Emerson 3051SFA, 3051SFC, 3051SFP, 3051SMV Quick Start Manual

Page 1
Quick Start Guide
00825-0100-4803, Rev EG
October 2018
Rosemount™ 3051S and 3051SF Series Flow Meter MultiVariable™ Transmitters
Page 2
Safety messages
NOTICE
This guide provides basic guidelines for Rosemount™ 3051S MultiVariable™ Transmitter (3051SMV). It also provides the basic Rosemount 3051SMV configuration guidelines for the Rosemount 3051SFA, Rosemount 3051SFC, and Rosemount 3051SFP. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Rosemount 3051SMV Reference Manual for more instruction.This document is also available electronically on Emerson.com/Rosemount.
WARNING
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices.
Review Rosemount 3051SMV Reference Manual for any restrictions associated with a safe installation.
• Before connecting a handheld communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an explosion-proof/flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Process leaks could result in death or serious injury.
• Install and tighten process connectors before applying pressure.
Electrical shock could cause death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Conduit/cable entries
• Unless marked, the conduit/cable entries in the transmitter housing use a ½–14 NPT thread form.
Entries marked “M20” are M20 × 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
• When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands,
or adapters in cable/conduit entries.
Contents
Mount the transmitter .................................. 3
Consider housing rotation ............................ 9
Set the switches ......................................... 10
Connect wiring and power up ..................... 11
Engineering Assistant installation ............... 15
Flow configuration ..................................... 17
Verifying device configuration .................... 26
Trimming the transmitter ........................... 30
Safety instrumented systems installation ... 31
Product certifications ................................. 32
Quick Start Guide October 2018
2 Rosemount 3051SMV
Page 3
1 Mount the transmitter
1.1 Liquid flow applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
A
A. Direction of flow
1.2 Gas flow applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
A
A. Direction of flow
October 2018 Quick Start Guide
Quick Start Guide 3
Page 4
1.3 Steam flow applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
A
A. Direction of flow
1.4 Mounting brackets
Figure 1-1: Mounting Bracket – Coplanar Flange
Panel mount
Pipe mount
Quick Start Guide October 2018
4 Rosemount 3051SMV
Page 5
Figure 1-2: Mounting Brackets – Traditional Flange
Panel mount Pipe mount
Figure 1-3: Mounting Brackets – In-line
Panel mount Pipe mount
1.5 Bolting considerations
About this task
If the transmitter installation requires assembly of a process flange, manifold, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitter. Only use bolts supplied with the transmitter or sold by Emerson™ as spare parts. Figure 1-4 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
October 2018 Quick Start Guide
Quick Start Guide 5
Page 6
Figure 1-4: Common Transmitter Assemblies
A
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in.
(44 mm)
4 × 2.25-in.
(57 mm)
C
4 × 1.75-in.
(44 mm)
4
× 1.50-in.
(38 mm)
B
4 × 2.88-in.
(73 mm)
A. Transmitter with coplanar flange B. Transmitter with coplanar flange and optional flange adapters C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional Rosemount Conventional
Manifold and flange adapters
Note
For all other manifolds, contact Customer Central technical support.
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 1-1 . If bolt material is not shown in Table 1-1, contact the local Emerson representative for more information.
Use the following bolt installation procedure:
Procedure
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See Table 1-1 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See Table 1-1 for final torque value.
Quick Start Guide October 2018
6 Rosemount 3051SMV
Page 7
5. Verify the flange bolts are protruding through the sensor module before applying pressure (see Figure 1-5).
Example
Table 1-1: Torque Values for the Flange and Flange Adapter Bolts
Bolt material Head markings Initial torque Final torque
Carbon Steel (CS)
B7M
300 in-lb 650 in-lb
Stainless Steel (SST)
316
316
316
SW
316
STM
316
R
B8M
150 in-lb 300 in-lb
Figure 1-5: Proper Bolt Installation
A
B
A. Bolt B. Sensor module
October 2018 Quick Start Guide
Quick Start Guide 7
Page 8
1.6 O-rings with flange adapters
WARNING
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. Only use the O-ring that is designed for its specific flange adapter.
A
B
C D
A. Flange adapter B. O-ring C. PTFE-based profile (square)
D. Elastomer profile (round)
Whenever the flange or adapters are removed, visually inspect the O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If the O­rings are replaced, re-torque the flange bolts and alignment screws after installation to compensate for seating of the O-rings.
Quick Start Guide October 2018
8 Rosemount 3051SMV
Page 9
2 Consider housing rotation
About this task
To improve field access to wiring or to better view the optional LCD display:
Procedure
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped) position.
3. Re-tighten the housing rotation set screw.
Figure 2-1: Transmitter Housing Set Screw
A. LCD display B. Housing rotation set screw (3/32-in.)
CAUTION
Do not rotate the housing more than 180° without first performing a disassembly procedure (refer to Troubleshooting for more information). Over-rotation may sever the electrical connection between the sensor module and the electronics.
October 2018 Quick Start Guide
Quick Start Guide 9
Page 10
3 Set the switches
The transmitter’s default configuration sets the alarm condition to high (HI) and the security to off.
Procedure
1. If the transmitter is installed, secure the bus and remove power.
2. Required: Remove the transmitter cover opposite the field terminal side. Do not remove the instrument covers in explosive environments when the circuit is live.
3. Slide the Security and Alarm switches into the preferred position by using a small screwdriver.
Note
The Security switch will need to be in the off position in order to make any configuration changes.
4. Required: In order to meet explosion-proof requirements, reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover. After the cover is seated properly, replace the flathead screw located on the bottom of the housing cover.
Figure 3-1: Transmitter Switch Configuration
A B
A. Security
B. AC Termination
Quick Start Guide October 2018
10 Rosemount 3051SMV
Page 11
4 Connect wiring and power up
About this task
CAUTION
Do not connect the power across the test terminals. Power could damage the test diode in the test connection. Twisted pairs yield best results. Use 24 to 14 AWG wire and do not exceed 5,000 ft. (1500 m).
