Micro Motion® ELITE® Coriolis Flow and Density
Sensors
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EC declaration of conformity for directives that apply to this product. The EC declaration of
conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on
the internet at www.micromotion.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive can be found on the internet at
www.micromotion.com/documentation.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the transmitter
configuration manual. Product data sheets and manuals are available from the Micro Motion web site at
www.micromotion.com/documentation.
Return policy
Micro Motion procedures must be followed when returning equipment. These procedures ensure legal compliance with
government transportation agencies and help provide a safe working environment for Micro Motion employees. Failure to follow
Micro Motion procedures will result in your equipment being refused delivery.
Information on return procedures and forms is available on our web support system at www.micromotion.com, or by phoning the
Micro Motion Customer Service department.
Micro Motion customer service
Email:
•Worldwide: flow.support@emerson.com
•Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800-522-6277U.K.0870 240 1978Australia800 158 727
•Recommendations for hygienic and self-draining applications
1.1Installation checklist
Make sure that the hazardous area specified on the approval tag is suitable for the
□
environment in which the meter will be installed.
Verify that the local ambient and process temperatures are within the limits of the
□
meter.
If your sensor has an integral transmitter, no wiring is required between the sensor
□
and transmitter. Follow the wiring instructions in the transmitter installation manual
for signal and power wiring.
If your transmitter has remote-mounted electronics, follow the instructions in this
□
manual for wiring between the sensor and the transmitter, and then follow the
instructions in the transmitter installation manual for power and signal wiring.
For the wiring between the sensor and the transmitter, consider maximum cable
□
lengths. The maximum distance between the sensor and transmitter depends on
the cable type. For all types of wiring, Micro Motion recommends using Micro
Motion cable.
Planning
Maximum lengths for Micro Motion cableTable 1-1:
Cable typeTo transmitterMaximum length
Micro Motion 9-wire9739 MVD transmitter1000 ft (300 m)
All other MVD transmitters60 ft (20 m)
Micro Motion 4-wireAll 4-wire MVD transmitters1000 ft (300 m)
Maximum lengths for user-supplied 4-wire cableTable 1-2:
Wire functionWire sizeMaximum length
Power (VDC)22 AWG (0,35 mm2)300 ft (90 m)
20 AWG (0,5 mm2)500 ft (150 m)
18 AWG (0,8 mm2)1000 ft (300 m)
Signal (RS-485)22 AWG (0,35 mm2) or larger1000 ft (300 m)
Installation Manual 1
Planning
For optimal performance, install the sensor in the preferred orientation. The sensor
□
will work in any orientation as long as the flow tubes remain full of process fluid.
Preferred sensor orientationTable 1-3:
Process
Liquids
Gases
Preferred
orientation
Alternate orientations
Slurries
Install the meter so that the flow direction arrow on the sensor case matches the
□
actual forward flow of the process. (Flow direction is also software-selectable.)
1.2Best practices
The following information can help you get the most from your sensor.
2Micro Motion ELITE
•There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
•If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases may flow upward or downward.
•Keep the sensor tubes full of process fluid.
•For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
•Minimize bending and torsional stress on the meter. Do not use the meter to align
misaligned piping.
•The sensor does not require external supports. The flanges will support the sensor in
any orientation. (Some sensor models installed in very small, flexible pipeline have
optional installation instructions that allow for external supports.)
1.3Temperature limits
•Sensors can be used in the process and ambient temperature ranges shown in the
temperature limit graphs. For the purposes of selecting electronics options,
temperature limit graphs should be used only as a general guide. If your process
conditions are close to the gray areas, it may be inappropriate to use electronics
options other than a junction box. Consult consult with your Micro Motion
representative.
•In all cases, the electronics cannot be operated where the ambient temperature is
below –40 °F (–40 °C) or above +140 °F (+60 °C). If a sensor is to be used where the
ambient temperature is outside of the range permissible for the electronics, the
electronics must be remotely located where the ambient temperature is within the
permissible range, as indicated by the shaded area of the temperature limit graphs.
•Temperature limits may be further restricted by hazardous area approvals. Refer to
the hazardous area approvals documentation shipped with the sensor or available
from the Micro Motion web site (www.micromotion.com).
•The extended-mount electronics option allows the sensor case to be insulated
without covering the transmitter, core processor, or junction box, but does not
affect temperature ratings.
Planning
Installation Manual 3
Planning
Figure 1-1:
Ambient and process temperature limits for ELITE CMF***M/L/H/P
(excludes cryogenic modifications) and CMFS007-015 meters
140 (60)
A
–40 (–40)
–148 (–100)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
Figure 1-2:
–400
(–240)
Ambient and process temperature limits for ELITE CMFS025–CMFS150
meters
140 (60)
C
D
B
140
(60)
140
(60)
D
113 (45)
400
(204)
D
113 (45)
C
A
–40 (–40)
D
–148 (–100)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
4Micro Motion ELITE
–58
(–50)
B
400
(204)
Ambient and process temperature limits for cryogenic ELITE metersFigure 1-3:
140 (60)
–40 (–40)
A
–148 (–100)
–400
(–240)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
Planning
C
D
176
(80)
B
Figure 1-4:
Ambient and process temperature limits for high temperature ELITE
meters
140 (60)
A
–40 (–40)
–148 (–100)
–50
(–58)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
C
D
B
662
(350)
Installation Manual 5
Planning
Ambient and process temperature limits for Super Duplex ELITE metersFigure 1-5:
140 (60)
A
–40 (–40)
–148 (–100)
–40
(–40)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
C
D
400
(204)
B
1.4Recommendations for hygienic and selfdraining applications
CMFS sensors are certified EHEDG TYPE EL CLASS I for hygienic applications when installed
vertically with the process fitting and gasket combinations listed in the Position Paper of
the EHEDG Test Methods Subgroup (available at http://www.ehedg.org). Other process
connections/gasket combinations may be used provided they have been evaluated and
successfully tested for in-place cleanability according to the latest edition of EHEDG
Document 2. Refer to the ELITE Product Data Sheet for further information about fitting
options.
For optimal cleanability and drainability:
•If possible, install the sensor in a vertical pipeline with the process fluid flowing
upward through the sensor.
•If the sensor must be installed in a horizontal pipeline, drainage is accomplished by
air purge evacuation of the pipeline circuit.
•For clean-in-place (CIP) applications, Micro Motion recommends using the
generally-accepted flow velocity of at least 1.5 m/s for cleaning the sensor.
•The gap between the electronics housing and sensor body should be inspected
periodically. Manually clean this gap when necessary.
6Micro Motion ELITE
Installation for self-draining applicationsFigure 1-6:
A
B
C
A.Process pipeline
B.Direction of normal process flow
C.Direction of drainage
Planning
Installation Manual 7
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.