Emerson Adapt, iTrust Adapt, UHA3R-0200L User Manual

Page 1
iTrust Adapt UPS 20kVA User Manual
Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.
Copyright © 2010 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change witho ut notice.
Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China Homepage: www.emersonnetworkpower.com.cn E-mail: support@emersonnetwork.com.cn
Page 2
Safety Precauti
ons
This manual contains the information concerning the installation and operation of Emerson iTrust Adapt /20kVA UPS (hereinafter referred to as UPS). Please
carefully read this manual prior to installation. The UPS must be installed, commissioned and serviced by engineers designated by the manufacturer or its
agent. Failure to observe this could result in personnel safety risk, UPS malfunction and invalidation of warranty. The UPS has been designed for commercial and industrial use only, and is not recommended for use in life
support applications. This is a Class A UPS product. In a residential environment, this product may nevertheless cause radio
interference, in which case, the user may be required to take additional measures.
Conformity And Standards
The UPS complies with 2006/95/EC, 93/68/EEC (LV Safety) and 2004/108/EC (EMC), with Australia and New Zealand EMC Framework (C-Tick) and with the following product standards for UPS: * IEC62040-1-1: General and safety requirements for use in operator access area * IEC62040-2: EMC requirements, Class C2 compliant * IEC62040-3: Performance requirements and test methods The UPS installation should follow the above instructions and use the accessories specified by manufacturer.
Warning: High Leakage Current
Earth connection is essential before connecting the input power (AC mains and battery included). This equipment must be earthed in accordance with the local electrical codes. Earth leakage current ranges from 3.5mA to 1000mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous residual current circuit breaker (RCCB) or residual current detector (RCD). RCCB must be selected, which is insensitive to DC unidirectional pulses (Class A) and transient current pulses. Note that the earth leakage current of the load will be carried by RCCB or RCD.
Warning: Reflected Protection
The UPS has a zero-voltage contact closure signal available for use with an external automatic circuit breaker (single power), to protect against backfeeding voltage to input terminal through the static bypass circuit. If the installation engineer do not need to use this signal, the external bypass switchgear must be labelled to advise service personnel that the circuit is connected to a UPS system. The label can be written: ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
Maintainable Components
All equipment internal maintenance and servicing procedures should be carried out only by trained personnel. Removal of components behind the protective cover requires the use of a tool and is restricted to service personnel. The UPS meets the safety requirements completely in operator access area. Only the service personnel can contact with the hazardous voltage inside the UPS. However, the risk of contacting with these voltages is minimized as the components with hazardous voltage may be contacted only uses a tool to remove the protective cover. No risk will exist if you follow the general norms and in accordance with the procedures recommended in this manual on equipment operation.
Page 3
Battery Voltage Above 400Vdc
Tools or keys must be used for all batteries maintenance, which should be carried out by trained personnel. Battery use requires special care. After the battery is connected, the voltage of the battery terminal will exceed 400Vdc, and physical contact would be fatal. Battery manufacturer provides the precautions to be observed when working on, or in the vicinity of the battery string. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.
Page 4
Page 5
Contents
Chapter 1 Product Introduction ........................................................................................................................................... 1
1.1 Feat
ures
................................................................................................................................................................ 1
1.2 Model
Configuration
.............................................................................................................................................. 1
1.3 Appearance And
Components
.............................................................................................................................. 2
1.3.1
Appearance ...............................................................................................................................................
2
1.3.2
Components ..............................................................................................................................................
2
1.4 Operating Principle ............................................................................................................................................... 3
1.5 UPS State And Operation
Mode ...........................................................................................................................
3
1.5.1 Normal
Mode
............................................................................................................................................. 3
1.5.2 Bypass
Mode
............................................................................................................................................. 3
1.5.3 Battery
Mode .............................................................................................................................................
4
1.5.4 ECO Mode (For Single System Only) ........................................................................................................ 4
1.5.5 Fault
State .................................................................................................................................................
4
1.6 S
pec
ificati
ons
........................................................................................................................................................ 5
Chapter 2 Installation .......................................................................................................................................................... 6
2.1 Unpacking I
nspection
............................................................................................................................................ 6
2.2
Location ................................................................................................................................................................
6
2.2.1 Distribution
Room
...................................................................................................................................... 7
2.2.2 Battery
Room
............................................................................................................................................. 7
2.2.3 St
orage
...................................................................................................................................................... 7
2.3 Installation
tools ....................................................................................................................................................
7
2.4 Mechanical Installation.......................................................................................................................................... 8
2.4.1 Tower Installation ...................................................................................................................................... 8
2.4.2 Rack
Installation ........................................................................................................................................
9
2.5 External Protective
Device
.................................................................................................................................. 10
2.5.1 Rectifier And Bypass
Inputting.................................................................................................................
10
2.5.2 Battery
Input ............................................................................................................................................
11
2.5.3 UPS Output ............................................................................................................................................. 11
2.6 Connecting Power Cables .................................................................................................................................. 11
2.6.1 Cables Selection...................................................................................................................................... 11
2.6.2 Connecting I/O
Cables
............................................................................................................................. 12
2.6.3 Connecting Battery
Cables
...................................................................................................................... 17
2.7 Connecting Communication
Cables....................................................................................................................
18
2.7.1 Connecting Dry Contact Communication Cable ...................................................................................... 18
2.7.2 Connecting USB Communication
Cable
.................................................................................................. 19
2.7.3 Connecting SNMP Card Communication
Cable ......................................................................................
19
2.8 Parallel System ................................................................................................................................................... 20
Page 6
2.8.1 Mechanical Installation ............................................................................................................................ 20
2.8.2 Setting Parallel A
ddresses
....................................................................................................................... 21
2.8.3 Connecting Parallel Cables ..................................................................................................................... 21
2.8.4 Connecting 1 + 1 Parallel POD
Cables....................................................................................................
22
2.9 Shared Batt
ery
.................................................................................................................................................... 22
2.10 Double Bus System .......................................................................................................................................... 23
2.10.1 System Installation ................................................................................................................................ 23
2.10.2 External Protective
Device.....................................................................................................................
23
2.10.3 Power
Cables ........................................................................................................................................
23
2.10.4 LBS Control
Cables
............................................................................................................................... 23
Chapter 3 Operation And Display P
ane
l............................................................................................................................ 24
3.1 Int
roduction
......................................................................................................................................................... 24
3.1.1 LED Indicat
ors
......................................................................................................................................... 24
3.1.2 Audible Alarm (B
uzzer)
............................................................................................................................ 24
3.1.3 Control Butt
ons
........................................................................................................................................ 25
3.1.4 LCD And Menu Butt
ons
........................................................................................................................... 25
3.2 LCD Screen T
ypes
.............................................................................................................................................. 25
3.2.1 Start S
creen
............................................................................................................................................. 25
3.2.2 Primary S
creen
........................................................................................................................................ 26
3.2.3 Default S
creen
......................................................................................................................................... 26
3.3 Detailed Description Of Menu Items ................................................................................................................... 27
3.4 Prompt Wi
ndow
................................................................................................................................................... 29
3.5 UPS Alarm Message List .................................................................................................................................... 29
Chapter 4 UPS Operation Inst
ructions
.............................................................................................................................. 32
4.1 UPS Start
-up
....................................................................................................................................................... 32
4.1.1 Normal Module Start-up P
rocedure
......................................................................................................... 32
4.1.2 Battery Module Start-up
Procedure .........................................................................................................
32
4.2 Transferring Procedures Between Operation
Modes
.......................................................................................... 32
4.2.1 Transferring From Normal Mode To Battery
Mode
.................................................................................. 32
4.2.2 Transferring From Normal Mode To Bypass
Mode..................................................................................
33
4.2.3 Transferring From Bypass Mode To Normal
Mode..................................................................................
33
4.2.4 Transferring From Normal Mode To Maintenance Bypass
Mode ............................................................
33
4.3 Complete Shutdown
Procedure ..........................................................................................................................
33
4.4 EPO P
rocedure
................................................................................................................................................... 34
4.5 Auto
Restar
t ........................................................................................................................................................ 34
4.6 UPS Reset P
rocedure
......................................................................................................................................... 34
4.7 Language
Selection ............................................................................................................................................
34
4.8 Changing Current Date And Time....................................................................................................................... 35
4.9 Controlling P
assword
.......................................................................................................................................... 35
Page 7
Chapter 5 Maint
enance
..................................................................................................................................................... 36
5.1 Fan
Maintenance ................................................................................................................................................
36
5.2 Battery Maint
enance
........................................................................................................................................... 36
5.3 Cleaning UPS ..................................................................................................................................................... 36
5.4 Checking UPS
State ...........................................................................................................................................
36
5.5 Checking UPS F
unctions
.................................................................................................................................... 36
Appendix 1 Battery
Module ...............................................................................................................................................
38
Appendix 2 Optional Part List ............................................................................................................................................ 40
Page 8
Page 9
Chapter 1 Product Introduction
1
Chapter 1 Product Intr
oduction
iTrust Adapt and 20kVA UPS (UPS for short) is an intelligent online UPS system with sine wave output developed by Emerson Network Power Co., Ltd. The UPS offers reliable and high quality AC power to your precision instrument. The UPS adopts modular design, and rack/tower installation can be used depending on
your requirements
. It is applicable to supplying AC power to small scale computer center, network, communication system, automatic control system and precision instrument.
This chapter gives a brief description of the UPS, including the UPS features, model configuration, appearance, components, operating principle, state, operation mode and specifications.
1.1 Features
iTrust Adapt UPS is compatible with iTrust Adapt 20kVA UPS. The UPS features include:
Compatible with two modes: 3-phase mains output and single-phase mains output. You should check the system wiring and conduct the panel setting manually
Capable of parallel connection to achieve up to 3 + 1 parallel redundant power
High-frequency double conversion topology structure, with high input power factor, wide input voltage range, and output immune to grid interference, thus adaptable to areas with unstable mains supply
High power density
Full digital control technology based on digital signal processor (DSP) to achieve high system reliability with self-protection and fault diagnosis functions
Intelligent battery management to extend the battery module life
Operation and display panel with both LCD and LED indication to help you learn about the system operation state and operating parameters
3U thickness. Tower installation and rack installation are optional to meet different installation requirements
Capable of ECO power supply mode, which helps you save energy to the maximum extent
Flexible network management with Emerson monitoring software
Fan fault self-test and automatic recognition functions
SNMP card optional, providing network communication function
Capable of connecting multiple battery strings, extending the power supply time of Battery mode
1.2 Model Configuration
The description of model configuration is shown in Table 1-1.
Table 1-1 Model configuration
Model
Description
UHA3R-0200L
For single and parallel 1 + 1 system, four battery modules are available; for parallel system above 1 + 1, battery connection is required
Page 10
2
Chapter 1 Product Introduction
iTrust Adapt UPS 20kVA User Manual
1.3 Appearance And Components
1.3.1 Appearance
The UPS appearance is shown in Figure 1-1.
Ventilation
holes
Operation
and
display panel
DIP switch, battery cold start
button
(with protective cover)
Figure 1-1 UPS appearance
Note
Non-authorized personnel are prohibited from opening the UPS chassis cover. Otherwise, electric shock may occur.
