Micro Motion® ELITE® Coriolis Flow and Density
Sensors
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EC declaration of conformity for directives that apply to this product. The EC declaration of
conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on
the internet at www.micromotion.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive can be found on the internet at
www.micromotion.com/documentation.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the transmitter
configuration manual. Product data sheets and manuals are available from the Micro Motion web site at
www.micromotion.com/documentation.
Return policy
Micro Motion procedures must be followed when returning equipment. These procedures ensure legal compliance with
government transportation agencies and help provide a safe working environment for Micro Motion employees. Failure to follow
Micro Motion procedures will result in your equipment being refused delivery.
Information on return procedures and forms is available on our web support system at www.micromotion.com, or by phoning the
Micro Motion Customer Service department.
Micro Motion customer service
Email:
•Worldwide: flow.support@emerson.com
•Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800-522-6277U.K.0870 240 1978Australia800 158 727
•Recommendations for hygienic and self-draining applications
1.1Installation checklist
Make sure that the hazardous area specified on the approval tag is suitable for the
□
environment in which the meter will be installed.
Verify that the local ambient and process temperatures are within the limits of the
□
meter.
If your sensor has an integral transmitter, no wiring is required between the sensor
□
and transmitter. Follow the wiring instructions in the transmitter installation manual
for signal and power wiring.
If your transmitter has remote-mounted electronics, follow the instructions in this
□
manual for wiring between the sensor and the transmitter, and then follow the
instructions in the transmitter installation manual for power and signal wiring.
For the wiring between the sensor and the transmitter, consider maximum cable
□
lengths. The maximum distance between the sensor and transmitter depends on
the cable type. For all types of wiring, Micro Motion recommends using Micro
Motion cable.
Planning
Maximum lengths for Micro Motion cableTable 1-1:
Cable typeTo transmitterMaximum length
Micro Motion 9-wire9739 MVD transmitter1000 ft (300 m)
All other MVD transmitters60 ft (20 m)
Micro Motion 4-wireAll 4-wire MVD transmitters1000 ft (300 m)
Maximum lengths for user-supplied 4-wire cableTable 1-2:
Wire functionWire sizeMaximum length
Power (VDC)22 AWG (0,35 mm2)300 ft (90 m)
20 AWG (0,5 mm2)500 ft (150 m)
18 AWG (0,8 mm2)1000 ft (300 m)
Signal (RS-485)22 AWG (0,35 mm2) or larger1000 ft (300 m)
Installation Manual 1
Planning
For optimal performance, install the sensor in the preferred orientation. The sensor
□
will work in any orientation as long as the flow tubes remain full of process fluid.
Preferred sensor orientationTable 1-3:
Process
Liquids
Gases
Preferred
orientation
Alternate orientations
Slurries
Install the meter so that the flow direction arrow on the sensor case matches the
□
actual forward flow of the process. (Flow direction is also software-selectable.)
1.2Best practices
The following information can help you get the most from your sensor.
2Micro Motion ELITE
•There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
•If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases may flow upward or downward.
•Keep the sensor tubes full of process fluid.
•For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
•Minimize bending and torsional stress on the meter. Do not use the meter to align
misaligned piping.
•The sensor does not require external supports. The flanges will support the sensor in
any orientation. (Some sensor models installed in very small, flexible pipeline have
optional installation instructions that allow for external supports.)
1.3Temperature limits
•Sensors can be used in the process and ambient temperature ranges shown in the
temperature limit graphs. For the purposes of selecting electronics options,
temperature limit graphs should be used only as a general guide. If your process
conditions are close to the gray areas, it may be inappropriate to use electronics
options other than a junction box. Consult consult with your Micro Motion
representative.
•In all cases, the electronics cannot be operated where the ambient temperature is
below –40 °F (–40 °C) or above +140 °F (+60 °C). If a sensor is to be used where the
ambient temperature is outside of the range permissible for the electronics, the
electronics must be remotely located where the ambient temperature is within the
permissible range, as indicated by the shaded area of the temperature limit graphs.
•Temperature limits may be further restricted by hazardous area approvals. Refer to
the hazardous area approvals documentation shipped with the sensor or available
from the Micro Motion web site (www.micromotion.com).
•The extended-mount electronics option allows the sensor case to be insulated
without covering the transmitter, core processor, or junction box, but does not
affect temperature ratings.
