EMERSON ADN5-24-3PM, ADN10-24-3PM, ADN20-24-3PM, ADN30-24-3PM, ADN40-24-3PM User Manual

rev 03.25.05
Technical Support: (888) 41ASTEC or (407) 241-2752
Americas: (760) 930-4600 Europe (UK) 44 (1384) 842-211 Asia (HK) 852-2437-9662
190
Special Features
120-960 Watts
ADN Series
Electrical Specs
•Complies with EN61000-3-2
•DC OK Signal (indicator)
•Adjustable Voltage
•Industrial grade design (no derating to 60°C)
•User-friendly front panel
•Single phase input available
•Highly efficient >90% switching technology
•High MTBF and reliability
•Peak current capability 2x rated current for 2 seconds
•Three year warranty
Input
Nominal voltage 380-480 VAC Power factor (PFC) EN61000-3-2 AC Input range 340-576 VAC DC Input range 450-820 VDC Frequency 47 - 63 Hz, 500 Hz Phase 1Ø or 3Ø on 5, 10 & 20A* models.
30A & 40A models are 3Ø only.
Output
Nominal voltage 24V (22.5 - 28.5 VDC Adj.) Holdup time >20ms at full load (25°C) Tolerance <±2% overall
(combination line/load/time/temp) Line regulation <0.5% Load regulation <0.5% Time & temp. drift <1% Initial voltage setting 24.5V ±1% Ripple <50mVpp Parallel Operation Current limit (fold forward)
constant power
10A, 20A, 30A User selectable 40A Active single wire parallel
Over voltage protection >30.5 <33 VDC
*On 20A unit, derate to 75% when operating 1Ø.
Storage/shipment -25°C to +85°C Operating -10°C to 60°C
(convection) (derate to 50% at +70°C) Humidity <90% RH noncondensing
per IEC 68-2-2, 68-2-3 IP20 (EN60529), protection
from moisture & conden­sation
Note: Derate output to 50% when unit is mounted sideways or front side up.
EMC Emissions EN500081-1, -2 Class B EN55011, EN55022
Radiated and Conducted including Annex A.
Immunity EN50082-1, -2; EN61000-4-2, Level 4,
EN61000-4-3 Level 3, EN61000-4-6 Level 3; EN61000-4-4 Level 4 input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11; Transient resistance according to VDE 0160/W2 over entire load range.
Approvals CB Scheme, EN60950; EN50178; EN60204;
UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC) EN61000-3-2, IEC 60079­15 Class 1, Zone 2 hazardous location, Groups IIA, IIB, IIC w/T3 temp class up to 60°C Ambient.
Protection Class 1 (IEC536), degree of protection
SELV rated per EN60950
Environmental
Safety
Total Power: 120 - 960 Watts Input Voltage: 1Ø or 3Ø 380-480 VAC # of Outputs: One
EUROPE
Astec House, Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX, UK
Telephone: 44 (1384) 842-211
Facsimile: 44 (1384) 843-355
AMERICAS
5810 Van Allen Way Carlsbad, CA 92008
Telephone: 760-930-4600
Facsimile: 760-930-0698
191
www.astecpower.com
Ordering Information
ASIA
Units 2111-2116, Level 21
Tower1, Metroplaza
223, Hing Fong Road
Fwai Fong, New Territories
Hong Kong
Telephone: 852-2437-9662
Facsimile: 852-2402-4426
Model Weight Power Input Voltage Current
ADN5-24-3PM 1.7lbs (730g) 120W 380-480VAC 5A ADN10-24-3PM 2.16lbs (980g) 240W 380-480VAC 10A ADN20-24-3PM 3.97lbs. (1800g) 480W 380-480VAC 20A ADN30-24-3PM 4.0lbs (2000g) 720W 380-480VAC 30A ADN40-24-3PM 6.6lbs (3300g) 960W 380-480VAC 40A
ADN Series
Catalog Number
Dimensions - inches (mm)
H W D
ADN5-24-3PM 4.88 (124) 2.91 (73) 4.55 (116)
Catalog Number
Dimensions - inches (mm)
H W D ADN10-24-3PM 4.88 (124) 3.50 (89) 4.55 (116) ADN20-24-3PM 4.88 (124) 5.90 (150) 4.55 (116) ADN30-24-3PM 4.88 (124) 9.72 (247) 4.55 (116) ADN40-24-3PM 4.88 (124) 11.10 (282) 4.55 (116)
Installation
Fusing
-Input Internally fused.
-Output
Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current
overload allows for reliable fuse tripping.
Mounting
Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-
PMBRK2 required).
Connections
Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. 16-12
AWG (0.5-4 mm
2
) for standard conductors. Output: Two connectors per output, connector size range:
16-10 AWG (1.5 - 6mm
2
) for solid conductors.
Case Fully enclosed metal housing with fine ventilation grid to keep out small parts.
-Free Space
25mm above and below
25 mm left and right
15 mm in front
70 mm above and below
25 mm left and right
15 mm in front