1.3.2 Components
Front panel As shown in Figure 1-1, the UPS front panel provides ventilation holes, operation and display panel, DIP switch and
battery cold start button (with protective cover). The operation and display panel provides LCD, menu buttons, LED indicators and control buttons. Refer to Chapter 3 Operation And Display Panel for details.
Rear panel As shown in Figure 1-2, the UPS rear panel provides parallel ports, load bus synchronization (LBS) ports, dry contact
I/O port, SNMP card port, USB port, I/O terminal block and ventilation holes.
Parallel ports
LBS ports
I/O terminal block (with protective cover)
SNMP card
port
(with
protective cover)
Dry contact I/O port USB port
Ventilation
holes
Figure 1-2 UPS rear panel
Page 11
Chapter 1 Product Introduction
3
1.4 Operating Principle
The operating principle of the UPS is shown in Figure 1-3.
Bypass
I/O filter
Rectifier/PFC
Inverter
Mains
DC/DC charger
Output
Battery
GND GND
Figure 1-3 Operating principle
1. The UPS is composed of mains input, I/O filter, rectifier/PFC, DC/DC charger, inverter, bypass, battery and UPS output.
2. When the mains is normal, the rectifier will start, and the DC/DC charger will charge the battery string. Before turning on the UPS, the output voltage is the bypass voltage. After turning on the UPS, the electronic transfer switch connects the inverter output to the load, and the mains supplies DC power to the inverter through the rectifier/PFC circuit. The inverter then converts DC power into pure sine wave AC power, and supplies AC power to the load through the electronic transfer switch.
3. When the mains is abnormal, the rectifier/PFC circuit boosts the battery voltage and supplies it to the inverter. The inverter then converts it into pure sine wave AC power, and supplies AC power to the load through the electronic transfer switch.
4. After the mains returns to normal state, the UPS will automatically transfer from Battery mode to Normal mode, the mains power supplies DC power to the inverter through the rectifier/PFC circuit, and then the electronic transfer switch supplies DC power to the load.
1.5 UPS State And Operation Mode
The UPS state and operation mode include: Normal mode, Bypass mode, Battery mode, ECO mode and Fault state. For the indicators introduced in this section, refer to Chapter 3 Operation And Display Panel.
1.5.1 Normal Mode
When the mains input is normal, the load is powered with voltage-stabilizing and frequency-stabilizing power by the mains after processing of the rectifier and the inverter, and meanwhile, the operation mode that the charger charging the battery is the Normal mode. In Normal mode, the inverter indicators are on (green).
1.5.2 Bypass Mode
If the overload overtime, inverter or rectifier failure appear during the UPS operation in Normal mode, the UPS will transfer to Bypass mode, that is, the load is powered by the bypass source, which comes directly from the mains input; if the rectifier is normal, the internal charger will charge the battery. In Bypass mode, the inverter indicators are off.
Note
In the event of mains failure or mains voltage out of range in Bypass mode, the UPS will shut down and stop the output.
Page 12
4
Chapter 1 Product Introduction
iTrust Adapt UPS 20kVA User Manual
Page 13
Chapter 1 Product Introduction
5
1.5.3 Battery Mode
Upon mains failure, rectifier overload or mains voltage out of range, the rectifier and internal charger will become inoperative, and the battery will supply power to the load through the inverter. The inverter indicators are on together with buzzer alarming, which notifies you that the UPS is in Battery mode.
Note
1. The battery has been fully charged before delivery. However, transportation and storage will inevitably cause some capacity loss. Therefore, it is required to charge the battery for eight hours before putting the UPS into operation, so as to ensure the adequate stand time for battery.
2. The battery cold start can also be used to start the UPS from the Battery (charged) mode upon mains failure. Therefore, the battery power can be used independently for improving the system availability to some extent.
1.5.4 ECO Mode (For Single System Only)
In ECO mode, the load is powered by bypass when the bypass voltage is normal, and the load is powered by inverter when the bypass voltage is abnormal. ECO mode is an energy-saving operation mode. For some power equipment that insensitive to power grid quality, you can use the ECO mode for power supply through bypass to reduce the power loss.
Note
1. In ECO mode, if the bypass failure or abnormal bypass voltage appears when the output is not overloaded, the UPS will transfer to Normal mode. However, if the bypass failure or abnormal bypass voltage appears when the output is overloaded, the UPS will not transfer to Normal mode, but shut down the bypass.
2. In ECO mode, the efficiency of the UPS is up to 98%.
1.5.5 Fault State
In Normal mode, the UPS will transfer to Bypass mode if the inverter failure or UPS overtemperature appears. In Battery mode, the UPS will shut down and stop the output if the inverter failure or UPS overtemperature appears. In Fault state, the fault indicators will turn on, the buzzer will keep beeping, and the corresponding fault information will be displayed on LCD panel.
Note
In Fault state, if the bypass failure or abnormal bypass voltage appears when the output is not overloaded, the UPS will shut down and be transfered to the inverter for power supply, such as radiator overheat. However, if the bypass failure or abnormal bypass voltage appears when the output is overloaded, the UPS will not be transfered to the inverter for power supply, but shut down the bypass.
Page 14
6
Chapter 1 Product Introduction
iTrust Adapt UPS 20kVA User Manual
1.6 Specifications
The UPS specifications are listed in Table 1-2.
Table 1-2 UPS specifications
Product model
UHA3R-0200L
Input
Rated voltage
3-phase: 380Vac
Voltage range
304Vac ~ 478Vac, at full load 228Vac ~ 304Vac, linear derating 228Vac, at half load
Rated frequency
50Hz/60Hz
Frequency range
40Hz ~ 70Hz
Power factor
0.99, at full load; ≥0.98, at half load
Output
Rated power
18kW
Voltage
220Vac ± 1% (3-phase balance load)
Frequency sync range
Rated frequency ± 2Hz (range is settable: ±0.5Hz ~ ±3Hz)
Frequency track rate
1Hz/s. Range is settable: 0.1Hz/s ~ 3Hz/s (single), 0.2Hz/s (parallel)
Rated power factor
0.9
Crest factor
3:1
Voltage harmonic
distortion
<2% (linear load), <5% (non-linear load)
Dynamic response
recovery time
60ms
Overload capacity
105% ~ 125%, 5min 125% ~ 150%, 1min
Bypass voltage
Upper limit: +10%, +15% or +20%; default: +15% Lower limit: -10%, -20%, -30% or -40%; default: -20%
Mains efficiency
>93%, up to 94%
Battery
Type
Sealed, lead-acid, maintenance-free battery
Cell No.
30, 32, 34, 36, 38, 40
Rated voltage
360Vdc ~ 480Vdc
Charge power
4.5kW
Transfer time
Mains←→Battery
0ms
Inverter←→Bypass
Synchronous transfer: 1ms Asynchronous transfer (default): 20ms Or 40ms, 60ms, 80ms and 100ms are available
Noise
58dB
Panel display mode
LED and LCD
Safety
IEC/EN62040-1-1
EMC
Conduction emission
IEC/EN62040-2
Immunity
I≤16A
IEC/EN61000-3-3; 16A<I75A, IEC/EN61000-3-11
Harmonic current
I≤16A,IEC/EN61000-3-2; 16A<I75A, IEC/EN61000-3-12; YD/T1095-2001, level 2
15%
Surge protection
IEC/EN-61000-4-5, enduration level 4 (4kV) (live line to earth), level 3 (2kV) (during live lines)
Protection level
IP20
Ambient
condition
Operating temperature
0°C ~ +40°C
Storage temperature
-40°C ~ +70°C (battery excluded); -20°C ~ +55°C (battery included)
Relative humidity
5%RH ~ 95%RH, non-condensing
Altitude
<2000m; derating in accordance with GB/T3859.2 when higher than 2000m
Size
W × H × D
435mm × 130mm × 750mm
Weight
Net weight
35kg
Gross weight
38kg
Page 15
Page 16
iTrust Adapt UPS 20kVA User Manual
6
Chapter 2 Installation
Chapter 2 Installation
This chapter introduces the UPS installation. Each site has its peculiarity, so this chapter provides the guidance with general installation procedures and methods for the installation engineer, who should conduct the installation according to the actual conditi ons.
Warning: Professional Installation
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter. If any problem is found, please get in touch with Emerson local service center immediately. Approved by the commissioning engineer, the UPS can be powered on.
Note: 3-phase 5-line for power input
The UPS can be connected to 3-phase 5-line (A, B, C, N, PE) TN, TT and IT AC power distribution system (IEC60364-3).
Warning: Battery Hazards
Special care should be taken into account when installing the battery. When connecting the battery, the voltage of the battery terminal will exceed 400Vdc hazardous voltage.
Eyeshade should be worn to prevent injury from accidental electric arcs
Remove rings, watches and all metal objects
Use tools with insulated handles
Wear rubber gloves
If a battery leaks electrolyte, or is physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and
disposed in accordance with local regulations
If your skin contacts with the electrolyte by accident, wash it immediately with water
2.1 Unpacking Inspection
After the UPS arrival, you should unpack it and check the following items:
1. Visually inspect the UPS appearance for transportation damage. If any problem is found, please notify the carrier immediately.
2. Check the accessories and model against the delivery list. If any problem is found, please notify the dealer immediately.
2.2 Location
To extend the UPS life, the selection of the UPS location should be:
Convenient wiring
Adequate operator access area
Well-ventilated location to meet the heat rejection requirement
Non-corrosive gas surrounded
No excessive moisture and heat sources
Free of dust
Compatible with fire-fighting requirements
Temperature of operation environment complies with the specifications, see Table 1-2 for details
Page 17
Chapter 2 Installation
7
2.2.1 Distribution Room
The UPS is designed for indoor installation, which should be installed in clean and well-ventilated environment, so as to keep the ambient temperature within the specifications range.
The internal fans provide the forced air cooling for the UPS. Cooling air enters the UPS through the front ventilation holes, and exhausts the hot air through the back ventilation holes. Therefore, do not restrict the ventilation holes. The front, rear and side panels of the UPS should be kept at least 200mm distance from the wall or consecutive equipment, so as not to obstruct the UPS ventilation and heat rejection. Otherwise, the UPS internal temperature will rise, which will shorten the UPS life.
If necessary, an indoor extractor fan should be installed to keep the indoor temperature from rising. An air filter should be used where the UPS is to operate in a dirty environment.
Note
The UPS is only suitable for installing on the concrete surface or other non-flammable surfaces.
2.2.2 Battery Room
A small amount of hydrogen and oxygen will be generated at the end of battery charging, therefore, you must ensure the fresh air ventilation of battery installation environment to meet the EN50272-2001 requirements.
The battery ambient temperature should be the constant temperature, for the ambient temperature is the main factor to affect the battery capacity and life. The battery standard operating temperature is 20°C, operation above this temperature will shorten the battery life, and operation below this temperature will reduce the battery capacity. If the battery average temperature in operation rises from 20°C to 30°C, the battery life will be reduced by 50%; if the battery temperature in operation exceeds 40°C, the battery life will be decreased exponentially. In general, the enabled ambient temperature of the battery is 15°C ~ 25°C. The battery should be kept away from heat and ventilation holes.
