Emerson 1F97-1277 User Manual

Big Blue Touchscreen Thermostat with
CAUTION
!
Automatic Heat/Cool Changeover Option
Installation and Operating Instructions for Model:
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Model Programming Choices
1F97-1277
Non-Programmable 5+1+1 Day 7 Day
APPLICATIONS
THERMOSTAT APPLICATION GUIDE
Description
Heat Pump (No Aux. or Emergency Heat) Yes Heat Pump (with Aux. or Emergency Heat) Yes Systems with up to 3 Stages Heat, 2 Stages Cool No Heat Only Systems Yes Millivolt Heat Only Systems – Floor or Wall Furnaces Yes Cool Only Systems Ye s Gas or Oil Heat Yes Electric Furnace Yes Hydronic (Hot Water) Zone Heat – 2 Wires Ye s Hydronic (Hot Water) Zone Heat – 3 Wires Ye s Wired Remote Temperature Sensor (Indoor/Outdoor) Yes
Dual Fuel Feature (Heat Pump Mode) Yes
1F97-1277 Touchscreen Thermostat
SPECIFICATIONS
Electrical Rating:
Battery Power.......................... mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Terminal Load ............................. 1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range ............................ 45 to 99°F (7 to 37°C)
Differential (Single Stage) .................... Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage) ..................... Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump) ..................... Heat 1.2°F; Cool 1.5°F
Operating Ambient.......................... 32°F to +105°F (0 to +41°C)
Operating Humidity ......................... 90% non-condensing max.
Shipping Temperature Range ................. -4 to +150°F (-20 to +65°C)
Dimensions Thermostat...................... 4-9/16"H x 5-13/16"W x 1-3/16"D
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
Index Page
Installation 2 Wiring Connections 2 Thermostat Quick Reference 4 Installer Conguration Menu 5 Operating Your Thermostat 8 Programming 9 Troubleshooting 12
www.white-rodgers.com
www.emersonclimate.com
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this product may replace a product that contains mercury.
Mercury and products containing mercury must not be discarded in household trash. Do not touch any spilled mercury. Wearing non-absorbent gloves, clean up any spilled mercury and place in a sealed container. For proper disposal of a product containing mercury or a sealed container of spilled mercury, place it in a suitable shipping container. Refer to www.thermostat-recycle.org for location to send the product containing mercury.
PART NO. 37-7388A
1241
2 "AA" Batteries
INSTALLATION
Mounting
Hole
Mounting
Hole
Place Level across Mounting Tabs (for appearance only)
Place Level
across
Mounting Tabs
(for appearance only)
+
S
-
W/E
6
L
WARNING
!
Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code.
Remove Old Thermostat
A standard heat/cool thermostat consists of three basic parts:
1. The cover, which may be either a snap-on or hinge type.
2. The base, which is removed by loosening all captive screws.
3. The switching subbase, which is removed by unscrewing
the mounting screws that hold it on the wall or adapter plate. Before removing wires from old thermostat,
label each wire with the terminal designation from which it was attached. Disconnect the wires from the old
thermostat one at a time. Do not let wires fall back into the wall.
Battery Location
2 "AA" alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. Remove the battery tag to engage the batteries. To replace batteries, set system to OFF, remove thermostat from wall and install the batteries in the rear along the top of the thermostat (see Figure 1).
Figure 1 – Thermostat Base Multi-Stage 1F97-1277
Installing New Thermostat
1. Pull the thermostat body off the thermostat base. Forcing
or prying on the thermostat will cause damage to the unit.
2. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
3. Move base out of the way. Drill mounting holes. If you
are using existing mounting holes and the holes drilled are too large and do not allow you to tighten base snugly,
use plastic screw anchors to secure the base.
4. Fasten base snugly to wall using mounting holes shown
in Figure 1 and two mounting screws. Leveling is for appearance only and will not affect thermostat operation.
5. Connect wires to terminal block on base using appropriate wiring schematic (see diagrams on next page).
6. Push excess wire into wall and plug hole with a re resis­tant material (such as berglass insulation) to prevent
drafts from affecting thermostat operation.
7. Carefully line the thermostat up with the base and snap
into place.
WIRING CONNECTIONS
Refer to equipment manufacturers' instructions for specic
system wiring information. After wiring, see CONFIGURA-
TION section for proper thermostat conguration.
Rear view of thermostat
For wiring diagrams, see next page. Wiring diagrams shown are for typical systems and describe the thermostat terminal functions.
