Emerson 20002158 User Manual

Installation Manual
20002158, Rev DI
March 2014
Micro Motion® ELITE® Coriolis Flow and Density Sensors
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EC declaration of conformity for directives that apply to this product. The EC declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at www.micromotion.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive can be found on the internet at
www.micromotion.com/documentation.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.

Other information

Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the transmitter configuration manual. Product data sheets and manuals are available from the Micro Motion web site at
www.micromotion.com/documentation.

Return policy

Micro Motion procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Failure to follow Micro Motion procedures will result in your equipment being refused delivery.
Information on return procedures and forms is available on our web support system at www.micromotion.com, or by phoning the Micro Motion Customer Service department.

Micro Motion customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800-522-6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 318 495 555 New Zealand 099 128 804
Mexico +41 (0) 41 7686 111 France 0800 917 901 India 800 440 1468
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000
Venezuela +58 26 1731 3446 Central & Eastern +41 (0) 41 7686 111 Japan +81 3 5769 6803
Russia/CIS +7 495 981 9811 South Korea +82 2 3438 4600
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudia Arabia 800 844 9564
UAE 800 0444 0684

Contents

Contents
Chapter 1 Planning ........................................................................................................................... 1
1.1 Installation checklist ........................................................................................................................1
1.2 Best practices ..................................................................................................................................2
1.3 Temperature limits ......................................................................................................................... 3
1.4 Recommendations for hygienic and self-draining applications ........................................................6
Chapter 2 Mounting ......................................................................................................................... 8
2.1 Recommendations for lifting heavy meters .....................................................................................8
2.2 Mount the sensor ............................................................................................................................9
2.3 Mount electronics of high-temperature sensors ............................................................................10
2.4 Mount a CMF010 sensor to a wall or pole ...................................................................................... 14
2.5 Mount a CMFS007, CMFS010 or CMFS015 sensor in a bracket .......................................................15
2.6 Mount a CMFS025, CMFS040 or CMFS050 sensor in a wall mount bracket .................................... 16
2.7 Secure wafer-style process connections ........................................................................................ 17
2.8 Attach extended electronics ......................................................................................................... 19
Chapter 3 Wiring ............................................................................................................................ 21
3.1 Options for wiring ......................................................................................................................... 21
3.2 Connect 4-wire cable .................................................................................................................... 22
3.3 Connect 9-wire cable .................................................................................................................... 26
Chapter 4 Grounding ...................................................................................................................... 28
Chapter 5 Supplementary information ............................................................................................29
5.1 Purge the sensor case ....................................................................................................................29
5.2 About rupture disks .......................................................................................................................31
Installation Manual i
Contents
ii Micro Motion ELITE
1 Planning
Topics covered in this chapter:

Installation checklist

Best practices
Temperature limits
Recommendations for hygienic and self-draining applications
1.1 Installation checklist
Make sure that the hazardous area specified on the approval tag is suitable for the
environment in which the meter will be installed.
Verify that the local ambient and process temperatures are within the limits of the
meter.
If your sensor has an integral transmitter, no wiring is required between the sensor
and transmitter. Follow the wiring instructions in the transmitter installation manual for signal and power wiring.
If your transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the instructions in the transmitter installation manual for power and signal wiring.
For the wiring between the sensor and the transmitter, consider maximum cable
lengths. The maximum distance between the sensor and transmitter depends on the cable type. For all types of wiring, Micro Motion recommends using Micro Motion cable.

Planning

Maximum lengths for Micro Motion cableTable 1-1:
Cable type To transmitter Maximum length
Micro Motion 9-wire 9739 MVD transmitter 1000 ft (300 m)
All other MVD transmitters 60 ft (20 m)
Micro Motion 4-wire All 4-wire MVD transmitters 1000 ft (300 m)
Maximum lengths for user-supplied 4-wire cableTable 1-2:
Wire function Wire size Maximum length
Power (VDC) 22 AWG (0,35 mm2) 300 ft (90 m)
20 AWG (0,5 mm2) 500 ft (150 m)
18 AWG (0,8 mm2) 1000 ft (300 m)
Signal (RS-485) 22 AWG (0,35 mm2) or larger 1000 ft (300 m)
Installation Manual 1
Planning
For optimal performance, install the sensor in the preferred orientation. The sensor
will work in any orientation as long as the flow tubes remain full of process fluid.
Preferred sensor orientationTable 1-3:
Process
Liquids
Gases
Preferred
orientation
Alternate orientations
Slurries
Install the meter so that the flow direction arrow on the sensor case matches the
actual forward flow of the process. (Flow direction is also software-selectable.)