Use the following steps to wire the transmitter:
Procedure
1. Remove the cover on the field terminals side of the housing.
2. Connect the positive lead to the “PWR/COMM +” terminal, and the negative lead to the “PWR/COMM –” terminal.
3. If the optional process temperature input is not installed, plug and seal the unused conduit connection. If the input is being utilized, see Install
optional process temperature input (Pt 100 RTD sensor) for more
information.
NOTICE
When the enclosed pipe plug is utilized in the conduit opening, it must be installed with a minimum engagement of five threads to comply with explosion-proof requirements. Refer to the Rosemount
™
3051SMV Reference Manual for more information.
4. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
5. Reinstall the housing cover and tighten so that metal contacts metal to meet explosion-proof requirements.
Figure 4-1 shows the wiring connections necessary to power a
Rosemount 3051SMV and enable communications with a hand-held Field Communicator.
October 2018 Quick Start Guide
Quick Start Guide 11
Page 12
Figure 4-1: Transmitter Wiring
Without optional process temperature connection
With optional process temperature connection
A
RL ≥ 250Ω
A
RL ≥ 250Ω
A. Power supply
Note
Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051SMV housing is properly grounded.
4.1 Conduit electrical connector wiring (option GE or GM)
For Rosemount™ 3051SMV with conduit electrical connectors GE or GM, refer to the cordset manufacturer’s installation instructions for wiring details. For FM Intrinsically Safe, Division 2 hazardous locations, install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA® 4X and IP66). See the Rosemount 3051SMV Reference Manual.
4.2
Power supply
The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, intrinsic safety barriers, and related components.
Quick Start Guide October 2018
12 Rosemount 3051SMV
Page 13
Figure 4-2: Load Limitation
Maximum loop resistance = 43.5 x (power supply voltage – 12.0)
1322
1000
500
0
12.0 20 30
42.4
Voltage (Vdc)
Load (Ohms)
Operating
region
HART communication requires a minimum loop resistance of 250Ω
4.3 Install optional process temperature input (Pt 100 RTD sensor)
About this task
Note
To meet ATEX/IECEx Flameproof certification, only ATEX/IECEx Flameproof cables (temperature input code C30, C32, C33, or C34) may be used.
Procedure
1. Mount the Pt 100 RTD sensor in the appropriate location.
Note
Use shielded four-wire cable for the process temperature connection.
2. Connect the RTD cable to the Rosemount 3051SMV by inserting the cable wires through the unused housing conduit and connect to the four screws on the transmitter terminal block. An appropriate cable gland should be used to seal the conduit opening around the cable.
3. Connect the RTD cable shield wire to the ground lug in the housing.
October 2018 Quick Start Guide
Quick Start Guide 13
Page 14
Figure 4-3: Rosemount 3051SMV RTD Wiring Connection
A
C
B
Red
Red
White
White
A. Ground lug
B. RTD cable assembly wires
C. Pt 100 RTD sensor
Quick Start Guide October 2018
14 Rosemount 3051SMV
Page 15
5 Engineering Assistant installation
Engineering Assistant 6.1 or later
The Rosemount™ 3051SMV Engineering Assistant 6.1 or later is PC-based software that performs configuration, maintenance, diagnostic functions, and serves as the primary communication interface to the Rosemount 3051SMV with the fully compensated mass and energy flow feature board.
The Rosemount 3051SMV Engineering Assistant software is required to complete the flow configuration.
NOTICE
To ensure correct operation, download the most current version of the Engineering Assistant software at Emerson.com/Rosemount-Engineering-
Assistant.
5.1 System requirements
The following are the minimum system requirements to install the Rosemount™ 3051SMV Engineering Assistant software:
• Pentium® -grade processor: 500 MHz or faster
• Operating system: Windows™ XP Professional (32-bit), or Windows 7 (32-
bit or 64-bit)
• 256 MB RAM
• 100 MB free hard disk space
• RS232 serial port or USB port (for use with HART® modem)
• CD-ROM
5.2
Install Rosemount 3051SMV Engineering Assistant 6.1 or later
Procedure
1. Uninstall any existing versions of Engineering Assistant 6.
2. Insert the new Engineering Assistant disk into the CD-ROM.
3. Windows™ should detect the presence of a CD and start the installation program. Follow the on-screen prompts to finish the installation. If Windows does not detect the CD, use Windows Explorer or My Computer to view the contents of the CD-ROM, and then double click the SETUP.EXE program.
4. A series of screens (Installation Wizard) will appear and assist in the installation process. Follow the on-screen prompts. It is recommended to use the default installation settings.
October 2018 Quick Start Guide
Quick Start Guide 15
Page 16
Note
Engineering Assistant versions 6.1 or later require the use of Microsoft®.NET Framework version 4.0 or later. If .NET version 4.0 is not currently installed, the software will be automatically installed during the Engineering Assistant installation. Microsoft .NET version
4.0 requires an additional 200 MB of disk space.
5.3 Connect to a personal computer
Procedure
1. Remove the cover from the field terminals side of the housing.
2. Power the device as outlined in Connect wiring and power up.
3. Connect the HART modem cable to the PC.
4. On the side of the transmitter marked “Field Terminals,” connect the modem mini-grabbers to the two terminals marked “PWR/COMM.”
5. Launch the Engineering Assistant software. For more information on launching software, see Launch Engineering Assistant 6.1 or later.
6. Once the configuration is complete, replace cover and tighten until metal contacts metal to meet explosion-proof requirements.
Figure 5-1 shows how to connect a computer to a Rosemount
3051SMV.
