Emerson 1098H-EGRs, 1098-EGR Instruction Manual

Instruction Manual Form 5084
October 2014
Types 1098-EGR and 1098H-EGR
Types 1098-EGR and 1098H-EGR Pressure Reducing Regulators
WARNING
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion,

causing property damage and personal injury or death.
Fisher® regulators must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. (Emerson™) instructions.
If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
Installation, operation and maintenance

personnel may result in improper adjustment and unsafe operation. Either condition may result in equipment

personnel when installing, operating and maintaining the Types 1098-EGR and 1098H-EGR pressure reducing regulator.
W6956
Figure 1. Type 1098-EGR
valve is also covered when a 61 Series pilot is used.
Instructions and parts lists for monitoring pilots and other equipment used with this regulator are found in
separate manuals.
Description
Introduction
Scope of the Manual
This manual describes and provides instructions and parts list for Type 1098-EGR or 1098H-EGR regulator complete with a standard P590 Series
 lter and either a 6350 Series regulator, a 61 Series pilot or a Type Y600AM pilot. The Type 1806 relief
www.fisherregulators.com
Types 1098-EGR and 1098H-EGR regulators provide economical and accurate pressure control in a wide variety of applications: natural gas distribution
systems; fuel gas supply to industrial boilers, furnaces,
ovens and mixers; and large commercial/industrial
establishments such as shopping centers and schools.
They are also used in plant air service and in liquid service where a slow stroking time (approximately 30 to 90 seconds) is desired on both opening and
closing the main valve.
D100339X012
Types 1098-EGR and 1098H-EGR

The Specications section lists pressure limitations and other specications for various Types 1098-EGR and 1098H-EGR constructions. Specications for a given regulator as it originally comes from the factory are stamped on nameplates located on both the actuator and main valve body, while the pilot control spring range is displayed on the pilot spring case and the pilot restriction code is stamped on the pilot body (S = standard gain, L = low gain and H = high gain).
Body Sizes and End Connection Styles
See Table 1
Main Valve Maximum Inlet Pressure
(1)
400 psig / 27.6 bar or body rating limit whichever is lower
Maximum Pilot Supply Pressure
(1)(2)
600 psig / 41.4 bar
Outlet Pressure Ranges
See Table 2
Main Valve Flow Direction
In through the seat ring and out through the cage
Pressure Registration
External
Temperature Capabilities
Nitrile (NBR):
-20 to 180°F / -29 to 82°C
Fluorocarbon (FKM):
0 to 300°F / -18 to 149°C,
Water is limited to 0 to 200°F / -18 to 93°C
Maximum and Minimum Differential Pressures
See Table 4
Actuator Sizes and Maximum Pressures
See Table 3
Main Valve Flow Characteristic
Linear (standard), Whisper Trim
or
Quick opening
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
2. For stability or overpressure protection, a reducing regulator may be installed upstream of the pilot according to the Installation section.
Ethylenepropylene (EPDM):
-20 to 275°F / -29 to 135°C
Options
• NACE Construction
• Boiler Fuel Construction
• Aqueous Service Construction
• Monitor Conguration
• Noise Abatement Trim
(1)
Table 1. Body Sizes and End Connection Styles
BODY SIZE
N PS DN
1 or 2 25 or 50 NPT, CL125 FF or CL250 RF NPT, CL150 RF, CL300 RF, CL600 RF, BWE, SWE or PN 16/25/40
3, 4 or 6 80, 100 or 150 CL125 FF or CL250 RF CL150 RF, CL300 RF, CL600 RF, BWE or PN 16/25/40
8 x 6 or 12 x 6 200 x 150 or 300 x 150 - - - - CL150 RF, CL300 RF, CL600 RF or BWE
2
CAST IRON STEEL OR STAINLESS STEEL
Types 1098-EGR and 1098H-EGR
Table 2. Outlet Pressure Ranges
PILOT TYPE
6351
6352
14 in. w.c. to 2 psig
6353
(1)
6354L
(2)
6354M
(2)
6354H
61L 61LD 61LE
7 in. w.c. to 2 psig
61H 10 to 65 0.69 to 4.5 Green Stripe 0Y066427022
61HP
7 to 16 in. w.c.