TERMINAL DESIGNATION DESCRIPTIONS
Terminal Designation Description
B ...................Changeover valve for heat pump energized constantly in heating
O ...................Changeover valve for heat pump energized constantly in cooling
Y ...................Compressor Relay
G ...................Fan Relay
RC...................Power for Cooling
RH...................Power for Heating
C ...................Common wire from secondary side of cooling
L ...................For Call for Service indicator for systems with diagnostic connection
6 ...................Powered closed connection for 3-wire zone valve
W ...................Heat Relay
-....................Common (DC) for wired remote temperature sensor
S ...................Frequency signal from remote temperature sensor
+ ...................Power (DC) to remote temperature sensor
2
WIRING CONNECTIONS
To Remote Te mperature Sensor
HEATING
To Remote Temperature Sensor
Single Stage Connections
Refer to equipment manufacturers' instructions for specic system
wiring information. This thermostat is designed to operate a single-transformer or two­transformer system.
You can congure the thermostat for use with the following systems:
Single Stage System with Single Transformer
To Remote Te mperature Sensor
Jumper
B
120VAC
TRANSFORMER
System
Single Stage
(SS)
CLASS II
Energized in Heat or Off Mode
System
Single Stage
(SS)
NEUTRAL
24VAC
HOT
Energiz­ed in Cool Mode
B
Energized in Heat, Off Mode
O
Energized on call for Cool (Com­pressor)
O
Energized in Cool Mode
Y
Remove Jumper Wire between RH & RC
Energized on call for Cool (Com­pressor)
G
Blower/ Circula­tor Fan Energiz­ed on call for Cool & for Heat (if ELE is sel­ected)
Y
RC
RH
C*
DC supply
24 Volt
voltage
Com-
24 Volt
24 Volt (Hot) Cool
(Hot) Heat
mon (option­al)
to re­mote Temp­erature Sensor
*Common connection required for fault or malfunction indication and remote sensor.
Single Stage with Two Transformers
Jumper
RC
24 Volt (Hot) Cool
RH
C*
24 Volt Com-
24 Volt
mon
(Hot)
(option-
Heat
al)
*Common connection required for fault or malfunction indication and remote sensor.
G
Blower/ Circula­tor Fan Energiz­ed on call for Heat or Cool (if ELE is sel­ected)
SINGLE STAGE gas, oil or electric.
HEAT PUMP TYPE 1 (HP 1). Single stage compressor system; gas
or electric backup.
After wiring, see INSTALLER CONFIGURATION section for proper
thermostat conguration.
{
+
S
-
Remote Temp­erature Sensor signal
DC Return to Remote Temp­erature Sensor
W
Energized on call for Heat
6
Third wire for 3-wire zone valve
L
Diagnostic Indicator (See
1
Note
)
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
{
NOTE: If continuous backlight or hardwired power input are desired but do not function
+
DC supply voltage to re­mote Temp­erature Sensor
S
Remote Temp­erature Sensor signal
-
DC Return to Remote Temp­erature Sensor
W
Energized on call for Heat
6
Third wire for 3-wire zone valve
Diagnostic Indicator (See Note
in both HEAT and COOL modes, cut the
L
heating transformer 24V wires and tape off. Connect the neutral circuit disconnected from the heating transformer to the neutral circuit of the cooling transformer. Discon­nect the wire to the RH terminal and install a jumper between RH and RC. Depending on the system requirements, replace the
1
)
cooling transformer with a 75VA class II transformer if needed.
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
COOLING
Heat Pump Systems
{
Jumper
B
System
Heat Pump 1 (HP1)
Energiz­ed in Heat/ Emer­gency Mode
O
Energized in Cool & Off Mode
Y
1st Stage Heat & Cool (Com­pressor) **
RC
G
Blower/ Circula­tor Fan
24 VAC
Energiz-
(Hot)
ed on
Cool
call for Heat or Cool
RH
24 VAC (Hot) Heat
24 VAC Common (optional)
NOTE : Connection for Call for Service diagnostic indicator compatible with mechanical or electronic condenser control with Comfort AlertTM.
+
C*
DC supply voltage to re­mote Temp­erature Sensor
S
Remote Temp­erature Sensor signal
-
DC Return to Remote Temp­erature Sensor
W
Auxil­iary & Emer­gency Heat 1st Stage
6
Power Closed Conn­ection for 3-wire zone valve
L
Diagnostic Indicator (See Note )
Comfort Alert II module or similar malfunction module
NEUTRAL
24VAC
HOT
TRANSFORMER
*24 VAC common connection optional for system operation.
Required for fault or malfunction indi-
cation, remote temperature sensor, or
for continuous backlight operation.
**Dual fuel de-energizes
compressor when auxiliary heat is
energized.
120VAC
CLASS II
3
1
2
3
4
5
6
7
8
9
10
11
12
Time of Day
Day of Week
Room Temperature
System Switch
Fan Switch
Indicates when thermostat is calling for Heat or Cool
Battery Level Indicator Indicating the current power level of the 2 “AA” batteries. Full power remaining. Half power remaining.
Change The batteries should be replaced at this time.