When the UPS uses an external battery, you must install a battery protective device (such as fuse or circuit breaker) in areas near the battery, and use the shortest wiring distance for the protective device and battery connection.
2.2.3 Storage
The UPS must be stored indoors to protect against the excessive moisture or overtemperature environment, when the UPS does not need to be installed immediately. The battery requires dry and low temperature, well-ventilated environment for storage, and the most suitable storage temperature is 20°C ~ 25°C.
Warning: Battery Hazards
During the battery storage period, the battery must be periodically charged according to the battery instructions. You can connect the UPS to the mains temporarily when charging the battery, so as to charge the battery for battery activation.
2.3 Installation tools
Prepare installation tools according to Table 2-1. The tools must be insulated and ESD-proof processed prior to
use
.
Table 2-1 Installation tools list
Installation tool
Specification
Application
Cross screwdriver
EJ5100mm
Remove the protective cover of terminal block, connect power cables
Wire-pressure plier
YT-12
Press wires for terminal block
Diagonal plier
MTC3C
Make cables
Page 18
iTrust Adapt UPS 20kVA User Manual
8
Chapter 2 Installation
2.4 Mechanical Installation
Note
The UPS is suitable for resistive-capacitive load (like computer), resistive load and micro-inductive load. It is not suitable for purely inductive load or purely capacitive load (like motor, air-conditioner and duplicator), nor can it be connected to half-wave rectifier load.
Two installation modes are available: tower installation and rack installation. You can select an appropriate installation mode according to the actual conditions.
According to different configuration requirements, the UPS has two configurations: battery modules excluded, and four battery modules. For tower installation, you should prepare the battery rack and battery cabinet for installing the battery modules; for rack installation, the battery modules and the UPS can be installed in the same rack together.
2.4.1 Tower Installation
1. Assemble a pair of support bases (accessories) and a support base extension (accessory) together through fastenings, as shown in Figure 2-1.
Support base
Fastening
Support base
extension
Figure 2-1 Connecting the support base with support base extension
2. Repeat step 1 to connect another pair of support bases with a support base extension.
3. Place the UPS on the support bases and support base extensions, as shown in Figure 2-2.
Support base
UPS
Support base
Figure 2-2 Installation complete
Note
For tower installation, two pairs of support bases should be placed respectively at both sides of the UPS, as shown in Figure 2-2. Otherwise, the UPS may be dumped.
Page 19
Chapter 2 Installation
9
2.4.2 Rack Installation
Installation procedures
for battery modules excluded
1. Take out eight M4*10 screws, and fix two brackets (accessories) respectively on both sides of the UPS front panel, as shown in Figure 2-3.
UPS
Bracket (2 pcs)
Screw (8 pcs)
Figure 2-3 Installing brackets
Note
Moving the UPS through brackets is prohibited.
2. Place the UPS on the guide rails in the rack, and push it completely into the rack. Take out four M6*16 screws to fix the UPS on the rack through brackets, as shown in Figure 2-4.
Guide
rail
Rack
UPS
Bracket
Screw (4 pcs)
Figure 2-4 Installing the UPS
Installation procedures
for battery modules included
The installation method of the battery module is the same as that of the UPS. Repeat the above procedures to install and fix the four battery modules and UPS on the rack one by one. As the battery module is heavy, you should pay attention to the following items in installation:
Two persons or more are required for the installation
Install the battery module, start the installation from the bottom, and then place the UPS onto the top, as shown in Figure 2-5
Moving the UPS and battery modules through brackets is prohibited
Page 20
iTrust Adapt UPS 20kVA User Manual
10
Chapter 2 Installation
UPS (1
piece)
Battery
module
(4
pcs)
Figure 2-5 UPS installation diagram of battery modules included
2.5 External Protective Device
The circuit breaker or other protective devices must be installed at the external AC input port of the UPS. This section provides the general guidance for qualified installation engineer. The qualified installation engineer should learn about the local wiring regulations for the equipment to be installed.
2.5.1 Rectifier And Bypass Inputting
Overcurrent The appropriate overcurrent protective device should be installed on the mains input distribution, and the current
capacity of power cable and the system overload requirements should be taken into account in installation (see Table 1-2). It is generally recommended to use the thermomagnet circuit breaker of IEC60947-2 tripping curve C (normal), when the current value reaches 125% of the current value listed in Table 2-2.
Split-bypass: When the system adopts split-bypass, the protective devices should be respectively installed at the mains input distribution for mains and bypass.
Main/Bypass
reflected protection
When using the main/bypass reflected protection function, the gross mains input needs to be equipped with the protective device with auxiliary contact function. The recommended model is S1N125 R125 TM FFC 4P + 1A + 1B + YO (220Vac).
Note
The same neutral must be used for the rectifier and bypass power. For IT power grid system, the protective device with four poles must be installed at the UPS external I/O distribution.
Earth leakage current The residual current detector (RCD) for the UPS upstream input distribution should be:
Sensitive to the DC unidirectional pulse (level A) in distribution network
Insensitive to the transient current pulse
General sensitivity type, settable: 0.3A ~ 1A
Page 21
Chapter 2 Installation
11
The residual current circuit breaker (RCCB) must be sensitive to the DC unidirectional pulse (level A) in distribution network, but insensitive to the transient current pulse, as shown in Figure 2-6 respectively.
Figure 2-6 RCCB symbols
When using the earth RCD in split-bypass system or parallel system, the RCD should be located at the upstream input distribution terminal to avoid generating the false alarm.
The earth leakage current introduced by the RFI filter in the UPS ranges from 3.5mA to 1000mA. It is recommended to confirm the sensitivity of each differential device of the upstream input distribution and downstream distribution (to load).
2.5.2 Battery Input
The overcurrent protective device has been placed into the battery module, when you choose the battery module options provided by Emerson. Otherwise, the external battery cabinet should provide DC compatible circuit breaker, so as to provide the overcurrent protection for the UPS and its batteries.
2.5.3 UPS Output
The protective device must be installed for the UPS output distribution. The protective device must be different from the input distribution protection switches, and it also provides the overload protection (see Table 1-2).
2.6 Connecting Power Cables
I/O cables and battery cables are required for connection. Battery modules provide the battery cable options. When designing the cables, you should follow the instructions in this section and the local wiring regulations, take the
environment situation into account, and refer to Table 3B of IEC60950-1.
Warning
1. Before carrying out the UPS wiring, ensure that you have learned about the location and state of the UPS input and mains distribution switch. Make sure that the switches are in open state, and put up the warning mark to prevent the switches from operating by others.
2. Failure to follow adequate earthing procedures can result in electromagnetic interference, electric shock hazard to personnel, and risk of fire.
2.6.1 Cables Selection
Select the cables according to Table 2-2.
Table 2-2 Maximum steady state AC and DC current
UPS rated
power (kVA)
Rated current (A)
Mains input current
1, 2
upon battery
charging with Max ability
Gross output current
2
at full load
Battery discharging current upon
Min battery voltage
380V
400V
415V
380V
400V
415V
20 (3-in 3-out)
36
36
36
30
29
28
67
20 (3-in 1-out)
36
36
36
90
87
84
67
Note:
1. The mains current input of the rectifier and bypass.
2. Non-linear load (switch mode power) affects the neutral cable design of output and bypass. The neutral cable current may exceed the rated phase current, in general, 1.732 times the rated current
Page 22
iTrust Adapt UPS 20kVA User Manual
12
Chapter 2 Installation
1. PE line: Use the shortest wiring route when connecting the cabinet earth cable. The cross sectional area (CSA) of the earth cable should be selected according to the AC power fault level, cable length and protection type. From
AS/IE
C60950-1,the CSA is 10mm2 (20kVA, 3-in 3-out), 25mm2 (20kVA, 3-in 1-out) as usual.
2. When selecting the battery cables, according to the current value shown in Table 2-2, the Max allowable voltage drop is 4Vdc. Do not ring the cables, so as to avoid increasing the electrical magentic interference (EMI).
2.6.2 Connecting I/O Cables
Distribution
mode and terminal block
1. Distribution mode There are two modes for UPS distribution: single power output distribution (POD) unit options provided by Emerson,
external distribution by the user. According to the actual requirements, the I/O cable connections are divided into four types: 3-in 3-out,
common
source
configuration (factory default), 3-in 3-out, split-bypass configuration, 3-in 1-out, common source configuration, 3-in 1-out, split-bypass configuration. In accordance with the four types of the two distribution methods, this section will introduce the I/O cables connection procedures respectively.
Note
This product is compatible with 3-in 3-out/3-in 1-out, factory default: 3-in 3-out. Change the format according to the following steps, if you need the 3-in 1-out system:
1. After the 3-in 1-out I/O connections are finished by following the instructions in this section, power on the system, then press the emergency power off (EPO) button immediately.
2. Set the system to Single Phase Output’ through the LCD menu ‘Settings -> 3-in 3-out/3-in 1-out.
3. Power off the system completely, then power it on again, the system will run in 3-in 1-out mode.
2. Terminal block The power cables connection of the UPS should be connected through the I/O terminal block located on the UPS rear
panel. Figure 2-7 gives the terminals distribution of the I/O terminal block.
Bat
+
Bat -
oN
oA oB oC
Bat N
PE
mN bN mA bA mB bB mC bC
3
3
3
3
Note: 1. Main input: mA, mB, mC, mN; Bypass input: bA, bB, bC, bN
Output: oA, oB, oC, oN; Battery: Bat +, Bat N, Bat -; GND: PE
2. In factory, four shorted copper bars 3 have been used to short terminals between mA and bA, mB and bB, mC and bC, mN and bN respectively
Figure 2-7 Terminals distribution of the I/O terminal block
Page 23
Chapter 2 Installation
13
When using the single POD options, the UPS power cables should be connected through the user terminal block, UPS terminal block and PE terminals of the single POD rear panel. The terminal distribution of each terminal block on the POD rear panel and PE terminals are shown in Figure 2-8.
User terminal
block
oN oN oA oB oC
3 3 3 3
mN bN mA bA
mB
bB mC bC
PE PE
oN oN oA oB oC mN bN mA bA mB bB mC bC
PE PE
UPS terminal
block
Note: 1. Main input: mA, mB, mC, mN; Bypass input: bA, bB, bC, bN
Output: oA, oB, oC, oN; Battery: Bat +, Bat N, Bat -; GND: PE
2. In factory, four shorted copper bar s 3 have been used to short terminals between mA and bA, mB and bB, mC and bC, mN and bN respectively
Figure 2-8 Terminals distribution of the terminal blocks and PE terminals
The UPS I/O terminal block, the single POD user terminal block and UPS terminal block all have protective covers. Before the connection, you should remove the protective cover of each terminal block; after the connection, you should reinstall these protective covers.
Warning
After the cables connection, you must reinstall the protective cover of each terminal block, so as to avoid the electric shock when the UPS is in operation state.
Single POD
options
(Recommended)
3-in 3-out, common source configuration (factory default)
1. Connect the live line (input phase A, input phase B and input phase C), N line and PE line respectively to the user terminal block (mA, mB, mC and mN terminals) and PE terminals of the single POD.