Y600AM
1. Without diaphragm limiter.
2. With diaphragm limiter.
15 in. w.c. to 1.2 psig
ACTUATOR TYPE ACTUATOR SIZE
1098
40 (standard)
1098H 30 350 24.1 400 27.6
OUTLET PRESSURE RANGE
psig bar
3 to 20 5 to 35
35 to 100
2 to 10 3 to 40
35 to 125
35 mbar to 0.1 bar
0.21 to 1.4
0.35 to 2.4
2.4 to 6.9
0.14 to 0.69
0.21 to 2.8
2.4 to 8.6
SPRING COLOR SPRING PART NUMBER
Green
Unpainted
Red
Yellow
Black
Yellow
Red
1B986027212 1B788327022
1K748527202
14A9672X012 14A9673X012
1E392527022 1K748527202
85 to 200 5.9 to 13.8 Blue 1L346127142
175 to 220 12.1 to 15.2 Blue 1L346127142
200 to 300 13.8 to 20.7 Green 15A9258X012
1 to 5 2 to 10 5 to 15
10 to 20
15 to 45
35 to 100
100 to 300
4 to 8 in. w.c.
1.2 to 2.5
2.5 to 4.5
4.5 to 7
17 mbar to 0.1 bar
0.07 to 0.3
0.14 to 0.69
0.35 to 1.0
0.69 to 1.4
1.0 to 3.1
2.4 to 6.9
6.9 to 20.7
10 to 20 mbar
17 to 4 mbar
37 mbar to 0.08 bar
0.08 to 0.17
0.17 to 0.31
0.31 to 0.48
Red
Yellow
Blue
Brown
Green
Yellow
Blue
Red Red
Unpainted
Yellow Green
Light Blue
Black
1B886327022
1J857827022
1B886427022
1J857927142
1B886527022
1E392527022 1D387227022
1D465127142 1B653827052 1B653927022 1B537027052 1B537127022 1B537227022 1B537327052
Table 3. Actuator Sizes and Maximum Pressures
OUTLET CONTROL PRESSURE EMERGENCY CASING PRESSURE
30
70
psig bar psig bar
100
75 50
6.9
5.2
3.4
115
82
65
7.9
5.6
4.5
Table 4. Maximum and Minimum Differential Pressures for Main Valve Selection
BODY SIZE
SPRING PART
NUMBER
SPRING
COLOR
MAXIMUM ALLOWABLE
DIFFERENTIAL PRESSURE
(1)
Size 30 Actuator Size 40 Actuator Size 70 Actuator
NPS DN psig bar psig bar psig bar psig bar
14A9687X012 Green 60 4.1 3.5 0.24 2.5 0.17 1 0.07
1 25
14A9680X012 Blue 125 8.6 5 0.34 3 0.21 1.5 0.10
14A9679X012 Red 400
(3)
27.6
(3)
7 0.48 5 0.34 2.5 0.17
14A6768X012 Yellow 20 1.4 - - - - - - - - - - - - - - - - 1 0.07
2 50
14A6626X012 Green 60 4.1 4 0.28 3 0.21 1.5 0.10
14A6627X012 Blue 125 8.6 6 0.41 5 0.34 2 0.14
14A6628X012 Red 400
(3)
27.6
(3)
11 0.76 10 0.69 3 0.21
14A6771X012 Yellow 20 1.4 - - - - - - - - - - - - - - - - 1 0.07
3 80
14A6629X012 Green 60 4.1 5 0.34 4 0.28 2 0.14
14A6630X012 Blue 125 8.6 8 0.55 6 0.41 2.5 0.17
14A6631X012 Red 400
(3)
27.6
(3)
14 0.97 11 0.76 4 0.28
14A6770X012 Yellow 20 1.4 - - - - - - - - - - - - - - - - 1.3 0.09
4 100
14A6632X012 Green 60 4.1 10 0.69 5 0.34 2.5 0.17
14A6633X012 Blue 125 8.6 13 0.90 8 0.55 3 0.21
14A6634X012 Red 400
(3)
27.6
(3)
22 1.5 13 0.90 5 0.34
15A2253X012 Yellow 20 1.4 - - - - - - - - - - - - - - - - 2.2 0.15
6, 8 x 6
or 12 x 6
1. Maximum inlet pressure is equal to set pressure plus maximum differential.
2. Requires special 6300 Series pilot construction without integral relief valve and with external Type 1806 40 psid / 2.8 bar d relief valve.
3. Should not exceed the body rating limit. Use this pressure value or the body rating limit, whichever is lower.
150, 200 x 150
or 300 x 150
14A9686X012 Green 60 4.1 13 0.90 9.5 0.66 4 0.28
14A9685X012 Blue 125 8.6 19 1.3 14 0.97 6 0.41
15A2615X012 Red 400
(3)
27.6
(3)
(2)
28
MINIMUM DIFFERENTIAL PRESSURE
REQUIRED FOR FULL STROKE
(2)
1.9
19 1.3 8 0.55
3
Types 1098-EGR and 1098H-EGR
Table 5. Supply Pressure Settings Required for the Type 95H Regulator
SUPPLY PRESSURE
BODY SIZE
NPS DN psig bar psig bar psig bar psig bar psig bar psig bar
1 25
2 50
3 80
4 100
6 or 8 x 6
1. The pressures shown in the table are the minimum supply pressures required by the pilot. If the inlet pressure is less than shown, an external pilot supply is necessary.