Figure 5-1: Connecting a PC to the Transmitter
Without optional process temperature connection
With optional process temperature connection
A
RL ≥ 250Ω
B
A
RL ≥ 250Ω
B
A. Power supply
B. Modem
Quick Start Guide October 2018
16 Rosemount 3051SMV
Page 17
6 Flow configuration
Rosemount™ 3051SMV Engineering Assistant 6.1 or later
The Rosemount 3051SMV Engineering Assistant is designed to guide the user through the setup of the flow configuration for a Rosemount 3051SMV. The flow configuration screens allow the user to specify the fluid, operating conditions, and information about the primary element, including inside pipe diameter. This information will be used by the Rosemount 3051SMV Engineering Assistant software to create flow configuration parameters that will be sent to the transmitter or saved for future use.
Online and offline modes
The Engineering Assistant software can be used in two modes: Online and Offline. In Online mode, the user can receive the configuration from the transmitter, edit the configuration, send the changed configuration to the transmitter, or save the configuration to a file. In offline mode, the user can create a new flow configuration and save the configuration to a file or open and modify an existing file.
The following pages provide instructions on creating a new flow configuration in offline mode. For more information on other functionality, see the Rosemount 3051SMV Reference Manual.
October 2018 Quick Start Guide
Quick Start Guide 17
Page 18
6.1 Basic navigation overview
Figure 6-1: Engineering Assistant Basic Navigation Overview
A
B C D E
G
H
F
Screen compo nent
Description of use
A The navigation tabs contain the flow configuration information. In Offline
mode, each tab will not become active until the required fields on the previous tab are completed. In Online mode, these tabs will be functional at all times.
B The Reset button will return each field within all of the flow configuration
tabs (Fluid Selection, Fluid Properties, and Primary Element Selection) to the values initially displayed at the start of the configuration.
• In Online mode, the values will return to the initial values received
from the device before the start of the configuration.
• If editing a previously saved flow configuration, the values will return
to those that were last saved. If starting a new flow configuration, all entered values will be erased.
C The Back button is used to step backward through the flow configuration
tabs.
D The Next button is used to step forward through the flow configuration
tabs. In Offline mode, the Next button will not become active until all required fields on the current page are completed.
E The Help button can be clicked at any time to get a detailed explanation
of the information that is required on the current configuration tab.
Quick Start Guide October 2018
18 Rosemount 3051SMV
Page 19
Screen compo nent
Description of use
F Any configuration information that needs to be entered or reviewed will
appear in this portion of the screen.
G These menus navigate to the Configure Flow, Basic Setup, Device,
Variables, Calibration, and Save/Send Configuration tabs.
H These buttons navigate to Config/Setup, Device Diagnostics or Process
Variables sections.
6.2 Launch Engineering Assistant 6.1 or later
About this task
Flow configuration for the Rosemount 3051SMV is achieved by launching the Engineering Assistant software from the Start menu.
Procedure
1. Select the Start menu > All Programs > Engineering Assistant. Engineering Assistant will open to the screen shown in Figure 6-2.
2. Select Offline button located in the lower right hand corner of the screen shown in Figure 6-2.
Figure 6-2: Engineering Assistant Device Connection Screen
October 2018 Quick Start Guide
Quick Start Guide 19
Page 20
6.3 Use Preferences tab
About this task
The Preferences tab, shown in Figure 6-3, allows you to select the preferred engineering units to display.
Procedure
1. Select the preferred engineering units.
2. If Custom Units are selected, configure the Individual Parameters.
3. Check the box if unit preferences should be retained for future Engineering Assistant sessions.
Figure 6-3: Preferences Tab
6.4 Select fluid for database liquid/gas
About this task
The Fluid Selection tab shown in Figure 6-4 allows the user to choose the process fluid.
Quick Start Guide October 2018
20 Rosemount 3051SMV
Page 21
Figure 6-4: Fluid Selection Tab
Note
The following example will show a flow configuration for the database gas air used with a Rosemount 405C Conditioning Orifice Plate as the primary element. The procedure to set up any other fluid with any other primary element will be similar to this example. Natural gases, custom liquids, and custom gases require additional steps during the configuration. See the Rosemount 3051SMV Reference Manual for more information.
Procedure
1. Engineering Assistant may open to the Preferences tab. Using the tabs at the top of the screen, navigate to the Fluid Selection tab.
2. Expand the Gas category (click on the + icon).
3. Expand the Database Gas category.
4. Select Air from the list of database fluids.
5. Enter the Nominal Operating Pressure, select the Enter or Tab key.
6. Enter the Nominal Operating Temperature, select the Enter or Tab key. Engineering Assistant will automatically fill in suggested operating ranges, as shown in Figure 6-4. These values may be edited as needed by the user.
7. Verify the Reference/Atmospheric Conditions are correct for the application. These values may be edited as needed.
Note
Reference pressure and temperature values are used by Engineering Assistant to convert the flow rate from mass units to mass units expressed as standard or normal volumetric units.
October 2018 Quick Start Guide
Quick Start Guide 21
Page 22
8. Select Next to proceed to the Fluid Properties tab.
6.5 Fluid properties
Note
The Fluid Properties tab is an optional step and is not required to complete a flow configuration.
The Fluid Properties tab for the database gas air is shown in Figure 6-5. This is used to verify the properties of the chosen fluid are acceptable.
To check density, compressibility, and viscosity of the selected fluid at other pressure and temperature values, enter a Pressure and Temperature and select Calculate.
Note
Changing the pressure and temperature values on the Fluid Properties tab does not affect the fluid configuration.
Figure 6-5: Fluid Properties Tab
6.6 Select primary element
About this task
The Primary Element Selection tab shown in Figure 6-6 allows the user to choose the primary element.
Quick Start Guide October 2018
22 Rosemount 3051SMV
Page 23
Figure 6-6: Primary Element Selection Tab
Continuing with the example configuration:
Procedure
1. Expand the Conditioning Orifice Plate category.
2. Select 405C/3051SFC.
3. Enter the measured Meter Tube Diameter (pipe ID) at a reference temperature. If the meter tube diameter cannot be measured, select a Nominal Pipe Size and Pipe Schedule to input an estimated value for the meter tube diameter (English units only).
4. If necessary, edit the Meter Tube Material.
5. Enter the Line Size and select the Beta of the conditioning orifice plate. The required primary element sizing parameters will be different depending on what primary element was selected.