Planning
Installation Manual 3
Planning
Figure 1-1:
Ambient and process temperature limits for ELITE CMF***M/L/H/P
(excludes cryogenic modifications) and CMFS007-015 meters
140 (60)
A
–40 (–40)
–148 (–100)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
Figure 1-2:
–400
(–240)
Ambient and process temperature limits for ELITE CMFS025–CMFS150
meters
140 (60)
C
D
B
140
(60)
140
(60)
D
113 (45)
400
(204)
D
113 (45)
C
A
–40 (–40)
D
–148 (–100)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
4Micro Motion ELITE
–58
(–50)
B
400
(204)
Ambient and process temperature limits for cryogenic ELITE metersFigure 1-3:
140 (60)
–40 (–40)
A
–148 (–100)
–400
(–240)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
Planning
C
D
176
(80)
B
Figure 1-4:
Ambient and process temperature limits for high temperature ELITE
meters
140 (60)
A
–40 (–40)
–148 (–100)
–50
(–58)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
C
D
B
662
(350)
Installation Manual 5
Planning
Ambient and process temperature limits for Super Duplex ELITE metersFigure 1-5:
140 (60)
A
–40 (–40)
–148 (–100)
–40
(–40)
A.Ambient temperature °F (°C)
B.Process temperature in °F (°C)
C.All available electronic options
D.Extended or remote mount electronics only
C
D
400
(204)
B
1.4Recommendations for hygienic and selfdraining applications
CMFS sensors are certified EHEDG TYPE EL CLASS I for hygienic applications when installed
vertically with the process fitting and gasket combinations listed in the Position Paper of
the EHEDG Test Methods Subgroup (available at http://www.ehedg.org). Other process
connections/gasket combinations may be used provided they have been evaluated and
successfully tested for in-place cleanability according to the latest edition of EHEDG
Document 2. Refer to the ELITE Product Data Sheet for further information about fitting
options.
For optimal cleanability and drainability:
•If possible, install the sensor in a vertical pipeline with the process fluid flowing
upward through the sensor.
•If the sensor must be installed in a horizontal pipeline, drainage is accomplished by
air purge evacuation of the pipeline circuit.
•For clean-in-place (CIP) applications, Micro Motion recommends using the
generally-accepted flow velocity of at least 1.5 m/s for cleaning the sensor.
•The gap between the electronics housing and sensor body should be inspected
periodically. Manually clean this gap when necessary.
6Micro Motion ELITE
Installation for self-draining applicationsFigure 1-6:
A
B
C
A.Process pipeline
B.Direction of normal process flow
C.Direction of drainage
Planning
Installation Manual 7
Mounting
2Mounting
Topics covered in this chapter:
•Recommendations for lifting heavy meters
•Mount the sensor
•Mount electronics of high-temperature sensors
•Mount a CMF010 sensor to a wall or pole
•Mount a CMFS007, CMFS010 or CMFS015 sensor in a bracket
•Mount a CMFS025, CMFS040 or CMFS050 sensor in a wall mount bracket
•Secure wafer-style process connections
•Attach extended electronics
2.1Recommendations for lifting heavy meters
Heavy meters (those over 50 lb. [22 kg]), and even lighter meters that must be installed in
elevated or difficult-to-reach places, usually require additional consideration when
transporting or lifting them into their installation location.
•Safe handling during transportation and installation is the responsibility of the
installer – know and follow all safety practices and regulations for your facility and
for any lifting/rigging equipment being used
•A professional rigging crew with proper equipment should be used
•Typical equipment for handling heavy meters includes the following:
-Fixed hoist boom trucks or cranes
-Continuous web belt slings
-Eye to eye web belt slings
-Two leg wire rope slings
•Lift a meter by its case or on the case side of its process fittings.
•Do not lift a meter by its electronics (junction box, transmitter, or any electrical
fittings) or by its purge fittings
•It may be useful to identify the meter center of gravity
•Protect the sealed surfaces on the process fittings with factory-installed flange
protectors or comparable field-installed protection
8Micro Motion ELITE
A
Mounting
Acceptable lifting pointsFigure 2-1:
Center of gravity for large metersFigure 2-2:
A.Typical center of gravity
Note
Complete and detailed dimensional drawings, including the location of the center of gravity, can be
found through the product drawings link in our online store (www.micromotion.com/onlinestore).
2.2Mount the sensor
Use your common practices to minimize torque and bending load on process connections.
Tip
To reduce the risk of condensation or excessive moisture, the conduit opening should not point
upward (if possible). The conduit opening of the junction box or core processor can be rotated freely
to facilitate wiring.