2. Connect the live line (output phase A, output phase B and output phase C), N line and PE line respectively to the user terminal block (oA, oB, oC and oN terminals) and PE terminals of the single POD.
3. Remove all the shorted copper bars 3 from the UPS I/O terminal block, connect the UPS terminal block of the single POD with the same silkprint terminal of the UPS I/O terminal block using one-to-one correspondence method, and connect two PE terminals of the UPS I/O terminal block to the single POD PE terminals.
3-in 3-out, split-bypass configuration
1. Remove all the shorted copper bars 3 from the single POD user terminal block.
2. Connect the live line (mains phase A, mains phase B and mains phase C), N line and PE line respectively to the user terminal block (mA, mB, mC and mN terminals) and PE terminals of the single POD.
3. Connect the live line (bypass phase A, bypass phase B and bypass phase C), N line and PE line respectively to the single POD user terminal block (bA, bB, bC and bN terminals).
4. Connect the live line (output phase A, output phase B and output phase C) and N line respectively to the single POD user terminal block (oA, oB, oC and oN terminals).
5. Remove all the shorted copper bars 3 from the UPS I/O terminal block, connect the UPS terminal block of the single POD with the same silkprint terminal of the UPS I/O terminal block using one-to-one correspondence method, and connect two PE terminals of the UPS I/O terminal block to the single POD PE terminals.
Page 24
iTrust Adapt UPS 20kVA User Manual
14
Chapter 2 Installation
3-in 1-out, common source configuration
Note
Except for the shorted copper bar 3, all the shorted copper bars mentioned in the installation procedures are the delivery accessories.
1. Short bA, bB and bC terminals of the single POD user terminal block using the shorted copper bar 7, short oA, oB and oC terminals using the shorted copper bar 5, and short mA and bA terminals using the shorted copper bar 6, then short mN and bN terminals, two oN terminals respectively using two shorted copper bars 4, as shown in Figure 2-9.
7
4
5
4
6
8
oN oN oA oB oC mN bN mA bA mB bB mC bC
PE PE
oN oN oA oB oC mN bN mA bA mB bB mC bC
PE PE
Figure 2-9 Shorted copper bars connection for single POD user terminal block
2. Connect the shorted copper bar 8 to one end of the shorted copper bar 7 (see Figure 2-9), and connect the live line (input phase A) to the shorted copper bar 8.
3. Connect the live line (input phase B and input phase C), N line and PE line respectively to the user terminal block (mB and mC terminals), shorted copper bar 4 of mN and bN terminals, and PE terminals of the single POD.
4. Connect the live line (output phase A), N line and PE line respectively to the shorted copper bar 5 of the user terminal block, shorted copper bar 4 of two oN terminals, and PE terminals of the single POD.
5. Remove all the shorted copper bars 3 from the UPS I/O terminal block, and connect the UPS terminal block of the single POD with the same silkprint terminal of the UPS I/O terminal block using one-to-one correspondence method.
6. As shown in Figure 2-10, you can paste the insulating film (accessory) to the shorted copper bar 10, and insert the buckles into the corresponding holes on the shorted copper bar 10.
Shorted copper
bar 10
Buckle
Insulating film
Assembling
Completed status
Figure 2-10 Pasting the insulating film to the shorted copper bar 10
7. As shown in Figure 2-11, you can short two PE terminals of the UPS I/O terminal block using the shorted
copper
bar
10 with an insulating film, and connect two screw holes of the shorted copper bar 10 to PE terminals of the single
POD.
Page 25
Chapter 2 Installation
15
PE
10
Figure 2-11 Shorted copper bar 10 for PE terminals of the UPS I/O terminal block
3-in 1-out, split-bypass configuration
1. Short bA, bB and bC terminals of the single POD user terminal block using the shorted copper bar 7, short oA, oB and oC terminals using the shorted copper bar 5, and then short mN and bN terminals, two oN terminals respectively using two shorted copper bars 4, as shown in Figure 2-12.
7
4
5
4
8
oN oN oA oB oC mN bN mA bA
mB
bB mC bC
PE PE
oN oN oA oB oC mN bN mA bA mB bB mC bC
PE PE
Figure 2-12 Shorted copper bars connection for single POD user terminal block
2. Connect the live line (mains phase A, mains phase B and mains phase C), N line and PE line respectively to the user terminal block (mA, mB and mC terminals), shorted copper bar 4 of mN and bN terminals, and PE terminals of the single POD.
3. Connect the shorted copper bar 8 to one end of the shorted copper bar 7 (see Figure 2-12), and connect the live line (bypass phase A) to the shorted copper bar 8.
4. Connect the bypass N line to the shorted copper bar 4 of of the single POD user terminal block (mN and bN terminals).
5. Connect the live line (output phase A), N line and PE line respectively to the shorted copper bar 5 of the user terminal block, shorted copper bar 4 of two oN terminals, and PE terminals of the single POD.
6. Remove all the shorted copper bars 3 from the UPS I/O terminal block, and connect the UPS terminal block of the single POD with the same silkprint terminal of the UPS I/O terminal block using one-to-one correspondence method.
7. As shown in Figure 2-10, you can paste the insulating film (accessory) to the shorted copper bar 10, and insert the buckles into the corresponding holes on the shorted copper bar 10.
8. As shown in Figure 2-11, you can short two PE terminals of the UPS I/O terminal block using the shorted
copper
bar
10 with an insulating film, and connect two screw holes of the shorted copper bar 10 to PE terminals of the single
POD. Self-distribution
Before carrying out the self-distribution, you should prepare the protective devices such as the mains miniature circuit breaker (MCB), bypass MCB, output MCB and maintenance MCB. It is recommended to use the 63A mains MCB, 125A bypass MCB, and 100A output MCB.
3-in 3-out, common source configuration (factory default)
1. Connect the live line (input phase A, input phase B and input phase C), N line and PE line respectively to the I/O terminal block (mA, mB, mC and mN terminals) and PE terminals of the UPS.
2. Connect the live line (output phase A, output phase B and output phase C), N line and PE line respectively to the I/O terminal block (oA, oB, oC and oN terminals) and PE terminals of the UPS.
Page 26
iTrust Adapt UPS 20kVA User Manual
16
Chapter 2 Installation
3-in 3-out, split-bypass configuration
1. Remove all the shorted copper bars 3 from the UPS I/O terminal block.
2. Connect the live line (mains phase A, mains phase B and mains phase C), N line and PE line respectively to the I/O terminal block (mA, mB, mC and mN terminals) and PE terminals of the UPS.
3. Connect the live line (bypass phase A, bypass phase B and bypass phase C), N line and PE line respectively to bA, bB, bC and bN terminals of the UPS I/O terminal block.
4. Connect the live line (output phase A, output phase B and output phase C), N line and PE line respectively to the I/O terminal block (oA, oB, oC and oN terminals) and PE terminals of the UPS.
3-in 1-out, common source configuration
1. As shown in Figure 2-10, you can paste the insulating film (accessory) to the shorted copper bar 10, and insert the buckles into the corresponding holes on the shorted copper bar 10.
2. As shown in Figure 2-13, you can short two PE terminals of the UPS I/O terminal block using the shorted copper bar 10 with an insulating film, short bA, bB and bC terminals using the shorted copper bar 7, short oA, oB and oC terminals using the shorted copper bar 5, and short mA and bA terminals using the shorted copper bar 6 and then short mN and bN terminals, two oN terminals using two shorted copper bars 4.
oN
oA oB oC
PE
mN
bN mA bA bB
bC
7
6
8
4 5 10
4
Figure 2-13 Shorted copper bars connection for UPS I/O terminal block
3. Connect the shorted copper bar 8 to one end of the shorted copper bar 7 (see Figure 2-13), and connect the live line (input phase A) to the shorted copper bar 8.
4. Connect the live line (input phase B and input phase C), N line, PE line respectively to the I/O terminal block (mB and mC terminals), shorted copper bar 4 of mN and bN terminals, and one screw hole of shorted copper bar 10 of the UPS.
5. Connect the live line (output phase A), N line and PE line respectively to the shorted copper bar 5 of the I/O terminal block, shorted copper bar 4 of two oN terminals and the other screw hole of shorted copper bar 10 of the UPS.
3-in 1-out, split-bypass configuration
1. As shown in Figure 2-10, you can paste the insulating film (accessory) to the shorted copper bar 10, and insert the buckles into the corresponding holes on the shorted copper bar 10.
2. Short two PE terminals of the UPS I/O terminal block using the shorted copper bar 10 with an insulating film, short bA, bB and bC terminals using the shorted copper bar 7, and short oA, oB and oC terminals using the shorted copper bar 5, and then short mN and bN terminals, two oN terminals using two shorted copper bars 4, as shown in Figure 2-14.
Page 27
Chapter 2 Installation
17
oN
oA oB oC
PE
mN
bN bA
bB
bC
7
4 5
10 4
8
Figure 2-14 Shorted copper bars connection for UPS I/O terminal block
3. Connect the live line (mains phase A, mains phase B and mains phase C), N line, PE line respectively to the I/O terminal block (mA, mB and mC terminals), shorted copper bar 4 of mN and bN terminals, and one screw hole of the shorted copper bar 10 of the UPS.
4. Connect the shorted copper bar 8 to one end of the shorted copper bar 7 (see Figure 2-14), and connect the live line (bypass phase A) to the shorted copper bar 8.
5. Connect the bypass N line to the shorted copper bar 4 of mN and bN terminals of the UPS I/O terminal block.
6. Connect the live line (output phase A), N line and PE line respectively to the shorted copper bar 5, shorted copper bar 4 of two oN terminals, and the other screw hole of shorted copper bar 10 of the UPS I/O terminal block.
Warning
Before the commissioning engineer arrival, if the load is not ready for accepting the power, please take good care of the safety insulation located at the end of the output cable.
After the I/O cables connection, you should find the label shown in Figure 2-15 on the UPS chassis protective cover for convenient maintenance, and then tick ‘√’ at the right side of OUTPUT and ‘BYPASS’, according to the actual conditions.
Figure 2-15 Label
2.6.3 Connecting Battery Cables
Note
If the battery module is not selected, this product needs to be equipped with positive and negative batteries. Each battery string ranges from 15-cell to 20-cell, and 12V for each cell.
Connection procedures for battery cables are as follows:
1. Confirm that all UPS external I/O switches are open.
2. Connect the battery cables.
Selected battery modules (4 pcs)
Page 28
iTrust Adapt UPS 20kVA User Manual
18
Chapter 2 Installation
SALARM
GND
On_battery
GND
On_bapass
GND
Epo_NC
+12V
+12V
Epo_IN
BFP_o
BFP_s
BFP_c
1) Take out the UPS options and select battery cables, insert the battery cables marked with Battery Module 1’, Battery Module 2, Battery Module 3 and Battery Module 4 respectively into any battery port on the rear panel of the four battery modules (see Figure 2).
2) Ground one end of the battery cable marked with UPS PE.
3) Connect the other end of the battery cables marked with ‘BAT +’, BAT N, BAT - respectively to Bat +’, Bat N, Bat - terminals of the UPS I/O terminal block (see Figure 2-7).