Menu key for entering
different modes such as Configuration, Set Time, Set Schedule and Cleaning
Enters user-friendly program into the schedule
Temperature UP/Down used for modifying set point as well as to navigating the menus
Set Temperature
THERMOSTAT QUICK REFERENCE
13
14
15
16
16
15
14
13
12
11
10
9
8
76
54
3
2
1
Home Screen Description
Figure 2 – Home Screen Display
Programming and Conguration Items
Displays and "Keypad Lockout" when in keypad
lockout mode. Displays Lockout" when limited range is activated and locked. Displays only "Temperature Limit" when limited range is activated.
Indicates period of day being programmed.
RUN SCHEDULE (run program) button.
SET TIME button or HOLD temperature button.
Displays "Change Filter" when the system has run
for the programmed lter time period as a reminder to change or clean your lter.
COPY button or INSTALLER CONFIG button.
CLEAN DISPLAY button allows 30 seconds to wipe off
the display or ADVANCE DAY button for programming.
Used in programming to set time and in conguration
menu to change selections.
"Hold Until" indicates the time when a temporary hold
period will end.
"Hours" and "Days" displays during steps in installer
conguration.
The words "Hold At" are displayed when the thermo-
stat is in the HOLD mode. "Temporary Hold At" is displayed when the thermostat is in a temporary HOLD mode.
"Call For Service" indicates a fault in the heating/cool-
ing system. It does not indicate a fault in the thermostat.
4
and "Temperature Limit" and "Keypad
Figure 3 – Programming & Conguration Items
"System On" indicates when heating or cooling stage
is energized.
"Copy" indicates the copy program feature is being
used during programming.
A steady "Cool Savings" display indicates the feature
is enabled in the installer menu. A ashing "Cool Sav­ings" display indicates the feature is active.
"Remote" indicates that the indoor remote temperature
sensor, is being accessed. "Outdoor Remote" indi­cates the outdoor remote temperature sensor is being accessed.
INSTALLER/CONFIGURATION MENU
To enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Cong touch key. This displays menu item #1 in the table below. Press or
to change a menu item.
Installer Note: To default the programming, clock and Conguration Menu to the Factory Default Settings, press the
and SYSTEM keys simultaneously. The thermostat display will go blank for a few seconds, and then all segments will display momentarily. For heat pump systems, Conguration Menu item 1 must be set to match the heat pump system.
If rst item does not show SS1 or HP1, you have an earlier thermostat model and need Instruction Sheet 37-6814D.
Menu
Reference
Number
Program-
mable
1 1 1 SS1 HP1, SS1 Selects Single Stage or Heat Pump
2 2 2
3 3 3
4 4 NA
5 5 4
6 6 NA
7 7 5
8 8 6
9 9 7
10 10 8
11 11 9
12 12 10
13 13 11
14 14 12
15 15 13
16 16 14
17 17 15
18 18 16
19 19 17
20 20 18
21 21 19
22 22 20
23 23 21
24 24 22
25 25 23
26 26 24
Non-
Program-
mable
Press
Button
to advance to the next menu item or to return to a previous menu item. Press
CONFIGURATION MENU
Displayed
(Factory Default)
(ELE) GAS GAS setting: furnace controls blower
Days, (7) P 5+1+1 or 0 Programs per week. (0 = non-programmable)
PS (4) 2 Program periods per day
Cool-Off-
Heat-Auto
Cool-Off-Heat-
Emer-Auto
E (On) OFF Selects Energy Management Recovery, E (with programming option on)
Cr, Heat (FA) SL Selects Adjustable Anticipation, cycle rate, Heat
Cr, Cool (FA) SL Selects Adjustable Anticipation, cycle rate, Cool
Cr/AU, Emer (FA) SL Selects Adjustable Anticipation, cycle rate auxiliary, (This item is
CL (OFF) On Selects Compressor Lockout
dL (On) OFF Selects Continuous Display backlight & intensity
dL (LO) HI Selects Backlight Intensity
0 4, LO to 4, HI Selects Adjustable Ambient Temperature Display [range -4 (LO)
°F °C Selects °F/°C Display (temperature units in Fahrenheit or Celsius).