Installation Manual 9
Mounting
CAUTION!
Do not lift the sensor by the electronics or purge connections. Lifting the sensor by the
electronics or purge connections can damage the device.
Mounting the sensorFigure 2-3:
Notes
•Do not use the sensor to support the piping.
•The sensor does not require external supports. The flanges will support the sensor in any
orientation. (Some sensor models installed in very small, flexible pipeline have optional installation
instructions that allow for external supports.)
2.3Mount electronics of high-temperature sensors
The electronics of high-temperature sensors are attached to the end of a 32" (812 mm)
pre-installed flexible conduit. The electronics must be separately mounted on a wall or
instrument pole.
10Micro Motion ELITE
Components of a high-temperature sensorFigure 2-4:
With some large meter sizes, the meter may ship with the electronics attached to the
sensor case. The meter cannot be operated in this configuration. Detach the electronics
bracket from the sensor case and then proceed to mount the electronics to a wall or
instrument pole as described below.
Important
Do not operate the meter while the electronics are attached to the sensor case.
Installation Manual 11
A
Mounting
Removing electronics from the sensor caseFigure 2-5:
A.Detach electronics from sensor case and mount to a wall or instrument pole
Procedure
•For wall mounting, use four 5/16" or four M8 bolts to secure the mounting bracket.
12Micro Motion ELITE
A
B
C
Mounting
Wall-mount componentsFigure 2-6:
A. Wall or flat surface
B. Electronics (enhanced core processor shown)
C. Flexible conduit
•For mounting to an instrument pole, use a 2-inch U-bolt pipe kit to secure the
mounting bracket.
Installation Manual 13
A
B
C
Mounting
Pole-mount componentsFigure 2-7:
A. Instrument pole
B. Electronics (enhanced core processor shown)
C. Flexible conduit
2.4Mount a CMF010 sensor to a wall or pole
The CMF010 sensor has an optional mounting configuration for use with small or flexible
pipeline. If the pipeline adequately supports the sensor, this procedure can be skipped.
1.Locate the optional mounting holes. For sensors with a junction box, the junction
box must be rotated to the side to expose the mounting holes.
14Micro Motion ELITE
Optional mounting for CMF010 sensorsFigure 2-8:
A
B
C
A. Two user-supplied 5/16" (M8) bolts
B. Junction box or core processor (junction box shown)
C. Mounting surface
Mounting
2.If necessary, install rigid standoffs between the sensor and the mounting surface.
2.5Mount a CMFS007, CMFS010 or CMFS015
sensor in a bracket
The CMFS007, CMFS010 and CMFS015 sensors have an optional mounting bracket for use
with small or flexible pipeline. If the pipeline adequately supports the sensor, this
procedure can be skipped.
1.Secure the mounting bracket to a wall or other flat surface with four user-supplied
5/16" (8 mm) bolts.
2.Place the sensor into the bracket.
3.Secure the sensor in the bracket with the supplied 5/16" (M8) U-bolts.
Installation Manual 15
A
B
C
Mounting
Mounting bracket for CMFS007, CMFS010, and CMFS015Figure 2-9:
A. Flange nut
B. Gasket (user-supplied)
C. Alignment ring
D. Flange bolt
E. Sensor wafer
3.Insert the flange bolts through both process connections, and thread the flange nuts
onto the bolts.
4.With your fingers, tighten the flange nuts.
5.Rotate the sensor alignment rings in the direction that pushes the bolts outward.
Tip
Rotate both sensor aligment rings until the assembly is centered and tight.
Alignment ring usageFigure 2-13:
A. Direction to rotate the alignment ring
B. Direction the flange bolts are pushed
C. Flange bolt
18Micro Motion ELITE
6.With a wrench, tighten the nuts in an alternating order.
2.8Attach extended electronics
If you ordered a sensor with extended electronics, you will need to install the extender
onto the sensor case.
Note
Extended core processors are matched at the factory to specific sensors. Keep each core processor
together with the sensor with which it was shipped.
CAUTION!
Keep the extender and feedthrough clean and dry. Moisture or debris in the extender or
feedthrough can damage electronics and result in measurement error or flowmeter failure.
Procedure
Mounting
1.Remove and recycle the plastic cap from the feedthrough on the sensor.