6. If necessary, select a primary element Material from the dropdown menu.
7. Select Next > to advance to the Save/Send Configuration tab.
Note
To be in compliance with appropriate national or international standards, beta ratios and differential producer diameters should be within the limits as listed in the applicable standards. The Engineering Assistant software will alert the user if a primary element value exceeds these limits, but will allow the user to proceed with the flow configuration.
October 2018 Quick Start Guide
Quick Start Guide 23
Page 24
6.7 Save/send configuration
About this task
The Save/Send Configuration tab shown in Figure 6-7 allows you to verify, save, and send the configuration information to the transmitter with the fully compensated mass and energy flow feature board.
Procedure
1. Review the information under the Flow Configuration and Device Configuration headings.
Note
For more information, see Verifying device configuration.
Figure 6-7: Save/Send Configuration Tab
2. Select the icon above each window to edit the configuration information in these windows.
Note
The user will be notified if the configuration has been modified since it was last sent to the transmitter. A warning message will be shown to the right of the Send Flow Data and/or Send Transmitter Data check boxes.
3. To send the configuration, select the Send To button.
Note
The Send Flow Data and Send Transmitter Data check boxes can be used to select what configuration data is sent to the transmitter. If either check box is unselected, the corresponding data will not be sent.
Quick Start Guide October 2018
24 Rosemount 3051SMV
Page 25
4. The Engineering Assistant Device Connection screen will appear, see
Figure 6-8.
Figure 6-8: Engineering Assistant Device Connection Screen
5. Select the Search button located in the lower right hand corner of the screen. Engineering Assistant will begin to search for connected devices.
6. When the search is completed, select the device to communicate with and select Send Configuration button.
Note
After the configuration is sent to the device, saving the configuration file is recommended. The user can select the Save button on the Save/ Send screen or select Save from the program menu.
Once the configuration is finished being sent to the device, the user will be notified by a pop-up dialog box.
7. If finished with the configuration process, close Engineering Assistant.
October 2018 Quick Start Guide
Quick Start Guide 25
Page 26
7 Verifying device configuration
Use Rosemount™ 3051SMV Engineering Assistant or any HART® -compliant master to communicate with and verify configuration of the Rosemount 3051SMV.
Table 7-1 shows the Field Communicator fast keys for the fully compensated
mass and energy flow. Table 7-2 shows the Fast Keys for the direct process variable output.
Note
Device configuration procedures are given for Rosemount 3051SMV Engineering Assistant 6.1 or later and AMS Device Manager 9.0 or later in the Rosemount 3051SMV Reference Manual.
A check (✓) indicates the basic configuration parameters. At a minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 7-1: Fast Keys for Fully Compensated Mass and Energy Flow
Function Fast Key
sequence
Absolute Pressure Reading and Status 1, 4, 2, 1, 5
Absolute Pressure Sensor Limits 1, 4, 1, 5, 8
Absolute Pressure Units 1, 3, 3, 5
Alarm and Saturation Level Configuration 1, 4, 2, 6, 6
Alarm and Saturation Levels 1, 4, 2, 6
Analog Output Trim Options 1, 2, 5, 2
Burst Mode Setup 1, 4, 3, 3, 3
Burst Mode Options 1, 4, 3, 3, 4
Callendar-van Dusen Sensor Matching 1, 2, 5, 5, 4
Configure Fixed Variables 1, 2, 4
✓ Damping 1, 3, 7
Diaphragm Seals Information 1, 4, 4, 5
✓ Differential Pressure Low Flow Cutoff 1, 4, 1, 1, 6
Differential Pressure Reading and Status 1, 4, 2, 1, 4
Differential Pressure Sensor Trim Options 1, 2, 5, 3
✓ Differential Pressure Zero Trim 1, 2, 5, 3, 1
Differential Pressure Units 1, 3, 3, 4
Quick Start Guide October 2018
26 Rosemount 3051SMV
Page 27
Table 7-1: Fast Keys for Fully Compensated Mass and Energy Flow
(continued)
Function Fast Key
sequence
Energy Rate Units 1, 3, 3, 2
Energy Reading and Status 1, 4, 2, 1, 2
Equipped Sensors 1, 4, 4, 4
Field Device Information 1, 4, 4, 1
Flow Calculation Type 1, 4, 1, 1, 2
✓ Flow Rate Units 1, 3, 3, 1
Flow Reading and Status 1, 4, 2, 1, 1
Gage Pressure Reading and Status 1, 4, 2, 1, 6
Gage Pressure Sensor Limits 1, 4, 1, 5, 9
Gage Pressure Units 1, 3, 3, 6
LCD Configuration 1, 3, 8
Loop Test 1, 2, 2
Module Temperature Reading and Status 1, 4, 2, 1, 8
Module Temperature Units 1, 3, 3, 8
Poll Address 1, 4, 3, 3, 1
Process Temperature Reading and Status 1, 4, 2, 1, 7
✓ Process Temperature Sensor Mode 1, 4, 1, 6, 8
Process Temperature Sensor Trim Options 1, 2, 5, 5
Process Temperature Unit 1, 3, 3, 7
✓ Ranging the Analog Output 1, 2, 5, 1
Recall Factory Trim Settings 1, 2, 5, 2, 3
Sensor Information 1, 4, 4, 2
Static Pressure Sensor Lower Trim (AP Sensor) 1, 2, 5, 4, 2
Static Pressure Sensor Trim Options 1, 2, 5, 4
Static Pressure Sensor Zero Trim (GP Sensor) 1, 2, 5, 4, 1
Status 1, 2, 1
✓ Tag 1, 3, 1
Test Flow Calculation 1, 2, 3