b (On) OFF Selects audible Beeper On/Off
dS (On) OFF Selects Daylight Saving Time calculation
AS, Heat (On) OFF Selects Automatic Schedule for comfort temperature Programming,
AS, Cool (On) OFF Selects Automatic Schedule for comfort temperature Programming,
CS, (OFF)
Cool Savings
HL, Heat (99) 62-98 TEMPERATURE LIMIT, HEAT (max. heat set point)
LL, Cool (45) 46-82 TEMPERATURE LIMIT, COOL (min. cool set point)
OFF,
Keypad Lockout
000 001-999 Selects Keypad Lockout Combination (active only if keypad Lockout
FS, Heat (On) OFF Fast second stage of heat (not available if SS1 is selected above)
Remote (OFF) On Remote temperature sensor, enable/disable
In, Remote Outdoor Remote Remote temperature sensor (Indoor/Outdoor)
LS (On) OFF Local temp. Sensor enable/disable (only when Indoor Remote is
dF (5) 5-50 Selects Dual Fuel Feature & set point (in Fahrenheit)
Cd (60) 0-99 Selects Compressor delay in seconds (only when dF is selected >5)
Change Filter
(OFF)
200 Hours 25-1975
Press
or to
select from listed
options Comments
(1 compressor)
ELE setting: thermostat controls blower
4 = Morning, Day, Evening, Night
Cool-Off-Heat,
Off-Heat, Cool-Off Cool-Off-Heat-Emer,
Off-Heat-Emer,
Cool-Off
1-2-3-4-5-6 Selects Cool Saving Feature & amount
L (total), P (partial), Temperature Limit
(limited temperature
range)
On Selects Change lter feature
(in increments
of 25 hours)
2 = Day, Night
System switch conguration in single stage
System switch conguration, heat pump mode
only to appear if HP1 is selected above)
to +4 (HI)]
heat mode
cool mode
Selects Keypad Lockout
is selected).
selected On).
(applicable only when HP1 is selected)
Change lter, duration hours
,
5
INSTALLER/CONFIGURATION MENU
1) This control can be congured for:
SS1 – Single Stage System HP1 – Heat Pump with one stage of compressor (2 heat/1 cool) (Dual Fuel see menu item 25)
2) GAS or Electric (ELE) fan operation. If the heating
system requires the thermostat to energize the fan, select ELE. Select GAS if the heating system energizes the fan on a call for heat. Note: Resetting the thermo-
stat switches the option to ELE.
3) Programs per week – This control can be congured for
7 independent day or 5+1+1 day programming or non-
programmable modes. Default is 7-day mode. The display indicates "7 Days" as default. Other options "5
Days" or "0 Days" can be selected by pressing touch
keys, mable mode, the step for EMR will be skipped, as this feature will not be available in this mode.
4) Program Steps per day – This control can be congured
for 4 or 2 program steps per day. Default is "4 PS" and can be toggled between 4 PS and 2 PS by pressing
the
5) System Switch Conguration (SS1/HP1) – This ther-
mostat is congured for Heat and Cool with Auto change­over default (Cool-Off-Heat-Auto). Can be congured as
Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or Cool Only (Cool-Off).
When the control is in heat pump conguration (HP1), the
system switch conguration will have an additional mode
available namely, Emer for Emergency Mode.
6) Energy Management Recovery (EMR) – (this step is
skipped if congured as non-programmable).
When set to "On" causes the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Example: Let us say, the heating program is 65°F at night and 70° at 7 AM. If the building temperature is 65°F, the difference is 5°F. Allowing 5 minutes per °F rise, the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per °F, because it takes longer to reach temperature. 7, 8 & 9) Cycle Rate Selection – The factory default setting is fast cycle (FA Cr) in all modes (Heat, Cool, Emer). To slow cycling (SL, Cr), press touch keys between FA & SL. The cycle rates are as below different selections: Mode Fast rate Slow rate Heat 0.6°F 1.2°F Cool 1.2°F 1.7°F Emer 1.2°F 1.7°F
10) Select Compressor Lockout (CL) – Selecting CL On
will cause the thermostat to wait 5 minutes between
cooling cycles. This is intended to help protect the compressor from short cycling. Some of the newer compressors have already got a time delay built in and
do not require this feature to be activated in the thermo-
stat. Your compressor manufacturer can tell you if this lockout feature is already present in their system. When the thermostat compressor time delay is activated, it will
ash the set point for up to ve minutes.
11) Select Continuous Backlight – In low lighting condi-
tions, display backlight improves the display contrast. When C terminal is connected, selecting dL On will turn
or . If "0 Days" is selected for non-program-
or touch keys.
or toggle
the backlight on continuously. Selecting dL Off will turn the backlight on momentarily after any key is pressed.
When C terminal is not powered (battery only), dL On
enables the momentary backlight whenever a key is pressed.
12) Select Backlight Intensity – This thermostat has the ability to provide two selectable intensities of the back­ light: HI and LO. Using toggle the selection between HI and LO.
13) Select Temperature Display Adjustment 4 LO to 4 HI This allows you to adjust the room temperature display by an amount in the range of -4°F to +4°F in 1° steps by using the accurately calibrated at the factory, however you have the option to change the display temperature value to match your previous thermostat, if you so prefer.
14) Select °F or °C Readout – Select the desired temper­ ature unit by pressing
15) Select Audio Prompting (Beeper) On or Off – Factory default setting is on (b, On). If you wish to turn off the beeper select OFF.