150 or
200 x 150
TYPE EGR
SPRING COLOR
Green
Blue
Red
Green
Blue
Red
Green
Blue
Red
Green
Blue
Red
Green
Blue
Red
Red Unpainted Yellow Green Light Blue Black
6
0.41
7
0.48
8
0.55
6
0.41
8
0.55
13
0.90
7
0.48
9
0.62
14
0.97
8
0.55
11
0.76
16
1.1
13
0.90
17
1.2
22
1.5
6
0.41
7
0.48
8
0.55
6
0.41
8
0.55
13
0.90
7
0.48
9
0.62
14
0.97
8
0.55
11
0.76
16
1.1
13
0.90
17
1.2
22
1.5
Type Y600AM Spring Color
7
0.48
8
0.55
9
0.62
7
0.48
9
0.62
14
0.97
8
0.55
10
0.69
15
1.0
9
0.62
12
0.83
17
1.2
14
0.97
18
1.2
23
1.6
8 10 11
9 11
16
10 12 17
11 14 19
15 20 25
0.55
0.69
0.76
0.62
0.76
1.1
0.69
0.83
1.2
0.76
0.97
1.3
1.0
1.4
1.7
11
0.76
13
0.90
14
0.97
12
0.83
14
0.97
19
1.3
13
0.90
15
1.0
20
1.4
14
0.97
17
1.2
22
1.5
18
1.2
23
1.6
28
1.9
13
0.90
14
0.97
15
1.0
13
0.90
15
1.0
20
1.4
14
0.97
16
1.1
21
1.5
15
1.0
18
1.2
23
1.6
20
1.4
24
1.7
29
2.0
Principle of Operation
The pilot-operated Types 1098-EGR and 1098H-EGR regulators both use inlet pressure as the operating
medium, which is reduced through pilot operation to load the actuator diaphragm. Outlet or downstream pressure
opposes loading pressure in the actuator and also
opposes the pilot control spring. The Type 1098-EGR regulator operation schematic is shown in Figure 2.
In operation, assume that outlet pressure is below the pilot control setting. Control spring force on the
pilot diaphragm opens the pilot valve plug providing
additional loading pressure to the actuator diaphragm.
This loading pressure forces the actuator stem
forward, opening the main valve plug via a bump connection. The upward motion of the plug allows gas to ow through the cage into the downstream system.
When downstream demand has been satised, outlet pressure tends to increase, acting on the pilot and actuator diaphragms. This pressure exceeds the pilot control spring setting, moving the pilot diaphragm away and letting the valve plug spring (Type 6351, 61 Series or Type Y600AM pilots) or bellows (Types 6352 through 6354M pilots) close the pilot valve plug (unbalanced in the Type 6351 or 61 Series pilots but balanced in the Types 6352 through 6354M pilots). Excess loading pressure on the
actuator diaphragm escapes downstream through the
bleed hole (Type 6351 pilot), bleed orice (61 Series pilot), restriction (Types 6352 through 6354M pilots) or xed restrictor (Type Y600AM pilot).
Reduced actuator loading pressure permits the main
valve to close. The combination of main valve spring
force and valve plug imbalance provides positive valve
plug shutoff against the port and upper seals.
To protect the Type 1098 or 1098H actuator diaphragm
from excessive differential pressure, the 6300 Series
pilots have a relief valve that allows loading pressure
to bleed downstream at approximately 25 psig / 1.7 bar differential across the actuator diaphragm. An external relief valve (Type 1806) is required when differential is higher than 25 psi / 1.7 bar or when using the 61 Series or Y600AM pilots.

A mounting assembly for a 40 psi / 2.8 bar differential relief valve is available for the Type 1098-EGR. The standard 25 psi / 1.7 bar differential relief valve
construction is integrally mounted between the loading
and downstream pressures in the 6351 through 6354 Series regulating pilots. Both differential relief
valves protect the main regulator diaphragm from damage that may occur from too high differential
between the loading pressure and downstream pressure.
The 40 psi / 2.8 bar differential relief valve construction is designed specically for the red main valve spring selection in the NPS 6 / DN 150 Type 1098-EGR-6354 with the size 30 actuator. This construction uses the Type 1806H relief valve (with a setting of 40 psi / 2.8 bar)
to relieve excess loading pressure and does not interfere
with the normal operation of the regulator.