October 2018 Quick Start Guide
Quick Start Guide 27
Page 28
Table 7-1: Fast Keys for Fully Compensated Mass and Energy Flow
(continued)
Function Fast Key
sequence
Totalizer Configuration 1, 4, 1, 3
Totalizer Reading and Status 1, 4, 2, 1, 3
Totalizer Units 1, 3, 3, 3
Variable Mapping 1, 4, 3, 4
Write Protect 1, 3, 5, 4
Table 7-2: Fast Keys for Direct Process Variable Output
Function Fast Key
sequence
Absolute Pressure Reading and Status 1, 4, 2, 1, 2
Absolute Pressure Sensor Limits 1, 4, 1, 2, 8
Absolute Pressure Units 1, 3, 3, 2
Alarm and Saturation Level Configuration 1, 4, 2, 6, 6
Alarm and Saturation Levels 1, 4, 2, 6
Analog Output Trim Options 1, 2, 4, 2
Burst Mode Setup 1, 4, 3, 3, 3
Burst Mode Options 1, 4, 3, 3, 4
Callendar-van Dusen Sensor Matching 1, 2, 4, 5, 4
✓ Damping 1, 3, 7
Diaphragm Seals Information 1, 4, 4, 4
Differential Pressure Reading and Status 1, 4, 2, 1, 1
Differential Pressure Sensor Trim Options 1, 2, 4, 3
✓ Differential Pressure Zero Trim 1, 2, 4, 3, 1
✓ Differential Pressure Units 1, 3, 3, 1
Equipped Sensors 1, 4, 4, 3
Field Device Information 1, 4, 4, 1
Gage Pressure Reading and Status 1, 4, 2, 1, 3
Gage Pressure Sensor Limits 1, 4, 1, 2, 9
Gage Pressure Units 1, 3, 3, 3
Quick Start Guide October 2018
28 Rosemount 3051SMV
Page 29
Table 7-2: Fast Keys for Direct Process Variable Output (continued)
Function Fast Key
sequence
LCD Configuration 1, 3, 8
Loop Test 1, 2, 2
Module Temperature Reading and Status 1, 4, 2, 1, 5
Module Temperature Units 1, 3, 3, 5
Poll Address 1, 4, 3, 3, 1
Process Temperature Reading and Status 1, 4, 2, 1, 4
Process Temperature Sensor Trim Options 1, 2, 4, 5
Process Temperature Unit 1, 3, 3, 4
✓ Ranging the Analog Output 1, 2, 4, 1
Recall Factory Trim Settings 1, 2, 4, 2, 3
Sensor Information 1, 4, 4, 2
Static Pressure Sensor Lower Trim (AP Sensor) 1, 2, 4, 4, 2
Static Pressure Sensor Trim Options 1, 2, 4, 4
Static Pressure Sensor Zero Trim (GP Sensor) 1, 2, 4, 4,1
Status 1, 2, 1
✓ Tag 1, 3, 1
✓ Transfer Function 1, 3, 6
Variable Mapping 1, 4, 3, 4
Write Protect 1, 3, 5, 4
October 2018 Quick Start Guide
Quick Start Guide 29
Page 30
8 Trimming the transmitter
Transmitters are shipped fully calibrated per request or by the factory default of full scale.
8.1 Zero trim
A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects on static and differential pressure sensors. When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct level.
The transmitter will only allow up to five percent of URL zero error to be trimmed.
8.1.1 Perform a zero trim using the Field Communicator
Procedure
1. Equalize or vent the transmitter and connect the Field Communicator (for more information on connecting the Field Communicator, see
Figure 4-1).
2. If the device is equipped with a static pressure sensor, zero the sensor by inputting the following Fast Key sequence at the Rosemount
™
3051SMV menu:
Flow Fast Keys
Direct output Fast Keys
Description
1, 2, 5, 4 1, 2, 4, 4 Static pressure sensor trim options
3. Use the zero trim (selection 1) for a transmitter equipped with a gage static pressure sensor or lower sensor trim (selection 2) for a transmitted equipped with an absolute static pressure sensor.
Note
When performing a lower sensor trim on an absolute pressure sensor, it is possible to degrade the performance of the sensor if inaccurate calibration equipment is used. Use a barometer that is at least three times as accurate as the absolute sensor of the transmitter.
4. Zero the differential pressure sensor by inputting the following Fast Key sequence at the Rosemount 3051SMV menu:
Flow Fast Keys
Direct output Fast Keys
Description
1, 2, 5, 3, 1 1, 2, 4, 3, 1 Differential pressure sensor zero trim
Quick Start Guide October 2018
30 Rosemount 3051SMV
Page 31
9 Safety instrumented systems installation
For safety certified installations, refer to the appropriate reference manual for the installation procedure and system requirements:
• For DP only measurements (measurement type D) refer to the Rosemount
3051S Reference Manual.
• For MultiVariable measurements (measurement type 1–7) refer to the
Rosemount 3051SMV Reference Manual.
October 2018 Quick Start Guide
Quick Start Guide 31
Page 32
10 Product certifications
10.1 Rosemount 3051SMV/3051SFx Product Certifications
Rev 2.0
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
10.1.1 USA
E5 US Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate
FM16US0089X
Standards
FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 – 2011, 3810 – 2005,ANSI/NEMA 250 – 2003
Markings
XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1,GP E, F, G; CL III; T5(–50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
I5 US Intrinsically Safe (IS) and Nonincendive (NI)
Certificate
FM16US0233
Standards
FM Class 3600 – 2011, FM Class 3610 – 2007, FM Class 3611 – 2004, FM Class 3810 – 2005, NEMA 250 – 1991
Markings
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C≤ T
a
≤ +70 °C) when connected per Rosemount drawing 03151-1206; Type 4X
Quick Start Guide October 2018
32 Rosemount 3051SMV
Page 33
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing 03151-1206.