4) Tighten the fixing screws on both battery port sides of the battery module through screwdriver, so as to prevent the battery cable from loosing or coming off.
Non-selected battery
modules
Connect the external battery with terminals +’, ‘N’ and ‘-’ respectively to ‘Bat +’, ‘Bat N’ and Bat - terminals of the UPS I/O terminal block (see Figure 2-7).
Note
1. It is prohibited to reverse the positive pole and negative pole of the battery.
2. Before replacing the battery module and connecting the battery cables, ensure that the UPS system is in maintenance mode.
3. The length of the battery cable option is 1.5m. If you need more length cables, please consult the dealer. It is recommended that the battery cable be shorter than 3m. Otherwise, the UPS cannot operate normally.
2.7 Connecting Communication Cables
Communication cables include: dry contact communication cable, USB communication cable and SNMP card communication cable.
All communication cables are the dual insulation cables which must be separated from the power cables for wiring. When the longest connection distance ranges from 25m to 50m, the CSA should be ranged from 0.5mm2 to 1.5mm2.
2.7.1 Connecting Dry Contact Communication Cable
The UPS provides five dry contact ports, see Figure 1-2 for specific positions. The silkprints of the five dry contact ports are 1, 2, 3, 4, 5. The pin distribution of each dry contact port is shown in Figure 2-16, and the port description is shown in Table 2-3.
+12V
Dry contact port 1
Dry contact port 2 Dry contact port 3
Dry contact port 4 Dry contact port 5
Figure 2-16 Pin distribution of dry contact ports
Table 2-3 Description of the dry contact ports
Silkprint
Port name
Pin NO.
Pin name
Meaning
1
Output port of alarm
1.1
S_ALARM
The signal level is 12V, when the system alarms
1.2
GND
GND
2
Output port of battery status
2.1
ON_BATTERY
The signal level is 12V, when the system runs in battery inversion mode
2.2
GND
GND
3
Output port of bypass status
3.1
ON_BYPASS
The level is 12V, when the system runs in bypass mode
3.2
GND
GND
Page 29
Chapter 2 Installation
19
Silkprint
Port name
Pin NO.
Pin name
Meaning
4
Input port of remote EPO *
4.1
EPO_NC
EPO activated, when opened to 4.2
4.2
+12V
EPO activated, when opened to 4.1
4.3
+12V
EPO activated, when shorted to 4.4
4.4
EPO_IN
EPO activated, when shorted to 4.3
5
Output port of bypass reflected
5.1
BFP_O
Bypass reflected protection relay (normally open), the bypass silicon controlled rectifier (SCR) will close when short circuit appears
5.2
BFP_S
The middle point of the bypass reflected protection relay
5.3
BFP_C
Bypass reflected protection relay (normally open), the bypass SCR will open when short circuit appears
Note*: Pin1 and pin2, or pin3 and pin4 of the dry contact port 4 reserves the corresponding terminals for configuring the EPO function. The external EPO device also needs the shielded cable to connect to the normally open/close remote EPO switch between the two terminals. If not necessary, you should disconnect pin3 and pin4 of the dry contact port 4, or short pin1 and pin2 of the dry contact port 4. Pin1 and pin2 of the dry contact port 4 have been shorted before delivery
Note
The EPO action of the UPS will close the rectifier, inverter and static bypass, but it can not disconnect the UPS mains input inside. If you want to disconnect the UPS completely, just disconnect the upstream input switch when generating the EPO,.
2.7.2 Connecting USB Communication Cable
Insert one end of the USB communication cable accessory into the USB port on the UPS rear panel (see Figure 1-2), and insert the other end of the USB communication cable into the computer USB port.
2.7.3 Connecting SNMP Card Communication Cable
The UPS provides the installation communication components of the SNMP card port (see Figure1-2), including: SNMP card, dry contact card and MODBUS card. For the installation and usage of the communication components, refer to the delivered documentation of each communication component. SNMP card port and USB port can be used together.
The pin distribution of each SNMP card port is shown in Figure 2-17.
GND_SNMP
SNMPSIG
+9_SNMP
RXD_SNMP TXD_SNMP
RXD232 TXD232
+9_TR
1
2 3
4 5
6 7 8
9
10
14 PIN
Figure 2-17 Pin distribution of SNMP card ports
Page 30
iTrust Adapt UPS 20kVA User Manual
20
Chapter 2 Installation
The pin description of each SNMP card port is shown in Table 2-4.
Table 2-4 Pin description of SNMP card ports
Pin
Description
1, 9
GND of SNMP card
2
SNMP card power prov ided by DSP panel
3
Signal from the SNMP card, which connects with RXD of the DSP
4
Signal to SNMP card, which connects with TXD of the DSP
5
Connect with RX of the RS232 communication port of the host
6
Connect with TX of the RS232 communication port of the host
7
Reserved
8
Selected communication signal, +9_TR is introduced into this pin after the SNMP card is plugged
10
The power supplied by DSP panel, for selecting the card
Note
If you wish to connect the SNMP card (model: UF-SNMP810) to Emerson temperature sensor (model: RDU-A-S01T) to make it be the battery temperature compensation, please connect the COM1 port of the SNMP card, and set the temperature sensor DIP address to 1’.
Warning
The DIP switch on the UPS front panel (see Figure1-1) is used to set the parallel address for each UPS single in parallel system installation. You are not required for setting the DIP switch in UPS single system installation. Set the DIP switch at will can result in UPS fault!
2.8 Parallel System
The UPS parallel system provides the user with N + X (2≤N + X4) parallel configuration, N stands for the basic parallel sets, X stands for the redundant sets.
The UPS parallel system has 1 + 1 parallel POD options, which can provide safe and reliable distribution function for parallel system. The 1 + 1 parallel system only needs one 1 + 1 parallel POD; if N≥2, the self-distribution will be required for the parallel system.
Parallel system installation includes:
Mechanical installation
Setting parallel addresses
Parallel cables connection
1 + 1 parallel POD cables connection
2.8.1 Mechanical Installation
Taking the rack installation of the 1 + 1 parallel system including battery module for example, the mechanical installation method of the parallel system is as follows:
1. The installation method of 1 + 1 parallel POD is the same as that of the UPS. Refer to 2.4.2 Rack Installation for details.
2. As shown in Figure 2-18, the battery module should be installed at the bottom, the UPS should be installed in the middle, and the 1 + 1 parallel POD should be installed on the top, so as to facilitate the cable connection and operation.
Page 31
Chapter 2 Installation
21
1 + 1 parallel POD (1 piece)
UPS (2
pcs)
Battery module (4 pcs)
Figure 2-18 1 + 1 parallel system including battery modules
2.8.2 Setting Parallel Addresses
The parallel addresses for all the UPS singles in parallel system should be set. The parallel addresses can be set through the DIP switch on the UPS front panel (see Figure 1-1). Remove the DIP switch protective cover, and set the DIP switch according to Table 2-5. The parallel address must be unique for each UPS singl e.
Table 2-5 DIP switch settings
Parallel addresses Parallel 1# Parallel 2# Parallel 3# Parallel 4#
DIP switch position
ON
DIP1 DIP2 DIP3 DIP4 DIP5
ON
DIP1 DIP2 DIP3 DIP4 DIP5
ON
DIP1 DIP2 DIP3 DIP4 DIP5
ON
DIP1 DIP2 DIP3 DIP4 DIP5
Warning
The default setting for DIP switch is1’, you can set the DIP switch to 2, 3 or 4. However, you should set the DIP switch position according to the description listed in Table 2-5. Otherwise, the UPS fault will occur!
2.8.3 Connecting Parallel Cables
The parallel system provides the parallel cable options. Through the parallel ports (see Figure 1-2) on the UPS rear panel, the parallel cables are connected in close-loop mode one by one. Taking the 3 + 1 parallel system for example, the schematic diagram of the parallel cables connection is shown in Figure 2-19.
UPS1 UPS2 UPS3
UPS4
Parallel cable Parallel cable
Parallel
port 1
P
arallel
port 1
Parallel
port 1
Parallel
port 1
Parallel cable
Parallel
port 2
Parallel
port 2
Parallel
port 2
Parallel
port 2
Parallel cable Parallel
cable
Figure 2-19 Parallel cables connection schematic diagram (3 + 1 parallel system)
Page 32
iTrust Adapt UPS 20kVA User Manual
22
Chapter 2 Installation
2.8.4 Connecting 1 + 1 Parallel POD Cables
Connecting 1 + 1 parallel POD cables includes: connecting cables between the UPS and 1 + 1 parallel POD and connecting input and output cables of the 1 + 1 parallel POD.
Connecting
cables between the UPS and 1 + 1 parallel POD
Connect the UPS1 terminal block (silkprint: UPS1) on the 1 + 1 parallel POD rear panel to the same silkprint terminal on the UPS1rear panel I/O terminal block using the one-to-one correspondence method. Connect the UPS2 terminal block (silkprint: UPS2) on the 1 + 1 parallel POD rear panel to the same silkprint terminal on the UPS2
rear panel I/O terminal block using one-to-one correspondence method.
Note
1. When connecting cables, connect the UPS end at first, and then connect the 1 + 1 parallel POD end.
2. For kinds of system connection differences such as 3-in 3-out (common source configuration), 3-in 3-out (split-bypass configuration), 3-in 1-out (common source configuration), 3-in 1-out (split-bypass configuration), refer to 2.6.2 Connecting I/O Cables.
Connecting
I/O cables of the 1 + 1 parallel POD
Note
1. An upstream protective MCB must be series connected between the 1 + 1 parallel POD and the mains. It is recommended to use 80A MCB in mains and 150A MCB in bypass.
2. Confirm reliable connection for the earth cable.
1. Connect the input cables.
For 3-in 3-out parallel system, connect the input cables (U, V, W, N, PE) respectively to the corresponding
terminals on the user terminal block (silkprint: USER) of the 1 + 1 POD rear panel.
For 3-in 1-out parallel system, connect the input cables (L, N, PE) respectively to the corresponding terminals on
the user terminal block of the 1 + 1 POD rear panel.
2. Connect the output cables. Connect one end of the output cable to the user terminal block of the 1 + 1 parallel POD, and connect the other end
of the output cable to the load.
2.9 Shared Battery
All the UPS singles in parallel system not only can share the battery string, but also can use the battery string independently. The use of the shared battery in parallel system can save money for you.
The following section will introduce the wiring and setting operation of the shared battery in parallel system.
Note
Each UPS single should be equipped with the independent battery MCB. Refer to Table 2-2 and voltage of battery string for battery MCB type.
1. Wiring: Power off the system completely and disconnect all battery MCBs of the UPS single, and then connect ‘+’, ‘N’ and - terminals of the shared battery respectively to Bat +’, Bat N’ and Bat - terminals (see Figure 2-7) of the corresponding UPS single I/O terminal block in parallel syste m, through each battery MCB.
2. Setting: Power on the system, set each UPS single to shared battery configuration through the LCD menu
Settings -> Shared Battery’ from each UPS single; set the LCD menu ‘Settings’ -> ‘Battery Cells Number’ and Single Group Batt Cap from each UPS single, and each single setting must be the same.