4
TYPE 6351
TYPE 6352, 6353 OR 6354
Types 1098-EGR and 1098H-EGR
TYPE 1098-EGR
A6563
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE LOADING PRESSURE
TYPE 1098-EGR WITH 6350 SERIES PILOT
TYPE 1098-EGR
TYPE 1806
A6641
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE LOADING PRESSURE
TYPE 61LD
TYPE 1098-EGR WITH TYPE 61LD PILOT AND TYPE 1806 RELIEF VALVE
Figure 2. Operational Schematics
5
Types 1098-EGR and 1098H-EGR
TYPE 95H
TYPE 1098-EGR
OPTIONAL:
TYPE 112 RESTRICTOR
TYPE Y600AM
M1008
TYPE 1098-EGR WITH TYPE Y600AM PILOT AND TYPE 95H PRESSURE SUPPLY REGULATOR
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE LOADING PRESSURE PILOT SUPPLY PRESSURE
Installation and Startup
WARNING
Personal injury, equipment damage or leakage due to escaping accumulated gas or bursting of pressure-containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given

appropriate nameplate or where conditions exceed any ratings of the adjacent piping or piping connections. To avoid such injury or damage, provide pressure­relieving or pressure-limiting devices to prevent service conditions from exceeding those limits.
FIXED RESTRICTOR
Figure 2. Operational Schematics (continued)
Additionally, physical damage to the regulator may result in personal injury and property damage due to escaping accumulated gas. To avoid such injury and damage, install the regulator in a safe location.
Standard Single-Pilot Regulator (Figure 3)
Installations
A Type 1098-EGR or Type 1098H-EGR regulator bleeds no gas to the atmosphere, making it suitable for
installation in pits or other enclosed locations without
elaborate venting systems. This regulator can also be installed in pits subject to ooding by venting the pilot spring case above the expected ood level so that the pilot diaphragm is exposed to atmospheric pressure.
6
Types 1098-EGR and 1098H-EGR
48A6566-A B1622
4 MAIN PIPE
DIAMETERS
 PIPE
PILOT SUPPLY LINE
FILTER
VENT
10 MAIN PIPE DIAMETERS
TYPE 1098-EGR OR 1098H-EGR REGULATOR WITH STANDARD 6350 SERIES PILOT
Figure 3. Standard Single-Pilot Installation
CONTROL LINE
TO PILOT LIGHT (IF USED FOR BOILER FUEL INSTALLATION)
n 13 mm PIPE
 I 13 mm PIPE
FILTER
TYPE Y600AM AUXILIARY PILOT
48A6566-A B1622
4 MAIN PIPE DIAMETERS
VENT
PILOT SUPPLY LINE
VENT
10 MAIN PIPE DIAMETERS
CONTROL LINE
TYPE 1098-EGR SIZE 70 REGULATOR WITH QUICK OPENING CAGE AND STANDARD TYPE 6352 WORKING PILOT
Figure 4. Typical Dual-Pilot Boiler Fuel Installation
TO PILOT LIGHT
n. 13 mm PIPE
7
Types 1098-EGR and 1098H-EGR
Note
Normal pressure drop assists shutoff. Therefore, leakage may result during any reverse pressure drop condition.
1. Use qualied personnel when installing, operating and maintaining regulators. Before installing, inspect the main valve, pilot and tubing for any
shipment damage or foreign material that may
have collected during crating and shipment. Make
certain the body interior is clean and the pipelines
are free of foreign material. Apply pipe compound
only to the external pipe threads with a screwed body or use suitable line gaskets and good bolting
practices with a anged body.
With a weld end body, be sure to remove the trim
package, including the gasket, according to the
Maintenance section before welding the body into
the line. Do not install the trim package until any post-weld heat treatment is completed. If heat treating, prevent scale buildup on all machined
guiding and sealing surfaces inside the body and
at the bonnet ange / body joint.
Note
 
the valve body.
2. Install a three-valve bypass around the regulator
if continuous operation is necessary during
maintenance or inspection. The pilot may be eld-
changed to the opposite-side mounting position by swapping the pilot pipe nipple to the opposite
bonnet tapping.
3. To keep the pilot spring case vent from being plugged or the spring case from collecting moisture, corrosive chemicals or other foreign material, point the vent down or otherwise protect it. To remotely vent the standard pilot, remove the vent and install obstruction-free tubing or piping into the 1/4 NPT vent tapping. Provide protection on a remote vent by
installing a screened vent cap into the remote end of
the vent pipe.
4. Run a 3/8 in. / 9.5 mm outer diameter or larger
pilot supply line from the upstream pipeline to
the lter inlet as shown in Figure 3. Do not make
the upstream pipeline connection in a turbulent
area, such as near a nipple, swage or elbow. If
the maximum pilot inlet pressure could exceed the
pilot rating, install a separate reducing regulator in the pilot supply line. Install a hand valve in the
pilot supply line and provide vent valves to properly
isolate and relieve the pressure from the regulator.