IE US FISCO Intrinsically Safe
Certificate
FM16US0233
Standards
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3616 – 2006, FM Class 3810 – 2005, NEMA 250 – 1991
Markings
IS CL I, DIV 1, GP A, B, C, D;
Standards
T4(–50 °C ≤ Ta ≤ +70 °C); when connected per Rosemount drawing 03151-1006; Type 4X
10.1.2 Canada
E6 Canada Explosionproof, Dust Ignition-proof, Division 2
Certificate
1143113
Standards
CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)
Markings
Explosionproof Class I, Division 1, Groups B, C, D; Dust­Ignitionproof Class II, Division 1, Groups E, F, G; Class III; suitable for Class I, Division 2, Groups A, B, C, D; Type 4X
I6 Canada Intrinsically Safe
Certificate
1143113
Standards
CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)
Markings
Intrinsically Safe Class I, Division 1; suitable for Class 1, Zone 0, IIC, T3C, Ta = 70 °C; when connected per Rosemount drawing 03151-1207; Type 4X
IF Canada FISCO Intrinsically Safe
Certificate
1143113
October 2018 Quick Start Guide
Quick Start Guide 33
Page 34
Standards
CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)
Markings
FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class I, Zone 0; T3C, Ta = 70 °C; when installed per Rosemount drawing 03151-1207; Type 4X
10.1.3 Europe
E1 ATEX Flameproof
Certificate
KEMA 00ATEX2143X
Standards
EN 60079-0:2012+A11:2013, EN 60079-1: 2014, EN 60079-26:2015
Markings
II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/
T4(–60 °C ≤ Ta ≤ +80 °C)
Temperature class Process temperature
T6 –60 °C to +70 °C
T5 –60 °C to +80 °C
T4 –60 °C to +120 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between Category 1 (process connection) and Category 2 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed.
Quick Start Guide October 2018
34 Rosemount 3051SMV
Page 35
I1 ATEX Intrinsic Safety
Certificate
Baseefa08ATEX0064X
Standards
EN 60079-0:2012, EN 60079-11:2012
Markings
II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤Ta ≤ +70 °C)
Parameter HART®FOUNDATION
Fieldbus
SuperModule
™
only
RTD (for 3051SFx)
HART Fieldbus
Voltage U
i
30 V 30 V 7.14 V 30 V 30 V
Current I
i
300 mA
300 mA 300 mA 2.31 mA 18.24 mA
Power P
i
1 W 1.3 W 887 mW 17.32 mW 137 mW
Capacitance C
i
14.8 nF 0 0.11 µF 0 0.8 nF
Inductance L
i
0 0 0 0 1.33 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
IA ATEX FISCO
Certificate
Baseefa08ATEX0064X
Standards
EN 60079-0:2012, EN 60079-11:2012
Markings
II 1 G Ex ia IIC T4 Ga, T4(–60 °C≤Ta ≤ +70 °C)
Parameter FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0
October 2018 Quick Start Guide
Quick Start Guide 35
Page 36
ND ATEX Dust
Certificate
BAS01ATEX1374X
Standards
EN 60079-0:2012, EN 60079-31:2009
Markings
II 1 D Ex ta IIIC T105 °C T
500
95 °C Da, (–20 °C ≤Ta ≤ +85 °C),
V
max
= 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7J impact test.
4. The SuperModule(s) must be securely screwed in place to maintain the ingress protection of the enclosure(s).
N1 ATEX Type n
Certificate
Baseefa08ATEX0065X
Standards
EN 60079-0:2012, EN 60079-15:2010
Markings
II 3 G Ex nA IIC T4 Gc, (–40 °C ≤Ta ≤ 70 °C), V
max
= 45 V
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding the 500 V electrical strength test as defined in Clause
6.5.1 of EN 60079-15:2010. This must be taken into account during installation.
10.1.4 International
E7 IECEx Flameproof and Dust
Certificate
IECEx KEM 08.0010X (Flameproof)
Standards
IEC 60079-0:2011, IEC 60079-1:2014,IEC 60079-26:2014
Markings
Ex db IIC T6…T4 Ga/Gb, T6(–60 °C≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤ +80 °C)
Temperature class Process temperature
T6 –60 °C to +70 °C
T5 –60 °C to +80 °C
T4 –60 °C to +120 °C
Quick Start Guide October 2018
36 Rosemount 3051SMV
Page 37
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed.
Certificate: IECEx BAS 09.0014X (Dust)
Standards: IEC 60079-0:2011, IEC 60079-31:2008
Markings: Ex ta IIIC T105 °C T
500
95 °C Da, (–20 °C ≤ Ta ≤ +85 °C), V
max
= 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7J impact test.
4. The Rosemount 3051S - SuperModule must be securely screwed in place to maintain the ingress protection of the enclosure.
I7 IECEx Intrinsic Safety
Certificate
IECEx BAS 08.0025X
Standards
IEC 60079-0:2011, IEC 60079-11:2011
Markings
Ex ia IIC T4 Ga, T4(–60 °C≤ Ta ≤ +70 °C)
Parameter HART FOUNDATION
Fieldbus
SuperModule only
RTD (for 3051SFx)
HART Fieldbus
Voltage U
i
30 V 30 V 7.14 V 30 V 30 V
October 2018 Quick Start Guide
Quick Start Guide 37
Page 38
Parameter HART FOUNDATION
Fieldbus
SuperModule only
RTD (for 3051SFx)
HART Fieldbus
Current I
i
300 mA 300 mA 300 mA 2.31 mA 18.24 mA
Power P
i
1 W 1.3 W 887 mW 17.32
mW
137 mW
Capacitance C
i
14.8 nF 0 0.11 µF 0 0.8 nF
Inductance Li0 0 0 0 1.33 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
IG IECEx FISCO
Certificate
IECEx BAS 08.0025X
Standards
IEC 60079-0:2011, IEC 60079-11:2011
Markings
Ex ia IIC T4 Ga, T4(–60 °C≤ Ta ≤ +70 °C)
Parameter FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0
N7 IECEx Type n
Certificate
I ECEx BAS 08.0026X
Standards
IEC 60079-0:2011, IEC 60079-15:2010
Markings
Ex nA IIC T5 Gc,(–40 °C ≤Ta ≤ 70 °C)
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding the 500 V electrical strength test as defined in Clause
Quick Start Guide October 2018
38 Rosemount 3051SMV
Page 39
6.5.1 of IEC 60079-15:2010. This must be taken into account during installation.