16) Select Daylight Saving Time Calculation – This feature will allow the thermostat to calculate the DST automati-
cally and apply it to the Real Time Clock display. Default On. Use 17 & 18)Select Automatic Schedule – This feature allows programming a “Comfort Temperature” into all program periods with the Auto Schedule key. When Heat AS (for Heat mode) or Cool AS (for Cool mode) is selected On, the Auto Schedule feature is ready to be set. Off in-
dicates that the feature is not ready to be used or a
“Comfort Temperature is already set. See Auto Schedule
in Programming section.
19) Select Cool Savings™: With Cool Savings™ enabled, the thermostat will make small adjustments to the setpoint temperature during periods of high demand to reduce AC system running time and save energy. When the cooling system has been running for more than 20 minutes, humidity in the home will be lower and a higher temperature will feel comfortable. After 20 minutes of run time, the thermostat will start increasing the setpoint
temperature in steps of less than one degree as the system continues to run. These adjustments will eventu-
ally cause the system to satisfy the thermostat to turn the system off and reduce the energy consumption. When the Cool Savings™ feature is active and making ad-
justments, the display will ash “Cool Savings”. The
amount of the adjustments to the setpoint temperature
is dependent on the Cool Savings™ value that is set, 1
being the least adjustment and 6 being the most adjust-
ment. With this feature set to OFF, no change will occur
when the AC system is continuously running during the
periods of high demand. Periods of high demand will nor-
mally occur during the late afternoon and early evening
on the hottest days of the summer. As demand lessens
the adjustments to setpoint temperature are reversed
until setpoint temperature returns to normal and “Cool
Savings” no longer ashes.
or touch keys. Your thermostat was
or touch keys to select the feature, OFF.
or touch keys you can
or . Factory default is °F.
6
INSTALLER/CONFIGURATION MENU
20) Heat Temperature Limit Range – This feature adjusts the highest setpoint temperature for heat. The default setting is 99°F. It can be changed between 62°F and 98°F by pressing the limit" icon will be displayed to the left of your setpoint temperature when using this feature. The "temperature
limit" icon will ash if an attempt is made to adjust the
temperature beyond the range selected.
21) Cool Temperature Limit Range – This feature adjusts the lowest setpoint temperature for cool. The default setting is 45°F. It can be changed between 46°F and 82°F by pressing the limit" icon will be displayed to the left of your setpoint temperature when using this feature. The "temperature
limit" icon will ash if an attempt is made to adjust the
temperature beyond the range selected.
22) Keypad Lockout – This step allows you to select the type of lockout or limited range security required. If no lockout or limited range security is required, press advance the menu. Three security settings are available in this menu item. Use the Lockout selections are: "Keypad Lockout and L" = Total Lockout. Total Lockout locks all keys. "Keypad Lockout and P" = Partial Lockout. Partial Lock­ out allows only the set temperature limits. "Temperature Limit/Keypad Lockout" prevents
changing the temperature limits in the Conguration
Menu. Keypad Lockout Combination Number Selection Display will read "OFF" "Keypad Lockout".
Skip this step and continue through the conguration
menu items 23 thru 26 if you require an Air Filter Change
out indicator or Humidier Pad Change out indicator by
pressing the Return to this point when you are ready to start your selected lock-out and continue by: Pressing Press Pressing combination number. Note: "000" is not a valid combination choice. Record the number you select for future use. Press select will start in 10 seconds. The system button will remain active for 10 seconds to allow setting Heat, Off, Cool or Auto.
or keys to select the lockout desired.
button to advance.
or keys to select ON.
. Display will read "000".
or keys to select your keypad lockout
to exit the menu. The security feature you
or key. The "temperature
or key. The "temperature
to
or keys to operate within your
23 Select Fast Second Stage ON or OFF – In the run mode, with the fast Heat feature enabled (FA Heat On), if the Heat setpoint temperature is manually raised by 3°F (2°C) or more above the actual temperature using second stage will energize immediately. With FA OFF,
second stage will not energize until the setpoint tempera-
ture is 1°F or more above actual temperature for more than ten minutes. The Fast Cool feature (FA Cool) pro-
vides the same controls when the setpoint temperature is
lowered.
24) Select Remote Temperature Sensor – This control
allows one wired remote temperature sensor (indoor,
F145-1328, or outdoor, F145-1378) be connected to it
and indicates the measured temperature in clock digits.
This menu enables you to select the remote sensor and
also congure it as indoor or outdoor temperature sensor.
Factory default is off. Select Remote On and Remote in
(for indoor) or Outdoor Remote. Local Temperature Sensor disable – This is applicable only when indoor remote temperature sensor is enabled. Factory default is On LS. You can make it Off LS if you desire by using indoor remote temperature reading will be used for control.