Page 33
Chapter 2 Installation
23
Note
When the parallel system uses the shared battery, the Single Group Batt Cap’ of the LCD setting of each UPS single stand s for
the gross capacity of battery string, and each single can calculate the battery capacity itself automatically.
3. Close the battery MCB of each single.
2.10 Double Bus System
2.10.1 System Installation
The double bus system is composed of two independent UPS system, and each UPS system can be composed of one or two parallel UPS singles. The double bus system has high reliability, which is suitable for the load with many input terminals. For single input load, you can add a selected static trigger switch (STS) to start the load bus synchronization (LBS).
The double bus system uses LBS to realize the output sync of the two independent (or parallel) UPS systems. One is the main system, and the other is the slave system. The operation mode of the double bus system contains main system and/or slave system for running in Normal or Bypass mode. The typical double bus system is shown in Figure 2-20.
Rectifier input
UPS1
Bypass
UPS2
Rectifier input
Rectifier input
UPS1
Bypass
UPS2
Rectifier input
Parallel
control
cable
LBS
Parallel control
cable
STS
Load
connection
Figure 2-20 Typical double bus system (with the STS and LBS)
2.10.2 External Protective Device
See 2.5 External Protective Device.
2.10.3 Power Cables
See 2.6 Connecting Power Cables.
2.10.4 LBS Control Cables
Just connect the LBS cables respectively to any two LBS ports (see Figure 1-2) of the two parallel systems.
Page 34
iTrust Adapt UPS 20kVA User Manual
24
Chapter 3 Operation And Display Panel
Chapter 3 Operation And Display
Panel
This chapter introduces the functions and use of the compon ents on the UPS operation and display panel, and provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and UPS alarm message list.
3.1 Introduction
The operation and display panel is located on the front door of the UPS. Through the operation and display panel, you can conduct the UPS operation control and query all the UPS parameters, UPS and battery states, and alarm message.
As shown in Figure 3-1, the operation and display panel provides LCD, menu buttons (F1 ~ F
4、H
ELP
)、LED
indicators (inverter indicator and fault indicator ), control buttons (FAULT CLEAR, ON, OFF, ALARM CLEAR, EPO).
LCD
Fault
indicator
Menu buttons
Control
buttons
Inverter indicator
Figure 3-1 Operation and display panel
3.1.1 LED Indicators
The LED indicators are composed of inverter indicator and fault indicator. Table 3-1 gives the indicators
description
.
Table 3-1 Description of LED indicators
LED
Color
State
Meaning
Inverter indicator
Green Steady green
Load power is supplied by the inverter
Blinking green
Inverter on, starting up, synchronizing, or standing by (ECO mode)
Off
Inverter not operating
Fault indicator
Red Blinking red
General fault (such as no battery)
Steady red
Serious fault (such as inverter fault)
Off
No fault
3.1.2 Audible Alarm (Buzzer)
The UPS activity is accompanied with the following two different kinds of audible alarms shown in Table 3-2.
Table 3-2 Audible alarm description
Sound
Meaning
One beep every second
Sound is generated when the UPS alarm appears, such as AC input failure
Continuous beep
Sound is generated when the UPS fault appears, such as fuse or hardware failure
Page 35
Chapter 3 Operation And Display Panel
25
3.1.3 Control Buttons
The operation and display panel provides five control buttons, which functions are described in Table 3-3.
Table 3-3 Description of control buttons
Control button
Silkprint
Description
EPO switch
EPO
Used to disconnect the load power and close the rectifier, inverter, static bypass and battery
Inverter on
ON
Used to start the inverter
Inverter off
OFF
Used to close the inverter
Fault recovery on/off
FAULT CLEAR
Recover the UPS function (clear fault in advance)
Alarm sound silence on/off
ALARM CLEAR
When an audible alarm is active, press this button to silence the audible alarm. Press this button again can restart the buzzer
3.1.4 LCD And Menu Buttons
The operation and display panel provides an LCD and five menu buttons (F1, F2, F3, F4, HELP). Table 3-4 gives the menu buttons function description.
Table 3-4 Menu buttons function description
Button
F1 F2 F3 F4
HELP
Function 1
HOME
ESC
Escape
Left
Right
Enter
Function 2
Up
Down
LCD provides you with the user-friendly interface and the 320 × 240 dot matrix image display. The user-friendly and menu-driven LCD allows you to easily browse through the input, output, load and battery parameters, learn about the current UPS status and alarm message, perform functional setting and control operation. The LCD also stores up to 512 historical alarm records that can retrieve for reference and diagnosis.
3.2 LCD Screen Types
3.2.1 Start Screen
Upon UPS start, the UPS executes the system self-test, and the start screen will appear and remain about 15 seconds, as shown in Figure 3-2.
F1
F2 F3 F4
HELP
Figure 3-2 Start screen
Page 36
iTrust Adapt UPS 20kVA User Manual
26
Chapter 3 Operation And Display Panel
3.2.2 Primary Screen
After the UPS system self-test, the primary screen shown in Figure 3-3 will appear. The primary screen is composed of four windows: system information window, data window, menu window and keypad window.
ITA 020kVA
1 3 3
2
:
0 : 6
System
information
window
L-N
voltage
(V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor
A(AB) B(BC) C(CA)
220 220 220
20.5 20.5 20.5
50.1 50.1 50.1 380 380 380
0.99 0.99 0.99 Output
Data window
Menu window
ES
Keypad window
C
F1
F2 F3 F4
HELP
Figure 3-3 Primary screen
The current icons on top of the F1 ~ F4 and HELP menu buttons give the explanations of each button. From any menu in primary screen, press the F1 button can return to the Output’ menu. For details about the primary screen, refer to 3.3 Detailed Description Of Menu Items.
3.2.3 Default Screen
During the UPS operation, if there is no alarm within 2 minutes, the default screen shown in Figure 3-4 will appear. After a short while, the LCD backlight will turn off. Press any menu button (F1 ~ F4, HELP), the primary screen will appear again.
ITA
020kVA
1 3 3 2
:
0
:
6
Press any
button
to
return
to the main menu
F1
F2 F3 F4
HELP
Figure 3-4 Default screen
Page 37
Chapter 3 Operation And Display Panel
27
3.3 Detailed Description Of Menu Items
The description in the following refers to the LCD primary screen shown in Figure 3-3. System
information wi
ndow
The system information window displays the current time and the UPS name. You are not required for operating the information of this window. For details, see Table 3-5.
Table 3-5 System information window
Item
Explanation
ITA 020kVA
UPS name, which stands for iTrust Adapt 20kVA UPS
12: 30: 36
Current time (format: 24 Hours, h: min: s)
Menu window and UPS data wi
ndow
The menu window displays the menu name of the data window. The data window displays the items of the menu selected from the menu window. UPS parameters can be browsed and functions can be set through the menu window and data window. Details are given in Table 3-6.
Table 3-6 Menu window and data window
Menu
Item
Explanation
Mains L-N voltage (V)
Phase voltage
L-N current (A)
Phase current
Frequency (Hz)
Input frequency
L-L voltage (V)
Line voltage
Power factor
Power factor
Bypass L-N voltage (V)
Phase voltage
Frequency (Hz)
Bypass frequency
L-L voltage (V)
Line voltage
Output L-N voltage (V)
Phase voltage
L-N current (A)
Phase current
Frequency (Hz)
Output frequency
L-L voltage (V)
Line voltage
Power factor
Power factor
Load Sout (kVA)
Sout: Apparent power
Pout (kW)
Pout: Active power
Qout (kVAR)
Qout: Reactive power
Load level (%)
The percentage of the UPS rated load
Crest factor
Output current crest factor
System Sout (kVA)
Sout: Apparent power
Pout (kW)
Pout: Active power
Qout (kVAR)
Qout: Reactive power
Battery
Battery voltage (V)
Battery bus voltage
Battery current (A)
Battery bus current
Battery temperature (°C)
Battery temperature (°C)
Battery remain time (Min.)
Battery run time remaining
Battery capacity (%)
Battery capacity (%), compared to the new battery capacity
Battery boost charging
Battery is boost charging
Battery float charging
Battery is float charging
Battery is not connected
Battery is not connected
Event
(Current alarm)
Display current alarm. See Table 3-8 for UPS alarm message list
Records
(Historical alarm)
Display all historical alarms. See Table 3-8 for UPS alarm message list
Language
(Language selection)
Options are displayed in Chinese or English
Page 38
iTrust Adapt UPS 20kVA User Manual
28
Chapter 3 Operation And Display Panel
Menu
Item
Explanation
Settings
Display contrast
Adjust the LCD contrast
Date format set
YYYY MM DD, DD MM YYYY and MM DD YYYY formats can be selected.
Date & time
Set the date and time
Comm1 baud rate
Set the communication baud rate of the USB port
Comm2 baud rate
For internal communication only, can not be set
Comm3 baud rate
Set the communication baud rate of the SNMP card port
Communication address
This setting is suitable for RS485 communication
Communication mode
Set the communication mode
Callback times
If the communication mode of the SNMP card por t is Modem, you can set alarm callback times here
Phone No.1
If the communication mode of the SNMP card por t is Modem, you can set phone No.1 here
Phone No.2
If the communication mode of the SNMP card por t is Modem, you can set phone No.2 here
Phone No.3
If the communication mode of the SNMP card por t is Modem, you can set phone No.3 here
Command password
You can change the command password. Default: ‘123456
Single Group Batt Cap
Battery capacity
Battery cells Number
Set the battery cell. The setting options include: 30-cell, 32-cell, 34-cell, 36-cell, 38-cell, 40-cell
Equalize Charge Allowed
Enabled or disenabled
Temp Compensation
Enabled or disabled
Temp Sensor Position
Set the position of the temperature sensor. ‘Remote only
Shared Battery
Set each single in parallel system to share the battery group or not
System Configuration
Set the single/parallel
Parallel Requisite Units
Set the parallel number
Parallel Redundant units
Set the redudant number
ECO Mode
ECO function enabled
Output Frequency Level
Set the output frequency
Output Voltage Level
Set the output voltage system
LBS Function
LBS function enabled
3-in 3-out/3-in 3-out
Set the output system: 3-in 3-out/3-in 3-out This setting can only be carried out after the EPO operation. After the setting, you must power off the system, and confirm that the system actual connection mode complies with the setting. Power on again, and the setting can come into force
Command (start, stop battery, system test or frocing boost charge)
Battery maintenance test
The battery maintenance test will lead to the battery being partly discharged, for rough assessment of the battery capacity. The load must range from 20% ~ 100%
Battery capacity test
The battery capacity test will lead to the battery being completely discharged, for accurate assessment of the battery capacity. The load must range from 20% ~ 100%
System test
For UPS self-test. The user actives this function, 5 seconds later, a pop window will appear to show the result of this test
Stop testing
Manually stop the test, including maintenance test, capacity test and system test
Forcing charge
Manually conduct the forcing charge for battery
Stop forcing charge
Manually stop the forcing boost charge for battery
Version Monitor Version
Provide the monitor software version
Rectifier Version
Provide the rectifier software version
Inverter Version
Provide the inverter software version
Keypad wi
ndow
The function of menu buttons (F1 ~ F4 and HELP) is shown in icon mode for the current display screen.