5. Attach a 1/2 NPT downstream pressure control
line downstream of the regulator in a straight run
of pipe, as shown in Figure 3. Do not make the tap near any elbow, swage or nipple that might cause turbulence. Connect the other end of the control line to the bonnet connection. Install a hand valve
in the control line to shut off the control pressure
when the bypass is in use.
6. If a quick acting solenoid is to be installed downstream of the regulator, the regulator
and solenoid should be located as far apart as
practical. This maximizes the gas piping volume
between the regulator and solenoid and improves the regulator response to quick-changing
ow rates.
WARNING
A regulator may vent some gas to the atmosphere. In hazardous or

accumulate and cause personal injury,

explosion. Vent a regulator in hazardous gas service to a remote, safe location away from air intakes or any hazardous location. The vent line or stack opening must be protected against condensation or clogging.
8
7. Consult the appropriate instruction manual for installation of an optional Type 662 pneumatic or electric remote control drive unit. For optional remote pneumatic loading of a 6350 or 61 Series pilot, make the loading piping connections to the 1/4 NPT vent connection.
Pre-startup Considerations
Before beginning the startup procedures in this section,
make sure the following conditions are in effect:
• Block valves isolate the regulator.
• Vent valves are closed.
• Hand valves are closed.
Types 1098-EGR and 1098H-EGR
CAUTION
Introduce pilot supply pressure into the regulator before introducing any downstream pressure or internal damage may occur due to reverse pressurization of the pilot and main valve components.
Always use pressure gauges to monitor downstream pressure during startup. Procedures used in putting
this regulator into operation must be planned accordingly if the downstream system is pressurized
by another regulator or by a manual bypass.
Note
For proper operation, pilot supply pressure must exceed control pressure

the actuator nameplate as minimum differential pressure.
The only adjustment necessary on a Type 1098-EGR or 1098H-EGR regulator is the pressure setting of
the pilot control spring. Turning the adjusting screw
clockwise into the spring case increases the spring
compression and pressure setting. Turning the
adjusting screw counterclockwise decreases the spring
compression and pressure setting.
Pilot Adjustment
To adjust standard 6350 Series pilots: Loosen the
locknut and turn the adjusting screw. Then tighten the locknut to maintain the adjustment position. On a standard Types 6352 through 6354M pilots, closing
cap must be removed before adjustment and
replaced afterward.
WARNING
To avoid possible personal injury from a pressure-loaded pilot, carefully vent the spring case before removing the closing cap. Otherwise, trapped loading pressure could forcefully eject the freed closing cap.
To adjust the 61 Series or Type Y600AM pilots:
Remove the closing cap and turn the adjusting screw. Any adjustments made should set the controlled
pressure within the appropriate spring range shown
in the Table 2.
Startup
1. Slowly open the pilot supply line hand valve.
2. Slowly open the upstream block valve and partially
open the downstream block valve for minimum
ow. Slowly open the hand valve in the control line.
3. Adjust the pilot setting, if necessary.
4. Completely open the downstream block valve.
5. Slowly close the bypass valve, if any.
Dual-Pilot Boiler Fuel Control
Applications
Boiler Fuel Pressure Control
To enhance proper operation and adequate response to negative pressure shock condition in low differential
pressure boiler fuel control applications, use the Type 1098-EGR boiler fuel conguration:
• Type 1098-EGR with Type 6352 pilot
• Size 70 Actuator
• Quick Opening Cage
• Yellow Main Spring
• Type Y600AM or 627M Auxiliary Pilot
mounted in parallel with the Type 6352 pilot
To provide faster response, two pilots mounted in parallel sense the downstream pressure. The Type 6352 pilot is the primary controlling pilot and the Type Y600AM or 627M auxiliary pilot stands by until it senses a negative pressure shock condition. The auxiliary pilot opens, allowing additional ow into the actuator, increasing the stroking speed and providing faster response. See Figure 5 for schematic. The quick-opening cage allows maximum
capacity at shorter travels to decrease stroking time
in opening and closing directions. The service conditions should not exceed 20 psig / 1.4 bar maximum inlet pressure and 10 psi / 0.69 bar maximum differential pressure.
Supply the boiler pilot light gas with the Type 1098-EGR.
The pilot light gas supply line should branch off the main fuel line downstream of the Type 1098-EGR and
include a separate regulator to control the nal pilot light gas pressure, if required (see Figure 6). This
allows the Type 1098-EGR to have its main valve plug just off the seat waiting for the sudden negative shock created when the boiler solenoid valve is opened to
light the boiler to the high re load. This installation practice signicantly increases the stroking speed of the Type 1098-EGR. See Figure 6 for schematic.