25) Select Dual Fuel Feature and Setpoint – This feature is applicable only in heat pump modes. An outside remote sensor must also be installed. When the outside tem­ perature falls below the selected setpoint temperature, dF, the thermostat will switch to gas heat and shut down the compressor. Use the desired setpoint temperature in the range of 5 to 50. Factory default is 5, which disables this feature. See Dual Fuel Temperature and Setpoint in Programming section. Select Compressor Delay – When dF is enabled, the shut down of the compressor(s) is delayed for a time period after the auxiliary stage is energized. This delay, Cd, is factory set at 60, but can be set in the range of 0 to 99.
26) Select Change Filter Run Time – The thermostat will display "Change Filter" after a set time of blower operation. This is a reminder to change or clean your air
lter. This time can be set from 25 to 1975 hours in 25
hour increments. A selection of OFF will cancel this feature. When "Change Filter" is displayed, you can clear it by pressing Clean Display. In a typical application, 200 hours of run time is approximately 30 days.
or touch keys. Then, only the
or keys to select the
the
7
OPERATING YOUR THERMOSTAT
IMPORTANT!
Choose the Fan Setting (Auto or On)
Fan Auto is the most commonly selected setting and runs the fan only when the heating or cooling system is on. Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning.
Choose the System Setting (Cool, Off, Heat, Emer, Auto)
Press the SYSTEM button to select:
Heat: Thermostat controls only the heating system. Off: Heating and Cooling systems are off. Cool: Thermostat controls only the cooling system. Auto: Auto Changeover is used in areas where both heating
and cooling may be required on the same day. AUTO allows the thermostat to automatically select heating or cooling depending on the indoor temperature and the selected heat and cool temperatures. When using AUTO, be sure to set the Cooling temperatures more than 1° Fahrenheit higher than the heating temperature. Emer: Setting is available only when the thermostat is cong- ured in HP1 mode.
Manual Operation for Non-Programmable Thermostats
Press the SYSTEM button to select Heat or Cool and use the
or buttons to adjust the temperature to your desired setting. After selecting your desired settings you can also press the SYSTEM button to select AUTO to allow the thermostat to automatically change between Heat and Cool.
Manual Operation (Bypassing the Program) Programmable Thermostats
Press or and the HOLD button and adjust the tempera­ture wherever you like. This will override the program. The HOLD feature bypasses the program and allows you to adjust the temperature manually, as needed. Whatever temperature you set in HOLD will be maintained 24 hours a day, until you manually change the temperature or press Run Schedule to cancel HOLD and resume the programmed schedule.
Program Override (Temporary Override)
Press or buttons to adjust the temperature. This will override the temperature setting for a (default) four hour over­ride period. The override period can be shortened by pressing
or lengthened by pressing . Program Override period can range from 15 minutes to 7 days. Example: If you turn up the heat during the morning program, it will be automatically lowered later, when the temporary hold period ends. To cancel the temporary setting at any time and return to the program, press Run Schedule. If the SYSTEM button is pressed to select AUTO the thermostat will change to Heat or Cool, whichever ran last. If it switches to heat but you want cool, or it changes to cool but you want heat, press both change to the other mode.
or buttons simultaneously to
PROGRAMMING
Set Current Time and Day
1) Press Menu key to enter installer menu. Then press Set Time once to indicate hour & A or P designation in clock display.
2) Press and hold either the reach the correct hour and A or P designation.
3) Press Set Time again to display minutes only in clock display.
4) Press and hold either the reach the correct minutes.
5) Press Set Time once again to display year.
6) Press and hold either the reach the correct year.
7) Press Set Time once again to display month.
8) Press and hold either the reach the correct month.
9) Press Set Time once again to display date of the month along with day of the week at top row (which is automatic).
10) Press and hold either the reach the correct day of the month and day of the week is automatically calculated and displayed at the top row.
11) Press Run Schedule once; now the display will show the correct time and room temperature.
or touch key until you
or touch keys until you
or touch key until you
or touch key until you
or touch key until you
Automatic Daylight Saving Calculation
The Real Time Clock will adjust automatically for daylight sav­ings time, in the following manner: Increment one hour at 2 AM on the second Sunday of March and decrement one hour at 2 AM on the rst Sunday of No­vember. (New DST effective 2007). The daylight saving feature can be enabled or disabled in
installer conguration mode. Default is dS ON (enabled). After entering installer conguration mode, momentarily
press actual temperature digits) and on (default – in clock digits).
OFF.
or touch key until the display indicates dS (in
and keys will toggle display and operation from on to
Programming Tip: Copy Button
You may copy any daily program to another day or group of days by pressing the Copy button. In 7 day programming mode when the Copy button is pressed, the other 6 days
of the week will ash. To copy the current program into the
remaining six days, simply press the Copy button again. To copy the current program to another day of the week, press Advance Day to select the day and press Copy to paste the program. In 5+1+1 day programming mode the copy function is similar. The weekday (Mon-Fri) program can be copied to
Sat and Sun (both ashing) or use Advance Day to choose
Sat or Sun and press the Copy button to paste the program.