Page 39
Chapter 3 Operation And Display Panel
29
3.4 Prompt Window
A prompt window is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command. The prompts and meanings are given in Table 3-7.
Table 3-7 Prompts and meanings
Prompt
Meaning
Transfer with interrupt, confirm or cancel
Inverter and bypass supplies are not synchronized, and any load transfer between the supplies will cause a brief load interruption
This operation leads to output shutdown, confirm or cancel
The bypass is in abnormal state, inverter shut down will cause the load power-off
Turn on more UPS to carry current load
The number of paralleled inverters already turned on is insufficient to carry the existing load
Battery will be depleted, confirm or cancel
Battery maintenance test discharges the battery 100%. This prompt apears to require your confirmation. Cancelling the test will ends the test and transfers the UPS to Normal mode
System self-test finished, everything is ok
No action required
System self-test finished, please check the current warnings
Check the current alarm message
Enter control password
Required for battery or UPS test
Battery self-test condition is low, please check battery state and load level
Battery test condition is not met. Please check whether the battery is in boost charge state and the load level is over 20%
Forcing charge condition is low, please check battery state
This prompt appears when you select the forcing charge command while the forcing charge condition is not met (such as no battery, charger failure)
Check the wiring according to the settings, power-off takes effect, 3-phase (1-phase) output
After setting the menu option 3-in 3-out/3-in 1-out, you can power off the system completely, and then power on again after the wiring is changed according to the settings
3.5 UPS Alarm Message List
The following list gives the UPS alarm message list based on the Current records’ and ‘Historical records menus in
Table 3-8.
Table 3-8 UPS alarm message list
Alarm message
Description
Inverter comm. fail
Internal communication failure between the monitoring board and inverter
Rectifier comm. fail
Internal communication failure between the monitoring board and rectifier
Parallel comm. fail
The CAN communication between different UPS s within a parallel system fails. 1.Check if there are some UPSs not powered on in the parallel system. If so, power on these UPSs and check if the alarm disappears. 2. Press the FAULT CLEAR button
Battery fault
Battery detected faulty (Reserved)
Battery replaced
Battery test failed, Battery should be replaced
Battery low pre-warning
Before the end of discharge, battery undervoltage pre-warning should occur. After this pre-warning, battery should have the capacity for 3 minutes discharging with full load. The time is user-configured from 3 minutes to 60 minutes. Shut down the load in time
Battery stop discharge
Inverter turned off due to low battery voltage. Check the utility failure and try to recover it
Mains volt. abnormal
Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input line-to-neutral voltage amplitude of rectifier
Mains undervoltage
Mains voltage is undervoltage. Derate for running and check the input line voltage
Mains freq. abnormal
Mains frequency is out of limit range and results in rectifier shutdown. Check the input frequency
Rectifier block
Rectifier detected faulty. Rectifier shuts down. Battery discharges
Rectifier overtemp.
The temperature of heat sink is too high to keep the rectifier running. The UPS can recover automatically. Check the environment and ventilation
Battery charger fault
Battery charger is over voltage
Control power 1 fail
UPS operates but Control Power is not available
Mains phase reversed
Rectifier AC input phase sequence is reversed
Rectifier overcurrent
Rectifier is over current
Soft start fail
Rectifier could not start due to low DC bus voltage
Page 40
iTrust Adapt UPS 20kVA User Manual
30
Chapter 3 Operation And Display Panel
Alarm message
Description
Bypass unable to trace
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range. The amplitude threshold is fixed for ±10% rating. This alarm will automatically recover when the bypass voltage goes normal.
1. First verify that the bypass voltage and frequency displayed on the operator control and display panel is within the selected range. Note that the rated voltage and frequency are specified by the ‘Output Voltage Level’ and ‘Output Frequency Level’ respectively.
2. If the displayed voltage is abnormal, please verify the actual bypass voltage and frequency presented to the UPS. Check the external power if it is found to be faulty
Bypass protection
This alarm is triggered by an inverter software program when the amplitude or frequency of bypass voltage is too high or too low. The amplitude threshold is fixed for ±10% rating. This alarm will automatically recover when the bypass voltage goes normal.
1. First check if there are some relevant alarms, such as Bypass Phase Reverse’, ‘Input Disconnect Fault’. If so, solve them first.
2. Then verify that the bypass voltage and frequency displayed on the LCD are within the limit. Note that the rated voltage and frequency are specified by the ‘Output Voltage Level’ and ‘Output Frequency Level’ respectively.
3. If the displayed voltage is abnormal, please verify the actual bypass voltage and frequency presented to the UPS. Check the external power if it is found to be faulty. If the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger through the configuration software according to the user feedback
Inverter asynchronous
This alarm is triggered by an inverter software program when the inverter and bypass waveforms are misaligned by more than 6 degrees in phase. The amplitude threshold is fixed for ±10% rating. This alarm will recover automatically when the alarm condition disappears.
1. First check if the alarm Bypass Unable To Trace’ or Bypass Protection. If so, solve it first.
2. Verify the waveform of the bypass voltage. If it is too distorted, ask the user to verify it and seek any possible measurement
Inverter fault
Inverter output voltage beyond limits. Load transfers to bypass
Inverter overtemp.
The temperature of the inverter heat sink is too high to keep inverter running. This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter bridge heat sink. The UPS will recover automatically after 5 minutes delay from the disappearance of the overtemperature signal. If the overtemperature condition is true, check the following items:
1. high ambient temperature. 2. blocked cooling airway. 3. any fan failure. 4. prolonged inverter overloa d
Fan fault
At least one of the cooling fans has failed
Inverter STS fail
At least one of the static switches of inverter side is open or shor t circuit. This fault is locked until power off
Bypass STS fail
At least one of the static switches of bypass side is open or short circuit. This fault is locked until power off
Operation invalid
Incorrect operation
Neighbor bypass SSTS fail
At least one of the static switches of single bypass side in parallel systemis open or short circuit. This fault is locked until power off
Output fuse fail
At least one inverter output fuse blowou. The inverter shuts down, the load transfers to bypass
Unit over load
The UPS is confirmed to be overload when the load arises above 105% nominal rating. The alarm automatically resets once the overload condition is removed. 1. Confirm that the alarm is true by checking the load percent indicated on the LCD to determine which phase is being overloaded. 2. If the alarm is true, measure the actual output current to verify tha t the indications are valid. Disconnect unnecessary load and ensure the safety.
Byp. abnormal shutdown
Both bypass and inverter voltages unavailable. Load interruption
Inverter over current
Inverter pulse width modulation module overloaded
Bypass phase reverse
The phase sequence direction of bypass voltage is reversed. Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C lags 120 degrees behind phase B. Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if it is found to be in error
Load impact transfers bypass
A transfer to bypass occurred due to a large step load. The UPS should recover automatically. Turn on connected equipment in sequential order to reduce the step loading of the inverter
Transfer time-out
The load is on bypass power due to excessive number of transfers that occurred within the last hour. The UPS will recover automatically and will transfer the load back to inverter power within an hour
Bus abnormal
DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass
Page 41
Chapter 3 Operation And Display Panel
31
Alarm message
Description
DC bus over voltage
Rectifier and inverter were shut down because DC bus voltage is too high. Check whether there is a fault in rectifier side. If not, check whether there is an overload. After recovering the fault, restart the inverter
Bypass over current
Bypass current is over limit above 135% rating. The UPS just alarms without any action
Setting save error
History records not saved (Reserved)
Input Disconnect Fault
AC mains input neutral is not checked out
Protocol version clash
Firmware incompatibility between Monitor Board and Digital Signal Processor Board
Manual on
Manual Turn On through operator control and display panel
Manual off
Manual Turn Off through operator control and display panel
EPO
Press the EPO switch directly or receive the external EPO command
Transfer confirm
Prompt to press the Enter button to acknowledge that an interrupted load transfer to bypass will happen
Transfer cancel
Prompt to press the ESC button to avoid that an interrupted load transfer to bypass will happen
Fault clear
Press FAULT CLEAR
Alarm silence
Press ALARM CLEAR
Turn on fail
Inverter failed to turn on when INVERTER ON direct access button was pressed. This may be as a result of Invalid Operation (maintenance bypass on) or DC bus or rectifier not ready
Alarm silence cancle
Press FAULT CLEAR or ALARM CLEAR
Bypass mode
The UPS is in Bypass mode
Normal mode
The UPS is in Normal mode
Battery mode
The UPS is in Battery mode
Check UPS output
The UPS is off and has no output
Battery float charging
Battery status (Float charge mode)
Battery boost charging
Battery status (Boost charge mode)
Battery discharging
Battery status (discharge mode)
Battery period testing
Automatic periodic battery maintenance discharge test (20% capacity discharge)
Batt. capacity testing
User initiated battery capacity discharge test (100% capacity discharge)
Batt. maint. testing
User initiated maintenance discharge test (20% capacity discharge)
UPS system testing
User initiated system test
Inverter in setting
Inverter starting up and synchronizing
Rectifier in setting
Rectifier starting up and synchronizing
Battery reverse
Reconnect the battery, check the battery connection
No battery
Check the battery and the battery wiring
Auto start
After UPS was shutdown at EOD, inverter auto starts when utility restore
REC FLASH UPDATE
Ongoing update of rectifier firmware
INV FLASH UPDATE
Ongoing update of inverter firmware
MONITOR FLASH UPDATE
Ongoing update of monitor firmware
DSP softwar error
Inverter software does not match the rectifier software
Note: If the alarm is caused through setting the software value by Emerson authorized engineer, and when you wish to change the setting values, please get in touch with the Emerson local customer service center
Page 42
iTrust Adapt UPS 20kVA User Manual
32
Chapter 4 UPS Operation Instructions
Chapter 4 UPS Operation Instructions
This chapter gives a detailed description of the UPS operation procedures. Refer to Chapter 3 Operation And Display Panel for all buttons operation and LED display in operation. During the
operation, the buzzer alarm may appear, at this point, you should press the ALARM CLEAR button for audible alarm silence.
Warning: Hazard mains and/or battery voltage exists behind the protective cover
No user accessable parts are located behind the protective covers that require a tool for removal. Only qualified service personnel are authorized to remove such covers.
4.1 UPS Start-up
The start-up procedures can be performed after the installation is finished, the system has been commissioned by authorized personnel and the external input switches are closed.
Warning
This procedure results in mains voltage being applied to the UPS output terminals. Confirm that the load power is safe, if there is a load to be connected with the UPS output terminal. Ensure that the load is isolated with the UPS output terminal, if the load is not ready for accepting the power.
4.1.1 Normal Module Start-up Procedure
This procedure is suitable for UPS start-up when the UPS is in complete disconnection state. Procedures are as follows:
1. Close the UPS external output switch and input switch on by one. At this point, LCD displays the start screen, and the rectifier starts. After the rectifier runs in normal state about 30s,
the rectifier start-up is finished.
2. Press the ON button for 2 seconds. At this point, the inverter starts, and the inverter indicators are blinking green. After the inverter runs in normal state,
the UPS transfers from bypass state to inverter state. The inverter indicators turn green, and the UPS runs in Normal state.