10.1.5 Brazil
E2 INMETRO Flameproof
Certificate
UL-BR 15.0393X
Standards
ABNT NBR IEC 60079-0:2008 + Corrigendum 1:2011, ABNT NBR IEC 60079-1:2009 + Corrigendum 1:2011, ABNT NBR IEC 60079-26:2008 + Corrigendum 1: 2008
Markings
Ex db IIC T* Ga/Gb, T6(–60 °C≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤ +80 °C), IP66
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1mm thick that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
I2 INMETRO Intrinsic Safety
Certificate
UL-BR 15.0357X
Standards
ABNT NBR IEC 60079-0:2008 + Addendum 1:2011, ABNT NBR IEC 60079-11:2009
Markings
Ex ia IIC T4 Ga (–60 °C≤ Ta ≤ +70 °C)
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90V transient suppressor, it is incapable of withstanding the 500V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment, areas requiring EPL Ga.
October 2018 Quick Start Guide
Quick Start Guide 39
Page 40
Parameter HART Fieldbus
Input RTD Input RTD
Voltage U
i
30 V 30 V 30 V 30 V
Current I
i
300 mA 2.31 mA 300 mA 18.24 mA
Power P
i
1 W 17.32 mW 1.3 W 137 mW
Capacitance Ci14.8 nF 0 0 0.8 nF
Inductance L
i
0 0 0 1.33 mH
I2/IB INMETRO Intrinsic Safety/FISCO
Certificate
UL-BR 15.0392X
Standards
ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013
Markings
Ex ia IIC T4 Ga (–60 °C≤ Ta ≤ +70 °C), IP66
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic charge buildup, it must not be rubbed or cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module may be replaced in a hazardous area. The Power Module has a surface resistivity greater than 1 GΩ and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge buildup.
3. The 3051S enclosure may be made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in areas that requires EPL Ga.
Table 10-1: Input Parameters
U
i
I
i
P
i
C
i
L
i
SuperModule 30 V 300 mA 1.0 W 30 nF 0
3051S...A; 3051SF…A; 3051SAL…C
30 V 300 mA 1.0 W 12 nF 0
3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0
3051S…F…IB; 3051SF…F…IB
17.5 V 380mA 5.32W 0 0
Quick Start Guide October 2018
40 Rosemount 3051SMV
Page 41
Table 10-1: Input Parameters (continued)
U
i
I
i
P
i
C
i
L
i
3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;
3051SAL…C… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 60 µH
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 µH
3051SAL… M7, M8, or M9 3051SAM… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 93 µH
RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
10.1.6 China
E3 China Flameproof and Dust Ignition-proof
Certificate
3051SMV: GYJ14.1039X [Mfg USA, China, Singapore] 3051SFx: GYJ11.1466X [Mfg USA, China, Singapore]
Standards
3051SMV: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010 3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010,
GB12476.1-2013, GB12476.5-2013
Markings
3051SMV: Ex d IIC T6/T5 Ga/Gb 3051SFx: Ex d IIC T4…T6 Ga/Gb; Ex tD A20 TA 105 °C; IP66
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use: For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
2. The relationship between T code and ambient temperature range for the 3051SMV are as follows:
T code
Ambient temperature range
T6 –50 °C ~ +65 °C (–58 °F ~ +149 °F)
T5 –50 °C ~ +80 °C (–58 °F ~ +176 °F)
The relationship between T code and ambient temperature range for the 3051SFx are as follows:
T code
Ambient temperature range
T6 –60 °C ~ +70 °C (–76 °F ~ +158 °F)
October 2018 Quick Start Guide
Quick Start Guide 41
Page 42
T code Ambient temperature range
T4/T5 –60 °C ~ +80 °C (–76 °F ~ +176 °F)
3. The earth connection facility in the enclosure should be connected reliably.
4. During installation, use and maintenance of the product in explosive atmosphere, observe the warning “Do not open cover when circuit is alive”. During installation, use, and maintenance in explosive dust atmosphere, observe the warning “Do not open when an explosive dust atmosphere is present”.
5. During installation there should be no mixture harmful to the housing.
6. During installation, use and maintenance in explosive dust atmosphere, product enclosure should be cleaned to avoid dust accumulation, but compressed air should not be used.
7. During installation in a hazardous location, cable glands and blanking plugs certified by state appointed inspection bodies with Ex d IIC Gb or Ex d IIC Gb DIP A20 [flow meters] IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs.
8. End users are not permitted to change any components, but to contact the manufacturer to avoid damage to the product.
9. Maintenance should be done when no explosive gas and dust atmosphere is present.
10. During installation, use and maintenance of this product, observe following standards:
GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”
GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
GB15577-2007 “Safety regulations for dust explosion prevention and protection”
GB12476.2-2010 “Electrical apparatus for use in the presence of combustible dust”
I3 China Intrinsic Safety
Certificate
3051SMV: GYJ14.1040X [Mfg USA, China, Singapore] 3051SFx: GYJ16.14 [Mfg USA, China, Singapore]
Quick Start Guide October 2018
42 Rosemount 3051SMV
Page 43
Standards
3051SMV: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 3051SFx: GB3836.1/4-2010, GB3836.20-2010,
GB12476.1-2000
Markings
3051SMV: Ex ia IIC T4 Ga 3051SFx: Ex ia IIC T4 Ga, Ex tD A20 TA105 °C T
500
95 °C; IP66
Special Conditions for Safe Use (X):
1. The enclosure may contain light metal, attention should be taken to avoid ignition hazard due to impact or friction.
2. The apparatus is not capable of withstanding the 500V electrical strength test defined in Clause 6.3.12 of GB3836.4-2010.
