11. One balancing kit
NOTE: Place the parts from the loose parts bags in small containers to keep them from being lost. If any parts are missing, contact your local retailer or catalog outlet for replacement before proceeding.
U.L. Model No.: CF830
A
B
J
C
4
3
2
1
E
F
G
D
I
H
L
M
K
N
O
P
1. Position the flange medallion upside down on a
soft, clean surface. Place the blade with the decorative side facing down onto the flange medallion. Attach the flange assembly to the blade and flange medallion using the four #10-32 x 22mm oval head screws as shown in Figure 2. Repeat for the four remaining blades.
NOTE: Take care not to scratch fan housing when installing blades.
2. The flange assemblies have interlocking tabs, be
sure that the flanges are installed in a clockwise manner to engage the interlocking feature. Be sure all the flanges are properly engaged and then tighten the flange screws. If one of the flanges do not seat properly on the motor hub, loosen the adjacent flange screws, re-engage and reseat the flanges, then tighten the screws again.
3. Attach the blade/flange assembly using two
1/4-20 x 12mm oval head screws (Figure 3). Install the remaining four fan blades assemblies using the same procedure.
4. Gently snug all flange screws to the motor
housing, working around the housing in a clockwise sequence. Failure to follow this procedure could result in fan wobble. This completes the blade installation.
Figure 2
If your fan is to replace an existing ceiling light fixture, turn electricity off at the main fuse box at this time and remove the existing light fixture.
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with national and local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
WARNING
!
Your new ceiling fan will require a grounded electrical supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and capable of withstanding a load of at least 50 pounds.
To reduce the risk of fire, electric shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support of 50 lbs. or Less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
WARNING
!
Electrical Requirements
Ceiling Fan Assembly
Procedures
To avoid possible fire or shock, follow all wiring instructions carefully. Any electrical work not described in these instructions should be done or approved by a licensed electrician.
WARNING
!
4
IMPORTANT: Your ceiling fan is supplied with an Fan/Light Dual Slide Wall Control (transmitter). This allows you to regulate your ceiling fan speed, airflow direction, and light intensity. Optional Emerson Electric Remote and Wall Control may also be used, see store or catalog.
IMPORTANT: Your ceiling fan will not function properly and may be damaged, if used with any wall dimmer switch or control other than the Emerson controls listed above.
IMPORTANT: Remove the five motor retainers from the motor hub and discard the retainers and retainer screws before installation of flange/blade assembly (Figure 1).
U.L. Model No.: CF830
Figure 1
SHIPPING RETAINERS (5)
FLANGE MEDALLION ASSEMBLY
FAN BLADE
#10-32 x 22mm OVAL HEAD BLADE SCREW (4 per blade/flange)
FAN FLANGE
CAUTION: Before installing and tightening the screws, be sure there are no wires pinched between the switch housing adapter and the switch housing.
8. Make sure all wires and connectors are inside the
switch housing, then position the switch housing on the switch housing plate aligning the three holes for installation.
9. Secure the switch housing by installing the four
#8-32 x 10mm pan head screws (Figure 6).
10. Carefully turn partially assembled fan upside
down and place gently in the styrofoam from carton, in preparation of final installation.
5
U.L. Model No.: CF830
5. Remove and retain one of the switch housing
mounting screws (Figure 4) from the motor hub. Loosen the two remaining switch housing screws.
6. Position the switch housing adapter onto the motor
hub. Rotate the switch housing adapter clockwise to engage the key hole slots (Figure 4). Secure the switch housing adapter to the fan motor housing by reinstalling the previously removed screw into the remaining hole. Tighten the three screws at this time.
To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
WARNING
!
To avoid possible fire or shock, do not pinch wires between the switch housing and the switch housing adapter.
WARNING
!
Figure 4
Figure 5
Figure 6
1/4-20 x 12mm OVAL
Figure 3
7. Engage the connector of the switch housing to the
switch housing adapter connector (Figure 5). The two connectors are keyed and color-coded and must be mated correctly (color-to-color) before they can be engaged. Be sure the connector latch closes properly.
HEAD BLADE SCREW (2 per flange)
BLADE FLANGE
INTERLOCKING FEATURE
SWITCH HOUSING
SWITCH HOUSING ADAPTER
SWITCH HOUSING ADAPTER
SWITCH HOUSING MOUNTING SCREW
SWITCH HOUSING COLOR CODED CONNECTOR
SWITCH HOUSING ADAPTER COLOR CODED CONNECTOR
SWITCH HOUSING
#8-32 X 10mm PAN HEAD SCREW (4)
Loading...
+ 11 hidden pages