1.2 Best practices

The following information can help you get the most from your sensor.
2 Micro Motion ELITE
There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases may flow upward or downward.
Keep the sensor tubes full of process fluid.
For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
Minimize bending and torsional stress on the meter. Do not use the meter to align
misaligned piping.
The sensor does not require external supports. The flanges will support the sensor in
any orientation. (Some sensor models installed in very small, flexible pipeline have optional installation instructions that allow for external supports.)

1.3 Temperature limits

Sensors can be used in the process and ambient temperature ranges shown in the
temperature limit graphs. For the purposes of selecting electronics options, temperature limit graphs should be used only as a general guide. If your process conditions are close to the gray areas, it may be inappropriate to use electronics options other than a junction box. Consult consult with your Micro Motion representative.
In all cases, the electronics cannot be operated where the ambient temperature is
below –40 °F (–40 °C) or above +140 °F (+60 °C). If a sensor is to be used where the ambient temperature is outside of the range permissible for the electronics, the electronics must be remotely located where the ambient temperature is within the permissible range, as indicated by the shaded area of the temperature limit graphs.
Temperature limits may be further restricted by hazardous area approvals. Refer to
the hazardous area approvals documentation shipped with the sensor or available from the Micro Motion web site (www.micromotion.com).
The extended-mount electronics option allows the sensor case to be insulated
without covering the transmitter, core processor, or junction box, but does not affect temperature ratings.
Planning
Installation Manual 3
Planning
Figure 1-1:
Ambient and process temperature limits for ELITE CMF***M/L/H/P (excludes cryogenic modifications) and CMFS007-015 meters
140 (60)
A
–40 (–40)
–148 (–100)
A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remote mount electronics only
Figure 1-2:
–400
(–240)
Ambient and process temperature limits for ELITE CMFS025–CMFS150 meters
140 (60)
C
D
B
140 (60)
140 (60)
D
113 (45)
400
(204)
D
113 (45)
C
A
–40 (–40)
D
–148 (–100)
A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remote mount electronics only
4 Micro Motion ELITE
–58
(–50)
B
400
(204)
Ambient and process temperature limits for cryogenic ELITE metersFigure 1-3:
140 (60)
–40 (–40)
A
–148 (–100)
–400
(–240)
A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remote mount electronics only
Planning
C
D
176 (80)
B
Figure 1-4:
Ambient and process temperature limits for high temperature ELITE meters
140 (60)
A
–40 (–40)
–148 (–100)
–50
(–58)
A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remote mount electronics only
C
D
B
662
(350)
Installation Manual 5
Planning
Ambient and process temperature limits for Super Duplex ELITE metersFigure 1-5:
140 (60)
A
–40 (–40)
–148 (–100)
–40
(–40)
A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remote mount electronics only
C
D
400
(204)
B
1.4 Recommendations for hygienic and self­draining applications
CMFS sensors are certified EHEDG TYPE EL CLASS I for hygienic applications when installed vertically with the process fitting and gasket combinations listed in the Position Paper of the EHEDG Test Methods Subgroup (available at http://www.ehedg.org). Other process connections/gasket combinations may be used provided they have been evaluated and successfully tested for in-place cleanability according to the latest edition of EHEDG Document 2. Refer to the ELITE Product Data Sheet for further information about fitting options.
For optimal cleanability and drainability:
If possible, install the sensor in a vertical pipeline with the process fluid flowing
upward through the sensor.
If the sensor must be installed in a horizontal pipeline, drainage is accomplished by
air purge evacuation of the pipeline circuit.
For clean-in-place (CIP) applications, Micro Motion recommends using the
generally-accepted flow velocity of at least 1.5 m/s for cleaning the sensor.
The gap between the electronics housing and sensor body should be inspected
periodically. Manually clean this gap when necessary.
6 Micro Motion ELITE
Installation for self-draining applicationsFigure 1-6:
A
B
C
A. Process pipeline B. Direction of normal process flow C. Direction of drainage
Planning
Installation Manual 7
Loading...
+ 25 hidden pages