Installation Manual 19
G
H
E
D
C
A
B
F
Mounting
Feedthrough and extender componentsFigure 2-14:
A. Transmitter or core processor
B. Extender
C. O-ring
D. Feedthrough
E. Clamping ring
F. Clamping screw
G. Plastic plug
H. Plastic cap
2.Loosen the clamping screw and remove the clamping ring. Leave the O-ring in place
on the feedthrough.
3.Remove and recycle the plastic plug from the extender.
4.Fit the extender onto the feedthrough by carefully aligning the notches on the
bottom of the extender with the notches on the feedthrough.
5.Close the clamping ring and tighten the clamping screw to 13–18 in-lbs.
(1,5–2 N-m).
20Micro Motion ELITE
Wiring
3Wiring
Topics covered in this chapter:
•Options for wiring
•Connect 4-wire cable
•Connect 9-wire cable
3.1Options for wiring
The wiring procedure you follow depends on which electronics option you have.
Wiring procedures by electronics optionTable 3-1:
Electronics optionWiring procedure
Integral transmitterNo wiring is required between sensor and transmitter. See the transmitter
installation manual for wiring the power and signal cable to the transmitter.
MVD™Direct Connect
Core processorConnect a 4-wire cable between the sensor and transmitter. Refer to the 4-wire
Junction boxConnect a 9-wire cable between the sensor and transmitter. Refer to the 9-wire
™
No transmitter to wire. See the MVD Direct Connect manual for wiring the
power and signal cable between the sensor and the direct host.
connection instructions in this manual.
connection instructions in this manual, as well as the Micro Motion 9-WireFlowmeter Cable Preparation and Installation Guide.
CAUTION!
Make sure the hazardous area specified on the sensor approval tag is suitable for the
environment in which the sensor will be installed. Failure to comply with the requirements for
intrinsic safety in a hazardous area could result in an explosion.
CAUTION!
Fully close and tighten all housing covers and conduit openings. Improperly sealed housings
can expose electronics to moisture, which can cause measurement error or flowmeter failure.
Inspect and grease all gaskets and O-rings.
Installation Manual 21
Wiring
3.2Connect 4-wire cable
3.2.1Prepare the 4-wire cable
Important
For user-supplied cable glands, the gland must be capable of terminating the drain wires.
Note
If you are installing unshielded cable in continuous metallic conduit with 360º termination shielding,
you only need to prepare the cable – you do not need to perform the shielding procedure.
22Micro Motion ELITE
Wiring
4-wire cable preparationFigure 3-1:
Remove the core processor
cover
Cable glands
Micro Motion
cable gland
Pass the wires through the gland nut and clamping insert.
Gland nut
1. Strip 4-1/2 inch (115 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 3/4 inch (19 mm) of shielding.
Clamping
insert
NPT
Wrap the drain wires twice around the shield and cut off
Gland supplier
Gland type
the excess drain wires.
Cable layout
through the gland.
Terminate the drain
wires inside the
M20
1. Strip 4-1/4 inch (108 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 1/2 inch (12 mm) of shielding.
User-supplied
cable gland
Pass the wires
gland.
Metal conduit
Run conduit to
sensor
Lay cable in conduit
Done
(do not perform the
shielding procedure)
Drain wires
wrapped around
shield
Go to the shielding
procedure
Installation Manual 23
Wiring
4-wire cable shieldingFigure 3-2:
From the preparation
procedure
Micro Motion
cable gland
Braided
(armored cable)
Apply the Heat Shrink
1. Slide the shielded heat shrink over the drain wires. Ensure that the
wires are completely covered.
2. Apply heat (250 °F or 120 °C) to shrink the tubing. Do not burn the
cable.
3. Position the clamping insert so the interior end is flush with the braid
of the heat shrink.
Assemble the Gland
1. Fold the shield or braid back over the clamping insert and 1/8 inch
(3 mm) past the O-ring.
2. Install the gland body into the conduit opening on the core processor housing.
3. Insert the wires through gland body and tighten the gland nut onto the gland body.
Cable shield
type
Shielded heat
shrink
Foil
(shielded cable)
NPT
Gland supplier
Gland typeM20
After heat applied
User-supplied
cable gland
Trim 7 mm from the shielded
heat shrink
Trim
Terminate the shield
and drain wires in the
Assemble the gland
according to vendor
gland
instructions
Shield folded back
Done
Gland body
4-wire cable types and usage
Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain
shield drain wires.
The 4-wire cable supplied by Micro Motion consists of one pair of red and black 18 AWG
(0.75 mm2) wires for the VDC connection, and one pair of white and green 22 AWG
(0.35 mm2) wires for the RS-485 connection.