9
Types 1098-EGR and 1098H-EGR
TYPE 1098-EGR SIZE 70
WITH QUICK OPENING CAGE
20 psibar MAXIMUM
GAS
SUPPLY
SAFTEY SHUT-OFF VALVE
TO BOILER
TYPE 6352
WORKING PILOT
TYPE Y600AM
AUXILIARY PILOT
E0711
Figure 5. Boiler Fuel Conguration
Note
Modulating solenoid load valves provide

one position to the other, effectively preventing sudden pressure changes in the system. Alternately, a snap-acting solenoid valve can be furnished with a characterized valve plug that, by allowing maximum capacity to be reached at a greater proportion of total travel, slows the action slightly. This action does not control shock as effectively as modulating solenoid valves.
Installation
1. Perform the Standard Single-Pilot Regulator Installation section through step 3, making sure
that the regulator is installed with the actuator
below the main valve as shown in Figure 4.
2. Run a 1/2 in. / 13 mm or larger pilot supply line from the upstream pipeline to the 1/2 NPT supply connection in the pipe tee as shown in Figure 4. Do not make the connection in a turbulent area, such as near a nipple, swage or elbow. If the maximum pilot
TYPE 1098-EGR
PILOT
GAS
SUPPLY
PILOT GAS
REGULATOR
E0710
Figure 6. Boiler Fuel Conguration Installation Guide
FAST-ACTING
LOAD VALVE
TO PILOT LIGHT
inlet pressure could exceed the pilot rating, install a
separate regulator in the pilot supply line and provide vent valves so that pressure can be properly isolated
and relieved from the regulator.
3. Attach a 1/2 NPT downstream pressure control line
ten pipe diameters downstream of the regulator in
a straight run of pipe. Do not make the tap near any elbow, swage or nipple, which might cause turbulence. Connect the other end of the control line to the 1/4 NPT connection in the control pipe tee as shown in Figure 4. Install a hand valve in the
control line to shut off the control pressure when
the bypass is in use. Also use the hand valve to dampen out pulsations, which may cause instability or cycling of the regulator.
4. Consult the appropriate instruction manual for
installation of an optional pneumatic or electric
remote control drive unit. For optional remote pneumatic loading of 6350 or 61 Series pilots,
make the loading piping connections to the
1/4 NPT vent connection.
10
Types 1098-EGR and 1098H-EGR
Type 1098-EGR
1098-EGR Working Monitor
6350 SERIES PILOT
6350 SERIES PILOT
March 2007
Type 1098-EGR
TYPE Y600M OR 627-109 MONITORING PILOT
6350 SERIES PILOT
A6788
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
LOADING PRESSURE
INTERMEDIATE PRESSURE
Startup
TYPE Y600M OR 627-109 MONITORING PILOT
Figure 7. Typical Working Monitor Installation
2. Connect another downstream pressure control line
1. Slowly open the pilot supply line hand valve.
2. Slowly open the upstream block valve and partially open the downstream block valve for minimum ow.
3. Slowly open the hand valve in the control line and
make sure that the standby pilot is set far enough below the working pilot so that the standby pilot
remains closed during normal operation. For example, with nal desired settings of 11 in. w.c. /
For two typical monitoring pilots, Table 7 gives
27 mbar for the working pilot and 10 in. w.c. / 25 mbar for the standby pilot, begin by reducing
the working pilot setting far enough below
10 in. w.c. / 25 mbar for the working pilot to shut off. Then set the standby pilot for an outlet pressure of 10 in. w.c. / 25 mbar. Finally, set the working pilot for an outlet pressure of 11 in. w.c. / 27 mbar. Table 6 shows how close the standby pilot can be set to the working pilot setting.
4. Completely open the downstream block valve.
Startup
On a working monitor installation (Figure 7), be sure that
the second-stage working regulator is set to operate at a pressure lower than the Type 1098-EGR or 1098H-EGR
working monitor regulator. To do this, increase the setting
5. Slowly close the bypass valve, if any.
Working Monitor (Figure 7)
Installation
of the monitoring pilot until the working pilot is in control of the intermediate pressure and the second-stage working
regulator is in control of the downstream pressure. If this is not done, the monitoring pilot tries to take control of the downstream pressure.
6350 SERIES PILOT
and hand valve (Figure 7) to the monitoring pilot
according to the monitoring pilot instruction manual. Attach a 1/2 NPT pressure control line and hand
valve from the intermediate pressure pipeline to the
working monitor regulator. Pipe supply pressure
between the monitoring pilot and the working monitor regulator according to the monitoring
pilot manual.
the spread between normal distribution pressure and the minimum pressure at which the working monitor regulator can be set to take over if the
working regulator fails to open.
1. For both working monitor regulator and working regulator, perform the Standard Single-Pilot Regulator Installation section through step 6.
1. Slowly open the upstream block valve and the hand valves in both pilot supply lines. This
energizes both pilots so that their setpoints can
be adjusted. Partially open the downstream block valve for minimum ow.