4.1.2 Battery Module Start-up Procedure
1. Check that the batteries have been well connected.
2. Press the battery cold start button on the UPS front panel (see Figure1-1). At this point, LCD displays the start screen. After the rectifier start-up is finished, the fault indicator is off.
3. Press the ON button for 2 seconds, the UPS will run in Battery mode.
4.2 Transferring Procedures Between Operation Modes
4.2.1 Transferring From Normal Mode To Battery Mode
In the event of mains failure, the UPS will transfer to Battery mode. If you wish to transfer the UPS from Battery mode to Normal mode, you should wait few seconds for mains input recovery. 10 seconds later, the rectifier will restart automatically, and the inverter will restore the power.
Page 43
Chapter 4 UPS Operation Instructions
33
4.2.2 Transferring From Normal Mode To Bypass Mode
In Normal mode, press the OFF for 2 seconds, you can transfer the UPS to Bypass mode.
Note
In Bypass mode, the load accepts the power not from the pure power outputted by the inverter, but from the mains power directly.
4.2.3 Transferring From Bypass Mode To Normal Mode
In Bypass mode, press the ON button for 2 seconds. After the inverter runs in normal state, the UPS transfers to Normal mode.
4.2.4 Transferring From Normal Mode To Maintenance Bypass Mode
When the UPS is running in Normal mode, you can use this procedure to make the load transfer from inverter output to maintenance bypass.
Caution
1. Before performing this procedure, you should check the LED information first, and make sure the bypass is normal and synchronizes with the inverter. Otherwise, it may result in the load power interruption for a while.
2. You should select the single POD options or prepare the maintenance bypass switch by yourself, so as to realize this function.
1. Press the OFF for 2 seconds. The inverter indicators are off, and the buzzer alarms. The load transfers to the static bypass, and the inverter shuts
down.
Note
Press the ALARM CLEAR button can silence the alarm, but the alarm message of the the LCD is not disappeared until the alarm status is cleared.
2. Close the maintenance bypass switch on the single POD front panel, and the maintenance bypass can supply power to the load.
Warning
If you wish to maintain the UPS, you should wait 10 minutes for the internal DC bus capacitance voltage discharging.
3. Disconnect the main/bypass input switch and output switch.
Caution
1. When the UPS is in Maintenance Bypass mode, the load does not have the mains abnormal protection.
2. After the UPS transfers to maintenance bypass, the UPS is not in operation, and the LCD is no display, and only the user terminal block of the single POD is electrified. Be careful when removes the UPS to be maintained.
4.3 Complete Shutdown Procedure
If you wish to shut down the UPS completely, the procedures in 4.2.4 Transferring From Normal Mode To Maintenance Bypass Mode should be followed, so as to transfer the UPS from Normal mode to Maintenance Bypass mode.
Disconnect the external input switch, if you wish to isolate the UPS from AC power.
Page 44
iTrust Adapt UPS 20kVA User Manual
34
Chapter 4 UPS Operation Instructions
4.4 EPO Procedure
The UPS operation and display panel has an EPO switch, which is designed to switch off the UPS in emergency conditions (such as fire, flood, and so on). The system will turn off the rectifier, inverter and stop powering the load immediately (inverter and bypass included), and the battery stops charging or discharging.
If the mains input is present, the UPS control circuit will remain active; however, the output is closed. To remove all mains power from the UPS, the external input switch should be disconnected.
4.5 Auto Restart
When the mains power failure, the UPS draws power from the battery to supply the load until the batteries are depleted, then the UPS will shut down.
The UPS will automatically restart and recover output power supply:
After the mains power is restored.
The UPS Auto Restart function is enabled.
After the Auto Restart is delayed (default: 10 minutes). During the Auto Restart delay, the UPS will charge the
battery to provide a safety margin for equipment shutdown if input power fails again.
If the Auto Restart function is disabled, you can restart the UPS manually by pressing the FAULT CLEAR button.
4.6 UPS Reset Procedure
The EPO action or the following reasons such as inverter overtemperature, power-off overload, battery overvoltage and excessive switching may result in the UPS power-off. After all appropriate measures have been taken to clear the faults indicated by the alarm message appearing on the LCD, you can carry out the following steps to restore the UPS to normal operation state.
1. Press the FAULT CLEAR button to make the system exit the EPO state.
2. Press the ON button for 2s.
Note
1. The rectifier restarts, and the bypass supplies power to the load. When the rectifier starts, the fault indicator blinks. When the rectifier runs in normal operation state (about 30 seconds later), the fault indicator will turn off.
2. 5 minutes after the overtemperature signal disappears, that is, when the overtemperature fault is eliminated, the rectifier will automatically start.
3. After the EPO button is pressed, if the mains input is disconnected, the UPS will shut down completely. When the mains input is available, the UPS will start and run in Bypass mode, and also the output is available.
4.7 Language Selection
The LCD menus are available in two languages: Chinese, English. Procedures for selecting the language:
1. From the Output’ menu, press F3 or F4 (left or right arrow) to select the Language menu.
2. Press F5 (Enter) to move the cursor to the data window of the LCD.
3. Use F3 and F4 (up and down arrows) to select the required language.
4. Press F5 (Enter) to confirm.
5. Return to the Output’ menu by repeatedly pressing F2 (ESC). At this point, all texts on the LCD will be displayed in the selected language.
Page 45
Chapter 4 UPS Operation Instructions
35
4.8 Changing Current Date And Time
Procedures for changing the system date and time:
1. From the Output’ menu, press F3 or F4 (left or right arrow) to select the Settings menu.
2. Press F5 (Enter) to move the cursor to the data window of the LCD.
3. Use F3 and F4 (up and down arrows) to select Date & time option, then press F5 (Enter).
4. Move the cursor to the row in which the date and time are displayed, then press F5 (Enter).
5. Use F3 or F4 (up or down arrows), and enter the current time and date information.
6. Press F5 (Enter) to confirm, and then press F2 (ESC) to return to the Output’ menu.
4.9 Controlling Password
The system provides the password protection for the UPS operation control. The default password is 123456. Only through the password verification can you conduct the UPS and battery test operation.
Page 46
iTrust Adapt UPS 20kVA User Manual
36
Chapter 5 Maintenance
Chapter 5
Maintenance
This chapter focuses on the UPS maintenance, including the fan maintenance, battery maintenance, UPS cleaning, UPS state check, UPS function check.
5.1 Fan Maintenance
The UPS fans are expected to run for 20000 hours ~ 40000 hours continuously. The higher the ambient temperature, the shorter the fan life is. Durin g the UPS operation, please verify the fan status once every half year by confirming that air blows out from the ventilation holes on the rear panel.
5.2 Battery Maintenance
The internal battery module of the UPS is sealed, lead-acid, maintenance-free battery. The battery life depends on the ambient temperature, charge and discharge times. High ambient temperature and deep discharge shortens the battery life.
To ensure the battery life, it is required to:
Keep the ambient temperature ranging from 15°C to 25°C.
Prevent small current discharge. Continuous battery operation time exceeding 24 hours is strictly prohibited.
Charge the battery for at least 12 hours, if the battery hasn't been charged for three months at specified ambient
temperature, or two months at high ambient temperature.
Note
1. Never short circuit the battery terminals, which will result in fire.
2. Never open the battery, as the electrolyte is harmful to human body. In the event of inadvertent contact of the electrolyte, wash the affected area immediately with plenty of clean water and go to see the doctor.
5.3 Cleaning UPS
Clean the UPS periodically, especially the ventilation holes, to ensure free airflow inside the UPS. If necessary, clean the UPS with a vacuum cleaner. Confirm that the ventilation holes are unobstructed.
5.4 Checking UPS State
It is recommended to check the UPS operation status once every half year. Procedures are as follows:
1. Check if the UPS is faulty: Is the FAULT indicator on? Is the UPS giving any alarm?
2. Check if the UPS is operating in Bypass mode: Normally, the UPS operates in Normal mode; if it is operating in Bypass mode, find out the reason, such as operator intervention, overload, internal fault, and so on.
3. Check if the battery is discharging: When AC mains is normal, the battery should not discharge; if the UPS operates in Battery mode, you should find out the reason, such as mains failure, battery test, operator intervention, and so on.
5.5 Checking UPS Functions
Note
UPS functions check procedures may cause power interruption to load!
Page 47
Chapter 5 Maintenance
37
It is recommended to check the UPS functions once every half year. Backup the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the OFF button to check if the buzzer beeps, indicators are on and the LCD display is normal.
2. Press the ALARM CLEAR button to check again if the indicators are on, the LCD display is normal and the UPS has been transfered to the inverter mode.
Page 48
iTrust Adapt UPS 20kVA User Manual
38
Appendix 1 Battery Module
Appendix
1 Battery Module
Appearance The protective panel has been installed before delivery to avoid the damage to the battery module during the
transportation. Remove six fixing screws to take off the protective panel after the battery module arrival. The appearance of the battery module is shown in Figure 1.
Fixing
screw
(6
pcs)
Protective panel
Figure 1 Appearance of the battery module
Rear panel Operation panel on the front panel of the battery module is not available. The battery module provides battery ports,
battery fuse box and ventilation holes on the rear panel, as shown in Figure 2.
Battery port 1 Battery port 2
Ventilation holes
Battery fuse box
Figure 2 Rear panel of the battery module
Page 49
Appendix 1 Battery Module
39
盒盖
Replacing the battery fuse If the battery internal fuse is damaged, loosen the protective cover of fuse box on the battery module rear panel and
replace the damaged fuse with a new one, then tighten the fixing screws of the protective cover of fuse box to prevent electric shock risk during the UPS operation, as shown in Figure 3.
Protective cover of fuse box
Figure 3 Schematic diagram of replacing fuse
Note
1. The battery loop and AC input are not insulated, a hazardous voltage may exist between the battery ports and ground, so it is prohibited to touch them for avoiding electric risk.
2. The length of the standard battery cable delivered with the battery module is 0.5m. If you need more length cable, please consult the dealer.
Page 50
iTrust Adapt UPS 20kVA User Manual
40
Appendix 2 Optional Part List
Appendix
2 Optional Part List
The optional part list is given in Table 1.
Table 1 Optional part list
Optional part
Type
Remark
Communication options UF-SNMP810
SNMP card assembly used in Intellislot UPS - ROHS
UF-DRY320
Dry contact extended card used in UPS - {R5}
UF-DRY310
Dry contact card and its assembly usd in UPS - {R5}
UF-RS485
RS232 to 485 component
UFMOD21Z1
MODBUS assembly used in UPS (UFMOD21Z1) - {R5}
POD
UF-POD3U20K10
3-in 3-out/3-in 3-in 1-out rack model 20kVA smart UPS single POD
UF-POD6U20K11
3-in 3-out/3-in 3-in 1-out rack model 20kVA smart UPS 1 + 1 parallel POD
Guide rail/rack
DMBM4.115.331
Used for rack installation mode
Battery module
U16-07C1
A battery cabinet with one-layer
Battery cable components selection
Used for battery module selection
Battery cabinet with two-layer
U20-24C2
Used for battery perparation by the user
Battery cabinet with three- layer
U20-38C3
Used for battery perparation by the user
Loading...