User-supplied 4-wire cable must meet the following requirements:
24Micro Motion ELITE
•Twisted pair construction.
•Applicable hazardous area requirements, if the core processor is installed in a
hazardous area.
•Wire gauge appropriate for the cable length between the core processor and the
transmitter.
Wire gaugeTable 3-2:
Wire gaugeMaximum cable length
VDC 22 AWG (0.35 mm2)300 ft (90 m)
VDC 20 AWG (0.5 mm2)500 ft (150 m)
VDC 18 AWG (0.8 mm2)1000 ft (300 m)
RS-485 22 AWG (0.35 mm2) or larger1000 ft (300 m)
3.2.2Connect the wires to the core processor terminals
After the 4-wire cable has been prepared and shielded (if required), connect the individual
wires of the 4-wire cable to the terminals on the core processor.
Wiring
Installation Manual 25
Wiring
Core processor terminalsFigure 3-3:
From Step 1 or 2
Standard
core processor
Connect the wires to the core processor terminals:
Red wire>Terminal 1 (Power supply +)
Black wire>Terminal 2 (Power supply –)
White wire>Terminal 3 (RS-485/A)
Green wire>Terminal 4 (RS-485/B)
Reinstall and tighten the core processor cover
Core processor
type
Enhanced
core processor
Connect the wires to the core processor terminals:
Red wire>Terminal 1 (Power supply +)
Black wire>Terminal 2 (Power supply –)
White wire>Terminal 3 (RS-485/A)
Green wire>Terminal 4 (RS-485/B)
1. Reinstall the core processor cover.
2. Torque cover screws to:
•10–13 in-lbs (1,13–1,47 N-m) for aluminum housing
•Minimum 19 in-lbs (2,1 N-m) for stainless steel
housing
Connect the wires to the transmitter
(see the transmitter manual)
terminals
3.3Connect 9-wire cable
1.Prepare and install the cable according to the instructions in the Micro Motion 9Wire Flowmeter Cable Preparation and Installation Guide.
2.Insert the stripped ends of the individual wires into the terminal blocks. Ensure that
no bare wires remain exposed.
26Micro Motion ELITE
Wiring
3.Match the wires color for color. For wiring at the transmitter or remote core
processor, refer to the transmitter documentation.
4.Tighten the screws to hold the wires in place.
5.Ensure integrity of gaskets, then tightly close and seal the junction box cover and all
housing covers on the transmitter or core processor.
6.Refer to the transmitter installation manual for signal and power wiring instructions.
Installation Manual 27
Grounding
4Grounding
The meter must be grounded according to the standards that are applicable at the site.
The customer is responsible for knowing and complying with all applicable standards.
Prerequisites
Micro Motion suggests the following guides for grounding practices:
•In Europe, IEC 79-14 is applicable to most installations, in particular Sections
12.2.2.3 and 12.2.2.4.
•In the U.S.A. and Canada, ISA 12.06.01 Part 1 provides examples with associated
applications and requirements.
If no external standards are applicable, follow these guidelines to ground the sensor:
•Keep all ground leads as short as possible, less than 1 Ω impedance.
•Connect ground leads directly to earth, or follow plant standards.
CAUTION!
Ground the flowmeter to earth, or follow ground network requirements for the facility.
Improper grounding can cause measurement error.
Procedure
Check the joints in the pipeline.
-If the joints in the pipeline are ground-bonded, the sensor is automatically grounded
and no further action is necessary (unless required by local code).
-If the joints in the pipeline are not grounded, connect a ground wire to the grounding
screw located on the sensor electronics.
Tip
The sensor electronics may be a transmitter, core processor, or junction box. The grounding
screw may be internal or external.
28Micro Motion ELITE
5Supplementary information
Topics covered in this chapter:
•Purge the sensor case
•About rupture disks
5.1Purge the sensor case
If the sensor has purge fittings, they should remain sealed at all times. After a purge plug
has been removed, the sensor case should be purged with argon or nitrogen and resealed.
Purging the case protects internal components. The sensor is purged of all oxygen and
sealed at the factory. If the purge plugs are never removed, it is not necessary to purge or
re-seal the sensor. For more information, contact Micro Motion Customer Service.
If a purge plug is removed from the sensor case, it will be necessary to repurge the case.
Supplementary information
CAUTION!
Take all necessary precautions when removing purge plugs. Removing a purge plug
compromises the secondary containment of the sensor and could expose the user to process
fluid.