11
Types 1098-EGR and 1098H-EGR
Table 6. Auxiliary Pilot Selection (Fast Stroke Dual Pilot)
SIZE CONSTRUCTION
Type Y600AM 1/4 6.4
3/4
NPT
Type 627M 1/2 13 5 to 10 0.34 to 0.69 10B3076X012 Yellow
Construction
Type 161AYW pilot and 150 psig /
10.3 bar maximum allowable
pilot inlet pressure
Type 627-109 pilot and 150 psig /
10.3 bar maximum allowable pilot
inlet pressure for cast iron body
or 750 psig / 51.7 bar maximum
allowable pilot inlet pressure for
malleable iron or steel body
ORIFICE SPRING RANGE
In. mm psi bar
4 to 8 in. w.c. 10 to 20 mbar 1B653827052 Red
7 to 16 in. w.c. 17 to 40 mbar 1B653927022 Unpainted
15 in. w.c. to 1.2 psi 37 mbar to 0.08 bar 1B537027052 Yellow
1.2 to 2.5 0.08 to 0.17 1B537127022 Green
2.5 to 4.5 0.17 to 0.31 1B537227022 Light Blue
4.5 to 7 0.31 to 0.48 1B537327052 Black
Table 7. Working Monitor Performance
MONITORING PILOT INFORMATION
Spring Range
psig bar
3 to 12 in. w.c.
11 to 25 in. w.c.
25 in. w.c. to 2.5 psi
2.5 to 4.5 psi
4.5 to 7 psi
5 to 20 15 to 40 35 to 80
70 to 150
130 to 200
7 to 30 mbar
27 to 62 mbar
62 mbar to 0.17 bar
0.17 to 0.31
0.31 to 0.4
0.34 to 1.4
1.0 to 2.8
2.4 to 5.5
4.8 to 10.3
9.0 to 13.8
SPRING
NUMBER
Spring Part Number
1B653927022 1B537027052
1B537127022 1B537227022 1B537327052
10B3076X012 10B3077X012 10B3078X012
10B3079X012
SPRING
COLOR
MINIMUM PRESSURE AT WHICH
WORKING MONITOR REGULATOR
3 in. w.c. / 7 mbar over
normal distribution pressure
14 in. w.c. / 34 mbar over
normal distribution pressure
normal distribution pressure
5.0 psig / 0.34 bar over
normal distribution pressure
MINIMUM PRESSURE AT WHICH AUXILIARY
PILOT CAN BE SET
1 in. w.c. / 2 mbar
Under working
pilot setpoint
6 in. w.c. / 14 mbar
Under working
pilot setpoint
8 in. w.c. / 21 mbar
Under working
pilot setpoint
CAN BE SET
3.0 psig / 0.21 bar over
2. To enable intermediate pressure adjustment with the working monitor regulator, slowly open the hand valve in the intermediate pressure control line.
3. To enable downstream pressure adjustment with the second-stage working regulator, slowly open the hand valve in the control line to this regulator.
4. Adjust the setting of the monitoring pilot to
establish the desired emergency downstream
pressure, which is to be maintained in the event
of open failure of the second-stage working
regulator. The emergency downstream pressure
should exceed the desired downstream pressure
by at least the amount listed in Table 7. The steps
followed to set the monitoring pilot may vary with
each piping situation; however, the basic method remains the same. The following sub steps a
and b may be used as examples for setting the monitoring pilot:
a. Increase the outlet pressure setting of the second-
stage working regulator until the monitoring pilot
takes control of the downstream pressure. Adjust
the monitoring pilot setting until the desired
emergency downstream pressure is achieved. Then, readjust the second-stage working regulator to establish the desired downstream pressure.
b. Install special piping (not shown in Figure 7) so
that the monitoring pilot senses the intermediate
pressure. The intermediate pressure then appears
to the monitoring pilot as if it was increased downstream pressure and the monitoring pilot
controls and reduces the intermediate pressure. Adjust the monitoring pilot setting until the desired
emergency downstream pressure is achieved
at the intermediate pressure stage. Then slowly
close the special piping and open up the monitoring downstream control line for
normal service.
5. Slowly open the downstream block valve.
6. Slowly close the bypass valve, if any.
12
Type 1098-EGR
Type 1098-EGR Upstream or Downstream “Wide-Open” Monitor
6350 SERIES PILOT
PILOT SUPPLY REGULATOR
6350 SERIES PILOT
July 2011
Type 1098-EGR
A6789
INLET PRESSURE
OUTLET PRESSURE
LOADING PRESSURE
MONITOR LOADING PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
PILOT SUPPLY REGULATOR
6350 SERIES PILOT
Figure 8. Typical Wide-Open Monitor Installations
Types 1098-EGR and 1098H-EGR
6350 SERIES PILOT
NOTICE
Adjustment Recommendations for Monitor Applications
Low amplitude/high frequency monitor trim oscillations can occur if the monitor regulator pressure setting is adjusted too closely to the working regulator pressure setting and/or if the monitor pilot supply regulator pressure setting is adjusted too closely to the monitor
regulator pressure setting. The monitor pressure
setting should be adjusted so it is at minimum two times the pilot proportional band pressure above the
working regulator pressure setting. The monitor pilot
supply pressure setting should be adjusted so it is at
minimum 5 psig / 0.34 bar plus the monitor minimum
differential pressure above the working regulator
pressure setting. These adjustments must be made such that other governing pressure limits, such as casing ratings, pilot maximum differential pressures or regulatory limits, are not exceeded.