3. Ambient temperature range: –60 °C ~ +70 °C
4. Intrinsically safe electric parameters:
Maximum input voltage:
Ui (V)
Maximum input current:
Ii (mA)
Maximum input power:
Pi (W)
Maximum internal parameters:
Ci (nF) Li (μH)
30 300 1.0 14.8 0
Maximum
output voltage:
Ui (V)
Maximum output current:
Ii (mA)
Maximum output power:
Pi (W)
Maximum external parameters:
C
i
(nF)
L
i
(μH)
RTD 30 2.31 17.32 0 0
SuperModule 7.14 300 887 110 0
5. The cables between this product and associated apparatus should be shielded cables. The shield should be grounded reliably in non­hazardous area.
6. The product should be used with Ex certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.
7. End users are not permitted to change any components, contact the manufacturer to avoid damage to the product.
8. During installation in hazardous location, cable glands, conduit, and blanking plugs certified by state-appointed inspection bodies with DIP A20 IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs.
October 2018 Quick Start Guide
Quick Start Guide 43
Page 44
9. During installation, use, and maintenance in explosive dust atmosphere, observe the warning “Do not open when an explosive dust atmosphere is present”.
10. Maintenance should be done when no explosive dust atmosphere is present.
11. During installation, use and maintenance of this product, observe following standards:
GB3836.13-2013 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres“
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”
GB3836.18-2010 “Intrinsically Safe System” GB50257-1996- “Code for construction and acceptance of electric
device for explosion atmospheres and fire hazard electrical equipment installation engineering”
GB15577-2007 Safety regulations for dust explosion prevention and protection
GB12476.2-2010 “Electrical apparatus for use in the presence of combustible dust”
10.1.7 EAC - Belarus, Kazakhstan, Russia
EM Technical Regulation Customs Union (EAC) Flameproof and Dust Ignition-proof
Certificate
RU C-US.AA87.B.00378
Markings
Ga/Gb Ex d IIC T6…T4 X
Ex tb IIIC T105 °C T
500
95 °C Db X
Ex ta IIIC T105 °C T
500
95 °C Da X
IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate
RU C-US.AA87.B.00378
Markings
0Ex ia IIC T4 Ga X
10.1.8 Japan
E4 Japan Flameproof
Certificate
CML 17JPN1147X
Markings
Ex d IIC T6…T4 Ga/Gb
Quick Start Guide October 2018
44 Rosemount 3051SMV
Page 45
Table 10-2:
Temperatur e class
Ambient temperature Process temperature
T6 –40 °C to +70 °C (–40 °F to +158
°F)
–60 °C to +70 °C (–76 °F to +158 °F)
T5 –40 °C to +75 °C (–40 °F to +167
°F)
–60 °C to +80 °C (–76 °F to +176 °F)
T4 –40 °C to +75 °C (–40 °F to +167
°F)
–60 °C to +120 °C (–76 °F to +248 °F)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1mm thickness that forms a boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance, and use shall consider the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions fr installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid insallations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
10.1.9 Republic of Korea
EP Republic of Korea Flameproof
Certificate
12-KB4BO-0180X [Mfg USA], 11-KB4BO-0068X [Mfg Singapore]
Markings
Ex d IIC T6...T4
IP Republic of Korea Intrinsic Safety [HART Only]
Certificate
10-KB4BO-0021X [Mfg USA, SMMC]
Markings
Ex ia IIC T4
10.1.10Combinations
K1
Combination of E1, I1, N1, and ND
K2
Combination of E2 and I2
October 2018 Quick Start Guide
Quick Start Guide 45
Page 46
K5
Combination of E5 and I5
K6
Combination of E6 and I6
K7
Combination of E7, I7, and N7
KA
Combination of E1, I1, E6, and I6
KB
Combination of E5, I5, E6, and I6
KC
Combination of E1, I1, E5, and I5
KD
Combination of E1, I1, E5, I5, E6, and I6
KM
Combination of EM and IM
KP
Combination of EP and IP
10.1.11Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate
17-RJ1679518-PDA
Intended Use
Measure gauge or absolute pressure of liquid, gas or vapor applications on ABS classed vessels, marine, and offshore installations. [HART only]
SBV Bureau Veritas (BV) Type Approval
Certificate
31910
BV Requirements
Bureau Veritas Rules for the Classification of Steel Ships
Application
Class Notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS. [HART only]
SDN Det Norske Veritas (DNV) Type Approval
Certificate
TAA00000K9
Intended Use
Det Norske Veritas’ Rules for Classification of Ships, High Speed and Light Craft, and Det Norske Veritas’ Offshore Standards.[HART only]
Application
Location classes
Type 3051S
Temperature D
Humidity B
Vibration A
EMC A
Quick Start Guide October 2018
46 Rosemount 3051SMV
Page 47
Enclosure D/IP66/IP68
SLL Lloyds Register (LR) Type Approval
Certificate
11/60002
Application
Environmental categories ENV1, ENV2, ENV3, and ENV5. [HART only]
October 2018 Quick Start Guide
Quick Start Guide 47
Page 48
10.2 Declaration of Conformity
Quick Start Guide October 2018
48 Rosemount 3051SMV
Page 49
October 2018 Quick Start Guide
Quick Start Guide 49
Page 50
Quick Start Guide October 2018
50 Rosemount 3051SMV
Page 51
10.3 ChinaRoHS
ᴹ
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 3051SMV
List of Rosemount 3051SMV Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘
/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
X O O O O O
༣փ㓴Ԧ
Housing
Assembly
X O O X O O
Րᝏಘ㓴Ԧ
Sensor
Assembly
X O O X O O
ᵜ㺘Ṭ㌫׍ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ֌
This table is proposed in accordance with the provision of SJ/T11364.
O:
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
X:
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
October 2018 Quick Start Guide
Quick Start Guide 51
Page 52
*00825-0100-4803*
Quick Start Guide
00825-0100-4803, Rev. EG
October 2018
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 [email protected]
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 [email protected]
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 [email protected]
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 [email protected]
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 [email protected]
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 [email protected]
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
Google.com/+RosemountMeasurement
©
2018 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...