CAUTION!
Improper pressurization of the sensor case could result in personal injury. Removing a purge
plug will require the sensor case to be repurged with a dry inert gas. Follow all instructions
provided in the case purging procedure.
Prerequisites
Make sure the following are available before beginning the purge procedure:
•Teflon® tape
•Argon or nitrogen gas sufficient to purge the sensor case
Procedure
1.Shut down the process, or set control devices for manual operation. Before
performing the case purging procedure, shut down the process or set the control
devices for manual operation. Performing the purge procedure while the flowmeter
is operating could affect measurement accuracy, resulting in inaccurate flow signals.
2.Remove both purge plugs from the sensor case. If purge lines are being used, open
the valve in the purge lines.
3.Prepare the purge plugs for reinstallation by wrapping them with 3–5 turns of Teflon
tape.
Installation Manual 29
Supplementary information
4.Connect the supply of nitrogen or argon gas to the inlet purge connection or open
5.Make sure that there is a tight seal between the inlet connection and sensor case, so
6.Run purge gas through the sensor.
inlet purge line. Leave the outlet connection open.
• Exercise caution to avoid introducing dirt, moisture, rust, or other contaminants
into the sensor case.
• If the purge gas is heavier than air (such as argon), locate the inlet lower than the
outlet, so that the purge gas will displace air from bottom to top.
• If the purge gas is lighter than air (such as nitrogen), locate the inlet higher than
the outlet, so that the purge gas will displace air from top to bottom.
that air cannot be drawn by suction into the case or purge line during the purging
process.
The purge time is the amount of time required for full exchange of atmosphere to
inert gas. The larger the line size, the greater amount of time is required to purge
the case. If purge lines are being used, increase the purge time to fill the additional
volume of the purge line.
Note
Keep the purge gas pressure below 30 psig (2 bar).
Purge timeTable 5-1:
Sensor modelPurge rate, in ft3/hr (l/h)Time, in minutes
CMF01020 (566)1
CMF02520 (566)1
CMF05020 (566)2
CMF10020 (566)5
CMF20020 (566)12
CMF30020 (566)30
CMF35020 (566)45
CMF40020 (566)55
CMFHC220 (566)100
CMFHC320 (566)170
CMFHC420 (566)268
CMFS00720 (566)1 1/2
CMFS01020 (566)1 1/2
CMFS01520 (566)1 1/2
CMFS02520 (566)4 1/2
CMFS04020 (566)4 1/2
CMFS05020 (566)4 1/2
CMFS07520 (566)6
30Micro Motion ELITE
Purge time (continued)Table 5-1:
Sensor modelPurge rate, in ft3/hr (l/h)Time, in minutes
CMFS10020 (566)6
CMFS15020 (566)6
7.At the appropriate time, shut off the gas supply, then immediately seal the purge
outlet and inlet connections with the purge plugs.
Note
Avoid pressurizing the sensor case. If pressure inside the case elevates above atmospheric
pressure during operation, the flowmeter density calibration will be inaccurate.
8.Make sure that the purge fitting seals are tight so that air cannot be drawn by
suction into the sensor case.
5.2About rupture disks
Supplementary information
Rupture disks are meant to vent process fluid from the sensor case in the event of a flow
tube rupture. Some users connect a pipeline to the rupture disk to help contain escaping
process fluid. For more information about rupture disks, contact Micro Motion Customer
Service.
If the sensor has rupture disks, they are installed in the sensor purge fitting openings. The
rupture disks should remain installed at all times. If you remove a rupture disk from the
sensor case, it will be necessary to re-purge the case.
CAUTION!
Stay clear of the rupture disk pressure relief area. High-pressure fluid escaping from the sensor
can cause severe injury or death.
Installation Manual 31
Micro Motion Inc. USA
Worldwide Headquarters
7070 Winchester Circle
Boulder, Colorado 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.micromotion.com
Micro Motion Europe
Emerson Process Management
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 318 495 555
F +31 (0) 318 495 556
www.micromotion.nl
*20002158*
20002158
Rev DI
2014
Micro Motion Asia
Emerson Process Management
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6777-8211
F +65 6770-8003
Micro Motion United Kingdom
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181
Micro Motion Japan
Emerson Process Management
1-2-5, Higashi Shinagawa
Shinagawa-ku
Tokyo 140-0002 Japan
T +81 3 5769-6803
F +81 3 5769-6844
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Process
Management family of companies. All other marks are property of
their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.