Wide-Open Monitor (Figure 8)
Either the upstream or downstream regulator can be
the monitor regulator. During normal operation, the
monitoring regulator is standing wide open with the reduction to distribution pressure being taken across
the working regulator. Only in case of open failure of
the working regulator does the wide open monitoring
regulator take control at its slightly higher setting.
Regardless of which regulator is used as the monitor,
it should be equipped with a pilot supply regulator set
to limit the pilot supply pressure to 10 to 15 psig / 0.69 to 1.0 bar above control pressure. Since the pilot on
the monitoring regulator is wide open during normal
operation, the pilot supply regulator prevents differential relief valve chatter on the monitoring regulator pilot.
Installation
1. For both the wide-open monitoring regulator and the working regulator, perform the Standard Single­Pilot Regulator Installation section through step 6.
2. Connect the control line of the wide-open
monitoring regulator (Figure 8) to downstream piping near the working regulator control line
connection. During normal operation the wide-
open monitoring regulator stands wide-open with the pressure reduction being taken across
the working regulator. Only in case of working
regulator failure does the wide-open monitoring
regulator take control at its slightly higher setting.
Startup
Repeat this procedure in turn for each regulator in
the installation.
1. Slowly open the pilot supply line hand valve.
2. Slowly open the upstream block valve and
partially open the downstream block valve for
minimum ow.
13
Types 1098-EGR and 1098H-EGR
BODY FLANGE
SEAT RING SCREWS INTO CAGE
P1507
Figure 9. Trim Package Removal
CAGE SCREWS INTO BODY FLANGE
3. Slowly open the hand valve in the control line and adjust the pilot setting if necessary. Set the
monitoring regulator at a slightly higher control
pressure than the working regulator.
4. Completely open the downstream block valve.
5. Slowly close the bypass valve, if any.
Shutdown
Installation arrangements vary, but in any installation it
is important that the valves be opened or closed slowly and that the outlet pressure be vented before venting inlet pressure to prevent damage caused by reverse
pressurization of the pilot or main valve. The following steps apply to the typical installation as indicated.
P1508
Figure 10. Seat Ring / Cage Removal or Installation
Using Body as Holding Fixture
4. Slowly open the upstream pipeline vent valve. Allow all pressure to bleed out of both the piping and the pilot.
Working Monitor
1. Slowly close the downstream block valve and the hand valve in the downstream pressure control line.
2. Slowly close the upstream block valve and the hand valves in both pilot supply lines.
3. Slowly open all vent valves and permit all pressures to bleed out of the piping and regulators.
Maintenance
Single-Pilot, Dual-Pilot Regulator or Wide-Open Monitor
As well as applying to a single-pilot regulator (Figure 3),
the steps in this procedure are also valid for a dual­pilot regulator (Figure 4) or a wide-open monitoring installation (Figure 8) and just need to be repeated for
each regulator in such an installation.
1. Slowly close the downstream block valve. If the control line is downstream of the block valve, also close the hand valve in the control line.
2. Slowly close the upstream block valve and the hand valve in the pilot supply line.
3. Slowly open the vent valve in the downstream pipeline. If the control line is downstream of the block valve, also open the vent valve in the control line. Permit all pressure to bleed out.
14
Regulator parts are subject to normal wear and must be
inspected and replaced as necessary. The frequency
of inspection and replacement of parts depends upon the severity of service conditions or the requirements
of local, state and federal regulations. Due to the
care Emerson™ takes in meeting all manufacturing
requirements (heat treating, dimensional tolerances, etc.), use only replacement parts manufactured or furnished by Emerson.
The stem O-rings (key 6, Figure 14) on the Type 1098
or 1098H actuator can be lubricated during regularly
scheduled maintenance, using the grease  tting (key 28, Figure 14). Stem O-rings can be checked
for damage during normal operation by line pressure leakage or unexpected grease extrusion from the
actuator vent (key 27, Figure 14). All O-rings, gaskets
and seals should be lubricated with a good grade of general-purpose grease and installed gently rather
than forced into position. Be certain that the nameplates
Loading...
+ 30 hidden pages