8
PROGRAMMING
Fill in the blank schedule on the next page then:
Enter the Heating Program
1) Press the Menu button and then press Set Schedule. Press SYSTEM button to select either "Heat" or "Cool"
in the system switch area indicating the active mode being programmed. You can switch to the other mode by press­ing the system switch at any time.
2) The top of the display will show the day(s) being pro­grammed. The time and set at temperature are also
displayed. "Morning" will also be displayed to indicate the period.
3) Press
selected temperature for the 1st heating period (Morning).
4) Press
The time will change in 15 minute increments.
5) Press FAN to select Auto or Prog.
6) After you have set the time and the temperature for the period to begin, press Set Schedule to advance to the next program period.
7) Repeat steps 2 through 6 until all of the program times and temperatures are set for all program periods on that day.
8) Press "Advance Day" to change to the next day and repeat steps 2 through 8.
9) When programming is complete and all of the times and temperatures match your desired heating schedule, press
Run Schedule. The thermostat will now run your program.
or key to change the temperature to your
or key to adjust the start time for period.
Enter the Cooling Program
1) Press the SYSTEM button until the Cool icon appears.
2) Follow Enter Heating Program instructions for entering
cooling times and temperatures.
Automatic Schedule
This feature provides a method to program every day with
the most popular time and temperature prole using one key
press. For this feature to be available, the Auto schedule op­tions (AS Cool or AS Heat) should be set on in the installer
conguration.
Select the desired “Comfort Temperature” in the setpoint. When the Auto Schedule touch key is pressed, it will start
ashing indicating that it is now ready to insert the displayed
temperature setpoint as the “Comfort Temperature” for the selected system mode currently in (Heat/Cool). A second press of the Auto Schedule touch key will complete the process. A 6 the night step. Once it is done, the touch key display Auto
Schedule will disappear disabling any further operation of Auto Schedule touch key. If desired it can be enabled again
in the installer conguration menu.
o
F setback temperature will also be inserted for
Entering Fan Program
In the Set Schedule mode, the FAN key is used to select the fan operation during a program period. The default state of the Fan key is FAN Auto (fan runs during a call for cool but not on a call for heat). It can be changed to FAN Prog (fan runs during a program period). Each press of the FAN key will change the mode of the fan between Auto and Prog.
In the Run mode, when a program period that has FAN Prog begins, the fan will turn on and stay on during the com­plete period. The display will show FAN On Prog. Pressing the FAN key will change FAN On Prog to On (fan running continuously) or Auto. To return to FAN On Prog, press Run Schedule.
9
PROGRAMMING
Energy Saving Factory Pre-Program
The 1F97-1277 thermostats are programmed with the energy saving settings shown in the table below for all days of the week. If this program suits your needs, simply set the thermostat clock and press the RUN button. The table below shows the factory set heating and cooling schedule for all days of the week.
*Wake Up (Morning)
Heating
Program
Cooling
Program
* You can eliminate these two program periods in the conguration menu (reference #4) if the building is occupied all day.
Day will change to 6:00 am and can be programmed as required.
6:00 AM 70°F 8:00 AM 62°F 5:00 PM 70°F 10:00 PM 62°F
6:00 AM 78°F 8:00 AM 85°F 5:00 PM 78°F 10:00 PM 82°F
Leave For Work
(Day)
*Return Home
(Evening)
Go To Bed
(Night)
Planning Your Program – Important
The Heating and Cooling Program schedules below allow you to pencil in your own program times and temperatures.
The 1F97-1277 comes congured for 7 day programming and can also be congured for 5+1+1 programming (see conguration section).
Factory settings are listed on Monday, Saturday and Sunday. If you are re-programming a 5+1+1 day schedule, pencil in your own times and temperatures directly below the factory times and temperatures.
If you are re-programming a 7 day ll in all lines with the times and temperatures you want.
Keep the following guidelines in mind when planning your program.
• In Heating, lower temperatures will save energy.
• In Cooling, higher temperatures will save energy.
If you plan on using Auto Changeover, do not program the heating higher than the cooling.
Worksheet for Re-Programming 5+1+1 and 7 Day Program
Heating
Program
MON
Wake Up Leave For Work Return Home Go To Bed
(Morning) Fan (Day) Fan (Evening) Fan (Night) Fan
6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
TUE
WED
THU
FRI
SAT
SUN
Cooling
Program
MON
TUE
WED
THU
FRI
SAT
SUN
6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
Wake Up Leave For Work Return Home Go To Bed
(Morning) Fan (Day) Fan (Evening) Fan (Night) Fan
6:00 AM 78°F Auto 8:00 AM 85°F Auto 5:00 PM 78°F Auto 10:00 PM 82°F Auto
6:00 AM 78°F Auto 8:00 AM 85°F Auto 5:00 PM 78°F Auto 10:00 PM 82°F Auto
6:00 AM 78°F Auto 8:00 AM 85°F Auto 5:00 PM 78°F Auto 10:00 PM 82°F Auto
10
PROGRAMMING
Wired Remote Temperature Sensing
One remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a maximum cable length of 100 meters (300 ft). Three terminals, +, S & ­are provided on the terminal block to connect to the White­Rodgers standard wired remote sensor. This sensor will be read by the thermostat only when 24VAC is present. When used as indoor sensor, the readings can be weighted
with the local sensor for specic program periods. User can enable or disable the remote sensor in the installer congura-
tion mode and also the outdoor temperature can be selected to show on the display.
Once in the installer conguration mode, momentarily press
the
or touch key until display indicates Remote (at the top left of the LCD) and OFF (default – in clock digits). Pressing display from Remote OFF to Remote On. When Remote On is selected, press indicate Remote In (for indoor remote). The Remote In to Outdoor Remote. When any remote is selected the temperature will display in the clock digits for one second alternating with the current time for three seconds when in Run Schedule mode. Outdoor Remote will indicate at the top left of display for outdoor remote reading. Only Remote will show at top left for indoor remote reading.
o
(
F or oC will not indicate with remote temperature readings).
Sensing Range: Outdoor temperature range is -40 to 140 Indoor temperature range is 32
or touch key will toggle the operation and
key for the display to
or keys will toggle the operation and display from
o
o
F to 99 oF
F
Weight of Remote Reading:
When in view schedule mode the weight of the indoor remote sensor will be shown in the left actual temperature digits des­ignated as A2 (default for average weight), H4 (high weight) or L1 (low weight). The period (Morning, Day, Evening, Night) will also be shown to the right of the weight value in the actual temperature digits. When in view schedule mode, press the same time to sequence the indoor remote temperature sensor weight from A2 to H4 to L1 and back to A2 for each of the program period times for each day. (The H4 weight is twice the weight of A2 and A2 is twice the weight of L1).
When Remote In is selected (with Remote selected to On), press
key for the display to indicate the status of the local sensor LS On (default for thermostat local sensor operation­al). The
and keys will toggle the function and display from LS (shown in actual temperature digits) and On (shown in clock digits) to LS OFF to designate the local sensor is disabled.
The local sensor may be disabled only if the indoor remote sensor is enabled and functional. If the indoor remote sensor is disabled or not functional, the local sensor will automatically enable and display in the run schedule mode. The actual temperature displayed in the run mode is the mathematical weighted sum of the two temperature sensors – local and indoor remote. (Outdoor remote sensor is not used for this computation). If the remote sensor is absent or not enabled then the actual temperature will be as measured by the local sensor.
and keys at the
11
TROUBLESHOOTING
Reset Operation
Note: When thermostat is reset, installer conguration menu settings and programming will reset to factory settings.
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C (do not short them together) and removing batteries for 2 minutes. After resetting the thermostat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.
Symptom Possible Cause Corrective Action
No Heat/No Cool/No Fan (common problems)
No Heat 1. Pilot light not lit.
No Cool 1. Cooling system requires service or
Heat, Cool or Fan Runs Constantly
Thermostat Setting & Thermostat Thermometer Disagree
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing)
Forgot Keypad Lockout Code
First item in Conguration
Menu is not SS1 or HP1
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or panel loose or not properly installed.
4. Loose connection to thermostat or system.
2. Furnace Lock-Out Condition. Heat may also be intermittent.
3. Heating system requires service or thermostat requires replacement.
thermostat requires replacement.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan ON.
1. Thermostat thermometer setting requires adjustment.
1. The location of the thermostat and/or the size of the Heating System may be inuencing the cycle rate.
Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch. Tighten connections.
Re-light pilot. Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local HVAC service person for assistance. Diagnostic: Set SYSTEM Switch to HEAT and raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the ther­mostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a HVAC service person to verify the heating is operating correctly.
Same as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to
a ve minute delay before the thermostat clicks in
Cooling.
Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal block. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/ Cool system for correct operation. If the system operates correctly, replace the thermostat.
The thermometer can be adjusted +/- 4 degrees. See Temperature Display Adjustment in the Con-
guration Menu section.
Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like an increased cycle time, choose
SL for slow cycle in the Conguration menu, step 7
(heat) or 8 (cool). If an acceptable cycle rate is not achieved, contact a local HVAC service person for additional suggestions.
Press the menu button (button will disappear) and hold in for 20 seconds. This unlocks the thermostat.
Earlier model of thermostat refer to 37-6814D.
White-Rodgers is a business of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
www.white-rodgers.com
www.emersonclimate.com